Nothing Special   »   [go: up one dir, main page]

ORIFICE Plate Calculation

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 5

30 bar shower water

Orifice plate dimensioning


30 bar

Flow target Pressure in Pressure out


Pump capacity
17 l/s 300 mWC 0 mWC
By-pass required
10 %
Minimum flow through pump
1.7 l/s

Pressure in 3000000 Pa
Pressure out 0 Pa
Area in 0.0001767144375 m2
Area orifice 0.0000196349375 m2
density 1000 kg/m3
factor 0.97

Flow 1.565 l/s

Page 1
30 bar shower water

Area 1 Orifice Area


Pipe dia Dia
15 mm 5 mm
0.015 m 0.005 m
0.000177 m2 1.96E-05 m2

Page 2
Sealing water

Orifice plate dimensioning


sealing water

Flow target Pressure in Pressure out Area 1 Orifice Area


Pump capacity Pipe dia Dia
1 l/s 100 mWC 0 mWC 40 mm 4 mm
By-pass required 0.04 m 0.004 m
60 % 0.001257 m2 1.26E-05 m2
Minimum flow through pump
0.6 l/s

Pressure in 1000000 Pa
Pressure out 0 Pa
Area in 0.001257 m2
Area orifice 1.26E-05 m2
density 1000 kg/m3
factor 0.97

Flow 0.548 l/s

Page 3
10 bar shower water

Orifice plate dimensioning


10 bar shower water

Flow target Pressure in Pressure out


Pump capacity
20 l/s 100 mWC 0
By-pass required
8 %
Minimum flow through pump
1.6 l/s

Pressure in 1000000 Pa
Pressure o 0 Pa
Area in 7.85E-05 m2
Area orific 2.83E-05 m2
density 1000 kg/m3
factor 0.97

Flow 1.534 l/s

Page 4
10 bar shower water

Pressure out Area 1 Orifice Area


Pipe dia Dia
mWC 10 mm 6 mm
0.01 m 0.006 m
7.85E-05 m2 2.83E-05 m2

Page 5