TABLE 9.6.1 Lighting Power Densities Using The Space-by-Space Method

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

TABLE 9.6.

1 Lighting Power Densities Using the Space-by-Space Method

LPD, W/ LPD, W/
Common Space Types a Building-Specific Space Types
m2
m2
Office-Enclosed 12 Gymnasium/Exercise Center
Office-Open Plan 12 Playing Area 15
Conference/MeetingfMultipurpose 14 Exercise Area 10

Classroom/Lecture/Training 15 Courthouse/Police Station/Penitentiary


For Penitentiary 14 Courtroom 20
Lobby 14 Confinement Cells 10
For Hotel 12 Judges' Chambers 14
For Performing Arts Theater 36 Fire Stations
For Motion Picture Theater 12 Engine Room 9
Audience/Seating Area 10 Sleeping Quarters 3
For Gymnasium 4 Post Office-Sorting Area 13
For Exercise Center 3 Convention Center-Exhibit Space 14
For Convention Center 8 Library
For Penitentiary 8 Card File and Cataloging 12
For Religious Buildings 18 Stacks 18
For Sports Arena 4 Reading Area 13
For Performing Arts Theater 28 Hospital
For Motion Picture Theater 13 Emergency 29
For Transportation 5 Recovery 9
Atrium-First Three Floors 6 Nurses' Station II

Atrium-Each Additional Floor 2 Exam/Treatment 16


Lounge/Recreation 13 Pharmacy 13
For Hospital 9 Patient Room 8
Dining Area 10 Operating Room 24
For Penitentiary 14 Nursery 6
For Hotel 14 Medical Supply 15
For Motel 13 Physical Therapy 10
For Bar Lounge/Leisure Dining 15 Radiology 4
For Family Dining 23 Laundry-Washing 6
Food Preparation 13 Automotive-Service/Repair 8
Laboratory 15 Manufacturing
Restrooms 10 Low Bay «25 ft Floor to Ceiling Height) 13
Dressing/Locker/Fitting Room 6 High Bay (225 ft Floor to Ceiling Height) 18

CorridorlTransition 5 Detailed Manufacturing 23


For Hospital 11 Equipment Room 13
For Manufacturing Facility 5 Control Room 5
Stairs-Active 6 Hotel/Motel Guest Rooms 12
Active Storage 9 Dormitory-Living Quarters 12
For Hospital 10 Museum
Inactive Storage 3 General Exhibition 11
For Museum 9 Restoration 18
Electrical/Mechanical 16 Bank/Office-Banking Activity Area 16

ANSI/ ASHRAE/IESNA Standard 90.1-2007 (SI Edition) 63


TABLE 9.6.1 Lighting Power Densities Using the Space-by-Space Method (continued)

LPD, WI LPD, WI
Common Space Types 3 Building-Specific Space Types
m2 m2
Workshop 20 Religious Buildings
Sales Area [for accent lighting, see Section 9.6.2(b)] 18 Worship Pulpit, Choir 26

Fellowship Hall 10
Retail
Sales Area [for accent lighting, see Section 9.6.3(c)] 18
Mall Concourse 18
Sports Arena
Ring Sports Area 29
Court Sports Area 25
Indoor Playing Field Area 15
Warehouse
Fine Material Storage 15
MediumlBulky Material Storage 10
Parking Garage-Garage Area 2
Transportation
Airport-Concourse 6
Air/TrainiBus-Baggage Area 11
Terminal-Ticket Counter 16
a In cases where both a common space type and a building-specific type are listed, the building specific space type shall apply.

64 ANSIIASHRAE/IESNA Standard 90.1-2007 (Sl Edition)