11 KV HT VCB
11 KV HT VCB
11 KV HT VCB
PROJECT
CONSTRUCTION OF MANIPUR STATE GUEST HOUSE
(3rd BHAWAN) AT DWARKA, SECTOR - 19, NEW DELHI
& SITE DEVELOPMENT INCULDING ALL SERVICES &
DEVELOPMENT WORKS
Architect
M/s Collage Design Pvt. Ltd.
300, Sai Sampanna, Station Road, Vikhroli
East, Mumbai-400083
Electrical Consultant
PARAM CONSULTING ENGINEERS PVT LTD
WZ-A2B, 3rd floor, Sainik Nagar, Near Nawada Metro station Pillar no. 732,
UTTAM NAGAR, NEW DELHI-110059
Office: 8929265353, Mob. 9911925820
Email: sssarbata@gmail.com, contact.pece@gmail.com
Technical specification
VACUUM CIRCUIT BREAKERS (11 KV)
1. GENERAL:
2. SYSTEM PARAMETERS:
The Vacuum Circuit Breakers shall be suitable for the following parameters:
Breaker shall be fully tested as per codes/ standards a test certificate from CPPI
shall be furnished. Also, pressure test certificate as per PEHLA recommendations
shall be furnished.
1
Bus bars shall be air insulated & mounted on cast epoxy insulated to withstand
short current of 44 KA for 3 Sees.
CT & cable compartment shall be preferably located on rear side. CTS shall be epoxy
insulated. Provision for terminating 2Nos. 3 core cable shall be provided. The cable
entry shall be from the bottom of the panel.
3. TECHNICAL FEATURES:
c. VCB shall be totally restrike free. Auto-reclosing shall be posing any problem.
The dielectric strength shall be recovered fast enough to perform multiple
open-close-open-operation.
d. VCB shall have negligible contact erosion even after 20,000 operations at
rated current.
5. ACCESSORIES
a. Auxiliary Switch
b. Closing Solenoid
c. Tripping Solenoid
d. Mech. Operation Counter
e. Shunt release
f. Motorised spring charging mechanise
g. Earthing switch
h. Space heaters
i. ON/OFF/TEST/ISOLATED Indicators & name plate.
j. Earth bus (copper) with earthing bolts for all SF- 6/VCB jointed together by bus
links/bolts.
6. INSTRUMENT TRANSFORMERS:
2
c. Terminal strip for all CTS/ PTS & control wiring with 1.5sq.mm. Copper
wiring cables.
7. SAFETY INTERLOCKS:
8. METERING
a. One 0-15 KV 96 sq. mm square voltmeter with selector switch & fuse.
b. One no. Ammeter with selector switch.
c. One Trivector meter for 3 Phase, 3wire unbalanced loads with ½ max.
demand indicator.
d. One KWH meter.
e. Indicating Lamps:
i. VCB ‘closed’ lamp (1 No.)
ii. VCB ‘open’ lamp (1 No.)
iii. VCB ‘Auto trip’ lamp (1 No.)
iv. VCB ‘Heating trip’ lamp (1 No.)
v. VCB ‘spring charged’ lamp (1 No.)
vi. Non-trip alarm (1 No.)
3
LIST OF MAKE AND MATERIALS
A) H.T. SWITCHGEAR
D) INSTRUMENT TRANSFORMERS
E) OTHER
In case any of makes for any of the materials is missed out in the above list, then the
contractor shall inform the consultants about the same obtain the approval. Therefore, he
can proceed with the supply of the equipment’s.
S.
N Contact
Vendor Address Contact. No. Email id
Person
1 Risha 17, 1st floor, kanishka building, DDA, Himanshu 9810035647 sales@risha.i
control LSC, Behra Enclave, Paschim Vihar, Mehta n
Engineers new Delhi - 110087
2 L.S. power Office: L.S P+OWER CONTROL Plot NAVEEN 0124 - naveenlspcpl0
Control No. - 349A, 2576244 1@gmail.com
G - Block, Sushant Lok - II, : 0124 -
Sec-57, Gurgaon-122002 4251419
3 Ambit Ambit Switchgear Pvt Ltd, Anand 9873145711 singhal@ambi
Switchgear C 50, Phase II, Singhal t.in
Pvt Ltd Noida 201305 UP.
4 Adlec power Novateur Electrical & Digital Pinky 9899985314 pinky.singh@a
Systems Pvt. Ltd. Singh dlecpower.co
Corp. Office: - C-34/4, 2nd floor, m
Lawrence Road Industrial Area, New
Delhi - 110035.
Works: - Delhi-Rohtak-Road, Decora
Station Road, Behind IUP Jindal,
Rohad, Jhajjar, Haryana-124501
I/We hereby declare that I/We have read and understood the above instructions
which have been issued as conditions of the contract.
In case any of makes for any of the materials is missed out in the above list, then the
contractor shall inform the consultants about the same obtain the approval. Therefore, he
can proceed with the supply of the equipment’s.
1
PARAM CONSULTING ENGINEERS PRIVATE LIMITED