255TAIYO EXU 61A V1.0.0.0 Appendix V1.0 EN
255TAIYO EXU 61A V1.0.0.0 Appendix V1.0 EN
255TAIYO EXU 61A V1.0.0.0 Appendix V1.0 EN
Appendix V1.0
AVR I
TAIYO EXU-61A
Extra wire !
See page 4.
Product information
- Measurements : in mm. (LxWxH = 285 x 206 x 115 mm)
- Weight : +/- 3.8Kg.
- Mounting : 1:1 ORIGINAL TAIYO EXU-61A.
- Wiring diagram : See page 4.
Mounting
Mounting of the product should be done in such a way that:
- the absolute maximum ambient temperature rating of the product will never be exceeded.
- maximum cooling (direction of cooling ribs and direction of airflow) is achieved.
- Mounting no humid air can flow through the product or condensation occurs.
- dust or other materials or residue will not remain in or on the product.
- the maximum vibration is not exceeded.
- personal contact with persons is impossible.
Wiring
- Diameter size of the wiring should be enough to carry the expected current. Wire insulation should be enough to withstand
the expected operating voltages and temperatures.
- To improve EMC emission and immunity, care should be taken for the lay out of the wiring. This in respect to all wiring in the
installation.
- Keep current carrying wires as short as possible.
- Keep wires carrying a total sum of zero Ampere close to each other, or in one single cable, E.g. R, S, T or k and l or
6 and 7.
- Avoid current carrying conductors next to sensing or control wiring. Especially current controlled by SCR’s or PWM controlled
transistors.
- If sensitive sensing signal cables need to be laid across distance along other cabling, shielded cable is preferred. Keep the
shield as long as possible and the wiring outside the shield as short as possible. Do not solder or shrink the shield to a
regular wire. Connect the original shield to ground at one side with an as large as possible contact surface.
TURKEY, Izmir UNITED ARAB EMIRATES, Sharjah UNITED KINGDOM, Stockton on Tees
INTEGRAL KDU Technical Services MJR Controls
Tel: +90 (555) 211 55 75 Tel: +971-6-5575480 Tel: +44 1642 762 151
Email: ozgur@integralguc.com Fax: +971-6-5575490 Fax: +44 1642 762 502
Website: www.kdutech.ae Website: www.mjrcontrols.com
E-mail: kdutech@kdutech.ae Email: chris.milner@mjrcontrols.com