6.0 Systemair BKF 560d6 F400-Ext 03
6.0 Systemair BKF 560d6 F400-Ext 03
6.0 Systemair BKF 560d6 F400-Ext 03
BKF smoke and heat extract fans are used in case of fire to extract
smoke gases and also during normal working conditions for standard
ventilation.
Smoke free escape routes assist egress and provide clear access
points for fire departments. Extracting poisonous and hot gases also
make fire extinguishing easier and reduce the damage on the
building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased -
on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively
observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency
converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate
possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be
bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor
(instructions).
Technical parameters
Norminal data
Frequency 50 Hz
Phase(s) 3~
Article name: BKF 560D6/F400 | Item Number: 95714 | Variant: 400V 3~ 50Hz - Y (Star) | Document type: Product card | Date: 2020-10-11 | Generated by: systemair
Online Catalogue | Language: English
Page 1 of 7
Starting current 11.6 A
Sound data
Protection/Classification
Insulation class F
Weight 95 kg
Others
Motor type AC
Article name: BKF 560D6/F400 | Item Number: 95714 | Variant: 400V 3~ 50Hz - Y (Star) | Document type: Product card | Date: 2020-10-11 | Generated by: systemair
Online Catalogue | Language: English
Page 2 of 7
Performance curve
Pa
400
300
284.74
200
100
4991.30
0
0 1000 2000 3000 4000 5000 6000 7000 m³/h
Hydraulic data
Power 731.1 W
Current 1.63 A
Inlet dB(A) 61 71 67 66 66 64 60 59 75
Outlet dB(A) 60 71 70 71 69 67 62 58 77
Surrounding dB(A) 48 63 53 57 49 45 42 42 65
Article name: BKF 560D6/F400 | Item Number: 95714 | Variant: 400V 3~ 50Hz - Y (Star) | Document type: Product card | Date: 2020-10-11 | Generated by: systemair
Online Catalogue | Language: English
Page 3 of 7
Dimension
B H L B1 H1 H2 H3 ~HM
BKF 560D4, D6, D4-6, D4-8 900 630 900 960 690 520 520 947
Article name: BKF 560D6/F400 | Item Number: 95714 | Variant: 400V 3~ 50Hz - Y (Star) | Document type: Product card | Date: 2020-10-11 | Generated by: systemair
Online Catalogue | Language: English
Page 4 of 7
Wiring
Article name: BKF 560D6/F400 | Item Number: 95714 | Variant: 400V 3~ 50Hz - Y (Star) | Document type: Product card | Date: 2020-10-11 | Generated by: systemair
Online Catalogue | Language: English
Page 5 of 7
Ecodesign
Product
Ecodesign
P nom 0.734 kW
Ps nom 316 Pa
External Leakage 0 %
Article name: BKF 560D6/F400 | Item Number: 95714 | Variant: 400V 3~ 50Hz - Y (Star) | Document type: Product card | Date: 2020-10-11 | Generated by: systemair
Online Catalogue | Language: English
Page 6 of 7
Accessories
FRQ5S-4A+LED V2 (36233) FRQS-4A V2 (36231)
FXDM5AM Frequency inv. IP54 (31387) U-EK230E Motor protection (30199)
FC102-1,1kW/3A-IP55, 150/50m (36158) DRAIN NIPPLE BKF (95458)
FLC BKF 500-560 (95736) PG-BKF 500-560 (95746)
WPR BKF 500-560 (95741)
Documents
BKF_E8306_15_06_2017.pdf
IMO_BKF_en_07_01_2019.pdf
Certif_DVV_DVAX_DVG_BKF_2020_KM_646474.pdf
CERTIF_DVV_DVAX_DVG_BKF_2797_CPR_597958.PDF
CERTIF_DVV_XS_XL_DVAX_DVG_BKF_2015_0086_CPR_597958.PDF
BKF_500_560_00.dxf
DoP_BKF
Specification
BKF smoke and heat extract fans
are intended to extract smoke gases in case of fire and also during normal working conditions for standard ventilation. Fire rating: 400°C/120 min (F400).
Certified according EN 12101-3. Continuous operation up to 120°C media. Casing made of zinc-magnesium coated steel (ZM). Backward curved
impeller made from galvanised or pre-galvanised steel. Equipped with single speed IE2 motor outside the air stream rsp. two speed motor. PTC serial
built-in motor. Installation possible in all positions, flange connection 30 mm. Installation outside building or inside building, outside fire zone in well
ventilated rooms. For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt),
respectively observe instructions. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in
case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in
frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial
connecting capability of the motor (instructions).