t1000 Plus Application Guide
t1000 Plus Application Guide
t1000 Plus Application Guide
34
T1000 PLUS
APPLICATION GUIDE
DOC. MIE91093 Rev. 1.34 Page 2 of 145
Disclaimer
Every effort has been made to make this material complete, accurate, and up-to-
date. In addition, changes are periodically added to the information herein; these
changes will be incorporated into new editions of the publication. ISA S.R.L reserves
the right to make improvements and/or changes in the product(s) and/or the
program(s) described in this document without notice, and shall not be responsible
for any damages, including but not limited to consequential damages, caused by
reliance on the material presented, including but not limited to typographical errors.
SH O R T FO REW O RD
Primo Lodi
Q&A Manager
DOC. MIE91093 Rev. 1.34 Page 8 of 145
S AFE TY AT W O R K
. The symbol
! is related to dangerous input or
output, and is located close to the following points:
- Outputs: main 0-250 V AC (500 V for E model); auxiliary 0-
250 V AC (500 V for E model); auxiliary 20 – 260 V DC;
- Inputs: AC voltage measurement (up to 600 V); START and
STOP Inputs (up to 250 V); resistors (up to 250 V).
I NTR O D U CT IO N
The single phase relay test set mod. T1000 PLUS is suited for
the testing and adjustments of the following types of relays;
the table lists also the paragraph that explains the test
procedure.
1 A PP L IC AT IO N E X AM PL E S
The first general comment is that when you save the result,
following data are always saved:
. Main current, or main AC voltage, or main DC voltage,
according to the selection performed with the push-button
(57);
. Auxiliary AC voltage;
. Auxiliary DC voltage;
. Timing.
If other measurements are selected by the menu, they will
also be saved along with these data.
As a consequence, there will be test results that can be not
relevant for the test: for instance, Vaux when the relay is an
over-current one.
Don’t save;
Automatic at trip;
Confirm at trip;
Manual.
1.1.1. Introduction
DOC. MIE91093 Rev. 1.34 Page 17 of 145
. Next steps depend upon the type of relay and upon the type
of test you want to perform. The following example applies to
an overcurrent relay with a time-dependent curve and one (or
more) time-independent threshold. Of this relay we want to
find and save trip and drop-off thresholds, and also the time-
dependent curve.
DOC. MIE91093 Rev. 1.34 Page 19 of 145
. Select ON+TIME, and start the test: the test goes OFF with
no message. Slowly increase the test current, until the relay
trips within tmax: this is the threshold; pressing the multi-
function knob tripping values can be saved.
Now we can measure trip timings, following the I-t curve with
as many points as desired. First thing, restore the Maintained
fault injection, as follows
Test control > Fault injection > Maintained (RET)
Then select the NO or NC level for the relay trip contact:
Timer start/stop > STOP > EXT > Clean (Voltage) > NO
(NC) ESC
Now, press ON and pre-adjust the first test current: as the
relay trips, don’t save test result; go OFF. Select ON+TIME: as
the relay trips, test goes OFF; pressing the multi-function knob
tripping values can be saved. The TRIP LED (43) turns on and
parameters at trip are displayed until ON or ON+TIME are
selected. Confirm save results pressing the multi-function
knob, and proceed with other test currents, until all points to
be tested are measured.
1.2.1. Introduction
DOC. MIE91093 Rev. 1.34 Page 22 of 145
. Next steps depend upon the type of relay and upon the type
of test you want to perform. The following example applies to
an overvoltage and undervoltage relay with one (or more)
time-independent threshold. Of this relay we want to find and
save trip and drop-off thresholds.
VN
Next, we find the drop-off threshold for V>. From the voltage
above, slowly decrease the voltage; as the relay resets,
pressing the multi-function knob tripping values can be saved.
The TRIP LED (43) turns on for 5 seconds; during 5 seconds,
parameters at reset are displayed; then, the standard
measurement is restored.
NOTE: stored value is the voltage as the relay resets. This
corresponds to the relay drop-off only if the current did not
change very much while the relay timing elapsed; however,
reset timing is usually very short, so current does not change
very much at release, and the measurement is accurate.
Next, we find the drop-off threshold for V<. From the voltage
above, slowly increase the voltage; as the relay resets,
confirm save results pressing the multi-function knob, and
proceed.
DOC. MIE91093 Rev. 1.34 Page 25 of 145
Now we can measure trip timings, following the V-t curve with
as many points as desired.
Press ON and pre-adjust the first test voltage (either more
than V> or less than V<): as the relay trips, don’t save test
result; go OFF. Select ON+TIME: as the relay trips, test goes
OFF; pressing the multi-function knob tripping values can be
saved. The TRIP LED (43) turns on and parameters at trip are
displayed until ON or ON+TIME are selected. Confirm save
results pressing the multi-function knob, and proceed with
other test voltage, until all points to be tested are measured.
If you have a three phase voltage relay to test, how can you
do it given the fact that T1000 PLUS only has two voltage
generators? The problem can be easily solved using the two
available voltages with a phase shift of 60°, and connecting
them as phase to phase voltages rather than phase voltages.
The drawing gives the idea.
DOC. MIE91093 Rev. 1.34 Page 26 of 145
V MAIN
VN
V AUX
The two voltages shold have the same amplitude, equal to the
phase to phase voltage: the connections is shown here below.
1.3.1. Introduction
Next, we find the drop-off threshold for V<. From the voltage
above, slowly increase the voltage; as the relay resets,
pressing the multi-function knob tripping values can be saved.
NOTE: stored value is the voltage as the relay resets. This
corresponds to the relay drop-off only if the current did not
change very much while the relay timing elapsed; however,
reset timing is usually very short, so current does not change
very much at release, and the measurement is accurate.
DOC. MIE91093 Rev. 1.34 Page 31 of 145
1.4.1. Introduction
MOTOR GENERATOR
Q
Forbidden
zone Eo jXsI I
ZS
RsI
V Q E0
I V
P
P
. Next steps are the search of the points of the P-Q curve we
have selected. The key test is performed at 180°; additional
tests are decided by the operator. In general, it is wise to
execute at leas two more tests, in order to ascertain that the
curve corresponds to the nominal one. In our example we will
test at 180° (P%); 120° (P1); 240° (P2).
DOC. MIE91093 Rev. 1.34 Page 37 of 145
1.5.1 Introduction
Since relay inputs are one current and one voltage, we’ll use I
main and V aux to perform the test.
The parameters that we will test are:
The characteristic angle, sometimes called MTA= max
torque angle (electromagnetic relays), and the Angle
sector, that is half of the operating angle;
The pick up of Io;
The pick up of Vo.
When testing one parameter we have to set the other two at a
value above the pick up.
Test MTA: we keep Vo and Io above the respective pick
ups.
Test the Angle sector: we keep Vo and Io above the
respective pick ups.
Test the pick up of Io: we keep Vo above the pick up,
and the current angle at the measured Characteristic
Angle.
Test the pick up of Vo: we keep Io above the
measured pick up, and the current angle at the
measured Characteristic Angle.
Characteristic Angle
MTA
Operating zone
Also, the earth directional relay shouldn’t trip for all values of
voltage and current. It is widely accepted that a directional
relay characteristic can run inside the dotted line area, as
shown in the figure.
DOC. MIE91093 Rev. 1.34 Page 41 of 145
Operating zone V1 = 6 V
10
I1R = 1 A
... and this point !
1
0.001 0.01 0.1 1 10
The first tests serve to measure the MTA and angle sector. We
will perform a threshold test by moving the test point on a
circle in the V-I plane.
TAKE CARE: φ1 is the angle at which you enter the operating area,
with the positive direction of angles; φ2 is the angle at which you leave
the operating area.
In the following are shown two cases: in the first one φ1 = 0°;
φ2 = 120°; MTA = 60°. In the second one φ1 = 240°; φ2 = 30°;
MTA = 315°.
2 I I
MTA 2
TRIP AREA
V
1 MTA
TRIP AREA
The V-I curve is tested setting the phase shift at MTA, and
modifying the current at constant voltage, or the voltage at
constant current. In our figure we have two points: P1 = 100
V, 5 mA; P2 = 6 V, 1 A.
Test of P1
. Press ON. Set the auxiliary voltage 100 V.
. The phase angle is not displayed with very low currents; so,
adjust the current angle to 90°, taking the mains as a
reference:
AUX VAC/VDC > Aux Vac control > Phase > Reference:
Current > (90°) ESC
Test of P2
. Press ON. Set the auxiliary voltage at 0 V.
. Use the 10 A range ; there I no problem with phase and
current measurements. Adjust the current to 1 A.
. Slowly increase the voltage, until the relay trips: P2 trip is
found. As the relay trips, pressing the multi-function knob
tripping values can be saved. The TRIP LED (43) turns on for 5
seconds; during 5 seconds, parameters at trip are displayed;
DOC. MIE91093 Rev. 1.34 Page 47 of 145
Other points can be found the same way. For the sake of
accuracy, test at constant voltage down to 8 V, and at
constant current from 10 mA up.
1.6.1. Introduction
Next steps depend upon the type of relay and upon the type of
test you want to perform. The following example applies to a
frequency relay with two high and two low thresholds; for both
we want to find and save trip and drop-off values.
DOC. MIE91093 Rev. 1.34 Page 49 of 145
Next, we find the drop-off threshold for F>>. From the trip
frequency above, slowly decrease the frequency; as the relay
resets, pressing the multi-function knob tripping values can
be saved.
Now we can measure trip timings, following the F-t curve with
as many points as desired.
Pre-adjust the first test frequency (either more than F> or less
than F<). Select ON+TIME: as the relay trips, test goes OFF;
pressing the multi-function knob tripping values can be saved.
The TRIP LED (43) turns on and parameters at trip are
displayed until ON or ON+TIME are selected. Confirm save
results pressing the multi-function knob, and proceed with
other test frequencies, until all points to be tested are
measured.
DOC. MIE91093 Rev. 1.34 Page 53 of 145
1.7.1. Introduction
L oad 3
L oad 2
L oad 1
Next steps depend upon the type of relay and upon the type of
test you want to perform. The following example applies to a
frequency ROC relay with:
. A frequency range, from F< to F>, within which it does not
trip;
. Absolute min and max frequencies, F<< and F>>, below and
above which it trips in time T2;
. For frequencies between F< and F<<, or between F> and
F>>, it trips with delay T1 if ROC is more than the set
DOC. MIE91093 Rev. 1.34 Page 55 of 145
In the dashed area the relay trips only if the ROC is higher
than the threshold.
V pre-fault = VN/1.73
Standard values are: 57.8 V for VN = 100 V; 63.5 V for VN =
110 V.
After this adjustment the pre-fault voltage is generated prior
to all tests, as the unit is OFF. Select ON: as the test is
started, the voltage goes to the fault value, that is adjusted by
the knob (20). Adjust the fault value at the same value as the
pre-fault.
First of all, set the maximum test time as 1.5 * T1, so that we
do not waste time:
Test control > Fault injection > Timed > 1.5*T1 (RET)
DOC. MIE91093 Rev. 1.34 Page 58 of 145
Now, set the starting frequency to F>; then, set the first value
for ROC:
AUX VAC/VDC > Aux VAC control > Frequency > Adjust
F> (RET)
Adjust ROC
The test procedure is the same as the one for the frequency
relay; tmax must be set to 0.8*T1.
The test procedure is the same as the one for the frequency
relay; tmax must be set to 0.8*T1.
1.8.1 Introduction
When these three conditions are reached, the relay will give
permission to close the
switchgear and connect the
G3
generator to the power line.
Note that in the following, all tests will start from a non
synchronized condition. Consider that prior to test start the
DOC. MIE91093 Rev. 1.34 Page 61 of 145
. Next, we find the drop-off threshold for V>. From the voltage
above, slowly increase it; as the relay resets, confirm save
results pressing the multi-function knob, and proceed.
NOTE: stored values are the voltages as the relay resets. This
corresponds to the relay drop-off only if the voltages did not
change very much while the relay timing elapsed; however,
reset timing is usually very short, so the voltage does not
change very much at release, and the measurement is
accurate.
. Now, repeat the procedure for V<. The starting voltage (pre-
fault and fault) will be less than VN (for instance, 90 V); the
threshold and drop-off for V< are found.
DOC. MIE91093 Rev. 1.34 Page 64 of 145
. Next, we find the drop-off threshold for A>. From the angle
above, slowly increase it; as the relay resets, confirm save
results pressing the multi-function knob, and proceed.
Now, repeat the procedure for A<. The starting angle will be
less than 0° (for instance, 315°); the threshold and drop-off
for A< are found.
time that allows the relay to reset; after this, test starts by
changing only the frequency of V2.
Reactance
4
0 Resistance
-10 -8 -6 -4 -2 0 2 4 6 8 10
-4
-8 Relay Characteristic
Generator Working Point
-12
-16
-20
The relay detect the loss of field fault when the working point
enters the relay characteristic curve (the circle). The typical
parameters for LOF relays are the following.
K2 R
K1
Let’s start with the test of point A, that means to measure the
parameter K2. Finding it means to move from a point having
zero impedance and increasing the impedance along the –X
axis. As we have to generate voltage and current at a given
phase angle, the first step is to convert impedance into these
parameters. Steps to be followed are:
. Compute the impedance corresponding to K2 and K1. For
instance, if we have the following setting:
- VN = 100 V;
- IN = 5 A;
- ZN = 11.56 Ohm;
- K2 = 0,1;
- K1 = 1
Then:
ZA = 1.156 Ohm;
DOC. MIE91093 Rev. 1.34 Page 72 of 145
Last, what about testing other points, like D? You can either
set current and angle and decrease the voltage, or set current
and voltage and decrease the angle.
1.11.1 Introduction
FAULT
OPEN
CLOS
E
Tof
Ton
CB Open - Closed
. The test is performed on the pair made of the relay and the
Recloser. All connections from the relay to the Recloser shall
be left. Nothing changes if the Recloser is inside the relay. The
relay can be of any type.
DOC. MIE91093 Rev. 1.34 Page 77 of 145
The reclaim time test, that is the test that the reclaim time is
correctly set, cannot be performed directly, because the
Recloser does not have an auxiliary output that trips as it
expires. For this reason, the reclaim time is tested with two
test sequences, as follows.
FAULT 1 2 N+1
TRIP 1 2 N+1
CLOSE 1 2 N+1
CLOSED
CB POS
OPEN
D1 R1 >TDr
The first fault starts the sequence. The relay trips after D1;
the Recloser sends a reclose command after R1. The test set
automatically injects fault No. 2 after the programmed TD,
that is more than TDr: the Recloser sends the reclose
command No. 2. If N = 1, the sequence is completed; else,
DOC. MIE91093 Rev. 1.34 Page 79 of 145
The second test allows also to verify the reclose timings RX,
and the number of reclose commands, N.
1 2 N+1
TRIP 1 2 N+1
CLOSE 1 2 (N+1
)
CLOSED
CB POS
OPEN
D1 R1 <TDr
The first fault starts the sequence. The relay trips after D1;
the Recloser sends a reclose command after R1. The test set
automatically injects fault No. 2 after the programmed TD,
that is less than TDr. If N = 1, the sequence is completed;
else, tests will continue until fault N+1 is generated, followed
by open N+1, but no reclose N+1; the CB will be left open.
The test set waits for the last close command for a time equal
to 10 times the last measured RX delay; then, the sequence is
finished.
The two tests together allow verifying TDr with the set
accuracy (for instance, 5%).
DOC. MIE91093 Rev. 1.34 Page 80 of 145
Note that the test set will produce N+1 test result pairs,
grouped in pairs on the bottom left of the display.
DOC. MIE91093 Rev. 1.34 Page 81 of 145
Start the test with ON+TIME. For each fault X, the display
shows on one line two test results: to the right, the relay trip
delay; to the left, the reclose delay. Test result time are four
digits with autoranging, so that the percent accuracy is the
same for fast and slow reclose times. It is possible to monitor
the test evolution looking at these times, and also at the STOP
and START lights ; the TRIP light follows the relay trip.
For the first test sequence, all tests will have two meaningful
timings ; for the second one, after the last test, the START
light will not turn on : this confirms that the Recloser has
expired all the programmed reclose attempts.
In all instances, as the test is over, the ON+TIME light turns
off, the test set goes to OFF, and the display shows the
message of results recording.
For the second test sequence, the last time result will be 0 s,
confirming that there was no trip within 10 times the last
measured reclose delay.
DOC. MIE91093 Rev. 1.34 Page 82 of 145
I POLE
MOUNTED CB
CB POSITION
The reclaim time test, that is the test that the reclaim time is
correctly set, cannot be performed directly, because the
Recloser does not have an auxiliary output that trips as it
expires. For this reason, the reclaim time is tested with two
test sequences, as follows.
FAULT 1 2 N+1
CLOSED
CB POS
OPEN
D1 R1 >TDr
DOC. MIE91093 Rev. 1.34 Page 84 of 145
The first fault starts the sequence. The CB opens after D1, and
then closes after R1. The test set automatically injects fault
No. 2 after the programmed TD, that is more than TDr: the CB
opens and closes again. If N = 1, the sequence is completed;
else, tests will continue until fault N+1 is generated, followed
by open N+1 and reclose N+1.
The second test allows also to verify the reclose timings RX,
and the number of reclose commands, N.
FAULT 1 2 N+1
CLOSED
CB POS
OPEN
D1 R1 >TDr
The first fault starts the sequence. The relay trips after D1;
the CB closes after R1. The test set automatically injects fault
No. 2 after the programmed TD, that is less than TDr. If N =
1, the sequence is completed; else, tests will continue until
fault N+1 is generated, followed by open N+1, but no close
N+1; the CB will remain open.
The test set waits for the last close for a time equal to 10
times the last measured RX delay; then, the sequence is
finished.
The two tests together allow verifying TDr with the set
accuracy (for instance, 5%).
DOC. MIE91093 Rev. 1.34 Page 85 of 145
Note that the test set will produce N+1 test result pairs.
Start the test with ON+TIME. For each fault X, the display
shows on one line two test results: to the right, the relay trip
delay; to the left, the reclose delay. Test result times are four
DOC. MIE91093 Rev. 1.34 Page 86 of 145
For the first test sequence, all tests will have two meaningful
timings ; for the second one, after the last test, the START
light will not turn on: this confirms that the CB has not closed.
In all instances, as the test is over, the ON+TIME light turns
off, the test set goes to OFF, and the display shows the
message of results recording.
For the second test sequence, the last time result will be 0 s,
confirming that there was no trip within 10 times the last
measured reclose delay.
NOTE: if it is wished to avoid waiting this time, which can be
very long, select OFF to stop the test: test results will be
saved anyway, and the last delay, no trip, will be displayed as
0.000.
DOC. MIE91093 Rev. 1.34 Page 87 of 145
1.12.1 Introduction
Z3
Z2
Z1
Z=V/I
During our tests, we do not modify the test angle and the test
current: as a consequence, the fault impedance becomes a
function of the test voltage only. Now, the point is that a
setting of nominal value Z is verified when we find that:
. With a fault at Z-d the relay trips in zone N;
. With a fault at Z+d the relay trips in zone N+1.
PH 3-1 1 PH VN V1 V1 VN V1 VN
V R N
V
R
I R
V T
V S
1) Fault current
Choose the test angle in the R-X plane. If the distance relay is
set on the CT star point towards Busbar, the angle Φ(I-V) has
the same value but negative, otherwise it has the same value.
These angles depend upon the test angle and the supply: see
the table below. The angle is adjusted prior to actual zone
testing, as follows.
Start the test; adjust the fault current; adjust the fault voltage
at 30 V. Now select the auxiliary Vac phase with respect to the
current, as follows:
AUX VAC/DC > Aux Vac control > Phase > Reference:
current ESC
This adjustment will not be modified during tests.
DOC. MIE91093 Rev. 1.34 Page 95 of 145
Given the fault impedances Z1, Z2, Z3, Z4 of the zone limits,
compute as follows the corresponding fault voltages V1, V2,
V3, V4:
Vf = Z*If*(1+KoL)
Where: T1, T2, T3, T4 are respectively the time settings for
zones 1, 2, 3, 4 (case of three zones plus the starter).
Z1 = (VT11+VT12)/(2*If*(1+KoL))
Once a limit has been found, repeat the test for other zone
limits. During these tests, current and phase are no more
modified.
The test continues with the following fault voltages, until all
limits are tested. The starter limit is found between 1.2 s trip
DOC. MIE91093 Rev. 1.34 Page 97 of 145
time and no trip. This limit can also be found starting the test
with V1=VN, and then lowering V1 until the relay trips.
If the starter is over-current, and it is desired to find threshold
settings IVN and IVo, the test is performed as a time
independent over-current relay, but test voltage will be 0 V for
the test of IVo, and VN for the test of IVN.
Note that in this type of fault the fault voltage is the phase to
phase voltage; fault currents are identical in module and
opposite in phase; the fault current angle is metered with
respect to the phase to phase voltage.
1) Fault current
For instance: If = 10 A
Vf = 20 * Z; with Z = 1 Ohm, Vf = 20 V.
VX = 30.58 V
The third phase does not change its amplitude, equal to VN.
4) Phase angle
φX1 = atg(Vf/VN)
φX1
V2 V3
Vf V’3
These values apply for the test of the zone having the
impedance of 1 Ohm ; for other zones they should be
repeated.
Vf1
V2 V’2 V3
Vf2 V’3
V R N
V
I
T
R
I
R
V T V S
V T N I S
V S N
DOC. MIE91093 Rev. 1.34 Page 102 of 145
PHASE 1
PHASE 2
PHASE 3
6.66 ms
1) Fault current
Choose the test angle in the R-X plane. If the distance relay is
set on the CT star point towards Busbar, the angle Φ(I-V) has
the same value but negative, otherwise it has the same value.
These angles are adjusted prior to actual zone testing, as
follows.
Start the test; adjust the fault current; adjust the fault voltage
at 30 V. Now select on all T1000 PLUS the auxiliary Vac phase
with respect to the current, as follows:
AUX VAC/DC > Aux Vac control > Phase > Reference:
current ESC
This adjustment will not be modified during tests.
DOC. MIE91093 Rev. 1.34 Page 103 of 145
Given the fault impedances Z1, Z2, Z3, Z4 of the zone limits,
compute as follows the corresponding fault voltages V1, V2,
V3, V4:
Vf = Z*If
For instance: If = 10 A
Vf = 10 * Z
Z1 = (VT31+VT32)/(2*If)
Once a limit has been found, repeat the test for other zone
limits. During these tests, current and phase are no more
modified.
The test continues with the following fault voltages, until all
limits are tested.
DOC. MIE91093 Rev. 1.34 Page 105 of 145
reading the number of impulses after the test, N2. The applied
energy is:
Es = (N2 – N1) * Ks.
The energy Et measured by the meter under test is read on
the display. The error of the meter under test is
E% = (Et – Es) * 100 / Es
Et = N * Kt
The error of the meter under test is:
E% = (Et – Es) * 100 / Es
ADJUSTMENT
KNOB
DISK OR
LED SWITCH LED TURNS ON
PRESSED = AS THE MARK
DISK IS DETECTED.
The reading head can be used for rotating disk meters, and for
meters with an LED signaling light.
For rotating disk meters, power-on the head, and press the
Disk or LED Switch to the left. Then, mount the scanning head
so that the green light is lighting the rotating disk.
DOC. MIE91093 Rev. 1.34 Page 111 of 145
Next, start the Energy Meter program, select the Manual test
to feed the meter, and move the adjustment knob so that the
LED on the head front blinks as the mark is passing below the
head: the clockwise knob rotation increases the detector
sensitivity. You are now ready to perform the desired test.
For LED meters, first of all, the light can be red, but not green
or blue.
Power-on the head, and press the Disk or LED Switch to the
left. Then, mount the scanning head so that the green light
from the the head is lighting the meter’s LED; then, release
the Disk or LED Switch: the light is removed.
Next, press ON, so that the energy meter turns, and move the
adjustment knob so that the LED on the head front blinks as
the meter’s LED is blinking: the clockwise knob rotation
increases the sensitivity. You are now ready to perform the
desired test.
DOC. MIE91093 Rev. 1.34 Page 112 of 145
1.15.1 Introduction
These values are the p.u. nominal current at relay level after
the CT. They are fundamental when calculating the test
currents to apply to the relay.
Pn
I1
3 * V1
Pn
I2
3 *V2
I1 I2
I "1 I "2
CTR1 CTR2
DOC. MIE91093 Rev. 1.34 Page 114 of 145
The following is the D1000 front panel. There are two pairs of
sockets: IN and OUT. IN is to be connected to the VCAUX
output of T1000 PLUS; D1000 converts the voltage into
current, and generates the differential current, that is
measured prior to connection to the relay. So, when we say
that the differential current is to be adjusted, this means
adjusting the auxiliary voltage.
DOC. MIE91093 Rev. 1.34 Page 117 of 145
A a
B b
I I
C c
1 2
N n
DOC. MIE91093 Rev. 1.34 Page 118 of 145
1st test
2nd test
Restraint Current:
IA IB I1 ( I1 I 2 )
2 * I1 I 2
IR
2 2 2
Differential Current: I D I A I B I1 ( I1 I 2 ) I 2
Other tests
1: Select Formula 1
2: Select Ext_I
5: and confirm
IA I1
ID IB ( I1 I 2 )
3 3
1.5
0.5
0
0 0.005 0.01 0.015 0.02 0.025
-0.5
-1
-1.5
I1 + I2
A a
100 Hz 50 Hz B b
I I C c
2 1
N n
Test procedure:
Connect the two currents to the relay input;
Increase I1 only until the relay trips;
Then increase Aux to increase the current from D1000
or TD1000, until the relay trip drops out.
Take note of the two currents and calculate the 2nd Harm %
H%: the harmonic percentage is, with D1000:
Ext _ I
H% *100
Iac Ext _ I
2 2
NOTE
Warning
The two T1000 PLUS must be supplied with the same phase,
either VR, or VY or VB. Since it is almost impossible to
determine what phase is used on each terminal, the SWT3
helps switching the power supply from one phase to another to
get the correct phase reference that will provide either almost
0 A or 400 A
DOC. MIE91093 Rev. 1.34 Page 129 of 145
IR
IB IY
IR Remote
IR local
IB local IY Remote
IB Remote
IY local
In this case there are already 60° phase shift between phase R
local end and the phase R of the remote end. Supposing you
have connected the T1000 PLUS to phase R in the remote end,
you have three possibilities on the local end:
Stop any injection, enter the Relay Menu and set the
instrument as follows:
MENU > TEST CONTROL > Fault Injection > Timed
Set Tmax = 0.1 s
NOTE
The relay trip can be achieved in two ways:
1. Telephone communication with the control room
2. Connect the trip command, available at the CB control box,
to digital input STOP of the T1000 PLUS
At the end of the tests, you have the time versus current
curve, from which you can derive the time versus temperature
curve, given the conversion coefficients.
1.18.1. Introduction
Now we can measure trip timings, following the I-t curve with
as many points as desired.
Now, press ON and pre-adjust the first test current: if the CB
trips, don’t save test result; go OFF. Select ON+TIME: as the
CB trips, test goes OFF; pressing the multi-function knob,
tripping values can be saved. Confirm save results pressing
the multi-function knob, and proceed with other test currents,
until all points to be tested are measured.
1.19.1. Introduction
Then, compute:
. Maximum voltage at IN: Max V(IN) = VA / IN;
. Knee voltage = Max V(IN) * P
AP PE N DI X 1 O VE R C UR RE NT R EL A YS
A) Parameter KT
KT* a
t (s) c
b
I
1
IR
Constants of the formula change according to the type of
curve; they are summarised in the following table.
IEC, IEEE a c b
IEC Class A Standard Inverse 0.14 0 0.02
IEC Class B Very Inverse 13.5 0 1
IEC Class C Extremely Inverse 80 0 2
IEC Long Time Inverse 120 0 1
IEC Short Time Inverse 0.05 0 0.04
b d e
t (s) K * a 3
I c I c
T 2
I
I
I c
I R R R
IAC, ANSI a b c d e
IAC Inverse 0.2078 0.863 0.8 -0.418 0.1947
IAC Short Time 0.0428 0.0609 0.62 -0.001 0.0221
Inverse
IAC Long Time 80 0 2 2 2
Inverse
IAC Very 0.09 0.7955 0.1 -1.2855 7.9586
Inverse
IEC Extremely 0.004 0.6379 0.62 1.7872 0.2461
Inverse
b
t ( s ) K T * a
c
I
1
IR
US a c b
US Moderately Inverse 0.0226 0.0104 0.02
US Inverse 0.18 5.95 2
US Very Inverse 0.0963 3.88 2
US Extremely Inverse 0.0352 5.67 2
DOC. MIE91093 Rev. 1.34 Page 143 of 145
B) Parameter t (I>)
ts
A
F (tI )
a
I where:
1
IR
1
A
F B
10a 1
t(I>) = Set time delay at 10 times the Pick-up Current.
A B a
IEC Class A 0.14 0 0.02
Standard Inverse
IEC Class B Very 13.5 0 1
Inverse
IEC Class C 80 0 2
Extremely Inverse
IEC Long Time 120 0 1
Inverse
IEC Short Time 0.05 0 0.04
Inverse