Detail 02 Thrust Block

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

22 1/2 45° BEARING

11 1 ° AREA
/2°
100%

100%
100%
100%
22 1/2° BEND 45° BEND
90° BEND
3/8" TIE RODS TEE
BEARING
AREA
22 1/2° 100% 15#
FELT

MIN
100% OF TEE "Y" BRANCH DEAD END TYPICAL SECTION
VALVE

FOR OTHER ANGLES NOT SHOWN, CALCULATE AS REQUIRED.


P

2 #5 REBARS EXPOSED
FOR BENDS: R = 2PA SIN /2
REBARS COATED WITH MASTIC)
FOR TEES AND DEAD ENDS: R = PA
TAMP BACKFILL MATERIAL WHERE: P = TEST PRESSURE, PSI
A = PIPE AREA, SQ INCHES P
BETWEEN BLOCK & PIPE

USE THE FORMULA BELOW TO CALCULATE BEARING R


WEIGHT OF CONCRETE TO AREA OF THRUST BLOCKS FOR VERTICAL BENDS WITH
RESIST 100% OF TOTAL THRUST DOWNWARD THRUST AND HORIZONTAL BENDS.

AREA THRUST BLOCK (SQ FT) = R/SxD

IN WHICH:
R = (FROM FORMULA ABOVE, IN LBS)
NOTES: S = ALLOWABLE SOIL PASSIVE PRESSURE IN LB/FT3
1. THRUST BLOCK CONC VOLUMES REQUIRED D = DISTANCE IN FEET FROM GRADE DOWN TO
FOR UPWARD THRUST SHALL BE CALCULATED CENTERLINE OF FITTING FOR HORIZONTAL BENDS;
BY DESIGN ENGINEER. FOR VERTICAL BENDS USE D = 1'-0" FOR
CALCULATION REGARDLESS OF DEPTH.

VERTICAL BEND WITH UPWARD THRUST HORIZONTAL BEND OR VERTICAL BENDS


WITH DOWNWARD THRUST
NOTES
1. THESE DETAILS SHALL APPLY TO ALL BURIED PRESSURE 5. FIGURE (100%) AT THRUST BLOCK INDICATES PERCENT
PIPING WITHOUT WELDED, SOLVENT WELDED, FLANGED, OF TOTAL THRUST TO BE APPLIED FOR BEARING AREA.
OR RIGID GROOVED END (VICTAULIC) COUPLINGS, AND 6. FITTINGS TO RECEIVE POLYETHYLENE WRAPPING SHALL
ALSO ON ALL PIPING WHICH CONTAIN SLEEVE TYPE BE WRAPPED PRIOR TO POURING THRUST BLOCK.
COUPLINGS OR FLANGE COUPLING ADAPTERS WHICH 7. THRUST BLOCKS FOR VERTICAL BENDS HAVING
ARE NOT RESTRAINED AND IN AREAS OF NON-RESTRAINT DOWNWARD RESULTANT THRUSTS SHALL BE THE SAME
WALL PENETRATIONS. WHEN REQUIRED, THRUST AS FOR HORIZONTAL BENDS.
BLOCKING SHALL BE PROVIDED AT ALL BENDS, TEES, 8. BEARING AREA OF THRUST BLOCK SHALL NOT BE LESS
WYES AND DEAD ENDS AS NECESSARY. THAN 1.0 SQ. FT.
2. ARROWS ( ) INDICATE THRUST DIRECTION. 9. USE THE MAXIMUM INTERNAL PRESSURE ANTICIPATED
3. CONCRETE FOR THRUST BLOCKS TO BE 6 SACK, 3/4" AGG (i.e. HYDROSTATIC TEST PRESSURE).
3
MAX 3000 PSI. 10. ALLOWABLE SOIL PASSIVE PRESSURE (LB/FT ) SHALL BE
4. CAST CONCRETE THRUST BLOCK AGAINST UNDISTURBED PROVIDED BY GEOTECHNICAL ENGINEER.
EARTH.

FAIRFIELD-SUISUN PUMP STATION AND COLLECTION SYSTEM DESIGN STANDARDS


DETAIL NO.

SEWER DISTRICT
1010 CHADBOURNE RD.
FAIRFIELD, CA 94534-9700
THRUST BLOCK DETAIL 2
(707) 429-8930 PH DATE
(707) 429-1280 FX (DETAIL INTENDED FOR USE BY DESIGN ENGINEER, NOT CONTRACTOR) 9/21

Detail-02.dwg / Thrust Block