Katke Sir Report Itr
Katke Sir Report Itr
Katke Sir Report Itr
CERTIFICATE
Place: Nanded
Date:
Mentor Principal
Prof. Mr.Y.S.Katke Sir Dr.G.V.Garje
Acknowledgment
1) Bus bar :-
3) Isolating Switches:-
In Sub-Station, it is often desired to disconnect a part of the
system for general maintenance and repairs. This is accomplished
by an isolating switch or isolator. An isolator is essentially a knife
Switch and is design to often open a circuit under no load, in other
words, isolator Switches are operate only when the line is which
they are connected carry no load. For example, consider that the
isolator are connected on both side of a cut breaker, if the isolators
are to be opened, the C.B. must be opened first. If an isolator is
opened carelessly, when carrying high current the resulting arc
easily causes flashover to earth.
4) Circuit breaker :-
A circuit breaker is a equipment, which can open or close a
circuit under normal as well as fault condition. These circuit
breaker breaks for a fault which can damage other instrument in
the station. It is so designed that it can be operated manually (or
by remote control) under normal conditions and automatically
under fault condition. A circuit breaker consists of fixed &
moving contacts, which are touching each other under normal
condition i.e. when breaker is closed. Whenever a fault occurs trip
coil gets energized, the moving contacts are pulled by some
mechanism & therefore the circuit is opened or circuit breaks.
When circuit breaks an arc is stack between contacts, the
production of arc not only interrupts the current but generates
enormous amount of heat which may cause damage to the system
or the breaker itself. Therefore the main problem in a circuit
breaker is to extinguish the arc within the shortest possible time so
that the heat generated by it may not reach a dangerous value. The
medium used for arc extinction is usually
Oil, Air, Sulfur Hexafluoride (SF6) or vacuum.
Circuit breakers can be classified on the basis of medium used
for arc extinction:
Type=ELFSF2-1 (r)
Rated Voltage=145 kV Rated Frequency=50 Hz
Rated Normal current=3150 Amps at 40oc
Rated Lightning Impulse Withstand Voltage=650 KV p Rated
Short Circuit Breaking Current=31.5 k Amps
Rated Short Time Withstand Current & Duration=31.3 k
Amps for 3 sec Line Charging Breaking Current=50 k Amps
First Pole To Clear Factor=1.5Rated Gas Pressure SF6/20oc
(abs) =7.0 bar
Closing & Opening Devices Supply Voltage=220 v (d.c)
b. Distance Relay:
a. Current Transformer :-
Basic Principle:
b. Transformer Oil:
d. Breather:
e. Diverter tank:
It is a drum like structure mounted on a transformer wall
&filled with transformer oil & connected to conservator. It
reduces arcing during tap changing operation.
f. Radiator:
It is of small thickness & large diameter plates & used for heat
dissipation during operation. Large diameter means large surface
area 7 better cooling.
g. Temperature Indicator:
i. Buchholz relay:
k. Tap Changing:
Mainly 132/33 kV transformer uses on-load tap changing
&33/11 kV transformer is used of load off-load tap changing. The
tap changer is generally done on H.V side because current flow is
less than lv side. Which reduces theflashing during the tap
changing. Here tap changed in 132/33 kV transformer
9) Specification of 132/33 kV Transformer:
1. Earth Screen.
2. Overhead Ground Wire.
3. Lightning Arrestor.
1. Earth Screen:
The power stations & the substations are generally have much
expensive equipments. These stations can be protected from direct
lightning strikes by providing earthing screens. It consists of a
network of Copper conductors mounted all over the electrical
equipments in the substation or Power station.
The screen is properly connected to earth on at least two
points through low impedance. On the occurrence of direct stroke
on the station the screen provides a low resistance path by which
lightning surges are connected to the ground. In this way station
equipments are protected against lightning.
3. Lightening Arrestors:
Firstly, we can see lightning arrestors. These lightning
arrestors can resist or ground the lightning, if falls on the
incoming feeders. The lightning arrestors can work in an angle of
30 degrees around them. They are mostly used for protection of
the instruments used in the substation. As the cost of the
instruments in the substation are very high to protect them from
high voltage lightning these arrestors are used.
It is a device used in Electrical Power systems the insulation
o the system from the damaging effect of lightning. Metal Oxide
varistor (MOVs) have been used for power system protection the
mid 70s.
The typical lightning arrestor is also known surge arrestor has
a high voltage terminal and a ground terminal. When a lightning
surge or switching surge travels down the power system to the
arrestor, the current from the surge is diverted around the
protected insulation in most cases to earth. Lightning arrestors
with earth switch are used after the current transformers to protect
it from lightning i.e. from high voltage entering into it. This
lightning arrestor has an earth switch that can directly earth the
lightning. The arrestor works at 30o to 45o angle of the lightning
making a cone. The earth switch can be operated manually, by
pulling the switch towards the ground. This also helps in breaking
the line entering the station. By doing so maintenance repair of
any instrument could be performed.
Working Principle:
The capacitor banks are used across the bus so that the voltage
does not get down below the required voltage. When the inductive
property of the line increases then the voltage lags behind current
& causes loss of money, so to raise the voltage up &prevent loss
of money capacitor banks are used. It raises the voltage and raises
power factor.
Now-a days SF6 circuit breaker are used at EHV voltages. The
control and operating cabinets are covered in polythene bags and
are packed in wooden and iron crates. These should be stored on
raised ground and should be covered with tarpaulins. The arcing
chambers and support insulators are packed in iron crates and
transported horizontally. The +ve pressure of SF6 gas is
maintained in these arcing chambers to avoid the ingress of
moisture. It should be ensured that this pressure is maintained
during the storage. Other accessories like pr.
Switches, density monitor, Air Piping, control cables, wiring
materials, SF6 gas pipes; SF6cylinder should be stored in store
shed.
19)Power transformers:
These are used for extending A.C. & D.C. supplies whenever required
through various circuits. There are two main Buses in this arrangement
connected by each diameter.
i) Through either of line breakers the line side Main Bus can be charged
normally (Bus-I).
ii) The line breaker, tie breaker and 2nd Bus breaker/Transfer Bus if closed
in series will charge the 2nd Main Bus/Transfer bus.
iii) Outage on anyone Bus can be availed without interruption on any Bus.
The second Bus can feed all the loads.
iv) Breaker from any bay can be taken out for maintenance without
interrupting the supply.
v) For efficient working two diameters are required having source in each
diameter preferably connected diagonally opposite to two different buses.
vi) ) If both the sources are connected to same Bus (i.e. from one side only
one tie breaker can be attended at a time).
vii) If all the four breakers connected to Bus are out the transformer can be
charged through the breaker from remote substation source.
viii) Changing over as in case of 2 Bus or 3 Bus systems is not necessary as
supply is not interrupted, in any case as said above.
ix) All the breakers in the diameters are in energized position including
tiebreakers to keep the system in tact in case of any fault.
x) On line or transformer fault the tie breaker with respective line or
transformer breaker will trip.
xi) On Bus fault on any Bus only the two breakers (of two diameters)
connected Bus will Trip.
1. Gangakhed
2. Khadka
3. Kodri
4. Ghodawat
5. Palam
6. Pinmpaldari
7. Midc