BUILDING WIRES - Single Core Wires

Cables specified in this table are intended for use in Conductor


Application
fixed installations for power and lighting.The
insulation and other components are suitable to
permit operation of the cables at a maximum
sustained conductor temperature of 70 °C.
Type Cu/PVC/PVC Fire Guard
Insualtion
Standards BS 6004:2012 , SLS733

Nominal Voltage 300/500V


Insulation 70 °C rated PVC compound
Sheath
Sheathing PVC compound
Packing Supplied in coils of 100 meters or as per customer
requirement
Conductor Soft annealed copper wires

ITEM N.C NO/NOM INSU. INSU. SHEATH SHEATH Maximum DC Packing


CODE AREA DIA. THICK. O.D. THICK. O.D Resistance Drum Cable
mm2 mm mm mm mm mm Ohm/km Type Length

A - 95 1 1/1.13 0.60 2.31 0.8 3.91 18.10 Coil 100m


A- 96 1.5 1/1.38 0.70 2.77 0.8 4.37 12.10 Coil 100m
A- 96 sub 1.5 7/0.53 0.70 2.96 0.8 4.56 12.10 Coil 100m
A - 97 2.5 1/1.78 0.80 3.37 0.8 4.97 7.41 Coil 100m
A - 97 sub 2.5 7/0.67 0.80 3.58 0.8 5.18 7.41 Coil 100m
A - 98 4 7/0.85 0.80 4.12 0.9 5.92 4.61 Coil 100m
A - 99 6 7/1.04 0.80 4.72 0.9 6.52 3.08 Coil 100m
A - 100 10 7/1.35 1.00 6.05 0.9 7.85 1.83 Coil 100m
A - 101 16 7/1.70 1.00 7.10 1 9.1 1.15 Coil 100m
A - 102 25 19/1.35 1.20 9.15 1.1 11.35 0.727 Coil 100m
A - 102 sub 25 7/2.14 1.20 8.82 1.1 11.02 0.727 Coil 100m
A - 103 35 19/1.53 1.20 10.05 1.1 12.25 0.524 Coil 100m

ACL Cables PLC


A: 60,Rodney Street, Colombo 08, Sri Lanka | P: +94 117 608 300 /+94 11 2697 652 | F: +94 112 699 503 | E: info@acl.lk