N100
Series name
004
Applicable motor rating (0.4kW to 3.7kW)
Input power supply specification L: three-phase 200-V class H: three-phase 400-V class S: single-phase 200-V class Configuration type (operator panel equipped)
Contents
04 Features / 05 Operation / 07 General Specifications / 09 Function List 16 Terminal Functions / 17 Standard Connection Diagram 18 Application Wiring Apparatus & Options / 26 Proper Operation
Features
driving no effect of changing load. Show high torque of 200% or greater at speeds as low as 0.5Hz during starting and operation.
Torque 20 200%
15
150%
10
100%
possible flexible application for various FA system, on remote driving at upper system and easy monitoring the status of driving. Realize remote motor control drive using exclusive MMI program.
Global products
Observe EN standard by attaching
Operation
120 130
130
120 130
105 115
135
105 115
155
105 150
120 130
155
Dimension Table
Type Singlephase 200 V class 004SF 115 X 130 X 135 007SF 015SF 004LF 115 X 130 X 135 3-phase 200 V class 007LF 015LF 115 X 130 X 135 022LF 037LF 150 X 130 X 155 140 X 120, M4 2.0kg0.1kg 037HF 105 X 120, M4 1.5kg0.1kg 105 X 120, M4 1.2kg0.1kg 115 X 130 X 135 140 X 120, M4 1.5kg0.1kg 3-phase 400 V class 007HF 115 X 130 X 135 015HF 022HF 150 X 130 X 155 140 X 120, M4 2.0kg0.1kg 105 X 120, M4 1.5kg0.1kg 105 X 120, M4 1.2kg0.1kg External Dimension Installation Dimension (mm)(W XHXD) (mm)(WXH, ) Weight (kg) Type External Dimension Installation Dimension (mm)(WXH XD) (mm)(WXH, ) 115 X 130 X 135 105 X 120, M4 Weight (kg)
004HF
130
1.2kg0.1kg
HYUNDAI INVERTER
04 05
130
Operation
Operation
Monitor section (LED) Power ON lamp Monitor lamp Monitor lamp Frequency setting potentiometer
General Specifications
Item N100 Applicable motor capacity (kW) Rated output capacity (kVA) Output Rated output current (A) Rated output voltage (V) Maximum output frequency (Hz) Power Phase, Voltage, Frequency supply Power Conditions Environment Protection Cooling method Control system Torque control Output frequency range Frequency setting resolution Frequency precision Analog Digital Analog Digital Self cooling Forced cooling Single-phase, 220~230 VAC, 50/60 Hz 004SF 007SF 0.4 1.2 3.0 0.75 2.1 5.0
200 V class 015SF 004LF 007LF 1.5 2.9 7.0 0.4 1.2 3.0 0.75 2.1 5.0
400 V class 015LF 022LF 037LF 004HF 007HF 015HF 022HF 037HF 1.5 2.9 7.0 2.2 4.6 11.0 3.7 7.1 17.0 0.4 1.5 1.8 0.75 2.8 3.4 1.5 4.0 4.8 2.2 6.0 7.2 3.7 7.6 9.2
3-phase, 380~480 V
Voltage: 10% / frequency: 5% IP20 Self cooling Forced cooling Self cooling Forced cooling
Space vector PWM control V/F control, sensorless vector control 0.01~400 Hz Max. setting frequency500 (DC 5 V input) Max. setting frequency1000 (DC10 V, 4~20 mA input) 0.01 Hz (100 Hz and less ), 0.1 Hz (100 Hz or more ) Within 0.1% of maximum output frequency Within 0.01% of maximum output frequency Any base frequency setting possible between 0 Hz and 400 Hz, constant torque or variable torque pattern selectable 150% of rated current for 60 sec More than 200% (at 0.5 Hz) Manual torque boost can be set between 0~50% 0.1~3000 sec setting possible linear, S-curve, U-curve selection possible 150% (5 sec) Operating frequency (0~10 Hz), operating time (1~10 sec), operating braking force (0~50%) variable External DC braking setting possible Operation current level setting possible (20~200% variable), enable/disable selection
Voltage/frequency characteristic Control Overload rating charac- Starting torque teristic Torque boost Acceleration/deceleration time setting Acceleration/deceleration pattern Dynamic Braking torque DC braking Current stall prevention operation level Voltage stall prevention operation level
HYUNDAI INVERTER
06 07
General Specifications
200 V class
400 V class
004SF 007SF 015SF 004L 007LF 015LF 022LF 037LF 004HF 007HF 015HF 022HF 037HF 0 to 5VDC, 0 to 10VDC, 4 to 20 mA, External variable resistor (1 k ~2 k ,1 W), main unit volume resistor Input from control panel Individual selection of forward or reverse run Used to reset fault output provided when protective function is activated Maximum 16 speeds (each speed can be set between 0 and 400 Hz), speed can be changed during operation Acceleration/deceleration time, base frequency, maximum frequency, multistage frequency, torque boost, electronic thermal, control method, motor parameter Instant shut-off of inverter output (frequency/voltage) Input selection of frequency setting current signal Self-protection selection of start signal Contact input for when stopping the inverter with external terminal Thermal contact input for when stopping inverter with externally mounted thermal relay Control panel or external operation transition selection programmable. V/F control or sensorless vector control method selection programmable. Multispeed operation, operation mode selection, DC braking, upper/lower frequency setting, frequency jump operation, PID control, AVR, 2-stage accel./decel., instantaneous power failure
Starting signal Abnormality reset Multispeed selection Input signal Control characteristic 2nd function selection Output stop Current input selection Self-protection function at starting External TRIP contact input External thermal input Operation mode selection Voltage/frequency characteristic
Operation functions
restart operation, electronic thermal, software lock, carrier frequency adjustment, auto tuning function, RS485 link operation, starting frequency adjustment, jogging operation, retry function, automatic torque boost function, usp function, second control function.
Output signals
Inverter running, frequency reached, frequency detection, overload warning fault Output frequency, output current, output voltage Output frequency, output current, output voltage, operation direction, PID feedback, terminal input, terminal output, transition frequency monitor, power consumption, operating time accumulation Fault list, fault history Power on (POWER), operational state (RUN), PRG, frequency (Hz), output current (A), RUN terminal, MIN/MAX volume terminal Overcurrent shut-off, regenerative overvoltage shut-off, undervoltage, output short circuit,
temperature abnormality, overload shut-off (electronic thermal), ground fault protection, external trip, communication error, USP error, EEPROM error
Ambient temperature Environment Ambient humidity Storage temperature Installation area Altitude and vibration Operator Misc. International directive compliance
-10~40C (no freezing) 90% RH or less (non-condensing) -20~60C Indoors without corrosive gases, flammable gases, oil mist or dust Maximum 1,000 m or less above sea level, 5.9 m/s2 or less Standard operator built-in control panel, optional remote operator CE, UL/cUL directive compliance
Function List
10.0
0.1
3000
sec
Deceleration time 1 setting Rotation direction setting Basic setting functions Fine tuning functions Terminal setting functions Second motor setting functions Sensorless vector setting functions
10.0 0 -
0.1 0 -
3000 1 -
sec -
HYUNDAI INVERTER
08 09
Function List
Unit -
Code description
0: main unit volume, 1: control terminal, 2: standard operator, 3: remote operator (communication) 0: standard operator, 1: control terminal, 2: remote operator (communication) 0~maximum frequency (A04) A03~400 Hz 0.0~400 Hz (by 0.01 Hz), start frequency at 0 V, 4 mA input 0.0~400 Hz (by 0.01 Hz) end frequency at 10 V, 20 mA input Start rate for the analog input End rate for the analog input 0: start at start frequency 1: start at 0 Hz 1~8 times, analog input filter sampling count 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.5~10.00 Hz (by 0.01 Hz) 0: free-run, 1: deceleration stop, 2: DC braking
0 60.00 60.00 0.00 0.00 0.0 100.0 0 4 5.00 10.00 15.00 20.00 30.00 40.00 50.00 60.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50 0
0 0.00 A03 0.00 0.00 0.0 0.0 0 1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50 0
2 A04 400.0 A04 A04 100.0 100.0 1 8 A04 A04 A04 A04 A04 A04 A04 A04 A04 A04 A04 A04 A04 A04 A04 10.00 2
Hz Hz Hz Hz % % Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz -
Function code A28 V/F characteristic A29 A30 A31 A32 A33 DC braking A34 A35 A36 A37 A38 Upper/ lower limit jump frequency A39 A40 A41 A42 A43 A44 A45 A46 A47 PID control A48 A49 A50 A51 Automatic Voltage Regulation (AVR) A52 A53 A54 A55 Acceleration /deceleration setting A57 A58 A59 A60 A61 Input signal adjustment A62 A63 A64 A65 A56
Name Torque boost mode selection Manual torque boost voltage setting Manual torque boost frequency setting V/F characteristic curve selection Output voltage gain setting DC braking function selection DC braking frequency setting DC braking output delay time setting DC braking force setting DC braking time setting Frequency upper limit setting Frequency lower limit setting Jump frequency setting 1 Jump frequency band-width setting 1 Jump frequency setting 2 Jump frequency band-width setting 2 Jump frequency setting 3 Jump frequency band-width setting 3 PID function selection PID P gain setting PID I gain setting PID D gain setting PID scale rate setting PID feedback input method setting AVR function selection Motor input voltage setting 2-stage acceleration time setting 2-stage deceleration time setting 2-stage accel./decel. switching method setting Acceleration transition frequency setting Deceleration transition frequency setting Acceleration pattern setting Deceleration pattern setting Voltage signal offset setting Voltage signal gain setting Current signal offset setting Current signal gain setting External voltage input selection
Initial value Minimum value Maximum value 0 5.0 10.0 0 100.0 0 0.50 0.0 10.0 0.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 10.0 10.0 0.0 100.0 0 0 220 380 10.0 10.0 0 0.00 0.00 0 0 0.0 100.0 0.0 100.0 0 0 0.0 0.0 0 20.0 0 0.00 0.0 0.0 0.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0 0.1 0.0 0.0 0.1 0 0 200 380 0.1 0.1 0 0.00 0.00 0 0 -10.0 0.0 -10.0 0.0 0 1 50.0 100.0 2 100.0 1 10.00 5.0 50.0 10.0 400.0 400.0 400.0 10.00 400.0 10.00 400.0 10.00 1 100.0 100.0 100.0 1000 1 2 240 480 3000 3000 1 400.0 400.0 2 2 10.0 200.0 10.0 200.0 1
Code description 0: manual torque boost, 1: automatic torque boost Manual torque boost voltage setting Manual torque boost frequency setting 0: constant torque, 1: reduced torque (1.7), 2: sensorless vector control 20~100% 0: disable, 1: enable 0.50~10.00 Hz (by 0.01 Hz) 0.0~5.0 sec (by 0.1 sec), free run time 0~50%, by 1% 0.0~10.0 sec (by 0.1 sec) A39~A04 (by 0.01 Hz) 0.00~A38 (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~10.00 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~10.00 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0.00~10.00 Hz (by 0.01 Hz) 0: PID control off, 1: PID control on 0.1~100.0% (by 0.1 sec) 0.0~100 sec (by 0.1 sec) 0.0~100 sec (by 0.1 sec) 0.1~1000.0 (by 0.1 sec) 0: current input, 1: voltage input 0: constant on, 1: constant off, 2: off during deceleration 200/220/230/240 (200-V class) 380/400/415/440/460/480 (400-V class) 0.1~999.9 sec (by 0.1 sec) 1000~3000 sec (by 1 sec) 0.1~999.9 sec (by 0.1 sec) 1000~3000 sec (by 1 sec) 0: terminal (2CH), 1: transition frequency (A57, A58) 0.00~400.0 Hz (by 0.01 Hz) 0.00~400.0 Hz (by 0.01 Hz) 0: linear, 1: S-curve, 2: U-curve 0: linear, 1: S-curve, 2: U-curve Voltage offset Voltage gain Current offset Current gain 0: 5 V input, 1: 10 V input
HYUNDAI INVERTER
10 11
Function List
b01
b02
Allowable instantaneous power failure time setting Reclosing stand by after instantaneous power failure recovered Electronic thermal level setting Electronic thermal characteristic selection Overload restriction mode selection
1.0
0.3
1.0
sec
b03
1.0
0.3
3.0
sec
0.3~3.0 sec (by 0.1 sec) 0.2X (inverter rated current)~1.2X (inverter rated current) 0: SUB (reduced torque characteristic) 1: CRT (constant torque characteristic) 0: overload, overvoltage restriction mode OFF 1: overload restriction mode ON 2: overvoltage restriction mode ON 3: overload, overvoltage restriction mode ON 0.2X (inverter rated current)~2.0X (inverter rated current) Deceleration rate when inverter restricts overload 0.1~10.0 sec (by 0.1 sec) 0: All parameters are locked when SFT from terminal is on. 1: All parameters except frequency setting are locked when SFT from terminal is on. 2: All parameters are locked 3: All parameters except frequency setting are locked. 0.50~10.00 Hz (by 0.01 Hz) 0.5~16 Hz (by 0.1 kHz) 0: Trip history initialization 1: Data initialization 0: Korea version 1: Europe version 2: US version 0.01~99.99 (by 0.01) 0: stop enabled 1: stop disabled Operation setting when the free-run stop is cancelled 0: 0 Hz restart 1: frequency matching restart 2: free run stop Communication number setting is 1 to 32
Electronic thermal
b04 b05
100.0 1
20.0 0
120.0 1
% -
125.0
20.0
200.0
b08
1.0
0.1
10.0
sec
Start frequency adjustment Carrier frequency adjustment Initialization mode selection Initial value selection (country code) Frequency conversion value setting Stop key validity selection during terminal operation Restarting after free-run stop signal selection Communication number
0.50 5.0 0
0.50 0.5 0
10.00 16.0 1
Hz kHz -
0 1.00 0
0 0.01 0
2 99.99 1
b16
b17
32
Others
C21
0.00
0.00
400.0
Hz
C22 C23
0.00 10.0
0.00 0.0
400.0 100.0
Hz %
HYUNDAI INVERTER
12 13
Function List
2/4/6/8 motor rated current setting range: 0.001~30.00 setting range: 0.001~20.00 setting range: 0.1~999.9 mH setting range: 0.01~100.0 mH setting range: 0.1~100.0 A setting range: 0.001~30.00 setting range: 0.001~20.00 setting range: 0.1~999.9 mH setting range: 0.01~100.0 mH setting range: 0.1~100.0 A
Protective Functions
Various functions are provided for the protection of the inverter and motor, they also perform the protection function when the inverter breaks down.
Function Overcurrent protection Overload protection (electronic thermal) regenerative Overvoltage protection Communication error Undervoltage protection Output short-circuit USP error EEPROM error External trip Temperature trip
Description When the inverter output current exceeds the rated current by more than approximately 200% while the motor is locked or reduced in speed,the protection circuit activates, halting inverter output. When the inverter output current causes the motor to overload, the electronic thermal trip in the inverter cuts off the inverter output. If regenerative energy from the motor or the main power supply voltage is high , the protective circuit activates to cut off the inverter output when the voltage of DC link exceeds the specification. The inverter output is cut off when communication to the inverter has an error due to external noise, excessive temperature rise, or other factors. When the input voltage to the inverter decreases, the control circuit does not function normally. When the input voltage is below the specification, the inverter output is cut off. The inverter output is short-circuited. This condition causes excessive current for the inverter, so the inverter output is turned off. The USP error is indicated when the power is turned on with the inverter in RUN state. (Enabled when the USP function is selected.) The inverter output is cut off when the EEPROM in the inverter has an error due to external noise, excessive temperature rise, or other factors. When the external equipment or unit has an error, the inverter receives the corresponding signal and cuts off the output. When the temperature in the main circuit increases due to cooling fan failure, the inverter output is cut off (only for the model with a cooling fan).
E05
Over.L
HYUNDAI INVERTER
14 15
Terminal Functions
Function
Power Supply
Motor
Terminal function 24VDC10%, 35 mA Contact input: Closed: on (operating) Open: off (stop)
Forward run command (FW), reverse run command (RV), Multi-speed commands 1~4 (CF1~4), 2-stage accel./decel. command (2CH), Reset (RS), free run stop (FRS), external trip (EXT), Second control function setting (SET), terminal software lock (SFT), Unattended start protection (USP), Current input selection (AT), jog operation (JG) Common terminals for input or monitor signal Output frequency meter, output current meter, output voltage meter Power supply for frequency setting Voltage frequency command signal Current frequency command signal Common terminal for frequency command
Monitor signal
FM H
Analog frequency meter 0~5VDC 0~5VDC (standard), 0~10VDC, input impedance 10 k 4~20 mA, input impedance 250
Output signal
12
Intelligent output terminal; Run status signal (RUN),frequency arrival signal (FA1), set frequency arrival signal (FA2), overload advance notice signal (OL), PID error deviation signal (OD), and alarm signal (AL) Common terminal for output signals Alarm output signals: At normal status,power off (initial setting value): AL0-AL2 (closed) At abnormal status : AL0-AL1 (closed)
Maximum 27 VDC, 50 mA
Contact rating: AC 250 V 2.5 A (resistor load) 0.2 A (induction load) DC 30 V 3.0 A (resistor load) 0.7 A (induction load)
1) Please change terminal No.5 to No.13 AT (current input selection) in case of 4~20mA input.
Inverter
MCCB Main Power Supply P24 6 5 4 3 2 1 FM CM1 H Frequency setting device 1kohm, 1 W 1) Current input 4~20 mA O O1 L P5 V AL0 AL1 AL2 12 CM2
RY1 RY2
MC R S T P24 U V W Motor
P RB
2) Braking Resistor
1) In case of changing terminal No.5 to No.13 AT (current input selection) on : 4~20mA selection off : Volume selection 2) Please refer to page 24.
DC 25 V
Sink type
Source type
P24
3
JB 3
1
2 1
JB 3
1
DC24V + CM1
JA
2
S CM1 Inverter
Sink type
DC24V S + P24
3 2
Source type
DC24V + DC24V + CM1
JB 3
1
DC24V + CM1
COM
P24
3
JA
2 1 2
JB 3
1
JA
2
S CM1 Inverter
HYUNDAI INVERTER
16 17
Inverter model (N100 Series) N100-004SF N100-004LF N100-007SF N100-007LF N100-015SF N100-015LF N100-022LF N100-037LF N100-004HF N100-007HF N100-015HF N100-022HF N100-037HF
Wiring Power lines 1.25 mm2 1.25 mm2 2.0 mm2 2.0 mm2 3.5 mm2 1.25 mm2 1.25 mm2 2.0 mm2 0.14~0.75 mm2 shielded cable Signal lines
Applicable equipment Fuse (class H) 5A 10A 15A 20A 30A 5A 10A 15A
0.75
Electromagnetic contactor (MC)
Noise Filter
- Field wiring connection must be made in accordance with a UL-listed and CSA-certified closed-loop terminal connector sized for the wire gauge required. Connector must be fixed using the crimping tool specified by the connector manufacturer. - Properly select the capacity of the circuit breaker to be used. - Check power wire size if cable length exceeds 20 m. - Use 0.75 mm2 wire for the alarm signal wire.
R
L1
S
L2
T
L3
Inverter
RB
T1 T2 T3
Noise Filter
EMI filter
Motor
Remote Operator
With the remote operator, you can control the parameters of the inverter and the commands by using the optional remote
operator cable.
The NOP100 enables parameter sets to be read out of the inverter or to be written into the inverter with READ or COPY
button.
Specification
Item Model name External dimension LCD Display LED Keypad Communication method Function Connection cable length NOP100 135 mm (H) X 75 mm (W) X 19 mm (D) 2 Line X 16 Character Forward operation, reverse operation, stop, mode changing display 12 Key RS485 (Modular connection) Fault list storage count: 3 count Built-in READ/COPY function 1.5 m, 3 m Remote Operator (NOP100)
Description
Key configuration
Connection diagram
( REMT ) Remote On : NOP Run/Stop Remote Off : Inverter Run/Stop ( READ ) Transmit parameter to NOP ( MON ) Enter monitor group ( Shift key ) Shift decimal point in parameter editing ( UP key ) Increase Data in parameter editing ( FWD ) ( REV ) Forward run command Reverse run command ( COPY ) Transmit parameter to inverter ( STR ) Store parameter ( FUNC ) Change editing mode and monitor mode ( DOWN key ) Decrease Data in parameter editing ( STOP ) Stop command
HYUNDAI INVERTER
18 19
Digital Operator
Digital operator is economical remote operator. Digital operator can control inverter parameter and operating commands. Digital operator has a 4-digit 7-segment LED, so it is possible not only operate inverter but also display inverter status.
Specification
Item Model name External dimension Display Keypad Communication method Function Connection cable length 7-segment LED Monitor lamp DOP1 67.5 mm (H) X 64.9 mm (W) X 35.1 mm (D) 4-digit 7-segment LED 7 (POWER / RUN / PRG / Hz / A / RUN key / Volume LED) 7 (RUN / STOP (RESET) / FUNC / UP / DOWN / STR / Volume) RS485 (Modular connection) Inverter operation & monitoring 1.5 m, 3 m
Digital Operator (DOP1)
Description
Key configuration
Connection diagram
( RUN LED ) On when the inverter is run status ( Display part[LED display] ) Display frequency, motor current, motor rotation speed, alarm history, and setting value. ( Power LED ) On when the inverter power is inputted. ( STOP/RESET key ) This key is use for stopping the motor or resetting errors.
RUN
( PRG LED ) This LED is on when the inverter is ready for parameter editing.
PRG POWER
Hz
( Hz/A LED ) Display units Hertz/Ampere LEDs. ( Potentiometer ) Set the inverter output frequency.(Be operated only when the lamp is ON)
RUN
STOP RESET
MIN.
MAX.
FUNC
STR
( FUNCTION key ) This key is used for changing parameter and command.
( UP/DOWN key ) This key is used to change data and increase of decrease the frequency.
( RUN key ) Press this key to run the motor. The run enable LED must be terminal operation.
( STORE key ) Press the store key to write the data and setting value to the memory.
(30.1)
75
11.25
52.5
11.25
55.6
135
POWER
RUN
PRG
Hz
17.4
RUN
STOP RESET
FUNC
STR
24
17
25.4
14
23.5
35.1
5.9
64.9
8.5
15
11.6
46.5
HYUNDAI INVERTER
20 21
System constitution
RS232/485 Converter
Screen Constitution
Operation function Display function
Display inverter running status - Frequency / Current / Voltage / Inverter RUN/STOP command Setting motor frequency Setting inverter parameter Rotate direction Display inverter status - RUN / STOP / TRIP Display inverter parameter - All of the inverter parameter
Simulation function
Memory variable running pattern - Useful several motor control - Treadmill/Washing machine/Crane - Display inverter running status according to PID control gain.
Reduce the conductive noise on the main power line generated from the inverter.
position Noise filter is the more near to noise source, Mountingthe better. the effect is
and constitution
Noise Filter Power Supply MCCB Line L1 L2 L3 PE Load L1' L2' L3' PE'
As Short as possible R S T
Inverter U V W
Motor
L2'
L3 C3 R3 PE C4 C4
L3' C7 PE'
HYUNDAI INVERTER
22 23
Specification table
Name Type name RB0 External resistance unit RB2 600 W 35 5% Maximum 10 sec. Instance : 3.8 kW Rating : 600 kW RB1 300 W 50 5% Maximum 10 sec. Rating capacity 200 W Resistance 180 5% Rating continuous ON time Maximum 10 sec. Consuming power Instance : 0.7 kW Rating : 200 kW Instance : 2.6 kW Rating : 300 kW Protect overheat Built-in temperature relay in resistance. At disorder high temperature, open(b contact) signal occurred. Rating contact AC 240 V 3 A (R load) 0.2 A (L load) DC 36 V 2 A (R load) Figure 1
2301 2201
3902
4.50.5
600.5
1281
52 2002 50010
200.5
3732 2702
641 60.2
301
2.4t
651
Connection diagram
Input-Reactor Ro L1 L2 L3 L1' L2' L3' Inverter R S T U V W Inverter R U V W Power Supply Output-Reactor Motor U V W L1 L2 L3 L1' L2' L3' X Y Z M M [Input-side AC reactor]
6-M(K)
[figure 2]
(Ro) (R) (So) (S) U X V Y (To) (T) W Z
Motor
Power Supply So To
Hmax.
200
Hmax.
Y Cmax.
[Output-side AC reactor]
S T
Y Cmax.
ACL-L I-2.5
L : 3- 200 V H : 3- 400 V Input-side Inverter output capacity (kVA) Depress harmonic Cooperation power Improve power factor
ACL-L-2.5
L : 3- 200 V H : 3- 400 V Inverter output capacity (kW)
Voltage
T 52 67 70 72 75
J 6 6 6 6 6
Voltage
Type ACL-L-0.4 ACL-L-0.75 ACL-L-1.5 ACL-L-2.2 ACL-L-3.7 ACL-H-0.4 ACL-H-0.75 ACL-H-1.5 ACL-H-2.2 ACL-H-3.7
200 V class
400 V class
A 110 130 160 180 220 110 130 150 180 180
T 65 80 75 90 90 65 80 75 90 90
J 6 6 6 6 6 6 6 6 6 6
HYUNDAI INVERTER
24 25
Proper Operation
Before use, be sure to read through the Instruction Manual to insure proper operation. Note that the inverter requires proper electrical wiring; a specialist should carry out the wiring. The inverter in this catalog is designed for general industrial applications. For special applications in fields such as aircraft, outer space, nuclear power, electrical power, transport vehicles, clinics, and submarine relay equipment, please consult us in advance. For application in a facility where human safety is at stake or serious losses may occur, be sure to program all safety devices to avoid serious accidents. The inverter is used for three-phase AC motor.
Vibration
Submersible motor
Explosion-proof motor
High-frequency run
Thermal relay
Wiring distance
Because a smoothing capacitor deteriorates as it undergoes internal chemical reaction, it should normally be replaced every five years. Be aware, however, that its life expectancy is considerably shorter when the inverter is subjected to such adverse factors such as high temperature, or heavy load exceeding the rated current of the inverter. Also, consumable parts such as cooling fans should be replaced according to the inverter periodic inspection of the maintenance guide (maintenance inspection and parts replacement must be performed by only specified trained personnel).
50 40 30 2.5 5 10
Capacitor lifetime (years)
HYUNDAI INVERTER
26 27
www.hyundai-elec.com
Head Office Seoul (Sales & Marketing) Orlando New Jersey London Tokyo Osaka Dubai Sofia Yangzhong
1, Jeonha-dong, Dong-gu, Ulsan, Korea Tel: 82-52-202-8101~8 Fax: 82-52-202-8100 140-2, Gye-dong, Jongno-gu, Seoul, Korea Tel: 82-2-746-7596, 8451 Fax: 82-2-746-8448 3452 Lake Lynda Drive, Suite 170, Orlando, Florida 32817, U.S.A. Tel: 1-407-249-7350 Fax: 1-407-275-4940 300 Sylvan Avenue, Englewood Cliffs, NJ, 07632, U.S.A. Tel: 1-201-816-0286 Fax: 1-201-816-4083 2nd Floor, The Triangle, 5-17 Hammersmith Grove, London, W6 0LG, UK Tel: 44-20-8741-0501 Fax: 44-20-8741-5620 8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo, 100-0006, Japan Tel: 81-3-3212-2076, 3215-7159 Fax: 81-3-3211-2093 I-Room 5th Fl. Nagahori-Plaza Bldg. 2-4-8, Minami Senba, Chuo-Ku, Osaka, 542-0081, Japan Tel: 81-6-6261-5766, 5767 Fax: 81-6-6261-5818 Level 2, Unit 205, Emaar Square-Bldg.4, Sheikh Zayed Road, P.O.Box 252458, Dubai, U.A.E. Tel: 971-4-425-7995 Fax: 971-4-425-7996 1271, Sofia 41, Rojen Blvd., Bulgaria Tel: 359-2-803-3200, 3220 Fax: 359-2-803-3203