Electrical Grounding
Electrical Grounding
Electrical Grounding
Building grounding
In the construction of most commercial buildings, one ground is usually run throughout
the building to keep the impedance as low as possible. Low impedance in the ground is
needed to makse sure that the the fuse blows when something gets short circuited to
ground wire (for example cable insution breaks inside the equipment and touches the
grounded metal case). The grounding system is primarily designed for electrical safety
in mind. The Protective Earth connection should be able to carry a heavy current to
protect the user from live-to-chassis faults by ensuring that the fuse or circuit breaker
will operate so the requirement is that the Protective Earth conductors can carry a 25A
fault current for at least 1 minute. The grounding system in the building electricity
distribution has only effect on the electromagnetic environment inside the building
which you must understand.
Unfortunately all building have big electrical equipment such as air conditioning units,
refrigerators, washers/dryers and other high current devices connected to the building
ground (the same ground you use for your AV system). Computers and other
equipments which use stiched power supplies generate harmonics to the electrical
power which usually end up being noise in the gounding system. Light dimmers are also
a storng source of interference and some of it typically ends to the ground wires also.
Thus the chances of getting a clean ground in a typical audio visual installation is slim,
especially in large commercial buildings, hotels, hospitals or convention centers.
For those not aware of the MEN system, the neutral bar is connected to an earthing
stake driven into the ground as near as possible to the customer's switchboard. All earth
wiring from power points, etc, is connected to the neutral bar. In the UK the same
practice is called Protective Multiple Earthing (PME). With P.M.E. the neutral and earth
conductors of the supply are combined. The supply company connects the neutral
solidly to earth frequently throughout the distribution network. At the customer's
connection point the company supplies an 'earth' (which is actually connected to the
neutral) to which all the installation earths and equipotential bonding are connected.
Another approach to bring grounding to the building is to bring it through armouring of
the supply cable. If the electricity company cannot easily supply or guarantee an
adequate earth conductor (for example supply comes on a pair of overhead wires), the
ser is generally responsible for the adequacy of the earth electrode. The method of
earthing can normally be found out by tracing the wiring from the meter/consumer unit.
It is usually fairly obvious.
How safe or unsafe MEN or PME is depends on the rules which cover its application, and
the record of the supply utility in avoiding neutrals going open circuit.
The key word in the titles is MULTIPLE. The exact situation will vary dramatically
depending on where the break in the neutral occurs. If it is just outside the substation,
then the neutral conductor will be replaced by all of the multiple earths in parallel, and
providing the load is balanced over the three phases, the voltage disturbance will not be
too serious.
When the supply company neutral goes open, the neutral return is via the earth stake.
Soil types here range from sand to loam to clay to rock, so the ground stake can range
from a good to a very poor earth. The voltage from each active to the "neutral" will
depend on the loads on each phase and the ground resistance.
The worse the balancing of your load over the three phases, the worse the voltage
disturbance will be. If we assume that the earthing spike has a resistance of 100 ohm, it
is pretty clear that your equipment is not going to work, but your neutral and earthed
metal work is going to rise to something near to phase voltage. This sound horrific, but
is actually not dangerous provided that all earthed metal work is nicely bonded, and
there are no unbonded earthed objects around that are better earths than your earth
spike.
For ground wire routing the electrical installation regulations worldwide generally state
that the ground wires should be routed on the same route than the mains curren
carrying wires going to the same outlet or distribution panel. This is the most often used
practice. Usually the safety ground is a separate yellow/green wire in the cable and
sometimes it is a separate wire in the same cable bundle (for example for 3 phase
distribution you might see sometimes a 4 or 5 wire cable and a separate safety ground
cable bundled on the side of the cable). In some countries (for example in USA) in some
case the metallic piping used to protect the mains carrying wire inside the walls can be
used as safety ground conductor (not usually very good or reliable in practice I think,
but is allowed in some cases).
However, the California Public Utilities Commission has specified that the service voltage
shall be kept in the range 114-120V, with some exceptions. This was done because
some studies showed a reduction in energy consumption at the lower voltages.
Information on NEMA plug configurations is available in NEMA Configuration Chart, Form
No. H4513. For availability check http://www.hubbell-wiring.com/.
his is really a fudge and means there is no real change of supply voltage, only a change
in the "label", with no incentive for electricity supply companies to actually change the
supply voltage.
To cope with both sets of limits an equipment will therefore need to cover 230V +/-10%
i.e. 207-253V. This will actually become the official limit for the whole of the EU in
2003.
This three phase power system is called THREE-PHASE STAR; FOUR-WIRE; EARTHED
NEUTRAL system. This is the most common way used in European wiring systems (and
used almost everywhere in Finland), but note that three-phase distribution circuits come
in several flavours. There is a distinct difference between those in the US and those in
Europe. They are classified as follows:
• TN: Transformer star point earthed. Protective Earth and Neutral share the
"ground" conductor (PEN) and are separated at the fuse panel. This circuit is
also referred to as TN-C (C for common PE and N). In UK this is called TN-C-S
(i.e. combined in supply and separate in the installation), and it is also referred
to as Protective Muliple Earthing (PME - as the PEN supply conductor is grounded
at regular intervals along the supply).
• TN-S: As above, but PE and N are brought separatley all the way from the
earthed transformer and never allowed to get into contact with each other
elsewhere. The idea is that PE shall never carry any current (it shall
consequently not carry any potential and is supposed to be very "clean". All
return currents go through the N conductor all the way to the transformer star
point. This system has become very popular in new installations in Europe and
has been a standard in hospitals for a long time.
• IT: The transformer is not erthed at all. The star point floats. Mostly used in
heavy and process industry where continued operation - even if there is an earth
fault - is required. The more common (european) voltages in these systems are
500 V and 690 V. In this case housing of the objects are connected to local
grouns.
• TT: Transformer and objects have separate grounds. Common in US.
Typically there are 4 wires routed to every house for 3 phase feed. Those are typically
them are labeled R, S, and T, the fourth being ground. The phase shift between R and S
are 120 deg., the same phase shift exists between S and T and between T and R. The
voltage difference between the live phases is 400 V, the voltage difference between any
live phase and ground is around 235 V. The usual household power outlet connection
uses one phase and ground. Three phase is usally used only on some permanetly wired
high power loads (typically ovens and electric stoves in normal household). A typical
rating for mains fuse in typical household in Finland which has three phase power is
3x25A (25A per phase).
If three phase connector is avaible some heavy equipments (in places where heavy
machinery is used), then the most common one available is 3x16A connection.
So if the outlest are very lightly loaded, you will get nearly 120V and if wiring hevily
loaded, the voltage drops to around 110V. In Europe the frequency is 50 Hz and voltage
on the outlet is nowadays is 230V (the real voltage typically is between 220V and
240V).
In USA the domestical service has typically 3 wires: 2 hots and a neutral. The voltage
between the 2 hots is 240 and the voltage from either hot to the neutral is 120 (half).
Normal electrical outlets are connected between the neutral and one hot wire. Some
heavy loads (like air conditioners) are connected between those two hot wires and
receive the full 240V load.
All office equipment requires only the hot and neutral wires to function. The third or
grounding wire is connected to exposed metal parts on the equipment. Within the
building, the grounding connections of all electrical receptacles are wired to one another
and are connected to the water piping. This ensures that all electrical equipment with
exposed metal parts has these parts electrically connected to each other and to exposed
metal fixtures in the building such as water fixtures.
The hot and neutral wires are interchangeable as far as the equipment is concerned (be
warned that there are some exceptions in some countries). Both are power carrying
wires. One of the power carrying wires is grounded for reasons of safety. In many parts
of Europe (nordic counties, Germany etc), the normal 3-wire receptacle is symmetrical
so that the neutral and hot wire connections can be swapped by simply rotating the
plug.
Grounding (Green or green/yellow) means that it's there to tie all of the stray metal
parts together so that (hopefully) none of them can get to where they'll make a hazard.
A far better term for this wire is that it is the "Bonding" conductor. Grounding wire
should NEVER be asked to carry current.
Do not thrust the color coding unless you know under which standard the wiring is
done. There some some other color codes also in use. Inside of any electronic
equipment, it is dangerous to trust any color codes unless you know which "Standard"
that unit was built under.
The practice where safery ground is connected using the same conductor as neutral is
called PEN (TN-C) and practice where there is separate ground wire in whole system is
called PE (TN-S).
Circuit breaker boxes: The main breaker box to the building is the single location where
the neutral and the ground wires come together. The electrical service will be grounded
at this point. IN ALL DOWNSTREAM BREAKER BOXES BOTH THE NEUTRAL AND GROUND
WIRES MUST BE KEPT APART FROM ONE ANOTHER. Otherwise you will have neutral
currents flowing on the ground wire. This is extremely important and is a major safety
and signal issue.
These simple rules apply to ALL cabling including CATV, Video, AC and signal. One
exception is the ethernet. Ground the computer LAN one end (preferably to the same
point as your audio system) and make sure that the thin ethernet connector metal parts
do not touch any parts of computer case (there are nice plastic isolation cases available
for them). I would recommend to use 10 Base-T ethernet which used twisted pair wiring
because it does not need any grounding and does not cause ground loops in any case.
Many new buildings in USA are equipped with "Isolated ground" receptacles. These are
normally recognizable because they are bright orange and have a triangle marked on
the face. Basically, these receptacles have a separate "green wire" equipment ground,
and the wire goes back directly to the circuit breaker panel, without being connected to
anything else. Isolated ground receptacles are installed in the hope that electrical noise
generated in the building, or by other pieces of equipment, will not disturb the operation
of delicate computer equipment plugged into them.
As far as what the NEC allows, an isolated ground is a grounding connection which is
grounded only at the separately derived system from which the circuit is supplied. It is
permitted to pass through panelboards, junction boxes, etc. without being bonded to
the equipment grounding conductor which serves those devices, thus minimizing
electromagnetic interference. It must be used in conjunction with an isolated grounding
receptacle to be effective. More details of isolated ground can be found at NEC 250-74
Exc #4.
All outside service grounds must be solidly connected to this ground point, including
power, telephone and cable television. For lightning protection, any antenna masts
should be grounded here as well. Ground connection points from the telephone system
controller, security alarm panel, audio equipment and other electronics gear should be
connected to this ground buss. All distribution of 3 phase voltage inside of building
should be done using 5 wire system. Distribution of 1 phase power should be done using
3 wire system. The safety ground wires should be interconnected in star or tree like
fashion. For more information check Residential Wiring and Grounding Guidelines from
Power Clinic.
If possible, all electronics and computer equipment should have a separate isolated
electrical subpanel with isolated ground receptacles provided at all locations remote
from the main. Isolated ground means that the ground wiring is otherwise isolated form
all other wiring except that it is connected to the main grounding bar for one single
point. This practice will ensure that all electronic equipment grounds are at the exact
same electrical potential and avoid the "minute differences" in grounds that cause
ground loops. These differences are reflected in signal-carrying conductors or shields
between the components and may be amplified to audible or visible levels.
Components that cannot have "equal-potential" grounds should have signals that are
isolated from each other. This can be expensive and difficult to achieve. It is much
easier to prevent the problems in the first place when designing the electrical
distribution. More information on that is available from Equitech articles: Power
Management in the Studio, Audio Wiring and Grounding, 1996 National Electrical Code
Technical Support Bulletin and Installing a Technical Grounding System. Those articles
provide you understanding how to make good grounding system for studio.
Do not try to modify your electrical wiring yourself. When you know what needs to be
done call professionals to do the job properly (you might need a special consultant to do
the plans for modifications because standard electricians don't usually know all the
special requirements audio studio has). When you have proper groundung system in
your studio then you can start doing the the audio wiring in a right way. You can easily
easily make your system very sensitive to power system noise if you do not do the
wiring properly. Rane application note Sound System Interconnections gives you good
undertanding how the audio connections should be done.
The problem is that in many cases you don't have possiblity to change the electrical
distrubution system already in the place, because it will come hard to do and expensive.
Then you have to live with what you get and try to solve those problems with suitable
isolation devices.
Improper grounding can create a lethal hazard. Even if you advert danger,
ground loops are the most common cause of AC line frequency hum in sound
systems. So it pays to learn about grounding, and use what you learn.
A ground loop occurs when there is more than one ground connection path
between two pieces od equipment. The duplicate ground paths form the
equivalent of a loop antenna which very efficiently picks up interference
currents. Lead resistance transforms these currents into voltage fluctuations. As
a consequence of ground loop induced voltages, the ground reference in the
system is no longer a stable potential, so signals ride on the noise.The noise
becomes part of the program signal.
Multiple point ground systems that employ balanced circuits with properly designed
equipment present no special noise problems.
Figure 4 shows the floating ground principle. Note that the ground in completely
isolated from the earth. This system is useful when the earth ground carries significant
noise. It does, however, rely on the equipment input stage to reject interference induced
in cable shields, so the input amp better be good.
This scheme is very effective in eliminating ground loops. When noise enters a
shield connection only to earth, that noise can't enter the signal path.
Implementing this approach requires balanced lines and transformers since ground is
not carried between components. There is still debate about the use of transformers in
modern audio equipment though.
Grounding Safety
The main reason we ground a sound system is for safety. Proper grounding can prevent
lethal shocks. The next reason for grounding a system that includes AC powered
equipment is that proper grounding may reduce external noise pickup.
The AC power cord ground (the green wire and the third pin on the AC plug) connects
the chassis of electronic equipment to a wire in the wall power service that leads to an
earth ground. The earth ground, required by electrical codes everywhere, can contribute
to ground loops.
One way to break this ground loop is to lift the AC ground on one piece of
equipment, typically the power amplifier. This removes the safety AC ground.
The system now relies upon the audio cable to provide the ground ... a practice
that is hazardous!!! You also put at risk your multi-pair snake, console, post rack
equipment, and most important the client. I do not endorse the use of AC
ground lifts for any system ... anywhere. Don't do it.
In certain situations you can lift the shield at one end (usually the output) of an
audio cable and eliminate the most likely path that carries ground loop currents.
This is the way all TSC amp racks are wired and is seen as standard for most
tour type rigs. This method takes into account that the shield doesn't carry audio
signals. It does protect against static and radio noise. With one end lifted
however, it continues to reject static and other interference into the audio path.
Note: don't cut the shield of a mic cable that carries phantom power or you'll cut
the power to the mic.
Always try and plug your equipment into the same AC service leg. This includes
FOH, amp land, monitor land, and band back-line. This not only reduces the
potenial of a ground loop, but also reduces the danger of electrical shock.
Always connect lighting, air conditioning, rigging motor, and so on to a
completely different phase or leg of the main power distribution.
Remember to plan ahead and always think safety.
WHAT IS A GROUND?
Succinctly put, a ground is a return path for current. Its purpose is to close the
current loop, not to lead it into the earth. If an interference current is diverted
successfully into earth ground, it will simply come out elsewhere in order to return
to its source. The only time earth ground is necessary is for lightning.
Confusion arises because the term ground is used for a variety of applications and
means different things to different people. Facility engineers, for example, look at a
ground as a return for lightning strikes. In this application, the ground needs to be
able to handle currents up to 100,000 A for a few milliseconds. Because the
approximately 1-microsecond rise time produces significant Fourier frequency
components up to about 300 kHz, inductance can become an important concern. In
contrast, electricians look at a ground as being a return path for fault currents,
which may involve tens or hundreds of amperes at 50 or 60 Hz. At this frequency
level, inductance is not important, so a length of 4/0 wire connected to the nearest
building steel works just fine--an earth ground may be present, but is not needed
for electrical safety.
These two cases are the most commonly known uses of grounding, but the
grounding requirements for EMI control in medical device applications are vastly
different. EMI can cover a very wide range: currents from microamperes to
amperes and frequencies from direct current to daylight. The duration of an event
can range from nanoseconds, in the case of a transient, to years, in the case of a
continuous wave. For the specific case of electrostatic discharge (ESD), transients
are measured in nanoseconds (giving Fourier frequency components up to 300
MHz), and currents range to 10 A or even higher. The edge rates and current
magnitudes are such that significant voltage bounce will occur across even the
smallest length of wire or circuit-board trace. Whatever the condition, however,
device designers must provide a way for the interfering current to return to its
source, and that rarely involves earth ground.
A ground loop exists whenever there is more than one conductive path between
two points. This condition allows interference currents to mix with signal currents,
which may lead to ground interference. Figure 1(a) shows the effects of a ground
loop when stray interference currents divide and flow through signal ground. This
problem can be eliminated by having a zero-impedance ground. Lacking such a
ground, separate ground paths can be provided. As shown in Figure 1(b), by
breaking the ground loop, the device designer has created a single-point ground.
The need for a single-point ground originated in telephony, where it was almost
impossible to get impedances low enough to prevent power line frequencies from
intruding as a hum, and the technique is still useful in a number of low-level, low-
frequency analog applications.
However, a single-point ground is not suitable for handling the higher frequencies
encountered in modern computing devices. Figure 2 shows the effect of a standing
wave on a cable shield that has been grounded to its enclosure at a single point. If
the shield were exposed to an incident interference of 150 MHz (a popular land
mobile radio frequency) with a wavelength of 2 m, the cable, which is represented
here as being a 1/4 wavelength of the interfering frequency, or 0.5 m, would act as
an efficient antenna, with standing wave voltage on the shield as indicated in the
figure. In the immediate proximity of the ground connection, the shield voltage is
near zero, but at the unterminated end, the voltage is at a maximum, and with
stray capacitance, there is ample coupling to the signal lines.
Consider, for example, the case of a designer who wanted to use a single-point
ground for two freestanding cabinets located about 10 ft apart. Based on the
common assumption that the inductance of a wire is 20 nH/in., the minimum
inductance for the single-point ground path would be about 2.5 µH. Using the
formula for impedance
Z = 2¼fL
A lightning strike, for example, might result in 10,000 A flowing in an I-beam with
10-V transients across even short lengths. Two interconnected devices grounded to
that I-beam at different points may easily experience upset. Or suppose a 1-in.
length of wire or circuit-board trace were subjected to a 10-A ESD event. Assuming
an inductance of about 20 nH, the voltage drop across the wire or trace could be
calculated using the equation
Interconnect Grounding. Once the designer has coped with the circuit-board
ground, the next consideration is the interconnects within the equipment, such as
the connections between the mother and daughter boards and the ribbon cables
between modules. EMI problems are frequently the result of high-impedance
interconnects. Again, designers need to keep the ground impedance low, either by
connecting the circuit boards or modules to a common ground plane or by providing
a very-low-impedance ground interconnect via the cable, usually by allocating as
many connector pins to grounds as possible. Although the connector space is an
important concern, so is functionality. For high-speed (100-MHz) interconnects,
there should be one ground line for each signal line. For lower speeds (~10 MHz),
one ground line for each five signal lines may be sufficient. Anything less is inviting
trouble.
CONCLUSION
Why Ground?
The NEC, National Electrical Code defines a ground as: "a conducting
connection, whether intentional or accidental between an electrical
circuit or equipment and the earth, or to some conducting body that
serves in place of the earth." When talking about grounding it is
actually two different subjects, earth grounding and equipment
grounding. Earth grounding is an intentional connection from a
circuit conductor usually the neutral to a ground electrode placed in
the earth. Equipment grounding is to ensure that operating
equipment within a structure is properly grounded. These two
grounding systems are required to be kept separate except for a
connection between the two systems to prevent differences in
potential from a possible flashover from a lightning strike. The
purpose of a ground besides the protection of people plants and
equipment is to provide a safe path for the dissipation of Fault
Currents, Lightning Strikes, Static Discharges, EMI and RFI signals
and Interference.
1) a ground conductor,
2) the connection/bonding of the conductor to the ground electrode,
and
B) The contact resistance of the earth to the electrode: The Bureau of Standards
has shown this resistance to be almost negligible providing that the ground
electrode is free form paint, grease etc. and that the ground electrode is in firm
contact with the earth.
The NEC specifies that the ground electrode shall be installed so that it is at least 8
ft. in length and in contact with the soil. There are 3 variables that affect the
resistance of a ground electrode.
The reason for measuring soil resistivity when selecting a location for a sub-station
or central office is to find a location that has the lowest possible resistance. Once a
site has been selected, measuring the soil resistivity will give you the information
necessary to design and build a ground field that will meet your ground resistance
requirements.
There are a number of factors affecting soil resistivity, soil composition being one of
them. Soil is rarely homogenous and the resistivity of the soil will vary
geographically and at different depths. The second factor affecting soil resistivity
is moisture or the amount of water in the ground. Moisture content changes
seasonally, varies according to the nature of the sub layers of earth and the depth
of the permanent water table. The chart below shows two differing types of soil and
the affects that moisture has on their resistivity.
Since soil resistivity is so closely related to moisture and moisture is present in the
soil we can logically assume that as moisture increases resistivity will decrease and
vice versa. As shown in the chart below you there can be a change in resistivity
from top to bottom by a factor of 50 fold.
Since soil and water are generally more stable at deeper strata it is
recommended that the ground rods be placed as deep as possible
into the earth, reaching the water table if possible. ground rods
should also be installed where there is a stable temperature i.e.
below the frost line.
Soil Resistivity
Type of Soil Soil resistivity
RE Earthing Resistance (½)
Earthing rod m depth Earthing strip m
½m 3 6 10 5 10 20
p = 2 AR
Where: p = the average soil resistivity to depth
in ohm - cm
¹ = is the constant 3.1416
A = the distance between the electrodes
in cm
R = the measured resistance value in ohms from
the test instrument
p = 191.5AR
Where: p = the average soil resistivity to depth
in ohm - cm
A = the distance between electrodes in feet
R = the measured resistance value in ohms
from the test instrument
For example, you have decided to install 10' ground rods as part of your grounding
system. To measure the soil resistivity at a depth of 10' requires that the spacing
between the test electrodes is 10'. The depth that the test electrodes is to be driven
is A/20. To measure the soil resistivity start the GEO and read the resistance value
in ohms. Now if your resistance reading is 100 ohms the soil resistivity for one
cubic meter would be:
p = 191.5 x 10 x 100
p = 191500 ohms per centimeter
p = 191500 divide by 100
p = 1915 ohms per cubic meter.
The ground stakes are positioned in a straight line equidistant form one another
and at a distance between one another reflecting the depth to be measured. The
ground stakes should be screwed in no deeper than 1/3 the distance from one
another. A known fixed current is generated by the GEO between the two outer
ground stakes and a drop in potential (which is a result of the resistance) is then
measured automatically between the two inner ground stakes. The GEO then
display this resistance value in ohms.
Because measurement results are often distorted and invalidated by underground
pieces of metal, underground aquifers etc. additional measurements in which the
stakes axis is turned 90 degrees is always recommended. By changing the depth
and distance several times a profile is produced that can determine a suitable
ground resistance system.
The 3 - pole fall of potential method is used to measure the dissipation capability a
single ground electrode, ground grids, foundation grounds and other grounding
systems.
The potential difference between rod under test attached to terminals E and S is
measured with a voltmeter and the current flow between rod under test attached to
terminal E and H is measured by an ammeter. These functions are done internally
by the GEO.
Other manufacturers of ground testers may use the letters X,Y, and Z or C1, P2,
and C2 as connection descriptions. Terminals marked X or C1 are terminal E on the
GEO, terminals marked Y or P2 are terminal S on the GEO, and terminals marked Z
or C2 are terminal H on the GEO.
For example: If the voltage between E and S is 30 volts. The current between E and
H is 2 amps. We can calculate the following.
R = E/I
E = 30 and I = 2
R = 30/2
RE= 15 ohms
Connect the ground tester as shown in the picture below. Push start, and read out
the RE, (resistance) value. This is the actual value of the ground electrode under
test. If this ground electrode is in parallel or series with other ground rods the RE
value is the total value of all resistances.
Stake Setting
To achieve the highest degree of accuracy when performing a 3 - Pole
ground resistance it is essential that the auxiliary ground electrode be placed
outside the sphere of influence of the ground electrode under test and the current
probe.
If you do not get outside the sphere of influence the effective areas of resistance
will overlap and invalidate any measurements that you are taking.
The following chart can be used as a guideline when setting of auxiliary (S) and
current (H) ground stakes.
To test the accuracy of the results and to ensure that the ground stake are outside
the 'spheres of influence' reposition ground stake S 3 ft in either direction and take
a fresh measurement. If the measured value remains fairly constant the distance
between the ground stakes is sufficient. If there is a significant change in the
reading (30%) you need to increase the distance between the ground rod under
test and S and H until the measured value remains fairly constant when
repositioning the S ground stake 3 ft. or so.
'Selective'
Measuring of
High Voltage
Transmission
Towers
Testing individual
ground electrode
resistances of
high voltage
transmission
towers with
overhead ground
or static wire
requires that
these overhead
ground wires be
disconnected. If a
tower has more
than one ground
at it’s base, these
must also be
disconnected one
by one and
tested. The GEO
X with LEM
INSTRUMENTS
INC's 12'
diameter clamp-
on current
transformer can
measure the
individual
resistance’s of
each leg without
disconnecting any
ground leads or
overhead
static/ground
wires.
Measuring
Ground
Resistance
At Central
Offices
When conducting a
grounding audit of a
central office there are
3 or 4 different
measurements that you
will want to make. First
locate the MGB (Master
Ground Bar) within the
central office to
determine what type of
ground system they
have in place. Generally
speaking the MGB will
have a ground lead
going to the MGN
(Multi-Grounded
Neutral) or incoming
service, a separate
ground lead from the
MGB to the ground field
for the central office,
another ground lead
from the MGB
connected to the water
pipe and a separate
ground lead connected
to structural or building
steel.
The first measurement to take is stakeless measurement
of all the individual grounds coming off of the MGB. The
purpose is to ensure that all the grounds are connected
especially the MGN. It is important to note that you are
not measuring the individual resistance rather the loop
resistance of what you are clamped around. Connect the
GEO Xs as shown below and measure the loop resistance
of the MGN, the ground field the water pipe and the
building steel.
The second
measurement to be
taken at a central office
for a ground audit is the
3-pole fall of potential
of the entire ground
system. Connect to the
MGB as illustrated
below, keeping in mind
the requirements for
the setting of the
reference ground
stakes. To get to
remote earth many
phone companies have
been known to utilize
unused cable pairs
sometimes going out by
as much as a mile.
Once the fall of potential test has been completed, record
the measurement and this test should be repeated at
least annually.
After we have completed the "Stakeless" check of the building we will then want to measure the resis
stake setting when doing your 3-pole test. This measurement should be recorded and measurements
The second measurement to be taken at a remote site for a ground audit is the 3-po
entire ground system. Connect to any of the grounds as illustrated here. Keep in mi
setting of the reference ground stakes. This measurement should be recorded and m
place at least semi-annually.
When you have finished the 3-pole fall of potential you will now want to measure the
through the selective clamp-on method. This will verify the integrity of the individua
connections and that the grounding potential is fairly uniform throughout. Do a selec
both ends of the remote site .
Measuring Ground Resistance for
Lightning Protection
Commercial/Industrial
Ground tester fo
measurements o
single grounds o
multi-loop syste
without breakin
into the circuits
Selective ground
measurements
without influenc
from parallel
grounds, stakele
ground
measurements f
quick testing,
Click here for more information on LEM Ground Testing Instruments measurements o
the specific grou
resistance. Grou
impedance of hi
voltage towers.
WinGEO
Software for PC
using Windows¨
Windows¨ 95,
Windows¨ NT.
Suited to UNILA
GEO X (with RS
interface or DOC
Handy GEO PACK), measure
data acquisition
Small, handy ground tester 3-pole ground measurement 2-pole remote control,
resistance measurements Digital display, bar graph Logging of logging, SETUP,
the measured values via an optional RS 232 interface and PC DIAGNOSIS.
software WinVIEW or directly via a printer.
No obligation to purchase
One day on site, 1/2 day class room and theory with hand outs
and binder for each participant, 1/2 day hands on skill building
using LEM GEO equipment in the field.
Custom carrying cases and water proof hard shell field cases