CA6BWPQ7
CA6BWPQ7
CA6BWPQ7
Test and Maintenance of System Faults....... 119 Fault Test Steps of Sound System ............... 200
2
6. Keep the flammable articles away from the Illustration A-X1 The insert and draw methods of
welding site, protect every cable, and do not the linker X1 on ZF control unit EST-117
let the splashing spark and solders produced
by welding spatter down on them to avoid
loss and injury caused by fire.
7. Do welding operation according to the normal
safety operation procedures of welding.
34B0359 start switch III--- the third position when turning the start
switch key clockwise. Use to start the diesel
engine, this position can not hold automatically,
Illustration 1-1 Start switch and its principle the start switch key will return to I position after
illustration released.
If the engine is failed to be started after three Sometimes it is hard to start the engine which
times attempt, turn off the start switch and start it mostly happens outdoor in cold winter. The
again after 30 minutes. Check the battery and temperature may be lower than -18 ℃ . If it is
starting circuit if it is necessary to find out possible, start the engine indoors or start it in
whether any trouble affects the starting. auxiliary way.
About the start switch terminals.
Six terminals are provided for the start switch,
namely, "30" ; "58" ; "15" ; "17" ; "19" ;
"50", see the following picture:
Illustration 1-2 start switch positions
Terminals that used in this machine: Procedures for Checking Start Switch
Trouble
30- for power supply
58-for P position. When start switch is at P 1. Remove all the connectors that connect to
position, terminal 30 is connected with terminal the start switch terminals to disconnect the
58. start switch from the whole circuit.
15- for turning on the power supply for whole 2. Turn the digital multimeter to Ω position for
machine. When the start switch at I position and 200 Ω .
III position, terminal 30 is connected with
terminal 15.
17-for engine starting. When the start switch is at
III position, terminal 30 is connected with
terminal 17.
8
Power-Supply System
Main components
3. Turn the start switch to O position. Use the Finally, we can judge that the start switch works
two probes of the multimeter to test the six normally if reading in the multimeter is identical
terminals of the start switch with two with that in the procedures after finish the above-
terminals for each time. There are 15 groups mentioned test procedures
for test, namely, [30,58] ; [30,15] ; [30,
17] ; [30, 19] ; [30, 50] ; [58, 15] ;
[58, 17] ; [58, 19] ; [58, 50] ; [15,
17], [15, 19] ; [15, 50] ; [17, 19] ;
[17,50] ; [19,50]. Reading "1" is shown in
the multimeter which indicates the resistance
between the two terminals is infinite.
4. Turn the start switch to P position. Use the
two probes of the digital multimeter to test the
six terminals of the start switch with two
terminals for each time, as the same
procedures in step 3. when testing terminal
[30, 58], the reading in the multimeter is 0,
which indicates the resistance between the
two terminals is 0, but reading of other
terminals is "1".
5. Turn the start switch to I position, use the two
probes of the multimeter to test the six
terminals of the start switch with two
terminals for each time, as the same
procedures in step 3. When testing terminal
[30, 15], the reading in the multimeter is 0,
which indicates the resistance between the
two terminals is 0, but reading of other
terminals is "1".
6. Turn the start switch to II position; use the
two probes of the multimeter to test the six
terminals of the start switch with two
terminals for each time. When testing
terminal [30, 15] ; [30, 19] ; [15, 19],
the reading in the multimeter is 0, which
indicates the resistance between those
terminals is 0, but reading of other terminals
is "1".
7. Turn the start switch to III position. The start
switch can not hold automatically at this
position. Use the two probes of the
multimeter to test the six terminals of the start
switch with two terminals for each time, as
the same procedures in step 3. when testing
terminals [30, 15] ; [30, 17], [30, 50] ;
[15,17] ; [15,50] ; [17,50],reading in
the multimeter is 0, and reading of other
terminals is 1 .
9
Power-Supply System
Main components
Illustration 1-10 31B0095 outside view and principle schematic symbol of relay
Illustration 1-13 31B0113 Relay 6. Connect the positive pole of the +24V power
supply to terminal "86" and the negative pole
to terminal "85"'; meanwhile, connect one
probe of the multimeter to terminal "30" of the
relay, and another one to terminal "87" , the
reading in the multimeter should be "0". Move
the probe for terminal "87" to terminal "87A",
the reading in the multimeter should be "1".
After finish the above-mentioned steps, if the
reading in the multimeter is the same with that
described in the above steps, then the relay can
be judged to be good.
As to the serious damaged normal open contact
and normal closed contact, the above-mentioned
steps are not suitable for checking.
Note: when testing relay 31B0113, it is
unnecessary to check terminal "87a".
Illustration 1-15 head surface of alternator Illustration 1-16 Inside principle schematic of
altemator
2. Rectify the current by the unilateral 2. Turn on the disconnect switch of the
conduction function of the silicon diode. At machine. Do not start the diesel engine.
any moment, only the positive diode which Connect the red probe of the multimeter to
has highest potential and connects with the "B+" terminal of the alternator, the black
one-phrase winding is conducting; also, only probe to "Ground" terminal of the alternator.
the negative diode which has lowest potential Keep a record of the multimeter reading. The
and connects with one-phrase winding is normal reading should be between "24" and
conducting. On this way, the six diodes "26".
conduct in turn, and then a stable impulsive
3. Start the diesel engine. The checking
direct voltage is available at its both sides.
methods are the same with the instruction in
3. The terminal voltage of the alternator is step 2. Record the reading in the multimeter
proportional to the engine speed. Therefore, again. The reading should higher than that in
the terminal voltage will change greatly step 2. which indicates that the alternator
because the engine rotates at different works normally.
speed. Equip with a regulator because the
The above-mentioned steps should be carried
terminal voltage can not meet the
out when the machine unloads. (Unload means
requirement for constant voltage of the
all of the electrical appliances are not turned on
electrical appliances.
when turning on the start switch)
4. The regulator controls the excitation current
If reading in the multimeter does not change after
through the inner electrical circuit to stabilize
step 2 and step 3, turn off the start switch and
the alternator output voltage by controlling
check the engine again according to the
the magnetic filed.
following steps:
CAUTION: Without batteries, do not 1. Check the alternator drive belt according to
allow the engine supplies power for the the instructions in operation manual. If it is
electrical appliances only. loose, adjust it.
2. Check the connection terminals of the
During the operation of diesel engine, do not
alternator. If they are loose, tighten them with
allow any metal tools or other metal conductors
a spanner.
close to the "B+" (Battery Positive) terminal
and "Ground" terminal of the alternator to avoid If it still doesn't work after check, please consult
short circuit. A short circuit on alternator could with liugong dealers and CUMMINS service
cause a serious result! station.
Illustration 1-17 outside view and principle schematic symbol of start motor
(1) Electromagnetic switch (2) Big contact of start motor (3) Yoke
(4) Rotator windings of start motor (5) Stator windings of start motor
The electromagnetic switch of start motor is push the yoke on the start motor move leftwards,
controlled by the start contact. When the start to drive the drive gear of the start motor move left
switch is turned to III position (start position), the to engage with the engine flywheel. Then the
start contact starts to work. The normal open start motor drives the flywheel to rotate, the
contact is energized with the power supply of diesel engine is starting to work.
electromagnetic switch (1) to turn on the
electromagnetic switch (1). After the
electromagnetic switch (1) turns on, the inner
electromagnetic coil produces suction and
makes the iron move rightwards to push the
tactile disc running. Then the two big contacts (2)
of the starter motor are energized. Current from
the batteries goes through the two big contacts
(2) and reaches the rotator winding (4) and stator
winding (5) of the start motor. The rotator winding
(4) is energized and produces electrodynamic
force to rotate under the magnetic filed effect of
the stator winding (5). Meanwhile, the iron of the
electromagnetic switch (1) moves rightwards to
21
Power-Supply System
Main components
FROM BATTERY
PLUNGER
CONTACTS
TO MOTOR
WINDINGS
SHIFT
LEVER
STARTING
MOTOR
Starter Solenoid
The start switch can not hold at III position for a The disconnect switch is used to control the
long time due to its auto-reposition function, connection between battery negative pole and
therefore, an assistor may be needed to help to frame of the machine. When the disconnect
check the start motor. switch is at "O" (OFF) position, the power-supply
of the machine is cut off. The electrical
1. Turn the digital multimeter to 50V range at its
appliances can not work even though the start
voltage position.
switch is turned on. When the disconnect switch
2. Turn the start switch to III (start) position until is at "I" (On) position, the negative pole of the
step 2 is finished. Connect the black probe of power-supply is energized. Then the connection
the multimeter to any metal units on the between the electrical appliances and power -
frame, the red probe to the big contact supply can be controlled by the start switch and
terminal of the start motor (see Illustration1- the engine can be started now.
19 "TO MOTOR WINDINGS" terminal in work
Illustration 1-20 Disconnect switch and principle
schematic of start motor). Reading in the
schematic symbol
multimeter should be about "24". If the start
motor has no response even though the
reading is correct, then the start motor is in
failure. If the reading is incorrect, continue to
check by following the below steps.
3. Turn the start switch to III (start) position
again; hold the start switch until step 3 is
finished. Connect the black probe of the
multimeter to any metal units on the frame,
the red probe to SWITCH TERMINAL on the
start motor. Reading in the multimeter should
be about "24". If the start motor has no
response even though the reading is correct,
then the start motor is in failure. If the reading
CAUTION: Turn off the disconnect
is incorrect, check the circuits that controlled
switch after finish each operation and
by start motor continuously.
running. Otherwise, electricity leakage could
Refer to system trouble test section for the circuit happen and results in serious damage.
trouble information.
Do not turn off the disconnect switch during
Sometimes the start motor can start when
operation of the machine, or it will result in
turning the start switch to III position, but the
serious damage to the electronic system!
engine can not run. The possible reason may be
from the abnormal engagement of the drive gear
Turn off the start switch firstly, then turn off
inside the start motor, or the injection pump of
the disconnect switch when stop the
the engine has trouble or other troubles in the
machine.
engine. Please contact with Liugong dealer and
CUMMINS service station.
Turn on the disconnect switch firstly, then
Disconnect Switch turn on the start switch when start the
machine.
Turn off the disconnect switch when welding Illustration 1-21 Battery and principle schematic
on the machine. symbol
Charge of Batteries
Two batteries are connected in series to produce
+24V power supply in this machine. The rated
Charge the battery if the hydrometer appears
capacity of the battery is 120 Ah, and the starting
black.
current at low temperature is 850 CCA.
As to a clear hydrometer, there may be bubbles
As reversible direct current, the battery connects
exist in the hydrometer. Remove all the
with the engine in series to supply power to all
connected cables on the battery. Shake the
the electrical appliances. It can supply high
battery slightly after the battery cools down, if the
current to motor starting in a short time to start
hydrometer is still clear, discard it.
the engine. It is also a large capacitor which can
absorb the overvoltage that could happen at any 1. Turn the disconnect switch to O position and
time in the circuit in order to protect all the turn the start switch to O position then take
electrical appliances of the machine. off the key.
24
Power-Supply System
Main components
2. Remove the battery from the machine. When 7. When the battery power loss is severe, the
removing the battery, disconnect the negative battery may not be charged at the initial
cable firstly and then disconnect the positive stages. The battery charge current can
cable. resume step by step along with the charge
process. It may take about 14 hours for
3. Clean the battery terminals and surface with
charging the battery.
a clean cloth. Remove the oxide on the
surface. 8. During charging, if the battery temperature
4. Under normal room temperature, connect the exceeds 45 ℃ , stop charging the battery
until the battery temperature drops down to
positive pole (+) clamp of the charger to the
room temperature, halve the current, and
position terminal (+) of the battery; the
keep charging.
negative pole (-) clamp of the charger to the
negative terminal (-) of the battery. Make sure 9. Check the hydrometer state one time per
that the battery terminals are clean and the hour during charge the battery. Stop charging
charge circuit is at good connection. if the hydrometer of the battery turns green.
5. Charge the battery with constant voltage 10. It is recommended to apply Vaseline on the
charger of 16.0 V (Max. does not exceed battery terminals to avoid electric corrosion
16.2 V) till the hydrometer of the battery turns after charging.
green. A green hydrometer indicates that the
battery is full of electricity. Notice of Charge
6. Charge the battery with constant current if it
Do not charge two batteries in series.
can not be charged with constant voltage.
Charge the battery with 12A constant current Keep ventilation when charging the battery at
till the battery hydrometer turns green. A normal temperature.
green hydrometer indicates that the battery is
Stop charging immediately to check the reason if
full of electricity.
the battery exhaust spurts acid during the
Table of charging time and battery voltage charging process.
Battery 12.45~ 12.45~ 12.35~ 12.20~ Carry out the electrification in good ventilation
Voltage 12.55V 12.35V 12.20V 12.05V area. Pay attention to safety.
Battery 12.05~ 11.95~ 11.80~ 11.65~ Do not charge the battery if its terminal cracks.
Voltage 11.95V 11.80V 11.65V 11.50V Discard it.
It is not permitted to use different type or brand 4. Hold the two probes of the digital multimeter.
batteries in series, and also can not use the Turn the disconnect switch to I position. Turn
same type and brand batteries with very different on the start switch and start the engine.
terminal voltages in series.
5. The digital multimeter reading is between
Turn off the disconnect switch before assembly 20V and 24V when the start motor is at
and disassembly the battery cables. Assemble starting instant, and return to the reading
the positive cables firstly, then the negative described in step 3 after the diesel engine
cables when assembly. Disassemble the started smoothly.
negative cables firstly, then the positive cables
The battery is good if the above steps can be
when disassembly.
finished, and the engine can be started
The battery must be fixed hard in order to avoid successfully. If the above steps couldn't be
damages caused by the jounce when the finished, please continue with testing according
machine is running. to the following steps:
The jounce will cause the connection loose 1. Remove all the connection cables of
between the battery terminals and cables when batteries, two batteries connections are
operation and driving the machine. Therefore, disconnedcted completely at this time.
check the connection terminals and the
2. Adjust the digital multimeter to 200V range of
grounding points of the battery cables and the
voltage function.
disconnect switch frequently. If there is
looseness, must close the disconnect switch, 3. Connect the red probe of the multimeter to
and tighten them with tools. the positive terminal of one battery, connect
the black probe to the negative terminal of
There are lagging in the battery terminals, cover
the other battery, the digital multimeter
the lagging for protection the terminals after
reading is about 12-16V.
connecting the battery or checking and servicing
the battery. 4. Check the other battery according to step 3,
the reading is the same with step 3.
Pay attention not to let the metal conductor
contacts with the positive/negative of the battery Replace the battery if the testing steps couldn't
terminals, otherwise it will cause short circuit and be finished.
damage the battery.
1-C Power supply of all the electro-devices The following components are needed for
on the machine realizing power supply of the electrical lift
system:
The following components are needed for
Disconnect switch
realizing the power supply of all the electro-
devices on the machine after starting the diesel Battery
engine:
Breaker
Disconnect switch
Fuse
Battery
The electrical lift system is the only one electro-
Start switch device which can realize lift function but not
through the control of the start switch.
All kinds of fuses
Power supply contactor
Test and Maintenance of the
Diode group
System faults
Alternator
The battery supplies power separately which will In this section, the description about the fault
be changed after starting the diesel engine, the diagnosis and test methods of the power supply
alternator will be the main power supply of the system is focus on the function introduced in
machine. The energy comes from the diesel Funciton Operation section. Other faults are
engine. routine.
1-D Start switch P supplies power
The function operation devices will be marked The experienced service personnel can test the
according to step A or B in the principle system faults according to the judgement steps
schematic. Sign step+No. on the operation in the flow chart
devices in the same step, for example, B1; B2;
B3 etc..
Illustration 1-22-1 Principle drawing 1-A
28
Power-Supply System
Test and Maintenance of the System faults
Test and Maintenance of Faults At the same time, the voltage reaches No.87
terminal of K9 start switch P work relay.
1-A Principle description of the The voltage reaches the fuse from third branch
machine power supply way of No.100 wire → XH4 → XA4 receptacle ,
and enters into the engine system from 5A fuse
Step A: As shown in the principle schematic, of the eingine indicator through No.121 wire;
when the disconnect switch is at I position, the then enters into No.30 terminal of the start switch
voltage of batteries supplies power to No.100 from 10A fuse of the start switch through No.111
through the alternator. wire → XA5 receptacle → XY1 receptacle to
prepare for the start switch.
The voltage is divided into two ways after
passing No.100 wire → XH4 receptacle → XA4 Step B: When the operator turns on the start
receptacle → 80A fuse terminal, one way passes switch and turns it to I position, the voltage which
No.176 wire and reaches K1, K2, K3, K4 power reaches No.30 terminal is divided into 5 ways
relay, the other way passes No.177 wire → XH4 through No.15 terminal → No.120 wire → XY1
receptacle → XA4 receptacle → alternator, and receptacle → XA2 receptacle. As shown in
does excitation to the alternator. above illustration.
29
Power-Supply System
Test and Maintenance of the System faults
One way voltage enters into the diode through One way voltage forms current loop through
No.120 wire → No.86 terminal of K14 start No.120 wire → No.86 terminal of K3 main relay
switch P work relay → the relay winding → → the relay winding → No.212 wire → ground,
No.212 wire → ground, which forms the current K3 main relay works, its NO contact closes. The
loop, the K9 start switch P work relay works, its voltage reaches K1 through No.176 wire in step
NO contact closes, NC contact opens. Voltage A, and then reaches No.187 wire and the fuse
reaches No.87 terminal of K9 start switch P work generatrix through K1 NO contact and supplies
relay in step A and supplies power to horn, radio, power to the branch way fuses. The branch way
flasher relay through NO contact of K9 → No.30 fuses controlled by K3 relay are: the backup
terminal → No.402 wire → the generatrix of fuse alarm 10A, the brake light 10A, the electric seat
and 10A fuse; And supplies power to the rotating 5A, the positioner light 10A, the front floodlight
beacon, the dome light through 5A fuse; Turn on l15A, the rearviewer 10A. K3 relay supplies
the corresponding switches for work after above power to the corresponding electro-devices by
devices realized power supply. the branch way fuses.
One way voltage forms current loop through One way voltage forms current loop through
No.120 wire → No. 86 terminal of K1 main relay No.120 wire → No.86 terminal of K4 main relay
→ the realy winding → No.212 wire → ground, → the relay winding → No.212 wire → ground,
K1 main relay works, its NO contact closes. The K4 main relay works, its NO contact closes. The
voltage reaches K1 through No.176 wire in step voltage reaches K1 through No.176 wire in step
A, and then reaches No.185 wire and the fuse A, and then reaches No.188 wire and the fuse
generatrix through K1 NO contact to supply generatrix through K1 NO contact and supplies
power to all branch ways fuses. The branch way power to the branch way fuses. The branch way
fuses controlled by K1 relay are: secondary fuses controlled by K4 relay are: the work light
steering 10A, parking brake 5A, the grid heating 20A, the rear floodlight 15A, and the defroster
relay 10A, the instrument 5A, the centralized 20A. K4 relay supplies power to the
lubrication system 10A, the shift control system corresponding electro-devices by the branch way
7.5A, the bucket positioner 5A, the boom shock fuses.
absorption 5A, the stabilized power supply 10A,
Step C: The engine can be started when the
the counterweight system 5A, start switch power
operator turns the start switch to III gear. The
supply 5A, the fan reversal solenoid 5A. K1 relay
voltage reached No.30 terminal of the start
will supply power to the corresponding electro-
devices by the branch way fuses. switch passes No.17 terminal → No.180 wire →
XY1 receptacle → XA5 receptacle → No.87
One way voltage forms current loop through terminal of K11 gear start interlock relay. As
No.120 wire → No.86 terminal of K2 main relay shown in above illustration.
→ the relay winding → No.212 wire → ground,
The shift control unit supplies power to No.584
K2 main relay works, its NO contact closes. The
wire when the shift control lever is at NEUTRAL
voltage reaches K1 through No.176 wire in step
state, the voltage forms current loop through
A, and then reaches No.186 wire and the fuse
generatrix through K1 NO contact and supplies No.584 → XA5 receptacle → No.86 terminal of
power to the branch way fuses. The branch way K11 gear start interlock relay → relay winding →
fuses controlled by K2 relay are: A/C 20A, A/C No.212 wire → ground, K11 gear start interlock
relay works, its NO contact closes.
5A, the wiper 20A, the lighter 10A. K2 relay
supplies power to the corresponding electro-
devices by the branch way fuses.
30
Power-Supply System
Test and Maintenance of the System faults
The voltage forms current loop from No.87 1. First, make sure every cable connection of
terminal of K11 gear start interlock relay → No.30 the battery and the grounding of the
terminal of K11 gear start interlock relay → disconnect switch are good.
No.182 wire → No.86 terminal of K start relay → 2. Then, measure the voltage between the
relay winding → No.212 wire → ground, K5 start positive terminal and the negative terminal of
relay works, its NO contact closes. The voltage
the battery. The battery is deficient in power if
reached K5 through No.176 terminal in step A,
the digital multimeter reading is the same to
reaches No.183 terminal through K5 NO contact
step1; please charge the battery according to
→ XA3 receptacle → XH3 receptacle → No.50
the battery charging procedure.
terminal of start motor induction switch control
terminal → ground, forms current loop, its NO 3. Otherwise, check the disconnect switch and
contact closes, the start motor works, starting the judge whether it is damaged or not according
engine. to the test methods introduced in Main
Component section if the digital multimeter
1-A-F1 Test steps of the main electro- reading is different with step1.
devices power supply faults
Description of the fault phenomenons: Turn the Step2. Listen to the engaged sound of the
disconnect switch and the start switch to I main power supply relay
position, each instrument doesn't respond, the
● Turn the disconnect switch and the start
electro-devices on the machine (except radio
; horn ; flasher ; beacon/doom lamp) don't switch to I position.
respond ( e.g, the light doesn't work when turn ● Pay attention to the engaged sound of the
on the light switch; the wiper doesn't move when main power supply relay under the left side of
operate the wiper, etc). driver seat in cab.
Conclusion: Conclusion:
If the result does OK, please turn to step 2. If the fuse melted, please turn to step13.
If the result doesn't OK, please test as follows: If the fuse doesn't melt, please turn to step 4.
31
Power-Supply System
Test and Maintenance of the System faults
● Connect the red probe of the digital If the fuse melted, please turn to step11.
multimeter to the plug terminal of No.176 wire
on main relay, the black probe to the nearby If the fuse doesn't melt, please turn to step7.
machine housing (grounding).
Step7. Test No.120 wire connection voltage of
● Connect the red probe of the digital main relay winding terminal
multimeter to the plug terminal of No.100 wire
on main relay, the black probe to the nearby ● Hold the disconnect switch and the start
machine housing (grounding). switch at I position.
● Adjust the digital multimeter to 200V range of
Test result:
voltage function.
The digital multimeter reading is between 24V ● Connect the red probe of the digital
and 31V. multimeter to No.86 terminal of No.120 wire
on main relay, the black probe to the nearby
machine housing (grounding).
32
Power-Supply System
Test and Maintenance of the System faults
The digital multimeter reading is between 24V The digital multimeter reading is between 24V
and 31V. and 31V.
Conclusion: Conclusion:
If the result does OK, please test the main relay If the result does OK, the line from the fuse to
according to Main Component section start switch has fault or the connector has
instruction. loosened.
If the result doesn't OK, please turn to step 8. If the result doesn't OK, please turn to step10.
● Step8. Test No.120 wire connection voltage
Step10. Test No.100 wire connection voltage
of start switch
of start motor
● Hold the disconnect switch and the start
switch at I position. ● Hold the disconnect switch and the start
●
switch at I position.
Adjust the digital multimeter to 200V range of
voltage function. ● Adjust the digital multimeter to 200V range of
●
voltage function.
Connect the red probe of the digital
multimeter to No.120 wire connection ● Connect the red probe of the digital
terminal of start switch, the black probe to the multimeter to No.100 wire plug terminal of
nearby machine housing (grounding). main relay, the black probe to the nearby
machine housing (grounding).
Test result:
Test result:
The digital multimeter reading is between 24V
and 31V. The digital multimeter reading is between 24V
and 31V.
Conclusion:
Conclusion:
If the result does OK, please turn to step12.
If the result does OK, there are two probabilities.
If the result doesn't OK, please turn to step9.
First, the line from No.100 wire connection of
Step9. Test No.100 wire connection voltage of start motor to No.100 wire connection of fuse has
start switch fuse fault or the connector has loosened, please
check them carefully. Second, XH4 receptacle
● Hold the disconnect switch and the start has fault, please pull out and insert over again.
switch at I position. Pull the wire connecting with the XH4 receptacle
slightly by hand in order to judge whether the
● Adjust the digital multimeter to 200V range of inside connector has loosened, and replace the
voltage function. connector if it has loosened.
● Connect the red probe of the digital If the result doesn't OK, the positive cable
multimeter to No.100 wire connection connection of battery has loosened.
terminal of start switch fuse, the black probe
to the nearby machine housing (grounding). Step11. Replace 10A start switch fuse
Yes
1-A-F2 Test steps of some electro- The power supply used in 1-A-F1 is different
from this step. Inside the fuse, they use the
devices power supply faults different generatrixs to supply power. Therefore,
if there is electro-devices power supply fault after
Description of the fault phenomenons: Turn the turned on the start switch, need to distinguish
disconnect switch and the start switch to I what kind of power supply the electro-devices
position. Turn on the switches of radio, horn, used, and if it is the fuse generatrix power
hazard flasher, rotating beacon and dome light, supply, please refer to 1-A-F1 fault test steps.
their corresponding electro-devices don't
respond, except these electro-devices, the other Step1. Test the condition of other electro-
electro-devices on the machine can work devices.
normally.
● Turn the disconnect switch and the start
switch to I position.
● Turn on the other switches (e.g. the front rotating beacon and dome light, and judge
floodlight switch, A/C switch) except the whether the electro-devices can work.
switches of radio, horn, hazard flasher,
35
Power-Supply System
Test and Maintenance of the System faults
Conclusion: Conclusion:
If the electro-devices can work, please turn to If the result does OK, check whether each
step2. branch way fuse is melted.
If the electro-devices couldn't work, please test If the result doesn't OK, please turn to step 4.
them according to 1-A-F1 test steps.
Step4. Test No.176 wire connection voltage of
Step2. Test the condition of K9 start switch P K9 start switch P work relay contact terminal.
work relay.
● Adjust the digital multimeter to 200V range of
● Hold the disconnect switch at I position. voltage function.
● Open the electronic control box, find K9 start ● Open the electronic control box, and pull out
switch P work relay, contacting the plastic K9 start switch P work relay.
housing of the relay by hand slightly.
● Turn the disconnect switch and the start
● Turn the start switch to I position. Turn on switch to I position.
and turn off the start switch, please try to feel
● Find No.176 wire connection of K9 start
whether there is obvious vibration during the
switch P work relay contact terminal. Insert
relay contact action at that moment.
the red probe of the digital multimeter into
No.100 wire plug on the back side of the
Conclusion:
relay base, pay attention to contact with the
inner copper. Connect the black probe to the
If the result does OK, please turn to step3.
nearby machine housing (grounding).
If the result doesn't OK, please turn to step5.
Test result:
Step3. Test No.402 wire connection voltage of
K9 start switch P work relay contact terminal. The digital multimeter reading is between 24V
and 31V.
● Turn the disconnect switch and the start
switch to I position. Conclusion:
● Adjust the digital multimeter to 200V range of
If the result does OK, please check or eliminate
voltage function.
the line fault from No.176 wire connection of K9
● Open the electronic control box. start switch P work relay to that of other wiring
harness in the cab.
D.Find the fuse generatrixs of radio, horn,
flasher, rotating beacon and dome light, insert If the result doesn't OK, please check K9 start
the red probe into the generatrixs, and pay switch P work relay according to Main
attention to contact with the inner copper. Component section instruction. Replace it if it is
Connect the black probe to the nearby machine damaged.
housing (grounding).
Step5. Test the voltage between No.466 wire
Test result: and No.212 wire of K9 start switch P work
relay winding terminal.
The digital multimeter reading is between 24V
and 31V. ● Adjust the digital multimeter to 200V range of
voltage function.
● Open the electronic control box, find K9 start relay base.
switch P work relay and pull it out from the
36
Power-Supply System
Test and Maintenance of the System faults
Test result:
Conclusion:
Test result:
Conclusion:
1-A-F3 Test steps of the main line ● Open the control box, find 80A bolt type main
fuse, and pull it out from the centralized
short circuit fault control box. Connect one probe of the digital
multimeter to 80A main fuse connection
Description of fault phenomenons: turn the terminal of the control box, another probe to
disconnect switch and the start switch to I the nearby machine housing (grounding).
position. The main fuse or the start switch fuse
melted, the new fuse keeps melting after Test result:
replaced.
The digital multimeter reading is 0 or not.
Step1. Test whether 80A main fuse
connection terminal of electronic control box Conclusion:
gets short circuit to ground?
If the result is NO, please turn to step5.
● Turn the disconnect switch to O position (turn
If the result is YES, please turn to step2.
off the disconnect switch).
● Adjust the digital multimeter to 200 Ω range.
38
Power-Supply System
Test and Maintenance of the System faults
Step2. Test whether the main relay contact If the result is YES, the lines inside the alternator
terminal of the control box gets short circuit get short circuit, please replace the alternator.
to ground?
Step4. Test whether No.177 wire gets short
● A.Turn the disconnect switch to O position circuit to ground?
(turn off the disconnect switch).
● Turn the disconnect switch to O position (turn
● B.Adjust the digital multimeter to 200 Ω off the disconnect switch).
range.
● Remove No.177 wire from B+ terminal of the
● C.Open the control box, find K1, K2, K3, K4 alternator.
main relays, and pull them out from the
centralized control box. Connect one probe ● Adjust the digital multimeter to 200 Ω range.
of the digital multimeter to No.30 contact
● Connect one probe of the digital multimeter
terminal of the original main relay on the
to No.177 wire terminal, another probe to the
control box, another probe to the nearby
nearby machine housing (grounding).
machine housing (grounding).
Test result:
Test result:
The digital multimeter reading is 0 or not.
The digital multimeter reading is 0 or not.
Conclusion: Conclusion:
If the result is NO, please turn to step5.
If the result is NO, please turn to step5.
If the result is YES, the lines inside the control
If the result is YES, No.177 wire gets short circuit
box get short circuit, please replace the control
inside the wiring harness, please check whether
box housing.
the wiring harness has worn and eliminate the
Step3. Test whether B+ terminal of the short circuit fault.
alternator gets short circuit to ground?
Step5. Test whether No.111 wire of start
switch fuse gets short circuit to ground?
● Turn the disconnect switch to O position (turn
off the disconnect switch).
● Turn the disconnect switch to O position (turn
● Remove No.177 wire from B+ terminal of the off the disconnect switch).
alternator.
● Pull out XA5 receptacle.
● Adjust the digital multimeter to 200 Ω range.
● Adjust the digital multimeter to 200 Ω range.
● Connect one probe of the digital multimeter
● Connect one probe of the digital multimeter
to B+ terminal of the alternator, another
to No.111 wire terminal of start switch fuse,
probe to the nearby machine housing
another probe to the nearby machine
(grounding).
housing (grounding).
Test result:
Test result:
The digital multimeter reading is 0 or not.
The digital multimeter reading is 0 or not.
Conclusion:
Conclusion:
If the result is NO, please turn to step5.
If the result is NO, please turn to setp8.
39
Power-Supply System
Test and Maintenance of the System faults
The digital multimeter reading is 0 or not. If the result is NO, the test is finished.
If the result is YES, the line gets short circuit
inside the control box, please replace the control
box housing.
Illustration 1-25 1-A-F3 Fault test flow chart
1-A-F4 Test steps of the engine Step1. Confirm whether the fault comes from
the main electro-devices power supply
faults connection faults.
Description of fault phenomenons: turn the ● If it is the main electro-devices power supply
disconnect switch to I position, turn the start connection fault, please check the fault
switch clockwise to III position, the engine can't according to 1-A-F1 about the main electro-
start. devices power supply faults.
● If the main electro-devices power supply can
be connected, please turn to step2.
● Adjust the digital multimeter to 200V range. ● Turn the disconnect switch to I position.
● Connect the red probe of the digital ● Turn the start switch clockwise to III position.
multimeter to the positive terminal of the
● Adjust the digital multimeter to 200V range.
battery, the black probe to the negative
terminal of the battery, and don't connect to ● Connect the red probe of the digital
the connection cable terminal. multimeter to No.86 terminal of original start
relay in the centralized control box, the black
Test result: probe to the nearby machine housing
(grounding).
The digital multimeter reading is between 24V
and 27V or not. Test result:
Test result:
Conclusion:
Main Components
Instrument system
Illustration 2-2 Instrument system principle
drawing symbol
The description of outer signal source will be The instrument system can be divided into micro-
introduced in detail in fault test and service controller mode, input mode and output mode
section. etc. according to the function. The control
principle drawing as follows:
Illustration 2-3 Instrument system configuration
TIMED
POWER MICRO-CONTROLLER MOTOR
(SOFTWARE, DRIVER
SIGNAL
INSPECTION, ALERT AND
FILTER WAVE,
CONNECTOR
INDICATOR LIGHTS
FAILURE ILLUMINATION
DIAGNOSE, ALERT LUMINOUS
DISCRETE
AND INDICATOR PARTS
SIGNAL INPUT
DRIVER
LIGHTS CONTROL,
TIMED MOTOR
CONTROL,
ARITHMETIC,
ETC.)
CONTINUOUS DISPLAY
SIGNAL INPUT DRIVER
The icons used on the instrument system comply The definition of the alert and indicator icons:
with the correlative ISO standard.
Turn left indicator
CAUTION: Pull out NO.36 core
receptacle of the instrument system before The light flashes when the machine
weld or maintain the machine. Otherwise, the turns left, the front & rear left turn
strong impacted current may burn the signal light will also flash simultaneously.
combination instrument. And connect No. 36
core receptacle after welding, or the Turn right indicator
machine won't work normally.
The light flashes when the machine
Illustration 2-4 No.36 core receptacle of turns right, the front & rear right turn
instrument system signal light will also flash simultaneously.
The electronic diesel engine state and fault When the main fault alert indicator flashes
indication but the buzzer doesn't beep, the machine has
fault and needs to be stopped to check, the
The following 5 icons are electronic diesel engine operator can drive the machine to the service
state and fault alert indicating icons, which will be station, finds the fault system according to
introduced in detail in electronic diesel engine the alert items in the instrument system and
section in this manual. operates the machine after eliminate the fault.
Keep the copper housing of the temperature Illustration 2-7 Pressure switch outline and
sensor contacting with the measured medium electronic principle drawing symbol
when use it, the resistance value of the
temperature sensitive component changes along
with the measured medium temperature variety
due to the good diathermancy of the copper, the
measured medium temperature is higher, the
resistance value of the temperature sensitive
component is lower. This character of resistance
variety will be translated into that of voltage Some pressure switches are used in this
variety along with temperature variety. The machine for each system pressure alarm, their
variational voltage signal enters into the micro- exteriors look very similar, but action values,
contoller of the instrument system, after withstand pressure values and installation sizes
calculation and disposal, exports signals and are all different. The part numbers are carved on
drives the timed motor instrument to indicate the housing of pressure switch for distinguish.
temperature. Pay attention when use them.
Illustration 2-6 Temperature sensor work The pressure switch parameter table in
principle appendix of service manual lists in detail all
pressure switches types and parameters, refer to
this table straightly if it is needed, or the unit is
the imperial standard. Hereinafter, just illuminate
the pressure switches used in this system.
Pressure alert switch of the instrument
system
Part No. Name Contact Action
value
(MPa)
30B0139 Parking brake NC 11.5
low pressure
alert switch
30B0292 Steering system NC 0.6
low pressure
alert switch
NOTICE
30B0182 Service brake NC/NO 10
low pressure
Turn off the start switch when replace the
alert switch
temperature sensor, replace it after the
30B0132 Transmission oil NC 1.45
machine cooling completely. There is liquid
pressure alert
overflow when loosen the temperature
switch
sensor, replenish the liquid after replacing
the temperature sensor. 30B0291 Secondary NO 0.6
steering running
switch
Pressure switch
30B0131 Engine oil NC 0.059
pressure alert
switch
50
Instrument System
Main Components
See above table, NC shows there is one group Regulate the pressure switch action pressure by
contacts inside the pressure switch; the contact adjusting pole (7). The action pressure of the
condition is NC when the system isn't pressure switch has been adjusted before leave
pressurized. NO shows there is one group the factory and use red paint for sign. Do not
contacts inside the pressure switch; the contact adjust the pole optionally, otherwise which will
condition is NO when the system isn't change the action value and cause accidents.
pressurized. NC/NO shows there are two groups
contacts inside the pressure switch, one is NO, Engine oil pressure alert switch
the other one is NC.
In normal condition, the engine system doesn't
Pressure switch work principle build pressure or system pressure doesn't reach
the action value when operator turns on the start
According to the different inner configurations, switch, the contact of engine oil pressure alert
the pressure switches are divided into switch keeps NC state, the engine oil pressure
dissepiment type pressure switch and piston alert indicator of the instrument system is
type pressure switch. But they have the same lightened. The system pressure will rise until the
work principle no matter what types they are. pressure oil of action value pushing inner NC
contact of pressure switch after turn on the start
Illustration 2-8 Pressure switch work principle
switch. The engine oil pressure alert indicator of
the instrument system will go out.
When the engine system has fault, and makes
the system pressure too low, the pressure switch
contact will close newly, the engine oil pressure
alert indicator of the instrument system will
lighten for alarm.
NOTICE
When the transmission system has fault, and The operator presses the parking brake switch
makes the system pressure too low, the pressure and starts the diesel engine; the brake oil enters
switch contact will close newly, the transmission into the parking brake oil line. When the pressure
oil pressure alert indicator of the instrument reaches the stated value, the pressure oil will
system will lighten for alarm. push the NC contact of the parking brake low
pressure alert switch, and the parking brake low
NOTICE pressure alert indicator of the instrument system
will go out, which shows that the system
When the transmission oil pressure alert pressure is normal.
indicator lightens, and the main fault alert
When the parking brake system has fault and
indicator lightens, please drive the machine
makes the system pressure too low, the pressure
to the service factory for check, and operate
switch contact will close newly, the parking brake
the machine after eliminate the faults.
low pressure alert switch of the instrument
system will act newly.
Service brake low pressure alert switch
NOTICE
The service brake low pressure alert switch is a
switch with double contacts, but just one group
When the parking brake low pressure alert
NC contact is used in this machine. It can be
indicator lightens, the main fault alert
used as a single contact NC pressure switch.
indicator lightens and the buzzer beeps, must
The check point of service brake low pressure stop the machine immediately and check the
alert switch is connected to the battery, the faults, and operate the machine after
pressure oil will push NC contact of service eliminate the faults.
brake low pressure alert switch if the battery
pressure is normal, the service brake low Steering system low pressure alert switch
pressure alert indicator of the instrument system
will go out, which shows that the system The steering system low pressure switch is a NC
pressure is normal. contact pressure switch.
When the operator turns on the start switch, the
NOTICE
steering pump doesn't run, the steering oil line
doesn't build pressure, the steering system low
When the service brake low pressure alert
pressure alert switch is at close state, and the
indicator lightens, the main fault alert
steering system low pressure alert indicator of
indicator lightens and the buzzer beeps, must
the instrument system will lighten.
stop the machine immediately and check the
faults, and operate the machine after When the operator starts the engine, the steering
eliminate the faults. pump runs, the steering oil line is connected.
When the pressure reaches the stated value, the
Parking brake low pressure alert switch pressure oil will push the NC contact of steering
system low pressure alert switch, and the
The parking brake low pressure alert switch is a steering system low pressure alert indicator of
NC contact pressure switch. the instrument system will go out, which shows
that the system pressure is normal.
When operator turns on the start switch, the
parking brake oil line doesn't build pressure, the
parking brake low pressure alert switch is at
close state, and the parking brake low pressure
alert indicator of the instrument system will
lighten.
52
Instrument System
Function Operation
When the engine goes out abnormally, the Fuel level sensor
steering system pressure descends quickly or
Illustration 2-9 Fuel level sensor outline and principle
the steering system has fault and makes the drawing symbol
system pressure too low; the pressure switch
contact will close newly, and the steering system
low pressure alert switch of the instrument
system will lighten newly. The CUP in the
instrument system will execute the secondary
steering.
NOTICE
NOTICE
Function Operation
When the secondary steering running
indicator lightens, there are 60s working All kinds of sensors and pressure switches in the
hours in the secondary steering pump, place instrument system belong to inspection
the machine straightly in 60s, check the components. The sensors measure the system
faults, and operate the machine after work information and show them by gauges
eliminate the faults. when the machine works. The pressure switches
monitor the system normal work condition, they
act when the system has fault, the instrument
system gives alarm.
The instrument system is a window implement
which collects and indicates the variational work
information of the machine.
53
Instrument System
Function Operation
There are other components have the clutch cut- The following electronic components are needed
off function, which will be introduced in detail in for realizing steering system fault indication.
chapter 6 Parking Brake and Clutch Cut-off of ● 5A fuse
this service manual.
● Instrument system
The clutch cut-off indicator in this instrument
system just shows No.600 wire state of ZF shift ● Steering system low pressure alert switch
control system, the clutch cut-off indicator will
lighten when the grounding voltage of No.600 2-M Start state indicator
wire is about +24V, the shift control system
executes the clutch cut-off function. The clutch The following electronic components are needed
cut-off indicator will go out when the grounding for realizing start state indication.
voltage of No.600 wire is 0V. The shift control ● 5A fuse
system doesn't execute the clutch cut-of
function. ● Instrument system
The following electronic components are needed ● Start motor
for realizing clutch cut-off indication.
2-N Parking brake low pressure alert
● 5A fuse
indicator
● Instrument system
●
The following electronic components are needed
ZF shift control system
for realizing parking brake low pressure alert
indication.
2-J Lubrication running indicator
● 5A fuse
The lubrication running indicator is the piston ● Instrument system
pump work indicator of the lubrication system.
The indicator will lighten when the piston pump ● Parking brake low pressure alert switch
runs, the indicator will go out when the piston
pump doesn't work. 2-O Service brake low pressure alert
indicator
The following electronic components are needed
for realizing lubrication system running
The following electronic components are needed
indication.
for realizing service brake low pressure alert
● 5A fuse indication.
● Instrument system ● 5A fuse
● Auto-return lubrication system ● Instrument system
● Service brake low pressure alert switch
2-K Secondary steering running indicator
2-P Engine oil pressure alert indicator
The following electronic components are needed
for realizing secondary steering running
The following electronic components are needed
indication.
for realizing engine oil pressure alert indication.
● 5A fuse
● 5A fuse
● Instrument system
● Instrument system
● Secondary steering running switch
55
Instrument System
Function Operation
2-T Buzzer
Illustration 2-10 Instrument system signal source and execution components distribution drawing 1
Illustration 2-11 Instrument system signal source and execution components distribution drawing 2
57
Instrument System
Function Operation
When turn on the start switch but not start the But when the machine operates or runs normally,
machine, as the diesel engine hasn't been the instrument system appears alert signals,
started, the hydraulic, brake, shift control must check the faults carefully. Some possible
systems don't build pressure, most of the alert faults may occur with high frequency are listed in
indicators will flash. Start the engine, every the following tables, but which don't include all
system runs normally, these indicators will go out the faults, so please dispose the fault according
one by one. to the practical condition.
Item Sign Fault description Fault point Remark
Start The indicator Start relay fault
state doesn’t lighten Neutral/start interlock relay fault
indicator when start the ZF system fault
Start switch fault
engine
Indicator damage
The engine Start motor fault
doesn’t go out Start relay fault
after starting
Engine Give alarm during Observe oil level condition from Read fault code from
oil operation engine oil dipstick electrical engine state
pressure Does engine oil pump run and fault indicator state,
alert normally dispose fault according
indicator CUMMIUS electrical system to CUMMUS engine
fault fault code disc if has
Engine oil pressure switch
143 fault. The engine oil
damage
pressure switch is
damage if doesn’t
appear 143 code.
Intake air Alert Air filter blocks, replace it. The
filter alert details see operation &
indicator maintenance manual
Engine Alert Observe coolant level, fill the Read fault code from
coolant coolant if not enough. The electrical engine state
level details see operation & and fault indicator state,
alert maintenance manual. dispose fault according
indicator to CUMMUS engine
fault code disc if has
197 fault.
Transmis Give alarm during Observe transmission oil level Refer to Transmission
sion oil operation from oil dipstick, fill oil if not of service manual
pressure enough.
alert Shift control valve fault
indicator ZF system fault
58
Instrument System
Function Operation
Service Give alarm during Check the battery according to Refer to Brake of
brake operation Brake of service manual if the service manual
alert battery pressure is not enough.
indicator Pay attention leakage.
Check battery according to
Brake of service manual if the
brake valve has fault.
The line has fault
Parking Give alarm during Check battery according to Refer to Brake of
brake operation Brake of service manual if the service manual
alert battery pressure is not enough.
indicator Pay attention leakage.
Check battery according to
Brake of service manual if the
brake valve has fault.
The line has fault
Steering Give alarm during Engine starts abnormally
system operation Steering pump damages
fault The line has fault
indicator
Engine The indicator Engine damages
charge doesn’t lighten Line fault
indicator before starting The indicator damages
engine
The indicators The engine damages
don’t go out after
starting engine
Seconda The indicator Control mode of instrument
ry doesn’t lighten system damages
steering when engine The indicator damages
running goes out
indicator abnormally or
steering pump
damages
59
Instrument System
System Fault Test and Service
This illustration just marks the related branch way and direction, other irrespective parallet connection
branch ways aren't marked.
Core No. Function Outer signal source Singal control state Wire No
2 Parking brake alet Parking brake low See signal instruction of 300
indicator pressure alert switch instrument system
3 Engine oil pressure alert Engine oil pressure alert See signal instruction of 301
indicator switch instrument system
4 Front floodlight high Combination switch See signal instruction of 403
beam indicator instrument system
61
Instrument System
System Fault Test and Service
Core No. Function Outer signal source Singal control state Wire No
5 Turn right indicator Combination switch See signal instruction of 404
instrument system
6 Turn left indicator Combination switch See signal instruction of 405
instrument system
8 Lubrication running Lubrication system input See signal instruction of 411
indicator instrument system
10 Service brake alert Service brake low See signal instruction of 303
indicator pressure alert switch instrument system
11 Steering system fault Steering system low See signal instruction of 312
pressure alert switch instrument system
12 Clutch cut-off indicator Parking brake clutch cut- See signal instruction of 600
off pressure switch and instrument system
parking brake button
13 Engine water Engine water 701
temperature sensor temperature sensor
14 Intake air filter alert Intake air filter alert See signal instruction of 310
indicator switch instrument system
14 Axle oil pressure alert Axle oil pressure alert See signal instruction of 304
indicator switch instrument system
17 Lubrication system fault Lubrication system 305
alert indicator output
18 Engine coolant level alert CUMMINS electrical See signal instruction of 306
indicator ECM output instrument system
19 Warning indicator CUMMINS electrical See signal instruction of 320
ECM output instrument system
20 Torque converter oil Torque converter oil 702
temperature sensor temperature sensor
21 Transmission oil Transmission oil See signal instruction of 307
pressure alert indicator pressure alert switch instrument system
22 Hydraulic oil filter alert Hydraulic oil filter alert See signal instruction of 308
indicator switch instrument system
23 Wait to start indicator CUMMINS electrical See signal instruction of 321
ECM output instrument system
24 Engine charge indicator L terminal of engine See signal instruction of 800
output instrument system
25 Service indicator CUMMINS electrical See signal instruction of 322
ECM output instrument system
26 Fuel in water indicator CUMMINS electrical See signal instruction of 323
ECM output instrument system
27 Stop indicator CUMMINS electrical See signal instruction of 324
ECM output instrument system
62
Instrument System
System Fault Test and Service
Core No. Function Outer signal source Singal control state Wire No
28 Hydraulic oil temperature Hydraulic oil temperature See signal instruction of 309
alert indicator switch instrument system
29 Start state indicator 50 terminal of start motor See signal instruction of 407
instrument system
30 Secondary steering Secondary steering See signal instruction of 408
running indicator running switch instrument system
31 Engine rev signal 704
32 Speed signal ZF shift control system 705
output
34 Fuel level sensor Fuel level sensor 201
earthing earthing
35 Fuel level sensor signal Fuel level sensor signal 703
Alert signal
Item Alert Flash or not Inout signal Inout signal Sign Remark
indicator level at level at alert
color normal state state
Turn left Green Flash Hang in the air Flash signal
indicator
Item Alert Flash or not Inout signal Inout signal Sign Remark
indicator level at level at alert
color normal state state
Lubrication Red No Hang in the air Earthing Not
system fault available for
alert indicator this
machine
Hydraulic oil Red No Hang in the air Earthing Not
tempertaure available for
alert indicator this
machine
Hydraulic oil Red No Hang in the air Earthing Not
filter alert available for
indicator this
machine
Engine coolant Red No Hang in the air Earthing
level alert
indicator
Axle oil Red No Hang in the air Earthing Not
pressure alert available for
this
machine
Engnie charge Red No D+ terminal of D+ terminal of From
indicator engine engine alternator
Item Alert Flash or not Inout signal Inout signal Sign Remark
indicator level at level at alert
color normal state state
Stop indicator Red No Hang in the air Earthing
Instrument signal 1
Instrument signal 2
Instrument signal 3
Test the fault of the engine water temperature a.Turn on the start switch, the engine water
gauge in the instrument system if it doesn't have temperature gauge pin should turn and indicate
indication or the indication isn't on time. the min read of yellow area. Turn off the start
switch, the read of pin drops down to limit value
from the min read. The instrument system has
damaged if the water temperature pin doesn't
move.
b.Turn off the start switch, and disassemble the
lead copper connector of water temperature
sensor from the engine.
66
Instrument System
System Fault Test and Service
c.Turn on the start switch, the lead copper (1) Check the loose condition of No.3 core of
connector of water temperature sensor contacts XK4 receptacle.
with engine metal housing or whole machine
(2) Check the condition of wiring harnesses from
metal housing (the place without paint). The pin
engine water temperature gauge receptacle
of water temperature gauge will indicate the max
to the sensor.
read.
d.Hang the lead copper connector of water Step 3. Test water temperature sensor is
temperature sensor in the air; the pin of water damaged or not.
temperatue gauge will indicate the min read.
a.The water temperature sensor may be
Conclusion: damaged if above test doesn't have fault.
b.Turn off the start switch, disassemble the
If the result does OK, please turn to step3.
watetr temperature sensor and replace it after
If the result doesn't OK, please turn to step2. the engine cooling, there is coolant overflow
during replacing, replenish the coolant according
Step2. Test whether there is fault in the line to overflow coolant quantity.
from engine water temperatue gauge to the
c.Replace the instrument system if the water
sensor.
temperature gauge pin indicates incorrectly
again after eliminate the fault.
a.Prepare one 10m lead, Divest insulation layer
about 10-20mm of the lead two terminals. Conclusion:
b.Disassemble the steering column assembly,
pull out the receptacle of the instrument system, The cab environment is needed to judge the
and wrap one terminal of the lead prepared in water temperature sensor parameter is correct or
step a with the lead copper connector of the not. Please replace with a new water
disassembled water temperature sensor, another temperature sensor if doubted that it has
terminal is connected to the cab. damaged. Then deliver the bad sensor back to
c.Pull slightly No.701 wire connected to No.13 the factory for test.
core of instrument system, judge the connecting
condition, use the special tool to connect newly if
it is loosened.
d.Adjust the digital multimeter to 200 Ω range of WARNING: Disassemble the water
Ω function, connect one probe to the lead inside temperature sensor after the engine cooling
the cab, another probe to No.13 core of the adequately! High temperature water and oil
instrument system. will injure human body; Please wear guard
glasses and gloves if it is necessary.
Test result:
2-B-F Torque converter oil temperature gauge
The digital multimeter reading is 0 Ω . fault test
Conclusion:
Fault phenomenon definition:
If the result does OK, the line doesn't have fault,
please turn to step3. Test the fault of the troque converter oil
If the result doesn't OK, the line has fault, temperature gauge in the instrument system if it
disassemble the interior decoration assembly doesn't have indication or the indication isn't on
and cup map on the left-rear side of the cab. time.
67
Instrument System
System Fault Test and Service
Step 2. Test whether there is fault in the line b.Turn off the start switch, disassemble the
from torque converter oil temperature gauge torque conveter oil temperature sensor and
to the sensor. replace it after the engine cooling, there is
coolant overflow during replacing, replenish the
coolant according to overflow coolant quantity.
a.Prepare one 10m lead, Divest insulation layer
about 10-20mm of the lead two terminals. c.Replace the instrument system if the oil
temperature gauge pin indicates incorrectly
b.Disassemble the steering column assembly,
again after eliminate the fault.
pull out the receptacle of the instrument system,
and wrap one terminal of the lead prepared in
step a with the lead copper connector of the
disassembled torque converter oil temperature
sensor, another terminal is connected to the cab.
68
Instrument System
System Fault Test and Service
If the result does OK, the instrument system is Step 1. Test whether the machine can shift
damaged. successfully and run normally.
If the result doesn't OK, No.703 wire has fault.
Conclusion:
2-D-F Speed LCD test
If the result does OK, the machine can shift
successfully and run normally which shows ZF
Do not turn on the start witch, if the speed LCD
shift control system doesn't have fault, the rev
leaks liquid, the black spot can be observed by
seonsor works normally, the signal source is
eye on the speed LCD, which shows the
normal.
instrument system is damaged.
If the result doesn't OK, please check as follows:
Observe the speed LCD when turn on the start
switch, the instrument system is damaged if the (1) Did replace the rev sensor? If it has been
speed LCD doesn't have reflection or the LCD replaced, please adjust the gap between rev
doesn't show the whole content. sensor and thransmission gear until the
whole machine can shift successfully (refer to
The rev sensor is used to check transmission
the shift control system section for details).
output gear rev when running, then let rev signal
translate into the impulse signal, input EST (2) If didn't replace the rev sensor, use the digital
electronic control unit. EST electronic control unit multimeter 2000 Ω range of Ω function, pull
exports the transmission impulse signal into the out the plug of the rev sensor, connect the
instrument system through the outer lead. CPU probes of the digital multimeter to two pins of
inside the instrument system calculates the input the rev sensor, the multimeter reading is
impulse signal number and sends to the speed 1020 ± 100 Ω . Otherwise the rev sensor is
LCD for show after converted into speed signal. damaged, please replace it.
The original signal of the speed signal comes (3) The rev sensor signal wire of ZF shift control
from the rev sensor, through EST electronic system is broken or not.
control unit and CPU of the instrument system,
reaches the speedometer finally. The special Step 2. Test the line fault
implement is needed if inspect the signal source,
but the field maintenance doesn't have the a.Prepare one 10m lead, divest the insulation
condition to inspect signal source. A new spare layer for about 10-20mm of the lead two
instrument system is needed to do the following terminals.
test steps. b.Turn off the start switch, disassemble the
LCD normal work temperature is 0~50 ℃ (0~122 steering column assembly, and pull out the
°F) in the instrument system, please keep the receptacle of the instrument system.
indoor temperature at normal work temperature Disassemble the interior decoration assembly
when operate the machine in cold weather. and cup map on the left-rear side of the cab, pull
slightly No.705 wire of X5 receptacle (one plug
Falut phenomenon definition: and one socket), judge the connecting condition
between No.705 wire and copper, use the
The speed LCD doesn't show reading during special tool to connect over again if the
running, just shows 0. connection is not tight. And turn to the next step
if it is tight.
71
Instrument System
System Fault Test and Service
c.Pull out X5 receptacle, and keep contacting CUMMINS engine ECM is the control centre of
one terminal of 10m lead with No.705 wire the engine system, which has self-check
copper until finish the measurement, another function. The electrical engine state indicator
terminal is connected to the instrument system. group on the instrument system will give alarm
when the engine system has fault.
d.Adjust the digital multimeter to 200 Ω range of
Ω function, one probe contacts with No.32 core The engine state indicator group will give alarm
copper of the instrument system, another probe signal if the engine system has fault and makes
contacts with the copper core of the instrument the rev gauge doesn't indicate or the indication
system. value is incorrect. To the opposite, if the engine
state indicator group doesn't give alarm signal,
Test result: the signal source doesn't have fault.
Fault test steps: Refer to 2-F-F right turn indicator fault test steps,
the tested lead is No.404 wire.
Step 1. Test the line fault
2-H-F Front floodlight high beam indicator b.Assemble the steering column, turn on the start
fault test switch, push the combination switch forwards for
floodlight high beam, observe whether the front
Falut phenomenon definition: floodlight high beam indicator works normally.
If the result doesn't OK, the line has open circuit, a.Turn off the start switch, and pull out 36-pin
check No.403 wire carefully, especially the receptacle of the instrument system.
receptacle, the round place, the active place
contacts with the metal plate. b.Turn on the start switch, don't start the engine,
press down the parking brake button.
Step 2. Replace the instrument system c.Adjust the digital multimete to 50V range of
voltage function. The red probe contacts with
a.Turn off the start switch, disassemble the No.12 core of the instrument system, the black
steering column, and replace the old instrument probe contacts with the metal housing (the place
system with a new one. without paint) of the cab (or contacts with No.200
wire of No.16 core of the instrument system)
74
Instrument System
System Fault Test and Service
Step 3. Test the grounding voltage of No.600 Check the lubrication system piston pump
wire, No.170 wire in turn. according to this service manual if the piston
pump doesn't run.
a.Pull the parking brake and hold it, turn off the
Fault test steps:
start switch, disassemble the fixing bolt of the
parking brake button plate, pull up the parking
Step 1. Test the line fault
brake assembly slightly. Put the assembly on the
control box, please notice that the copper
a.Turn off the start switch, disassemble the
connector can't contact with the metal housing of
steering column, and pull out the receptacle of
the machine.
the instrument system. Find No.411 wire
b.Adjust the digital multimeter to 50V range of connected to No.8 core of the instrument system,
voltage function. Turn on the start switch, the red pull it slightly by hand to judge it is loosed or not,
probe contacts with No.600 wire copper use the special tool to connect it if it is loosed.
connector of the parking brake button, the black
b.Pull out XK7 receptacle connected to the
probe contacts with the metal housing (the place
lubrication system, find No.411 wire connecte to
without paint) of the cab. The digital multimeter
No.3 core, pull it slightly by hand to judge it is
reading is between 24V and 31V.
loosed or not, and use the special tool to connect
it if it is loosed.
75
Instrument System
System Fault Test and Service
If the result does OK, the line doesn't have fault, The secondary steering indicator doesn't lighten
please turn to step 2. when the secondary steering motor runs.
If the result doesn't OK, the line has open circuit, Check the secondary steering motor according
check No.411 wire carefully, especially the to the service manual if the secondary steering
receptacle, the round place, the active place motor can't run normally.
contacts with the metal plate.
Fault test steps:
Step 2. Test the grounding voltage of No.411
wire of the instrument system. Step 1. Test whether the voltage of No.122
wire of the secondary steering pressure
a.Turn off the start switch, disassemble the switch is +24V.
steering column, take out the instrument system
and pull out 36-pin of the instrument system. a.Pull out two receptacles of the secondary
b.Adjust the digital multimeter to 50V range of steering pressure switch.
voltage function. Turn on the start switch, and b.Turn on the start switch, and adjust the digital
press the KD button to start the piston pump. The multimeter to 50V range of voltage function. The
red probe contacts with No.8 core of the red probe contacts with No.122 wire copper
instrument system. The black probe is connected receptacle. The black probe is connected with
with the metal housing (the place without paint) the metal housing (the place without paint) of the
of the cab. cab.
The digital multimeter reading is between 24V The digital multimeter reading is between 24V
and 31V. and 31V.
Conclusion:
(1) Judge the instrument system has electricity If the result doesn't OK, the line has open circuit,
or not, all indicators lighten or not, 5A fuse check No.411 wire carefully, especially the
melts if the instrument system doesn't receptacle, the round place, the active place
electrify. contacts with the metal plate.
(2) No.122 wire has fault if the instrument
2-L-F Steering system fault indicator fault test
system works normally, check No.411 wire
carefully, especially the receptacle, the round
Fault phenomenon definition:
place, the active place contacts with the
metal plate.
The steering system fault indicator doesn't
lighten at all times when the secondary steering
Step 2. Judge the pressure switch is
damaged or not. pump has run.
The steering system fault indicator doesn't
a.Open the electronic control box, pull out the lighten when the secondary steering pump
secondary steering relay in order to make sure doesn't run.
not to start the secondary steering piston pump
during testing. Fault test steps:
b.Connect No.122 wire and No.408 wire, and
Step 1. The steering system fault indicator
make sure the copper has good contact.
doesn't lighten when the secondary steering
Observe the secondary steering running
pump has run. Replace the instrument
indicator lightens or not.
system.
Conclusion:
Please turn to step2 if the secondary steering
If the result does OK, the secondary steering pump doesn't run.
pressure switch is damaged.
Step 2. Test whether No.312, No.231 wires
If the result doesn't OK, please turn to step 3。 have the line fault.
Step 3. Replace the instrument system. a.Turn off the start switch, disassemble the
steering column, and pull out the receptacle of
a.Turn off the start switch, disassemble the the instrument system. Find No.312 wire
steering column, and replace the old instrument connected to No.11 core of the instrument
system with a new one.. system, pull the wire slightly by hand, judge it is
b.Assemble the steering column, turn on the start loosed or not, use the special tool to connect it if
switch, and keep No.122 wire short in step 2 it is loosed.
connecting with No.408 wire. Observe the b.Find the steering pressure alert switch on the
secondary steering indicator lightens or not. bottom of the cab, pull out its two receptacles,
push the copper connector, connect two copper
Conclusion: together in order to connect No.312 wire to
No.231 wire.
If the result does OK, the secondary steering
indicator of the original instrument system is c.Adjust the digital multimeter to 200 Ω range of
Ω function, one probe contacts with 11 core of
damaged. Send the instrument system back to
the instrument system, another probe contacts
the factory for service. The maintenance should
with 16 core of the instrument system.
be carried out in the clean anti-static room, do
(grounding)
not disassemble the instrument system without
permission.
77
Instrument System
System Fault Test and Service
The digital multimeter reading is 0 Ω . If the result does OK, the steering pressure alert
switch is damaged when the steering system
Conclusion: fault indicator lightens.
If the result doesn't OK, the instrument system is
If the result does OK, the line doesn't have fault,
damaged when the steering system fault
please turn to step 3.
indicator doesn't lighten.
(1) If the result doesn't OK, the line has opern Illustration 2-11 Secondary steering start control
circuit. Check No.312 wire carefully,
logic sequence drawing
especially the receptacle, the round place,
and the active place contacts with the metal
+24VIN TURN ON THE
plate. START SWITCH TURN OFF THE
START SWITCH
STEERING SYSTEM
(2) Check the grounding condition of No.231 FAILURE INDICATOR/ INPUT START FAILURE
Step 2. Test the steering pressure alert switch See above illustration, grounding can be
is damaged or not. considered as low level, +24V as high level. The
first line is the voltage wave shape of the power
a.Connect the receptacle of the instrument supply system. The second line is the voltage
system. wave shape of the steering pressure alert switch
b.Connect two coppers of the steering pressure namely the voltage condition of No.11 core of the
alert switch to each other in order to connect instrument system. The third line is the
No.312 wire to No.231 wire. secondary steering output control voltage
condition namely the voltage condition of No.36
c.Disassemble the interior decoration assembly
core of the instrument system.
and cup mat on the left-rear side of the cab,
observe the electronic centralized controller, find Keep monitoring the instrument system from the
K6 secondary steering relay on the electronic steering pressure alert switch signal. The
centralized controller and pull it out. steering system doesn't build voltage before turn
on the start switch, close the NC contact of the
d.Adjust the digital multimeter to 50V range of
steering pressure alert switch and earthing by
voltage function. Find No.85 and No.86 terminals
outer circuit, the level is low level, as shown in
on the relay socket according to the sign on the
the second line of above illustration.
relay, they are the sockets of No.409 wire and
No.212 wire. Insert red probe into No.86 terminal Turn on the start switch, and start the engine, the
of the relay socket, the black probe into No.85 steering system pressure is built step by step,
terminal. the NC contact of the steering pressure alert
e.Turn on the start switch, observe the steering switch has been pushed open, the signal rises
system fault indicator of the instrument system from low level to high level by the resistance
lightens or not, and observe the digital action inside the instrument system.
multimeter reading.
Test result:
The steering pressure alert switch NC contact c.Prepare one 10m lead, divest the insulation
closes newly and earthing by outer circuit when layer for about 10-20mm of the lead two
operating and running the machine, the steering terminals, one terminal of the lead is connected
system pressure loses due to the fault, the to No.407 wire or the copper connector of
resistance action inside the instrument system is No.183 wire, another is connected to the
counteracted. The signal declines from high level receptacle of the instrument system in the cab.
to low level. The steering system fault indicator
d.Adjust the digital multimeter to 200 Ω range of
lightens on the instrument system.
Ω function, one probe contacts with No.407 wire
CPU inside the instrument system collects the of the instrument system, another probe is
signal condition from the power supply system connected to the lead copper core in the cab.
and the steering pressure alert switch, when the
low level signal of the steering pressure alert Test result:
switch reaches, the secondary steering exports
+24V voltage to drive the secondary steering The digital multimeter reading is 0 Ω .
control relay and then drives the steering motor.
As shown in the third line of above illustration. Conclusion:
The battery power will be consumed rapidly due
If the result does OK, the line doesn't have fault,
to the big work current after the secondary
please turn to step 2.
steering motor starting to work. The work time of
the secondary steering motor is 60s which is If the result doesn't OK, The line has open circuit,
setup by CPU in the instrument system. check No.407 wire carefully, especially the
Therefore, it will stop work automatically after receptacle, the round place, the active place
working for 60s. contacts with the metal plate.
2-M-F Start state indicator fault test Step 2. Replace the instrument system.
Fault phenomenon definition: a.Turn off the start switch, disassemble the
steering column, and replace the old instrument
The start state indicator doesn't lighten when system with a new one.
starting the engine and running the motor. b.Assemble the steering column, turn on the start
Check the start motor according to this service switch, start the engine, observe the start state
manual if the start motor doesn't run. indicator lightens or not.
Step 1. Test the line fault. If the result does OK, the start state indicator of
the original instrument system is damaged. Send
a.Turn off the start switch, disassemble the the old instrument system back to the factory for
steering column, and pull out the receptacle of service. The maintenance should be carried out
the instrument system. Find the receptacle in the in the clean anti-static room, do not disassemble
steering column of the instrument system. the instrument system without permission.
b.Pull No.407 wire connected to No.29 core of
the instrument system slightly by hand, judge its
loose condition, and use the special tool to
connect it if it is loosed.
79
Instrument System
System Fault Test and Service
2-N-F Parking brake low pressure alert c.Adjust the digital multimeter to 200 Ω , one
indicator fault test probe contacts with No.2 core of the instrument
system, another probe is connected to No.16
Falut phenomenon definition: core of the instrument sysem (grounding).
Step 2. Test whether No.300, No.231 wires The service brake low pressure indicator doesn't
have line fault. lighten when the service brake system pressure
is low.
a.Turn off the start switch, disassemble the For the machine stops for a long time, the
steering column, and pull out the receptacle of service brake low pressure indicator doesn't
the instrument system. Find No.300 wire of No.2 lighten when turn on the start switch.
core. Pull No.300 wire connected to No.2 core of
the instrument system slightly by hand, judge it is
loosed or not, use the special tool to connect it if
it is loosed.
b.Keep connecting two coppers of the parking
brake pressure alert switch to each other in order
to connect No.312 wire to No.231 wire.
80
Instrument System
System Fault Test and Service
Step 1. Check the service brake low pressure If the result doesn't OK, the line doesn't have
alert switch is damaged or not. fault, the service brake low pressure alert
indicator inside the original instrument system is
a.Turn off the start switch, and find the service damaged. Send the instrument system back to
brake low pressure alert switch on the pedal the factory for service. The maintenance should
under the cab. Pull out two receptacles, push out be carried out in the clean anti-static room, do
the copper connector, and connect two copper not disassemble the instrument system without
connectors together in order to connect No.303 permission.
wire to No.214 wire.
(1) If the result doesn't OK, the line has open
b.Observe the service brake low pressure alert circuit. Check No.303 wire carefully,
switch lightens or not when turn on the start especially the receptacle, the round place,
switch but don't start the engine. the active place contacts with the metal plate.
Conclusion:
If the result doesn't OK, please turn to step 2. The transmission oil pressure alert indicator
doesn't lighten when turn on the start switch but
Step 2. Test whether No.301, No.229 wires don't start the engine.
have line fault.
Fault test steps:
a.Turn off the start switch, disassemble the
steering column, pull out the receptacle of the Step 1. Test transmission oil pressure alert
instrument system. Find No.301 wire of No.3 switch is damaged or not.
core. Pull No.301 wire connected to No.3 core of
the instrument system slightly by hand, judge its a.Turn off the start switch, find the transmission
loose condition, and use the special tool to oil pressure alert switch under the transmission.
connect it if it is loosed. Pull out two receptacles, push out the copper
b.Keep connecting two copper connectors of the connector, and connect two copper connectors
service brake low pressure alert switch together together in order to connect No.307 wire to
in order to connect No.301 wire to No.229 wire. No.231 wire.
b.Turn on the start switch but don't start the
c.Adjust the digital multimeter to 200 Ω , one
probe contacts with No.3 core of the instrument engine, observe the transmission oil pressure
system, another probe is connected to No.16 alert indicator lightens or not.
core of the instrument sysem (grounding).
Conclusion:
Test result:
If the result does OK, the transmission oil
pressure alert switch is damaged.
The digital multimeter reading is 0 Ω .
If the result doesn't OK, please turn to step 2.
Conclusion:
Step 2. Test whether No.307, No.231 wires
If the result doesn't OK, the line doesn't have have line fault.
fault, the engine oil pressure alert indicator inside
the original instrument system is damaged. Send a.Turn off the start switch, disassemble the
the instrument system back to the factory for steering column, pull out the receptacle of the
service. The maintenance should be carried out instrument system. Find No.307 wire of No.21
in the clean anti-static room, do not disassemble core. Pull No.307 wire connected to No.21 core
the instrument system without permission. of the instrument system slightly by hand, judge
(1) If the result doesn't OK, the line has open its loose condition, and use the special tool to
circuit. Check No.301 wire carefully, connect it if it is loosed.
especially the receptacle, the round place, b.Keep connecting two copper connectors of the
amd the active place contacts with the metal transmission oil pressure alert switch together in
plate. order to connect No.307 wire to No.231 wire.
(2) Check the grounding condition of No.229 c.Adjust the digital multimeter to 200 Ω , one
wire carefully. The grounding resistance probe contacts with No.21 core of the instrument
value is 0 Ω or not. system, another probe is connected to No.16
core of the instrument sysem (grounding).
2-Q-F Transmission oil pressure alert
indicator fault test Test result:
The transmission oil pressure alert indicator The digital multimeter reading is 0 Ω .
doesn't lighten when the transmission oil
pressure is low.
82
Instrument System
System Fault Test and Service
Conclusion: Conclusion:
If the result doesn't OK, the line doesn't have If the result does OK, the engine intake air filter
fault, the engine oil pressure alert indicator inside switch is damaged.
the original instrument system is damaged. Send
the instrument system back to the factory for If the result doesn't OK, please turn to step 2。
service. The maintenance should be carried out
Step 2. Test whether No.310, No.229 wires
in the clean anti-static room, do not disassemble
have line fault.
the instrument system without permission.
(1) If the result doesn't OK, the line has open a.Turn off the start switch, disassemble the
circuit. Check No.307 wire carefully, steering column, and pull out the receptacle of
especially the receptacle, the round place, the instrument system. Find No.310 wire of
the active place contact with the metal plate. No.14 core. Pull No.310 wire connected to No.14
core of the instrument system slightly by hand,
(2) Check the grounding condition of No.231
judge its loose condition, and use the special tool
wire carefully. The grounding resistance
to connect it if it is loosed.
value is 0 Ω or not.
b.Keep connecting two copper connectors of
2-R-F Engine intake air filter alert indicator engine intake air filter alert switch together in
fault test order to connect No.310 wire to No.229 wire.
c.Adjust the digital multimeter to 200 Ω , one
Falut phenomenon definition: probe contacts with No.14 core of the instrument
system, another probe is connected to No.16
The engine intake air filter indicator doesn't core of the instrument sysem (grounding).
lighten when the engine air filter blocks.
When operating the machine, there is serious Test result:
black smoke (not includes the instants of starting
and step on the gas), must stop the machine to The digital multimeter reading is 0 Ω .
check the engine air filter, the engine intake air
filter blocks but the alert indicator doesn't lighten. Conclusion:
Fault test steps: If the result doesn't OK, the line doesn't have
fault, the engine intake air filter alert indicator
Step 1. Test the engine intake air filter alert inside the original instrument system is
switch is damaged or not. damaged. Send the instrument system back to
the factory for service. The maintenance should
a.Turn off the start switch, and find the engine be carried out in the clean anti-static room, do
intake air filter alert switch on the engine air filter. not disassemble the instrument system without
Pull out two receptacles, push out the copper permission.
connector, and connect two copper connectors (1) If the result doesn't OK, the line has open
together in order to connect No.310 wire to circuit. Check No.310 wire carefully,
No.229 wire. especially the receptacle, the round place,
b.Turn on the start switch but don't start the and the active place contacts with the metal
engine, observe the engine intake air filter alert plate.
indicator lightens or not. (2) Check the grounding condition of No.229
wire carefully. The grounding resistance
value is 0 Ω or not.
83
Instrument System
System Fault Test and Service
2-S-F Engine charge indicator fault test If the result doesn't OK, No.800 wire has open
circuit, check No.800 wire carefully, especially
Fault phenomenon definition: the receptacle, the round place, the active place
contact with the metal plate.
The voltage/service meter works normally after
starting the engine, the engine charge indicator 2-T-F Buzzer fault test
doesn't lighten when the service meter works
normally. Fault phenomenon definition:
Check it according to this service manual if the
When any one of the steering system fault
service meter of voltage/service meter doesn't
indicator, engine oil pressure alert indicator,
time.
parking brake low pressure alert indicator and
the service brake low pressure alert indicator
Fault test steps:
lightens, the mute switch is at OFF state (not
mute), the buzzer doesn't beep.
Step 1. Test the voltage of No.800 wire on the
instrument system.
Fault test steps:
a.Turn off the start switch, disassemble the
Step 1. Test the voltage of No.417 wire of the
steering column, and pull out the receptacle of
mute switch.
instrument system. Find No.800 wire of No.24
core. Pull No.800 wire connected to No.24 core
a.Turn off the start switch, use the screwdriver to
of the instrument system slightly by hand, judge
prize the 8-joint pendant switch from the steering
its loose condition, and use the special tool to
column (disassemble the steering column if it
connect it if it is loosed.
can't be prized), find No.417 wire of mute switch
b.Adjust the digital multimeter to 50V range. on the 8-joint pendant switch, the mute switch is
Insert red probe into No.24 core (No.800 wire) of at OFF state (not mute).
the instrument system, the black probe is
b.Adjust the digital multimeter to 50V range.
connected to No.16 core of the instrument sysem
Insert red probe into No.417 wire hole of the
(grounding).
mute switch receptacle, keep contacting with
c.Turn on the start switch and start the engine. copper piece inside No.417 wire. The black
Observe the digital multimeter reading. probe contacts with the metal housing (the place
without paint) of the cab (grounding).
Test result:
c.Turn on the start switch, pull up the parking
brake button, and bserve the digital multimeter
The digital multimeter reading is between 24V
reading.
and 31V.
Test result:
Conclusion:
The digital multimeter reading is between 24V
If the result doesn't OK, the line doesn't have
and 31V.
fault, the engine charge indicator inside the
original instrument system is damaged. Send the
Conclusion:
instrument system back to the factory for service.
The maintenance should be carried out in the
If the result does OK, please turn to step 2.
clean anti-static room, do not disassemble the
instrument system without permission. If the result doesn't OK, the instrument system
has inner fault.
84
Instrument System
System Fault Test and Service
If the result does OK, the buzzer is damaged. 2-V-F Fault test when the instrument system
can't realize the background illumination
If the result doesn't OK, the mute switch is
damaged. Falut phenomenon definition:
2-U-F Fault test when the instrument system
Turn on the position light after turn on the start
can't work
switch, the instrument system background light
doesn't lighten and can not realize the
Falut phenomenon definition:
background illumination.
The guage pin doesn't return to 0, parts of Fault test steps:
indicators don't give alarm after turning on the
start switch. Step 1. Test the voltage of No.416 wire on the
instrument system.
Fault test steps:
a.Turn off the start switch, disassemble the
Step 1. Test the voltage of No.122 wire of the
steering column, find No.416 wire of No.7 core
instrument system.
and No.200 wire of No.6 core, pull them slightly
by hand and judge their loose condition, use the
a.Turn off the start switch, disassemble the
special tool to connect them if they are loosed.
steering column, find No.122 wire of No.9 core
and No.200 wire of No.16 core, pull them slightly b.Prepare two pins, insert one into No.416 wire
by hand and judge their loose condition, use the of No.7 core and make sure the pin contacts with
special tool to connect them if they are loosed. the copper core, insert another pin into No.200
wire of No.16 core and make sure the pin
b.Prepare two pins, insert one into No.122 wire
contacts with the copper core. Please notice that
of No.9 core and make sure the pin contacts with
two pins don't contact with each other.
the wire, insert another pin into No.200 wire of
No.16 core and make sure the pin contacts with c.Turn on the start switch and observe the digital
the copper core. Please notice that two pins don't multimeter reading.
contact with each other.
c.Turn on the start switch and observe the digital
multimeter reading.
85
Instrument System
System Fault Test and Service
Test result:
Conclusion:
Main Components
The idle/diag (diagnostic) inc /dec switch is at 2. Idle/diag (diagnostic)inc /dec switch
idle set function when the diagnostic switch is at
OFF position (see illustration 3-6). This switch is Press the idle/diag (diagnostic) inc/dec switch
a pendant switch contains self-lock, which is (this switch is reset switch) up/down to adjust the
locked at OFF position, and must pull the buckle engine idle when the diagnostic switch is at OFF
if turn it to ON position (see illustration 3-7). This position (see illustration 3-9), and the adjust
design is to prevent the false operation. When range is 600-1200rev. When the diagnostic
the diagnostic switch is at ON position (see switch is at ON position (see the illustration 3-
illustration 3-8). If the engine has fault, the fault 10), if the engine has more than two fauls, press
codes will be displayed through the warn up/down the idle/diag (diagnostic) inc /dec switch
indicator on the panel assembly. to transform the engine fault codes, and the fault
Illustration 3-7 codes will be displayed through the warn
indicator on the panel assembly.
Illustration 3-9
3. Warn Indicator
The warn indicator symbol is WARN. The warn
indicator provides important information of the
operator, and denotes the system faults, which
require the operator to notice these informations
in time. The warn indicator also can describe the
diagnostic fault codes.
If the warn indicator flickers during operation,
please stop the machine immediately, and turn
off the start switch to shut off the engine. Then
turn on the start switch again, turn the start
switch to I position, and read the fault code
according to DIAGNOSTIC ON/OFF SWITCH
section instruction. At last, consult with the
technical service center in time to eliminate the
fault.
The warn indicator is also used as maintenance
warn indicator. The warn indicator will lighten and
the machine needs maintenance when the
service time is arrived at preset time (the default
system maintenance interval is 250 hours). It is
not the fault warning, and no fault code displayed
although the warn indicator lightens.
4. Wait to start indicator
The symbol is WTS. When the operation
temperature that the system tested inside the
machine is lower than 18 ℃ , the machine will
switch on the cold boot secondary device (the
grid heater) automatically for quicker warm-up of
the engine, and the indicator lightens at this time.
The indicator goes out means that the
temperature has reached the desired
requirement, the operator can start the engine
now.
Remark:
System Principle Summary B.Start the start switch, and turn it to I position,
the power supply is on. Every branch fuse in the
control box has voltage, and two-way fuses are
A.Two branches of battery provide power to the related to the electronic diesel engine system
electronic diesel engine system after turning on among them.
the battery disconnect switch.
(a) The voltage arrives at No.160 wire and
(a) The voltage passes No.101 wire and No.161 wire through the electronic fuse,
arrives at 30A fuse inside the electronic and then divided into two branches. One
control box through XZ1 receptacle, then way passes through No.160 wire to the
supplies power to ECU after passing XZ1 receptacle XJ6 and arrives at 9-pin data
receptacle to No.113 wire and reaches diagnostic interface as the power supply
XH7 Deutsh 4-pin connector. of the interface. The other way passes
(b) The voltage passes No.102 wire and through No.161 wire to XH1 and Deutsh
arrives at 150A fuse inside the electronic 50-pin connector then arrives at
control box, then reaches the contact of electronic diesel engine ECU for power
K14 heater through No.103 wire. supply.
92
Electronic Diesel Engine System
System Principle Summary
Fault phenomenon: the engine rev can't be Fault phenomenon: turn on the start switch, 5
increased, the engine keeps idle when indicators should flash firstly then go out in
depressing down the accelerator. normal condition, there are faults if the
indicators, especially the stop indicator, warn
Fault test steps: indicator don't lighten.
Fault test steps:
Step1.
1. Check the wire connection, check No.320
Check the wiring
wire, No.321 wire, No.322 wire, No.323 wire,
1. Check the wire connection, check No.756 No.324 wire and No.704 wire connection
wire, No.757 wire, No.758 wire connection condition from the engine Deutsh 50-pin
condition from engine XH5 Deutsh 50-pin connector to XY5 receptacle of panel
connector to XL3 receptacle, Connect the assembly. Connect the wires again if they
wires again if they have loosened and make have loosened and make sure the
sure the connection reliability connection reliability
2. Test the voltage between No.756 wire and 2. Check the 5A fuse of the start switch power
No.758 wire at XL3 with the voltmeter after inside the control box in the cab, and replace
connecting the wire. The standard voltage is the corresponding fuse if the fuse has
5V. The wire may be off if there isn't voltage. melted.
Step2. 3. Check the indicators. Electrify all indicators,
the indicators are damaged if they don't
Check 5A fuse
lighten, replace the damaged indicators.
1. Check the 5A fuse of the start switch power
inside the control box in the cab, and replace C.Typical fault codes:
the corresponding fuse if the fuse has
melted. Typical fault codes are: 131, 132, 364, and 391;
Step3. 131: Accelerator position sensor circuit -HV
short circuit;
Check the accelerator
132: Accelerator position sensor circuit -LV short
1. Firstly, check whether the voltage is 5V
circuit;
between No.756 wire and No.758 wire at XL3
with the voltmeter? The accelerator maybe invalid when there is
either 131 fault code or 132 fault code.
2. Secondly, check the voltage between No.757
wire and No.758 wire, the normal value 197: The engine cooling water level warning. The
should be among 0.5V-4V along with the engine cooling water level is low, please fill the
change of the accelerator position, the cooling water.
accelerator may be damaged if not.
364: CAN communication error of fuel pump
Step4. control module - abnormal update rate。
Disposal way: Replace the accelerator. Pay 391: The power supply voltage of fuel shut off
attention to the correspondence between the valve is wrong。
wire colour and number of XL3 receptacle when
See <<appendix>> for detailed table of
replacing the accelerator.
electronic diesel engine fault codes
95
Electronic Diesel Engine System
Engine Fault Codes Table
SPEED BACKUP
Function Brief Introduction SENSOR ALARM
OUTPUT
TRANSMISSION
CLG856III wheel loader uses ZF transmission SPEED ELECTRONIC NEUTRAL
SENSOR CONTROL
and axle. The transmission is electro-hydraulic STARTING
OUTPUT
4WG-200. This manual introduces electronic POWER
SHUT OFF
control component of transmission, called the
SPEEDMETER
shift control system. HARNESS
Illustration 4-2 ERGO-II Exterior drawing and principle drawing symbol of shift control lever
Work principle
See above illustration, it is the gear selector the digital multimeter measurement, but it
inner principle drawing; the following illustration doesn't work normally due to the inner contacts
is the micro-switch action connection drawing. damage.
Use the digital multimeter to check the gear
selector fault accroding to above illustration. But
this method is not suitable for checking the
damage condition of micro-switches' contacts
inside the gear selector. It will show no fault by
108
Shift Control System (FULL-AUTOMATIC)
Main Components
Illustration 4-4 ERGO-II gear selector inner 2. Refer to above illustration. Adjust the digital
switch connection drawing multimeter to 200 Ω range of resistance
function. Insert probe into the corresponding
core of lead combinations under the
receptacle of gear selector (the color
delegates the lead color): [RED,YELLOW]、
[RED, PINK], [RED, BROWN], the digital
multimeter reading is 0.
3. Insert one probe of multimeter into the
corresponding core of receptacle red lead,
insert another probe into the corresponding
core (measure [RED, WHITE] combination)
of white lead, the digital multimeter reading is
1. Press F button on the ERGO-II gear
selector by hand, the multimeter reading
turns to 0, but after releasing the button, the
multimeter reading turns back to 1 again.
With the same principle, measure [RED,
YELLOW] combination and press F button,
the multimeter reading changes from "0" →
"1" → "0".
4. Insert one probe of multimeter into the
corresponding core of receptacle red lead,
Generally, ERGO-II gear selector has lock insert another probe into the corresponding
function in order to prevent error operation, core (measure [RED, WHITE] combination)
unlock ERGO-II gear selector firstly when shift of white lead, the digital multimeter reading is
the machine. The unlock is setup by the 1. Press R button on the ERGO-II gear
software, sometimes press KD button long time, selector by hand, the multimeter reading
sometimes press KD button+F button (or R turns to 0, but after releasing the button, the
button) on the gear selector at the same time. multimeter reading turns back to 1 again.
There are different unlock methods for each With the same principle, measure [RED,
machine, the details refer to the machine PINK] combination and press R button, the
operation manual, CLG856III wheel loader multimeter reading changes from "0" → "1"
maybe have not gear selector lock function. → "0".
ERGO-II gear selector fault test 5. Insert one probe of multimeter into the
corresponding core of receptacle red lead,
The inner micro-switches of gear selector are all insert another probe into the corresponding
instant switches. It needs to keep connectiong core (measure [RED, BROWN]
condition manually during measurement. See the combination) of brown lead, the digital
following methods, use the resistance function of multimeter reading is 0. Press N button on
digital multimeter to measure fault, test them if the ERGO-II gear selector by hand, the
doubt that ERGO-II gear selector has fault. This multimeter reading turns to 1, but after
section will introduce the method of fault test by releasing the button, the multimeter reading
using the voltage function of digital multimeter. turns back to 0 again.
6. Insert one probe of multimeter into the 8. Insert one probe of multimeter into the
corresponding core of receptacle red lead, corresponding core of receptacle red lead,
insert another probe into the corresponding insert another probe into the corresponding
core (measure [RED, BLUE] combination) core (measure [RED, PURPLE]
of blue lead, the digital multimeter reading is combination) of purple lead, the digital
1. Press "+"button on the ERGO-II gear multimeter reading is 1. Press KD button on
selector by hand, the multimeter reading the ERGO-II gear selector by hand, the
turns to 0, but after releasing the button, the multimeter reading turns to 0, but after
multimeter reading turns back to 1 again. releasing the button, the multimeter reading
turns back to 1 again.
7. Insert one probe of multimeter into the
corresponding core of receptacle red lead, Most of the ERGO-II gear selectors that passed
insert another probe into the corresponding the above tests successfully are good selectors.
core (measure [RED, ORANGE]
combination) of orange lead, the digital Display
multimeter reading is 1. Press "-" button on
the ERGO-II gear selector by hand, the The display is located on right side of the front
multimeter reading turns to 0, but after panel, which the operator can observe by eye.
releasing the button, the multimeter reading The display is used for display the select gear of
turns back to 1 again. the operator in normal driving, the real gear of
machine driving and driving direction. The
display is also used to show service information
and fault codes when the shift control system
has fault.
The display uses CAN to realize the data
communication.
Illustration 4-5 Display outline and principle drawing symbol
1. Display of the operator select gear 2.Forward driving driection 3.Display of fault codes and real gear
4. Symbol for error in the system 5.Reverse driving direction
110
Shift Control System (FULL-AUTOMATIC)
Main Components
In the display, Left area is composed by upwards The full-auto shift control system machine is
arrow, downwards arrow and four middle bars. assembled with two speed sensors, which are
The upwards arrow lightens, which means the used separately to test the input gear speed and
machine driving direction is forward, and vice the output gear speed of transmission. See
versa. Four middle bars show the operator pre- illustration 4-11 (solenoid and clutch action
select gear, and each bar shows one gear. For drawing) for the specific location. EST-25T
example, the operator pre-select gear is III gear electronic control unit needs these two speeds to
if there are 3 bars lightened at the same time. judge the states of the diesel engine and the real
speed, and analyze the load condition and the
Right area shows service symbols, the shift
speed condition for deciding the real machine
control system has fault when the spanner
gear.
symbol appears, which needs repair.
Illustration 4-7 Speed sensor work principle
The middle area shows the real gear of
drawing
transmission during normal machine operation.
In full-auto shift control system, the selected gear
of transmission lies on the load condition and the
real speed but not the operator pre-select gear.
N shows NEUTRAL gear in this area. NN shows
NO NEUTRAL gear. F+ number shows
FORWARD gear, No.1, 2, 3, 4 show gears. For
example, F3 shows FORWARD III gear. R+
number shows REVERSE gear, No.1, 2, 3, 4
show gears. For example, R3 shows REVERSE
III gear. The middle area shows the fault codes
when the shift control system has fault. Refer to
Function Operation in this section for details.
Work principle
Speed sensor
The speed sensor is installed on the tansmission
Illustration 4-6 Speed sensor outline and housing for testing the output gear rev of the
principle drawing symbol transmission.
The speed sensor is composed by winding,
permanent magnet, and pole. The winding is
wraped around the pole, which is connected to
permanent magnet. The magnetic force line of
magnetic field produced around the permanent
magnet passes through the air gap, the teeth of
1
2 SPEED SENSOR gear, and forms closed magnetic circuit.
Sometimes the magnetic field effects on teeth
gap, sometimes on teeth during the gear rotation
for changing the air gap, and the flux is changing
along with the air gap. The variational flux
induces the proportionable sine signal with rev in
the winding, which was delivered into electronic
control unit for disposal by wiring harness
connection.
111
Shift Control System (FULL-AUTOMATIC)
Main Components
Illustration 4-8 EST-25T Electronic control unit Illustration 4-9 EST-25T Electronic control unit
outline and principle drawing symbol switch drawing
Contrast illustration 4-12 oil circulation diagram The transmission clutch cut-off function is just
4WG-200 with illustration 4-11 solenoid and used at gear I& II, whatever the machine is at
clutch action drawing, through which can get the FORWARD and REVERSE gear. Their actions in
control relationship between the solenoid and the the transmission show: solenoid M3 or M1 is cut
clutch. It is basically that: solenoid M5 controls off when execute clutch cut-off order, namely KV
the clutch K4, M3 controls KV, M1 controls KR, or KR clutch is cut off. Because KV and KR
the solenoid is electrified and the clutch works. clutches are separately the Forward or Reverse
Solenoids M2 and M4 control the clutch K1, K2, clutches, therefore, the performance of the
K3 together. M4 is electrified, M2 isn't electrified, transmission clutch cut-off order is realized by
and K2 clutch works. M2 and M4 are electrified cut-off direction clutch.
together, K1 clutch works. M2 and M4 aren't
electrified, K3 clutch works. Solenoid test
Use the digital multimeter's resistance function to Illustration 5-12 Fixing positions of the
test X9 receptacle (the terminal of shift control components
valve), the resistance values of A-F、B-F、C-F、
D-F、 E-F should be about 85-100 Ω .
Otherwise, the solenoid is damaged.
Function Operation
Display EST-25 electronic control unit Illustration 5-14 Neutral/start interlock relay and
start relay
ERGO-II gear selector
Output speed sensor and input speed sensor
(transmission is not assembled on the machine
in this illustration, input speed sensor just has
fixing position but not assembly)
The following illustration is the component
connection drawing of full-auto control function.
Illustration 4-13 Full-auto shift control system
(the components' positions are not the real fixing
positions in illustration)
The transmission power output is cut off when Illustration 4-17 Transmission clutch ON/OFF
close the transmission clutch ON/OFF switch switch
during the machine brake, which not only can
increase the machine brake performance, but
also can protect the transmission and the power
train. Moreover, the power from the transmission
is used at the hydraulic system and improves the
work efficiency.
The transmission clutch cut-off function is
cancelled when the transmission clutch ON/OFF
switch is at OFF position, the transmission power
output is not cut off when the machine brakes.
EST-25T electronic control unit disposes the
transmission clutch cut-off order. The electronic
control unit executes the shift order by solenoid 1
on the shift control valve when the machine runs
or operates. The transmission clutch cut-off order
is sent and transmited into the electronic unit
when the machine is at F1, F2 or R1, R2, the
electronic control unit will cut off power supply of 1. Lock buckle
solenoid which controls the direction, thereby cut See illustration 4-17, the upper picture shows
off the clutch which controls the direction for that the transmission clutch ON/OFF switch is at
realizing the purpose of cut off the transmission ON position; the underside picture shows that
power output. the transmission clutch ON/OFF switch is at OFF
The transmission clutch cut-off function is just position.
used at F1, F2 or R1, R2. EST-25T electronic In general, the transmission clutch ON/OFF
control unit doesn't execute the transmission switch is at ON position. When running or
clutch cut-off order even if the transmission operating, the transmission clutch ON/OFF is at
clutch ON/OFF switch is at ON position during OFF position. According to above illustration, pull
the brake in order to pretect the running safety the lock buckle downward and press it down at
when the machine is at high speed gear. the same time in order to reach OFF position.
The transmission clutch ON/OFF switch has a
lock buckle to prevent wrong operation. In
general, the switch is locked at ON position. The
switch is at OFF position when driving or
operating the machine.
CAUTION: Do not use the transmission The machine can be started successfully when
clutch cut-off function for operator's safety the operator starts the machine at F1, F2 or R1,
when driving or operating the machine on the R2. EST-25T electronic control unit doesn't
ramp. execute this order when the start speed of the
machine is higher than gear II, but will send out
CAUTION: The transmission clutch cut- gear II starting order. The electronic control unit
off switch should be at ON position when will allow the transmission to execute the
driving or operating the machine on the flat operator's desired gear according to the
ground, otherwise it will affect the brake feedback signals of the speed sensor on the flat
performance, shortening the service life of ground.
brake system and the power train!
4-F Downshift control
The following components are needed for The downshift switch is only active when the
realizing the transmission clutch cut-off function: ERGO-II shift lever is set to second gear. Press
Fuse and release the downshift switch will make the
transmission remain in first gear until the shift
Transmission clutch ON/OFF switch lever is moved; either speed or direction is
EST-25T electronic control unit changed.
4-A-F1 Starting fault test of the In general, EST-25T electronic unit couldn't pass
the self-test, which shows the shift control
machine system has fault. The purpose of the following
steps is to eliminate the faults of the measurable
Fault phenomenon definition components in the system through the digital
multimeter.
The operator turns on the start switch and turns
ERGO-II gear selector to NEUTRAL position, Fault test steps:
then starts the diesel engine when the whole
machine electrifies, but there isn't any respond in
the diesel engine. Consider whether the shift
control system has sent out the Neutral/start
interlock signal firstly.
122
Shift Control System (FULL-AUTOMATIC)
Test and Maintenance of System Faults
Illustration 4-20 EST-25T electronic control unit 3. Refer to the principle drawing, X14 is "+
X1 (35-PIN) receptacle drawing and shift control "short circuit terminal of power supply, X15 is
system lead "-"short circuit terminal of power supply. All
leads that connected to the short circuit
terminals are connected. So No.1, No.2
cores of X1 receptacle are connected to A
core, B core of X12 receptacle, that is
connected to No.170 wire, which is the power
line of shift control system. Therefore, there
is +24V voltage of grounding at No.1, No.2
cores of X1 receptacle. No.18, No.35 cores
of X1 receptacle are " - " short circuit
terminals power supply of shfit control
system. Adjust the digital multimeter to 50V
range of voltage function. Measure [1, 18],
[1, 35], [2, 18], [2, 35] core
combinations of X1 receptacle separately,
Please notice that only insert red probe into
No.1, No.2 cores, black probe into No.18,
No.35 cores.
Test result:
Conclusion:
1. Turn off the start switch, assemble the 3. Connect the black probe to the cab housing
receptacle over again. Turn on the start (grounding). Insert the red probe into B core
switch, and pull out the parking brake button. of X2 receptacle (No.512 wire), and contacts
Measure the condition of ERGO-II gear with inner copper piece. Press F button of
selector in the shift control system according ERGO-II gear selector, the digital multimeter
to the shift control system principle drawing reading is 0. Release F button, the digital
and the following table (refer to illustration 4- multimeter reading is between 24V and 31V.
3). Insert the red probe into A core (No.532 wire)
of X3 receptacle, and contacts with inner
Test ERGO-II gear selector at X2 and X3
copper piece. Press F button again, the
receptacles, " ● " shows high level, " ○ " shows digital multimeter reading is between 24V
low level:
and 31V. Release F button, the digital
VP+ F R N C-S T- T+ KD multimeter reading is 0.
504 512 520 516 532 528 524 536 4. Keep the connection between the black
RD YL PK BR WH OR BL VK probe and cab housing (grounding). Insert
red probe into C core (No.520 wire) of X2
F ● ○ ●
receptacle, and contacts with inner copper
R ● ○ ● piece. Press R button of ERGO-II gear
N ● ○ selector, the digital multimeter reading is 0.
Release R button, the digital multimeter
T+ ● ●
reading is between 24V and 31V. Hold the
T- ● ● black probe, insert red probe into A core
K ● ● (No.532 wire) of X3 receptacle, and contacts
D with the inner copper piece. Press R button
again, the digital multimeter reading is
between 24V and 31V. Release R button, the
2. Adjust the digital multimeter to 50V range of digital multimeter reading is 0.
voltage function. Connect the black probe to 5. Keep the connection between the black
the cab housing (grounding). Insert the red probe and cab housing (grounding). Insert
probe into A core of X2 receptacle (No.504 red probe into D core (No.516 wire) of X2
wire), and contacts with the copper piece in A receptacle, and contacts with inner copper
core. The digital multimeter reading is piece. Press N button of ERGO-II gear
between 24V and 31V. Hold the black probe, selector, the digital multimeter reading is 0.
and insert red probe into B core of X2 Release N button, the digital multimeter
receptacle (No.512 wire), C core (No.520 reading is between 24V and 31V.
WIRE) and D core (No.516 wire) separately,
and contacts with the copper pieces in B, C 6. Keep the connection between the black
and D cores. The digital multimeter reading is probe and cab housing (grounding). Insert
between 24V and 31V. red probe into B core (No.528 wire) of X3
receptacle, and contacts with inner copper
piece. Press T- button of ERGO-II gear
selector, the digital multimeter reading is
between 24V and 31V. Release T- button, the
digital multimeter reading is 0.
125
Shift Control System (FULL-AUTOMATIC)
Test and Maintenance of System Faults
7. Keep the connection between the black Test shift control valve solenoid at X1 receptacle:
probe and cab housing (grounding). Insert
red probe into C core (No.524 wire) of X3 X1 core Resistance Corresponding
receptacle, and contacts with inner copper X9 receptacle
piece. Press T+ button of ERGO-II gear 31-35 85~100 Ω A-F
selector, the digital multimeter reading is
between 24V and 31V. Release T+ button, 33-35 B-F
the digital multimeter reading is 0. 15-35 C-F
8. Keep the connection between the black 32-35 D-F
probe and cab housing (grounding). Insert 14-35 E-F
red probe into D core (No.536 wire) of X3
receptacle, and contacts with inner copper 2. Adjust the digital multimeter to 200 Ω range
piece. Press KD button of ERGO-II gear of Ω function, use the probes positive or
selector, the digital multimeter reading is negative to measure the core combinations
between 24V and 31V. Release KD button, separately in above table [31-35], [33-35],
the digital multimeter reading is 0. [15-35], [32-35], [14-35].
Generally, the self-test of EST-25T electronic The digital multimeter reading is between 85 Ω
control unit couldn't check the faults of ERGO-II and 100 Ω .
gear selector completely. It just can check the
current gear of ERGO-II gear selector before Conclusion:
starting. The instruction in this step can check all
functions of ERGO-II gear selector. Therefore, it If the result does OK, please turn to step6.
is allowed to check the current gear of ERGO-II
If the result doesn't OK, please test as follows:
but not needed to check all gears when dispose
the machine's start fault. It is necessary to check 1. Check whether there is open circuit or any
ERGO-II function completely if there isn't any other fault in the line from shift control valve
fault of the gear after starting the machine. to EST-25T electronic control unit.
If the result does OK, please turn to step5. 2. The inner solenoid of shift control valve is
damaged if the line hasn't fault. The test of 5
If the result doesn't OK, please test as follows:
couples of combinations corresponds with 5
1. Check whether there is open circuit or any solenoids separately in the shift control valve.
other fault in the line from ERGO-II gear Maintain the shift control valve if the test
selector to EST-25T electronic control unit. value of any couple is not in the range of
2. Replace ERGO-II gear selector. measurement.
Step5. Test whether the shift control Step6. Test whether the speed sensor
valve solenoid has fault at X1 of shift control system has fault at X1
receptacle. receptacle.
1. Refer to shift control system principle 1. Refer to shift control system principle
drawing and illustration 4-20. Turn off the drawing and illustration 4-20.
start switch, and remove X1 receptacle.
126
Shift Control System (FULL-AUTOMATIC)
Test and Maintenance of System Faults
X1 core Resistance Corresponding The transmission oil level should in the normal
X10 receptacle range of oil dipstick when the machine is
17-27 920~1120 Ω 1-2 running.
9-34 920~1120 Ω 1-2 Conclusion:
2. Adjust the digital multimeter to 2K Ω range of
Ω function, use the probe positive or HIGH-Drain oil
negative to measure the core combinations LOW-Fill oil
in above table [17-27] and [9-34].
If it is OK, please turn to step2.
Test result: Step2. Test ERGO-II gear selector according to
step4 introduced in 5-A-F1.
The digital multimeter reading is between 920 Ω
and 1120 Ω . Conclusion:
Step1. Disconnect the transmission clutch If the result doesn't OK, the service brake clutch
cut-off signal (the voltage of No.600 wire is 0), cut-off switch or the transmission clutch ON/OFF
judge whether the machine has gear I, II. switch is damaged.
5-A-F5 Fault test of the backup Step2. Test ERGO-II gear selector according
to step4 introduced in 5-A-F1.
alarm when the shift control lever
is at R after starting the machine Conclusion:
Test result::
Conclusion:
EST117 electronic control unit of the shift control The DW-3 shift lever is also available with
sytem receives the outer signals from the gear integrated KD button.
selector, the speed sensor, KD key, disposes For the protection from unintended start off, a
these signals and sends them into the computer Neutral interlock is installed:
to calculate. CPU drives the shift control valve on
the transmission for getting the desired gear by Position "N" - Controller lever blocked in this
output circuit. position
SPEED
SENSOR BACKUP
ALARM
TRANSMISSION
OUTPUT
KD ELECTRONIC
CONTROL
NEUTRAL
POWER
STARTING
SHUT OFF
OUTPUT
HARNESS
SPEEDMETER Work principle
See above illustration, the upper half part is the 3. See the principle drawing, output AD3
gear selector inner principle drawing, the lower (corresponding) → black wire, AD2 → green
half part is the micro-switch action connection wire, AD1 → blue wire, AD7 → purple wire,
drawing. Use the digital multimeter to check the ED1 → red wire, AD6 → gray wire, AD4 →
gear selector fault accroding to above illustration. yellow wire, AD5 → pink wire. The red wire
But this method is not suitable for checking the and the black wire are connected. See the
damage condition of micro-switches' contacts left downside corner in above illustration, F
inside the gear selector. In general, it will show means FORWARD, N means NEUTRAL, R
no fault by the digital multimeter measurement, means REVERSE; see the right downside
but it doesn't work normally due to the inner conrner in above illustration, "1", "2", "3", "4"
contacts damage. mean gears separately. " ● "means
connection. The gear/digital combination
DW-3 gear selector fault test reflects the outer shift signal. For example,
when the operator turn the shift control lever
Using the digital multimeter to check the gear to F1 (FORWARD 1), AD4 is connected
selector fault is a very straight and convenient according to above illustration, AD1, AD3 are
method, the details show as follows: connected. Therefore, AD4, AD1 and AD3
are connected together when the shift control
1. Turn off the start switch, open the steering
lever is at F1. In addition, AD3 and ED1 are
column assembly, and pull out the X2
connected forever.
receptalce connected to DW-3 gear selector
and wiring harness. 4. AD1, AD3, AD6 ED1 outputs are connected
when DW-3 is at I gear of NEUTRAL
2. Adjust the digital multimeter to 200 Ω range position, its inner micro-switch S4 contact is
of resistance function. Inspect the following
closed, S1 normal close contact is closed.
groups when pull one gear of DW-3 gear
The corresponding blue wire, black wire, gray
selector (the following colors show the wire
wire, red wire should be connected, the
colors): [BLACK, GREEN]、 [BLACK, resistance value between each two wires is
BLUE]、 [BLACK, PURPLE]、 [BLACK, 0. Insert two probes of the digital multimeter
RED]、 [BLACK, GRAY]、 [BLACK, separately into the corresponding color cores
YELLOW]、 [BLACK, PINK]、 [GREEN, of combination colors listed in step 2.
BLUE]、 [GREEN, PURPLE]、 [GREEN,
[BLACK, BLUE]、 [BLACK, GRAY]、
RED]、 [GREEN, GRAY]、 [GREEN,
[BLACK, RED]、 [BLUE, RED]、 [BLUE,
YELLOW]、 [GREEN, PINK]、 [BLUE,
GRAY]、 [RED, GRAY ], the digital
PURPLE]、 [BLUE, RED]、 [BLUE, multimeter reading of the above
GRAY]、 [BLUE, YELLOW]、 [BLUE, combinations is 0, and the reading of the
PINK]、 [PURPLE, RED]、 [PURPLE、 other combinations is 1.
GRAY]、 [PURPLE, YELLOW]、 [PURPLE,
PINK]、 [RED, GRAY]、 [RED, YELLOW]、
[RED, PINK]、 [GRAY, YELLOW]、
[GRAY, PINK]。
132
Shift Control System (SEMI-AUTOMATIC)
Main Components
5. AD3, AD6, ED1 outputs are connected 8. AD3, AD1, AD4, ED1 outputs are
when DW-3 is at gear II of NEUTRAL connected when DW-3 is at F1, its inner
position, its inner micro-switch S1 normal micro-switch S4 contact is closed, S1 normal
close contact is closed. The corresponding open contact is closed, S2 normal open
black wire, gray wire, red wire should be contact is closed. The corresponding black
connected, the resistance value between wire, blue wire, yellow wire and red wire
each two wires is 0. Insert two probes of the should be connected, the resistance value
digital multimeter separately into the between each two wires is 0. Insert two
corresponding color cores of combination probes of the digital multimeter separately
colors listed in step 2. [BLACK, GRAY]、 into the corresponding color cores of
[BLACK, RED]、 [RED, GRAY ], the digital combination colors listed in step 2. [BLACK,
multimeter reading of the above BLUE]、 [BLACK, RED]、 [BLACK,
combinations is 0, and the reading of the YELLOW]、 [BLUE, RED], [BLUE,
other combinations is 1. YELLOW], [RED, YELLOW], the digital
multimeter reading of the above
6. AD3, AD2, AD6, ED1 outputs are combinations is 0, and the reading of the
connected when DW-3 is at gear III of
other combinations is 1.
NEUTRAL position, its inner micro-switch S5
contact is closed, S1 normal close contact is 9. AD3, AD4, ED1 outputs are connected
closed. The corresponding black wire, green when DW-3 is at F2, its inner micro-switch S4
wire, gray wire and red wire should be contact is closed, S1 normal open contact is
connected, the resistance value between closed, S2 normal open contact is closed.
each two wires is 0. Insert two probes of the The corresponding black wire, yellow wire
digital multimeter separately into the and red wire should be connected, the
corresponding color cores of combination resistance value between each two wires is
colors listed in step 2. [BLACK, GREEN]、 0. Insert two probes of the digital multimeter
[BLACK, RED]、 [RED, GRAY ] 、 separately into the corresponding color cores
[GREEN, RED]、 [GREEN, GRAY]、 of combination colors listed in step 2.
[RED,GRAY], the digital multimeter reading [BLACK, RED]、 [BLACK, YELLOW]、
of the above combinations is 0, and the [RED, YELLOW], the digital multimeter
reading of the other combinations is 1. reading of the above combinations is 0, and
the reading of the other combinations is 1.
7. AD3, AD2, AD1, AD6, ED1 outputs are
connected when DW-3 is at gear IV of 10. AD3, AD2, AD4, ED1 outputs are
NEUTRAL position, its inner micro-switch S4, connected when DW-3 is at F3, its inner
S5 contact is closed. The corresponding micro-switch S5 contact is closed, S1 normal
black wire, green wire, blue wire, gray wire open contact is closed, S2 normal open
and red wire should be connected, the contact is closed. The corresponding black
resistance value between each two wires is wire, green wire, red wire and yellow wire
0. Insert two probes of the digital multimeter should be connected, the resistance value
separately into the corresponding color cores between each two wires is 0. Insert two
of combination colors listed in step 2. probes of the digital multimeter separately
[BLACK, GREEN]、 [BLACK, BLUE]、 into the corresponding color cores of
[BLACK, RED]、 [BLACK, GRAY]、 combination colors listed in step 2. [BLACK,
[GREEN, BLUE], [GREEN, RED]、 GREEN]、 [BLACK, RED]、 [BLACK,
[GREEN, GRAY]、 [BLUE, RED], [BLUE, YELLOW]、 [GREEN, RED]、 [GREEN,
GRAY], [RED, GRAY], the digital YELLOW]、 [RED, YELLOW], the digital
multimeter reading of the above multimeter reading of the above
combinations is 0, and the reading of the combinations is 0, and the reading of the
other combinations is 1. other combinations is 1.
133
Shift Control System (SEMI-AUTOMATIC)
Main Components
11. AD3, AD2, AD1, AD4, ED1 outputs are 14. AD3, AD2, AD5, ED1 outputs are
connected when DW-3 is at F4, its inner connected when DW-3 is at R3, its inner
micro-switch S4, S5 contacts are closed, S1 micro-switch S5 contact is closed, S1 normal
normal open contact is closed, S2 normal open contact is closed, S3 normal open
open contact is closed. The corresponding contact is closed. The corresponding black
black wire, green wire, blue wire, yellow wire wire, green wire, red wire and pink wire
and red wire should be connected, the should be connected, the resistance value
resistance value between each two wires is between each two wires is 0. Insert two
0. Insert two probes of the digital multimeter probes of the digital multimeter separately
separately into the corresponding color cores into the corresponding color cores of
of combination colors listed in step 2. combination colors listed in step 2. [BLACK,
[BLACK, GREEN]、 [BLACK, BLUE]、 GREEN]、 [BLACK, RED]、 [BLACK,
[BLACK, YELLOW]、 [BLACK, RED]、 PINK]、 [GREEN, RED]、 [GREEN,
[GREEN, BLUE], [GREEN, RED]、 PINK]、 [RED, PINK], the digital multimeter
[GREEN, YELLOW]、 [BLUE, RED], reading of the above combinations is 0, and
[BLUE, YELLOW], [RED, YELLOW], the the reading of the other combinations is 1.
digital multimeter reading of the above
combinations is 0, and the reading of the 15. AD3, AD2, AD1, AD5, ED1 outputs are
connected when DW-3 is at R4, its inner
other combinations is 1.
micro-switch S4, S5 contacts are closed, S1
12. AD3, AD1, AD5, ED1 outputs are normal open contact is closed, S3 normal
connected when DW-3 is at R1, its inner open contact is closed. The corresponding
micro-switch S4 contact is closed, S1 normal black wire, green wire, blue wire, pink wire
open contact is closed, S3 normal open and red wire should be connected, the
contact is closed. The corresponding black resistance value between each two wires is
wire, blue wire, pink wire and red wire should 0. Insert two probes of the digital multimeter
be connected, the resistance value between separately into the corresponding color cores
each two wires is 0. Insert two probes of the of combination colors listed in step 2.
digital multimeter separately into the [BLACK, GREEN]、 [BLACK, BLUE]、
corresponding color cores of combination [BLACK, PINK]、 [BLACK, RED]、
colors listed in step 2. [BLACK, BLUE]、 [GREEN, BLUE], [GREEN, RED]、
[BLACK, PINK]、 [BLACK, RED]、 [BLUE, [GREEN, PINK]、 [BLUE, PINK], [BLUE,
PINK], [BLUE, RED], [PINK, RED], the RED], [RED, PINK], the digital multimeter
digital multimeter reading of the above reading of the above combinations is 0, and
combinations is 0, and the reading of the the reading of the other combinations is 1.
other combinations is 1.
13. AD3, AD5, ED1 outputs are connected
when DW-3 is at R2, its inner micro-switch
S4 contact is closed, S1 normal open contact
is closed, S3 normal open contact is closed.
The corresponding black wire, pink wire and
red wire should be connected, the resistance
value between each two wires is 0. Insert
two probes of the digital multimeter
separately into the corresponding color cores
of combination colors listed in step 2.
[BLACK, PINK]、 [BLACK, RED]、 [PINK,
RED], the digital multimeter reading of the
above combinations is 0, and the reading of
the other combinations is 1.
134
Shift Control System (SEMI-AUTOMATIC)
Main Components
16. Press KD button and hold it which will DW-3 gear selector is good if it can completed
increase AD7 output connection no matter the above tests successfully.
DW-3 is at any position. For example, press
KD button and hold it when DW-3 is at R2, Solenoid group
AD3, AD5, ED1, AD7 outputs are
connected, the corresponding black wire, The shift control valve contains 5 solenoids, M1-
pink wire, red wire and purple wire should be M5, their positions show as above illustration.
connected, the resistance value between The signal from DW-3 gear selector is sent into
each two wires is 0. Insert two probes of the EST117 electronic control unit when the operator
digital multimeter separately into the selects the direction and gear signal, the
corresponding color cores of combination electronic control unit gives off the corresponding
colors listed in step 2. [BLACK, PINK]、 shift signals according the software calculation
[BLACK, RED]、 [PINK, RED]、 [BLACK, and realizes through output the driving voltage to
PURPLE]、 [PINK, PURPLE]、 [RED, solenoid. The purpose of the solenoids is to turn
PURPLE], the digital multimeter reading of on and off the oil flow to the clutches in the
the above combinations is 0, and the reading transmission and realize the transmission shift or
of the other combinations is 1. change direction.
Illustration 5-5 Shift control valve (cutaway view) and principle drawing symbol
135
Shift Control System (SEMI-AUTOMATIC)
Main Components
Contrast illustration 5-7 oil circulation diagram The transmission clutch cut-off function is just
4WG-200 with illustration 5-6 solenoid and clutch used at gear I& II, whatever the machine is at
action drawing, through which can get the control FORWARD and REVERSE gear. Their actions in
relationship between the solenoid and the clutch. the transmission show: solenoid M3 or M1 is cut
It is basically that: solenoid M5 controls the off when execute clutch cut-off order, namely KV
clutch K4, M3 controls KV, M1 controls KR, the or KR clutch is cut off. Because KV and KR
solenoid is electrified and the clutch works. clutches are separately the Forward or Reverse
Solenoids M2 and M4 control the clutch K1, K2, clutches, therefore, the performance of the
K3 together. M4 is electrified, M2 isn't electrified, transmission clutch cut-off order is realized by
and K2 clutch works. M2 and M4 are electrified cut-off direction clutch.
together, K1 clutch works. M2 and M4 aren't
electrified, K3 clutch works. Solenoid test
Use the digital multimeter's resistance function to Illustration 5-9 Output speed sensor work
test X9 receptacle (the terminal of shift control principle drawing
valve), the resistance values of A-F、B-F、C-F、
D-F、E-F should be about 85-100 Ω . Otherwise
the solenoid is damaged.
Output speed sensor
Illustration 5-8 Output speed sensor outline and
principle drawing symbol
3. Turn the sensor back out 1/2 turn(180°in the Illustration 5-10 EST117 Electronic control unit
counterclockwise direction). This sets air gap outline and principle drawing symbol
(L) to 0.5+0.3mm.
4. Measure the distance between the
transmission fixing surface and the sensor
fixing surface, select the suitable washer,
disassemble the speed sensor, and put the
washer on it, then assemble it over again.
Function Operation
DW-3 gear selector is locked at NEUTRAL, The transmission power output is cut off when
which can't be pushed forwards or pulled close the transmission clutch ON/OFF switch
backwards for changing the direction of the during the machine brake, which not only can
machine. increase the machine brake performance, but
also can protect the transmission and the power
Illustration 5-15 Neutral/lock switch on the
steering column (locked) train. Moreover, the power from the transmission
is used at the hydraulic system and improves the
work efficiency.
The transmission clutch cut-off function is
cancelled when the transmission clutch ON/OFF
switch is at OFF position, and the transmission
1 power output is not cut off when the machine
brakes.
EST117 electronic control unit disposes the
transmission clutch cut-off order. The electronic
control unit executes the shift order by solenoid
on the shift control valve when the machine runs
1. The switch is locked or operates. The transmission clutch cut-off order
Illustration 5-16 Neutral/lock switch on the is sent and transmited into the electronic unit
steering column (unlocked) when the machine is at F1, F2 or R1, R2, the
electronic control unit will cut off power supply of
solenoid which controls the direction, thereby cut
off the clutch which controls the direction for
realizing the purpose of cut off the transmission
power output.
2
The transmission clutch cut-off function is just
used at F1, F2 or R1, R2. EST117 electronic
control unit doesn't execute the transmission
clutch cut-off order even if the transmission
clutch ON/OFF switch is at ON position during
the brake in order to pretect the running safety
2. The switch is unlocked when the machine is at high speed gear.
The transmission clutch ON/OFF switch has a
5-D Transmission clutch cut-off lock buckle for preventing accident operation, in
function general, the switch is locked at ON position. The
switch is at OFF position when running or
operating the machine.
The operator can select transmission clutch cut-
off function when the machine runs on the flat
ground.
The transmission clutch cut-off function can be
realized by pressing the transmission clutch ON/
OFF switch inside the cab.
142
Shift Control System (SEMI-AUTOMATIC)
Function Operation
Illustration 5-17 Transmission clutch ON/OFF CAUTION: The transmission clutch cut-
switch off switch should be at ON position when
driving or operating the machine on the flat
ground, otherwise it will affect the brake
performance, shortening the service life of
brake system and the power train!
Test power supply at X1 receptacle: Illustration 5-21 EST117 electronic control unit
X1 (35-PIN) receptacle drawing and shift control
POS PIN WIRE POS PIN system lead connection drawing
X1 1 682 X14 +24V
X1 2 654 X14 +24V
X5 9 612 X14 +24V
X5 10 616 X14 +24V
X1 18 666 X15 -
X1 35 678 X15 -
X5 14 632 X15 -
X5 15 636 X15 -
See above table, it lists the function of X1
receptacle core, which comes from the right
table of the following illustration 5-21, the
comprehension method is the same as the
following right table.
See the following illustration, left side is the
number position of X1 receptacle core, right
side is the lead connection table of shift
control system. For example, "X1 31 430 X9
A" shows that No.430 wire connects No.31
core of X1 receptacle to A core of X9
receptacle. Refer to the principle drawing,
this is the lead from EST117 electronic
control unit to shift control valve solenoid.
148
Shift Control System (SEMI-AUTOMATIC)
Test and Maintenance of System Faults
3. Refer to the principle drawing, X14 is "+ Step4. Test whether DW-3 gear selector of
"short circuit terminal of power supply, X15 is shift control system has fault at X1
"-" short circuit terminal of power supply. All receptacle.
leads that connected to the short circuit
terminals are connected. So No.1, No.2 1. Turn off the start switch, measure the
cores of X1 receptacle are connected to No.9 condition of DW-3 gear selector in the shift
core, No10 core of X5 receptacle, that is control system according to the shift control
connected to No.170 wire, which is the power system principle drawing and illustration 5-
line of shift control system. Therefore, there 21.
is +24V voltage of grounding at No.1, No.2
cores of X1 receptacle. No.18, No.35 cores Check DW-3 gear selector at X1 receptacle, " ●
" shows connection:
of X1 receptacle are " - " short circuit
terminals power supply of shfit control 25 5 8 23 26 29 24 19
system. Adjust the digital multimeter to 50V N1 ● ● ● ●
range of voltage function. Measure [1, 18],
[1, 35], [2, 18], [2, 35] core
N2 ● ● ●
combinations of X1 receptacle separately. N3 ● ● ● ●
Please notice that only insert red probe into N4 ● ● ● ● ●
No.1, No.2 cores, black probe into No.18,
No.35 cores. F1 ● ● ● ●
F2 ● ● ●
Test result: F3 ● ● ● ●
The digital multimeter readomg is between 24V F4 ● ● ● ● ●
and 31V. R1 ● ● ● ●
R2 ● ● ●
Conclusion:
R3 ● ● ● ●
If the result does OK, please turn to step4. R4 ● ● ● ● ●
If the result doesn't OK, please test as follows: KD ● ● ●
1. Check the condition of 7.5A ZFshift fuse, 2. Adjust the digital multimeter to 200 Ω range
replace it if it is melted. If the new fuse still of Ω function, measure the following
melts, please check the short circuit fault. combinations when pulling each gear of DW-
2. Check the short circuit fault from fuse to X5 3 gear selector, [25, 5], [25, 8], [25,
receptacle, X5 receptacle to X1 receptacle if 23], [25, 26], [25, 29], [25, 24], [25,
7.5A ZF shift fuse doesn't melt. 19], [5, 8], [5, 23], [5, 26], [5, 29],
[5, 24], [5, 19], [8, 23], [8, 26], [8,
3. Check the grounding condition of No.666 29], [8, 24], [8, 19], [23, 26], [23,
wire, No.678 wire, No.632 wire, No.636, 29], [23, 24], [23, 19], [26, 29], [26,
No.228 wire of X5 and X1 receptacles. 24], [26, 19], [29, 24], [29, 19], [24,
19], there are 28 couples of combinations.
149
Shift Control System (SEMI-AUTOMATIC)
Test and Maintenance of System Faults
3. Turn DW-3 gear selector to N1, refer to 7. Turn DW-3 gear selector to F1, refer to above
above table, 25, 26, 29, 19 of X1 table, 25, 23, 26, 19 of X1 receptacle are
receptacle are connected each two at N1, connected each two at F1, use the probe
use the probe positive or negative of the positive or negative of the multimeter to
multimeter to measure the resistances of 28 measure the resistances of 28 couples
couples of combinations. [25, 26], [25, combinations. [25, 23], [25, 26], [25,
29], [25, 19], [26, 29], [26, 19], [29, 19], [23, 26], [23, 19], [26, 19], the
19], the digital multimeter reading of the digital multimeter reading of the above
above combinations is 0, and the reading of combinations is 0, and the reading of the
the other combinations is 1. other combinations is 1.
4. Turn DW-3 gear selector to N2, refer to 8. Turn DW-3 gear selector to F2, refer to above
above table, 25, 29, 19 of X1 receptacle table, 25, 23, 19 of X1 receptacle are
are connected each two at N2, use the probe connected each two at F2, use the probe
positive or negative of the multimeter to positive or negative of the multimeter to
measure the resistances of 28 couples of measure the resistances of 28 couples
combinations. [25, 29], [25, 19], [29, combinations. [[25, 23], [25, 19], [23,
19], the digital multimeter reading of the 19], the digital multimeter reading of the
above combinations is 0, and the reading of above combinations is 0, and the reading of
the other combinations is 1. the other combinations is 1.
5. Turn DW-3 gear selector to N3, refer to 9. Turn DW-3 gear selector to F3, refer to above
above table, 25,8,29,19 of X1 receptacle table, 25, 8, 23, 19 of X1 receptacle are
are connected each two at N3, use the probe connected each two at F3, use the probe
positive or negative of the multimeter to positive or negative of the multimeter to
measure the resistances of 28 couples measure the resistances of 28 couples
combinations. [25,8],[25,29],[25,19], combinations. [25,8],[25,23],[25,19],
[8, 29], [8, 19], [29, 19], the digital [8, 23], [8, 19], [23, 19], the digital
multimeter reading of the above multimeter reading of the above
combinations is 0, and the reading of the combinations is 0, and the reading of the
other combinations is 1. other combinations is 1.
6. Turn DW-3 gear selector to N4, refer to 10. Turn DW-3 gear selector to F4, refer to above
above table, 25, 8, 26, 29, 19 of X1 table, 25, 8, 23, 26, 19 of X1 receptacle
receptacle are connected each two at N4, are connected each two at F4, use the probe
use the probe positive or negative of the positive or negative of the multimeter to
multimeter to measure the resistances of 28 measure the resistances of 28 couples
couples combinations. [25, 8], [25, 26], combinations. [25,8],[25,23],[25,26],
[25, 29], [25, 19], [8, 26], [8, 29], [8, [25, 19], [8, 23], [8, 26], [8, 19], [23,
19], [26, 29], [26, 19], [29, 19], the 26], [23, 19], [26, 19], the digital
digital multimeter reading of the above multimeter reading of the above
combinations is 0, and the reading of the combinations is 0, and the reading of the
other combinations is 1. other combinations is 1.
150
Shift Control System (SEMI-AUTOMATIC)
Test and Maintenance of System Faults
11. Turn DW-3 gear selector to R1, refer to 15. Press KD button of DW-3 gear selector and
above table, 25,5,26,19 of X1 receptacle hold it, refer to above table, 25, 24, 19 of
are connected each two at R1, use the probe X1 receptacle are connected each two at KD
positive or negative of the multimeter to function, use the probe positive or negative
measure the resistances of 28 couples of the multimeter to measure the resistances
combinations. [25,5],[25,26],[25,19], of 28 couples combinations. [25, 24], [25,
[5, 26], [5, 19], [26, 19], the digital 19], [24, 19], the digital multimeter reading
multimeter reading of the above of the above combinations is 0, and the
combinations is 0, and the reading of the reading of the other combinations is 1.
other combinations is 1.
Conclusion:
12. Turn DW-3 gear selector to R2, refer to
above table, 25,5,19 of X1 receptacle are Generally, the self-test of EST117 electronic
connected each two at R2, use the probe
control unit couldn't check the faults of DW-3
positive or negative of the multimeter to
gear selector completely. It just can check the
measure the resistances of 28 couples
current gear of DW-3 gear selector before
combinations. [25, 5], [25, 19], [5, 19], starting. The instruction in this step can check all
the digital multimeter reading of the above
functions of DW-3 gear selector. Therefore, it is
combinations is 0, and the reading of the
allowed to check the current gear of DW-3 but
other combinations is 1.
not needed to check all gears when dispose the
13. Turn DW-3 gear selector to R3, refer to machine's start fault. It is necessary to check
above table, 25, 5, 8, 19 of X1 receptacle DW-3 function completely if there isn't any fault
are connected each two at R3, use the probe of the gear after starting the machine.
positive or negative of the multimeter to
If the result does OK, please turn to step5.
measure the resistances of 28 couples
combinations. [25, 5], [25, 8], [25, 19], If the result doesn't OK, please test as follows:
[5, 8], [5, 19], [8, 19], the digital 1. Check whether there is open circuit or any
multimeter reading of the above
other fault in the line from DW-3 gear selector
combinations is 0, and the reading of the
to EST117 electronic control unit.
other combinations is 1.
2. Replace DW-3 gear selector.
14. Turn DW-3 gear selector to R4, refer to
above table, 25, 5, 8, 26, 19 of X1 Step5. Test whether the shift control valve
receptacle are connected each two at R4,
solenoid has fault at X1 receptacle.
use the probe positive or negative of the
multimeter to measure the resistances of 28
1. Refer to shift control system principle
couples combinations. [25, 5], [25, 8], drawing and illustration 5-21.
[25, 26], [25, 19], [5, 8], [5, 26], [5,
19], [8, 26], [8, 19], [26, 19], the digital Test shift control valve solenoid at X1 receptacle:
multimeter reading of the above
X1 core Resistance Corresponding X9
combinations is 0, and the reading of the
receptacle
other combinations is 1.
31-35 85~100 Ω A-F
33-35 B-F
15-35 C-F
32-35 D-F
14-35 E-F
151
Shift Control System (SEMI-AUTOMATIC)
Test and Maintenance of System Faults
If the result doesn't OK, please test as follows: Step2. Turn the transmission clutch ON/OFF
switch to ON position, observe whether the
1. Check whether there is open circuit or any
indicator on the panel is going out.
fault in the line from DW-3 gear selector to
EST117 electronic control unit.
1. Turn on the start switch, don't start the diesel
2. Replace DW-3 gear selector. engine, and turn the transmission clutch ON/
OFF switch to ON position.
5-A-F3 Fault test of the machine without
I, II gear after starting 2. Insert the parking brake clutch cut-off switch
receptacle over again.
Fault phenomenon definition:
The machine couldn't be started when the shift Test result::
control lever is at F1/F2 or R1/R2 after starting
the diesel engine. Observe whether the indicator on the panel is
going out.
Fault test steps:
Conclusion:
Step1. Disconnect the transmission clutch
cut-off signal, judge whether the machine has If the result does OK, the parking brake clutch
gear I, II. cut-off switch is damaged.
1. Turn the transmission clutch ON/OFF switch If the result doesn't OK, the service brake clutch
to OFF position, remove No.600 wire cut-off switch or the transmission clutch ON/OFF
receptacle from the parking brake clutch cut- switch is damaged.
off switch. Turn on the start switch and turn
Step3. Pull out the parking brake button, and
DW-3 gear selector to NEUTRAL position.
press down. The clutch cut-off indicator on
Press down the parking brake switch for
the panel will lighten and then go out.
releasing the parking brake. Observe
whether the clutch cut-off indicator on the
panel is going out. 1. Turn on the start switch, don't start the diesel
engine, pull out and press down the parking
2. Start the diesel engine at I, II gear. Judge brake button.
whether the machine can start normally.
2. Insert the receptacle of parking brake clutch
cut-off switch over again.
Test result::
The machine starts when the indicator goes out. Test result::
Test result::
3. Parking brake clutch cut-off switch: this Illustration 6-5 Service brake clutch cut-off switch
switch consists of two contacts, one is normal installation location
open, another is normal close, three
terminals, and the middle terminal is the
common terminal of these two contacts. The
normal close contact is off, the normal open
contact is on when the pressure is higher
than 11.5MPva; the normal close contact is
on, the normal open contact is off when the
pressure is lower than11.5MPva.
Illustration 6-4 Parking brake clutch ON/OFF
switch installation location
System principle:
1. Turn on the start switch, 5A fuse of parking
brake electrifies and supplies power to
No.136 wire; 7.5A fuse of shift control lever
electrifies and supplies power to No.170 wire.
156
Parking Brake and Transmission Clutch Cut-off System
Main Components
2. Pull out the parking brake switch, No.170 NOTICE: Understand the shift control system
wire and No.600 wire are connected, 24V rules firstly, viz No.600 wire is the clutch cut-
voltage signal supplies power to No.600 wire off signal wire of shift control system. When
after passes from No.170 wire to No.11 coil of No.600 wire inputs high level to control unit
XA1 receptacle, and reaches parking brake EST-25 of shift control system, the shift
switch. No.600 wire high level signal is control lever is at 1st, 2nd gear, the
inputted to shift control unit EST-25, thereby transmission clutch comes away, no power
cut-off the power output of transmission gear output, the transmission is at NEUTRAL.
I, and gear Ⅱ . At this time, No.600 wire high
level signal is inputted into the gauge, the
clutch cut-off indicator of the gauge lightens.
3. Press the parking brake switch, No.136 wire
and No.478 wire are connected. If the
pressure of the parking brake clutch cut-off
switch is lower than 11.5Mpa, its normal
close contact is on (No.478 wire and No.600
wire are connected), 24V signal is inputted to
the control unit EST-25T through No.600 wire
at X5 receptacle, thereby cut-off the power
output of transmission gear I, and gear Ⅱ . At
this time, No.486 wire hasn't electricity, the
parking brake solenoid doesn't work, and the
machine is at parking brake state. If the
pressure of the parking brake clutch cut-off
switch is higher than 11.5Mpa, its normal
open contact is on (No.478 wire and No.486
wire are connected ), No.486 wire electrifies,
the parking brake solenoid works and the
parking brake is released; at the same time,
No.600 wire hasn't electricity and the
transmission power outputs normally.
4. The service brake clutch cut-off switch
contact is closed when depress the brake.
No.170 wire and No.602 wire are connected,
No.602 wire electrifies. At this time, No.600
wire electrifies and inputs power to control
unit by receptacle X5 if the transmission
clutch ON/OF pendant switch is closed. If the
transmission clutch ON/OFF pendant switch
is disconnected, No.600 wire hasn't
electricity and transmission power outputs
normally.
157
Parking Brake and Transmission Clutch Cut-off System
System Fault Test and Service
2. Please turn to step 2 if the voltage is between Step 3. Test whether the parking brake button
24V and 31V. is good.
3. If the voltage is 0, please refer to
1. Turn off the start switch, pull out the parking
transmission system service manual to
brake button, use the resistance function of
eliminate faults; or refer to shift control
multimeter to measure the resistance of the
system section to eliminate faults.
parking brake button normal open contacts
(two contacts connected to No.136 wire and
Step 2. Test whether the parking brake clutch
cut-off switch is god. No.478 wire), the resistance value should be
infinity; measure the resistance of normal
close contacts (two contacts connected to
1. Turn on the start switch, and press the
No.170 wire and No.600 wire), the resistance
parking brake button after the engine starting
value should be 0.
for 30 seconds, pull out No.600 wire from the
parking brake clutch cut-off switch. If the 2. press the parking brake button, use the
clutch cut-off indicator is still on, so the resistance function of multimeter to measure
parking brake clutch cut-off switch hasn't the resistance of parking brake button normal
problem; if the clutch cut-off indicator is off, open contact, the resistance should be 0,
please check the parking brake clutch cut-off measure the normal close contact resistance,
switch is damaged or not. the resistance value should be infinity.
2. Turn on the start switch, press the parking 3. Please turn to step 4 if the test resistance
brake button after the engine starting for 30 value meets the demand.
seconds, pull out No.600 wire and No.478
4. If the test resistance value can't meet the
wire from the parking brake clutch cut-off
demand, the parking brake button is
switch, use the resistance function of
damaged, please replace it, and finish the
multimeter to measure parking brake clutch
test; but if the fault still exists, please turn to
cut-off switch normal close contact (two
step 4.
contacts connected to No.478 wire and
No.600 wire formerly), if the resistance is 0,
Step 4. Test whether the service brake clutch
use pressure gauge to check whether the cut-off switch is good.
pressure of the parking brake clutch cut-off
switch is higher than 11.5MPa. The parking
1. Use the resistance function of multimeter to
brake clutch cut-off switch is damaged if it is,
measure the contact resistance of service
please replace the parking brake clutch cut-
brake clutch cut-off switch, the resistance
off switch, and finish checking if the fault is
value should be infinity.
repaired. Check the brake system faults if the
pressure is lower than 11.5MPa, please refer 2. If the resistance is 0, the service brake clutch
to the brake system section in the service cut-off switch is damaged, please replace it,
manual. Please turn to step 3 if the fault still stop checking if the faults are repaired; but if
exists. the fault still exists, please turn to step 5.
3. If the resistance is infinity, please turn to step
5.
Step 5. Test whether No.600 wire is short cut-off switch, use 200V voltage function of
circuit to power supply multimeter to measure whether the
grounding voltage of No.600 wire at X5
1. Turn on the start switch, don't start the receptacle is between 24V and 26V.
engine, pull up the parking brake button, pull
out No.600 wire from parking brake clutch
159
Parking Brake and Transmission Clutch Cut-off System
System Fault Test and Service
Step 4. Test whether the parking brake clutch 4. The parking brake button is damaged if the
cut-off switch is good resistance value can't meet the demand,
please replace it, and stop checking if the
1. Turn on the start switch, press the parking faults are repaired. Please turn to step 6 if the
brake button after the engine starting for 30 fault still exists.
seconds, remove No.486 wire and No.478
wire form the parking brake clutch cut-off Step 6. check whether the wiring is
switch, use the resistance function of disconnected?
multimeter to measure the normal open
contact resistance of the parking brake clutch 1. Check the resistance value of No.486 wire is
cut-off switch (two contacts connected to 0 or not by 3m lead from the parking brake
No.478 wire and No.486 wire). clutch cut-off switch to parking brake
solenoid, it is normal if the resistance value is
2. If the resistance is infinity, check whether the
0. Check No.486 wire carefully for abrasion if
pressure of the parking brake clutch cut-off
the resistance value is infinity, or check the
switch is higher than 11.5Mpa by the
connecting condition of XH2 receptacle,
pressure meter, the parking brake clutch cut-
repair the wiring.
off switch is damaged if the pressure is
higher than 11.5MPa, please replace it, and 2. Check the resistance value of No.478 wire is
stop checking if the faults are repaired. 0 or not by 3m lead from the parking brake
Please turn to step 4 if the fault still exists. clutch cut-off switch to parking brake button,
Check the brake system faults if the pressure it is normal if the resistance value is 0. Check
is lower than 11.5MPa, please refer to No.478 wire carefully for abrasion if the
BRAKE SYSTEM section service manual. resistance value is infinity, or check the
connecting condition of XH2 receptacle,
3. Please turn to step 5 if the resistance value is
repair the wiring.
0.
3. Check the resistance value of No.136 wire is
Step 5. Test whether the parking brake clutch 0 or not by 3m lead from 5A fuse of parking
cut-off switch is good condition brake to parking brake button, it is normal if
the resistance value is 0. Check No.136 wire
1. Turn off the start switch, pull up the parking carefully for abrasion if the resistance value
brake switch, use the resistance function of is infinity, or check the connecting condition
multimeter to measure the resistance of the of XA1、 XK4 receptacle, repair the wiring.
parking brake switch normal open contacts Stop checking if the faults are repaired.
(two contacts connected to No.136 wire and
No. 478 wire), the resistance value should be
infinity; measure the resistance of the normal
close contacts (two contacts connected to
No.170 wire and No.600 wire), the resistance
value is 0.
2. Press the parking brake button, use the
resistance function of the multimeter to
measure the resistance of the parking brake
button normal open contact, the resistance
value should be 0, the resistance value of the
normal close contact should be infinity
3. Please turn to step 6 if the resistance value
meets the demand.
161
Lights
Main Components
The combination light fault test steps (a) When the wiper is at O, use a probe of
the digital multimeter to connect the
The combination switch is composed by the corresponding copper of BR/WH wire,
inner separate switches, so can use the another probe connected to the
multimeter resistance function to check the corresponding copper of RD/BK wire, the
combination switch. This method is not available digital multimeter reading is 0. use two
for the switch with some damaged contacts, this probes to contact the corresponding
kind of switches look like normal but can't use coppers of the following each wire colour
when connecting to the circuit. This section won't group separately [BU, BK], [BU, BR/
introduce this question due to its low occurrence WH], [RD/BK,BK], [GN, BK], [GN, BR/
frequency, please replace it with a new WH], the multimeter reading is 1.
combination switch if it has such faults. This
(b) Turn the wiper to J, use a probe of the
section will just introduce the general test
multimeter to contact GN wire, another
methods.
probe contacts with BK wire, the
Replace with a new combination switch multimeter reading is 0. Then contact a
assembly when the combination switch is probe with the corresponding copper of
damaged, Liugong doesn't approve to repair the RR/WH wire, another probe contacts with
combination switch because the assembly of the the corresponding copper of RD/BK wire,
combination switch needs the special technics the multimeter reading is 0. Use two
guarantee. probes to contact the corresponding
coppers of the following each wire colour
Judgement steps of whether the combination
switch is damaged: group separately [BU, BK], [BU, BR/
WH], [RD/BK, BK], [GN, BR/WH], the
1. Adjust the digital multimeter to 200 Ω range multimeter reading is 1.
of Ω function. (c) Turn the wiper to I, use a probe of the
2. Open the steering column assembly, and multimeter to contact RD/BK wire,
disassemble the combination switch from the another probe contacts with BK wire, the
steering column and pull out its receptacle multimeter reading is 0. Use two probes
from the wiring harness. Use either the to contact the corresponding coppers of
positive or negative terminal of the probe, the the following each wire colour group
measure position of the digital multimeter is separately [BU, BK], [BU, BR/WH],
the copper terminal of the combination switch [RD/BK,BR/WH],[GN,BK],[GN,BR/
receptacle. Distinguish from the wiring color WH], the multimeter reading is 1.
because there isn't definition about the
(d) Turn the wiper to II, use a probe of the
receptacle core numbers of the combination
multimeter to contact BU wire, another
switch on the combinantion switch principle
probe contacts with BK wire, the
drawing.
multimeter reading is 0, use two probes
3. Wiper function measurement: to contact the corresponding coppers of
the following each wire colour group
separately [BU,BR/WH],[RD/BK,BK],
[RD/BK,BR/WH],[GN,BK],[GN,BR/
WH], the multimeter reading is 1. Turn the
wiper to O position after measuring.
165
Lights
Main Components
4. Horn function measurement: press the horn 7. Front floodlight function measurement: use
and hold it. The horn switch is a reposition the probes of the digital multimeter to contact
switch, it will reposition after releasing. Keep the corresponding coppers of the following
this switch at PRESS position when wire colour groups [WH/BK, YL] or [WH/
measuring, can't let it reposition, which needs BK, WH], the multimeter reading of one
another person to help. Use a probe of the group is 0, the other group is 1. Pull the
digital multimeter to contact the switch one time along with the installation
corresponding copper of BK wire, the direction of the combination switch, the
multimeter reading is 0, but its reading is 1 multimeter reading changes from 0 to 1 or
after releasing. changes from 1 to 0.
5. Front window washer function measurement: The combination switch is good if it can complete
see the instruction, push the front window above steps. In addition, it is not necessary to
washer and hold it, refer to step 4, this switch operate according to above steps when check,
is a reposition switch. Keep it at washing check the corresponding functions firstly if doubt
position when measuring. Use a probe of the that some functions have problems.
digital multimeter to contact the
corresponding copper of GY wire, another
Brake light switch
probe contacts with the corresponding Illustration 7-8 Brake light swigch and principle
copper of BK wire, the multimeter reading is drawing symbol
0, and the reading is 1 after releasing.
Replenish washing liquid in time after
measuring.
6. Turn signal measurement:
(a) Push the combination switch handle
forwards. Use a probe of the digital
multimeter to contact the corresponding The brake switch is a pressure switch, which is
copper of BL/WH wire, another probe fixed inside the brake valve, the brake oil line
contacts with the corresponding copper of filling oil when the operator depressing down the
BK/WH/GN wire, the multimeter reading pedal, the oil pressure increases. When the
is 0, and its reading is 1 when turn the pressure reaches the action pressure of the
combination switch to NUEUTRAL pressure switch, the normal open contacts of the
position. pressure switch will close and connect the circuit
(b) Push the combination switch handle of the contacts.
backwards. Use a probe of the digital The brake light switch operation value is 0.5MPa,
multimeter to contact the corresponding and the contact state is ON.
copper of BK/BR wire, another probe
contacts with the corresponding copper of NOTICE
BK/WH/GN wire, the multimeter reading
is 0, and its reading is 1 when turn the Make sure the cleanness of the screw thread
combination switch to NEUTRAL hole before install the pressure switch.
position.
166
Lights
Main Components
Brake light switch falut test method Illustration 7-9 Backup alarm and principle
drawing symbol
The brake switch is a pressure switch, the switch
can operate only connecting it into the medium
loop and let the medium pressure reach the
operation pressure, so it is not available to judge
the pressure switch condition according to the
usual measurement by the resistance.
The brake light doesn't lighten when the operator
depresses down the brake pedal. If the brake
switch has fault, it is not necessary to
disassemble the brake switch from the barke
valve, just need to simulate its action state. The
details as follows: The backup alarm is an intermittent beep buzzer,
1. Turn DW-3 gear selector to NEUTRAL it works together with the backup light when the
position, pull the parking brake button, and operator reverses the machine.
disassemble two receptacles of the brake
light from the swich, connect their coppers Backup alarm fault test method
together. Simulate the open operation of the
brake light switch. The backup alarm is a buzzer, this buzzer is
controlled by the inner electrical wire, so can't
2. Turn on the start switch, the brake switch is use the digital multimeter simply to measure the
damaged if the brake light is lightened, the outer characteristic from the receptacle of the
brake light line doesn't has fault. If the brake backup alarm.
light still not be lightened, the loop of the
brake light has fault, which is not related to The backup light lights but the backup alarm
the brake light switch. doesn't sound when turn the shift control lever to
REVERSE gear, the general test methods as
CAUTION: The above operation is only follows:
for the test of the diesel engine at close state. 1. Turn DW-3 gear selector to NEUTRAL
Resume rapidly once finishing the test. Never position, pull up the parking brake button,
do these operations when the machine is turn on the start switch and start the diesel
running or working, otherwise it will threat engine, turn the shift control lever to R1 gear.
the machine operation safety.
2. Adjust the digital multimeter to voltage
Backup alarm function (50V). Open the left-rear position
light- chimney, and pull out the backup alarm
receptacle XI4. Use two probes of the digital
multimeter to measure the voltage between
two coppers of the receptacle of the harness
terminal (not the backup alarm terminal), the
multimeter reading is between 24V and 31V.
The backup alarm is damaged if the multimeter
reading is the same to step 2, and need to
replace the backup alarm. If the multimeter
reading is not in this range, please check the
backup alarm lines for other problems.
167
Lights
Main Components
The flash relay rated load is 40-130W, the See above illustration, work light switch, rear
flashing frequency is 60-120 time/min; when the floodlight switch, hazard flasher switch are the
load changes (decreases), the flashing same with the pendant switch. The work light
frequency increases but doesn't exceed 140time/ and the rear floodlight switch use the principle in
min. illustration 1. The hazard flasher switch uses the
principle in illustration 2. They all are the double-
The flash relay determines the flashing position switches, and hold at ON position.
frequency of the turn signal light, when the main
turn signal light has fault, the flashing frequency If the back light inside the pendant switch is
of other turn signal lights will increase due to the damaged, disassemble it from the pendant
ralay's effect. switch and replace it, shown as below:
Illustration 7-12 Pendant switch assembly
Flash relay fault test method
1. Take out the pendant switch group from the The position light & front floodlight switch is 3-
switch hole, and don't damage the buckle of position pendant switch, which hold at ON
the compositive switch groove. Pull out WH position.
8-core receptacle on the back of the pendant
switch, and let the copper on the back of the Position light & front floodlight switch fault
switch expose. test steps
2. Adjust the digital multimeter to Ω function 1. Take out the 8-joijn pendant switch group
(200 Ω ). from the switch hole, and don't damage the
3. Hold the pendant switch at OFF position, use buckle of the compositive switch groove. Pull
either the positive or negative of the probe of out WH 8-core receptacle on the back of the
the digital multimeter to measure [1, 5] pendant switch, and let the copper on back of
copper combination on the back of the the switch expose.
pendant switch, and need to measure [2, 6]
copper combination if measure the hazard 2. Adjust the digital multimeter to Ω function
flasher switch. The digital multimeter reading (200 Ω ).
is 1. 3. Hold the pendant switch at OFF position, use
either the positive or negative of the probe of
4. Hold the pendant switch at ON position, use
either the positive or negative of the probe of the digital multimeter to measure [1,3],[2,
6], [2, 8] copper combinations on the back
the digital multimeter to measure [1, 5] of the pendant switch. The digital multimeter
copper combination on the back of the
reading is 1.
pendant switch, and need to measure [2, 6]
copper combination if measure the hazard 4. Hold the pendant switch at ON position, use
flasher switch. The digital multimeter reading either the positive or negative of the probe of
is 0. the digital multimeter to measure [2,6],[2,
The pendant switch is normal if it can complete 8], [1, 3] copper combinations on the back
of the pendant switch. The digital multimeter
above testing, otherwise the pendant switch is
damaged. reading of [2, 6], [2, 8] combinations is 0.
The digital multimeter reading of [1, 3]
Position light & front floodlight switch combination is 1.
Illustration 7-13 Position light & front floodlight 5. Hold the pendant switch at ON position, use
switch and principle drawing symbol either the positive or negative of the probe of
the digital multimeter to measure [2,6],[2,
8], [1, 3] copper combinations on the back
of the pendant switch. The digital multimeter
reading is 0.
The position light & front floodlight switch is
normal if it can complete above testing,
otherwise the position light & front floodlight
switch is damaged.
Function Operation
Operation steps:
Operation steps:
Operation steps:
The following electronic components are needed 7-F Rear floodlight operation
for realizing the work light operation.
● Fuse The following electronic components are needed
for realizing the work light operation.
● Position light & front flood light switch
● Fuse
● Work light switch
● Position light & front flood light switch
● Work light
● Read flood light switch
● K9 work light relay
● K7 read flood relay
172
Lights
Function Operation
Operation steps:
Illustration 7-21 Brake light component position Illustration 7-22 Backup light component position
(the demonstration machine is CLG856III with 8- (the demonstration machine is CLG856III of
bar front frame) semi-auto control)
Operation steps:
The professional service personnel can test Step 1. Test whether 10A dome light fuse
according to the judgement steps in the flow melts.
chart (if has).
a.Open the electronic control box, find the dome
7-A-F Dome light fault test light fuse according to its nameplate indication
and check its melting condition.
Illustration 7-23 principle drawing 7-A
Conclusion:
See above illustration, it is dome light line Step 2. Test the dome light bulbs.
principle drawing. The dome light switch is
located on the dome light. When turn on the a.Open the dome light chimney, and notice that
dome light, it doesn't lighten, please test it the dome light has two bulbs, left/right each.
according to the test steps and the flow chart. Check the dome light bulb is damaged or not.
Illustration 7-24 Dome light fault test flow chart 7- Conclusion:
A-F
The bulb has fault, please replace the bulb.
The bulb is good, please turn to step 3.
Test result:
Conclusion: Conclusion:
If the result does OK, replace the dome light If the result doesn't OK, please eliminate the
assembly or open it for service. relative line fault.
If the result doesn't OK, please turn to step 4.
Step 6. Test the dome light line
Step 4. Test the ground wire of dome light for
fastness a.Adjust the digital multimeter to Ω function (200
Ω range).
a.Adjust the digital multimeter to Ω function (200 b.Turn the disconnect switch and the start switch
Ω range). to 0 gear.
b.Turn the disconnect switch and start switch to I c.Disconnect XD8, XE4, XK5 receptacles in turn
gear (turn on the start switch). according to the incidental receptacle position
distributing drawing of this manual.
c.Check the groungind resistance of XE2-5 core,
XK6-1 core, and XE3-1 core according to the d.Check the grounding resistance of No.1 core
incidental receptacle position distributing drawing and No.2 core of XD8 receptacle, XE4-4 core,
of this manual. XK5-3 core, and XA1-13 core.
Conclusion: Conclusion:
If the result does OK, please turn to step 5. If the result does OK, please replace the dome
light or eliminate the short circuit fault inside the
If the result doesn't OK, please eliminate the
dome light.
ground wire fault.
If the result doesn't OK, please eliminate the
Step 5. Test the dome light line short circuit fault of relative lines.
Test result:
Illustration 7-25 Front floodlight, turn light, position light, work light, rear floodlight principle drawing1
177
Lights
System Fault Test and Service
Illustration 7-25 Front floodlight, turn light, position light, work light, rear floodlight principle drawing2
The red line is front floodlight current access, the The fault test methods of each light in the light
green line is work light current access, the blue group are very similar. This section will describe
line is rear floodlight current access, the yellow the principles of various lights in detail, and list
line is position light is position light current the flow chart as the reference to fault test, but
access, the purple line is turn light current not describe the fault test steps again. The
access, the ground line that current passed specific test steps are similar to those introduced
through doesn't mark any sign. in dome light section, please refer to that section.
178
Lights
System Fault Test and Service
7-B-F Front floodlight work principle Illustration 7-26 Front floodlight fault test flow
description chart 7-B-F
3. Push the steering column swich backwards, Illustration 7-27 Turn light fault test flow chart 7-
No.428 wire connects No.404 wire by inner C-F1
contacts of the steering column switch when
turn the machine right, +24V supplies power
to the right-front turn light filament after
passing through No.404 wire and XY2 →
XQ8 → XQ2 receptacles, then to ground by
the filament; the other way reaches te right-
rear turn light filament after passing through
XY4 → XI3 receptacles and final passes the
filament to ground, the right-fornt turn light
and the right-rear turn light lighten. At the
same time, another way enters into the panel
system, the right turn signal indicator on the
panel will lighten. The machine is turning
right.
4. The operator will turn on the parking light
switch when the machine needs emergency
parking, No.428 wire connects No.404 wire
and No.405 wire together by the inner
contacts of the parking brake switch, +24V
supplies power to the left-front turn light, the
left-rear turn light and the left turn signal
indicator on the panel by No.405 wire; also
supplies power to the right-front turn light, the
right-rear turn light and the right turn signal
indicator on the panel by No.404 wire. The
above lights are all lightened.
The turn light can't be lightened when turn on the
turn light switch or hazard flasher switch, please
check the fault according to the flow chart.
180
Lights
System Fault Test and Service
Illustration 7-28 hazard flasher fault test flow 3. +24V power supply is divided into 6 ways
chart 7-C-F2 after No.416 wire electrifies, one way passing
XY2 → XQ8 to XQ1 and XQ6, the front
position light of left/right front combination
light will lighten. One way passing XY4 to XI2
and XI6, the rear position light of left/right
rear combination light will lighten. One way
enters into instrument system and supplies
the background illumination to instrument.
One way supplies power to the backboard
diode of each pendant switch for realizing
background illumination of the pendant
switch. One way enters into work light switch
and becomes the switch power supply. One
way enters into the rear floodlight switch and
becomes the switch power supply.
Press the position light &front floodlight switch to
position light position, the position light can't be
lightened, please check the fault according to the
flow chart.
Illustration 7-29 Position light fault test flow chart 2. Press the work light switch, No.416 Wire
7-D-F Connects No.415 Wire, +24V power supply
passing No.415 wire → XY2 → XA5 → work
light relay, the relay works, its normal open
contacts close. No.131 power supply wire
from 20A fuse passing the close contacts of
the work light relay and connects with No.482
wire, then reaches XD1, XD2, XD3, XD4 by
XA5, XK6 XE3 receptacles. Four work lights
on the top of the cab electrify and realize
illumination.
The work light can't be lightened when turn on
the work light switch, please check the fault
according to the flow chart.
Illustration 7-30 Work light fault test flow chart 7- 7-F-F Rear floodlight fault test
E-F
7-F-F Rear floodlight work principle
description
Illustration 7-31 Rear floodlight fault test flow 7-G-F Rotating beacon fault test
chart 7-F-F
Illustration 7-32 Principle drawing 7-G
7-H-F Brake light work principle description 3. The normal open contacts of the brake light
close, No.155 wire connects No.481 wire,
1. See the principle drawing, the blue line is supplies power to the brake light relay by
brake light control loop, the red line is brake XA5 receptacle, the brake light relay works,
light loop. its normal open contacts close, No.155 wire
connects No.479 wire. +24V power supply
2. No.155 wire of the brake light power supply
provides power to two brake lights after
wire reaches the brake light relay contact
terminal from 10A fuse, passing XA2 passing through No.479 wire → XA5 → XH2
and reaches XI2 and XI6. The left/right brake
receptacle to brake light switch. The brake
lights are lightened at the same time.
light switch is installed on the brake valve,
the brake light normal open contacts close The brake light can't be lightened when the
when the operator depresses down the brake operator depresses down the brake pedal,
pedal. please check the fault according to the flow
chart.
186
Lights
System Fault Test and Service
CAUTION: The short connection operation of the brake light switch receptacle is only for the
test of the diesel engine at close state. Resume rapidly once finishing the test. Never do these
operations when the machine is running or working, otherwise it will threat the machine
operation safety.
187
Lights
System Fault Test and Service
7-I-F Backup light work principle description into XJ3 voltage/service meter and
instrument assembly as L terminal of the
1. See the purple line in the principle drawing, alternator The positive of the charging
No.171 wire exports +24V power supply from indicator in the instrument assembly
10A fuse after turn on the start switch, connects with the power supply of the
passing the backup alarm control relay and instrument assembly, the negative connects
No.800 wire → XA5 receptacle → XH2 with the ground by No.800 wire, then the
receptacle → L terminal of the alternator then indicator is lightened.
to ground by inner circuit of the alternator.
The backup alarm control relay works, its
normal close contacts is disconnected, cut-
off the connection between No.350 wire and
No.212 wire. At this time, No.800 wire enters
188
Lights
System Fault Test and Service
Main Components
1. Secondary steering running indicator
2. Steering system fault indicator
Secondary steering Motor 30B0291 Secondary steering running
Illustration 8-1 Secondary steering motor switch
Illustration 8-4 Secondary steering running
switch
Illustration 8-5 Steering system low pressure The steering system low pressure alert
alert switch indicator turns on (see illustration 8-5) when
the system pressure is under 0.6Mp → No.
312 wire electrifies → the steering system
fault indicator lights (see illustration 8-3) →
the gauge No.36 pin outputs +24V ~ 32V
voltage (the time is 40 sec) → No 409 wire
electrifies → the secondary steering relay
works → No 465 wire electrifies → the
secondary steering motor works → the
secondary steering motor drives the
secondary steering pump and supplies the
power output to steering system →
secondary steering running switch turns on
Secondary steering system principle: → No 408 wire connected to the grounding
wire → the secondary steering running
1. Manual operation indicator lights
Turn on the start switch, and press the
secondary steering switch (see illustration 8-
2).
No.409 wire electrifies → the secondary
steering relay works (in the wiring control
box) → No.465 wire electrifies → the
secondary steering motor works → the
secondary steering motor drives the
secondary steering pump and supplies the
power output to steering system → the
secondary steering running switch (see
illustration 8-4) turns on → No.408 wire
connected to the grounding wire → the
secondary steering running indicator lights
(see illustration 8-3).
2. Automatic operation
192
Secondary Steering System
Fault Test Steps of Secondary Steering System
Fault Test Steps of Secondary Yes: please replace the secondary steering
system fuse
Steering System
No: please turn to 1-B
1. Secondary steering motor manual no 1-B Press the secondary steering switch when
work the start switch is OFF, use the resistance
function of the multimeter to measure whether
1-A Test whether 10A secondary steering system No.1 pin and No. 5 pin of the secondary steering
fuse has melted? switch are connected?
Yes: please turn to 1-C
193
Secondary Steering System
Fault Test Steps of Secondary Steering System
No: the secondary steering switch is damaged, Yes: please turn to 2-D
please replace the switch.
No: the steering system low pressure alert switch
1-C Test whether the secondary steering relay (in is damaged; please replace the steering system
the control box) is damaged? low pressure alert switch.
Yes: please replace the secondary steering relay. 2-D Turn on the start switch, use the DC voltage
function of the multimeter to measure whether
No: please turn to 1-D
the grounding voltage of the gauge receptacle
1-D Turn on the start switch, press the secondary No.36 pin (No.409 wire) is between 24V and
steering switch, use the DC voltage function of 32V?
the multimeter to measure whether the
Yes: please turn to 1-C
grounding voltage of No. 465 wire on the
secondary steering motor is between 24V and No: the gauge has fault, please replace it.
32V?
3. The secondary steering motor can work
Yes: please turn to 1-E
normally but can't turn
No: please turn to 1-F
Test the fault of the hydraulic system.
1-E Test whether the secondary steering motor is
damaged?
Yes: please replace the secondary steering
motor.
No: please turn to 1-F
1-F Test the receptacle condition according to
the system principle.
Main Components
1 2
1 2
Wiper
Front wiper I、 II and washer relays
195
Wiper and Washer System
Common Fault Test
2 1 3
Common Fault Test The wiper motor drives the wiper to work (see
illustration 9-2). The front, rear wiper motors of
the machine are magnet motors and negative
Wiper principle: controlled.
196
Wiper and Washer System
Common Fault Test
There are 5 wires connected outward to the front There are 5 wires connected outward to the rear
wiper motor, the red is power supply wire (the wiper motor, the red is power supply wire (the
common brush leads of high gear armature and common brush leads of high gear armature and
low gear armature connected to No. 129 wire), low gear armature connected to No. 129 wire),
the black is negative wire (connected to the the black is negative wire (connected to the
ground by the motor housing, connected to No. ground by the motor housing, connected to No.
213 wire), the blue is another brush lead of high 205 wire), the blue is another brush lead of high
gear armature (connected to No. 330 wire), the gear armature (connected to No. 337 wire), the
green is another brush lead of low gear armature green is another brush lead of low gear armature
(connected to No. 331 wire), the white is reset (connected to No. 338 wire), the white is reset
wire (connected to No. 329 wire). wire (connected to No. 339 wire).
No. 129 wire electrifies (+24V) after starting the No. 129 wire electrifies (+24V) after starting the
start switch. When the combination lever wiper start switch. When the rear wiper switch (see
switch (see illustration 9-1) is at I gear, No. 328 illustration 9-5) is at 1st gear, No. 3 pin is
wire is connected to No. 202 grounding wire, connected to No.5 pin, and the motor runs at low
which makes the wiper motor 1st gear relay K7 gear.
(see illustration 9-6) works, that is the motor runs
When the rear wiper switch is at 2nd gear, No.3
at low gear when No. 331 wire is connected to
pin is connected to No.1 pin, and the motor runs
No. 213 grounding wire.
at high gear.
When the combination lever wiper switch is at II
If turn off the wiper switch (that is turn the switch
gear, No. 327 wire is connected to No. 202 wire,
to O gear from 1st or 2nd gear), No.5 pin and No.
which makes the wiper 2th gear relay K8 works,
7 are connected. At the moment of turn off the
that is the motor runs at high gear when No. 330
switch, the wiper doesn't stop at the first position,
wire is connected to No. 213 grounding wire.
the current passes by No. 129 lead-low gear
If turn off the wiper switch (that is turn the switch armature-wiper switch No.5 pin-wiper switch
from I gear or II gear to O gear through J gear), No.7 pin-white reset wire-ground (illustration:
when turn the switch to J gear, if the wiper there is a auto reset device in the motor, make
doesn't stop at the first position, the current sure the wiper can always stop at the first
passes by No. 129 lead-No. 328 lead of low gear position, the reset wire is connected to the power
armature-wiper switch-white reset No. 329 lead- supply wire when the wiper is at the first position,
ground (illustration: there is a reset device in the otherwise the reset wire is connected to the
motor, make sure the wiper brush can always negative wire) the motor runs continuously.
stop at the first position, the reset wire is
The reset wire is connected with the power
connected to the power supply wire when the
supply wire when the wiper runs to the first
wiper is at the first position, otherwise the reset
position, the wiper motor' low gear armature gets
wire is connected to the negative wire), the motor
short circuit, the motor keeps running under the
runs continuously.
inertia action and generates electricity, then
The reset wire is connected to the power supply produces the electromagnetism brake torque
wire when the wiper runs to the first position, the and stops running immediately, the wiper stops
wiper motor' low gear armature gets short circuit, working when it runs to O gear.
the motor keeps running under the inertia action
and generates electricity, then produces the
The measuring methods of wiper motor
electromagnetism brake torque and stops in short circuit and open circuit:
running immediately, the wiper stops working
when it runs to O gear.
197
Wiper and Washer System
Common Fault Test
Disconnect the connection between the wiper No: please turn to 1-E
motor and the whole machine wiring, and use the
1-E Turn on the start switch, turn the combination
resistance function of the multimeter to measure
switch to I gear, use the voltage function of the
the wiper motor resistance between red wire and
multimeter to measure whether the voltage
blue wire or green wire. If the resistance is
between No.1 pin (No.129 wire) and No.4 pin
infinity, it is open circuit. Use the resistance
(No.331 wire) of XJ2 receptacle is between 24V
function of multimeter to measure the resistance
between the red wire and any other wire; if the and 32V?
resistance is limited, it is short circuit. Yes: please turn to 1-F
Washer principle: No: please turn to 1-G
Turn on the start switch, 20A wiper fuse 1-F Test whether the front wiper motor gets short
electrifies (+24V), the front washer switch (see circuit or open circuit?
illustration 9-1) and the rear washer switch (see Yes: please replace the front wiper assembly.
illustration 9-4) are connected, the front washer
relay K13 (see illustration 9-6) works, the front, No: please turn to 1-G
rear washer motors (see illustration 9-5) work by 1-G Test whether the receptacles have loosened
No.420. 421 wires, water in the kettle is taken out and the wiring harnesses have worn according to
to the nozzle (installed under the front, rear the principle of the wiper and washer systems.
windows) and spray to the windshield.
Fault Test Steps of the Wiper and 2. Front wiper II gear doesn't work
Washer Systems:
2-A Turn on the start switch, the front wiper I
1. Front wiper I gear doesn't work gear works normally?
Yes: please turn to 2-C
1-A Turn on the start switch, the front wiper II
No: please turn to 1-B
gear works normally?
2-B Test whether 20A fuses of the wiper and the
Yes: please turn to 1-C
washer systems have melted?
No: please turn to 1-B
Yes: please replace the fuse.
1-B Test whether 20A fuses of wiper and washer
No: please turn to 2-C
systems have melted?
2-C Turn off the start switch, turn the
Yes: please replace the fuse
combination switch to II gear, pull out No.327
No: please turn to 1-C wire on the wiper II gear relay, use the resistance
function of the multimeter to measure whether
1-C Turn off the start switch, turn the
No.328 wire is connected to the ground?
combination switch to I gear, pull out No.328 wire
on the wiper I gear relay, use the resistance Yes: please turn to 2-D
function of the multimeter to measure whether
No: the front wiper switch is damaged, please
No.328 wire is connected to the ground?
replace the combination switch.
Yes: please turn to 1-D
2-D Test whether the front wiper II gear relay is
No: the front wiper switch is damaged, please damaged?
replace the combination switch.
Yes: please replace the front wiper II gear relay.
1-D Test whether the front wiper I gear relay is
No: please turn to 2-E
damaged?
Yes: please replace the front wiper I gear relay.
198
Wiper and Washer System
Common Fault Test
2-E Turn on the start switch, turn the combination Yes: please replace the rear wiper assembly.
switch to II gear, use the DC voltage function of
No: Test whether the receptacles have loosened
the multimeter to measure whether the voltage
and the wiring harnesses have worn according to
between No.1 pin (No.129 wire) and No.3 pin
the principle of the wiper and washer systems.
(No.330 wire) of XJ2 receptacle is between 24V
and 32V? 4. Rear wiper II gear doesn't work
Yes: please turn to 1-F
4-A Turn on the start switch, the rear wiper I gear
No: Test whether the receptacles have loosened
works normally?
and the wiring harnesses have worn according to
the principle of the wiper and washer systems Yes: please turn to 4-C
No: please turn to 4-B
3. Rear wiper I gear doesn't work
4-B Test whether 20A fuses of the wiper and
3-A Turn on the start switch, the rear wiper II washer systems have melted?
gear works normally?
Yes: please replace the fuses
Yes: please turn to 3-C
No: please turn to 4-C
No: please turn to 3-B
4-C Turn off the start switch, turn the rear wiper
3-B Test whether 20A fuses of the wiper and switch to II gear, use the resistance function of
washer systems have melted? the multimeter to measure whether No.3 pin and
No.1 pin of rear wiper switch are connected?
Yes: please replace the fuse.
Yes: please turn to 4-D
No: please turn to 3-C
No: the rear wiper switch is damaged; please
3-C Turn off the start switch, turn the
replace the rear wiper switch.
combination switch to I gear, use the resistance
function of the multimeter to measure whether 4-D Turn on the start switch, turn the rear wiper
the voltage between No.1 pin (No.129 wire) and switch to II gear, use the DC voltage of the
No.3 pin (No.330 wire) of XJ2 receptacle is multimeter to measure whether the voltage
between 24V and 32V? between No.1 pin (No.129 wire) and No.3 pin
(No.337 wire) of XJ8 receptacle is between 24V
Yes: please turn to 3-D
and 32V?
No: the rear wiper is damaged; please replace
Yes: please turn to 3-E
the rear wiper switch.
No: Test whether the receptacles have loosend
3-D Turn on the start switch, turn the rear wiper
and the wiring harnesses have worn according to
switch to I gear, use the DC voltage function of
the principle drawing of the wiper and washer
multimeter to measure whether the voltage
systems..
between No.1 pin (No.129 wire) and No.4 pin
(No.338 wire) of XJ8 receptacle is between 24V
5. The washer nozzle doesn't work
and 32V?
Yes: please turn to 3-E 5-A Observe whether the motor runs and sprays
normally?
No: Test whether the receptacle have loosened
and the wiring harnesses have worn according to 5-B Test the water line has disconnected or not
the principle of the wiper and washer systems. (water hose has disconnected or is bundled too
tightening)
3-E Test whether the front, rear wiper motor gets
short circuit or open circuit? 5-C Test the nozzle is jammed or not.
199
Sound System
Main Components
37B0242 Radio
Function Brief Introduction
Turn on the power supply can play the radio or
the tape.
Illustration 10-1 Radio
Radio Instruction
① Preselected Key1 ② Preselected key2 ③ Preselected Key3 ④ Preselected Key4 ⑤ Preselected Key5
⑥ Preselected Key6 ⑦ Switch ⑧ Sound Mode Key ⑨ Volume Key ⑩ Radio Key
⑾ Auto-memory ⑿ FM/AM Switch ⒀ LCD
200
Sound System
Fault Test Steps of Sound System
38B0047 Speaker
Illustration 10-3 Speaker
37B0243 Antenna
201
Sound System
Fault Test Steps of Sound System
Unplug XD9 and XE1 receptacles, test their (1) Check and make sure the tape is in good
resistance values. The values should be (or condition. The tape ungirds may damage the
close to) the nominal values. If the resistance sound system and tape. Use a pencil or other
value is zero or the circuit is open, the tools to tighten the tape.
speaker is damaged. If the positive/negative
pole of the speaker hasn't voltage, please 7. The speaker volume reduces
check the condition of the receptacles and automatically
the wiring harnesses.
(1) The safety circuit inside will prevent the
2. Check the left/right balance set of the
sound system interior temperature from
speaker.
exceeding the stated value.
3. Check the antenna and connector.
(2) Increase the volume when the temperature is
reduced.
2. Start the sound, the LCD doesn't display.
6. Tape looseness
202
Auto-Return System
Main Components
4. The pilot valve solenoid condition is good These windings can lock the single handle
when the digital multimeter reading is about control lever at operation position when the
100. The pilot valve solenoid has burnt off, operator controls the lever for lifting the boom,
and needs replacement when the digital floating the boom and tilting the bucket. The
multimeter reading is 0. The pilot valve single handle control lever can return to the
solenoid may be short circuit between the middle position automatically when the boom lift
coils when the digital multimeter reading is kickout and the bucket positioner are at the limit
less than 70, please replace it. position.
Single handle control lever and the pilot The pilot valve solenoid electronic parameter:
valve (available for CLG856III with full- the temperature is 25 ℃ , the winding resistance
auto shift control) is 100 ± 5 Ω .
The single handle control lever in this machine Pilot valve solenoid fault check method:
integrates the shift control, the boom and the
bucket operation as a whole. 1. Open the single handle control lever side
The single handle boom and bucket operation cover, and pull out the electronic receptacle
functions will be introduced in this section, but of the pilot valve solenoid.
the shift control function will be introduced in the 2. Adjust the digital multimeter to 200 Ω
corresponding section. function.
Illustration 11-2 Single handle control lever and 3. Use the digital multimeter probe to connect
pilot valve figuration and electronic principle two probes of the pilot valve solenoid
drawing symbol (available for CLG856III with full- receptacle separately.
auto shift control)
4. The pilot valve solenoid condition is good
when the digital multimeter reading is about
100. The pilot valve solenoid has burnt off
and needs replacement when the digital
multimeter reading is 0. The pilot valve
solenoid may be short circuit between the
coils when the digital multimeter reading is
less than 70, please replace it.
Boom Magnet
The boom magnet is welded on the boom, close
to the articulation position of the boom. It is the
boom lifting limit magnet, and provides the
magnetic field for the approach switch. The
permanent magnet is installed in the white line
frame.
The boom magnetic field intensity is at the place
13mm above the central axes of the magnet, the
magnetic field intensity is not less than
The pilot valve is fixed under the single handle
225G(Gauss).
control lever, there are three group windings
inside, which control the boom kickout, the boom
float and the bucket positioner functions
separately.
204
Auto-Return System
Main Components
Illustration 11-3 Boom magnet exterior drawing Illustration 11-5 Boom lift kickout and bucket
positioner approach switches exterior drawing
symbol
See above illustration, the induction point 1. Turn on the start switch, observe the red
position is Hall switch position inside the boom indicator and green indicator, if there is one
lift kickout switch, the green indicator on the indicator doesn't lighten, the switch is
approach switch shows the power supply state, damaged, and please replace it. Carry out
and the red one shows the work state of the the following steps if two indicators lighten.
approach switch.
2. Lower the boom slowly and level the bucket
In above illustration, the plastic or wooden block on the ground.
layer is used to test, its thickness is 4-6mm,
3. Disassemble the boom lift kickout switch
during test, this layer is not used, keep the
from the fixing hood, observe the red
distance between the burst magnet and
indicator condition after put the boom lift
induction surface for 4-6mm.
kickout switch induction surface close to the
The red indicator and green indicator lighten at boom magnet up to 4-6mm away from it.
the same time when the switches are switched Remove the boom lift kickout switch away if
on, input +24V power to the pilot valve solenoid. the red indicator doesn't go out, and closing
Hall switch checks the magnetic field existence up the boom magnet again 2s later, observe
when the magnet is close to the inducton point of the red indicator condition, the indicator is
the switch, Hall switch exports signals to drive damaged if it doesn't go out. Remove the
the inner electrical circuit and shut off the output boom lift kickout switch away if the red
voltage of the approach switch when the indicator goes out, observe whether the red
magnetic field intensity reaches to desired value, indicator lightens again after 2s. The boom lift
the red indicator goes out at this time. The red kickout switch is damaged if it can't lighten
indicator lightens newly 1-2s later after the newly.
magnet being moved and starts next work
The above operation must be carried out under
circulation.
the safety condition.
NOTICE Bucket positioner approach switch
During adjustment, when the boom lift See the boom lift kickout switch instruction for
kickout switch is close to the boom magnet, the bucket positioner switch exterior drawing and
must make the induction surface distance is principle drawing. Its outline is the same to the
4-6mm. boom lift kickout switch.
Refer to the boom lift kickout approach switch
During installation, when the boom lift work principle instruction for the bucket
kickout switch is close to the boom magnet, positioner approach switch work principle.
must make the induction surface center
Illustration 11-7 The induction relationship
corresponding to the magnet center.
between the bucket positioner switch and the
bucket magnet
Boom lift kickout switch fault test method
See above illustration, the induction point Bucket positioner switch fault test method
position is Hall switch position inside the bucket
positioner approach switch. It is different that the The switch interior wires are separate, can't test
bucket positioner switch has two Hall switches, the resistance and voltage according to the
but the boom lift kickout switch just has one Hall traditional method. Test them according to the
switch. The gree indicator on the approach following methods if doubt the switch has fault,
switch shows the power supply state, the red need a second to help if use this method to test.
indicator shows the work state of the approach
1. Turn on the start switch, observe the red
switch.
indicator and green indicator, if there is one
See above illustration, use the plastic or wooden indicator doesn't lighten, the switch is
block layer to measure, its thickness is 4-6mm, damaged, and please replace it. Carry out
during test, this layer is not used, keep the the following steps if two indicators lighten.
distance between the burst magnet and the
2. Lower the boom slowly and level the bucket
induction surface for 4-6mm.
on the ground.
The red indicator and green indicator lighten at
3. Disassemble the boom lift kickout switch
the same time when the switches are switched
from the fixing hood (use the spare magnet to
on, input +24V power to the pilot valve solenoid.
test, note the process direction is opposite to
Hall switch exports signals to drive the inner wire
the return direction), observe the red
and cut off the switch output voltage when the
indicator condition after put the bucket
magnet is close to the right side induction point
positioner switch induction surface close to
of the approach switch from process direction → the boom magnet according to the above
left side induction point, the red indicator goes
illustration induction direction (the indicator
out at this time. The red indicator lightens newly
as the reference)-first left induction point-then
and starts next work circulation after remove
right induction point. Observe the red
away the magnet, see above illustration, closing
indicator lightens newly from goes out when
up the left side induction point of the approach
the switch is close to the magnet according to
switch from return direction → right side the above illustration induction direction-first
induction point.
right induction point-then left induction point.
The bucket positioner approach switch has (The reference is switch, the motion object is
restriction current protection function. magnet, so the direction is opposite to the
real operation process direction and return
NOTICE direction). Repeat this step for 2-3 times, the
switch which can complete the test
During adjustment, when the boom lift successfully is good.
kickout switch is close to the boom magnet,
The above operation must be carried out under
must make the induction surface distance is
the safety condition.
4-6mm.
System test and service b.Turn off the start switch, open the side cover of
fixing base of the pilot valve, find and unplug XK1
11-A Boom float function principle receptacle, measure XK1 receptacle terminal of
description the cab wiring harness.
c.Turn on the start switch, use red probe of the
Lower the boom when push the single handle digital multimeter to connect the corresponding
control lever forward, when push it to limit core of No.135 wire, use black probe to connect
position the lever will keep at limit position the corresponding core of No.209 wire.
automatically, realize this function by the boom
float solenoid inside the pilot valve. Test result:
When the start switch is ON, No.135 wire obtains
+24V voltage from 5A fuse, passing XA1 → XK1 The digital multimeter reading is between 24V
receptacle to the boom float solenoid then to the and 31V.
ground. The magnetic field is produced around
the solenoid when the solenoid electrifies. The Conclusion:
magnetic field produced by the solenoid
electrifying can't make the close magnetic circuit If the result does OK, please turn to step 3
due to the pilot valve's special configuration If the result doesn't OK, please turn to step 2
when the single handle control lever keeps at
NEUTRAL position. The close magnetic circuit is Step 2. Test whether the boom lift kickout
produced around the pilot valve boom float position and bucket leveling position can
solenoid in order to decrease the magnetic circuit keep automatically?
spacing when the operator pushes the single
handle control lever forward to the limit position. a.Push the single handle control lever to boom
So the control lever can be kept at the limit lift position or bucket leveling position, observe
position whether the lever can keep automatically.
Pull the single handle control lever to NEUTRAL
position manually to disconnect the close Conclusion:
magnetic circuit.
If it can keep, please check as follows:
11-A-F Fault test when the control lever can't
(1) Check No.209 wire grounding condition.
be locked at boom float position
(2) Check the connecting condition between
Fault phenomenon definition: No.135 wire of XK1 and total No.135 wire.
If it can not keep, please check as follows:
The single handle control lever can't keep at float
position automatically when push it forward to (1) Check 5A fuse for melting condition.
the limit position and do floating operation. (2) Check X1 receptacle connecting condition.
Fault test steps: (3) Check No.135 wire connecting condition at
No.32 fuse.
Step 1. Test whether there is +24V voltage
between two cores of XK1 receptacle. Step 3. Test the resistance of the boom
floating solenoid
a.Adjust the digital multimeter to voltage function
(50V). a.Adjust the digital multimeter to Ω function (200
Ω ).
210
Auto-Return System
System fault test and service
When the start switch is ON, No.135 wire obtains Fault test steps:
+24V voltage from 5A fuse, passing XA1 → XQ8
→ XQ3 receptacle to the boom lift kickout switch Step 1. Test the red indicator of the boom lift
then to the ground. The switch exports +24V kickout switch lightens or not when electrify?
voltage to the boom lift kickout solenoid then to
the ground passing No.476 → XQ3 → XQ8 → a.Turn on the start switch, observe the red
XK2 when the red indicator and green indicator indicator lightens or not from the observe window
lighten. The magnetic field is produced around of the fixing hood on the boom kickout switch.
the solenoid when the solenoid electrifies. The b.Turn off the start switch if it doesn't lighten, pull
magnetic field produced by the solenoid out and insert XQ8 and XQ3 receptacle newly,
electrifying can't make the close magnetic circuit pull No.135 wire and No.219 wire of XQ8
due to the pilot valve's special configuration receptacle and XQ3 receptacle two terminals
when the single handle control lever keeps at slightly by hand to check their connecting
NEUTRAL position. The close magnetic circuit is condition.
produced around the pilot valve boom lift kickout
solenoid in order to decrease the magnetic circuit c.Turn on the start switch and observe the red
spacing when the operator pushes the single indicator condition if they don't loosen.
handle control lever backward to the limit
position. So the control lever can be kept at the Conclusion:
limit position. The boom magnet is close to the
boom lift kickout switch slowly when the boom If the result does OK, please turn to step 2.
reaches to the limit position, the lift kickout switch If the result doesn't OK, please turn to step 5.
output is cut off, No.476 wire doesn't have
voltage output when the the switch reaches the Step 2. Test the green indicator of the boom
best position. The red indicator goes out. The lift kickout switch lightens or not when
single handle control lever returns to NEUTRAL electrify?
position automatically when the pilot valve
kickout solenoid stops working. a.Turn on the start switch, observe the green
Lower the boom by control lever reversely, indicator lightens or not from the observe window
separate the boom magnet and boom lift kickout of the fixing hood on the boom kickout switch.
switch, the switch exports +24V voltage to the This step should be carried out when the boom
boom kickout solenoid newly by No.476 wire kickout switch and the boom magnet are not at
after the switch stops output for 2s, the winding the action position.
electrifies, the red indicator lightens newly, start b.Turn off the start switch if it doesn't lighten, pull
next circulation. out and insert XQ8 and XQ3 receptacle newly,
pull No.135 wire, No.219 wire and No.476 wire of
11-B-F1 Fault test when the control lever XQ8 receptacle and XQ3 receptacle two
can't be locked at boom lifting position terminals slightly by hand to check their
connecting condition.
Fault phenomenon definition:
c.Turn on the start switch and observe the green
The single handle control lever can't keep at indicator condition if they don't loosen.
boom lifting position automatically when push the
Conclustion:
lever backward to the limit position during boom
lifting.
If the result does OK, please turn to step 3.
If the result doesn't OK, the boom kickout switch
is damaged.
212
Auto-Return System
System fault test and service
Step 3. Test whether there is +24V voltage Step 5. Test whether the boom float position
between two cores of XK2 receptacle wiring and bucket leveling position can keep
harness. automatically?
a.Adjust the digital multimeter to voltage function a.Push the single handle control lever to the
(50V). boom float position or bucket leveling position,
b.Remove XK2 receptacle, turn on the start observe whether the lever can keep
switch. automatically. Please to step 6 if it can keep
automatically.
c.Use red probe of the digital multimeter to
connect No.476 wire corresponding core of XK2 b.If it can't keep automatically, please turn off the
receptacle, use black probe to connect another start switch, open the electronic control box
copper piece of XK2 receptacle. inside the cab, and find 5A fuse then observe its
melting condition.
Test result:
Conclusion:
The digital multimeter reading is between 24V
and 31V. If it has melted, please replace 5A fuse. If the
new fuse melts again, please eliminate the short
Conclusion: circuit fault.
If it doesn't melt, please turn to step 6.
If the result does OK, please turn to step 4
Step 6. Test whether there is +24V voltage
If the result doesn't OK, please turn to step 7
between two cores of XQ3 receptacle wiring
Step 4. Test the resistance of the boom harness.
kickout solenoid
a.Adjust the digital multimeter to voltage function
(50V).
a.Adjust the digital multimeter to Ω function (200
Ω ). b.Remove XQ3 receptacle, turn on the start
b.Use the probe of multimeter to connect two switch.
pins of XK2 receptacle of the pilot valve solenoid c.Use red probe of the digital multimeter to
terminal. connect No.135 wire corresponding core of
XQ32 receptacle, use black probe to connect
Test result: another copper piece of XQ3 receptacle.
If the result does OK, the pilot valve has inner Conclusion:
fault.
If the result does OK, the boom kickout switch is
If the result doesn't OK, the boom kickout
damaged.
solenoid is damaged.
If the result doesn't OK, judge the grounding
condition of No.219 wire firstly, if the grounding
condition is good, please check the line fault
between 5A fuse and XQ3 receptacle.
213
Auto-Return System
System fault test and service
Step 7. Test whether there is open circuit in d.Use two probes of the multimeter to connect
the line between XK2 and XQ3 receptacles. separately with two copper receptacles of XK2
receptacle of the cab wiring harness.
a.Turn off the start switch, remove XQ3 and XQ2
receptacles. Test result:
b.Insert a 80mm long lead which shucks off two
sides insulation layer each 10mm into No.2 The digital multimeter reading is about 0 Ω .
(No.476 wire)and No.1 core (No.219 wire) of
Conclusion:
XQ3 receptacle connecting with front frame
wiring harness, please pay attention to contact
the lead copper wire with the copper receptacle If the result does OK, the boom kickout switch is
of XQ3 receptacle well. damaged.
If the result doesn't OK, please check the
c.Adjust the digital multimeter to Ω function (200
Ω ). grounding condition of No.210 wire, and check
the open circuit phenomenon in the lines.
Illustration 11-13 Fault test flow chart 11-B-F1 when the control lever can't be locked at boom lifting
position
11-B-F2 Fault test when the boom reaches at The control lever keeps at boom lifting position
lifting limit position, the control lever can't when push the lever backward to the limit
return to NEUTRAL position position during boom lifting, the lever can't return
to NEUTRAL position when the boom reaches
Fault phenomenon definition: the limit position.
214
Auto-Return System
System fault test and service
Fault test steps: Illustration 11-14 Fault test flow chart 11-B-F2
when the boom lifts to the limit position, it can't
Step 1. Test the clearance between the boom return to NEUTRAL position automatically
kickout switch and the boom magnet.
Conclusion:
Conclusion:
Turn on the start switch, No.135 wire obtains Fault test steps:
+24V voltage from 5A fuse, passing XA1 → XQ8
→ XQ1 receptacle to the bucket leveling switch Step 1. Test the red indicator of the bucket
then to the ground. The switch exports +24V positioner switch lightens or not when
voltage to the bucket leveling solenoid then to electrify?
the ground passing No.477 wire → XQ4 → XQ8
→ XK3 when the red indicator and green a.Turn on the start switch, observe the red
indicator lighten. The magnetic field is produced indicator lightens or not from the observe window
around the solenoid when the solenoid of the fixing hood on the bucket positioner
electrifies. The magnetic field produced by the switch.
solenoid electrifying can't make the close b.Turn off the start switch if it doesn't lighten, pull
magnetic circuit due to the pilot valve's special out and insert XQ8 and XQ4 receptacle newly,
configuration when the single handle control pull No.135 wire and No.219 wire of XQ8
lever keeps at NEUTRAL position. The close receptacle and XQ4 receptacle two terminals
magnetic circuit is produced around the pilot slightly by hand to check their connecting
valve bucket leveling solenoid in order to condition.
decrease the magnetic circuit spacing when the
operator pushes the single handle control lever c.Turn on the start switch and observe the
left to the limit position. So the control lever can condition of the red indicator if they don't loosen.
be kept at the limit position. The bucket magnet
is close to the bucket positioner switch slowly Conclusion:
when the bucket reaches to leveling position, the
positioner switch output is cut off, No.477 wire If the result does OK, please turn to step 2.
doesn't have voltage output when the the switch If the result doesn't OK, please turn to step 5.
reaches the best position. The red indicator goes
out. The single handle control lever returns to Step 2. Test the green indicator of the bucket
NEUTRAL position automatically when the pilot positioner switch lightens or not when
valve bucket positioner switch stops working. Tilt electrify?
the bucket left, the bucket magnet closes up the
bucket positioner switch. a.Observe the green indicator lightens or not
Operate the single handle control lever reversely from the observe window of the fixing hood on
for dumping, the bucket magnet contacts with the the bucket positioner switch when turn on the
bucket positioner switch newly, the positioner start switch. This step should be carried out
switch exports +24V voltage to the bucket when the bucket positioner switch and the bucket
leveling solenoid by No.477 wire, the winding magnet are not at positioner switch action
electrifies working, the red indicator lighten position.
newly. The next circulation starts. b.Turn off the start switch if it doesn't lighten, pull
out and insert XQ8 and XQ4 receptacle newly,
11-C-F1 Fault test when the control lever pull No.135 wire and No.219 wire of XQ8
can't be locked at HOLDING position. receptacle and XQ4 receptacle two terminals
slightly by hand to check their connecting
Fault phenomenon definition: condition.
Push the control lever to the desired position, the c.Turn on the start switch and observe the
lever can't hold at this position automatically condition of the green indicator if they don't
during leveling bucket. loosen.
216
Auto-Return System
System fault test and service
If the result does OK, please turn to step 4 a.Adjust the digital multimeter to voltage function
(50V).
If the result doesn't OK, please turn to step 7
b.Remove XQ4 receptacle, turn on the start
Step 4. Test the resistance of the bucket switch.
positioner solenoid c.Use the red probe of the digital multimeter to
connect No.135 wire of XQ4 receptacle
a.Adjust the digital multimeter to Ω function (200 corresponding copper piece, the black probe
Ω ). connects to another copper piece of XQ4
receptacle.
b.Use the probe of the digital multimeter to
connect two probes of XK3 receptacle of the pilot
Test result:
valve solenoid terminal separately.
The digital multimeter reading is between 24V
Test result:
and 31V.
The digital multimeter reading is between 90 Ω Conclusion:
and 100 Ω .
If the result doesn't OK, judge the grounding c.Adjust the digital multimeter to Ω function (200
condition of No.219 wire firstly, and please check Ω ).
the line fault between 5A fuse and XQ4 d.Use the probe of the digital multimeter to
receptacle if the grounding condition is good. connect two copper pieces of XK3 receptacle of
the cab harness separately.
Step 7. Test the wire connecting condition
between XK3 and XQ4. Test result:
a.Turn off the start switch, remove XQ4 and XK3
The digital multimeter reading is about 0 Ω .
receptacles.
b.Insert a 80mm long lead which shucks off two Conclusion:
sides insulation layer each 10mm into No.2
(No.476 wire)and No.1 core (No.219 wire) of If the result does OK, the bucket positioner
XQ3 receptacle connecting with the front frame switch is damaged.
harness, please pay attention to contact the lead
If the result doesn't OK, please check the
copper wire with the copper receptacle of XQ3
grounding condition of No.211 wire, and check
receptacle well.
the open circuit among the lines.
Illustration 11-15 Fault flow chart 11-C-F1 when the control lever can't be locked at bucket leveling
position
218
Auto-Return System
System fault test and service
11-C-F2 Fault test when the bucket reaches b.Turn on the start switch, push the single handle
leveling position, the control lever can't control lever forward to the limit position, the
return to NEUTRAL position control lever will keep at boom floating position,
close up the bucket positioner switch to bucket
Fault phenomenon definition: magnet manually. Or close up the magnet to the
switch manually. Observe the control lever
Push the control lever inside and hold it at this returns or not?
position when tilt the bucket back, the control c.Pull out XK3 and XK1 receptacles after
lever can't return to NEUTRAL position when the checking, and return to the condition before test.
bucket tilts back to leveling position.
Conclusion:
Fault test steps:
If it returns, the pilot valve has inner fault.
Step 1. Test the clearance between the
positioner switch and the bucket magnet If it doesn't return, the bucket positioner switch is
damaged.
a.Turn off the start switch, disassemble the Illustration 11-16 Fault flow chart 11-C-F2 when
bucket positioner switch from the switch the control lever can't return to NEUTRAL
receptacle. Or prepare one spare magnet. position after the bucket tilting to leveling position
b.Turn on the start switch, push the single handle
control lever to the bucket tilting position, the
control lever will keep at tilting position
automatically. Close up the bucket positioner
switch to bucket magnet manually. Or prepare
one spare magnet, and close up the spare
magnet to the switch manually. Observe the
control lever returns or not?
Conclusion:
a.Turn off the start switch, and turn the pilot valve
switch to OFF position. Pull out XK3 receptacle
and XK1 receptacle, and connect the pilot valve
solenoid with the receptacles across.
219
Lubrication system
Main Components
Lubrication system This cycle will be stopped when turn off the start
switch in the stop machine time or lubrication
time cycle, but time will be stored. The operation
will proceed from the last stored stop time when
Function Brief Introduction turn on the start switch.
This machine uses Germany VOGEL central This machine's set when leave the factory: the
lubrication device for automatic lubricating. The lubrication interval time: 1h, one lubrication
grease used in central lubrication device is 1# running time: 12min.
MOS2 or 2# grease or grease level ≤ NLG1
grade2, the oil tank capacity has 2L. The grease
choice is relative to area environmental Main Components
temperature, eg, need 1# MOS2 at 0°C (32°
F)area. Piston pump
The lubrication cycle starts after turn on the start
switch firstly, the lubrication pump motor starts, 15C0018 (KFGS1-5+924) electromotion
lubrication pump has 2L capacity tank, which has
the lubrication system works. The lubrication
inner-set controller, the pump element has
pump motor turn off automatically after the
collocated as a unit with piston pump in the
lubrication cycle time reaches the preestablished
manufactory. The controller inside the
time, stop machine time starts, the next
electromotion lubrication piston pump controls
lubrication cycle starts after stop time reaches
the electronic controlling of the lubrication
the preestablished time. All of lubrication work
system.
will proceed according to the preestablished time
program.
Illustration 12-1 Controller inside the piston pump
220
Lubrication system
Main Components
When system pressure exceeds 300 bar due to Each set progressive feeder consists of the first
the progressive feeder or lubrication point section, the end section and the feeder section,
blockage, the valve opens and discharges the first section and the end section has one
lubricant. each, the feeder section is not less than 3. This
machine will define the progressive feeder as
78A0034 Safety valve
VPKM-8, 8 feeder sections; VPKM-10, 10 feeder
sections; VPKM-3, 3 feeder sections according
to the middle section's quantity of the
progressive feeder.
Oil drain sequence of the progressive feeder is:
the farthest outlet away from the inlet drains oil
firstly, and the nearest outlet away form the inlet
drains oil lastly. The second feeder section can't
drain oil if the first section blocks.
Progressive feeder
The progressive feeder will divide the grease
from the pump device into several parts.
This machine has 3 sets progressive feeders, the
tab in the system principle drawing is VPKM-8
VPKM-10, VPKM-3.
Illutration 12-5 Central lubrication principle
drawing (the sample is CLG856III with 8-bar front
frame)
Each feeder section has the different type for Illustration 12-7 Straight male connector and
distinguishing; the different type feeder section elbow male connector
has the different parameter.
These types are marked on the feeder sections
and the central lubrication principle drawing, eg:
"2S", "2T", "0.5S" etc. The first number shows
oil drain capacity of each outlet and each cycle in
type label. The second English letter shows each
section outlet quantity, "T" means 2 outlets,
"S"means 1 outlet.
One terminal of the straight male connector
NOTICE 00A0569 (or elbow male connector 01A0255) is
connected to the control valve outlet of the
The different type feeder sections have the progressive feeder, and one terminal is
same figurations, keep the feeder section connected to oil tube.
type consistency if replace the feed section
separately, otherwise the lubrication system Illustration 12-8 Tube connection
can not work separately.
1、Pump 2、High pressure hose 3、Main feeder 4、secondary feeder 5、Lubrication point
6、Pump unit 7、Wire package 8、Safety valve
12-A Auto-lubrication Function Operation The following components are needed for
realizing this function:
The auto-lubrication function doesn't need the ● Fuse
operator's special operation, the controller inside
the piston pump controls the auto-lubrication ● Instrument system (lubrication fault and work
function ON/OFF. It works once the machine indication)
powers on. ● VOGEL centralized lubrication device (with
The first lubrication cycle starts automatically controller inside the piston pump, pump unit,
after turning on the start switch first time, the progressive feeder, lubricant, straight male
lubrication pump motor starts, the lubrication connector, elbow male connector etc).
system works. The lubrication pump motor turns
off automatically after the lubrication cycle time
reaches the preestablished value-12min, stop
machine time starts, next lubrication cycle starts
after stop machine time reaches the
preestablished intervals time-1h. All subsequent
lubrication operations will proceed according to
the preestablished time program.
The machine turns off the start switch or
lubrication pump motor is turned off during stop
machine time or lubrication cycle, this cycle will
be terminated, time will be stored. Operation will
proceed from the last stored time when turn on
the start switch again.
227
Lubrication system
Function Operation
Illustration 12-13 Main components Illustration 12-14 Main components (tfhe sample
is CLG856III with 8-bar front frame manual shift
control)
The auto-lubrication setting stop cycle resets When the lubricant level is low, please fill the
automatically after start the manual lubrication lubricant by the following methods.
cycle, the auto-lubrication stop time starts timing
newly after finished manual lubrication cycle. Fill grease with common grease gun
The following components are needed for Fill the lubricant with the common grease gun
realizing this function: through the conical head nipple on the pump.
● Fuse
● Manual lubrication switch
● Instrument system (lubrication fault and work
indication)
● VOGEL centralized lubrication device (with
controller inside the piston pump, pump unit,
progressive feeder, lubricant, straight male
connector, elbow male connector etc).
Illustration 12-15 Conical head grease nipple on
228
Lubrication system
Function Operation
3. Remove the branch line of main feeder System Fault Test and
outlet, turn on the start switch, press the
manual lubrication button once to start the Service
piston pump (don't need to press the manual
lubrication button if the piston pump still runs System work principle general
after turn on the start switch), observe the
removed branch line until there isn't air in the The exterior lines of lubrication system shown as
grease, turn off the start switch, connect the below, the exterior lines are simple.
branch line newly.
No.154 wire from 10A fuse passes XA2 → XK7
4. Empty the oil intake of the secondary feeder, receptacle and provides +24V power to the
oil outlet of the secondary feeder and every lubrication system, grounding after passes
lubrication point according to above method. No.221 wire behind XK7 receptacle. The
5. Assemble all lines after empty each electrical controller inside the lubrication system
component and lines, starts the piston pump, passing XK7 → No.411 wire exports the running
observe each lubrication point by eye until indication signal of lubrication system to
overflowing the grease which shows the instrument system as indication, indicating the
system works normally. instrument system by XK7 → No. 305 wire
output the lubrication system fault indication
The above steps are the empty operation of the signal.
whole system, it is not necessary to empty and
check each system node according to above +24V voltage from 10A fuse reaches the manual
operation if know clearly the position of lubrication switch by No.154 wire, No.154 wire
replacement components or service point or air connects No.470 wire when press the manual
bubble influence position, only empty the front/ lubrication switch, +24V voltage exports the
rear service nodes. manual lubrication indicating singal through
No.470 wire → XK7 → the controller inside the
lubrication system.
Illustration12-18 Lubrication system principle drawing
230
Lubrication system
System Fault Test and Service
If the result does OK, please turn to step 4. a.Adjust the digital multimeter to voltage function
If the result doesn't OK, please turn to step 2. (50V)
b.Pull out the round receptacle of piston pump.
Step 2. Test 10A fuse of centralized Notice the draw and insert method, is there any
lubrication system has melted or not. screw thread?
c.Turn on the start switch, press the manual
a.Turn off the start switch, open the electronic
lubrication button and hold at ON position (need
controller, find the 10A fuse of centralized
another person).
lubrication system, pull it out, and observe its
melting condition by eye. d.Use the digital multimeter red probe to contact
No.3 core of receptacle according to the core
sign of the round receptacle, the black probe
contacts with No.1 core.
231
Lubrication system
System Fault Test and Service
The digital multimeter reading is between 24V If the result does OK, please check the line fault
and 31V. between the manual lubrication button and the
piston pump.
Conclusion:
If the result doesn't OK, please turn to step 7.
If the result does OK, please turn to step 5.
Step 7. Test whether there is +24V voltage in
If the result doesn't OK, please turn to step 6. No.154 wire and No.204 wire of manual
lubrication button.
Step 5. Plug the receptacle newly.
a.Adjust the digital multimeter to voltage function
a.Plug the round receptacle of piston pump (50V).
newly. b.Press the manual lubrication button and hold it
b.Draw and plug XK7 receptacle once. at ON position (need another person), use the
c.Turn on the start switch, press the manual digital multimeter red probe to contact No.154
lubrication button, and judge the piston pump wire, the black probe contacts with No.204 wire
running condition. (or metallic component in the cab).
If the result does OK, the fault has been The digital multimeter reading is between 24V
eliminated. and 31V.
Test result:
Illustration 12-19 12-A-F1 Fault flow chart when the piston pump can't work
233
Lubrication system
System Fault Test and Service
Illustration 12-21 Lubricaiton point position 1 (available for CLG856III with 6-bar front frame)
235
Lubrication system
System Fault Test and Service
Illustration 12-22 Lubrication point postion 2 (available for CLG856III with 6-bar front frame)
The whole lubrication system can not lubricate Disassemble the line connecting this lubrication
once one lubrication point or fault point is point which doubt blocking, clean the oil outlet of
blocked, but piston pump still runs, the safty the safety valve, start the piston pump (by
valve drains oil. pressing the manual lubrication button), observe
the safety valve condition, the removed oil lines
One lubrication point blocks resulting in the
for grease overflow or not. The oil lines have no
safety valve oil drain fault, sometimes, some
problem, this lubrication point has been blocked
lubrication points block also resulting in the fault,
if the safety valve doesn't drain oil and the
so just need your patience when eliminate fault.
grease overflows in the removed oil lines.
Observe the overflow grease from bearing of
It has to spend some time to judge and settle the
lubrication point or mobile parts if the machine is
problem if doesn't know what causes the system
new, which shows the lubrication point is fluent; it
jam, and waster some greases and use
is difficult to judge the lubrication point fluence by
eliminating method to analyse the system fault
aspect if the machine is old or the lubrication
step by step.
point is not easy to observe. The lubrication point
will be blocked due to the mobile parts over-worn
or dirty entering. The worn will be appeared and
give off the sound if the lubricant can't enter in
some lubrication point.
236
Lubrication system
System Fault Test and Service
Step 1. Test whether there is grease (2) The line connected to the main feeder intake
overflows from the outlet of the main feeder has grease overflow when the safety valve
or not? doesn't drain oil.
Step 4. Judge VPKM-8 II level feeder line or Step 6. Use elimination method to inspect
the lubrication point blocks or not. block point on VPKM-8 II level feeder line or
the lubrication point.
a.Turn off the start switch, connect one of
disassembled two lines in step1 to main feeder. a.Turn off the start switch, Mark number on
b.Clean the safety valve outlet, turn on the start VPKM-8 II level feeder oil outlet line according to
switch. lubrication system principle drawing. Then
remove all connecting lines of oil outlet.
c.Press the manual lubrication button, start the
b.Clean the safety valve oil outlet, turn on the
piston pump (this step can be omitted if the
piston pump is running after starting the start start switch. Press the manual lubrication button,
start the piston pump (not need to press the
switch) .
manual lubrication button if the piston pump is
Test result: running after starting the start switch). Observe
the safety valve drains oil or not, grease
Observe the safety valve drains oil or not. overflows from VPKM-8 feeder outlet if the safety
valve doesn't drain oil, please turn to step d.
Conclusion: c.Turn off the start switch if the safety valve
drains oil. Disassemble the oil intake of VPKM-8
If it drains oil, VPKM-8 II level feeder line or the II feeder, clean the safety valve oil drain outlet,
lubrication point blocks, please turn to step 6. turn on the start switch and start the piston
pump, observe oil intake overflows grease or not,
If it doesn't drain oil, please turn to step 5.
the safety valve drain oil. The VPKM-8 has inner
block and clean or replace if the safety valve
Step 5. Judge VPKM-5 II level feeder line or
doesn't drain oil and the oil intake overflows
the lubrication point blocks or not.
grease. The block doesn't appear frequently due
to inner diameter of line is usuall bigger than the
a.Turn off the start switch, connect the other one
safety valve or grease line inside feeder.
of disassembled two lines in step1 to main
feeder. d.Turn off the start switch, connect lines of 22, 23
lubrication points to oil outlet of VPKM-8 II level
b.Clean the safety valve outlet, turn on the start
feeder. Clean the safety valve oil outlet, turn on
switch.
the start switch and start piston pump, observe
c.Press the manual lubrication button, start the the safety valve drains oil or not. Please turn to
piston pump (this step can be omitted if the step e if the safety valve drains oil. If the safety
piston pump is running after starting the start valve doesn't drain oil, please turn to step f.
switch) .
Test result:
Conclusion:
e.If the safety valve drains oil, the block may be Test result:
on 22, 23 lubrication points or lines, perhaps one
point block or two points all block, confirm it in The blocked lubrication point or line can be found
this step. The detais as follows: turn off the start after inspecting all lubrication points.
switch, remove the line connecting 22 lubrication
point, clean the oil outlet, then turn on the start Conclusion:
switch, start the piston pump and observe the
safety valve drains oil or not; if the safety valve Clean and service the blocked lubrication point
drains oil, the block point is on 23 lubrication or line, replace it if necessary.
point or connection line. If the safety valve
doesn't drain oil, the block point is on 22 Step 7. Use the elimination method to inspect
lubrication point or the connection line, not on 23 block point of VPKM-5 II level feeder line or
lubrication point. If the block is on 23 lubrication the lubrication point
point, also need to confirm 22 lubrication point
for block. Turn off the start switch, remove line of a.Turn off the start switch, Mark number on
23 lubrication point and assemble 22 lubrication VPKM-5 II level feeder oil outlet line according to
point, clean the safety valve oil outlet, turn on the lubrication system principle drawing. Then
start switch, start the piston pump, observe the remove all connecting lines of oil outlet.
safety valve drains oil or not, if the safety valve b.Clean the safety valve oil outlet, turn on the
doesn't drain oil, 22 lubrication point doesn't start switch. Press the manual lubrication button,
block, vice visa. start the piston pump (not need to press the
f.Repeat step d, and step e, connect lines of 20 manual lubrication button if the piston pump is
lubrication point, 14 lubrication point and 21 running after starting the start switch). Observe
lubrication point, 17 lubrication point and 18 the safety valve drains oil or not, grease
lubrication point, 15 and 16 lubrication points, 13 overflows from VPKM-5 feeder outlet if doesn't
lubrication point, 11 and 12 lubrication point, 9 drain, please turn to step d.
and 10 lubrication point step by step, connect oil c.Turn off the start switch if the safety valve
outlet line of one distributary piece per time, for drains oil. Disassemble the oil intake of VPKM-5
example, 05S just connects 20 lubrication point, II feeder, clean the safety valve oil outlet, turn on
this step is just as one point, 1T distributary piece the start switch and start the piston pump,
connects 14 and 20 lubrication points, ,this step observe oil intake overflows grease or not, the
has two lubrication points. safety valve oil drain. The VPKM-5 has inner
g.Judge the line or lubrication pont for block after block and clean or replace if the safety valve
finding the block lubrication point line. For doesn't drain oil and the oil intake overflows
example, find 23 lubrication point block after grease. The block doesn't appear frequently due
passing through above checks, turn off the start to inner diameter of line is usuall bigger than the
switch, disassemble the rear swing lubrication safety valve or grease line inside feeder.
point line where 23 lubrication point has reached, d.Turn off the start switch, connect lines of 7, 8
clean the safety valve oil outlet, turn on the start lubrication points to oil outlet of VPKM-5 II level
switch, start the piston pump, observe overflow feeder. Clean the safety valve oil outlet, turn on
grease of disassemble line of 23 lubrication the start switch and start piston pump, observe
point, the safety valve drains oil, the block point the safety valve drains oil or not. Please turn to
is inside 23 lubrication point if the line overflows step e if the safety valve drains oil. If the safety
grease and the safety valve doesn't drain,. 23 valve doesn't drain oil, please turn to step f.
lubrication point blocks if the safety valve drains
and line doesn't overflow grease.
239
Lubrication system
System Fault Test and Service
e.If the safety valve drains oil, the block may be Conclusion:
on 7, 8 lubrication points or lines, perhaps one
point block or two points all block, confirm it in Clean and service the blocked lubrication point
this step. The detais as follows: turn off the start or line, replace it if necessary.
switch, remove the line connecting 7 lubrication
point, clean the oil outlet, then turn on the start
switch, start the piston pump and observe the
safety valve drains oil or not; if the safety valve
drains oil, the block point is on 8 lubrication point
or connection line. If the safety valve doesn't
drain oil, the block point is on 7 lubrication point
or the connection line, not on 8 lubrication point.
If the block is on 8 lubrication point, also need to
confirm 7 lubrication point for block. Turn off the
start switch, remove line of 8 lubrication point
and assemble 7 lubrication point, clean the
safety valve oil outlet, turn on the start switch,
start the piston pump, observe the safety valve
drains oil or not, if the safety valve doesn't drain,
7 lubrication point doesn't block, vice visa.
f.Repeat step d, step e, connect lines of 4 and 6
lubrication points, 3 and 5 lubrication points, 2
lubrication point, 1 lubrication point step by step,
connect oil outlet line of one distributary piece
per time, for example, 3S just connects one
lubrication point, this step is just as one point, 1T
distributary piece connects two lubrication points,
this step has two lubrication points.
g.Judge the line or lubrication pont for block after
finding the block lubrication point line. For
example, find 8 lubrication point block after
passing through above checks, turn off the start
switch, disassemble the rear swing lubrication
point line where 8 lubrication point has reached,
clean the safety valve oil outlet, turn on the start
switch, start the piston pump, observe overflow
grease of disassemble line of 8 lubrication point,
the safety valve drain, the block point is inside 8
lubrication point if the line overflows grease and
the safety valve doesn't drain,. 8 lubrication point
blocks if the safety valve drains and line doesn't
overflow grease.
Test result:
Illustration 12-23 12-A-F3 Safety valve oil drain fault test flow chart (suitable for CLG856III with 6-bar
front frame)
12-A-F3 Safety valve oil drain fault test The lubricant drains from the safety valve after
(suitable for CLG856III with 8-bar front frame) starting the piston pump which shows the
lubrication system has block and makes the
Fault phenomenon definition: system pressure higher than 300 bar, the safety
valve drains oil automatically.
241
Lubrication system
System Fault Test and Service
Fault test steps: Analyze the safety valve fault of draining oil
according to occurrence probability after
Check the grease qualiity firstly, most of non- eliminating the grease quality question. Firstly,
lubrication point block faults are caused by oil check the lubrication point block condition;
quality. The grease dirty, rigid, cold weather or secondly, check progressive feeder block
parking machine for a long time will change the condition; finally, check the line block condition.
grease quality, and lead to extortionate system
pressure. The piston pump will idle and can't
drain oil if the grease quality is too rigid.
Illustration 12-24 Lubrication system assembly principle drawing (suitable for CLG856III with 8-bar front
frame)
242
Lubrication system
System Fault Test and Service
Illustration 12-25 Lubrication point position 1 (suitable for CLG856III with 8-bar front frame)
243
Lubrication system
System Fault Test and Service
Illustration 12-26 Lubrication point position 2 (suitable for CLG856III with 8-bar front frame)
244
Lubrication system
System Fault Test and Service
The main feeder blocks if the result is the same Test result:
to the second condition.-Disassemble the main
feeder to clean or replace, assemble it again Observe the safety valve drains oil or not.
after eliminating fault. Drain out the main feeder
firstly after assemble it, and then assemble the Conclusion:
oil outlet and intake of the main feeder after drain
out. If it drains oil, VPKM-8 II level feeder line or the
lubrication point blocks, please turn to step 6.
Step 3. Judge the safety valve blocks or not.
If it doesn't drain oil, please turn to step 5.
a.Turn off the start switch, and disassemble the
Step 5. Judge VPKM-10 II level feeder line or
outlet oil line of the safety valve. the lubrication point blocks or not.
b.Clean the oil outlet of the safety valve, turn on
the start switch. a.Turn off the start switch, connect the other one
c.Press the manual lubrication button, start the of disassembled two lines in step1 to main
piston pump (this step can be omitted if the feeder.
piston pump is still running after turning on the b.Clean the safety valve outlet, turn on the start
start switch) switch.
c.Press the manual lubrication button, start the
Test result:
piston pump (this step can be omitted if the
piston pump is running after starting the start
Observe the safety valve drains oil or not.
switch) .
Conclusion:
Test result:
If it drains oil, please clean or replace the safety
Observe the safety valve drains oil or not.
valve, assemble it after eliminating fault. Drain
out the safety valve firstly after assemble it, fixing
Conclusion:
the line after draining out the safety valve.
If it doesn't drain oil, please clean the line when If it drains oil, VPKM-10 II level feeder line or the
there is block in line from the safety valve to the lubrication point blocks, please turn to step 7.
main feeder, drain out the line firstly after
If it doesn't drain oil, the system is good, no
assembly, fixing the line again after draining out
block, and can work normally.
the safety valve.
Step 6. Use elimination method to inspect
Step 4. Judge VPKM-8 II level feeder line or
block point on VPKM-8 II level feeder line or
the lubrication point blocks or not.
the lubrication point.
a.Turn off the start switch, connect one of
a.Turn off the start switch, Mark number on
disassembled two lines in step1 to main feeder.
VPKM-8 II level feeder oil outlet line according to
b.Clean the safety valve outlet, turn on the start lubrication system principle drawing. Then
switch. remove all connecting lines of oil outlet.
c.Press the manual lubrication button, start the
piston pump (this step can be omitted if the
piston pump is running after starting the start
switch) .
246
Lubrication system
System Fault Test and Service
b.Clean the safety valve oil outlet, turn on the f.Repeat step d, step e, connect lines of 30 and
start switch. Press the manual lubrication button, 31 lubrication points, 29 lubrication point, 27 and
start the piston pump (not need to press the 28 lubrication points, 25 and 26 lubrication
manual lubrication button if the piston pump is points, 23 and 24 lubrication points, 21 and 22
running after starting the start switch). Observe lubrication points, 19 and 20 lubrication points
the safety valve drains or not, grease overflows step by step, connect oil outlet line of one
from VPKM-8 feeder outlet if the safety valve distributary piece per time, for example, 05S just
doesn't drain oil, please turn to step d. connects 29 lubrication point, this step is just as
c.Turn off the start switch if the safety valve one point, 2T distributary piece connects two
drains oil. Disassemble the oil intake of VPKM-8 lubrication points, this step has two lubrication
II feeder, clean the safety valve oil outlet, turn on points.
the start switch and start the piston pump, g.Judge the line or lubrication pont for block after
observe oil intake overflows grease or not, the finding the block lubrication point line. For
safety valve drain oil. The VPKM-8 has inner example, find 33 lubrication point block after
block and clean or replace if the safety valve passing through above checks, turn off the start
doesn't drain oil and the oil intake overflows switch, disassemble the rear swing lubrication
grease. The block doesn't appear frequently due point line where 33 lubrication point has reached,
to inner diameter of line is usuall bigger than the clean the safety valve oil outlet, turn on the start
safety valve or grease line inside feeder. switch, start the piston pump, observe overflow
d.Turn off the start switch, connect lines of 22, 23 grease of disassemble line of 33 lubrication
lubrication points to oil outlet of VPKM-8 II level point, the safety valve drain, the block point is
feeder. Clean the safety valve oil outlet, turn on inside 33 lubrication point if the line overflows
the start switch and start piston pump, observe grease and the safety valve doesn't drain,. 33
the safety valve drains oil or not. Please turn to lubrication point blocks if the safety valve drains
step e if the safety valve drains oil. If the safety and line doesn't overflow grease.
valve doesn't drain oil, please turn to step f.
Test result:
e.If the safety valve drains oil, the block may be
on 32, 33 lubrication points or lines, perhaps one The block lubrication point or line can be found
point block or two points all block, confirm it in after inspecting all lubrication points.
this step. The detais as follows: turn off the start
switch, remove the line connecting 32 lubrication Conclusion:
point, clean the oil outlet, then turn on the start
switch, start the piston pump and observe the Clean and service the blocked lubrication point
safety valve drains oil or not; if the safety valve or line, replace it if necessary.
drains oil, the block point is on 33 lubrication
point or connection line. If the safety valve Step 7. Use the elimination method to check
doesn't drain oil, the block point is on 32 the block point of VPKM-10 II level feeder line
lubrication point or the connection line, not on 33 or the lubrication point.
lubrication point. If the block is on 33 lubrication
point, also need to confirm 32 lubrication point a.Turn off the start switch, Mark number on
for block. Turn off the start switch, remove line of VPKM-10 II level feeder oil outlet line according
33 lubrication point and assemble 32 lubrication to lubrication system principle drawing. Then
point, clean the safety valve oil outlet, turn on the remove all connecting lines of oil outlet.
start switch, start the piston pump, observe the
safety valve drains oil or not, if the safety valve
doesn't drain, 32 lubrication point doesn't block,
vice visa.
247
Lubrication system
System Fault Test and Service
b.Clean the safety valve oil outlet, turn on the f.Repeat step d, step e, connect lines of 15 and
start switch. Press the manual lubrication button, 16 lubrication points, 13 and 14 lubrication
start the piston pump (not need to press the points, 11 and 12 lubrication points, 9 and 10
manual lubrication button if the piston pump is lubrication points, 7 and 8 lubrication points, 5
running after starting the start switch). Observe and 6 lubrication points, 3 and 4 lubrication
the safety valve drains oil or not, grease points, 2 lubrication point, 1 lubrication point step
overflows from VPKM-10 feeder outlet if the by step, connect oil outlet line of one distributary
safety valve doesn't drain oil, please turn to step piece per time, for example, 2S just connects
d. one lubrication point, this step is just as one
c.Turn off the start switch if the safety valve point, 1T distributary piece connects two
drains oil. Disassemble the oil intake of VPKM- lubrication points, this step has two lubrication
10 II feeder, clean the safety valve oil outlet, turn points.
on the start switch and start the piston pump, g.Judge the line or lubrication pont for block after
observe oil intake overflows grease or not, the finding the block lubrication point line. For
safety valve drain oil. The VPKM-10 has inner example, find 18 lubrication point block after
block and clean or replace if the safety valve passing through above checks, turn off the start
doesn't drain oil and the oil intake overflows switch, disassemble the rear swing lubrication
grease. The block doesn't appear frequently due point line where 18 lubrication point has reached,
to inner diameter of line is usuall bigger than the clean the safety valve oil outlet, turn on the start
safety valve or grease line inside feeder. switch, start the piston pump, observe overflow
d.Turn off the start switch, connect lines of 17, 18 grease of disassemble line of 18 lubrication
lubrication points to oil outlet of VPKM-10 II level point, the safety valve drain, the block point is
feeder. Clean the safety valve oil outlet, turn on inside 18 lubrication point if the line overflows
the start switch and start piston pump, observe grease and the safety valve doesn't drain,. 18
the safety valve drains oil or not. Please turn to lubrication point blocks if the safety valve drains
step e if the safety valve drains oil. If the safety and line doesn't overflow grease.
valve doesn't drain oil, please turn to step f.
Test result:
e.If the safety valve drains oil, the block may be
on 17, 18 lubrication points or lines, perhaps one The blocked lubrication point or line can be found
point block or two points all block, confirm it in after inspecting all lubrication points.
this step. The detais as follows: turn off the start
switch, remove the line connecting 17 lubrication Conclusion:
point, clean the oil outlet, then turn on the start
switch, start the piston pump and observe the Clean and service the blocked lubrication point
safety valve drains oil or not; if the safety valve or line, replace it if necessary.
drains oil, the block point is on 18 lubrication
point or connection line. If the safety valve
doesn't drain oil, the block point is on 17
lubrication point or the connection line, not on 18
lubrication point. If the block is on 18 lubrication
point, also need to confirm 17 lubrication point
for block. Turn off the start switch, remove line of
18 lubrication point and assemble 17 lubrication
point, clean the safety valve oil outlet, turn on the
start switch, start the piston pump, observe the
safety valve drains oil or not, if the safety valve
doesn't drain, 17 lubrication point doesn't block,
vice visa.
248
Lubrication system
System Fault Test and Service
Illustration 12-27 12-A-F3 Safety valve oil drain test flow chart (suitable for CLG856III with 8-bar front
frame)
12-A-F4 Other faults test block after the lubrication point or line damage.
The faults of lubrication point or lubrication line
The most faults of the lubrication system are due
can be checked out by eye. So please foster the
to lubrication line damages except for above
habit to observe the lubrication point or line by
faults. The lubricant will overflow from damaged
eye after driving or operating the machine, in
point, can't reach the lubrication point, some may
order to find the faults as soon as possible.
249
Lubrication system
System Fault Test and Service
12-B-F Fault test when the manual lubrication Step 2. Test whether there is +24V voltage in
function can't start the piston pump. No.470 wire of the manual lubrication switch.
Fault phenomenon definition: a.Insert red probe of the digital multimeter to the
corresponding copper piece of No.470 wire of
There is no problem of the lubrication system No.8 core on the back of the manual lubrication
normal lubrication periodic running, but the switch, black probe contacts with the machine
piston pump can't be started even if pressing the metal housing.
manual lubrication button. b.Press the manual lubrication switch and hold it.
The manual lubrication switch is installed on 4- c.Release the manual lubrication switch after
joint switch combination of the panel. Turn on the measurement.
start switch, observe the piston pump of the
lubrication system for running, if running, wait for Test result:
finishing one lubrication period, the stop running
period is coming, inspect according to the The digital multimeter reading is between 24V
following steps. and 31V.
Step 1. Test whether there is +24V grounding Conclusion:
voltage in No.154 wire of the manual
lubrication switch. If the result does OK, please turn to step 3.
a.Turn off the start switch, and disassemble the If the result doesn't OK, the manual lubrication
left panel from the instrument. Push 4-joint switch is damaged, please replace it.
pendant switch out from the socket groove, don't
damage the buckle of the integration switch Step 3. Test whether there is +24V voltage in
when take it out. No.470 wire and No.211 wire of XK7
receptacle (need another person).
b.Adjust the digital multimeter to 50V range of
voltage function. a.Turn off the start switch, pull out XK7
c.Turn on the start switch, insert red probe of the receptacle under the steering column of the cab,
digital multimeter into the corresponding copper measuring direction is from the cab harness
piece of No.154 wire of No.8 core receptacle on connecting XK7 receptacle.
the back of the manual lubrication switch, black b.Use red probe of the digital multimeter to
probe contacts with the machine metal housing. connect the corresponding No.2 core of No.470
line, and use black probe to connect the
Test result:
corresponding No.5 core of No.221 line.
The digital multimeter reading is between 24V Test result:
and 31V.
The digital multimeter reading is between 24V
Conclusion:
and 31V.
If the result does OK, please turn to step 2.
If the result doesn't OK, the line from 10A fuse to
No.154 wire of the manual lubrication switch has
fault. Pull & insert XJ1 receptacle newly, pull
No.154 wire of XJ1 receptacle two terminals by
hand, judge the connecting condition between
the inner piece and lead.
250
Lubrication system
System Fault Test and Service
Conclusion:
38B0075 Horn
Illustration 13-1 Horn
Horn relay
252
Horn and lighter
Fault check steps of the Lighter
Main Component
When install and use the lift mechanism, When install and use the lift mechanism, two
please keep the pivots of two hinges in the hinges need to fill up the lubrication.
same line and plumb with the fixing holes of
two pivots. Two hinges don't have blocked Hood lift controller
phenomenon after installation.
Illustration 16-2 Hood lift controller outline and principle drawing symbol
VIEW A
RED (+) WHITE (MOTOR-)
The hood lift controller is the special controller of Illustration 16-3 Breaker and principle drawing
the lift mechanism which is used to control the symbol
positive and negative journey (lift or lower). The
lift controller is composed by relays.
Breaker
A 40A auto-return breaker is used in this
machine for controlling the hood lift mechanism.
The breaker will be off and then return according
to the current state when the lift system is
electrified.
258
Electrical Lift System
Main Components
3. Use the digital multimeter probes to connect Illustration 16-6 Lift mechanism and lift control
the middle receptacle and another receptacle box
of the lift switch separately, move and hold
the lift switch along another receptacle
connected to the probe. The digital
multimeter reading is 0.
4. Release the lift switch, it resets automatically,
hold the probe connecting with the middle
receptacle of the lift switch, another probe
connects to another receptacle of the lift
switch, move and hold the lift switch along
reverse direction of step 3. The digital
multimeter reading is 0.
5. The lift switch which can complete these test
steps successfully is good. Otherwise it is
damaged.
Function Operation
d.Pull out XG9 receptacle, use the red probe of Step 4. Test 5A fuse has melted or not?
the digital multimeter to contact No.492 wire
corresponding receptacle of XG9 receptacle a.Open the single circuit fuse box, observe 5A
(wiring harness terminal), the black probe fuse has melted or not.
contacts with No.255 wire corresponding
receptacle of XG9 receptacle, pay attention not Conclusion:
to contact these two probes with each other.
If it has melted, please turn to step 5.
Test result:
If it doesn't melt, please turn to step 6.
The digital multimeter reading is between 24V
and 31V. Step 5. Replace with new 5A fuse.
Conclusion:
Others
5 Cover
6 Rear window 0 Green
washer I ① --- ⑤ Yes
Lock Special
No. Name Instruction Reset Illustration Color
buckle instruction
1 Quick coupler 0 Lock Red
unlock switch I ① --- ⑤
3 Cover
4 0 Yellow
I ① --- ⑤ Lock
② --- ⑥
Pendant Combination Switch
Lock Special
No. Name Instruction Reset Illustration Color
buckle instruction
1 Diagnostic ON/ 0 Lock Green
OFF switch I ① --- ⑤ DIAG
2 Idle/diag I ① --- ③ Yes ID L E Green
(diagnostic)inc / 0 D IA G
dec switch II ③ --- ⑦ Yes
3 Rear floodlight 0 Blue
switch I ① --- ⑤