Heatload Calculation HVAC

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4
At a glance
Powered by AI
The document contains calculations for heat gain and load for an accounting section located on the ground floor of a building.

The different sections covered include sensible heat gain from glasses, walls and roof, transmission gain from other elements, internal and latent heat gains, and outdoor conditions.

The factors considered for calculating the sensible heat gain include sun gain factor, equivalent temperature difference factor and area for different glasses, walls, roof and other elements.

Job Name : NSDC Chennai

Floor : Ground Floor


Space : Account Section

SENSIBLE HEAT
SOLAR GAIN GLASS HEAT GAIN
Item Area Sun Gain Factor Btu/hr
(Sq ft) (Btu/h.sq ft)
N-Glass 0 0
NE-Glass 0 0
E-Glass 0 0
SE-Glass 0 0
S-Glass 0 0
SW-Glass 0 0
W-Glass 0 0
NW-Glass 0 0
Skylight 0 0
SOLAR & TRANS. GAI WALLS & ROOF
Item Area Eq. Temp. Diff. Factor
(Sq ft) (°F)
N-Wall 0 0
NE-Wall 0 0
E-Wall 0 0
SE-Wall 0 0
S-Wall 0 0
SW-Wall 0 0
W-Wall 0 0
NW-Wall 0 0
Room Sun 0 0
Roof Shaded 0.00 0
TRANS. GAIN EXCEPT WALLS & ROOF
Item Area Eq. Temp. Diff. Factor
(Sq ft) (°F)
All Glasses 0 25.9 0
Partition Wall 0 20.9 0
Ceiling 0.00 20.9 0
Floor 875.90 20.9 0.44 8054.7764
INTERNAL HEAT GAIN
People 15 Heat Gain 276 4140
Light 1.38 Area 875.90 4109.7228
Eq. Load 1313.85 W 3.4 4467.09
OUTSIDE & INFILTRATION AIR
CFM Δ°F BF FACTOR
127.55 25.9 0.1 1.08 356.7940488
SAFETY FACTOR
Supply Duct heat Supply Duct leak
Heat Gain From fan HP (%) 1690.270659904
gain + loss +

8% 5.00% 1056.41916244
EFFECTIVE ROOM SENSIBLE HEAT (ERSH ) 23875.073071144
LATENT HEAT
People 15 Heat Gain 231 3465
OUTSIDE & INFILTRATION AIR
CFM Δ Grains BF FACTOR
127.55 79.1 0.1 0.68 686.0874552
ROOM LATENT HEAT
Supply Duct leakage loss + Safety Factor (%) 207.55437276
5.00%
EFFECTIVE ROOM LATENT HEAT (ERLH) 4358.64182796
EFFECTIVE ROOM TOTAL HEAT (ERTH) 28233.714899104

OUTDOOR HEAT
CFM Δ°F / Grains CF=1-BF FACTOR
SENSIBLE 127.554 25.9 0.9 1.08 3211.1464392
LATENT 127.554 79.1 0.9 0.68 6174.7870968
HEAT SUB TOTAL
Return Duct
Heat Gain & HP Pump + 5% 1880.9824217552
Leak Loss +

GRAND TOTAL HEAT 39500.630856859


Area ft² 875.90
Volume ft³ 10481.8953
Height ft 11.967

AIR QUANTITY
Condition DB (°F) WB (°F) % RH GR / LB
Outside 97.9 82.4 143.7
Room 72 55 64.6
Difference 25.9 79.1

OUTSIDE AIR (VENTILATION)


(cfm/person × No. of persons) + (0.06 × Area sq ft)
Fresh Air 5 15 52.554 127.55

Effective Room Sensible Heat Factor


ESHF 23875.07 28233.71 0.845622800841616

ADP
Selected ADP 52

Dehumidifide Rise
Dehumidifide Rise 18

Dehumidifide Air Flow


Dehumidifide Air Flow 1228.14161888601

Tonnage
TR 3.2917192380716

CORRECTION FACTOR
BYPASS FACTOR 0.1
75 CFM
25.9 S.TEMP

19.44 deno
N-Wall 0
NE-Wall 0
E-Wall 0
SE-Wall 0
S-Wall 0
SW-Wall 0
W-Wall 0
NW-Wall 0
Room Sun 0
Roof Shaded 0

Add 21128.38
Room -72

-52 ADP
20

-0.1
`