GUARANTEED TECHNICAL PARTICULARS PAGE: 1 1VYN400990-009

12kV VACUUM CIRCUIT BREAKER TYPE VD4


VD4 12.06.13E CONTD: 2 REV: 00
PREPARED BY CHECKED BY APPROVED BY YEAR/WEEK
MVB PPD SD 01/05

RATING AS PER STANDARD: IEC 56 VD4.12.06.13E

1 ) Rated Voltage & Frequency 12kV, 50Hz

2) Current Rating
a) Continuous rating open erection 800 Amps
b) Continuous rating in self ventilated 800 Amps
cubicle
c) Short time current 3 Sec. 13.1 kA

3) Rated Ambient Temperature 40°C

4) Maximum rise of temperature over 65°C


reference ambient for current rating at 40°C

5) Derating factor for 50 °C ambient 0.8


temperature

6) Rated Operating duty O - 0.3 sec, CO - 3 min. CO

7) Breaking capacity based on duty cycle


(as per clause 6)
a) Symmetrical at rated voltage 13.1kA
b) Percentage DC component 28 - 40%

8) Transient recovery voltage


a) Rate of rise at 12kV As per IEC 56
b) Peak Voltage at l2kV As per IEC 56

9) Total travel of the Mechanism 12 mm

10) Total length of break per pole 8 mm


GUARANTEED TECHNICAL PARTICULARS PAGE: 2 1VYN400990-009
12kV VACUUM CIRCUIT BREAKER TYPE VD4
VD4 12.06.13E CONTD: 3 REV: 00
PREPARED BY CHECKED BY APPROVED BY YEAR/WEEK
MVB PPD SD 01/05

RATING AS PER STANDARD: IEC 56 VD4.12.06.13E

11 ) Rate of contact travel


a ) At tripping 1.1 - 2.45 m/s
b) At closing 0.6 - 1 .2 m/s

12) Type of special device, if any, used to None


limit the rate of restriking voltage

13) Type of contacts Spiral electrodes Butt type

14) Material of contacts Copper Chromium

15) Contact pressure at no load 2200 N

16) Insulation level of CB


a) One minute power frequency 28kV
withstand voltage
b) Impulse voltage withstand with 75kVp
1.2/50 micro second wave shape

17) Minimum clearance in air

a) Between phase 95 mm
b) Between live parts & earth . 110 mm
c) Center distance between phases 150 mm
GUARANTEED TECHNICAL PARTICULARS PAGE: 3 1VYN400990-009
12kV VACUUM CIRCUIT BREAKER TYPE VD4
VD4 12.06.13E CONTD: 4 REV: 00
PREPARED BY CHECKED BY APPROVED BY YEAR/WEEK
MVB PPD SD 01/05

RATING AS PER STANDARD: IEC 56 VD4.12.06.13E

18) Whether CB is designed to close and latch To close and latch


on making or fitted with making current
release

19) Whether CB is trip free or fixed trip Trip free

c) If trip free, is it completely trip free Yes


under every method of closing (except
manual closing)

20) Type of operating mechanism Spring wound stored energy


mechanism
Manual

e) Motor (Optional) Spring wound by motor (optional)


f) No. of CB operations stored O-C-O

21 ) Spring charging motor Optional


a) Rating 150W
b) Rated voltage 110 V DC, 220 V DC & 230 V AC
85 to 110%
c) Voltage variation 15 seconds
d) Time required to charge the springs
completely at rated voltage

22) Method of closing


a) Normal Electromagnet
b) Manual Closing Provided
GUARANTEED TECHNICAL PARTICULARS PAGE: 4 1VYN400990-009
12kV VACUUM CIRCUIT BREAKER TYPE VD4
VD4 12.06.13E CONTD: 5 REV: 00
PREPARED BY CHECKED BY APPROVED BY YEAR/WEEK
MVB PPD SD 01/05

RATING AS PER STANDARD: IEC 56 VD4.12.06.13E

23) Type of closing mechanism -- Stored energy spring mechanism -

24) Closing coil details

a) Rated voltage -- As per clients requirement -


b) Voltage variation 85 to 110 %
c) Power required at rated voltage 180 W

25) Method of tripping


a) Normal Electromagnet
b) Manual tripping Provided
c) Emergency Provided with Panel

26) Type of tripping mechanism -- Stored energy spring mechanism -

27) Tripping coil details


a) Rated voltage -- As per client's requirement -
b) Voltage variation 70 to 110 %
c) Power required at rated voltage 180 W

28) Arc duration


a) Arcing time at 100% breaking < 12-15 ms
capacity, max.
b) Opening time 35 to 55 ms
c) Total break time at 100% breaking
capacity, 50 to 60 ms

29) Closing time, 50 to 70 ms


GUARANTEED TECHNICAL PARTICULARS PAGE: 5 1VYN400990-009
12kV VACUUM CIRCUIT BREAKER TYPE VD4
VD4 12.06.13E CONTD: -- REV: 00
PREPARED BY CHECKED BY APPROVED BY YEAR/WEEK
MVB PPD SD 01/05

RATING AS PER STANDARD: IEC 56 VD4.12.06.13E

30) No. of openings CB is capable of


performing without inspection replacement
of contacts or other main parts
a) At no load or very low current 10000
b) At 100% rated current app. 5000
c) At 100% rated breaking current 100

31 ) Auxiliary contacts
a) N/O and N/C contacts provided 6 NO+6NC
b) Whether convertible at site NO
c) Breaking current DC and inductive
circuit at 110 & 220 V DC respectively at 5 & 2 Amps.
L/R = 25 ms
d) Breaking current AC and P.F. = 0.7 at 10 A
220 V AC

32) Interlocks provided Yes


(As per IEC requirements)

33) CB operable in
a) Test / Service position Yes
b) In between Test and Service position No

34) Weight of Circuit Breaker (Approx.) 110 Kgs

35) Provision for slow closing for maintenance No


purpose

36) Rated Capacitive Breaking Current


a) Nominal Current 0.8 x Rated Current
b) Breaking Current 400 Amps.
c) Making Current 16kA peak at 4.5k Hz Frequency
.