Air Filter Test Services
Air Filter Test Services
Air Filter Test Services
ASHRAE 52.2
Conditioning Tests
• KCl conditioning
• IPA (isopropyl alcohol) conditioning
o IPA spray
o IPA dip
After the initial efficiency (Ei) is calculated, the filters are loaded with ASHRAE dust (a standardized
test dust consisting of carbon black, ISO fine dust, and cotton linters) in a series of five steps to a
chosen final pressure drop. After each dust load, the efficiency of the filter is determined.
RTI includes a filter weight gain value for customers who request it. A photo of your filter will be
included as well, if requested.
RTI emails these reports as four-page PDF files usually within one day of the test completion. An
example of this report is available from Kathleen Owen at mko@rti.org. Modified tests based on the
methodology of ASHRAE 52.2 are readily available. If you don't see your idea listed on this Web
page, please ask about it.
Contact
• Kathleen Owen, mko@rti.org
* ASHRAE Standard 52.2-2007, Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by
Particle Size, American National Standards Institute/American Society of Heating, Refrigerating and Air-Conditioning
Engineers Atlanta, GA. (The test method itself may be purchased from ASHRAE.)
ASHRAE 52.2 Variations
RTI offers many variations on the standard ASHRAE 52.2 test*. Our most common options are listed
below. Please ask if you need a test that isn't listed. We may already perform that test or we can work
with you to develop a new methodology.
Efficiency Test: ESPs, Electronic Air Cleaners, Mixed Media Air Cleaners
This test is essentially the same as the initial efficiency test except that we test unusually shaped or
electrically powered air cleaners. Let us know your needs; we can probably come up with a way to test
it for you. For ESPs and other air cleaners where a full 52.2 test isn't applicable, this is a good option
for getting data to compare with the initial efficiency of an ASHRAE 52.2 test.
Conditioning Steps
In lieu of the current first dust load, we can perform the conditioning step with ultrafine (nanometer)
KCl aerosol as described in the pending informative appendix to 52.2. We can also do conditioning
based on IPA or other exposures.
Dusts
We perform tests similar to ASHRAE 52.2 with alternate loading dusts. Dusts we have used include
ISO fine, ASHRAE dust without carbon, and actual duct dust. Dust without carbon is especially
important for testing ESPs because the carbon black of the regular ASHRAE dust may short out the
unit. Dust loading with alternate dusts may be done in conjunction with efficiency tests or simply to
get weight gains or dust-holding capacities for air cleaners or media.
Nanoparticle Filtration
For smaller particles (nanoparticles), we can test your filters with a scanning mobility particle sizer
(SMPS). This instrument measures particles down to approximately 20 nm and up to approximately
500 nm. We can cover this whole size range or some fraction of this. This test is very useful for
showing that your filter actually improves below its most penetrating particle size (MPPS).
Other Airflows
ASHRAE 52.2 only recognizes seven face velocities for MERV evaluations. We can test at many other
airflow rates.
Test reports are very similar to our ASHRAE 52.2 reports but may be modified substantially to meet
customer needs. These include, as appropriate:
• Description of the filter
• Test parameters
• Clean filter efficiency data (table and graph)
• Dust-loaded filter efficiency data (table and graph)
• Pressure drop curve for the clean filter at various air flow rates
• Minimum efficiency values averaged for the smallest (E1), medium (E2), and largest (E3)
particle sizes
• MERV estimates
• Conditioning times and method
• Filter weight gain
RTI emails these reports as PDF files usually within one day of the test completion.
Contact
• Kathleen Owen, mko@rti.org
* ASHRAE 52.2 is a standard test method to determine the efficiency of clean and dust-loaded residential and commercial
HVAC filters. It may be purchased from ASHRAE.
Conditioning Tests
ASHRAE 52.2 currently has a conditioning step in the form of a small ASHRAE dust load. Alternate
conditioning steps are being discussed and developed. An informative appendix to ASHRAE 52.2 is in
development to replace the current conditioning procedure to one using a KCl-conditioning aerosol.
This step is not required, but may give useful information that is not obtained through a 52.2 test.
Other conditioning steps including several using isopropyl alcohol (IPA) are in use, especially in
Europe.
KCl Conditioning
This is a conditioning test with submicron, ~40 nm, KCl aerosol as described in the pending
informative appendix to ASHRAE 52.2. It starts with an efficiency test per 52.2 of a clean filter. The
filter is then exposed to the submicron aerosol until the efficiency measurements stabilize or the
maximum CT is reached. The goal of this method is to mimic efficiency drops seen in real use for
some electrostatically charged filters; it does not remove all charge from the filter. This conditioning
may be followed by the other dust loads of ASHRAE 52.2, a single dust-load, or not dust-loading as
the customer chooses.
• IPA spray -- filter is sprayed until it is visibly saturated then allowed to dry for 24 hours before
the post-conditioning efficiency test.
• IPA dip – filter or media swatch is submerged in IPA, then dried for 24 hours.
Contact
• Kathleen Owen, mko@rti.org
EPA Method 319
EPA Method 319* is a test method aimed at testing paint overspray arrestors for the aerospace
industry. It is easily adapted for any similar filters. Briefly, filters or other air cleaners are placed in a
24- x 24-inch duct with a well-defined airflow. Three clean filters (or filter systems) are tested with a
solid aerosol (KCl) and three identical filters are tested with liquid aerosol. Use of the solid- and
liquid-phase aerosols is designed to account for the likelihood that paint overspray would include both
phases of aerosol and brackets arrestor performance. Method 319 requires a face velocity of 120 fpm.
The aerosols cover the particle size range from 0.3-10 μm as used in ASHRAE 52.2. In Method 319,
the results are reported by aerodynamic diameter with somewhat different size channels. Upstream and
downstream particle counts in each size of bin are collected and the efficiency is calculated from these
numbers.
RTI includes a photo of your filter or filter system, if you request it. RTI emails these reports as PDF
files usually within 1 day of the test completion.
Modified tests based on Method 319 are readily available. Possibilities include:
• Single efficiency test -- just one filter or one filter with each aerosol (useful for filter
development)
• Flow rates -- other flow rates may be used
• Nanoparticle filtration -- for smaller particles (nanoparticles), we can test your filters with a
scanning mobility particle sizer (SMPS). This instrument measures particles down to
approximately 20 nm and up to approximately 500 nm. We can cover this whole size range or
some fraction of this. It is very useful for showing that your filter actually improves below its
MPPS (most penetrating particle size).
Contact
• Kathleen Owen, mko@rti.org
* Method 319, Determination of Filtration Efficiency for Paint Overspray Arrestors, was published October 29, 1996 in the
Federal Register (61FR55842). EPA proposed that this method be used by filter manufacturers to certify the efficiency of
their filters for meeting the filtration efficiency requirements, which were also proposed in the same Federal Register. The
National Emission Standards for Hazardous Air Pollutants (NESHAP) for Aerospace Manufacturing and Rework Facilities
was promulgated in the Federal Register on September 1, 1995 as Subpart 66 of 40CFR Part 63.
Gas-Phase Air Cleaner Tests
Several options for gas-phase air cleaner testing at RTI are currently available. ASHRAE and ISO are
developing standard tests which RTI will add to its offering as they become available. More tests may
be added if customer need exists.*
Typical test:
• Challenge gas: 40 ppm toluene
• Temperature: 75°F
• Relative humidity: 45%
• Airflow rate: 1000 cfm
• Test duration: 2 hours with challenge, 1 hour desorption
Contact
• Kathleen Owen, mko@rti.org
* Most tests will be performed in our ASHRAE 52.2 test rig; thus, the velocity and aerosol uniformity already meets the QA
specifications of that test method. Our test rigs also provide temperature and humidity control as well as options for air
cleanup and single-pass or recirculation options.
Swatch, Fabric, and Media Tests
Performance of Aerosol Penetration Measurements of Fabrics
The swatch tests are performed on a small scale (e.g., 4-inch diameter samples, flowrates under 1 cfm)
by challenging fabric swatches with a polydisperse aerosol while measuring the aerosol concentrations
upstream and downstream of the fabric. The apparatus is based on ASTM Standard F1215-89 for
determining the filtration efficiency of flat-sheet filter media.
Test Parameters
• Temperature
o Fabrics to be worn by people may be tested at 90oF
o Media swatches for HVAC may be tested at 75oF
o Range 70 - 90oF
• Humidity
o Fabrics to be worn by people may be tested at 60%
o Media swatches for HVAC may be tested at 45%
o Range: 0 - 60%
• Airflow rate -- fabrics may be tested for a specified pressure drop (e.g., 0.1 in H2O) or a
specified flow rate (up to ~18 Lpm)
• Aerosols
o Liquid aerosol, usually oleic acid, a low-volatility oil
o Solid aerosol, usually KCl, a salt
o Nanoparticles, SiO2
• Aerosol generators -- collisons, spray nozzle, others
• Particle counters
o Optical particle counters (OPCs) or aerosol spectrometer covering the particle diameter
size range from 0.3 to 3 μm in 10 particle-sizing channels
o Scanning mobility particle sizer (SMPS) covering the particle diameter size range from
20 to 450 nm
• Swatch diameter -- variable from approximately 2 to 4 inches
Aerosol Penetration
Aerosol penetration is based on the ratio of downstream to upstream aerosol concentrations computed
on a channel-by-channel basis to compute the fractional penetration at the mean particle diameter of
each channel. Penetration velocity may be determined by multiplying the penetration by the face
velocity. Penetration velocity is used when comparing results from constant pressure drop tests of
fabrics having different air permeabilities.