DATA SHEET 

IMPULSE VALVE DISCHARGE PRESSURE  Specifications 
SWITCH  Part Number  02‐12534 
Temperature 
32 to 130°F (0 to 54°C) 
Limits 
Enclosure 
NEMA 4 
Classification 
Single pole, double throw 
Contact Rating  5A resistive/3A inductive @ 30 VDC 
Normally open or normally closed 
  Body Material  Aluminum with irridite finish 
Description  Pressure 
1/4” (6 mm) NPT 
Connection 
The  discharge  pressure  switch  (DPS)  is  used  to 
Approximate  4.125” (105 mm) 
provide a positive confirmation to the control system 
Length  (including both connectors) 
that  the  Fike  fire  suppression  system  has  been 
Electrical 
discharged  manually  via  the  strike  button  on  the  1/2” (15 mm) NPT 
Connection 
Impulse  Valve  Operator  (IVO).  In  response,  the 
(3) 18 gauge x 20" (508 mm) long 
control  panel  will  activate  various  audio/visual  Wire Leads 
Violet (C), Blue (NO), Black (NC) 
warning  devices  and  auxiliary  relays  to  notify 
Pressure Setting  40 psig (3 bar), increasing 
occupants that the system has been discharged. 
Weight  6.5 ounces (184 g) 
The switch is mounted to the discharge piping and is 
operated  pneumatically  using  the  agent  pressure  in  Approvals 
the discharge piping network. 
Underwriters Laboratories (UL) 
 
Underwriters Laboratories of Canada (ULC) 
Factory Mutual (FM) 
For  exact  certification  listings,  please  reference  the  respective 
agency web site. 