Chiller Inductor
Chiller Inductor
Chiller Inductor
Net Cooling
Unit Tag Qty Model No Nominal Voltage Refrigerant Type
Capacity (ton.R)
CH-1 1 YLAA0041HE46XCBSXTX 38.88 460-3-60.0 R410A
PIN:
YLAA0041HE 46XCBSXTXA SXBLXCXX44 SE1XXXHXXX YAXGPXX7XX XXX1XXEXXX
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90
Electrical Data
Circuit 1 2 3 4
Compressor RLA 18 / 18 18 / 18
Fan QTY/FLA (each) 2/4 2/4
High LRA Current 125 / 125 125 / 125
Single Point
Min. Circuit Ampacity 96
Recommended Fuse/CB Rating 110
Max. Inverse Time CB Rating 110
Max. Dual Element Fuse Size (A) 110 Operating Condition Electrical Data
Unit Short Circuit Withstand (STD) 5 [kA] Compressor kW 34.04
Wires Per Phase 1 Total Fan kW 6.720
Wire Range (Lug Size) #6 AWG - 500 kcmil Total kW 40.76
Starter Type Across The Line
Notes:
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program,
which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units
may be found in the AHRI Directory at www.ahridirectory.org.
Unit contains freeze protection fluids in the evaporator with a leaving chilled fluid temperature
above 32 DEG F [0 DEG C] and is certified when rated per the Standard with water. Auxiliary
components included in total KW - Oil heaters, Chiller controls. Auxiliary power is already included
in the compressor and fan power
ASHRAE Standard 90.1-2010 and ASHRAE Standard 90.1-2013 & 2016 Compliant.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4).