Distribution System Design For Smart City
Distribution System Design For Smart City
Distribution System Design For Smart City
Department of electrical
Power &Machine
Distribution System
Design For Smart City
Prepared By,
Acknowledgment
We would like to express our gratitude for everyone
who helped us during the graduation project starting
with endless thanks for our supervisor Prof Dr. A.A
Salam, Dr. Azza ELdesouky Salam who didn’t keep any
effort in encouraging us to do a great job, Eng. Mai El-
adany monitoring and providing our group with valuable
information and advices to be better each time. Thanks
for the continuous support and kind communication
which had a great effect regarding to feel interesting
about what we are working on. Thanks are extended to
our project leader for beneficial lectures and his effort to
help members team.
Chapter (1)
Introduction
1.1Introduction---------------------------------------------------2
1.2 The scope of the project------------------------------------------2
1.3 objectives of the project----------------------------------------------3
Chapter (2)
Primary and Secondary Service and System
Configurations
2.2Types of Sub transmission lines--------------------------------------7
2.2.1 Radial circuit arrangements in commercial building-------8
2.2.2Radial circuit arrangement: Common primary feeder to
Secondary unit substations---------------------------------------------9
2.2.3 Radial circuit arrangement: Individual primary feeder to
Secondary unit substations-------------------------------------------10
2.2.4 Primary radial-selective circuit arrangements--------------11
2.2.5 Secondary-selective circuit arrangement (Double-ended
substation with single tie) -------------------------------------------12
2.2.6 Secondary-selective circuit arrangement (Individual
substations with interconnecting ties) -----------------------------13
2.2.7 Primary- and secondary-selective circuit arrangement
(Double-ended substation with selective primary) --------------14
2.2.8 Looped primary circuit arrangement----------------------15
2.2.9 Basic spot network--------------------------------------------16
Chapter (3)
Load estimation
3.1 Introduction-----------------------------------------------------------29
3.2 Description of the project land-------------------------------------29
3.3 consideration of load calculations---------------------------------31
3.3.1 Diversity factor----------------------------------------------------32
3.4 Load calculations of buildings-------------------------------------33
3.4.1 Building (13A) ---------------------------------------------------33
3.4.1.1 Calculation of flat load---------------------------------------33
3.4.1.2 Calculations of the total building loads--------------------33
3.4.2 Building (13B) ----------------------------------------------------34
3.4.3 building (10C) -----------------------------------------------------35
3.4.4 building (5) --------------------------------------------------------36
3.5 Load calculation of blocks------------------------------------------36
3.5.1 Block (1) --------------------------------------------------------36
3.5.2 Block (2) --------------------------------------------------------37
3.5.3 Block (3) --------------------------------------------------------39
3.5.4 Block (4) --------------------------------------------------------39
3.5.5 Block (5) --------------------------------------------------------40
3.5.6 Block (6) --------------------------------------------------------40
3.5.7 Block (7) --------------------------------------------------------41
3.6 Critical loads---------------------------------------------------------41
3.6.1 Critical loads of block (1) ------------------------------------42
3.6.2 Critical loads of block (2) ------------------------------------42
3.6.3 Critical loads of block (3) ------------------------------------43
3.6.4 Critical loads of block (4) ------------------------------------44
3.6.5 Critical loads of block (5) ------------------------------------44
3.6.6 Critical loads of block (6) ------------------------------------45
3.6.7 Critical loads of block (7) ------------------------------------45
Chapter (4)
Renewable Energies
4. Introduction -----------------------------------------------------------47
II
4.1Wind Energy----------------------------------------------------------48
4.1.1 Basic principle of wind energy--------------------------------48
4.1.2 Wind Turbines---------------------------------------------------48
4.2.9Batteries-------------------------------------------------------69
4.2.10PV Output Power-------------------------------------------69
Power calculation of pv system----------------------------------71
4.3.Electrical Energy Storage Systems---------------------------74
4.3.1Electricity and the roles of EES---------------------------74
4.3.2Emerging needs for EES-----------------------------------76
4.3.2.1More renewable energy, less fossil Fuel---------------76
4.3.3The roles of electrical energy storage technologies----78
4.3.3.1The roles from the viewpoint of a utility------------79
4.3.3.2The roles from the viewpoint of consumers--------80
4.3.3.3The roles from the viewpoint of generators of
renewable energy---------------------------------------------81
4.3.4Types and features of energy storage systems-----------81
4.3.4.1Classification of EES systems-----------------------81
4.3.4.2 Mechanical storage system------------------------82
4.3.4.3Electrochemical storage Systems----------------82
4.3.4.4Thermal storage systems---------------------------83
4.3.5Configurations of EES-------------------------------------83
4.3.5.1Off-line systems---------------------------------------83
4.3.5.2Line-interactive systems------------------------------84
4.3.5.3On-linesystem-----------------------------------------------84
4.3.6 Choosing the Battery Type----------------------------------85
4.3.7New trends in applications---------------------------------86
4.3.8Management and control hierarchy of storage systems-89
4.3.8.1Internal configuration of battery storage systems---89
4.3.8.2External connection of EES systems----------------90
Chapter (5)
Transformer
5.1Introduction------------------------------------------------------96
5.2 What is a transformer? -----------------------------------------97
5.3 Types of transformers-------------------------------------------98
5.4Main Parts of Distribution Transformers----------------------98
5.4.1Iron Core----------------------------------------------------98
5.4.2Windings----------------------------------------------------99
5.4.3Tank---------------------------------------------------------99
5.4.4Oil Expansion Conservator-------------------------------99
5.4.5Terminals---------------------------------------------------99
5.4.6TapChanger------------------------------------------------99 IV
5.4.7Cooling Oil--------------------------------------------------99
5.5Number of phases-----------------------------------------------100
5.6Transformerratios----------------------------------------------100
5.7The regulation of a transformer-----------------------------100
5.8The efficiency of a transformer-----------------------------101
5.9Parallel operation of the transformers----------------------101
5.10Methods of cooling-------------------------------------------102
5.10.1Oil-Immersed Distribution Transformer------------102
5.1.0.2Dry-type transformer--------------------------------103
5.11 Specification of the used transformer-------------------103
5.12Determining capacity of thetransformer-----------------104
Chapter (6)
Cables
6.1 Introduction --------------------------------------------------------107
6.2 Factors considered in design and selection of cables ---------107
6.3 Cable insulation materials ---------------------------------------108
6.3.1 Paper -----------------------------------------------------------108
6.3.2 P.V.C. ---------------------------------------------------------108
6.3.3 Thermosetting (XLPE) --------------------------------------108
6.4 Derating Factors ---------------------------------------------------108
6.5 Calculation of cross section of cables --------------------------110
6.5.1Cables selected in our project -------------------------------111
6.5.1.1 Medium voltage cable ------------------------------------111
6.5.1.2 Low voltage cable -----------------------------------------112
6.6 voltage drop calculation ------------------------------------------114
6.6 Joints and terminations ----------------------------------------117
6.7 Cable trays ---------------------------------------------------------118
6.7.1 Types of cable trays-----------------------------------------118
6.7.1.1 Ladder ------------------------------------------------------118
4.7.1.2 Cable Tray (Race Ways) ---------------------------------118
6.8 The Conduits ------------------------------------------------------119
6.9 Cable Trench / Channel ------------------------------------------120
6.10 Distribution panels ----------------------------------------------122
6.10.1 Medium voltage distribution panel (M.V.D.P) --------123
6.10.1.1 Measuring instruments ----------------------------------123
6.10.1.2 Protection instruments -----------------------------------124
6.10.1.3 switchgears instruments ---------------------------------124
6.10.2 Low voltage distribution panel ---------------------------125
6.10.2.1 Main panel ------------------------------------------------125
6.10.2.2 Sub panels -------------------------------------------------126 V
Chapter (7)
Earthing
7.1 Introduction --------------------------------------------------------128
7.2 The advantages of earthing --------------------------------------128
7.3 The disadvantages of earthing -----------------------------------129
7.3.1 The two important disadvantages are ---------------------129
7.4Combining neutral with earth ------------------------------------130
7.5 In household wiring -----------------------------------------------130
7.6 IEC Terminology--------------------------------------------------131
7.6.1 TN network ---------------------------------------------------131
7.6.2 TT network ---------------------------------------------------133
7.6.3 IT network ----------------------------------------------------134
7.7 Theory vs. Practice------------------------------------------------134
7.8 Earth Electrode Measurement (Single Electrode) ------------135
7.9 Earth Electrode Measurement (Multiple Probe System) -----137
7.10 Soil Resistivity ---------------------------------------------------139
Chapter (5)
Protection system
8.1 Introduction --------------------------------------------------------144
8.2 Circuit breaker -----------------------------------------------------145
8.3 The types of the Circuit breakers -------------------------------145
8.3.1 Medium voltage circuit breaker ----------------------------145
8.3.2 Low voltage circuit breakers -------------------------------146
8.3.2.1 Miniature circuit breaker---------------------------------146
8.3.2.2 Molded case circuit breaker ------------------------------148
8.4 Types of protection used in our project ------------------------148
8.4.1 Over-current protection -------------------------------------148
8.4.2 Earth-fault protection ---------------------------------------150
8.4.3 Short circuit protection -------------------------------------150
8.5 Calculation of short circuit current -----------------------------151
8.5.1 Steps of impedance calculations used in short circuit -151
current calculations------------------------------------------------153
8.5.2 calculation of short circuit current for block (1)---------153
8.5.3 Calculation of short circuit current for other blocks ----154
VI
Chapter 1
IN THIS CHAPTER:
1.1Introduction
Over the recent years most of the Middle East countries were still
building their infra-structure like industrial, commercial and civil
projects. However whether the project is industrial or civil, it can’t
be done without scientific electricity distribution systems, so the
distribution system has the biggest importance in the construction
of any project. So sophisticated standards were set and improved to
assure that all designs and installations are made in highest quality
to achieve the desired safety for employee and public with highest
performance and less cost.
So in our project we will study the load to obtain the total power
absorbed by the load and relevant position and the position of the
power distribution centers (switchboards); after that we can
calculate the length of the connection elements.
After knowing the total power absorbed and the dimensions of the
transformer we can calculate the dimensions of the conductors by
evaluation of the current (Iload) in the single connection elements;
and we must know the conductors type (conductors and insulation
materials, configuration, ……); by knowing the length and the
cross section of the conductors we can calculate the voltage drop at
the load current under specific reference conditions and compare it
with the voltage drop limits at the final loads to modification the
dimensions of the conductors.
Fig 1-1 shows the flow chart summering the steps of this project.
Load analysis:
- Definition of the power absorbed by the load and
relevant position;
- Definition of the position of the power distribution
centers(switchboards)
- Definition of the paths and calculation of the length of
the connection elements
- Definition of the total power absorbed, taking into
account the utilization factor and demand factors
Dimensioning of conductor:
- evaluation of the current (Ib) in the single connection
elements,
- definition of the conductor type (conductors and
isolation materials,
Configuration,...)
- definition of the cross section and of the current
carrying capacity,
- calculations of the voltage drop at the load current
under specific refrance
Conditions (motor starting,...).
Chapter 2
IN THIS CHAPTER:
Comparison of Configurations
Primary and Secondary Service and System Configurations Chapter2
2.1 Introduction
In order to provide electrical service to a building or buildings,
you must first determine what type of system is available from the
utility company or from a privately owned and operated system
such as might be found on a college or university campus or
industrial or commercial complex, as the case may be. Once this
is known, it is important to understand the characteristics of the
system—not only voltage, capacity, and available fault current but
also the operational, reliability, and relative cost characteristics
inherent to the system by virtue of its configuration or arrangement.
Knowing the characteristics associated with the system arrangement,
the most appropriate service and distribution system for the
application at hand can be determined.
2.2.1.1 Characteristics
1. Simplest and lowest cost way of distributions.
2. Lowest reliability. A fault in the supply circuit, transformer, or the
main bus will cause interruption of service to all loads.
3. Modern distribution equipment has demonstrated sufficient
reliability to justify use of the redial circuit arrangement in many
applications.
4. Most commonly used circuit arrangement
2.2.2.1Characteristics
Multiple small rather than single large secondary substations.
Used when demand, size of building, or both may be required to
maintain adequate voltage at the utilization equipment.
Smaller substation located close to center of load area.
Provides better voltage conditions, lower system losses, less
expensive installation cost than using relatively long, high-
amperage, low-voltage feeder circuits.
A primary feeder fault will cause the main protective device to
operate and interrupt service to all loads. Service cannot be restored
until the source of trouble has been eliminated.
If a fault were in a transformer, service could be restored to all
loads except those served by that transformer.
2.2.3.1 Characteristics
First three characteristics are the same as figure 3.2
This arrangement has the advantage of limiting outages, due to a
feeder or transformer, to the loads associated with the faulted
equipment
The cost is usually higher than the arrangement shown in figure
2.2
10
(a) fused Dual switches (b) Duplex load interrupter switches with
transformer primary fuses
2.2.4.1 Characteristics
These circuit arrangements reduce both the extent and duration of
an outage caused by a primary feeder fault.
Operating feature - duplicate primary feeder circuit and load
interrupter switches, permit connection to either primary feeder
circuit.
Each feeder must be capable of saving the entire load.
Suitablesafety interlocks usually required to prevent closing of
both switches at the same time.
Under normal operating conditions, appropriate switches are
closed to balance loads between two primary feeder circuit.
Primary-selective switches are usually manually operated, but can
be automated for quicker restoration of service. Automated switching
is more costly but may be justified in many applications.
11
If a fault occurs in a secondary substation transformer, service can
be restored to all loads except those served from the faulted
transformer.
2.2.5.1 Characteristics
Under normal conditions, operates as two separate radial systems
with the secondary bus-tie circuit breaker normally open.
Loads should be divided equally between the two bus sections.
If a fault occurs on a primary feeder or in a transformer, service is
interrupted to all loads served from that half of the double-ended
arrangement. Service can
be restored to all secondary buses by opening the secondary main
on the faulted side and closing the tie breaker.
The main-tie-main breakers are normally interlocked to prevent
paralleling the transformer and to prevent closing into a secondary
bus fault. They can also be automated to transfer to standby operation
and retransfer to normal operation.
Cost of this arrangement will depend upon the spare capacity in
the transformer and primary feeder. The minimum will be determined
by the essential loads that need to be served under standby operating
conditions. If service is to be provided for all loads under standby
conditions, then the primary feeders and transformers must be 12
capable of carrying the total load on both substation buses.
2.2.6.1 Characteristics
In this modification of the secondary-selective circuit
arrangement shown if figure, there is only one transformer in each
secondary substation; but adjacent substations are interconnected in
pairs by a normally open low-voltage tie circuit.
When the primary feeder or transformer supplying one secondary
substation bus is out of service, essential loads on that substation bus
can be supplied over the tie circuit.
Operating aspects of this system are somewhat complicated if the
two substations are separated by distance.
This would not be a desirable choice in a new building service
design because a multiple key interlock system would be required to
avoid tying the two substations together while they were both
energized.
13
2.2.7.1 Characteristics
Used when highly reliable service is needed, such as hospital or
data center loads.
Has the combined benefits and characteristics of the arrangement
shown in figure and figure
Small premium cost over configuration shown in figure
forprimary selector switches.
14
2.2.8.1 Characteristics
Basically a two-circuit radial system with the ends connected
together forming a continuous loop.
3.2.8.1 Characteristics
The spot network is a localized distribution center consisting of
two or more transformer/network protector units connected to a
common bus called a "collector bus". A building may have one or
more spot network services.
Spot network are employed to provide a reliable source of power 16
to important electrical loads. Spare capacity is built in to allow for
at least one contingency, i.e., loss of a transformer or primary
network feeder will cause no interruption of service.
Disadvantages
1. High-profile arrangement equipped with circuit breaker bypass
facilities does not provide for circuit protection when bypass
facilities are being used inside the substation.
2. A single bus arrangement has the lowest reliability.
3. Failure of a circuit breaker or a bus fault causes loss of the entire
substation.
4. Maintenance switching can complicate and disable some of the
protective relay scheme and over all relay coordination.
5. Maintenance at the upper elevations of high-profile arrangements
necessitates de-energization or protection of the lower equipment.
Advantages
1. Accommodation of circuit breaker maintenance while maintaining
service and line protection.
2. Accommodation of circuit breaker maintenance while maintaining
service and line protection.
3. Reasonable in cost.
4. Fairly small land area.
5. Easily expandable.
Disadvantages
1. An additional circuit breaker is required for bus tie.
2. Since the bus tie breaker, have to be able to be substituted for any
line breaker, its associated relaying may be somewhat complicated.
3. Failure of a circuit breaker or a bus fault causes loss of the entire
substation.
4. Somewhat complicated switching is required to remove a circuit
breaker from service for maintenance.
21
Advantages
1. Flexible operation.
2. High reliability.
3. Isolation of bus sections and circuit breakers for maintenance
without disrupting circuitoperation .
4. Double feed to each circuit.
5. No main buses.
6. Expandable to breaker-and-a-half configuration .
7. Economic design.
Disadvantages
1. Ring may be split by faults on two circuits or a fault during
breaker maintenance to leave possibly undesirable circuit
combinations (supply/load) on the remaining bus sections. Some
consider this, however, to be a second contingency factor.
2. Each circuit has to have its own potential source for relaying.
24
Advantages
1. Flexible operation
2. High reliability.
3. Can isolate either main bus for maintenance without disrupting
service.
4. Can isolate any circuit breaker for maintenance without disrupting
service.
5. Double feed to each circuit6.Bus fault does not interrupt service to
any circuits.
6. All switching done with circuit breakers.
Disadvantages
1. One-and-a-half breakers are required per circuit.
2. Relaying is involved, since the center breaker has to respond to
faults of either of its associated circuits.
3. Each circuit should have its own potential source for relaying.
25
Fig(2.15) Breaker-and-a-half.
28
IN THIS CHAPTER:
Chapter 3
Description of the project land
Critical loads
Load Estimation Chapter3
3.1 Introduction
Load calculation is as important as it helps in cable cross section
design, circuit breaker design, transformer rating and distribution
boards.
Block (6)
Is the same as block (3) in its construction and area.
Block (7)
Is the same as block (1) in its construction, but its area is 7300m².
The ground of this block is stores of area 3205m².
Note:
• The ground of each block is connected under buildings.
Fire pump 14
Water pump 9.4
Elevators motor 18.75 31
Elevators motor of mall 9.4
Escalators 9.4
Hotel 0.4
Office 1
Mall 1
Note: 32
Load KVA
Building load 133.12
Service of Building 4.5
Basement 4.5
Water pumps 18.75
Fire pumps 28
Elevators 37.5
Total load 226.37
Load KVA
Building load 148
Service of Building 6.03
Basement 6.03
Water pumps 18.75
Fire pumps 28
Elevators 37.5
Total load 243.51
Load KVA
Building load 66
Service of Building 5.5
Basement 5.5
Total load 77
Load KVA
Streets load 24.6
Ground load 51.3
Building (13A) 226.37
Building (13B) 243.51
Building (10C) 205.7 36
Building (5) 77
Total load of block 828.48
c- Loads of Hotel: 37
Hotel consists of 2 building of 13 floors, building of 3 floors,
building of 2 floors and 2 building of 6 floors of area 590, 40, 80
and 540 m2 respectively.
load KVA
Streets load 43
Mall load 213.5
Hotel load 546.7
Office load 478
Total load of block 1281.2
Load KVA
Streets load 21.3
Ground load 87.8
Building (13A) 226.37
Building (13B) 243.51
Building (10C) 205.7
Building (5) 77
Total load of block 861.68
Load KVA
Streets load 29.2
Ground load 138.6
Building (13A)1 226.37
Building (13A)2 226.37
Building (13B)1 243.51
Building (13B)2 243.51
Building (5)1 77
Building (5)2 77
Total load of block 1261.56
Load KVA
Streets load 19.3
Ground load 68.72
The building 422.5
Total load of block 510.52
Load KVA
Streets load 21.3
Ground load 87.8
Building (13A) 226.37
Building (13B) 243.51
Building (10C) 205.7
Building (5) 77
Total load of block 861.68
Load KVA
Streets load 27.3
Ground load 21.3
Building (13A) 226.37
Building (13B) 243.51
Building (10C) 205.7
Building (5) 77
Total load of block 801.17
Tables (3-15) to (3-17) show the critical loads of each building of this
block.
Table (3.15) the critical loads of building (10C).
Critical load K VA
(50%) of Building 2.25
Service
Fire pump 28
Elevators 37.5
Water pump 18.75
Critical loads K VA
(50%) of Building 3.015
Service
Fire pump 28
Elevators 37.5
Water pump 18.75
45
Chapter 4
IN THIS CHAPTER:
Wind Energy
Solar energy
4.1Wind Energy
4.1.1 Basic principle of wind energy
The terms "wind energy" or "wind power" describe the process by
which the wind is used to generate mechanical power or electricity.
Wind turbines convert the kinetic energy in the wind into
mechanical power. This mechanical power can be used for specific
tasks (such as grinding grain or pumping water) or a generator can
convert this mechanical power into electricity to power homes,
businesses, schools.
48
brushed motor can reach a good efficiency, but are typically at most
70%.
There are many great advantages to using a brushed motor. One of
the biggest reasons is because typically you can find one not
requiring any gearing and still get a battery charging voltage in light
wind. They are also quite easy to find, they can be purchased from
eBay, surplus supply stores, industrial supply stores, and can find
them on different things that might get thrown away or given away
(like a treadmill).
(1)
where A = swept area of turbine blades, in m2
ρ = air density, in kg/m3
u = wind speed, in m/s
The process of converting wind power to electrical power results in
efficiency losses, as described in the diagram below.
(2)
Where C tot = overall efficiency = Cp Ct Cg
Overall efficiency is typically between 0.3 and 0.5, and varies with
both wind speed and rotational speed of the turbine. For a fixed
rotational speed, the turbine operates most efficiently at what's
known as the rated wind speed. At this wind speed, the electrical 52
power generated by a wind turbine is near its maximum (Per), and
overall efficiency is denoted C tot R.
(3)
For a fixed rotational speed, the electrical power output of a wind
turbine can be estimated using the profile below.
Where
u c = cut-in speed, the speed at which the electrical power output
rises above zero and power production starts.
u r = rated wind speed.
u f = furling wind speed, the speed at which the turbine is shut
down to prevent structural damage.
53
55
Fig 4-6 Pitch Fig-7 yaw adjustment
56
58
59
4.2Solar energy
The energy in solar irradiation comes in the form of electromagnetic
waves of a wide spectrum. Longer wavelengths have less energy (for
instance infrared) than shorter ones such as visible light or UV.
The spectrum can be depicted in a graph, the spectral distribution,
which shows the relative weights of individual wavelengths plotted
over all wavelengths, measured in W / m (wavelength).
The diagram displays the spectrum of a sun ray just outside the entry
into the earth’s atmosphere. The peak of the spectrum is within the
visible spectrum, but there are still significant amounts of shorter and
longer wavelengths present.
4.2.2Photovoltaic cells
The Principles of Photovoltaic cells
PV cells are made of at least two layers of semiconductor material.
One layer has a positive charge" P-type", the other layer has
negative charge" N-type" with different electrical properties, joined
together. The joint between these two semiconductors is called the
"P-N junction."
Sunlight striking the photovoltaic cell is absorbed by the cell. The
energy of the absorbed light generates particles with positive or 62
4.2.3PV connection
PV cells are interconnected together in a package called a module.
When two modules are wired together in series, their voltage is
doubled while the current stays constant.
When two modules are wired in parallel, their current is doubled
while the voltage stays constant.
To achieve the desired voltage and current, modules are wired in
series and parallel into what is called a PV array.
63
4.2.4Types of cells
4.2.4.1Crystalline silicon
Crystalline cells have been in service the longest and exhibit
outstanding longevity. Cells developed almost 40 years ago are still
operating and most manufacturers offer 10-year or longer
warranties on crystalline cells. There are two sub-categories of
crystalline cells – single crystal and polycrystalline. They both
perform similarly. The efficiency of crystalline cells is around 13%.
4.2.4.2 Amorphous silicon
Amorphous silicon is a recent technology for solar cells. It is
cheaper to produce and offers greater flexibility, but their efficiency
is half of the crystalline cells and they will degrade withuse.
These types of cells will produce power in low light situations.
This technology is expected to improve application ossibilities far
exceeding crystalline technology. Currently; the best choice for
solar cells will be the crystalline variety.
64
4.2.5.2Grid-interface system
Uses power from the central utility when needed and supplies surplus
home-generated power back to the utility. Termed a “parallel” system by
the utility.
4.2.7.1Charge controllers
Regulate the voltage entering batteries to avoid overcharging the
batteries.
Available in different capacities and must be selected to match the
system.
Prevents losses of power back through the panels at night.
67
4.2.7.2Wiring
Some direct current (DC) equipment may be desirable to operate in
a home. DC appliances and equipment, although initially more
Distribution System Design For Smart City
Renewable Energies Chapter4
4.2.8MountingPV panels
PV arrays must be placed to receive the most sunlight. A 45-degree
slope to the panels with a south orientation is best. The 45-degree
slope will help offset the shorter winter day by bringing the panels
closer to perpendicular to the lower winter sun.
There are several ways to mount the panels – fixed, fixed with
adjustable tilt angles, manual tracking, passive tracking, and active
trackers. All of these mounting approaches can be placed on the
ground or on a roof except for some active trackers which are pole
mounted and thus more suited for a ground mount.
Fixed mounts are the least costly and lowest energy producing
mounting systems. A metal frame suited for outdoor conditions is
best. PV panels will substantially outlive the best wood racks.
The fixed mount with adjustable tilt angles and manual tracking
mounts will require manually changing the angle of the PV panels
either several times a day (manual tracking) and/or seasonal
adjustments to keep the panels as close to perpendicular as possible
to the sun (tilt angle adjustments).
trackers occurs during the longest days of summer. There are not
large gains in the winter.
4.2.9Batteries
Batteries are the best method of storing energy from a PV system
for the periods when the sun is not shining. (This is for stand-alone
or non -grid connected systems.) The information from calculating
the daily load will be needed for determining the battery sizing.
4.2.10PV Output Power
The basic element of a solar energy conversion system is the PV
module/cell, which absorbs photons of light from the incident solar
radiation, and releases electrons to provide a DC current to a closed
electrical circuit. The rating of a PV module is expressed in peak-
watt and is equal to the maximum power produced by a module
under standard test conditions (STC).
However, a single PV module has limited potential to provide
power at high voltage or high current levels. It is thus mandatory to
connect PV modules in series and parallel, in a form of array, in
order to scale-up the voltage and current to reach a given level of
electrical power.
The manufacturers of PVs usually provide the characteristic of their
PV module under STC by
specifying Isc (short circuit current in A), Voc (open-circuit
voltage in V),IMPP (current at maximum power point in A), VMPP
(voltage at maximum power point in ),and NOT(nominal operating
temperature of cell in o C).
69
70
Block"2"
{office1,office2,hotel1,hotel2,hotel3,hotel4}
Office1 : 1bulding area=910
number of modules =558
power of modules = 85374Watt =0.1067175MVA
Office2 : 2bulding area=445 for each building
71
number of modules =273
power of modules = 41769Watt
{13B}:area =910
number of modules =558
power of modules=85374Watt =0.1067175MVA
{13A}:area=680
number of modules =417
power of modules =63801Watt =0.07975MVA
Block" 5"
area = 2117
number of modules =1298
power of modules=198594Watt =0.2482425MVA
Mall: area=350
number of modules =214
power of modules =32742Watt =0.0409275MVA
73
4.3.1.5Transmission by cable
Electricity always needs cables for transmission, and supplying
electricity to mobile applications and to isolated areas presents
difficulties. EES systems such as batteries can solve this problem
with their mobile and charge/discharge capabilities. In remote
places without a power grid connection recharging an electric
vehicle may present a challenge, but EES can help realize an
environmentally friendly transport system without using
conventional combustion engines.
Off-grid areas
In off-grid areas where a considerable amount of energy is
consumed, particularly in the transport sector, fossil energy should
be replaced with less or non-fossil energy in such products as plug
in hybrid electric vehicles (PHEVs) or electric vehicles (EVs) (see
Figure 1). More precisely, fossil fuels should be replaced by low-
carbon electricity produced mainly by renewable generation. The
most promising solution is to replace petrol or diesel-driven cars by
electric ones with batteries. In spite of remaining issues (short
driving distance and long charging time) EES is the key technology
for electric vehicles.
the other hand longer storage duration and fewer cycles are needed.
The following sections describe the roles in detail.
2) Power quality
A basic service that must be provided by power utilities is to keep
supply power voltage and frequency within tolerance, which they
can do by adjusting supply to changing demand. Frequency is
controlled by adjusting the output of power generators; EES can 79
provide frequency control functions. Voltage is generally controlled
by taps of transformers, and reactive power with phase modifiers.
Distribution System Design For Smart City
Renewable Energies Chapter4
4) Isolated grids
Where a utility company supplies electricity within a small, isolated
power network, for example on an island, the power output from
small-capacity generators such as diesel and renewable energy must
match the power demand. By installing EES the utility can supply
stable power to consumers.
Flow batteries.
Redox flow battery (RFB)
Hybrid flow battery (HFB)
82
4.3.5Configurations of EES
Energy storage systems can be replaced off-line, in a line-
interactive mode, or on-line to deal with power quality problems
4.3.5.1Off-line systems
Off-line (Also called standby) energy storage systems (Figure.4)
are cost-effective for small, less critical, stand-alone applications
such as isolated PCs and peripherals. However, when an outage
occurs in the utility supply, this configuration may not be able to
switch to its storage power supply fast enough to prevent
disturbances in highly sensitive equipment. If filters are present,
standby systems will protect against most transients by limiting
excess voltage, but their ability to protect against sags and surges is
significantly less than on-line or line-interactive designs.
83
4.3.5.2Line-interactive systems
Line-interactive systems (Figure.5) provide highly effective power
conditioning and energy storage backup. Their voltage boost
circuitry and fast acting transfer switches protect against voltage
sags and surges and provide extremely quick response to
disturbances. Transfer switches with response times of ~1/4 power
cycle provide adequate protection for the most sensitive devices.
The energy efficiency of line-interactive storage system is higher
than that of on-line systems and becomes an important cost-saving
advantage when protecting hundreds of kilowatts of critical loads.
4.3.5.3On-line systems
The on-line configuration (Figure.6) provides the highest level of
protection for critical loads. Off-line and line-interactive storage systems
reduce the impact of transients, surges, and sags by clipping the peaks,
boosting power, or switching to storage backup. In contract, on-line
energy storage systems regenerate the sine wave and do not involve
switching. The configuration protects against all utility disturbances
because the system completely isolates the load from the utility
supply at all times. Since on-line systems continuously condition
input supply, they have relatively large parasitic losses.
84
1. Sodium-Sulfur,
2. Zinc-Bromine,
3. Hydrogen-Nickels. and
4 Lead-acid
Out of the above four only the lead-acid battery has been the front
runner. A cycle life of 1000-1500 may easily be reached with the
present technology.
85
87
For our project we will use the lead-acid battery and online energy
storage system configuration.
Lead-acid battery
Lead acid batteries are the world’s most widely used battery type
and have been commercially deployed since about 1890. Lead acid
battery systems are used in both mobile and stationary applications.
Their typical applications are emergency power supply systems,
stand-alone systems with PV, battery systems for mitigation of
output fluctuations from wind power and as starter batteries in
vehicles. Stationary lead acid batteries have to meet far higher 91
product quality standards than starter batteries. Typical service life
is 6 to 15 years with a cycle life of 1 500 cycles at 80 % depth of
Distribution System Design For Smart City
Renewable Energies Chapter4
92
Chapter 5
IN THIS CHAPTER:
What is a transformer?
Types of transformers
Methods of cooling
Transformer Chapter5
5.1Introduction
The transformer is defined as a static device which by
electromagnetic induction transforms alternating voltage and
current between two or more windings at the same frequency and
usually at different values of voltage and current. The transformer
consists of two winding and iron core; the winding connected to the
source is called the primary winding, and the one connected to the
load is called the secondary winding. The two windings are
insulated from each other and from the core; the core is high
presence magnetic circuit that links all the transformer’s windings.
Energy is transferred from the primary to the secondary through a
magnetic induction. There may be more than one secondary
windings, each connected to a different load or interconnected to
provide different output voltages. Without high transmission and
distribution voltages the power losses and voltage drops associated
with line resistance would make electrical power transfer very
inefficient. Currently the highest practical generating voltage is
around 25 kV, so transformers are needed to step up voltage for
economical transmission, and step down voltage to levels that safe
for the customer to use.
The number of times the wires are wrapped around the core
("turns") is very important and determines how the transformer
changes the voltage.
If the primary has fewer turns than the secondary, you have a
step-up transformer that increases the voltage.
If the primary has more turns than the secondary, you have a
step-down transformer that reduces the voltage.
If the primary has the same number of turns as the secondary, the
outgoing voltage will be the same as what comes in. This is the case
for an isolation transformer.
5.3.2Step-down transformers
5.3.4Variable auto-transformers
5.4.2Windings
High tension turns are made of copper wires of either circular cross
sections varnish isolated or rectangular cross sections isolated by
silicone paper.
Low tension turns are made of either no insulated copper foils with
insulating paper in between or of rectangular wires insulated by
cylindrical paper sheets.
5.4.3Tank
5.4.7Cooling Oil
Transformers are filled with special oil (Duala (5) or equal) of high
insulating grade according to IEC 99
specifications.
5.5Number ofphases
5.5.1Single phase.
Two or more winding, coupled by acommon magnetic core.
5.5.2Poly phase.
A polyphase transformer
consists of separate insulated
electric windings for the
different phases, wound upon a
single core structure, certain
portions of which are common
to the different phases as shown
in figure (5.10)
Fig (5.2)
5.6Transformer ratios
The voltage ratio of a constant-voltage transformer, i.e., the ratio of
primary to secondary voltage, depends primarily upon the ratio of
the primary to the secondary turns. The voltage ratio will vary
slightly with the amount and power factor of the load. For general
work the voltage ratio can be taken as equal to the turn ratio of the
windings. The current ratio of a constant-voltage transformer will
be approximately equal to the inverse ratio of the turns in the two
windings.
100
101
Fig (5.3) shows the the correct connection and the wrong connection of transformers used in
parallel operation.
5.10Methods of cooling
High temperatures will damage the winding insulation. Power
transformers rated up to several hundred kVA can be adequately
cooled by natural convective air-cooling, sometimes assisted by
fans. In larger transformers, part of the design problem is removal
of heat. Some power transformers are immersed in transformer oil
that both cools and insulates the windings. Some "dry" transformers
(containing no liquid) are enclosed in sealed, pressurized tanks and
cooled by nitrogen or sulfur hexafluoride gas.
102
5.1.0.2Dry-type transformer
Close to the load which improves over all system regulation and
reduces costly secondary line losses.
∆-Y connection
103
Step-down 22/0.4 KV
Z%=5%
Distribution System Design For Smart City
Transformer Chapter5
∆-Y connection
Step-down 22/0.4 KV
Z%=6%
104
105
Chapter 6
Cable insulation materials
Derating Factors
Distribution panels
Cables Chapter6
6.1 Introduction
This Chapter is concerned with the selection of wiring cables for use
in an electrical installation. It also deals with the methods of
supporting such cables, ways in which they can be enclosed to provide
additional protection, and how the conductors are identified. All such
cables must conform in all respects with the Egyptian Code (E.C).
This Electrician's Guide does not deal with cables for use in supply
systems, heating cables, or cables for use in the high voltage circuits
of signs and special discharge lamps.
6.3.2 P.V.C.
Polyvinyl chloride (p.v.c.) is now the most usual low voltage cable
insulation. It is clean to handle and is reasonably resistant to oils and
other chemicals. When p.v.c. burns, it emits dense smoke and
corrosive hydrogen chloride gas. The physical characteristics of the
material change with temperature: when cold it becomes hard and
difficult to strip, and so BS 7671 specifies that it should not be worked
at temperatures below 5°C. However a special p.v.c. is available
which remains flexible at temperatures down to -20°C.
one or more layers consistently on the reel. The more layers on the
reel, the less amperage a cable can handle due to the effects caused by
the buildup of heat.
These following derating factors are considered in our calculation
1- Ground temperature derating factor
109
110
111
112
113
Where:
mV: V.D per meter per ampere.
L : cable length.
A : current value.
n : number of cables per phase.
The value of V.D related to the type of cable and its cross section
per meter length can be given from factory's manuals [2]
The length of cable is measured between the main switch board and
the sub main switch board. The distance between boards, the spear
length and non-linear distance must be taken in consideration to
determine cable length.
- The allowable percentage value of voltage drop is 5%
5
400 20volt
100
115
116
Fig(6.2)cable-termination
117
(a) (b)
Fig (6.3) Cable trays
6.7.1.1 Ladder
Made of steel as tow plates connected together . These trays offer
strength and high capacity in industrial facilities. Also it is good in
case of heavy loads of cables as ( power station – cement factory –
heavy industries – chemical industries ) and it gives the best solution
for towers and high building. Fig (6.4)
* Application:
Widely used in glass, electronic, photo voltaic and automotive
industry. Fig(6-5).
119
Fig( 6-7)
121
122
a) At incoming panel:
b) At outgoing panel:
c) at bus-tie panel:
- Three ammeter and current transformer (C.T).
a) At outgoing feeders:
- Non directional over current protection relay feds from (C.T, D.C).
- Non directional earth fault current protection feds from (C.T , D.C).
-D.C source .
b) At incoming circuits:
-Non directional over current protection relay fed from (C.T, D.C).
- Non directional earth fault current protection relay fed from (C.T ,
D.C).
-D.C source.
c) At BUS-Tie panel:
-Non directional over current protection relay feds from (C.T, D.C).
- Non directional earth fault current protection relay fed from (C.T ,
D.C).
-Earth leakage E/L relay.
-Three ammeter and current transformer (C.T).
-D.C source .
6.10.2.1Main panel
a) Fuse
b) Circuit breaker
125
The sub panel is panels which it’s distributed inside the floor and
it’s number depend on the floor geometry and floor loads (sockets,
lighting, appliance ).
the sub panel is nearly look like the main floor panel in construction
it’s consist of main breaker 3 Ø and sub breakers 1Ø which feeds
directly to the loads through wires to the loads.
126
IN THIS CHAPTER:
Chapter 7
Advantages& Disadvantages of
Earthing
IEC Terminology
Soil Resistivity
Earthing Chapter 7
7.1 Introduction
Ground or earth in a mains (AC power ) electrical wiring
system is a conductor that exists primarily to provide a low
impedance path to the earth to prevent transient hazardous voltages
from appearing on equipment ; normally a grounding conductor
does not carry current . Neutral is a circuit conductor that may carry
current in normal operation, and which is usually connected to
earth.
They are:
1- The whole electrical system is tied to the potential of the general
mass of earth and cannot float at another potential. For example, we
128
can fairly certain that the neutral of our supply is at, or near, zero
volts (earth potential) and that the phase conductors of our standard
resistance through the fault path and back to the supply very low by
having a metallic connection from the earth back to the supply
transformer (a TN system). Then when a fault happens a very high
current will flow rapidly blowing a fuse (or tripping a circuit
breaker).
7.6.1 TN network
In a TN earthing system, one of the points in the generator or 131
transformer is connected with earth, usually the star point in the
7.6.2 TT network
In a TT earthing system, the protective earth connection of the
consumer is provided by a local connection to earth, independent of
any earth connection at the generator.
133
6.6.3 IT network
In an IT network, the distribution system has no connection to
earth at all, or it has only a high impedance connection. In such
systems, an insulation monitoring device is used to monitor the
impedance.
where:
R: resistance to remote earth (W)
r: soil resistivity (W-cm)
L: length of conducting path (cm)
A: cross-sectional area of path (cm)
137
Once the resistance to remote earth for each electrode in the entire
grounding system is determined, one can calculate the resistance to
remote earth for the entire grounding system in one of two ways. The
first approach is in understanding that the electrodes are in parallel
with each other (through the grounding grid and ground itself.)
Because they are in parallel, the rule for parallel resistances can be
used.
142
IN THIS CHAPTER:
Chapter 8
Circuit breaker and their types
8-1 Introduction
Every electrical thing need protection .The house wiring is
protected by fuse. Modern generators are protected by complex
protective schemes . Protective relays is necessary with every
electrical plant and not part of power system is left unprotected. The
choice of protection is depend upon some aspect such as type and
rating of protected equipment, its importance, location, probable
abnormal condition, cost, etc…
The need of protective relaying protects the concerned equipment
from abnormal operating condition and faults. When an abnormal
condition develops in the protected equipment or machine , the
protective relaying for the protected equipment or machine sense
the abnormal condition and initiates an alarm or closes the tripping
circuit of the circuit breaker (C.B) so as to open the C.B and isolate
the equipment or machine from the supply. In other words,
protective relaying senses the abnormal condition in apart of the
power system and gives an alarm or isolates that faulty system from
healthy system. This can be achieved by essential component that
are C.B. and relays.
It should be note that protection relay does not prevent the
appearance of faults . It can take action only after fault has
occurred. Relay distinguish between normal and abnormal
condition .Whenever an abnormal condition develops, the relay
close its contacts, there by the trip circuit of the C.B. is closed.
Current from supply flow in the trip coil of the C.B. and C.B. opens
and faulty part is disconnected from supply. Removal of faulty part
from the system is automatic and fast.
Besides the relays and C.Bs ,there are several other important
components in protective relay scheme, these include protective
current transformers, voltage transformer ,auxiliaries, etc... Each
component is important. Protective relaying is a team-work of
these components.
The function of Protective relaying include the following :
144
1. To sound an alarm or to close the trip circuit of C.B. so as to
disconnect a component during an abnormal condition in the
3) Motor Protection
To calculate the 3-Φ short circuit current ( Is.c ) from the equation :
I sc =Us/Zf=1.05 Un/Zf
Where :
Zf: the total impedance between source and the short circuit
position
By using equation :
Note : 151
( Rseq ) = 0.047 mΩ
( Xseq ) = 0.316mΩ
Where:
And calculate the equivalent resistance per meter from the equation
:
( Req ) =
= 22.5 Ω.mm2 per meter for the copper and = 33 Ω.mm2 per
meter for the Aluminum
and (A) is the cross section area in mm2
Impedance of the bus duct :
Assuming that the equivalent reactance ( Xeq ) = 0.15 mΩ and the
resistance of it is calculated as in the case of cables . 152
Note: In our design, a bus duct from transformer to the main- board
is used.
Zsc = = 8Ω
Isc = = 27.27 KA
Req = = 10mΩ
Zt = 10.33+0.3+8+0.319 =18.95mΩ
Isc = = 12.19 KA
Req = = 0.45mΩ
ISC = = 25.46 KA
Req = = 0.321 mΩ
Zeq= 0.33mΩ
Zt=0.331+0.3+8+0.319=8.95mΩ
ISC = = 25.78KA
Req = = 3.36mΩ
Zeq =4.6mΩ
Zt = 4.6+.3+8+0.319 = 13.22mΩ
Isc = = 17.47KA
Isc = = 13.5KA
block(4)
Table 8.3 calculation of short circuit for block (4)
block(5)
Table 8.4 calculation of short circuit for block (5)
Load Req Xeq Zeq Zt Isc Isc MVA
mΩ mΩ mΩ mΩ KA breaking breaking
capacity
Build 0.6 0.4 0.7 9.3 24.8 30 20.8
ing 1.6 0.4 1.62 10.2 22.6 25 17.3
block(7)
calculation of short circuit for block (7) as same as block (1) 157
References
الكىد المصري ألسس تصميم وشروط تنفيذ التىصيالت الكهربية في المباني
Instructions, LEM
Superior Grounding,
http://www.superiorgrounding.com/soils.html
Grounding, ERICO
Web site
http://www.greenrhinoenergy.com/solar/
http://www.i15.p.lodz.pl/strony/EIC/res/Description_of_technology_pv.html
http://www.buildingwithawareness.com/blog/2009/03/determining-the-actual-
power-output-of-photovoltaic-pv-panels-for-green-homes/
www.eia.gov
www.sayedsaad.com
www.answers.com
www.tkne.net
www.ieee xplore.ieee.org
159
www.dvd4arab.com
www.scholar.google.com.eg