Gas-Insulated Switchgear Type 8DQ1: Technical Data
Gas-Insulated Switchgear Type 8DQ1: Technical Data
Gas-Insulated Switchgear Type 8DQ1: Technical Data
switchgear type
8DQ1
Technical data
siemens-energy.com
Technical data GIS type 8DQ1
Rated switching impulse withstand voltage (250 / 2500 μs) - up to 1050 kV up to 1175 kV
Rated normal current busbar up to 6300 A up to 6300 A up to 6300 A
Rated normal current feeder up to 5000 A up to 5000 A up to 5000 A
Rated short-circuit breaking current (< 2 cycles) up to 80 kA up to 63 kA up to 63 kA
Leakage rate per year and gas compartment (type-tested) < 0.1 %
Bay height, depth (depending on bay arrangement) 3800 mm x 5800 mm 4800 mm x 10000 mm
Bay weight 11 t 21 t
Subject to changes and errors. The information given in this document only contains general descriptions
and/or performance features which may not always specifically reflect those described, or which may
undergo modification in the course of further development of the products. The requested performance
features are binding only when they are expressly agreed upon in the concluded contract.