Digital Weight Transmitter With 4 Channels: User Manual
Digital Weight Transmitter With 4 Channels: User Manual
Digital Weight Transmitter With 4 Channels: User Manual
www.diniargeo.com
Contents
Introduction 7
On / Off 23
Equalisation 30
Gravity 33
4
USER_MAN_ENG_DGTQ_V8
Selection of the PC serial port 44
Diagnostics 54
Cells / converter test 54
Firmware release 54
Serial number 54
Display 54
Keypad 54
Serial ports 55
CTS signal 55
Inputs 55
Outputs 55
Analog output 55
Alarms 57
Optimized layout for A4 print.
5
USER_MAN_ENG_DGTQ_V8
Optimized layout for A4 print.
6
USER_MAN_ENG_DGTQ_V8
Introduction
Dear Customer,
Thank you for purchasing a DINI ARGEO product.
This manual contains all the instructions for a correct installation and commissioning of the DGTQ 4-channel digital weight transmitter.
While thanking you for purchasing this product, we would like to draw your attention to some aspects of this manual.
This booklet provides useful information for the correct operation and maintenance of the scale to which it refers; it is therefore essential
to pay the greatest attention to all those paragraphs that illustrate the simplest and safest way to operate.
It is recommended that you carefully follow the instructions for programming the weight transmitter; performing actions not indicated in
this manual could compromise the proper functioning of the scale.
The utmost care has been taken in compiling this manual, but reports of any inaccuracies are always welcome.
The instrument is covered by warranty and MUST NOT BE TAMPERED WITH BY THE USER under any circumstances.
Any attempt at repair or modification may expose the user to the danger of electric shock and voids any warranty conditions, relieving
the Manufacturer from all liability.
Any problem with the product must be reported to the manufacturer or to the retailer where it was purchased.
In any case, always TURN OFF THE POWER SUPPLY before any installation or repair operation.
7
USER_MAN_ENG_DGTQ_V8
Transmitter installation
Installation requirements
Observe the following conditions for correct installation of the transmitter and of the load receiver:
8
USER_MAN_ENG_DGTQ_V8
Electrical precautions
• Use a regulated mains supply within ± 10% of the rated voltage.
• The electrical protections (fuses, etc.) are the responsibility of the installer.
• Observe the recommended minimum distances between cables of different categories (see table on page 10).
• The following cables must comply with the maximum permissible lengths (see table on page 10), they must be shielded and must
be inserted alone in metal conduits or pipes:
- the load cell extension cables;
9
USER_MAN_ENG_DGTQ_V8
RECOMMENDED DISTANCES AND CABLE CLASSIFICATION
≥ 100 mm
≥ 200 mm
≥ 500 mm
Distance ≥ 100 mm
≥ 500 mm
≥ 500 mm
Coaxial cables.
CURRENT:
100 metres with 2 x 0.25 mm2 cable;
50 metres with 150 metres with 2 x 0.5 mm2 cable;
6 x 0.25 mm2 cable; 1200 m with shielded 2 x 300 metres with 2 x 1 mm2 cable.
15 m with baud rate up 24 AWG twisted pair with
100 metres with to 19200. outer braid + aluminium VOLTAGE:
6 x 0.5 mm2 cable. strip. 50 metres with 2 x 0.25 mm2 cable;
75 metres with 2 x 0.5 mm2 cable;
150 metres with 2 x 1 mm2 cable.
Optimized layout for A4 print.
10
USER_MAN_ENG_DGTQ_V8
Earthing of the system
For correct earthing and optimal system operation, the load cells, junction box, if any, and weighing structure must be earthed.
EXAMPLES:
• If the load cells are connected to the transmitter through a junction box, the cable shield from the transmitter and the cell cable shields
must be connected to the earth socket of the junction box (refer to the junction box manual) and the junction box must be earthed using
a copper cable with a cross-section of not less than 16 mm2.
• If the load cells are connected directly to the transmitter (without using the junction box), the cell cable shields must be connected to the
earthing point (or earth bar).
• If the weighing system involves large and/or outdoor structures (weighbridges, silos, etc.) and the distance between the junction box and
the weight transmitter is greater than 10 m, connect the cell cable shields to the earth socket in the junction box.
WEIGHING STRUCTURE
Earth the weighing structure and/or any unconnected structures (e.g. silos that release material onto the weighing structure) using cables
with a cross-section of not less than 16 mm2.
Also connect the upper part with the lower part of each cell by means of a copper braid with a cross-section not less than 16 mm2 (refer
to the earthing examples on page 12 and page 13).
GENERAL NOTES:
• All earth cables must be of suitable length, so as to obtain an overall resistance of the earthing system of less than 1 Ω.
• If the weighing system involves large and/or outdoor structures (weighbridges, silos, etc.):
- the earth connection must be made by connecting the earth cables to an earth bar and the earth bar to the earth post
with a cable having a cross-section of not less than 50 mm2;
- the thickness of the cables must be greater (50 mm2 instead of 16 mm2 and 100 mm2 instead of 50 mm2), because the
voltages at stake are greater (e.g. lightning);
- the earth post must be placed at a distance of at least 10 m from the structure.
• If the load receiver is more than 10 m from the transmitter, we recommend using the SENSE line and load cells equipped
with a (SENSE) compensation circuit.
Optimized layout for A4 print.
11
USER_MAN_ENG_DGTQ_V8
EXAMPLE OF EARTHING OF A WEIGHBRIDGE
Weight transmitter
Load cell
Weighbridge
Earth cables
Ø 8 - sec. 50 mm2
Ø 11.3 - sec. 100 mm2
Drilled copper plate positioned
on the side wall
Weighbridge
12
USER_MAN_ENG_DGTQ_V8
EXAMPLE OF EARTHING OF A SILO
Protective earth
bypass for the
load cell
Load cell
13
USER_MAN_ENG_DGTQ_V8
Technical features
POWER SUPPLY 12 ÷ 24 Vdc LPS or with class 2 power supply.
DISPLAY DIVISIONS 10000e, 2 x 3000e for legal weighing, expandable up to 800,000 for internal use (with a
minimum cell signal of 1.6 mV/V).
SAMPLING SPEED Up to 400 conv. / sec.
MINIMUM VOLTAGE PER DIVISION 0.3 µV (approved instrument); 0.03 µV (non-approved instrument).
KEYPAD 5 keys.
LOAD CELL POWER SUPPLY 5 Vdc ± 5%, 120 mA (max 8 cells of 350 Ω).
LOAD CELL CONNECTION 6 wires (CELL1) with sense, 4 wires (CELLS 2, 3, 4).
14
USER_MAN_ENG_DGTQ_V8
Load cell installation
After carrying out the instructions for the platform or load receiver, the shielded cable from the cell(s) must be properly connected to the
terminal block(s) of the transmitter (from CELL1 to CELL4; see section “Wiring diagrams”).
The transmitter has one channel (CELL1) for 6-wire connection to load cells (using the SENSE), while for the remaining channels (CELL2,
CELL3, CELL4) only 4-wire connection is allowed.
The SENSE allows you to compensate for any voltage drop on the section of cable connecting the transmitter to the load receiver.
It is especially useful when the distance between the transmitter and the load receiver is more than 10 metres.
S+
S+
S+
S+
- - - -
+
+
E+
E+
E+
E+
E-
E-
E-
E-
- - - -
+
+
S-
S-
S-
S-
SEN +
SEN +
SEN +
SEN +
EXC +
EXC +
EXC +
EXC +
SIG +
SIG +
SIG +
SIG +
SEN -
SEN -
SEN -
SEN -
EXC -
EXC -
EXC -
EXC -
SIG -
SIG -
SIG -
SIG -
26 25 24
26 23
25 22
24 21
23 22 21 26 25 24
26 23
25 22
24 21
23 22 21
LOAD CELL
LOAD CELL LOAD CELL
LOAD CELL
6-WIRE CONNECTION CELL1 4-WIRE CONNECTION CELL1
J1 J2
J1
SENSE
CELL 2 CELL 1
CELL 3 CELL 4
15
USER_MAN_ENG_DGTQ_V8
Optimized layout for A4 print.
CAL
Internal use
Wiring diagrams
DGTQ - DGTQAN
E-
-
+
V+ EXC -
26
S- S+
COM - EXC +
25
-
ANALOG
I+
13 12 11
SEN - +
24
E+
B (-) SEN +
10
23
LOAD CELL
9
A (+) SIG -
COM1
22
SIG +
8
21
GND
16
RX2
COM
COM2
6
TX2
OUT 1
USER_MAN_ENG_DGTQ_V8
5
IN 2 OUT 2
4
IN 1 OUT 3
INPUT
3
COM
OUTPUT
OUT 4
-
2
GND OUT 5
12 ÷ 24 Vdc
OUT 6
20 19 18 17 16 15 14
+
+ Vdc
POWER
E-
-
+
V+ EXC -
26
S- S+
COM - EXC +
25
-
ANALOG
I+
13 12 11
SEN - +
24
LOAD
T
3
COM
PUT
OUT 4
-
2
GND OUT 5
12 ÷ 24 Vdc
OUT 6
16 15 14
+
+ Vdc
POWER
DGTQPB
CAL
Internal use
E-
-
+
V+ EXC -
26
S- S+
COM - EXC +
25
-
ANALOG
I+
13 12 11
SEN - +
24
E+
B (-) SEN +
10
23
LOAD CELL
9
A (+) SIG -
COM1
22
SIG +
8
21
GND
7
RX2
17
COM
COM2
6
TX2
PROFIBUS
OUT 1
USER_MAN_ENG_DGTQ_V8
5
IN 2 OUT 2
4
IN 1 OUT 3
INPUT
3
COM
OUTPUT
OUT 4
-
2
GND OUT 5
12 ÷ 24 Vdc
OUT 6
20 19 18 17 16 15 14
+
+ Vdc
POWER
NET F W1 W2
SP1 SP2
18
USER_MAN_ENG_DGTQ_V8
Advanced programming menu
The advanced menu contains all the transmitter configuration parameters for the most advanced adjustments.
i
HOW TO EXIT THE SETUP AND SAVE CHANGES
In the menu description on the following pages the symbol indicates repeated pressing of the key until the parameter
indicated is reached.
Optimized layout for A4 print.
19
USER_MAN_ENG_DGTQ_V8
Block diagram of the menu
A
888888 TYPE Mode of use (page 22).
C 1 1
setup ConfiG nChan Continued on page 21.
...
2 Display updating frequency (page 33).
dsp.rf
2
Com.prn Printer port configuration (page 45).
5 1
inputs inp.01
Digital inputs (page 40).
2
inp.02
6 1
output out.01
Digital outputs (page 41).
2
out.02
D
diaG Diagnostics (page 54).
20
USER_MAN_ENG_DGTQ
Full ConfiG setup menu is displayed.
3
Filt.50
2
auto-0
4
0.traCk
6 1
Calib deCi
2
u.m.
3 Calibration parameters
div
4
ranGe1
5
ranGe2
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
21
USER_MAN_ENG_DGTQ
Mode of use of the DGTQ
2 1 scale mode.
ind.Ch
3 4 scale mode.
transm
Mode 1 “DEP.CH”
Allows you to connect the load cells (from 2 to 4) directly and to equalise them.
Cell 1 Cell 2
NET F W1 W2
SP1 SP2
Cell 3 Cell 4
Mode 2 “IND.CH”
Allows you to connect a single cell or a multi-cell scale with a junction box.
NET F W1 W2
SP1 SP2
Scale 1
22
USER_MAN_ENG_DGTQ
Mode 3 “TRANSM”
Allows you to manage up to 4 independent scales.
Scale 1 Scale 2
NET F W1 W2
SP1 SP2
Scale 3 Scale 4
On / Off
STAND-BY CONDITION
32 31 30
CELL3 During normal
29 28 27
operation, pressing and holding the key
CELL2
26 25 24 23 22 21 20 19 18
CELL1 for 2 seconds switches the transmitter to standby mode.
SIG+ EXC- EXC+ SIG- SIG+ EXC- EXC+ SIG- SIG+ EXC- EXC+ SEN- SEN+ SIG- SIG+
From stand-by mode you can turn on the transmitter by pressing the key .
INPUT RELAYS RS232
3 4 5 6 7 8 15 16 17
To turn off the transmitter completely, you must shut down the power supply.
COM IN1 IN2 RL1 RL2 COM TX RX GND
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
23
USER_MAN_ENG_DGTQ
Theoretical calibration
Dependent channels
A 3
888888 TYPE dep.Ch
C 1 1
Setup ConfiG nChan
6 1
Calib DECI
2
U.M.
3
DIV
4
RANGE1
7 1
theo.CA Cel.sen
2
Cel.Cap
3
Dead.ld
4
kno.wGt
CALIBRATION PROCEDURE:
5. Enter the weight value of the structure in the dead.ld parameter. If you do not know this value, enter “0”.
6. If the structure contains a quantity of material whose weight value is known (e.g. full silo), enter this value in the KNo.WGT parameter.
24
USER_MAN_ENG_DGTQ
Independent channels / transm
A 2
888888 TYPE Ind.Ch
C 1 1
Setup ConfiG nChan
2
Chan
6 1
Calib DECI
2
U.M.
3
DIV
4
RANGE1
7 1
theo.CA Cel.sen
2
Cel.Cap
3
Dead.ld
4
kno.wGt
CALIBRATION PROCEDURE:
6. Enter the weight value of the structure in the dead.ld parameter. If you do not know this value, enter “0”.
7. If the structure contains a quantity of material whose weight value is known (e.g. full silo), enter this value in the KNo.WGT parameter.
9. If transm mode has been selected, repeat the procedure from point 3 for each scale to be calibrated.
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
25
USER_MAN_ENG_DGTQ
Calibration with sample weights
6 1
Calib DECI
2
U.M.
3
DIV
4
RANGE1
7 1
Calib.p equal
2
n tp
3
tp 0
4
ddt1
5
tp 1
6
ddt2
7
tp 2
8
ddt3
9
tp 3
CALIBRATION PROCEDURE:
26
USER_MAN_ENG_DGTQ
5. Acquire the calibration points:
i
For successful calibration, the value of the largest sample weight must be at least 50% of the capacity.
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
27
USER_MAN_ENG_DGTQ
Independent channels / transm
A 2
888888 TYPE ind.Ch
C 1 1
Setup ConfiG nChan
2
nChan
6 1
Calib DECI
2
U.M.
3
DIV
4
RANGE1
7 1
Calib.p equal
2
n tp
3
tp 0
4
ddt1
5
tp 1
6
ddt2
7
tp 2
8
ddt3
9
tp 3
CALIBRATION PROCEDURE:
28
USER_MAN_ENG_DGTQ
5. Acquire the calibration points:
i
For successful calibration, the value of the largest sample weight must be at least 50% of the capacity.
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
29
USER_MAN_ENG_DGTQ
Equalisation
If the dependent channel mode has been set, you can improve the accuracy of the system by digitally equalising the connected cells.
888888 A 1
TYPE dep.Ch
C 1
Setup ConfiG
6 1
Calib deCi
7 1
Visible only if
Calib.p equal reset? type = Dep.Ch
2 1
4 3 4 3
press press press
4 3
press press
(visible only if (visible only if
CHAN = 3) CHAN = 4) n tp
i
Equalisation can only be performed if the system is configured with dependent channels and calibration with sample weights is
active.
For successful equalisation, it is advisable to use a compact weight with as small a supporting surface as possible, so that it rests
as much as possible on only one cell. The weight value must be at least 20% of the capacity.
30
USER_MAN_ENG_DGTQ
Manual calibration
888888 A
TYPE
C 1
Setup ConfiG
6 1
Calib deCi
8
man.Cal
If you know the number of ADC converter points for a known weight (for example if you want to copy the calibration from one transmitter
to another) the calibration points can be entered manually:
2. Using the and keys, select the calibration point you want to enter / change (from 0 to 3).
Press the key to confirm.
3. The display shows weiGht, use the , and keys to enter the weight value.
Press the key to confirm.
4. The display shows points, use the , and keys to enter the converter points value.
Press the key to confirm.
i
Repeat the procedure for each calibration point.
If transm mode has been selected, the procedure must be repeated for each scale (CHAN 2, 3, 4).
888888 A
TYPE
i
If transm mode has been selected, it is first necessary to
C 1
Setup ConfiG select the channel on which the zero calibration is to be
performed (CHAN 1 2, 3, 4).
7
0.Calib
ADC ADC
Kg Kg
Tp 0 Tp n Tp 0 Tp n
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
31
USER_MAN_ENG_DGTQ
Filter and stability
Filter adjustment
888888 A
TYPE
C 1
Setup ConfiG
5 1
Param Stabil
i
In the case of an approved instrument, it is possible to select only FLT filters.
The higher the filter value, and greater is its intervention.
888888 A
TYPE
C 1
Setup ConfiG
5 1
Param Stabil
5
div.stb
The value 0 disables the stability control. From 0 to 99.
By entering a value other than 0, you enable stability control. = 02.
Enter the number of deviation divisions beyond which the transmitter detects instability. = 02.
32
USER_MAN_ENG_DGTQ
Display updating frequency
Additional filter that acts only by displaying the weight, thus increasing its stability.
Useful in particular applications where you want to make the weight more stable in the eyes of the operator.
A
i
888888 TYPE
This parameter does not affect the actual speed and stability of the weight
(set via the filter). It only affects the indication of the weight on the display.
C 1
Setup ConfiG
2 1
dsp.rf norm Function disabled.
2 1 display update per second.
1 hz
3 2.5 display updates per second.
2.5 hz
4 5 display updates per second.
5 hz
5 10 display updates per second.
10 hz
6
20 hz 20 display updates per second.
Gravity
888888 A
TYPE
C 1 1
Setup ConfiG param
From 9.75001 to
4
Grav 9.84999.
= 9.80390.
i
In the case of an approved transmitter, the value is read-only.
EXAMPLE:
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
33
USER_MAN_ENG_DGTQ
Zeroing parameters
888888 A
TYPE
C 1 1 1
Setup ConfiG param stabil
2 % auto-zeroing on ignition.
auto.0
3 % manual zeroing.
0-perC
4 Zero tracking.
0.traCk
Auto-zeroing on ignition
2 1 Disabled.
auto.0 disab
2 1 Enabled, enter in C.PERC the % value of the capacity. from 0 to 50%.
enab C.perC
from 0 to 10%.
3
CyCle 1
C.perC In Ind.Ch mode, it is possible to perform an auto-zeroing
cycle of all connected scales. Enter in C.perC the % value
of the capacity. Visible only if
type ≠ ind.Ch
Zero tracking
This menu allows to set zero tracking, i.e. the compensation parameter of the thermal drift of the scale; the set value corresponds to
the number of divisions that is reset to zero in the fixed time of 1 second.
4 1 10 divisions.
0-perc tr 10
2 8 divisions.
tr 8
3 6 divisions.
tr 6
4 4 divisions.
tr 4
5 2 divisions.
tr 2
6 1 division.
tr 1
7 1/2 division.
tr1/2
8 1/4 division.
tr1/4
9 Tracking disabled.
TR no
i
In the case of an approved transmitter, it is possible to select the values tr1/2, tr1/4, tr no.
34
USER_MAN_ENG_DGTQ
Restoring zero
A
888888 Type
C 1
F.mode funCt
Semi-automatic zeroing
By pressing the key, or sending the zero command, the transmitter zeroes the gross weight on the scale. For a moment the display
shows “zero” and then it shows 0 (gross weight).
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
35
USER_MAN_ENG_DGTQ
Tare functions and parameters
Tare mode
A
888888 Type
C 1
F.mode funCt
5 Tare blocked. When the gross weight drops to 0, the tare remains
tare loCk engaged.
unloCK Tare unlocked. When the gross weight drops to 0, the tare is cleared.
Semi-automatic tare
By pressing the key, or sending the tare command, the transmitter sets as tare the weight on the scale. For a moment the display
shows “tare” and then it shows 0 (net weight). The light indicates that the net weight is shown on the display.
Predetermined tare
By holding down the key, or by means of the predetermined tare command, it is possible to enter a tare value manually.
For a moment the display shows “-tm-” and shows the tare present (or 0 if no tare is present).
Enter the tare value and press to confirm.
36
USER_MAN_ENG_DGTQ
Alibi memory
The alibi memory allows you to store the weight values transmitted to the computer for further processing and/or data integration.
The stored values can then be retrieved from the PC port or directly on the display of the transmitter for later checking.
C 1 1
F.mode funCt viss
4
alibi
Example
If the weighing that has been saved is as follows:
A weighing operation can only be saved if the weight ≥ 0, stable and valid (not underloaded or overloaded).
To store the weighing operation by key, the function must be active (see “Reactivating printing” on page 47).
In addition, if the transmitter is approved, the weight must exceed 20 divisions.
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
37
USER_MAN_ENG_DGTQ
Reading the alibi memory
FROM THE TRANSMITTER (MANUAL)
FROM PC
To read a weighing operation from a PC, see the serial command “READING A WEIGHING OPERATION IN THE ALIBI MEMORY” on
page 53.
FROM PLC
To read a weighing operation from a PLC, refer to the Modbus and Fieldbus protocol manuals.
i
If the alibi memory is empty, when the key is pressed the display shows “empty” for one second and returns to weighing mode.
If an invalid ID is entered, the display shows “No id” and returns to weighing mode.
C 1
Setup ConfiG
i
This operation deletes all saved weighing operations; it is not possible to delete a weighing operation individually.
38
USER_MAN_ENG_DGTQ
Use functions
A
888888 Type
C 1 1
F.mode funCt viss
2
peak
3
Conver
4
alibi
5
none
High resolution
viss Weight display in high resolution (x10). Press the key to activate or deactivate the function.
When the weight is displayed in high resolution, the indicator light is lit.
In the case of an approved transmitter, the high-resolution weight display is automatically deactivated after 5 seconds.
Peak detection
peak Detection of the maximum weight value during a time interval. Press the key to activate the function. The display shows
“-peak-” every 5 sec and the transmitter shows the maximum weight reached since the function was activated.
To deactivate the function press the again, the display shows “peakof” for a moment and shows the instantaneous
weight again.
By holding down the key it is possible to select in the piC.tim parameter the minimum time of the pulse duration,
expressed in hundredths of a second. The lower this value, the higher the peak function sensitivity.
Alibi memory
alibi (See section “Alibi memory” page 37).
No function
none No function when the key is pressed.
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
39
USER_MAN_ENG_DGTQ
Input configuration
888888 A
TYPE
C 1
Setup ConfiG
5 1
inputs inp.01 Such as inp.02 ( = zero).
2 1 No function.
inp.02 NoNE
2 key.
zero
3
tare key.
4
mode key.
5
print key.
6
C key.
7 Reboots the transmitter.
off
8 Disable keypad (and re-enable).
Dis.key
INPUT CONNECTION:
i
The input is activated when there is a potential difference between terminals 4 - 5 (IN1 and IN2)
and terminal 3 (INCOM). The inputs are bidirectional, therefore it is possible to invert GND and Vdc.
INPUT
COM
IN 2
IN 1
5 4 3
IN
GND
40
USER_MAN_ENG_DGTQ
Output configuration
888888 A
TYPE
C 1
Setup ConfiG
6 1 Such as out.06.
output out.01
6 1 1
out.06 funC 0 none No function.
2 Setpoint on gross weight.
1 Gros
3 Setpoint on net weight.
2 net
4 Gross weight on zero.
4 Gro.0
5 Net weight on zero.
5 net.0
out.01 = 1 Gros 6
out.02 = 1 Gros 6 moti Unstable weight.
out.03 = 0 none 7
23 k.pr Pressing the key.
out.04 = 0 none
out.05 = 0 none 8
25.k.mod Pressing the key.
out.06 = 0 none
9
26 k.C Pressing the key.
10
27.k.zer Pressing the key.
11
28.k.tar Pressing the key.
12 Error.
29 err
13 Setpoint on net weight with tare.
30.net.t
2 1 Contact normally open.
no/nC no
2 Contact normally closed.
nC
3 1 Direct activation / deactivation.
on.stat drCt
2 Activation / deactivation at stability.
stbl
4 1 Hysteresis disabled.
rl.ist ist.off
2 Hysteresis enabled.
ist.on
5 1 Activation duration time (s).
enab.tm 0.000
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
41
USER_MAN_ENG_DGTQ
Analog output configuration
The DGTQAN model has an analog output in voltage (0 - 5 / 0 - 10 Vdc) or current (4 - 20 / 0 - 20 mA).
888888 A
TYPE
C 1
Setup ConfiG
7
an.out 1
Chan Selection of the scale associated with the analog output.
Visible only if type = ind.Ch / transm and Chan ≥ 2.
i
Voltage or current operation is determined by the connection to the transmitter terminals:
COM -
COM -
COM -
V+
V+
V+
V+
I+
I+
I+
I+
13 12 11 13 12 11 13 12 11 13 12 11
42
USER_MAN_ENG_DGTQ
CALIBRATION PROCEDURE:
A B C
Connect a multimeter to the transmitter. Press to update the output value Increase or decrease the value to
Go to the parameter to be changed on the multimeter. reach the desired output.
(ao max, ao ze, ao min) and set an
approximate value. 100 D/A points ~ 0.015 V / 0.035 mA
1000 D/A points ~ 0.15 V / 0.34 mA
10000 D/A points ~ 1.57 V / 3.42 mA
Voltage output Current output 9.95
62650 ≈ 10 V 58600 ≈ 20 mA Example:
0≈0V 12700 ≈ 4 mA Increase ao max from 62650 to
0 ≈ 0 mA 62750.
D E F
Press to update the output value Repeat the procedure from point “C” Save the changes (press the key
on the multimeter. until the desired value is reached, several times until you reach the
then press to save. message save? , then press the
key to confirm).
9.98 10.00
V / mA V / mA
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
43
USER_MAN_ENG_DGTQ
Serial communication configuration
The transmitter has 2 serial ports (232 and 485) that can be used indiscriminately to communicate:
• In bidirectional mode with the PC / PLC (“PC” port);
• In one-directional mode with the PC, thermal printer, repeater (“PRN” port);
It is necessary to choose which port to use as PC and, consequently, which one to use as PRN.
C 1
Setup ConfiG
3 1 1
serial PC.sel Com1 Use of serial port 485as PC port (Pin 9-10).
2
Com2 Use of serial port 232 as PC port (Pin 6-7-8).
i
In model DGTQPB select port COM1 as PC port to communicate with the PLC through the built-in fieldbus.
44
USER_MAN_ENG_DGTQ
Configuration of the printer port (COM.PRN)
888888 A
TYPE
C 1
Setup ConfiG
3 1
serial PC.sel
2 1 Transmission mode.
Com.prn Pr.mode
2 Baud rate.
baud.pr
3 Parity.
prty.pr
4 Data bits.
bit.pr
5 Stop bits.
stop.pr
7 CTS signal.
Prn.Cts
8 Print language.
pr.Conf
Transmission mode
1 1
pr.mode pr-no Transmission not enabled.
2
prpC.hk Transmission of the weight value when the key is pressed.
3 Transmission of the weight to DINI ARGEO 6-digit repeater.
repe.6
4
prPC.ex Extended string transmission when the key is pressed.
5
prpC.st Standard string transmission when the key is pressed.
6 Continuous transmission of the extended string.
all.ext
7 Continuous transmission of the standard string.
all.std
8 Enables printing on DINI ARGEO printer.
tpr
i
For the specifications of transmission modes, strings and protocols see the section “TRANSMISSION PROTOCOLS”.
Setting pr.mode = repe.6 automatically sets the serial port to 4800, N-8-1. It is however possible to set it differently.
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
45
USER_MAN_ENG_DGTQ
Baud rate, parity, data bits, stop bits
2 1 2
baud.pr 9600 4800
3 4
2400 1200
5 6
115200 57600
7 8
38400 19200
3 1
bit.pr n-8-1 No parity, 8 data bits, 1 stop bit.
2
o-8-1 Odd, 8 data bits, 1 stop bit.
3
o-7-2 Odd, 7 data bits, 2 stop bits.
4 Odd, 7 data bits, 1 stop bit.
o-7-1
5
e-8-1 Even, 8 data bits, 1 stop bit.
6 Even, 7 data bits, 2 stop bits.
e-7-2
7 Even, 7 data bits, 1 stop bit.
e-7-1
8 No parity, 7 data bits, 2 stop bits.
n-7-2
9 No parity, 8 data bits, 2 stop bits.
n-8-2
4 1
pWR.PRN pwr.ext
2 Printer turned on at the time of printing.
ext.off
CTS signal
On serial port 232 there is the CTS (Clear to send) signal in pin 16.
Print language
8 1 1 visible only if pr.mode = tpr
pr.Conf lanG ital Italian.
2
espa Spanish.
i
3
fran French.
Using the Dinitools software you can configure
4
deut German. additional printing parameters.
5 English.
enGl
46
USER_MAN_ENG_DGTQ
Reactivation of printing
A
888888 Type
C 1
F.mode funCt
888888 A
TYPE
C 1
Setup ConfiG
3 1
serial PC.sel
1 Transmission mode.
Com.PC PCmode
2 Baud rate.
baud
3 Parity.
parity
4 Data bits.
bit
5 Stop bits.
stop
Transmission mode
1 1 Transmission on demand.
pCmode onde
2 Transmission of the weight on DINI ARGEO 6-digit repeater.
repe.6
3 Standard string transmission when the key is pressed.
Prin.st
4 Extended string transmission when the key is pressed.
prin.ex
5
485 Transmission with 485 protocol (enter the 485 address of the transmitter).
6
modbus Transmission with Modbus protocol (refer to the Modbus protocol manual).
7
all.max Continuous high speed weight transmission for conversion applications (single channel only)
8 Continuous transmission of the standard string.
all.std
9 Continuous transmission of the extended string.
all.ext
10 Stable transmission of the standard string.
stab.st
11 Stable transmission of the extended string.
stab.ex
LEGEND:
Optimized layout for A4 print.
Indicates repeated pressing of Parameter visible only under Parameter or menu subject to
Default value of the parameter.
the key. certain conditions. approval.
47
USER_MAN_ENG_DGTQ
Baud rate, parity, data bits, stop bits
2 1
baud 9600
2
4800
3
2400
4
1200
5
115200
6
57600
7
38400
8
19200
3 1
bit n-8-1 No parity, 8 data bits, 1 stop bit.
2
o-8-1 Odd, 8 data bits, 1 stop bit.
3
o-7-2 Odd, 7 data bits, 2 stop bits.
4 Odd, 7 data bits, 1 stop bit.
o-7-1
5
e-8-1 Even, 8 data bits, 1 stop bit.
6 Even, 7 data bits, 2 stop bits.
e-7-2
7 Even, 7 data bits, 1 stop bit.
e-7-1
8 No parity, 7 data bits, 2 stop bits.
n-7-2
9 No parity, 8 data bits, 2 stop bits.
n-8-2
48
USER_MAN_ENG_DGTQ
Communication protocols
Standard string
[01]ST,GS, 0.0,kg<CR><LF>
Where:
Extended string
[01]1ST,1, 0.0,PT 20.8, 0,kg,01/02/19 11:12:13<CR><LF>
Where:
49
USER_MAN_ENG_DGTQ_V8
Multi-scale string If type = transm
50
USER_MAN_ENG_DGTQ_V8
Serial commands
By selecting the PC port on demand mode (onde), you can communicate with the transmitter via serial commands.
For each command received, the transmitter emits a string containing the response (refer to the command description) or one of the
following signals:
OK<CRLF> Command sent when sending a correct command. This response does not imply that the command is executed.
ERR01<CRLF> Command sent correctly but followed by letters entered unintentionally (e.g. READF, TARES).
ERR02<CRLF> Incorrect command data.
ERR03<CRLF> Command sent not allowed (transmitter busy, or not used in the selected operating mode).
ERR04<CRLF> Command sent non-existent.
i
If the 485 protocol has been selected, you must precede the command with the transmitter address (e.g. 01READ).
Format R E A D Format R E X T
Response Standard string. Response Extended string.
Format G R 1 0 Format T A R E
Response Standard string with weight in resolution x10. Response OK (or ERRxx).
Format T M A N t t t t t t Format Z E R O
Where tttttt tare value Response OK (or ERRxx).
Response OK (or ERRxx).
Format K E Y E D Format K E Y E E
Format I N P U n Format O U T S n
Where n Input (1 ÷ 2). Where n Output (1 ÷ 6).
Response I N P U n v v v v Response O U T S n v v v v
n Input number. n Output number.
Input status: Output status:
Where Where
vvvv 0000 = Not active. vvvv 0000 = Not active.
0001 = Active. 0001 = Active.
FFFF = Input reading error. FFFF = Output reading error.
Optimized layout for A4 print.
51
USER_MAN_ENG_DGTQ_V8
PRESSING A KEY
Format K E Y P x x
xx Key code.
i
To simulate pressing a key, you must send the KEYP and
00 KEYR commands in succession.
01 If more than 1.5 s pass after the KEYP command is sent,
Where the transmitter will execute the function associated with
02
prolonged pressing of the key.
03
04
SCALE INFORMATION
Format R A L L
s s , b , N N N N N N u u , L L L L L L u u ,
Response Y Y T T T T T T u u , S S S , A A A , C C C C
, , R R R R R - I I I I I I
UL = Underload.
OL = Overload.
ss
ST = Stable weight.
US = Unstable weight.
b Number of the active scale.
NNNNNNuu Net weight with unit of measurement.
LLLLLLuu Gross weight with unit of measurement.
YY PT if a manual tare is present or “ ”.
TTTTTTuu Tare with unit of measurement.
Scale status:
000 = scale weighing.
Where SSS
001 = entering a numerical value.
002 = scale in technical menu.
Counter keys pressed:
0001 =
0002 =
AAA
0003 =
0004 =
0170 =
CCCC Code of last key pressed.
RRRRR Last rewrite number saved to Alibi memory.
IIIIII Last ID number saved to Alibi memory.
Optimized layout for A4 print.
52
USER_MAN_ENG_DGTQ_V8
READING OF MICROVOLTS READING OF CONVERTER POINTS
Format M V O L Format R A Z F
Response Standard string. Response Standard string.
Format A L D L Format R E X D
Response ALDLOK / ALDLNO Response Extended string.
Format A L R D X X X X X - Y Y Y Y Y Y
b , L L L L L L L L L L u u ,
Response
Y Y T T T T T T T T T T u u
b Scale number.
LLLLLLLLLLuu Gross weight with unit of measurement.
Where
YY “PT if a manual tare is present or “ ”.
TTTTTTTTTTuu Tare with unit of measurement.
Format P I D
P I D S T , b , L L L L L L L L L L u u , Y Y
Response T T T T T T T T T T u u , X X X X X - Y Y Y Y
Y Y
b Scale number.
LLLLLLLLLLuu Gross weight with unit of measurement.
YY “PT if a manual tare is present or “ ”.
Where
TTTTTTTTTTuu Tare with unit of measurement.
XXXXX Rewrite number.
YYYYYY ID number.
i
The alibi memory commands are executed only if funCt = alibi.
In TRANSM mode, if the commands “ZERO”, “TARE” and “TMAN” are followed by “,X”, the command is executed only on the
indicated scale. For example:
Format T A R E , X Format Z E R O , X
Where Scale: Where Scale:
0 = scale 1 0 = scale 1
X X
1 = scale 2 1 = scale 2
2 = scale 3 2 = scale 3
3 = scale 4 3 = scale 4
The Modbus protocol and the Fieldbus protocols are described in the respective manuals.
Optimized layout for A4 print.
53
USER_MAN_ENG_DGTQ_V8
Diagnostics
888888 A
TYPE
D
diaG
For correct operation, the value of the µV of each channel must be less than 30000 with a weight equal to the maximum capacity.
This value must be stable, and increase if a load is applied to the cell.
4 Display of the A/D points of the converter related to the weight on the scale.
ADC.pnt
Use the and keys to display the different channels (in dep.Ch mode the sum is also visible).
For correct operation, the value of A/D points must be stable, and increase if a load is applied to the cell.
Firmware release
1 Display of firmware release (e.g. 08.04.00).
prG.ver
Serial number
14 Display of transmitter serial number.
ser.num
Display
7 Activation of all display segments and indicators.
displa
Keypad
8 The code of last key pressed is shown on the display:
keyb
8001
8002
8003
8004
80AA
54
USER_MAN_ENG_DGTQ_V8
Serial ports
9 Bridge between serial ports (for manufacturer’s use).
ser
CTS signal
10 Checking the CTS signal of the printer (on) connected to the PRN port.
Cts.st.
Inputs
12 Checking the status of the inputs:
inputs
value 0 indicates that the input is disabled, value 1 indicates that the input is enabled.
Usethe and keys to display the two inputs.
Outputs
11
output Activation of the output shown on the display (rel.1 / rel.2).
Use the and keys to activate the two outputs.
Analog output
13
an.out Analog output test.
Use the , , keys to enter the D/A point value of the analog output.
Press the key to confirm and update the V / mA value of the analog output.
In weighing mode, if the output functions (1 Gross / 2 net) have been set correctly, pressing for 3 seconds will enter the setpoint
programming menu:
visible only if rl.ist = ist.on
Once you have entered the desired values, press . The display shows “store” and returns to weighing mode.
Optimized layout for A4 print.
55
USER_MAN_ENG_DGTQ_V8
Restoring factory settings
888888 A
TYPE
C 1
Setup ConfiG
8
defau
The transmitter is initialized and the default parameters (indicated by the symbol) are activated. Pressing the display shows “dflt?”
confirm further with or exit by pressing another key.
The actual activation of the default parameters is performed by saving the settings (save?) while exiting the menu.
888888 A
TYPE
Visible only with optional clock card
C 1
F.mode funCt
4
CloCk
hour Set the hour and press . The time format is 24h.
i
The date and time format is: DD/MM/YY, HH:MM:SS (24h),
Optimized layout for A4 print.
56
USER_MAN_ENG_DGTQ_V8
Alarms
Alarm Description
preC Displayed if you try to calibrate a point without first confirming the number of calibration points (n tp).
erpnt Calibration error: during the acquisition of a calibration point a NULL value was read from the converter.
Error that occurs if the capacity of channel X is not set, or there is an error in the calibration parameters of
err.x.1
channel X, where X indicates the number of the channel to which the error refers.
Error that occurs if the capacity of channel X is not set, or there is an error in the calibration parameters of
over x
channel X, where X indicates the number of the channel to which the error refers.
Calibration error: a sample weight that is too low was used; it is recommended to use a weight of at least half
er 11
the scale’s capacity.
er 12 Calibration error: The acquired calibration point (tp 1 / tp 2 / tp 3) is equal to the zero point (tp0).
Scale to be calibrated (we recommend resetting the transmitter to the factory default “defau” settings before
er 37
proceeding).
Scale to be calibrated (we recommend resetting the transmitter to the factory default “defau” settings before
er 39
proceeding).
Negative internal points were calculated during calibration:
C.er. -36 • the calibration point is below the zero point;
• The signal is negative (check the connections).
Internal points below the minimum value were calculated during calibration:
C.er. -37 • the calibration point is equal to the zero point;
• too high a capacity has been set with respect to the division.
hw.err Hardware error: software not compatible with the installed hardware.
Displayed when the alibi memory is enabled and the transmitter does not detect the presence of the card
al.err
when the power is turned on. The Conv function is set automatically, but not saved in the setup environment.
busy Printing in progress (printer serial port busy) or transmitter waiting to transmit a print to PC.
un.over You are trying to print with the weight in underload or overload.
------
The weight is overloaded (9 divisions over the maximum capacity).
Gros.er You are trying to print with a non-positive gross weight (less than or equal to zero).
ner.err You are trying to print with a non-positive net weight (less than or equal to zero).
low Net weight less than the minimum weight required for printing.
Conv You are trying to print while the transmitter is converting the unit of measurement.
57
USER_MAN_ENG_DGTQ_V8
Notes
This publication, or any part of it, may not be reproduced without written permission from the Manufacturer. All information in this
manual is based on the data available at the time of its publication; the Manufacturer reserves the right to make changes to its
products at any time, without notice and without incurring any penalty. We therefore recommend that you always check for updates.
The person responsible for the use of the scale must ensure that all safety regulations in force in the country of use are
applied, ensure that the scale is employed in accordance with the intended use and avoid any dangerous situation for the user.
The Manufacturer declines all responsibility for any weighing errors.
Optimized layout for A4 print.
58
USER_MAN_ENG_DGTQ_V8
HEAD OFFICE
Via Della Fisica, 20
www.diniargeo.com
Via Dell’Elettronica, 15
SERVICE ASSISTANCE