PT. REKAYASA INDUSTRI – FUJI ELECTRIC

DCS I/O List

Document No : Origin Rev No. Contract No :

RD-I-PC-P00-2002 FH 3 15000105-OS-10103

PROJECT :
EPC CONTRACT FOR RANTAU DEDAP
GEOTHERMAL POWER PLANT PROJECT
OWNER : PT. SUPREME ENERGY RANTAU DEDAP (SERD)
LOCATION : SOUTH SUMATRA, INDONESIA

3 Issue for Construction 09-Aug-2021 S.Akiyama K.Tsuzuki K.Tsuzuki

2 Issue for Construction 24-Jan-2020 S.Akiyama K.Tsuzuki H.Nagaoka

1 Issue for Construction 08-Nov-2019 S.Akiyama K.Tsuzuki H.Nagaoka

0 Issue for Construction 27-Jun-2018 S.Akiyama K.Tsuzuki H.Nagaoka

B Issue for Review 25-Apr-2018 S.Akiyama K.Tsuzuki A.Hayashi

A Issue for Review 27-Dec-2018 S.Akiyama K.Tsuzuki H.Nagaoka

Rev Status Date Prepared Check Approved

Consortium of PT REKAYASA INDUSTRI and FUJI ELECTRIC


DCS I/O List

Document No : Origin Rev No. Contract No :

RD-I-PC-P00-2002 FH 3 15000105-OS-10103

Page 2/ 132
Consortium of PT REKAYASA INDUSTRI and FUJI ELECTRIC
TABLE OF CONTENTS

1. RULE FOR FILLING IN OF THE COLUMNS ・・・・・・・・・・・・ Page 4

2. DCS IO LIST FOR HARD WIRED

2-1. POWER PLANT FOR EACH UNIT AREA ・・・・・・・・・・・・ Page 7

2-2. POWER PLANT FOR COMMON AREA ・・・・・・・・・・・・ Page 30

2-3. SEPARATPR & WELLPAD-E AREA ・・・・・・・・・・・・ Page 40

2-4. WELLPAD-I AREA ・・・・・・・・・・・・ Page 49

2-5. WELLPAD-L AREA ・・・・・・・・・・・・ Page 52

2-6. WELLPAD-M AREA ・・・・・・・・・・・・ Page 55

2-7. WELLPAD-C AREA ・・・・・・・・・・・・ Page 58

2-8. WELLPAD-B AREA ・・・・・・・・・・・・ Page 60

3. DCS IO LIST FOR COMMUNICATION

3-1. POWER PLANT FOR EACH UNIT AREA ・・・・・・・・・・・・ Page 65

3-2. POWER PLANT FOR COMMON AREA ・・・・・・・・・・・・ Page 72

3-3. SEPARATPR & WELLPAD-E AREA ・・・・・・・・・・・・ Page 75

3-4. WELLPAD-I AREA ・・・・・・・・・・・・ Page 76

3-5. WELLPAD-L AREA ・・・・・・・・・・・・ Page 77

3-6. WELLPAD-M AREA ・・・・・・・・・・・・ Page 78

3-7. WELLPAD-C AREA ・・・・・・・・・・・・ Page 79

3-8. WELLPAD-B AREA ・・・・・・・・・・・・ Page 80

3-9. WELLPAD-N AREA ・・・・・・・・・・・・ Page 81

The internal revision is Rev.4 3 / 81


1. RULE FOR FILLING IN OF THE COLUMNS

APPLIED ILD or IBD


NC/NO DCS APPLICATION
VOLTAGE
No. Tag No. DESCRIPTION RANGE UNIT SIGNAL RAITING PULSE/ FROM TO DIAGRAM REMARKS
ON
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT

NOTE1 NOTE2 NOTE3 NOTE4 NOTE5 NOTE6 NOTE7 NOTE8 NOTE9 NOTE10 NOTE11 NOTE12

NOTE1 : SERIAL NO.

NOTE2 : POINT ID NO.


Point ID is numbered as per following naming convention
1, All Point ID has Prefix "*" or "RD00". If it has "*", put it "RD01" or "RD02". "RD01" for Unit1, "RD02" for Unit2.
2, System Code and Equipment Unit Code
2-1, Signal is originally generated from the Field instrument or equipment.
Follow the KKS No that is defined in "Instrument List for STG & Auxiliaries(RD-I-PC-PH01-2002)" or "Equipment list(RD-PRD01-ENG-CREG-2004)"
2-2, Signal is generated from the logic incorporated in the DCS
2-2-1, Signal goes to Field Instrument or equipment
Follow the KKS No of Field Instrument or equipment that is defined in "Instrument List for STG & Auxiliaries(RD-I-PC-PH01-2002)" or "Equipment list(RD-PRD01-ENG-CREG-2004)"
2-2-2, Signal goes to other cabinet
Follow the KKS No of To side cubicle KKS defined in "Equipment list(RD-PRD01-ENG-CREG-2004)"
2-3, Signal is generated from the logic incorporated in the other cabinet
Follow the KKS No of FROM side cubicle KKS defined in "Equipment list(RD-PRD01-ENG-CREG-2004)"
3, Component Code
XQ : Hard wired Analog Input
YJ : Hard wired Analog Output
XG : Hard wired Degital Input
YB : Hard wired Dgital Output
XN : Communication Analog Input
XP : Communication Degital Input
YP : Communication Degital Output
XT : Communication Pulse Input
4, Special case consideration
In the case of component code number(2 digit) will prospectively run short, equipment unit code An is incresed

NOTE3 : SERVICE OF SIGNAL

NOTE4 : ENGINEERING RANGE OF SIGNAL

NOTE5 : ENGINEERING UNIT OF SIGNAL (%, A, cosφ, degC, Hz, bar,barg, kg/cm2g, kV, mm, MVAR, Mvarh/P, MW, MWh/P, rpm, V, μm)

NOTE6 : INTERFACE METHOD


AII : 4-20mA ANALOG INPUT POWER IS SUPPLIED FROM DCS (DC24V)
AIX : 4-20mA ANALOG INPUT
AI : ANALOG INPUT
AOX : 4-20mA ANALOG OUTPUT
PI : PULSE INPUT
DI : DRY CONTACT DEGITAL INPUT (DC24V SUPPLY BY DCS)
DOH : DRY CONTACT DEGITAL OUTPUT (AC230V OR DC110V SUPPLIED BY EXTERNAL)
DOL : DRY CONTACT DEGITAL OUTPUT (DC24V SUPPLIED BY EXTERNAL)
DOW : WET CONTACT (DC110V FOR SOLENOID VALVE SUPPLIED BY DCS)
DO : DEGITAL OUTPUT
TC : THERMOCUPLE
RTD : RESISTANCE TEMPERATURE DITECTOR

NOTE7 : KIND OF SIGNAL (4-20mA,1-5V(1-****)),OHM,mV,MODBUS)


4-20mA : Used for AI,AO control siganl
Mv : Used for Thermocouple siganl
Ω : Used for RTD siganl
Hz : PULSE FREQUENCY
TCP/IP : Modbus TCP/IP
RS485 : Modbus RTU with RS485 physical layer
IEC61870 : IEC60870-5-104
IEC61850 : IEC61850
FO CABLE : Fibre Optic Cable
HART : Data is collected through HART Protocol

NOTE8 : ELEMENT OF SIGNAL (NO,NC)


NO : For DI. Once contact is turned ON upper side state desc is lighted
NO PULSE : For DO. If upper side state desc is pushed , contact is turned ON
NC : For DI. Once contact is turned ON lower side state desc is lighted
NC PULSE : For DO. If upper side state desc is pushed , contact is turned OFF

NOTE9 : RATING OF SIGNAL

4 / 81
1. RULE FOR FILLING IN OF THE COLUMNS

APPLIED ILD or IBD


NC/NO DCS APPLICATION
VOLTAGE
No. Tag No. DESCRIPTION RANGE UNIT SIGNAL RAITING PULSE/ FROM TO DIAGRAM REMARKS
ON
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT

NOTE1 NOTE2 NOTE3 NOTE4 NOTE5 NOTE6 NOTE7 NOTE8 NOTE9 NOTE10 NOTE11 NOTE12

NOTE10: LOCATION OF FROM/TO OF SIGNAL


TPR : TURBINE PROTECTION RELAY CUBICLE
TGR : TURBINE GENERATOR REGURATOR VUBICLE
GPR : GENERATOR AND TRANSFORMER PROTECTION RELAY CUBICLE
DMS : DC MOTOR STARTING CUBICLE
DCS : Distributed Control System
SYN : SYNCHRONIZER PANEL
F : FIELD
DCSSEP : DCS CONTROL CABINET FOR SEPARATOR AND WELLPAD-E
DCSRDI : REMOTE I/O CABINET FOR WELLPAD RD-I
DCSRDL : REMOTE I/O CABINET FOR WELLPAD RD-L
DCSRDM : REMOTE I/O CABINET FOR WELLPAD RD-M
DCSRDC : REMOTE I/O CABINET FOR WELLPAD RD-C
RIORDB : REMOTE I/O CABINET FOR WELLPAD RD-B
MCCRIO(LV) : REMOTE I/O CABINET FOR LV MCC
MCCRIO(MV) : REMOTE I/O CABINET FOR MV MCC
CTRIO : REMOTE I/O CABINET FOR COOLING TOWER
LINEBAY1 : LINE BAY1
LINEBAY2 : LINE BAY2
TRAFOBAY1 : TRANSFORMER BAY1
TRAFOBAY2 : TRANSFORMER BAY2
COUPLERBAY : COUPLER BAY
GSUT : GENERATOR STEP UP TRANSFORMER
UAT : 11kV/6.3kV Unit Auxiliary Transformer
UST : 6.3kV/400V Unit Service Transformer
SGST : 400V/6.3kV SGS Transformer
SST : 6.3kV/0,4kV Common Station Service Transformer
LT : LIGHTING TRANSFORMER
STELT : COMMON STATION ESSENTIAL SERVICE LIGHTING TRANSFORMER
STNELT : COMMON STATION NON ESSENTIAL SERVICE LIGHTING TRANSFORMER
ACCBT : 6.3kV/0,4kV Accomodation Block Transformer
RD-ITR : 6.3kV/400V WELLPAD-I TRANSFORMER
RD-LTR : 6.3kV/400V WELLPAD-L TRANSFORMER
RD-MTR : 6.3kV/400V WELLPAD-M TRANSFORMER
RD-CTR : 6.3kV/400V WELLPAD-C TRANSFORMER
RD-BTR : 6.3kV/400V WELLPAD-B TRANSFORMER
RD-SSTR : 6.3kV/400V Separator Station Transformer
LVESWB : 400V LV ESSENTIAL SWITCHBOARD
STLVESWB : 400V COMMON STATION LV ESSENTIAL SWITCHBOARD
LVNESWB : 400V LV NON ESSENTIAL SWITCHBOARD
STLVNESWB : 400V COMMON STATION LV NON ESSENTIAL SWITCHBOARD
MVSWG : 6.3kV MV SWITCHGEAR
STMVSWG : 6.3kV COMMON STATION MV SWITCHGEAR
SGSSMVSWG : 6.3kV SGS SS MV SWITCHGEAR
LVSWG : 400V LV SWITCHGEAR
STLVSWG : 400V COMMON STATION LV SWITCHGEAR
RCPEDG : REMOTE CONTROL PANEL FOR EMERGENCY DIESEL GENERATOR
GSWG : GENERATOR SWITHGEAR UNIT
DCMDB : 110V DC MAIN DISTRIBUTION BOAD
UPSMDB : 230V AC UPS MAIN DISTRIBUTION BOARD
EDG : EMERGENCY DIESEL GENERATOR
HVAC : HEATING, VENTILATION, AIR-CONDITIONING SYSTEMS
VSD : VARIABLE SPEED DRIVE
RD-ELVPDB : LV POWER DISTRIBUTION BOARD FOR WELLPAD-E
RD-ILVPDB : LV POWER DISTRIBUTION BOARD FOR WELLPAD-I
RD-LLVPDB : LV POWER DISTRIBUTION BOARD FOR WELLPAD-L
RD-MLVPDB : LV POWER DISTRIBUTION BOARD FOR WELLPAD-M
RD-CLVPDB : LV POWER DISTRIBUTION BOARD FOR WELLPAD-C
RD-BLVPDB : LV POWER DISTRIBUTION BOARD FOR WELLPAD-B
RD-SSLVPDB : LV Power Distribution Board for Separator Station
RD-IRMU : RD-I RING MAIN UNIT
RD-LRMU : RD-L RING MAIN UNIT
RD-MRMU : RD-M RING MAIN UNIT
RD-CRMU : RD-C RING MAIN UNIT
RD-BRMU : RD-B RING MAIN UNIT
RD-ERMU : RD-E Ring Main Unit
BCA : 110V DC BATTERY CHARGER (A)
BCARD-SS : 110V DC BATTERY CHARGER (A) WELLPAD SEPARATOR STATION AND WELLPAD-E
BCARD-I : 110V DC BATTERY CHARGER (A) WELLPAD SEPARATOR STATION AND WELLPAD-I
BCARD-L : 110V DC BATTERY CHARGER (A) WELLPAD SEPARATOR STATION AND WELLPAD-L
BCARD-M : 110V DC BATTERY CHARGER (A) WELLPAD SEPARATOR STATION AND WELLPAD-M
BCARD-C : 110V DC BATTERY CHARGER (A) WELLPAD SEPARATOR STATION AND WELLPAD-C
BCARD-B : 110V DC BATTERY CHARGER (A) WELLPAD SEPARATOR STATION AND WELLPAD-B
BCB : 110V DC BATTERY CHARGER (B)
DCBAT(A) : 110V DC SYSTEM BATTERY (A)
DCBAT(B) : 110V DC SYSTEM BATTERY (B)
UPS(A) : UNINTERRUPTIBLE POWER SUPPLY (A)
UPS(B) : UNINTERRUPTIBLE POWER SUPPLY (B)
UPSBAT(A) : UPS Battery (A)
UPSBAT(B) : UPS Battery (B)

5 / 81
1. RULE FOR FILLING IN OF THE COLUMNS

APPLIED ILD or IBD


NC/NO DCS APPLICATION
VOLTAGE
No. Tag No. DESCRIPTION RANGE UNIT SIGNAL RAITING PULSE/ FROM TO DIAGRAM REMARKS
ON
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT

NOTE1 NOTE2 NOTE3 NOTE4 NOTE5 NOTE6 NOTE7 NOTE8 NOTE9 NOTE10 NOTE11 NOTE12

NOTE11 : FUNCTIONS
IND : INDICATION
ANN : ANNUNCIATION
CONT : CONTROL
ATS : AUTOMATIC TURBINE START UP
LOG : DATA LOGGING FUNCTION INCLUDING DATA STORAGE
SOE : SEQUENCE OF EVENT

NOTE12: REFERENCE DRAWING NO. OF SIGNAL


Drawing Title Project Control Dwg No.
GT Interlock Block Diagram for Generator & Transformer Protection RD-I-CI-PH0-2004
Control and Interlock Block Diagram for Turbine & Auxiliaries RD-I-CI-PH0-2003
T Related Turbine and Turbine Auxiliaries
S Related Steam Line Auxiliaries
W Related Water Line Auxiliary
P Related Steam Separation System
A Related Acid Dosing System
Instrumentation Diagram for STG & Auxiliaries RD-I-CI-PH0-2001
C Related Control Loop
R Related Field Meaurment
F ATS FLOW CHART RD-I-CI-PH0-2005
STG EHG & AVR Block Diagram(TGR) RD-I-CI-PH0-2002
TG Related EHG & AVR
TT Related AVT (Automatic Valve Test)

6 / 81
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL
HH/H/ NWL+900 NWL+150 NWL-150 NWL-1150
1 * MAG 10 CL 001 XQ 01 Condenser Level (A) 19 Condenser Level (A) 0-2150 mm AIX ---- ---- ---- 1% *TPR NA *DCS C01 ○ ○ ---- ○ ----
L/LL (P1) (P2) (P2) (P1)
HH/H/ NWL+900 NWL+150 NWL-150 NWL-1150
2 * MAG 10 CL 002 XQ 01 Condenser Level (B) 19 Condenser Level (B) 0-2150 mm AIX ---- ---- ---- 1% *TPR NA *DCS C01 ○ ○ ---- ○ ----
L/LL (P1) (P2) (P2) (P1)
HH/H/ NWL+900 NWL+150 NWL-150 NWL-1150
3 * MAG 10 CL 003 XQ 01 Condenser Level (C) 19 Condenser Level (C) 0-2150 mm AIX ---- ---- ---- 1% *TPR NA *DCS C01 ○ ○ ---- ○ ----
L/LL (P1) (P2) (P2) (P1)

4 * LCA 31 FH 101 YJ 01 Condenser Level Control Valve (A) MV 30 Condenser Lvl Ctl Valve (A) MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C02 ---- ---- ○ ---- ○ ----

5 * LCA 31 CG 101 XQ 01 Condenser Level Control Valve (A) Position 31 Condenser Lvl Ctl Valve (A) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C02 ○ ---- ○ ---- ○ ----

6 * LCA 32 FH 101 YJ 01 Condenser Level Control Valve (B) MV 30 Condenser Lvl Ctl Valve (B) MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C02 ○ ---- ○ ---- ○ ----

7 * LCA 32 CG 101 XQ 01 Condenser Level Control Valve (B) Position 31 Condenser Lvl Ctl Valve (B) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C02 ○ ---- ○ ---- ○ ----

8 * LCA 81 FH 001 YJ 01 Main Cooling Water Inlet Valve (A) MV 22 MCW Inlet Valve (A) MV 0-100 % AOX ---- ---- ---- ---- *DCS NA F C08 ---- ---- ○ ---- ○ ----

9 * LCA 81 CG 001 XQ 01 Main Cooling Water Inlet Valve (A) Position 23 MCW Inlet Valve (A) Pos 0-100 % AII ---- ---- ---- ---- F NA *DCS C08 ○ ---- ○ ---- ○ ----

10 * LCA 82 FH 001 YJ 01 Main Cooling Water Inlet Valve (B) MV 22 MCW Inlet Valve (B) MV 0-100 % AOX ---- ---- ---- ---- *DCS NA F C08 ---- ---- ○ ---- ○ ----

11 * LCA 82 CG 001 XQ 01 Main Cooling Water Inlet Valve (B) Position 23 MCW Inlet Valve (B) Pos 0-100 % AII ---- ---- ---- ---- F NA *DCS C08 ○ ---- ○ ---- ○ ----

HH/H/ BTM+300 80
12 * PAD 11 CL 001 XQ 01 Cooling Tower Basin Level (Up Stream of Screen) 32 CT Basin Lvl (Up Strm of Screen) 0-5000 mm AII ---- ---- ---- 1% F NA *CTRIO C09 ○ ○ ---- ○ ----
L/LL (P2) (P1)
BTM+6300 BTM+4300
13 * PAD 12 CL 001 XQ 01 Cooling Tower Basin Level (Down Stream of Screen) 32 CT Basin Lvl (Dn Strm of Screen) 0-5000 mm AII ---- ---- ---- 1% F NA *CTRIO C09 ○ L ○ ---- ○ ----
(P2) (P1)
0.02
14 * MAW 10 CP 001 XQ 01 Grand Steam Supply Pressure 27 Grand Steam Supply Pressure -0.1-+0.2 barg AII ---- ---- ---- 1% F NA *DCS C11 ○ L ○ ---- ○ ----
(P2)

15 * MAW 10 FH 090 YJ 01 Grand Steam Supply Pressure Control Valve MV 30 Grand Stm Sup Press Ctl Vlv MV 0-100 % AOX ---- ---- ---- ---- *DCS NA F C11 ○ ---- ○ ---- ○ ----

16 * MAW 10 CG 090 XQ 01 Grand Steam Supply Pressure Control Valve Position 31 Grand Stm Sup Press Ctl Vlv Pos 0-100 % AII ---- ---- ---- ---- F NA *DCS C11 ○ ---- ○ ---- ○ ----

50 35
17 * MAV 43 CT 001 XQ 01 Lube Oil Supply Temperature 27 Lube Oil Supply Temperature 0-100 degC RTD ---- ---- ---- 1% F NA *DCS C13 ○ H/L ○ ---- ○ ----
(P2) (P2)

18 * MAV 43 FH 106 YJ 01 Lube Oil Supply Temperature Control Valve MV 31 Lube Oil Supply Temp Ctl Vlv MV 0-100 % AOX ---- ---- ---- ---- *DCS NA F C13 ○ ---- ○ ---- ○ ----

19 * MAV 43 CG 106 XQ 01 Lube Oil Supply Temperature Control Valve Position 32 Lube Oil Supply Temp Ctl Vlv Pos 0-100 % AII ---- ---- ---- ---- F NA *DCS C13 ---- ---- ○ ---- ○ ----

20 * LCE 40 CF 001 XQ 01 Turbine Wash Water Flow 24 Turbine Wash Water Flow 0-5 kg/s AII ---- ---- ---- ---- F U0-ARS *DCS C15 ○ ---- ○ ---- ○ ----

21 * LCE 40 FH 101 YJ 01 Turbine Wash Water Control Valve MV 27 Turbine WW Control Valve MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C15 ---- ---- ○ ---- ○ ----

22 * LCE 40 CG 101 XQ 01 Turbine Wash Water Control Valve Position 28 Turbine WW Control Valve Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C15 ○ ---- ○ ---- ○ ----

23 * LBA 71 FH 101 YJ 01 HP Scrubber Outlet HP Steam Vent Valve (A) MV 26 HP Steam Vent Valve (A) MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C36 ---- ---- ○ ---- ○ ----

24 * LBA 71 CG 101 XQ 01 HP Scrubber Outlet HP Steam Vent Valve (A) Position 27 HP Steam Vent Valve (A) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C36 ○ ---- ○ ---- ○ ----

25 * LBA 71 AA 101 XG 01 HP Scrubber Outlet HP Steam Vent Valve (A) Manual Overide Active 31 HP Steam Vent Valve (A) Man Ord REMOTE/LOCAL ---- DI ---- ---- NO ---- F U0-ARS *DCS C36 ○ ---- ---- ---- ○ ----

26 * LBA 71 FH 102 YJ 01 HP Scrubber Outlet HP Steam Vent Valve (B) MV 26 HP Steam Vent Valve (B) MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C36 ---- ---- ○ ---- ○ ----

27 * LBA 71 CG 102 XQ 01 HP Scrubber Outlet HP Steam Vent Valve (B) Position 27 HP Steam Vent Valve (B) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C36 ○ ---- ○ ---- ○ ----

28 * LBA 71 AA 102 XG 01 HP Scrubber Outlet HP Steam Vent Valve (B) Manual Overide Active 31 HP Steam Vent Valve (B) Man Ord REMOTE/LOCAL ---- DI ---- ---- NO ---- F U0-ARS *DCS C36 ○ ---- ---- ---- ○ ----

29 * LBA 91 FH 101 YJ 01 LP Scrubber Outlet LP Steam Vent Valve (A) MV 26 LP Steam Vent Valve (A) MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C38 ---- ---- ○ ---- ○ ----

30 * LBA 91 CG 101 XQ 01 LP Scrubber Outlet LP Steam Vent Valve (A) Position 27 LP Steam Vent Valve (A) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C38 ○ ---- ○ ---- ○ ----

31 * LBA 91 AA 101 XG 01 LP Scrubber Outlet LP Steam Vent Valve (A) Manual Override Active 31 LP Steam Vent Valve (A) Man Ord REMOTE/LOCAL ---- DI ---- ---- NO ---- F U0-ARS *DCS C36 ○ ---- ---- ---- ○ ----

32 * LBA 91 FH 102 YJ 01 LP Scrubber Outlet LP Steam Vent Valve (B) MV 26 LP Steam Vent Valve (B) MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C38 ---- ---- ○ ---- ○ ----

33 * LBA 91 CG 102 XQ 01 LP Scrubber Outlet LP Steam Vent Valve (B) Position 27 LP Steam Vent Valve (B) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C38 ○ ---- ○ ---- ○ ----

34 * LBA 91 AA 102 XG 01 ST SPARE FEEDER (52HD-0) CB CLOSE COMMAND 31 LP Steam Vent Valve (B) Man Ord REMOTE/LOCAL ---- DI ---- ---- NO ---- F U0-ARS *DCS C38 ○ ---- ---- ---- ○ ----

35 * LBF 10 FH 101 YJ 01 HP to LP Let Down Control Valve (A) MV 25 Let Down Ctl Valve (A) MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C40 ---- ---- ○ ---- ○ ----

36 * LBF 10 CG 101 XQ 01 HP to LP Let Down Control Valve (A) Position 26 Let Down Ctl Valve (A) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C40 ○ ---- ---- ---- ○ ----

38 * LBF 10 FH 102 YJ 01 HP to LP Let Down Control Valve (B) MV 25 Let Down Ctl Valve (B) MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C40 ---- ---- ○ ---- ○ ----

39 * LBF 10 CG 102 XQ 01 HP to LP Let Down Control Valve (B) Position 26 Let Down Ctl Valve (B) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C40 ○ ---- ---- ---- ○ ----

41 * LCT 11 CG 101 XQ 01 HP Scrubber EDV Position 24 HP Scrubber EDV Position 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C32 ---- ---- ○ ---- ○ ----

42 * LCT 11 FH 101 YJ 01 HP Scrubber EDV MV 18 HP Scrubber EDV MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C32 ○ ---- ○ ---- ○ ----

43 * LCT 21 CG 101 XQ 01 LP Scrubber EDV Position 24 LP Scrubber EDV Position 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C32 ---- ---- ○ ---- ○ ----

44 * LCT 21 FH 101 YJ 01 LP Scrubber EDV MV 18 LP Scrubber EDV MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C32 ○ ---- ○ ---- ○ ----

45 * LBA 71 CF 003 XQ 01 HP Main Steam Flow 19 HP Main Steam Flow 0-100 kg/s AII ---- ---- ---- ---- F U0-ARS *DCS R01 ○ ---- ○ ---- ○ ----

46 * LBA 91 CF 003 XQ 01 LP Main Steam Flow 19 LP Main Steam Flow 0-50 kg/s AII ---- ---- ---- ---- F U0-ARS *DCS R01 ○ ---- ○ ---- ○ ----

47 * LBG 10 CF 004 XQ 01 GRS Motive Steam Flow 22 GRS Motive Steam Flow 0-10 kg/s AII ---- ---- ---- ---- F U0-ARS *DCS R02 ○ ---- ---- ---- ○ ----

48 * MAJ 60 CF 001 XQ 01 NCG Discharge Flow 18 NCG Discharge Flow 0-5 kg/s AII ---- ---- ---- ---- F U0-ARS *DCS R02 ○ ---- ---- ---- ○ ----

49 * PGB 51 CF 081 XG 01 Vacuum Pump (A) Seal Water Flow (L) 26 VP (A) Seal Water Flow (L) NORMAL/LOW ---- DI ---- ---- NC ---- F U0-ARS *DCS R05 ○ ---- ○ ---- ○ ----

50 * PGB 52 CF 081 XG 01 Vacuum Pump (B) Seal Water Flow (L) 26 VP (B) Seal Water Flow (L) NORMAL/LOW ---- DI ---- ---- NC ---- F U0-ARS *DCS R05 ○ ---- ○ ---- ○ ----

51 * PGB 61 CF 081 XG 01 Hotwell Pump (A) Mechanical Seal Water Flow (L) 32 HWP (A) Mech Seal Water Flow (L) NORMAL/LOW ---- DI ---- ---- NC ---- F U0-ARS *DCS R05 ○ ---- ○ ---- ○ ----

52 * PGB 62 CF 081 XG 01 Hotwell Pump (B) Mechanical Seal Water Flow (L) 32 HWP (B) Mech Seal Water Flow (L) NORMAL/LOW ---- DI ---- ---- NC ---- F U0-ARS *DCS R05 ○ ---- ○ ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL
6.6 4.8
53 * LBA 71 CP 002 XQ 01 HP Scrubber Outlet Steam Pressure (A) 32 HP Scrubber Outlet Stm Press (A) 0-20 barg AIX ---- ---- ---- 0.5% *TGR NA *DCS R10 ○ H/L ○ ---- ○ ----
(P2) (P2)
6.6 4.8
54 * LBA 71 CP 003 XQ 01 HP Scrubber Outlet Steam Pressure (B) 32 HP Scrubber Outlet Stm Press (B) 0-20 barg AIX ---- ---- ---- 0.5% *TGR NA *DCS R10 ○ H/L ○ ---- ○ ----
(P2) (P2)
6.6 4.8
55 * LBA 71 CP 004 XQ 01 HP Scrubber Outlet Steam Pressure (C) 32 HP Scrubber Outlet Stm Press (C) 0-20 barg AIX ---- ---- ---- 0.5% *TGR NA *DCS R10 ○ H/L ○ ---- ○ ----
(P2) (P2)
1.74 0.62
56 * LBA 91 CP 002 XQ 01 LP Scrubber Outlet Steam Pressure (A) 32 LP Scrubber Outlet Stm Press (A) 0-5 barg AIX ---- ---- ---- 0.5% *TGR NA *DCS R11 ○ H/L ○ ---- ○ ----
(P2) (P2)
1.74 0.62
57 * LBA 91 CP 003 XQ 01 LP Scrubber Outlet Steam Pressure (B) 32 LP Scrubber Outlet Stm Press (B) 0-5 barg AIX ---- ---- ---- 0.5% *TGR NA *DCS R11 ○ H/L ○ ---- ○ ----
(P2) (P2)
1.74 0.62
58 * LBA 91 CP 004 XQ 01 LP Scrubber Outlet Steam Pressure (C) 32 LP Scrubber Outlet Stm Press (C) 0-5 barg AIX ---- ---- ---- 0.5% *TGR NA *DCS R11 ○ H/L ○ ---- ○ ----
(P2) (P2)

59 * LBA 71 CP 005 XQ 01 HP Venturi Steam Pressure 26 HP Venturi Steam Pressure 0-10 barg AII ---- ---- ---- ---- F U0-ARS *DCS R13 ○ ---- ---- ---- ○ ----

60 * LBA 91 CP 005 XQ 01 LP Venturi Steam Pressure 26 LP Venturi Steam Pressure 0-5 barg AII ---- ---- ---- ---- F U0-ARS *DCS R13 ○ ---- ---- ---- ○ ----

7.24 6.24
61 * LBA 71 CP 006 XQ 01 HP Turbine Inlet Steam Pressure 32 HP Turbine Inlet Steam Pressure 0-10 barg AII ---- ---- ---- 1% F U0-ARS *DCS R14 ○ HH/H ---- ---- ○ ----
(P1) (P2)
1.96 1.62
62 * LBA 91 CP 006 XQ 01 LP Turbine Inlet Steam Pressure 32 LP Turbine Inlet Steam Pressure 0-5 barg AII ---- ---- ---- 1% F U0-ARS *DCS R14 ○ HH/H ---- ---- ○ ---- Rev.4; Setting value updated 4
(P2) (P2)
0.5
63 * LBA 72 CP 001 XQ 01 HP Steam Strainer (L) Differential Pressure 32 HP Steam Strainer (L) Diff Press 0-1 bar AII ---- ---- ---- 1% F U0-ARS *DCS R17 ○ H ---- ---- ○ ----
(P2)
0.5
64 * LBA 73 CP 001 XQ 01 HP Steam Strainer (R) Differential Pressure 32 HP Steam Strainer (R) Diff Press 0-1 bar AII ---- ---- ---- 1% F U0-ARS *DCS R17 ○ H ---- ---- ○ ----
(P2)
0.5
65 * LBA 92 CP 001 XQ 01 LP Steam Strainer (L) Differential Pressure 32 LP Steam Strainer (L) Diff Press 0-1 bar AII ---- ---- ---- 1% F U0-ARS *DCS R17 ○ H ---- ---- ○ ----
(P2)
0.5
66 * LBA 93 CP 001 XQ 01 LP Steam Strainer (R) Differential Pressure 32 LP Steam Strainer (R) Diff Press 0-1 bar AII ---- ---- ---- 1% F U0-ARS *DCS R17 ○ H ---- ---- ○ ----
(P2)

67 * MAA 10 CP 001 XQ 01 Turbine HP Chamber Pressure 28 Turbine HP Chamber Pressure 0-15 barg AII ---- ---- ---- ---- F U0-ARS *DCS R18 ○ ---- ---- ---- ○ ----

68 * MAA 10 CP 002 XQ 01 Turbine LP Chamber Pressure 28 Turbine LP Chamber Pressure -1-3 barg AIX ---- ---- ---- ---- *TPR NA *DCS R18 ○ ---- ○ ---- ○ ----

curve curve
69 * MAG 10 CP 001 XQ 01 Turbine Exhaust Pressure (A) 28 Turbine Exhaust Pressure (A) 0-1.5 bara AIX ---- ---- ---- 1% *TPR NA *DCS R19 ○ H ○ ---- ○ ----
(P1) (P2)
curve curve
70 * MAG 10 CP 002 XQ 01 Turbine Exhaust Pressure (B) 28 Turbine Exhaust Pressure (B) 0-1.5 bara AIX ---- ---- ---- 1% *TPR NA *DCS R19 ○ H ○ ---- ○ ----
(P1) (P2)
curve curve
71 * MAG 10 CP 003 XQ 01 Turbine Exhaust Pressure (C) 28 Turbine Exhaust Pressure (C) 0-1.5 bara AIX ---- ---- ---- 1% *TPR NA *DCS R19 ○ H ○ ---- ○ ----
(P1) (P2)
see
72 * LBG 31 CP 001 XQ 01 Ejector (A) Steam Inlet Pressure 29 Ejector (A) Steam Inlet Press 0-15 barg AII ---- ---- ---- 1% F U0-ARS *DCS R21 ○ H ---- ---- ○ ----
Curve
see
73 * LBG 32 CP 001 XQ 01 Ejector (B) Steam Inlet Pressure 29 Ejector (B) Steam Inlet Press 0-15 barg AII ---- ---- ---- 1% F U0-ARS *DCS R21 ○ H ---- ---- ○ ----
Curve
see
74 * LBG 33 CP 001 XQ 01 Ejector (C) Steam Inlet Pressure 29 Ejector (C) Steam Inlet Press 0-15 barg AII ---- ---- ---- 1% F U0-ARS *DCS R21 ○ H ---- ---- ○ ----
Curve
0.9
75 * MAJ 40 CP 001 XQ 01 Intercondenser NCG Outlet Pressure 31 Intercondenser NCG Outlet Press -1-+1 barg AII ---- ---- ---- 1% F U0-ARS *DCS R21 ○ L ○ ---- ○ ----
(P1)

76 * PGB 26 CP 001 XQ 01 Intercondenser Cooling Water Inlet Pressure 29 Intercondenser CW Inlet Press 0-5 barg AII ---- ---- ---- ---- F U0-ARS *DCS R21 ○ ---- ---- ---- ○ ----

77 * PGB 26 CP 002 XQ 01 Intercondenser Cooling Water Inlet Pressure 29 Intercondenser CW Inlet Press 0-5 barg AII ---- ---- ---- ---- F U0-ARS *DCS R21 ○ ---- ---- ---- ○ ----

772 * MAJ 11 CP 001 XQ 01 Condenser NCG Outlet Pressure (A) 28 Cond NCG Outlet Pressure (A) 0-1.5 barg AII ---- ---- ---- ---- F NA *DCS R22 ○ ---- ---- ---- ○ ----

773 * MAJ 12 CP 001 XQ 01 Condenser NCG Outlet Pressure (B) 28 Cond NCG Outlet Pressure (B) 0-1.5 barg AII ---- ---- ---- ---- F NA *DCS R22 ○ ---- ---- ---- ○ ----

1.6
78 * PGB 11 CP 001 XQ 01 Auxiliary Cooling Water Supply Pressure 19 ACW Supply Pressure 0-6 barg AII ---- ---- ---- 1% F U0-ARS *DCS R22 ○ L ○ ---- ○ ----
(P2)

79 * LCA 21 CP 001 XQ 01 Hotwell Pump (A) Suction Pressure 24 HWP (A) Suction Pressure -1-1 barg AII ---- ---- ---- ---- F U0-ARS *DCS R23 ○ ---- ○ ---- ○ ----

80 * LCA 22 CP 001 XQ 01 Hotwell Pump (B) Suction Pressure 24 HWP (B) Suction Pressure -1-1 barg AII ---- ---- ---- ---- F U0-ARS *DCS R23 ○ ---- ○ ---- ○ ----

81 * LCA 21 CP 002 XQ 01 Hotwell Pump (A) Discharge Pressure 26 HWP (A) Discharge Pressure 0-6 barg AII ---- ---- ---- ---- F U0-ARS *DCS R23 ○ ---- ○ ---- ○ ----

82 * LCA 22 CP 002 XQ 01 Hotwell Pump (B) Discharge Pressure 26 HWP (B) Discharge Pressure 0-6 barg AII ---- ---- ---- ---- F U0-ARS *DCS R23 ○ ---- ○ ---- ○ ----

1.8
83 * MAV 46 CP 001 XQ 01 Lube Oile Supply Pressure (A) 29 Lube Oile Supply Pressure (A) 0-6 barg AIX ---- ---- ---- 1% *TPR NA *DCS R31 ○ H/L ○ ---- ○ ----
(P1)
1.8
84 * MAV 46 CP 002 XQ 01 Lube Oile Supply Pressure (B) 29 Lube Oile Supply Pressure (B) 0-6 barg AIX ---- ---- ---- 1% *TPR NA *DCS R31 ○ H/L ○ ---- ○ ----
(P1)
1.8
85 * MAV 46 CP 003 XQ 01 Lube Oile Supply Pressure (C) 29 Lube Oile Supply Pressure (C) 0-6 barg AIX ---- ---- ---- 1% *TPR NA *DCS R31 ○ H/L ○ ---- ○ ----
(P1)
H
86 * MAV 44 CP 081 XG 01 Lube Oil Filter Differential Pressure (H) 30 Lube Oil Filter Diff Press (H) NORMAL/HIGH ---- DI ---- ---- NC ---- F NA *DCS R32 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
5.0
87 * MAV 21 CP 001 XQ 01 Main Oil Pump (A) Discharge Pressure 26 MOP (A) Discharge Pressure 0-10 barg AIX ---- ---- ---- 1% *TPR NA *DCS R32 ○ L ---- ---- ○ ----
(P1)
5.0
88 * MAV 22 CP 001 XQ 01 Main Oil Pump (B) Discharge Pressure 25 MOP(B) Discharge Pressure 0-10 barg AIX ---- ---- ---- 1% *TPR NA *DCS R32 ○ L ---- ---- ○ ----
(P1)
H
89 * MAX 21 CP 081 XG 01 Line Filter (A) Differential Pressure 16 COP(A) Filter dP NORMAL/HIGH ---- DI ---- ---- NC ---- F NA *DCS R37 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
H
90 * MAX 22 CP 081 XG 01 Line Filter (B) Differential Pressure 16 COP(B) Filter dP NORMAL/HIGH ---- DI ---- ---- NC ---- F NA *DCS R37 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
H
91 * MAX 23 CP 081 XG 01 Polishing Filter Differential Pressure 19 Polishing Filter dP NORMAL/HIGH ---- DI ---- ---- NC ---- F NA *DCS R37 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
L
92 * MAX 30 CP 081 XG 01 Control Oil Pump Discharge Pressure 23 COP Discharge Pressure NORMAL/LOW ---- DI ---- ---- NC ---- F NA *DCS R37 ○ ○ ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
120
93 * MAX 30 CP 001 XQ 01 Control Oil Supply Pressure 27 Control Oil Supply Pressure 0-250 barg AII ---- ---- ---- 1% F NA *DCS R37 ○ L ○ ---- ○ ---- Rev.4 Range is updated 4
(P2)

94 * MAA 11 CP 101 XQ 01 HP SV(L) Cylinder Pressure (For Maintenance) 32 HP SV(L) Cyldr Press (For Maint) 0-400 barg AIX ---- ---- ---- ---- *TPR NA *DCS R38 ○ ---- ---- ---- ○ ----

95 * MAA 11 CP 102 XQ 01 HP CV(L) Cylinder Pressure (For Maintenance) 32 HP CV(L) Cyldr Press (For Maint) 0-400 barg AIX ---- ---- ---- ---- *TPR NA *DCS R38 ○ ---- ---- ---- ○ ----

96 * MAA 12 CP 101 XQ 01 HP SV(R) Cylinder Pressure (For Maintenance) 32 HP SV(R) Cyldr Press (For Maint) 0-400 barg AIX ---- ---- ---- ---- *TPR NA *DCS R38 ○ ---- ---- ---- ○ ----

97 * MAA 12 CP 102 XQ 01 HP CV(R) Cylinder Pressure (For Maintenance) 32 HP CV(R) Cyldr Press (For Maint) 0-400 barg AIX ---- ---- ---- ---- *TPR NA *DCS R38 ○ ---- ---- ---- ○ ----

98 * MAA 31 CP 101 XQ 01 LP SV(L) Cylinder Pressure (For Maintenance) 32 LP SV(L) Cyldr Press (For Maint) 0-400 barg AIX ---- ---- ---- ---- *TPR NA *DCS R39 ○ ---- ---- ---- ○ ----

99 * MAA 31 CP 102 XQ 01 LP CV(L) Cylinder Pressure (For Maintenance) 32 LP CV(L) Cyldr Press (For Maint) 0-400 barg AIX ---- ---- ---- ---- *TPR NA *DCS R39 ○ ---- ---- ---- ○ ----

100 * MAA 32 CP 101 XQ 01 LP SV(R) Cylinder Pressure (For Maintenance) 32 LP SV(R) Cyldr Press (For Maint) 0-400 barg AIX ---- ---- ---- ---- *TPR NA *DCS R39 ○ ---- ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL

101 * MAA 32 CP 102 XQ 01 LP CV(R) Cylinder Pressure (For Maintenance) 32 LP CV(R) Cyldr Press (For Maint) 0-400 barg AIX ---- ---- ---- ---- *TPR NA *DCS R39 ○ ---- ---- ---- ○ ----

191 171
102 * LBA 71 CT 003 XQ 01 HP Turbine Inlet Steam Temperature 27 HP Turbine Inlet Steam Temp 0-200 degC TC ---- ---- ---- 1% F U0-ARS *DCS R42 ○ HH/H ---- ---- ○ ---- Rev.4; Setting value updated 4
(P1) (P2)
161 141
103 * LBA 91 CT 003 XQ 01 LP Turbine Inlet Steam Temperature 27 LP Turbine Inlet Steam Temp 0-150 degC TC ---- ---- ---- 1% F U0-ARS *DCS R42 ○ HH/H ---- ---- ○ ----
(P1) (P2)
110 90
104 * MAA 10 CT 001 XQ 01 Turbine Exhaust Temperature 27 Turbine Exhaust Temperature 0-150 degC TC ---- ---- ---- 1% F NA *DCS R42 ○ HH/H ---- ---- ○ ----
(P1) (P2)
155 140
105 * MAJ 41 CT 001 XQ 01 Vacuum Pump (A) Motor Winding (U) Temperature 29 VP (A) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R45 ○ HH/H ---- ---- ○ ----
(P1) (P2)
155 140
106 * MAJ 41 CT 002 XQ 01 Vacuum Pump (A) Motor Winding (V) Temperature 29 VP (A) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R45 ○ HH/H ---- ---- ○ ----
(P1) (P2)
155 140
107 * MAJ 41 CT 003 XQ 01 Vacuum Pump (A) Motor Winding (W) Temperature 29 VP (A) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R45 ○ HH/H ---- ---- ○ ----
(P1) (P2)
105 95
108 * MAJ 41 CT 004 XQ 01 Vacuum Pump (A) Motor Bearing (NDE) Temperature 31 VP (A) Motor Bearing (NDE) Temp 0-150 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R45 ○ HH/H ---- ---- ○ ----
(P1) (P2)
105 95
109 * MAJ 41 CT 005 XQ 01 Vacuum Pump (A) Motor Bearing (DE) Temperature 30 VP (A) Motor Bearing (DE) Temp 0-150 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R45 ○ HH/H ---- ---- ○ ----
(P1) (P2)
155 140
110 * MAJ 42 CT 001 XQ 01 Vacuum Pump (B) Motor Winding (U) Temperature 29 VP (B) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R46 ○ HH/H ---- ---- ○ ----
(P1) (P2)
155 140
111 * MAJ 42 CT 002 XQ 01 Vacuum Pump (B) Motor Winding (V) Temperature 29 VP (B) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R46 ○ HH/H ---- ---- ○ ----
(P1) (P2)
155 140
112 * MAJ 42 CT 003 XQ 01 Vacuum Pump (B) Motor Winding (W) Temperature 29 VP (B) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R46 ○ HH/H ---- ---- ○ ----
(P1) (P2)
105 95
113 * MAJ 42 CT 004 XQ 01 Vacuum Pump (B) Motor Bearing (NDE) Temperature 31 VP (B) Motor Bearing (NDE) Temp 0-150 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R46 ○ HH/H ---- ---- ○ ----
(P1) (P2)
105 95
114 * MAJ 42 CT 005 XQ 01 Vacuum Pump (B) Motor Bearing (DE) Temperature 30 VP (B) Motor Bearing (DE) Temp 0-150 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R46 ○ HH/H ---- ---- ○ ----
(P1) (P2)
23
115 * MAJ 41 CT 006 XQ 01 Seal Water Discharge Separator (A) Drain Temperature 32 Sl Water Discg Sep(A) Drain Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R47 ○ H ○ ---- ○ ----
(P2)
23
116 * MAJ 42 CT 006 XQ 01 Seal Water Discharge Separator (B) Drain Temperature 32 Sl Water Discg Sep(B) Drain Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R47 ○ H ○ ---- ○ ----
(P2)

117 * LCA 10 CT 001 XQ 01 Condenser Outlet Temperature 28 Condenser Outlet Tmeperature 0-100 degC RTD ---- ---- ---- ---- F U0-ARS *DCS R48 ○ ---- ---- ---- ○ ----

118 * LCA 31 CT 001 XQ 01 Hotwell Pump Discharge Temperature 31 Hotwell Pump Outlet Temperature 0-100 degC RTD ---- ---- ---- ---- F U0-ARS *DCS R48 ○ ---- ---- ---- ○ ----

119 * MAG 10 CT 001 XQ 01 Condenser Temperature 21 Condenser Temperature 0-100 degC RTD ---- ---- ---- ---- F NA *DCS R48 ○ ---- ---- ---- ○ ----

120 * LCA 70 CT 001 XQ 01 Main Cooling Warter Inlet Temperature 30 Main Cooling Warter Inlet Temp 0-100 degC RTD ---- ---- ---- ---- F U0-ARS *DCS R48 ○ ---- ---- ---- ○ ----

774 * MAJ 11 CT 001 XQ 01 Condenser NCG Outlet Temperature (A) 29 Condenser NCG Outlet Temp (A) 0-100 degC RTD ---- ---- ---- ---- F NA *DCS R48 ○ ---- ○ ---- ○ ----

775 * MAJ 12 CT 001 XQ 01 Condenser NCG Outlet Temeprature (B) 29 Condenser NCG Outlet Temp (B) 0-100 degC RTD ---- ---- ---- ---- F NA *DCS R48 ○ ---- ○ ---- ○ ----

782 * MAJ 20 CT 001 XQ 01 Condenser NCG Outlet Temperature 25 Condenser NCG Outlet Temp 0-8 degC RTD ---- ---- ---- ---- F NA *DCS R49 ○ ---- ---- ---- ○ ----

121 * MAJ 40 CT 001 XQ 01 Intercondenser Temperature-1 28 Intercondenser Temperature-1 0-100 degC RTD ---- ---- ---- ---- F U0-ARS *DCS R49 ○ ---- ---- ---- ○ ----

122 * MAJ 40 CT 002 XQ 01 Intercondenser Temperature-2 28 Intercondenser Temperature-2 0-100 degC RTD ---- ---- ---- ---- F U0-ARS *DCS R49 ○ ---- ---- ---- ○ ----

123 * MAJ 40 CT 003 XQ 01 Intercondenser Temperature-3 28 Intercondenser Temperature-3 0-100 degC RTD ---- ---- ---- ---- F U0-ARS *DCS R49 ○ ---- ---- ---- ○ ----

124 * MAJ 40 CT 004 XQ 01 Intercondenser Temperature-4 28 Intercondenser Temperature-4 0-100 degC RTD ---- ---- ---- ---- F U0-ARS *DCS R49 ○ ---- ---- ---- ○ ----

783 * MAJ 40 CT 005 XQ 01 Intercondenser NCG Outlet Temperature 29 IntercondenserNCG Outlet Temp 0-100 degC RTD ---- ---- ---- ---- F U0-ARS *DCS R49 ○ ---- ---- ---- ○ ----

155 140
125 * LCA 21 CT 004 XQ 01 Hotwell Pump (A) Motor Winding (U) Temperature 30 HWP (A) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R50 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
126 * LCA 21 CT 005 XQ 01 Hotwell Pump (A) Motor Winding (V) Temperature 30 HWP (A) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R50 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
127 * LCA 21 CT 006 XQ 01 Hotwell Pump (A) Motor Winding (W) Temperature 31 HWP (A) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R50 ○ HH/H ○ ---- ○ ----
(P1) (P2)
95 85
128 * LCA 21 CT 003 XQ 01 Hotwell Pump (A) Motor Thrust Bearing Temperature 32 HWP(A) Motor Thrust Bearing Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R50 ○ HH/H ○ ---- ○ ---- Rev.4 Deleted 4
(P1) (P2)
105 95
129 * LCA 21 CT 001 XQ 01 Hotwell Pump (A) Motor Bearing (NDE) Temperature 32 HWP (A) Motor Bearing (NDE) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R50 ○ HH/H ○ ---- ○ ----
(P1) (P2)
105 95
130 * LCA 21 CT 002 XQ 01 Hotwell Pump (A) Motor Bearing (DE) Temperature 31 HWP (A) Motor Bearing (DE) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R50 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
131 * LCA 22 CT 004 XQ 01 Hotwell Pump (B) Motor Winding (U) Temperature 31 HWP (B) Motor Winding (U) Tempe 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R51 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
132 * LCA 22 CT 005 XQ 01 Hotwell Pump (B) Motor Winding (V) Temperature 30 HWP (B) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R51 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
133 * LCA 22 CT 006 XQ 01 Hotwell Pump (B) Motor Winding (W) Temperature 31 HWP (B) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R51 ○ HH/H ○ ---- ○ ----
(P1) (P2)
95 85
134 * LCA 22 CT 003 XQ 01 Hotwell Pump (B) Motor Thrust Bearing Temperature 32 HWP(B) Motor Thrust Bearing Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R51 ○ HH/H ○ ---- ○ ---- Rev.4 Deleted 4
(P1) (P2)
105 95
135 * LCA 22 CT 001 XQ 01 Hotwell Pump (B) Motor Bearing (NDE) Temperature 32 HWP (B) Motor Bearing (NDE) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R51 ○ HH/H ○ ---- ○ ----
(P1) (P2)
105 95
136 * LCA 22 CT 002 XQ 01 Hotwell Pump (B) Motor Bearing (DE) Temperature 31 HWP (B) Motor Bearing (DE) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R51 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
137 * PAD 01 CT 001 XQ 01 Cooling Tower Fan (A) Motor Winding (U) Temperature 32 CT Fan(A) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R55 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
138 * PAD 01 CT 002 XQ 01 Cooling Tower Fan (A) Motor Winding (V) Temperature 32 CT Fan(A) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R55 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
139 * PAD 01 CT 003 XQ 01 Cooling Tower Fan (A) Motor Winding (W) Temperature 32 CT Fan(A) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R55 ○ HH/H ○ ---- ○ ----
(P1) (P2)
H
140 * PAD 01 CT 081 XG 01 Cooling Tower Fan (A) Gear Temperature 27 CT Fan(A) Gear Temperature NORMAL/HIGH ---- DI ---- ---- NC ---- F NA *CTRIO R55 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
155 140
141 * PAD 02 CT 001 XQ 01 Cooling Tower Fan (B) Motor Winding (U) Temperature 32 CT Fan(B) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R56 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
142 * PAD 02 CT 002 XQ 01 Cooling Tower Fan (B) Motor Winding (V) Temperature 32 CT Fan(B) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R56 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
143 * PAD 02 CT 003 XQ 01 Cooling Tower Fan (B) Motor Winding (W) Temperature 32 CT Fan(B) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R56 ○ HH/H ○ ---- ○ ----
(P1) (P2)
H
144 * PAD 02 CT 081 XG 01 Cooling Tower Fan (B) Gear Temperature 27 CT Fan(B) Gear Temperature NORMAL/HIGH ---- DI ---- ---- NC ---- F NA *CTRIO R56 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
155 140
145 * PAD 03 CT 001 XQ 01 Cooling Tower Fan (C) Motor Winding (U) Temperature 32 CT Fan(C) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R57 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
146 * PAD 03 CT 002 XQ 01 Cooling Tower Fan (C) Motor Winding (V) Temperature 32 CT Fan(C) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R57 ○ HH/H ○ ---- ○ ----
(P1) (P2)
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL
155 140
147 * PAD 03 CT 003 XQ 01 Cooling Tower Fan (C) Motor Winding (W) Temperature 32 CT Fan(C) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R57 ○ HH/H ○ ---- ○ ----
(P1) (P2)
H
148 * PAD 03 CT 081 XG 01 Cooling Tower Fan (C) Gear Temperature 27 CT Fan(C) Gear Temperature NORMAL/HIGH ---- DI ---- ---- NC ---- F NA *CTRIO R57 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
155 140
149 * PAD 04 CT 001 XQ 01 Cooling Tower Fan (D) Motor Winding (U) Temperature 32 CT Fan(D) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R58 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
150 * PAD 04 CT 002 XQ 01 Cooling Tower Fan (D) Motor Winding (V) Temperature 32 CT Fan(D) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R58 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
151 * PAD 04 CT 003 XQ 01 Cooling Tower Fan (D) Motor Winding (W) Temperature 32 CT Fan(D) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R58 ○ HH/H ○ ---- ○ ----
(P1) (P2)
H
152 * PAD 04 CT 081 XG 01 Cooling Tower Fan (D) Gear Temperature 27 CT Fan(D) Gear Temperature NORMAL/HIGH ---- DI ---- ---- NC ---- F NA *CTRIO R58 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
155 140
153 * PAD 05 CT 001 XQ 01 Cooling Tower Fan (E) Motor Winding (U) Temperature 32 CT Fan(E) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R59 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
154 * PAD 05 CT 002 XQ 01 Cooling Tower Fan (E) Motor Winding (V) Temperature 32 CT Fan(E) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R59 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
155 * PAD 05 CT 003 XQ 01 Cooling Tower Fan (E) Motor Winding (W) Temperature 32 CT Fan(E) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R59 ○ HH/H ○ ---- ○ ----
(P1) (P2)
H
156 * PAD 05 CT 081 XG 01 Cooling Tower Fan (E) Gear Temperature 27 CT Fan(E) Gear Temperature NORMAL/HIGH ---- DI ---- ---- NC ---- F NA *CTRIO R59 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
155 140
157 * PAD 06 CT 001 XQ 01 Cooling Tower Fan (F) Motor Winding (U) Temperature 32 CT Fan(F) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R60 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
158 * PAD 06 CT 002 XQ 01 Cooling Tower Fan (F) Motor Winding (V) Temperature 32 CT Fan(F) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R60 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
159 * PAD 06 CT 003 XQ 01 Cooling Tower Fan (F) Motor Winding (W) Temperature 32 CT Fan(F) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F NA *CTRIO R60 ○ HH/H ○ ---- ○ ----
(P1) (P2)
H
160 * PAD 06 CT 081 XG 01 Cooling Tower Fan (F) Gear Temperature 27 CT Fan(F) Gear Temperature NORMAL/HIGH ---- DI ---- ---- NC ---- F NA *CTRIO R60 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
155 140
161 * PGB 11 CT 001 XQ 01 Auxiliary Cooling Water Pump (A) Motor Winding (U) Temperature 31 ACWP (A) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R70 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
162 * PGB 11 CT 002 XQ 01 Auxiliary Cooling Water Pump (A) Motor Winding (V) Temperature 31 ACWP (A) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R70 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
163 * PGB 11 CT 003 XQ 01 Auxiliary Cooling Water Pump (A) Motor Winding (W) Temperature 31 ACWP (A) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R70 ○ HH/H ○ ---- ○ ----
(P1) (P2)

784 * PGB 20 CT 001 XQ 01 Auxiliary Cooling Water Supply Temperature 22 ACW Supply Temperature 0-100 degC RTD ---- ---- ---- ---- F U0-ARS *DCS R70 ○ ---- ---- ---- ○ ----

155 140
164 * PGB 12 CT 001 XQ 01 Auxiliary Cooling Water Pump (B) Motor Winding (U) Temperature 31 ACWP (B) Motor Winding (U) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R71 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
165 * PGB 12 CT 002 XQ 01 Auxiliary Cooling Water Pump (B) Motor Winding (V) Temperature 31 ACWP (B) Motor Winding (V) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R71 ○ HH/H ○ ---- ○ ----
(P1) (P2)
155 140
166 * PGB 12 CT 003 XQ 01 Auxiliary Cooling Water Pump (B) Motor Winding (W) Temperature 31 ACWP (B) Motor Winding (W) Temp 0-200 degC RTD ---- ---- ---- 1% F U0-ARS *DCS R71 ○ HH/H ○ ---- ○ ----
(P1) (P2)

167 * MAV 10 CT 001 XQ 01 Main Oil Tank Temperature 25 Main Oil Tank Temperature 0-100 degC RTD ---- ---- ---- ---- F NA *DCS R73 ○ ---- ○ ---- ○ ----

70
168 * MAX 10 CT 001 XQ 01 Control Oil Tank Temperature 28 Control Oil Tank Temperature 0-100 degC RTD ---- ---- ---- 1% F NA *DCS R73 ○ H ○ ---- ○ ----
(P2)
120 100
169 * MAA 10 CT 013 XQ 01 Turbine No.1 Bearing Metal Temperature 31 Turbine No.1 Bearing Metal Temp 0-150 degC AIX ---- ---- ---- 1% *TPR NA *DCS R74 ○ HH/H ---- ---- ○ ----
(P1) (P2)
120 100
170 * MAA 10 CT 014 XQ 01 Turbine No.2 Bearing Metal Temperature 31 Turbine No.2 Bearing Metal Temp 0-150 degC AIX ---- ---- ---- 1% *TPR NA *DCS R74 ○ HH/H ---- ---- ○ ----
(P1) (P2)
120 100
171 * MAA 10 CT 011 XQ 01 Turbine Thrust Bearing(Front) Metal Temperature 32 Tur Thrust Brg(Front) Metal Temp 0-150 degC AIX ---- ---- ---- 1% *TPR NA *DCS R74 ○ HH/H ---- ---- ○ ----
(P1) (P2)
120 100
172 * MAA 10 CT 012 XQ 01 Turbine Thrust Bearing(Rear) Metal Temperature 31 Tur Thrust Brg(Rear) Metal Temp 0-150 degC AIX ---- ---- ---- 1% *TPR NA *DCS R74 ○ HH/H ---- ---- ○ ----
(P1) (P2)
120 90
173 * MKA 10 CT 001 XQ 01 Generator No. 1 Bearing Metal Temperature 27 Gen No.1 Bearing Metal Temp 0-150 degC AIX ---- ---- ---- 1% *TPR NA *DCS R74 ○ HH/H ---- ---- ○ ----
(P1) (P2)
120 90
174 * MKA 10 CT 002 XQ 01 Generator No. 2 Bearing Metal Temperature 27 Gen No.2 Bearing Metal Temp 0-150 degC AIX ---- ---- ---- 1% *TPR NA *DCS R74 ○ HH/H ---- ---- ○ ----
(P1) (P2)
110
175 * MKA 10 CT 011 XQ 01 Generator Stator Winding (U) Temperature (A) 31 Gen Stator Winding (U) Temp (A) 0-180 degC RTD ---- ---- ---- 1% F NA *DCS R78 ○ H ---- ---- ○ ----
(P2)
110
176 * MKA 10 CT 012 XQ 01 Generator Stator Winding (U) Temperature (B) 32 Gen Stator Winding (U) Temp (B) 0-180 degC RTD ---- ---- ---- 1% F NA *DCS R78 ○ H ---- ---- ○ ----
(P2)
110
177 * MKA 10 CT 013 XQ 01 Generator Stator Winding (V) Temperature (A) 31 Gen Stator Winding (V) Temp (A) 0-180 degC RTD ---- ---- ---- 1% F NA *DCS R78 ○ H ---- ---- ○ ----
(P2)
110
178 * MKA 10 CT 014 XQ 01 Generator Stator Winding (V) Temperature (B) 31 Gen Stator Winding (V) Temp (B) 0-180 degC RTD ---- ---- ---- 1% F NA *DCS R78 ○ H ---- ---- ○ ----
(P2)
110
179 * MKA 10 CT 015 XQ 01 Generator Stator Winding (W) Temperature (A) 31 Gen Stator Winding (W) Temp (A) 0-180 degC RTD ---- ---- ---- 1% F NA *DCS R78 ○ H ---- ---- ○ ----
(P2)
110
180 * MKA 10 CT 016 XQ 01 Generator Stator Winding (W) Temperature (B) 31 Gen Stator Winding (W) Temp (B) 0-180 degC RTD ---- ---- ---- 1% F NA *DCS R78 ○ H ---- ---- ○ ----
(P2)
110
181 * MKA 10 CT 021 XQ 01 Generator Stator Core Temperature (A)(Tur. side) 32 Gen Stator Core Temp(A)(TurSide) 0-200 degC TC ---- ---- ---- 1% F NA *DCS R79 ○ H ---- ---- ○ ----
(P2)
110
182 * MKA 10 CT 022 XQ 01 Generator Stator Core Temperature (B)(Tur. side) 32 Gen Stator Core Temp(B)(TurSide) 0-200 degC TC ---- ---- ---- 1% F NA *DCS R79 ○ H ---- ---- ○ ----
(P2)
110
183 * MKA 10 CT 023 XQ 01 Generator Stator Core Temperature (C)(Tur. side) 32 Gen Stator Core Temp(C)(TurSide) 0-200 degC TC ---- ---- ---- 1% F NA *DCS R79 ○ H ---- ---- ○ ----
(P2)
110
184 * MKA 10 CT 024 XQ 01 Generator Stator Core Temperature (A)(Ex. side) 31 Gen Stator Core Temp(A)(ExSide) 0-200 degC TC ---- ---- ---- 1% F NA *DCS R79 ○ H ---- ---- ○ ----
(P2)
110
185 * MKA 10 CT 025 XQ 01 Generator Stator Core Temperature (B)(Ex. side) 31 Gen Stator Core Temp(B)(ExSide) 0-200 degC TC ---- ---- ---- 1% F NA *DCS R79 ○ H ---- ---- ○ ----
(P2)
110
186 * MKA 10 CT 026 XQ 01 Generator Stator Core Temperature (C)(Ex. side) 31 Gen Stator Core Temp(C)(ExSide) 0-200 degC TC ---- ---- ---- 1% F NA *DCS R79 ○ H ---- ---- ○ ----
(P2)
38
187 * MKA 10 CT 031 XQ 01 Generator Cooler Air Temperature (A)(Outlet) 30 Gen Cooler Air Temp(A)(Outlet) 0-150 degC RTD ---- ---- ---- 1% F NA *DCS R80 ○ H ---- ---- ○ ----
(P2)
38
188 * MKA 10 CT 032 XQ 01 Generator Cooler Air Temperature (B)(Outlet) 30 Gen Cooler Air Temp(B)(Outlet) 0-150 degC RTD ---- ---- ---- 1% F NA *DCS R80 ○ H ---- ---- ○ ----
(P2)
38
189 * MKA 10 CT 033 XQ 01 Generator Cooler Air Temperature (C)(Outlet) 30 Gen Cooler Air Temp(C)(Outlet) 0-150 degC RTD ---- ---- ---- 1% F NA *DCS R80 ○ H ---- ---- ○ ----
(P2)
69
190 * MKA 10 CT 034 XQ 01 Generator Cooler Air Temperature (A)(Inlet) 29 Gen Cooler Air Temp(A)(Inlet) 0-150 degC RTD ---- ---- ---- 1% F NA *DCS R80 ○ H ○ ---- ○ ----
(P2)
69
191 * MKA 10 CT 035 XQ 01 Generator Cooler Air Temperature (B)(Inlet) 29 Gen Cooler Air Temp(B)(Inlet) 0-150 degC RTD ---- ---- ---- 1% F NA *DCS R80 ○ H ○ ---- ○ ----
(P2)
69
192 * MKA 10 CT 036 XQ 01 Generator Cooler Air Temperature (C)(Inlet) 29 Gen Cooler Air Temp(C)(Inlet) 0-150 degC RTD ---- ---- ---- 1% F NA *DCS R80 ○ H ○ ---- ○ ----
(P2)
7.5 6.0
193 * PAD 12 CQ 001 XQ 01 Cooling Tower Basin pH Analysis 31 Cooling Tower Basin pH Analysis 0-14 pH AII ---- ---- ---- 1% F NA *CTRIO R81 ○ H/L ○ ---- ○ ----
(P2) (P2)
HH/H/ BTM+1570 BTM+1200 BTM+600
194 * LCT 11 CL 001 XQ 01 HP Scrubber Level (A) 21 HP Scrubber Level (A) 0-2560 mm AIX ---- ---- ---- 1% *TPR NA *DCS R82 ○ ○ ---- ○ ----
L (P2) (P2) (P2)
HH/H/ BTM+1570 BTM+1200 BTM+600
195 * LCT 11 CL 002 XQ 01 HP Scrubber Level (B) 21 HP Scrubber Level (B) 0-2560 mm AIX ---- ---- ---- 1% *TPR NA *DCS R82 ○ ○ ---- ○ ----
L (P2) (P2) (P2)
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL
HH/H/ BTM+1570 BTM+1200 BTM+600
196 * LCT 11 CL 003 XQ 01 HP Scrubber Level (C) 21 HP Scrubber Level (C) 0-2560 mm AIX ---- ---- ---- 1% *TPR NA *DCS R82 ○ ○ ---- ○ ----
L (P2) (P2) (P2)
HH/H/ BTM+1680 BTM+1300 BTM+700
197 * LCT 21 CL 001 XQ 01 LP Scrubber Level (A) 21 LP Scrubber Level (A) 0-2060 mm AIX ---- ---- ---- 1% *TPR NA *DCS R83 ○ ○ ---- ○ ----
L (P1) (P2) (P2)
HH/H/ BTM+1680 BTM+1300 BTM+700
198 * LCT 21 CL 002 XQ 01 LP Scrubber Level (B) 21 LP Scrubber Level (B) 0-2060 mm AIX ---- ---- ---- 1% *TPR NA *DCS R83 ○ ○ ---- ○ ----
L (P1) (P2) (P2)
HH/H/ BTM+1680 BTM+1300 BTM+700
199 * LCT 21 CL 003 XQ 01 LP Scrubber Level (C) 21 LP Scrubber Level (C) 0-2060 mm AIX ---- ---- ---- 1% *TPR NA *DCS R83 ○ ○ ---- ○ ----
L (P1) (P2) (P2)

200 * MAJ 41 CL 081 XG 01 Seal Water Discharge Separater Level (A) 32 Sl Water Discharge Sep Level (A) NORMAL/HIGH ---- DI ---- ---- NC ---- F U0-ARS *DCS R85 ○ ---- ○ ---- ○ ----

201 * MAJ 42 CL 081 XG 01 Seal Water Discharge Separater Level (B) 32 Sl Water Discharge Sep Level (B) NORMAL/HIGH ---- DI ---- ---- NC ---- F U0-ARS *DCS R85 ○ ---- ○ ---- ○ ----

HH/H/ BTM+2500 BTM+300


202 * GMF 11 CL 001 XG 01 GRS U-seal Pit Level 20 GRS U-seal Pit Level BTM~BTM+10500 mm AII ---- ---- ---- 1% F U0-ARS *DCS R85 ○ ○ ---- ○ ---- Rev.4 Range is filled 4
L/LL (P2) (P2)
L
206 * PAD 01 CL 081 XG 01 Cooling Tower Fan (A) Gear Reducer Oil Level (L) 31 CT Fan(A) Gear Redc Oil Lvl (L) NORMAL/LOW ---- DI ---- ---- NC ---- F NA *CTRIO R86 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1)
L
207 * PAD 02 CL 081 XG 01 Cooling Tower Fan (B) Gear Reducer Oil Level (L) 31 CT Fan(B) Gear Redc Oil Lvl (L) NORMAL/LOW ---- DI ---- ---- NC ---- F NA *CTRIO R86 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1)
L
208 * PAD 03 CL 081 XG 01 Cooling Tower Fan (C) Gear Reducer Oil Level (L) 31 CT Fan(C) Gear Redc Oil Lvl (L) NORMAL/LOW ---- DI ---- ---- NC ---- F NA *CTRIO R86 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1)
L
209 * PAD 04 CL 081 XG 01 Cooling Tower Fan (D) Gear Reducer Oil Level (L) 31 CT Fan(D) Gear Redc Oil Lvl (L) NORMAL/LOW ---- DI ---- ---- NC ---- F NA *CTRIO R86 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1)
L
210 * PAD 05 CL 081 XG 01 Cooling Tower Fan (E) Gear Reducer Oil Level (L) 31 CT Fan(E) Gear Redc Oil Lvl (L) NORMAL/LOW ---- DI ---- ---- NC ---- F NA *CTRIO R86 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1)
L
211 * PAD 06 CL 081 XG 01 Cooling Tower Fan (F) Gear Reducer Oil Level (L) 31 CT Fan(F) Gear Redc Oil Lvl (L) NORMAL/LOW ---- DI ---- ---- NC ---- F NA *CTRIO R86 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1)
L
212 * MAV 10 CL 081 XG 01 Main Oil Tank Level 20 Main Oil Tank Level NORMAL/LOW ---- DI ---- ---- NC ---- F NA *DCS R88 ○ ○ ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1)
L
213 * MAX 10 CL 081 XG 01 Control Oil Tank Level 22 Control Oil Tank Level NORMAL/LOW ---- DI ---- ---- NC ---- F NA *DCS R88 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1)
H 200
214 * MKA 10 CL 001 XG 01 Generator Cooling Water Leakage (A) 29 Gen Cooling Water Leakage (A) NORMAL/HIGH ---- DI ---- ---- NC ---- *TPR NA *DCS R89B ○ ---- ---- ○ ---- Rev.4 Signal type is changed 4
(P1) (P2)
H 200
215 * MKA 10 CL 002 XG 01 Generator Cooling Water Leakage (A) 29 Gen Cooling Water Leakage (A) NORMAL/HIGH ---- DI ---- ---- NC ---- *TPR NA *DCS R89B ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1) (P2)
H 200
216 * MKA 10 CL 003 XG 01 Generator Cooling Water Leakage (B) 29 Gen Cooling Water Leakage (B) NORMAL/HIGH ---- DI ---- ---- NC ---- *TPR NA *DCS R89B ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1) (P2)
H 200
217 * MKA 10 CL 004 XG 01 Generator Cooling Water Leakage (B) 29 Gen Cooling Water Leakage (B) NORMAL/HIGH ---- DI ---- ---- NC ---- *TPR NA *DCS R89B ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1) (P2)
250 125
218 * MAA 10 CY 001 XQ 01 Turbine No. 1 Bearing Shaft Vibration (X) 30 Tur No.1 Bearing Shaft Vib (X) 0-400 μm AIX ---- ---- ---- 1% *TPR NA *DCS R91 ○ HH/H ---- ---- ○ ----
(P1) (P2)
250 125
219 * MAA 10 CY 002 XQ 01 Turbine No. 1 Bearing Shaft Vibration (Y) 30 Tur No.1 Bearing Shaft Vib (Y) 0-400 μm AIX ---- ---- ---- 1% *TPR NA *DCS R91 ○ HH/H ---- ---- ○ ----
(P1) (P2)
250 125
220 * MAA 10 CY 003 XQ 01 Turbine No. 2 Bearing Shaft Vibration (X) 30 Tur No.2 Bearing Shaft Vib (X) 0-400 μm AIX ---- ---- ---- 1% *TPR NA *DCS R91 ○ HH/H ---- ---- ○ ----
(P1) (P2)
250 125
221 * MAA 10 CY 004 XQ 01 Turbine No. 2 Bearing Shaft Vibration (Y) 30 Tur No.2 Bearing Shaft Vib (Y) 0-400 μm AIX ---- ---- ---- 1% *TPR NA *DCS R91 ○ HH/H ---- ---- ○ ----
(P1) (P2)
250 125
222 * MKA 10 CY 001 XQ 01 Generator No. 1 Bearing Shaft Vibration (X) 30 Gen No.1 Bearing Shaft Vib (X) 0-400 μm AIX ---- ---- ---- 1% *TPR NA *DCS R91A ○ HH/H ---- ---- ○ ----
(P1) (P2)
250 125
223 * MKA 10 CY 002 XQ 01 Generator No. 1 Bearing Shaft Vibration (Y) 30 Gen No.1 Bearing Shaft Vib (Y) 0-400 μm AIX ---- ---- ---- 1% *TPR NA *DCS R91A ○ HH/H ---- ---- ○ ----
(P1) (P2)
250 125
224 * MKA 10 CY 003 XQ 01 Generator No. 2 Bearing Shaft Vibration (X) 30 Gen No.2 Bearing Shaft Vib (X) 0-400 μm AIX ---- ---- ---- 1% *TPR NA *DCS R91A ○ HH/H ---- ---- ○ ----
(P1) (P2)
250 125
225 * MKA 10 CY 004 XQ 01 Generator No. 2 Bearing Shaft Vibration (Y) 30 Gen No.2 Bearing Shaft Vib (Y) 0-400 μm AIX ---- ---- ---- 1% *TPR NA *DCS R91A ○ HH/H ---- ---- ○ ----
(P1) (P2)

226 * MAK 10 CG 001 XQ 01 Expansion for Rotor 19 Expansion for Rotor -2-+10 mm AIX ---- ---- ---- ---- *TPR NA *DCS R92 ○ ---- ---- ---- ○ ----

227 * MAK 10 CG 003 XQ 01 Expansion for Casing 20 Expansion for Casing -4-+8 mm AIX ---- ---- ---- ---- *TPR NA *DCS R92 ○ ---- ---- ---- ○ ----

1.0 0.5
228 * MAK 10 CG 011 XQ 01 Turbine Shaft Position (A) 26 Turbine Shaft Position (A) -1.5-+1.5 mm AIX ---- ---- ---- 1% *TPR NA *DCS R92 ○ HH/H ---- ---- ○ ----
(P1) (P2)
1.0 0.5
229 * MAK 10 CG 012 XQ 01 Turbine Shaft Position (B) 26 Turbine Shaft Position (B) -1.5-+1.5 mm AIX ---- ---- ---- 1% *TPR NA *DCS R92 ○ HH/H ---- ---- ○ ----
(P1) (P2)
1.0 0.5
230 * MAK 10 CG 013 XQ 01 Turbine Shaft Position (C) 26 Turbine Shaft Position (C) -1.5-+1.5 mm AIX ---- ---- ---- 1% *TPR NA *DCS R92 ○ HH/H ---- ---- ○ ----
(P1) (P2)

231 * MAA 10 CS 011 XQ 01 Turbine Zero Speed 18 Turbine Zero Speed 0-3600 rpm AIX ---- ---- ---- ---- *TPR NA *DCS R93 ○ ---- ○ ---- ○ ----

232 * MAA 10 CS 012 XG 01 Turbine Zero Speed 18 Turbine Zero Speed OFF/ON ---- DI ---- ---- NO ---- *TPR NA *DCS R93 ○ ---- ○ ---- ○ ----

992 * MAA 10 CS 011 XG 02 Turbine Eccentricity 20 Turbine Eccentricity 0-100 um AIX ---- ---- ---- ---- *TPR NA *DCS R93 ○ ---- ---- ---- ○ ----

18 7.0
233 * PAD 01 CV 001 XQ 01 Cooling Tower Fan (A) Gear Reducer Vibration 27 CT Fan (A) Gear Reducer Vib 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R95 ○ HH/H ○ ---- ○ ----
(P1) (P2)
18 7.0
234 * PAD 01 CV 011 XQ 01 Cooling Tower Fan (A) Motor Vibration 26 CT Fan (A) Motor Vibration 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R95 ○ HH/H ---- ---- ○ ----
(P1) (P2)
18 7.0
235 * PAD 02 CV 001 XQ 01 Cooling Tower Fan (B) Gear Reducer Vibration 27 CT Fan (B) Gear Reducer Vib 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R95 ○ HH/H ○ ---- ○ ----
(P1) (P2)
18 7.0
236 * PAD 02 CV 012 XQ 01 Cooling Tower Fan (B) Motor Vibration 26 CT Fan (B) Motor Vibration 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R95 ○ HH/H ---- ---- ○ ----
(P1) (P2)
18 7.0
237 * PAD 03 CV 001 XQ 01 Cooling Tower Fan (C) Gear Reducer vibration 27 CT Fan (C) Gear Reducer Vib 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R96 ○ HH/H ○ ---- ○ ----
(P1) (P2)
18 7.0
238 * PAD 03 CV 013 XQ 01 Cooling Tower Fan (C) Motor Vibration 26 CT Fan (C) Motor Vibration 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R96 ○ HH/H ---- ---- ○ ----
(P1) (P2)
18 7.0
239 * PAD 04 CV 001 XQ 01 Cooling Tower Fan (D) Gear Reducer Vibration 27 CT Fan (D) Gear Reducer Vib 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R96 ○ HH/H ○ ---- ○ ----
(P1) (P2)
18 7.0
240 * PAD 04 CV 014 XQ 01 Cooling Tower Fan (D) Motor Vibration 26 CT Fan (D) Motor Vibration 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R96 ○ HH/H ---- ---- ○ ----
(P1) (P2)
18 7.0
241 * PAD 05 CV 001 XQ 01 Cooling Tower Fan (E) Gear Reducer Vibration 27 CT Fan (E) Gear Reducer Vib 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R97 ○ HH/H ○ ---- ○ ----
(P1) (P2)
18 7.0
242 * PAD 05 CV 015 XQ 01 Cooling Tower Fan (E) Motor Vibration 26 CT Fan (E) Motor Vibration 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R97 ○ HH/H ---- ---- ○ ----
(P1) (P2)
18 7.0
243 * PAD 06 CV 001 XQ 01 Cooling Tower Fan (F) Gear Reducer Vibration 27 CT Fan (F) Gear Reducer Vib 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R97 ○ HH/H ○ ---- ○ ----
(P1) (P2)
18 7.0
244 * PAD 06 CV 016 XQ 01 Cooling Tower Fan (F) Motor Vibration 26 CT Fan (F) Motor Vibration 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R97 ○ HH/H ---- ---- ○ ----
(P1) (P2)
13.8 8.9
245 * LCA 21 CV 001 XQ 01 Hotwell Pump (A) Motor Vibration (X) 27 HWP (A) Motor Vibration (X) 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R99 ○ HH/H ○ ---- ○ ----
(P1) (P2)
13.8 8.9
246 * LCA 21 CV 002 XQ 01 Hotwell Pump (A) Motor Vibration (Y) 27 HWP (A) Motor Vibration (Y) 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R99 ○ HH/H ○ ---- ○ ----
(P1) (P2)
13.8 8.9
247 * LCA 22 CV 001 XQ 01 Hotwell Pump (B) Motor Vibration (X) 27 HWP (B) Motor Vibration (X) 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R99 ○ HH/H ○ ---- ○ ----
(P1) (P2)
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL
13.8 8.9
248 * LCA 22 CV 002 XQ 01 Hotwell Pump (B) Motor Vibration (Y) 27 HWP (B) Motor Vibration (Y) 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R99 ○ HH/H ○ ---- ○ ----
(P1) (P2)
4.5
249 * MAJ 41 CV 001 XQ 01 Vacuum Pump (A) Vibration 25 Vacuum Pump (A) Vibration 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R100 ○ H ---- ---- ○ ----
(P2)
4.5
250 * MAJ 42 CV 001 XQ 01 Vacuum Pump (B) Vibration 25 Vacuum Pump (B) Vibration 0-25 mm/s AIX ---- ---- ---- 1% *TPR NA *DCS R100 ○ H ---- ---- ○ ----
(P2)

251 * CHA 10 GH 001 XQ 01 Generator Current (R) 21 Generator Current (R) 0-4000 A AIX ---- ---- ---- ---- *GPR NA *DCS R115 ○ ---- ○ ---- ○ ---- Rev.4 Range is changed 4

252 * CHA 10 GH 001 XQ 02 Generator Current (S) 21 Generator Current (S) 0-4000 A AIX ---- ---- ---- ---- *GPR NA *DCS R115 ○ ---- ○ ---- ○ ---- Rev.4 Range is changed 4

253 * CHA 10 GH 001 XQ 03 Generator Current (T) 21 Generator Current (T) 0-4000 A AIX ---- ---- ---- ---- *GPR NA *DCS R115 ○ ---- ○ ---- ○ ---- Rev.4 Range is changed 4

254 * CHA 10 GH 001 XQ 04 Generator Voltage (U-V) 23 Generator Voltage (U-V) 0-15 kV AIX ---- ---- ---- ---- *GPR NA *DCS R115 ○ ---- ○ ---- ○ ----

255 * CHA 10 GH 001 XQ 05 Generator Voltage (V-W) 23 Generator Voltage (V-W) 0-15 kV AIX ---- ---- ---- ---- *GPR NA *DCS R115 ○ ---- ○ ---- ○ ----

256 * CHA 10 GH 001 XQ 06 Generator Voltage (W-U) 23 Generator Voltage (W-U) 0-15 kV AIX ---- ---- ---- ---- *GPR NA *DCS R115 ○ ---- ○ ---- ○ ----

257 * CHA 10 GH 001 XQ 07 Generator Power 15 Generator Power 0-80 MW AIX ---- ---- ---- ---- *GPR NA *DCS R115 ○ ---- ○ ---- ○ ----

258 * CHA 10 GH 001 XQ 08 Generator Reactive Power 24 Generator Reactive Power -80-+80 MVAR AIX ---- ---- ---- ---- *GPR NA *DCS R115 ○ ---- ○ ---- ○ ----

259 * CHA 10 GH 001 XQ 09 Generator Power Factor 23 Generator Power Factor -0.5-1-+0.5 PF AIX ---- ---- ---- ---- *GPR NA *DCS R115 ○ ---- ○ ---- ○ ----

260 * CHA 10 GH 001 XQ 10 Generator Frequency 19 Generator Frequency 45-55 Hz AIX ---- ---- ---- ---- *GPR NA *DCS R115 ○ ---- ○ ---- ○ ----

MWh/
261 * CHA 10 GH 001 XQ 11 Generator Watt Hour 20 Generator Watt Hour 0-99999999 PI ---- ---- ---- ---- *GPR NA *DCS R116 ○ ---- ---- ---- ○ ----
PULSE
MVARh/
262 * CHA 10 GH 001 XQ 12 Generator VAR Hour 20 Generator VAR Hour 0-99999999 PI ---- ---- ---- ---- *GPR NA *DCS R116 ○ ---- ---- ---- ○ ----
PULSE

263 * CHA 10 GH 001 XQ 13 Generator Active Power A 25 Generator Active Power A 0-80 MW AIX ---- ---- ---- ---- *GPR NA *DCS R116 ○ ---- ○ ---- ○ ---- Rev.4 Range is changed 4

264 * CHA 10 GH 001 XQ 14 Generator Active Power B 25 Generator Active Power B 0-80 MW AIX ---- ---- ---- ---- *GPR NA *DCS R116 ○ ---- ○ ---- ○ ---- Rev.4 Range is changed 4

NO
265 * CAA 10 GH 001 YB 01 Turbine Reset 17 TURBINE RESET CMD OFF/RESET ---- DOH DC110 1W ---- *DCS NA *TPR T01 ---- ---- ○ ---- ○ ----
PULSE
NC
266 * CAA 10 GH 001 YB 02 Turbine Trip 16 TURBINE TRIP CMD OFF/TRIP ---- DOH DC110 1W ---- *DCS NA *TPR T01 ---- ---- ○ ---- ○ ---- Rev.4 Signal Type is changed 4
PULSE
NC
267 * CAA 10 GH 001 YB 03 DCS Major Fault 15 DCS Major Fault NORMAL/FAULT ---- DOH DC110 1W ---- *DCS NA *TPR T01 ---- ---- ○ ---- ○ ○ Rev.4 Signal Type is changed 4
PULSE

268 * CAA 10 GH 001 XG 01 PPCR Emergency Trip 19 PPCR Emergency Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T01 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

269 * CAA 10 GH 001 XG 02 Local Emergency Trip 20 Local Emergency Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T01 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

270 * CAA 10 GH 001 XG 03 Turbine Trip 12 Turbine Trip RESET/TRIP ---- DI ---- ---- NO ---- *TPR NA *DCS T01 ---- P1 ○ ---- ○ ○ Rev.4a ANN level is corrected 4a

271 * CAA 10 GH 001 XG 04 TPR Power Supply Abnormal 25 TPR Power Supply Abnormal NORMAL/ALARM ---- DI ---- ---- NC ---- *TPR NA *DCS T01 ---- P2 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

272 * CAA 10 GH 001 XG 05 TSI Unit Abnormal 17 TSI Unit Abnormal NORMAL/ALARM ---- DI ---- ---- NO ---- *TPR NA *DCS T01 ---- P2 ---- ---- ○ ○ Rev.4 Signal type is updated 4

273 * CAA 10 GH 001 XG 06 VMS Unit Abnormal 17 VMS Unit Abnormal NORMAL/ALARM ---- DI ---- ---- NO ---- *TPR NA *DCS T01 ---- P2 ---- ---- ○ ○ Rev.4 Signal type is updated 4

3300
274 * MAA 10 CS 001 XG 01 Over Speed (A) 14 Over Speed (A) OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a
(P1)
3300
275 * MAA 10 CS 002 XG 01 Over Speed (B) 14 Over Speed (B) OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a
(P1)
3300
276 * MAA 10 CS 003 XG 01 Over Speed (C) 14 Over Speed (C) OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a
(P1)

277 * MAA 10 CS 001 XG 10 Over Speed Trip 15 Over Speed Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

278 * MAK 10 CG 011 XG 01 Turbine Shaft Position (A) HH/LL 29 Turbine Shaft Position (A) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

279 * MAK 10 CG 012 XG 01 Turbine Shaft Position (B) HH/LL 29 Turbine Shaft Position (B) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

280 * MAK 10 CG 013 XG 01 Turbine Shaft Position (C) HH/LL 29 Turbine Shaft Position (C) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

281 * MAK 10 CG 011 XG 10 Turbine Shaft Position Trip 27 Turbine Shaft Position Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

282 * MAG 10 CL 001 XG 01 Condenser Level (A) HH 22 Condenser Level (A) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

283 * MAG 10 CL 002 XG 01 Condenser Level (B) HH 22 Condenser Level (B) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

284 * MAG 10 CL 003 XG 01 Condenser Level (C) HH 22 Condenser Level (C) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

285 * MAG 10 CL 001 XG 10 Condenser Level Trip 20 Condenser Level Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ○ ---- ○ ○ Rev.4a ANN level is corrected 4a

286 * MAV 46 CP 001 XG 01 Lube Oil Supply Pressure (A) LL 31 Lube Oil Supply Pressure (A) LL OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

287 * MAV 46 CP 002 XG 01 Lube Oil Supply Pressure (B) LL 31 Lube Oil Supply Pressure (B) LL OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

288 * MAV 46 CP 003 XG 01 Lube Oil Supply Pressure (C) LL 31 Lube Oil Supply Pressure (C) LL OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

289 * MAV 46 CP 001 XG 10 Lube Oil Supply Pressure Trip 29 Lube Oil Supply Pressure Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T02 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

290 * MAG 10 CP 001 XG 01 Turbine Exhaust Pressure (A) HH 31 Turbine Exhaust Pressure (A) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

291 * MAG 10 CP 002 XG 01 Turbine Exhaust Pressure (B) HH 31 Turbine Exhaust Pressure (B) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

292 * MAG 10 CP 003 XG 01 Turbine Exhaust Pressure (C) HH 31 Turbine Exhaust Pressure (C) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

293 * MAG 10 CP 001 XG 02 Turbine Exhaust Pressure (A) ≧F(x) 31 Turbine Exhaust Press (A) ≧F(x) OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

294 * MAG 10 CP 002 XG 02 Turbine Exhaust Pressure (B) ≧F(x) 31 Turbine Exhaust Press (B) ≧F(x) OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

295 * MAG 10 CP 003 XG 02 Turbine Exhaust Pressure (C) ≧F(x) 31 Turbine Exhaust Press (C) ≧F(x) OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

296 * MAG 10 CP 001 XG 10 Turbine Exhaust Pressure Trip 29 Turbine Exhaust Pressure Trip OFF/TRIP ---- DI ---- ---- NO ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4 Signal type is changed 4

297 * MAG 10 CP 001 XG 11 Total Life Time 300min Over at Low Vacuum Operation 32 Total 300min Over at Low Vac Ope OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL

298 * MAG 10 CP 001 XG 12 Integrated Timer 300 min Elapsed 32 Integrated Timer 300 min Elapsed OFF/ON ---- DI ---- ---- NO ---- *TPR NA *DCS T03 ○ ---- ---- ---- ○ ○ Rev.4 Signal type is changed 4

299 * MAG 10 CP 001 XG 13 Turbine Trip within 5min 24 Turbine Trip within 5min OFF/ON ---- DI ---- ---- NO ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

300 * MAG 10 CP 001 XG 14 Integrated Timer count 22 Integrated Timer count OFF/ON ---- DI ---- ---- NO ---- *TPR NA *DCS T03 ○ ---- ---- ---- ○ ○ Rev.4 Signal type is changed 4

301 * LCT 11 CL 001 XG 01 HP Scrubber Level (A) HH 24 HP Scrubber Level (A) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

302 * LCT 11 CL 002 XG 01 HP Scrubber Level (B) HH 24 HP Scrubber Level (B) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

303 * LCT 11 CL 003 XG 01 HP Scrubber Level (C) HH 24 HP Scrubber Level (C) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

304 * LCT 11 CL 001 XG 10 HP Scrubber Level Trip 22 HP Scrubber Level Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

993 * LCT 21 CL 001 XG 01 LP Scrubber Level (A) HH 24 LP Scrubber Level (A) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

994 * LCT 21 CL 002 XG 01 LP Scrubber Level (B) HH 24 LP Scrubber Level (B) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

995 * LCT 21 CL 003 XG 01 LP Scrubber Level (C) HH 24 LP Scrubber Level (C) HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

996 * LCT 21 CL 001 XG 10 LP Scrubber Level Trip 22 LP Scrubber Level Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T03 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

305 * MAA 10 CT 013 XG 01 Turbine No.1 Bearing Metal Temp HH 30 Tur No.1 Bearing Metal Temp HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

306 * MAA 10 CT 014 XG 01 Turbine No.2 Bearing Metal Temp HH 30 Tur No.2 Bearing Metal Temp HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

307 * MAA 10 CT 011 XG 01 Turbine Thrust(F) Bearing Metal Temp HH 31 Tur Thrust(F) Brg Metal Temp HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

308 * MAA 10 CT 012 XG 01 Turbine Thrust(R) Bearing Metal Temp HH 31 Tur Thrust(R) Brg Metal Temp HH OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

309 * MKA 10 CT 001 XG 01 Generator No.1 Bearing Metal Temp HH 30 Gen No.1 Bearing Metal Temp HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

310 * MKA 10 CT 002 XG 01 Generator No.2 Bearing Metal Temp HH 30 Gen No.2 Bearing Metal Temp HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

311 * MAA 10 CT 011 XG 10 TG Bearing Metal Temp HH 24 TG Bearing Metal Temp HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

313 * LCA 21 AP 001 XG 51 Both Hotwell Pump Stop 22 Both Hotwell Pump Stop OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ○ ---- ○ ○ Rev.4a ANN level is corrected 4a

314 * PGB 11 AP 001 XG 51 Both ACWP Stop 14 Both ACWP Stop OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ○ ---- ○ ○ Rev.4a ANN level is corrected 4a

315 * MAA 10 CY 001 XG 01 T/G Vibration HH 16 T/G Vibration HH OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

316 * MAA 10 CY 001 XG 10 T/G Vibration Trip 18 T/G Vibration Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

317 * MAA 10 CY 001 XG 02 T/G Vibration H 15 T/G Vibration H OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T04 ---- P1 ---- ---- ○ ○ Rev.4a ANN level is corrected 4a

NO
318 * MAA 11 AA 001 YB 10 HPSV Open 13 HPSV OPEN CMD OFF/OPEN ---- DOH DC110 1W ---- *DCS NA *TPR T10 ---- ---- ○ ---- ○ ----
PULSE

319 * MAA 11 CG 081 XG 01 HPSV(L) Full Open 18 HPSV(L) Full Open OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS T10 ○ ---- ○ ---- ○ ----

320 * MAA 11 CG 082 XG 02 HPSV(L) Full Close 19 HPSV(L) Full Close OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS T10 ○ ---- ○ ---- ○ ----

321 * MAA 12 CG 081 XG 01 HPSV(R) Full Open 18 HPSV(R) Full Open OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS T11 ○ ---- ○ ---- ○ ----

322 * MAA 12 CG 082 XG 02 HPSV(R) Full Close 19 HPSV(R) Full Close OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS T11 ○ ---- ○ ---- ○ ----

NO
323 * MAC 31 AA 001 YB 10 LPSV Open 13 LPSV OPEN CMD OFF/OPEN ---- DOH DC110 1W ---- *DCS NA *TPR T14 ---- ---- ○ ---- ○ ----
PULSE

324 * MAC 31 CG 081 XG 01 LPSV(L) Full Open 18 LPSV(L) Full Open OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS T14 ○ ---- ○ ---- ○ ----

325 * MAC 31 CG 082 XG 02 LPSV(L) Full Close 19 LPSV(L) Full Close OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS T14 ○ ---- ○ ---- ○ ----

326 * MAC 32 CG 081 XG 10 LPSV(R) Full Open 18 LPCV(R) Full Open OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS T14A ○ ---- ○ ---- ○ ----

327 * MAC 32 CG 082 XG 01 LPSV(R) Full Close 19 LPCV(R) Full Close OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS T14A ○ ---- ○ ---- ○ ----

328 * MAV 22 AP 001 XG 01 MOP(B) Discharge Pressure L 27 MOP(B) Discharge Pressure L NORMAL/LOW DI ---- ---- NC ---- *TPR NA *DCS T20 ---- ---- ○ ---- ○ ---- Rev.4 Signal type is changed 4

NO
329 * MAV 21 AP 001 YB 01 MOP (A) Auto 13 MOP (A) Auto OFF/AUTO ---- DOH DC110 1W ---- *DCS NA *TPR T20 ---- ---- ○ ---- ○ ----
PULSE
NO
330 * MAV 21 AP 001 YB 02 MOP (A) Manual 15 MOP (A) Manual OFF/MAN ---- DOH DC110 1W ---- *DCS NA *TPR T20 ---- ---- ○ ---- ○ ----
PULSE

331 * MAV 21 AP 001 XG 02 MOP (A) Auto Mode 18 MOP (A) Auto Mode MAN/AUTO ---- DI ---- ---- NO ---- *TPR NA *DCS T20 ○ ---- ○ ---- ○ ----

NO
332 * MAV 21 AP 001 YB 03 MOP (A) start 13 MOP (A) Start OFF/start ---- DOH DC110 1W ---- *DCS NA *TPR T20 ---- ---- ○ ---- ○ ----
PULSE
NO
333 * MAV 21 AP 001 YB 04 MOP (A) Stop 12 MOP (A) Stop OFF/STOP ---- DOH DC110 1W ---- *DCS NA *TPR T20 ---- ---- ○ ---- ○ ----
PULSE

334 * MAV 21 AP 001 XG 05 MOP (A) Auto Start 19 MOP (A) Auto Start OFF/START ---- DI ---- ---- NC ---- *TPR NA *DCS T20 ---- P2 ---- ---- ○ ---- Rev.4 Signal type is updated 4

335 * MAV 21 AP 001 XG 03 MOP (A) Running 16 MOP (A) Running STOP/RUN ---- DI ---- ---- NO ---- *TPR NA *DCS T20 ○ ---- ○ ---- ○ ----

336 * MAV 21 AP 001 XG 06 MOP (A) Fault Trip 18 MOP (A) Fault Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T20 ---- P1 ○ ---- ○ ---- Rev.4 Signal type is updated 4

337 * MAV 21 AP 001 XG 07 MOP (A) Remote Mode 20 MOP (A) Remote Mode LOCAL/REMOTE ---- DI ---- ---- NO ---- *TPR NA *DCS T20 ---- ---- ○ ---- ○ ----

975 * MAV 21 AP 001 XG 08 MOP (A) Rack-in Position 24 MOP (A) Rack-in Position OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T20 ○ ---- ---- ---- ○ ----

338 * MAV 21 AP 001 XQ 01 MOP (A) CURRENT 15 MOP (A) CURRENT 0-100 A AIX ---- ---- ---- ---- *LVESWB NA *MCCRIO(LV) T20 ---- ---- ○ ---- ○ ---- Rev.4a Alarm is not needed 4a

339 * MAV 21 AP 001 XG 01 MOP(A) Discharge Pressure L 27 MOP(A) Discharge Pressure L NORMAL/LOW ---- DI ---- ---- NC ---- *TPR NA *DCS T21 ---- ---- ○ ---- ○ ---- Rev.4 Signal type is updated 4

NO
340 * MAV 22 AP 001 YB 01 MOP (B) Auto 13 MOP (B) Auto OFF/AUTO ---- DOH DC110 1W ---- *DCS NA *TPR T21 ---- ---- ○ ---- ○ ----
PULSE
NO
341 * MAV 22 AP 001 YB 02 MOP (B) Manual 15 MOP (B) Manual OFF/MAN ---- DOH DC110 1W ---- *DCS NA *TPR T21 ---- ---- ○ ---- ○ ----
PULSE

342 * MAV 22 AP 001 XG 02 MOP (B) Auto Mode 18 MOP (B) Auto Mode MAN/AUTO ---- DI ---- ---- NO ---- *TPR NA *DCS T21 ○ ---- ○ ---- ○ ----

NO
343 * MAV 22 AP 001 YB 03 MOP (B) start 13 MOP (B) start OFF/START ---- DOH DC110 1W ---- *DCS NA *TPR T21 ---- ---- ○ ---- ○ ----
PULSE
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL
NO
344 * MAV 22 AP 001 YB 04 MOP (B) Stop 12 MOP (B) Stop OFF/STOP ---- DOH DC110 1W ---- *DCS NA *TPR T21 ---- ---- ○ ---- ○ ----
PULSE

345 * MAV 22 AP 001 XG 05 MOP (B) Auto Start 19 MOP (B) Auto Start OFF/START ---- DI ---- ---- NC ---- *TPR NA *DCS T21 ---- P2 ---- ---- ○ ---- Rev.4 Signal type is updated 4

346 * MAV 22 AP 001 XG 03 MOP (B) Running 16 MOP (B) Running STOP/RUN ---- DI ---- ---- NO ---- *TPR NA *DCS T21 ○ ---- ○ ---- ○ ----

347 * MAV 22 AP 001 XG 06 MOP (B) Fault Trip 18 MOP (B) Fault Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T21 ---- P1 ○ ---- ○ ---- Rev.4 Signal type is updated 4

348 * MAV 22 AP 001 XG 07 MOP (B) Remote Mode 20 MOP (B) Remote Mode LOCAL/REMOTE ---- DI ---- ---- NO ---- *TPR NA *DCS T21 ---- ---- ○ ---- ○ ----

976 * MAV 22 AP 001 XG 08 MOP (B) Rack-in Position 24 MOP (B) Rack-in Position OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T21 ○ ---- ---- ---- ○ ----

349 * MAV 22 AP 001 XQ 01 MOP (B) CURRENT 15 MOP (B) CURRENT 0-100 A AIX ---- ---- ---- ---- *LVNESWB NA *MCCRIO(LV) T21 ---- ---- ○ ---- ○ ---- Rev.4a Alarm is not needed 4a

NO
350 * MAV 23 AP 001 YB 01 EOP Auto 9 EOP Auto OFF/AUTO ---- DOH DC110 1W ---- *DCS NA *DMS T22 ---- ---- ○ ---- ○ ----
PULSE
NO
351 * MAV 23 AP 001 YB 02 EOP Manual 10 EOP Manual OFF/MAN ---- DOH DC110 1W ---- *DCS NA *DMS T22 ---- ---- ○ ---- ○ ----
PULSE
NO
352 * MAV 23 AP 001 YB 03 EOP start 9 EOP start OFF/START ---- DOH DC110 1W ---- *DCS NA *DMS T22 ---- ---- ○ ---- ○ ----
PULSE
NO
353 * MAV 23 AP 001 YB 04 EOP Stop 8 EOP Stop OFF/STOP ---- DOH DC110 1W ---- *DCS NA *DMS T22 ---- ---- ○ ---- ○ ----
PULSE
AUTO shall be selected at DCS
354 * MAV 23 AP 001 XG 01 EOP Auto Mode 14 EOP Auto Mode MAN/AUTO ---- DI ---- ---- NO ---- *DMS NA *DCS T22 ○ P2 ○ ---- ○ ----
STARTUP

355 * MAV 23 AP 001 XG 02 Lube Oil Pressure LL 20 Lube Oil Pressure LL NORMAL/LOW ---- DI ---- ---- NC ---- *TPR NA *DCS T22 ---- P1 ---- ---- ○ ---- Rev.4 Signal type is updated 4

356 * MAV 23 AP 001 XG 03 EOP Auto Start 14 EOP Auto Start OFF/START ---- DI ---- ---- NO ---- *DMS NA *DCS T22 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

357 * MAV 23 AP 001 XG 04 EOP Runnning 13 EOP Runnning STOP/RUN ---- DI ---- ---- NO ---- *DMS NA *DCS T22 ○ ---- ---- ---- ○ ----

358 * MAV 23 AP 001 XG 05 EOP Trip 9 EOP Trip OFF/TRIP ---- DI ---- ---- NC ---- *DMS NA *DCS T22 ---- P1 ---- ---- ○ ---- Rev.4 Signal type is updated 4

359 * MAV 23 AP 001 XG 06 EOP Over Load 13 EOP Over Load OFF/OVERLOAD ---- DI ---- ---- NC ---- *DMS NA *DCS T22 ---- P2 ---- ---- ○ ---- Rev.4 Signal type is updated 4

360 * MAV 23 AP 001 XG 07 EOP P/S FAIL 12 EOP P/S FAIL NORMAL/ALARM ---- DI ---- ---- NC ---- *DMS NA *DCS T22 ---- P2 ---- ---- ○ ---- Rev.4 Signal type is updated 4

NO
361 * MAV 51 AP 001 YB 01 JOP start 9 JOP start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB T23 ---- ---- ○ ---- ○ ----
PULSE
NC
362 * MAV 51 AP 001 YB 02 JOP Stop 8 JOP Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB T23 ---- ---- ○ ---- ○ ----
PULSE

363 * MAV 51 AP 001 XG 01 JOP Running Indication 22 JOP Running Indication STOP/RUN ---- DI ---- ---- NO ---- *TPR NA *DCS T23 ○ ---- ---- ---- ○ ----

364 * MAV 51 AP 001 XG 02 JOP Remote Mode Selected 24 JOP Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T23 ○ ---- ○ ---- ○ ----

365 * MAV 51 AP 001 XG 03 JOP Trip Indication 19 JOP Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) T23 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

366 * MAV 51 AP 001 XG 04 JOP Rack-in Position 20 JOP Rack-in Position OFF/ON DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T23 ○ ---- ---- ---- ○ ----

367 * MAX 51 AP 001 XQ 01 JOP CURRENT 11 JOP CURRENT 0-150 A AIX ---- ---- ---- ---- *LVNESWB NA *MCCRIO(LV) T23 ---- ---- ○ ---- ○ ---- Rev.4a Alarm is not needed 4a

368 * MAV 81 AN 001 XG 01 LVCE Incoming Under Voltage 28 LVCE Incoming Under Voltage OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T24 ---- ---- ○ ---- ○ ---- Rev.4 Deleted 4

369 * MAV 81 AN 001 XG 02 Outgoing To LVCE Close Status Open 28 OG To LVCE Close Status Open OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T24 ---- ---- ○ ---- ○ ---- Rev.4 Deleted 4

370 * MAV 81 AN 001 XG 03 LVCE Incoming from EDG Close Status Close 30 LVCE IC from EDG Close Status OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T24 ---- ---- ○ ---- ○ ---- Rev.4 Deleted 4

371 * MAV 81 AN 001 XG 04 RCP EDG Running Status Run 26 RCP EDG Running Status Run OFF/ON ---- DI ---- ---- NO ---- *RCPEDG NA *DCS T24 ---- ---- ○ ---- ○ ---- Rev.4 Deleted 4

NO
372 * MAV 81 AN 001 YB 01 Oil Tank Vapour Extractor start 31 Oil Tank Vapour Extractor start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB T24 ---- ---- ○ ---- ○ ----
PULSE
NC
373 * MAV 81 AN 001 YB 02 Oil Tank Vapour Extractor Stop 30 Oil Tank Vapour Extractor Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB T24 ---- ---- ○ ---- ○ ----
PULSE

374 * MAV 81 AN 001 XG 05 Oil Tank Vapour Extractor Running Indication 29 Oil Tank Vapour Extractor Run STOP/RUN ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T24 ○ ---- ---- ---- ○ ----

375 * MAV 81 AN 001 XG 06 Oil Tank Vapour Extractor Trip Indication 30 Oil Tank Vapour Extractor Trip OFF/TRIP ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) T24 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

376 * MAV 81 AN 001 XG 07 Oil Tank Vapour Extractor Remote Mode Selected 32 Oil Tank Vapour Extractor Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T24 ○ ---- ---- ---- ○ ----

377 * MAV 81 AN 001 XG 08 Oil Tank Vapour Extractor Rack-in Position 32 Oil Tank Vapr Extrtr Rack-in Pos OFF/ON DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T24 ○ ---- ---- ---- ○ ----

378 * MAV 71 AT 001 XG 01 Oil Purifier Start 18 Oil Purifier Start STOP/RUN ---- DI ---- ---- NO ---- F NA *DCS T25 ○ ---- ---- ---- ○ ----

379 * MAV 71 AT 001 XG 02 Oil Purifier Trip 17 Oil Purifier Trip OFF/TRIP ---- DI ---- ---- NC ---- F NA *DCS T25 ---- P1 ---- ---- ○ ---- Rev.4 Signal type is updated 4

NO
380 * MAK 10 KE 001 YB 01 Turning Gear Motor Auto Command 27 Turning Gear Motor Auto Cmd OFF/AUTO ---- DOH DC110 1W ---- *DCS NA *TPR T26 ---- ---- ○ ---- ○ ----
PULSE
NO
381 * MAK 10 KE 001 YB 02 Turning Gear Motor Manual Command 29 Turning Gear Motor Manual Cmd OFF/MAN ---- DOH DC110 1W ---- *DCS NA *TPR T26 ---- ---- ○ ---- ○ ----
PULSE

988 * MAK 10 KE 001 XG 07 Turning Gear Motor Manual 25 Turning Gear Motor Manual OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T26 ○ P2 ○ ---- ○ ---- Rev.4 Signal type is updated 4

NO
382 * MAK 10 KE 001 YB 03 Turning Gear Motor start 24 Turning Gear Motor start OFF/START ---- DOH DC110 1W ---- *DCS NA *TPR T26 ---- ---- ○ ---- ○ ----
PULSE
NO
383 * MAK 10 KE 001 YB 04 Turning Gear Motor Stop 23 Turning Gear Motor Stop OFF/STOP ---- DOH DC110 1W ---- *DCS NA *TPR T26 ---- ---- ○ ---- ○ ----
PULSE

384 * MAK 10 KE 001 XG 01 Turning Gear Motor Running Indication 26 Turning Gear Motor Running STOP/RUN ---- DI ---- ---- NO ---- *TPR NA *DCS T26 ○ ---- ---- ---- ○ ----

385 * MAK 10 KE 001 XG 02 Turning Gear Motor Remote Mode Selected 30 Turning Gear Motor Remote Mode LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T26 ○ ---- ○ ---- ○ ----

386 * MAK 10 KE 001 XG 03 Turning Gear Motor Trip Indication 23 Turning Gear Motor Trip OFF/TRIP ---- DI ---- ---- NC ---- *TPR NA *DCS T26 ---- P1 ○ ---- ○ ---- Rev.4 Signal type is updated 4

387 * MAK 10 KE 001 XG 04 Turning Gear Motor Rack-in Position 30 Turning Gear Motor Rack-in Pos OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T26 ○ ---- ---- ---- ○ ----

388 * MAK 10 KE 001 XG 05 Turning Device Auto engaged Time Over 30 Turning Auto engaged Time Over OFF/ON ---- DI ---- ---- NC ---- *TPR NA *DCS T27 ---- P2 ---- ---- ○ ---- Rev.4 Signal type is updated 4

389 * MAK 10 KE 001 XG 06 Turning Device Auto engaged Progress 29 Turning Auto engaged Progress OFF/ON ---- DI ---- ---- NO ---- *TPR NA *DCS T27 ○ ---- ---- ---- ○ ----

NO
390 * MAV 11 AH 001 YB 01 Main Oil Tank Heater start 26 Main Oil Tank Heater start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB T29 ---- ---- ○ ---- ○ ----
PULSE
NC
391 * MAV 11 AH 001 YB 02 Main Oil Tank Heater Stop 25 Main Oil Tank Heater Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB T29 ---- ---- ○ ---- ○ ----
PULSE
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL

392 * MAV 11 AH 001 XG 01 Main Oil Tank Heater Running 29 Main Oil Tank Heater Running STOP/RUN ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T29 ○ ---- ---- ---- ○ ----

393 * MAV 11 AH 001 XG 02 Main Oil Tank Heater Fault Trip 31 Main Oil Tank Heater Fault Trip OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) T29 ---- P1 ○ ---- ○ ---- Rev.4 Signal type is updated 4

394 * MAV 11 AH 001 XG 03 Main Oil Tank Heater Remote Mode 27 Main Oil Tank Heater Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T29 ○ ---- ○ ---- ○ ----

NO
395 * MAX 21 AP 001 YB 01 COP (A) start 13 COP (A) start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB T35 ---- ---- ○ ---- ○ ----
PULSE
NC
396 * MAX 21 AP 001 YB 02 COP (A) Stop 12 COP (A) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB T35 ---- ---- ○ ---- ○ ----
PULSE

397 * MAX 21 AP 001 XG 01 COP (A) Running 16 COP (A) Running STOP/RUN ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T35 ○ ---- ---- ---- ○ ----

398 * MAX 21 AP 001 XG 02 COP (A) Remote Mode Selected 28 COP (A) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T35 ○ ---- ○ ---- ○ ----

399 * MAX 21 AP 001 XG 03 COP (A) Trip Indication 23 COP (A) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) T35 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

400 * MAX 21 AP 001 XG 04 COP (A) Rack-in Position 24 COP (A) Rack-in Position OFF/ON DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T35 ○ ---- ---- ---- ○ ----

401 * MAX 21 AP 001 XQ 01 COP (A) CURRENT 15 COP (A) CURRENT 0-100 A AIX ---- ---- ---- ---- *LVNESWB NA *MCCRIO(LV) T35 ---- ---- ○ ---- ○ ---- Rev.4a Alarm is not needed 4a

NO
402 * MAX 22 AP 001 YB 01 COP (B) start 13 COP (B) start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB T36 ---- ---- ○ ---- ○ ----
PULSE
NC
403 * MAX 22 AP 001 YB 02 COP (B) Stop 12 COP (B) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB T36 ---- ---- ○ ---- ○ ----
PULSE

404 * MAX 22 AP 001 XG 01 COP (B) Running Indication 26 COP (B) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T36 ○ ---- ---- ---- ○ ----

405 * MAX 22 AP 001 XG 02 COP (B) Remote Mode Selected 28 COP (B) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T36 ○ ---- ○ ---- ○ ----

406 * MAX 22 AP 001 XG 03 COP (B) Trip Indication 23 COP (B) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) T36 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

407 * MAX 22 AP 001 XG 04 COP (B) Rack-in Position 24 COP (B) Rack-in Position OFF/ON DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T36 ○ ---- ---- ---- ○ ----

408 * MAX 22 AP 001 XQ 01 COP (B) CURRENT 15 COP (B) CURRENT 0-100 A AIX ---- ---- ---- ---- *LVNESWB NA *MCCRIO(LV) T36 ---- ---- ○ ---- ○ ---- Rev.4a Alarm is not needed 4a

NO
409 * MAX 23 AN 001 YB 01 Control Oil Radiaor start 25 Control Oil Radiaor start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB T37 ---- ---- ○ ---- ○ ----
PULSE
NC
410 * MAX 23 AN 001 YB 02 Control Oil Radiaor Stop 24 Control Oil Radiaor Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB T37 ---- ---- ○ ---- ○ ----
PULSE

411 * MAX 23 AN 001 XG 01 Control Oil Radiaor Running Indication 27 Control Oil Radiaor Running STOP/RUN ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T37 ○ ---- ---- ---- ○ ----

412 * MAX 23 AN 001 XG 02 Control Oil Radiaor Remote Mode Selected 31 Control Oil Radiaor Remote Mode LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T37 ○ ---- ○ ---- ○ ----

413 * MAX 23 AN 001 XG 03 Control Oil Radiaor Trip Indication 24 Control Oil Radiaor Trip OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) T37 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

414 * MAX 23 AN 001 XG 04 Control Oil Radiaor Rack-in Position 31 Control Oil Radiaor Rack-in Pos OFF/ON DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) T37 ○ ---- ---- ---- ○ ----

NO
415 * MAG 10 AA 001 YB 01 Vaccum Breaker Valve Close command 30 Vaccum Breaker Valve Close cmd OPEN/CLOSE ---- DOW DC110 11.2W ---- *DCS U0-ARS F T40 ---- ---- ○ ---- ○ ----
LATCH
NO
416 * MAG 10 AA 001 YB 02 Vaccum Breaker Valve Close command 30 Vaccum Breaker Valve Close cmd OPEN/CLOSE ---- DOW DC110 11.2W ---- *DCS U0-ARS F T40 ---- ---- ○ ---- ○ ----
LATCH

417 * MAG 10 CG 081 XG 01 Vaccum Breaker Valve Open 25 Vaccum Breaker Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS T40 ○ ---- ○ ---- ○ ----

418 * MAG 10 CG 082 XG 02 Vaccum Breaker Valve Close 27 Vaccum Breaker Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS DCS T40 ○ ---- ○ ---- ○ ----

NO
419 * MKA 10 AH 001 YB 01 Generator Space Heater start 28 Generator Space Heater start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB T48 ---- ---- ○ ---- ○ ----
PULSE
NC
420 * MKA 10 AH 001 YB 02 Generator Space Heater Stop 27 Generator Space Heater Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB T48 ---- ---- ○ ---- ○ ----
PULSE

421 * MKA 10 AH 001 XG 01 Generator Space Heater Running 31 Generator Space Heater Running STOP/RUN ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T48 ○ ---- ---- ---- ○ ----

422 * MKA 10 AH 001 XG 02 Generator Space Heater Fault Trip 27 Gen Space Heater Fault Trip OFF/TRIP ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) T48 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

423 * MKA 10 AH 001 XG 03 Generator Space Heater Remote Mode 29 Gen Space Heater Remote Mode LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T48 ○ ---- ○ ---- ○ ----

NO
424 * MKC 10 AH 001 YB 01 Generator Exciter Space Heater start 30 Gen Exciter Space Heater start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB T49 ---- ---- ○ ---- ○ ----
PULSE
NC
425 * MKC 10 AH 001 YB 02 Generator Exciter Space Heater Stop 29 Gen Exciter Space Heater Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB T49 ---- ---- ○ ---- ○ ----
PULSE

426 * MKC 10 AH 001 XG 01 Generator Exciter Space Heater Running 32 Gen Exciter Space Heater Running STOP/RUN ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T49 ○ ---- ---- ---- ○ ----

427 * MKC 10 AH 001 XG 02 Generator Exciter Space Heater Fault Trip 29 Gen Exciter Space Heater Trip OFF/TRIP ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) T49 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

428 * MKC 10 AH 001 XG 03 Generator Exciter Space Heater Remote Mode 32 Gen Exciter Space Heater Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T49 ○ ---- ○ ---- ○ ----

NO
969 * MAX 11 AH 001 YB 01 Control Oil Tank Heater start 29 Control Oil Tank Heater start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB T50 ---- ---- ○ ---- ○ ----
PULSE
NC
970 * MAX 11 AH 001 YB 02 Control Oil Tank Heater Stop 28 Control Oil Tank Heater Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB T50 ---- ---- ○ ---- ○ ----
PULSE

971 * MAX 11 AH 001 XG 01 Control Oil Tank Heater Running 27 Control Tank Heater Running STOP/RUN ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T50 ---- ---- ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

972 * MAX 11 AH 001 XG 02 Control Oil Tank Heater Fault Trip 24 Control Tank Heater Trip OFF/TRIP ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) T50 ○ P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

973 * MAX 11 AH 001 XG 03 Control Oil Tank Heater Remote Mode 31 Ctl Oil Tank Heater Remote Mode LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T50 ○ ---- ○ ---- ○ ----

974 * MAX 11 AH 001 XG 04 Control Oil Tank Heater Rack-in Position 31 Ctl Oil Tank Heater Rack-in Pos OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) T50 ○ ---- ○ ---- ○ ----

NO
434 * MAJ 41 AA 002 YB 01 Vacuum Pump (A) Air Breathing Valve Open Command 32 VP(A) Air Breathing Vlv Open Cmd CLOSE/OPEN ---- DOW DC110 10W ---- *DCS U0-ARS F S11 ---- ---- ○ ---- ○ ---- Rev.4a Signal type is corrected 4a
LATCH

435 * MAJ 41 CG 083 XG 01 Vacuum Pump (A) Air Breathing Valve Open 31 VP(A) Air Breathing Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S11 ○ ---- ○ ---- ○ ----

436 * MAJ 41 CG 084 XG 01 Vacuum Pump (A) Air Breathing Valve Close 31 VP(A) Air Breathing Valve Close OPEN/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S11 ○ ---- ○ ---- ○ ----

NO
437 * MAJ 41 AP 001 YB 01 Vaccume Pump (A) start 22 Vaccume Pump (A) start OFF/START ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG S12 ---- ---- ○ ---- ○ ----
PULSE
NC
438 * MAJ 41 AP 001 YB 02 Vaccume Pump (A) Stop 21 Vaccume Pump (A) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG S12 ---- ---- ○ ---- ○ ----
PULSE

439 * MAJ 41 AP 001 XG 01 Vaccume Pump (A) Running Indication 24 Vaccume Pump (A) Running STOP/RUN ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) S12 ○ ---- ○ ---- ○ ----

440 * MAJ 41 AP 001 XG 02 Vaccume Pump (A) Remote Mode Selected 28 Vaccume Pump (A) Remote Mode LOCAL/REMOTE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) S12 ○ ---- ○ ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL

441 * MAJ 41 AP 001 XG 03 Vaccume Pump (A) Trip Indication 21 Vaccume Pump (A) Trip OFF/TRIP ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) S12 ---- P1 ○ ---- ○ ○ Rev.4a ANN level is corrected 4a

442 * MAJ 41 AP 001 XG 04 Vaccume Pump (A) Rack-in Position 28 Vaccume Pump (A) Rack-in Pos OFF/ON ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) S12 ○ ---- ○ ---- ○ ----

443 * MAJ 41 AP 001 XG 05 Vaccume Pump (A) Trip Circuit Healthy 27 VP (A) Trip Circuit Healthy HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) S12 ---- ---- ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

1004 * MAJ 41 AP 001 XG 06 Vacuum Pump (A) Control Power healthy 27 VP(A) Control Power healthy HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) S12 ○ ---- ---- ---- ○ ---- Rev.4a contact type is corrected 4a

NO
444 * MAJ 31 AA 001 YB 01 Ejector (A) NCG Inlet Valve Open Command 31 Ejector (A) NCG Inl Vlv Opn Cmd OFF/OPEN ---- DOL DC24 2W ---- *DCS U0-ARS F S13 ---- ---- ○ ---- ○ ----
LATCH
NO
445 * MAJ 31 AA 001 YB 02 Ejector (A) NCG Inlet Valve Close Command 31 Ejector (A) NCG Inl Vlv Cls Cmd OPEN/CLOSE ---- DOL DC24 2W ---- *DCS U0-ARS F S13 ---- ---- ○ ---- ○ ----
LATCH

446 * MAJ 31 AA 001 XG 01 Ejector (A) NCG Inlet Valve Failure 31 Ejector (A) NCG Inl Vlv Failure NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S13 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

447 * MAJ 31 AA 001 XG 02 Ejector (A) NCG Inlet Valve Torque Over 31 Ejector A NCG Inl Vlv Tor Over NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S13 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

448 * MAJ 31 CG 081 XG 03 Ejector (A) NCG Inlet Valve Open 32 Ejector (A) NCG Inlet Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S13 ○ ---- ○ ---- ○ ----

449 * MAJ 31 CG 082 XG 04 Ejector (A) NCG Inlet Valve Close 31 Ejector (A) NCG Inlet Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S13 ○ ---- ○ ---- ○ ----

450 * MAJ 31 AA 001 XG 05 Ejector (A) NCG Inlet Valve Remote Mode 32 Ejector (A) NCG Inlet Vlv Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS *DCS S13 ○ ---- ---- ---- ○ ----

451 * MAJ 31 AA 001 XG 06 Ejector (A) NCG Inlet Valve Loss of Power Source 32 Ejector (A) NCG Inl Vlv Pow Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S13 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
452 * PGB 27 AA 001 YB 01 After Condenser Cooling Water Isolating Valve Open Command 31 After Cond CW Isol Vlv Open Cmd OFF/OPEN ---- DOW DC110 25W ---- *DCS U0-ARS F S14 ---- ---- ○ ---- ○ ----
LATCH

453 * PGB 27 CG 081 XG 01 After Condenser Cooling Water Isolating Valve Open 27 After Cond CW Isol Vlv Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S14 ○ ---- ○ ---- ○ ----

454 * PGB 27 CG 082 XG 02 After Condenser Cooling Water Isolating Valve Close 28 After Cond CW Isol Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S14 ○ ---- ○ ---- ○ ----

NO
455 * LBG 31 AA 001 YB 01 Ejector (A) Driving Steam Inlet Valve Open Command 32 Ejc (A) Driv Stm Int Vlv Opn Cmd CLOSE/OPEN ---- DOW DC110 25W ---- *DCS U0-ARS F S15 ---- ---- ○ ---- ○ ----
LATCH

456 * LBG 31 CG 081 XG 01 Ejector (A) Driving Steam Inlet Valve Open 31 Ejc (A) Driv Steam Int Vlv Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S15 ○ ---- ○ ---- ○ ----

457 * LBG 31 CG 082 XG 02 Ejector (A) Driving Steam Inlet Valve Close 32 Ejc (A) Driv Steam Int Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S15 ○ ---- ○ ---- ○ ----

NO
458 * MAJ 41 AA 001 YB 01 Vacuum Pump (A) Inlet Isolation Valve Open Command 32 VP (A) NCG Inl Isol Vlv Open Cmd OFF/OPEN ---- DOL DC24 2W ---- *DCS U0-ARS F S16 ---- ---- ○ ---- ○ ----
LATCH
NO
459 * MAJ 41 AA 001 YB 02 Vacuum Pump (A) Inlet Isolation Valve Close Command 32 VP (A) NCG Inl Isol Vlv Cls Cmd OFF/CLOSE ---- DOL DC24 2W ---- *DCS U0-ARS F S16 ---- ---- ○ ---- ○ ----
LATCH

460 * MAJ 41 AA 001 XG 01 Vacuum Pump (A) Inlet Isolation Valve Failure 30 VP (A) NCG Inlet Isol Vlv Fail NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S16 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

461 * MAJ 41 AA 001 XG 02 Vacuum Pump (A) Inlet Isolation Valve Torque Over 32 VP (A) NCG Inlet Valve Trq Over NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S16 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

462 * MAJ 41 CG 081 XG 03 Vacuum Pump (A) Inlet Isolation Valve Open 32 VP (A) NCG Inlet Isol Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S16 ○ ---- ○ ---- ○ ----

463 * MAJ 41 CG 082 XG 04 Vacuum Pump (A) Inlet Isolation Valve Close 31 VP (A) NCG Inlet Isol Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S16 ○ ---- ○ ---- ○ ----

464 * MAJ 41 AA 001 XG 05 Vacuum Pump (A) Inlet Isolation Valve Remote Mode 32 VP (A) NCG Inlet Isol Vlv Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS *DCS S16 ○ ---- ---- ---- ○ ----

465 * MAJ 41 AA 001 XG 06 Vacuum Pump (A) Inlet Isolation Valve Loss of Power Source 32 VP (A) NCG Inl Isol Vlv Pow Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S16 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
466 * MAJ 42 AA 002 YB 01 Vacuum Pump (B) Air Breathing Valve Open Command 32 VP(B) Air Breathing Vlv Open Cmd CLOSE/OPEN ---- DOW DC110 10W ---- *DCS U0-ARS F S21 ---- ---- ○ ---- ○ ----
LATCH

467 * MAJ 42 CG 083 XG 01 Vacuum Pump (B) Air Breathing Valve Open 31 VP (B) Air Breathing Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S21 ○ ---- ○ ---- ○ ----

468 * MAJ 42 CG 084 XG 01 Vacuum Pump (B) Air Breathing Valve Close 32 VP (B) Air Breathing Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S21 ○ ---- ○ ---- ○ ----

NO
469 * MAJ 42 AP 001 YB 01 Vaccume Pump (B) start 22 Vaccume Pump (B) start OFF/START ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG S22 ---- ---- ○ ---- ○ ----
PULSE
NC
470 * MAJ 42 AP 001 YB 02 Vaccume Pump (B) Stop 21 Vaccume Pump (B) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG S22 ---- ---- ○ ---- ○ ----
PULSE

471 * MAJ 42 AP 001 XG 01 Vaccume Pump (B) Running Indication 24 Vaccume Pump (B) Running STOP/RUN ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) S22 ○ ---- ○ ---- ○ ----

472 * MAJ 42 AP 001 XG 02 Vaccume Pump (B) Remote Mode Selected 28 Vaccume Pump (B) Remote Mode LOCAL/REMOTE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) S22 ○ ---- ○ ---- ○ ----

473 * MAJ 42 AP 001 XG 03 Vaccume Pump (B) Trip Indication 32 Vaccume Pump (B) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) S22 ---- P1 ○ ---- ○ ○ Rev.4a ANN level is corrected 4a

474 * MAJ 42 AP 001 XG 04 Vaccume Pump (B) Rack-in Position 28 Vaccume Pump (B) Rack-in Pos OFF/ON ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) S22 ○ ---- ○ ---- ○ ----

475 * MAJ 42 AP 001 XG 05 Vaccume Pump (B) Trip Circuit Healthy 27 VP (B) Trip Circuit Healthy HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) S22 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

1005 * MAJ 42 AP 001 XG 06 Vacuum Pump (B) Control Power healthy 27 VP(B) Control Power healthy HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) S12 ○ ---- ---- ---- ○ ---- Rev.4a contact type is corrected 4a

NO
476 * MAJ 32 AA 001 YB 01 Ejector (B) NCG Inlet Valve Open Command 31 Ejector (B) NCG Int Vlv Opn Cmd OFF/OPEN ---- DOL DC24 2W ---- *DCS U0-ARS F S23 ---- ---- ○ ---- ○ ----
LATCH
NO
477 * MAJ 32 AA 001 YB 02 Ejector (B) NCG Inlet Valve Close Command 31 Ejector (B) NCG Int Vlv Cls Cmd OFF/CLOSE ---- DOL DC24 2W ---- *DCS U0-ARS F S23 ---- ---- ○ ---- ○ ----
LATCH

478 * MAJ 32 AA 001 XG 01 Ejector (B) NCG Inlet Valve Failure 31 Ejector (B) NCG Int Vlv Failure NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S23 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

479 * MAJ 32 AA 001 XG 02 Ejector (B) NCG Inlet Valve Torque Over 31 Ejector B NCG Int Vlv Tor Over NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S23 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

480 * MAJ 32 CG 081 XG 03 Ejector (B) NCG Inlet Valve Open 30 Ejector (B) NCG Inlet Vlv Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S23 ○ ---- ○ ---- ○ ----

481 * MAJ 32 CG 082 XG 04 Ejector (B) NCG Inlet Valve Close 31 Ejector (B) NCG Inlet Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S23 ○ ---- ○ ---- ○ ----

482 * MAJ 32 AA 001 XG 05 Ejector (B) NCG Inlet Valve Remote Mode 30 Ejector (B) NCG Int Vlv Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS *DCS S23 ○ ---- ---- ---- ○ ----

483 * MAJ 32 AA 001 XG 06 Ejector (B) NCG Inlet Valve Loss of Power Source 31 Ejector (B) NCG Int Vlv Pow Los NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S23 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
484 * LBG 32 AA 001 YB 01 Ejector (B) Driving Steam Inlet Valve Open Command 32 Ejc (B) Driv Stm Int Vlv Opn Cmd CLOSE/OPEN ---- DOW DC110 25W ---- *DCS U0-ARS F S25 ---- ---- ○ ---- ○ ----
LATCH

485 * LBG 32 CG 081 XG 01 Ejector (B) Driving Steam Inlet Valve Open 31 Ejc (B) Driv Steam Int Vlv Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S25 ○ ---- ○ ---- ○ ----

486 * LBG 32 CG 082 XG 02 Ejector (B) Driving Steam Inlet Valve Close 32 Ejc (B) Driv Steam Int Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S25 ○ ---- ○ ---- ○ ----

NO
487 * MAJ 42 AA 001 YB 01 Vacuum Pump (B) Inlet Isolation Valve Open Command 32 VP (B) NCG Int Isol Vlv Open Cmd OFF/OPEN ---- DOL DC24 2W ---- *DCS U0-ARS F S26 ---- ---- ○ ---- ○ ----
LATCH
NO
488 * MAJ 42 AA 001 YB 02 Vacuum Pump (B) Inlet Isolation Valve Close Command 32 VP (B) NCG Int Isol Vlv Cls Cmd OFF/CLOSE ---- DOL DC24 2W ---- *DCS U0-ARS F S26 ---- ---- ○ ---- ○ ----
LATCH
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL

489 * MAJ 42 AA 001 XG 01 Vacuum Pump (B) Inlet Isolation Valve Failure 30 VP (B) NCG Inlet Isol Vlv Fail NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S26 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

490 * MAJ 42 AA 001 XG 02 Vacuum Pump (B) Inlet Isolation Valve Torque Over 32 VP (B) NCG Inl Isol Vlv Trq Ovr NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S26 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

491 * MAJ 42 CG 081 XG 03 Vacuum Pump (B) Inlet Isolation Valve Open 32 VP (B) NCG Inlet Isol Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S26 ○ ---- ○ ---- ○ ----

492 * MAJ 42 CG 082 XG 04 Vacuum Pump (B) Inlet Isolation Valve Close 31 VP (B) NCG Inlet Isol Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S26 ○ ---- ○ ---- ○ ----

493 * MAJ 42 AA 001 XG 05 Vacuum Pump (B) Inlet Isolation Valve Remote Mode 32 VP (B) NCG Inlet Isol Vlv Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS *DCS S26 ○ ---- ---- ---- ○ ----

494 * MAJ 42 AA 001 XG 06 Vacuum Pump (B) Inlet Isolation Valve Loss of Power Source 32 VP (B) NCG Inl Isol Vlv Pow Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S26 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
495 * MAJ 33 AA 001 YB 01 Ejector (C) NCG Inlet Valve Open Command 31 Ejector (C) NCG Inl Vlv Opn Cmd OFF/OPEN ---- DOL DC24 2W ---- *DCS U0-ARS F S33 ---- ---- ○ ---- ○ ----
LATCH
NO
496 * MAJ 33 AA 001 YB 02 Ejector (C) NCG Inlet Valve Close Command 31 Ejector (C) NCG Inl Vlv Cls Cmd OFF/CLOSE ---- DOL DC24 2W ---- *DCS U0-ARS F S33 ---- ---- ○ ---- ○ ----
LATCH

497 * MAJ 33 AA 001 XG 01 Ejector (C) NCG Inlet Valve Failure 31 Ejector (C) NCG Inl Vlv Failure NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S33 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

498 * MAJ 33 AA 001 XG 02 Ejector (C) NCG Inlet Valve Torque Over 31 Ejector C NCG Inl Vlv Trq Over NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S33 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

499 * MAJ 33 CG 081 XG 03 Ejector (C) NCG Inlet Valve Open 32 Ejector (C) NCG Inlet Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S33 ○ ---- ○ ---- ○ ----

500 * MAJ 33 CG 082 XG 04 Ejector (C) NCG Inlet Valve Close 31 Ejector (C) NCG Inlet Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S33 ○ ---- ○ ---- ○ ----

501 * MAJ 33 AA 001 XG 05 Ejector (C) NCG Inlet Valve Remote Mode 32 Ejector (C) NCG Inlet Vlv Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS *DCS S33 ○ ---- ---- ---- ○ ----

502 * MAJ 33 AA 001 XG 06 Ejector (C) NCG Inlet Valve Loss of Power Source 31 Ejector (C) NCG Inl Vlv Pow Los NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S33 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
503 * LBG 33 AA 001 YB 01 Ejector (C) Driving Steam Inlet Valve Open Command 32 Ejc (C) Driv Stm Inl Vlv Opn Cmd CLOSE/OPEN ---- DOW DC110 25W ---- *DCS U0-ARS F S35 ---- ---- ○ ---- ○ ----
LATCH

504 * LBG 33 CG 081 XG 01 Ejector (C) Driving Steam Inlet Valve Open 31 Ejc (C) Driv Steam Inl Vlv Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S35 ○ ---- ○ ---- ○ ----

505 * LBG 33 CG 082 XG 02 Ejector (C) Driving Steam Inlet Valve Close 32 Ejc (C) Driv Steam Inl Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S35 ○ ---- ○ ---- ○ ----

NO
506 * MAJ 50 AA 001 YB 01 Back up Ejector Inlet Valve Open Command 30 Back up Ejc Inlet Vlv Open Cmd OFF/OPEN ---- DOL DC24 2W ---- *DCS U0-ARS F S43 ---- ---- ○ ---- ○ ----
LATCH
NO
507 * MAJ 50 AA 001 YB 02 Back up Ejector Inlet Valve Close Command 31 Back up Ejc Inlet Vlv Close Cmd OFF/CLOSE ---- DOL DC24 2W ---- *DCS U0-ARS F S43 ---- ---- ○ ---- ○ ----
LATCH

508 * MAJ 50 AA 001 XG 01 Back up Ejector Inlet Valve Failure 31 Back up Ejc Inlet Valve Failure NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S43 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

509 * MAJ 50 AA 001 XG 02 Back up Ejector Inlet Valve Torque Over 30 Back up Ejc Inlet Vlv Trq Over NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S43 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

510 * MAJ 50 CG 081 XG 03 Back up Ejector Inlet Valve Open 32 Back up Ejector Inlet Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S43 ○ ---- ○ ---- ○ ----

511 * MAJ 50 CG 082 XG 04 Back up Ejector Inlet Valve Close 31 Back up Ejector Inlet Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S43 ○ ---- ○ ---- ○ ----

512 * MAJ 50 AA 001 XG 05 Back up Ejector Inlet Valve Remote Mode 32 Back up Ejector Inlet Vlv Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS *DCS S43 ○ ---- ---- ---- ○ ----

513 * MAJ 50 AA 001 XG 06 Back up Ejector Inlet Valve Loss of Power Source 32 Back up Ejector Inl Vlv Pow Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS S43 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
514 * LBG 20 AA 001 YB 01 Back Up Ejector Driving Steam Inlet Valve Open Command 31 BU Ejc Driv Stm Inl Vlv Opn Cmd CLOSE/OPEN ---- DOW DC110 25W ---- *DCS U0-ARS F S45 ---- ---- ○ ---- ○ ----
LATCH

515 * LBG 20 CG 081 XG 01 Back Up Ejector Driving Steam Inlet Valve Open 28 BU Ejc Driv Stm Inl Vlv Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S45 ○ ---- ○ ---- ○ ----

516 * LBG 20 CG 082 XG 02 Back Up Ejector Driving Steam Inlet Valve Close 28 BU Ejc Driv Stm In Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S45 ○ ---- ○ ---- ○ ----

517 * LCA 21 CG 081 XG 01 HWP(A) Suction Valve Open 23 HWP(A) Inlet Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS W01 ---- ---- ○ ---- ○ ----

NO
518 * LCA 21 AP 001 YB 01 HWP(A) start 12 HWP(A) start OFF/START ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG W01 ---- ---- ○ ---- ○ ----
PULSE
NC
519 * LCA 21 AP 001 YB 02 HWP(A) Stop 11 HWP(A) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG W01 ---- ---- ○ ---- ○ ----
PULSE

520 * LCA 21 AP 001 XG 01 HWP(A) Running Indication 25 HWP(A) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *TPR NA *DCS W01 ○ ---- ○ ---- ○ ----

521 * LCA 21 AP 001 XG 02 HWP(A) Remote Mode Selected 27 HWP(A) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) W01 ○ ---- ---- ---- ○ ----

522 * LCA 21 AP 001 XG 03 HWP(A) Trip Indication 22 HWP(A) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) W01 ---- P1 ○ ---- ○ ○ Rev.4a ANN level is corrected 4a

523 * LCA 21 AP 001 XG 04 HWP(A) Rack-in Position 23 HWP(A) Rack-in Position OFF/ON ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) W01 ○ ---- ---- ---- ○ ----

524 * LCA 21 AP 001 XG 05 HWP(A) Trip Circuit Healthy 27 HWP(A) Trip Circuit Healthy HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) W01 ○ ---- ---- ---- ○ ----

1002 * LCA 21 AP 001 XG 06 HWP(A) Control Power healthy 29 HWP(A) Control Power healthy HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) W01 ○ ---- ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

NO
525 * LCA 23 AA 001 YB 01 HWP(A) Minimum Flow Valve Open Command 30 HWP(A) Min Flow Valve Open Cmd OFF/OPEN ---- DOL DC24 2W ---- *DCS U0-ARS F W02 ---- ---- ○ ---- ○ ----
LATCH
NO
526 * LCA 23 AA 001 YB 02 HWP(A) Minimum Flow Valve Close Command 31 HWP(A) Min Flow Valve Close Cmd OFF/CLOSE ---- DOL DC24 2W ---- *DCS U0-ARS F W02 ---- ---- ○ ---- ○ ----
LATCH

527 * LCA 23 AA 001 XG 01 HWP(A) Minimum Flow Valve Failure 29 HWP(A) Min Flow Valve Failure NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W02 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

528 * LCA 23 AA 001 XG 02 HWP(A) Minimum Flow Valve Torque Over 31 HWP(A) Min Flow Valve Trq Over NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W02 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

529 * LCA 23 CG 081 XG 03 HWP(A) Minimum Flow Valve Open 30 HWP(A) Minimum Flow Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS W02 ○ ---- ○ ---- ○ ----

530 * LCA 23 CG 082 XG 04 HWP(A) Minimum Flow Valve Close 31 HWP(A) Minimum Flow Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS W02 ○ ---- ○ ---- ○ ----

531 * LCA 23 AA 001 XG 05 HWP(A) Minimum Flow Valve Remote Mode 28 HWP(A) Min Flow Valve Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS *DCS W02 ○ ---- ○ ---- ○ ----

532 * LCA 23 AA 001 XG 06 HWP(A) Minimum Flow Valve Loss of Power Source 30 HWP(A) Min Flow Valve Pow Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W02 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
533 * LCA 31 AA 001 YB 01 HWP(A) Outlet Isolation Valve Open Command 31 HWP(A) Outlet Isol Vlv Open Cmd OFF/OPEN ---- DOL DC24 2W ---- *DCS U0-ARS F W03 ---- ---- ○ ---- ○ ----
LATCH
NO
534 * LCA 31 AA 001 YB 02 HWP(A) Outlet Isolation Valve Close Command 32 HWP(A) Outlet Isol Vlv Close Cmd OFF/CLOSE ---- DOL DC24 2W ---- *DCS U0-ARS F W03 ---- ---- ○ ---- ○ ----
LATCH

535 * LCA 31 AA 001 XG 01 HWP(A) Outlet Isolation Valve Failure 30 HWP(A) Outlet Isol Vlv Failure NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W03 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

536 * LCA 31 AA 001 XG 02 HWP(A) Outlet Isolation Valve Torque Over 32 HWP(A) Outlet Isol Vlv Trq Over NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W03 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

537 * LCA 31 CG 081 XG 03 HWP(A) Outlet Isolation Valve Open 27 HWP(A) Outlet Isol Vlv Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS W03 ○ ---- ○ ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL

538 * LCA 31 CG 082 XG 04 HWP(A) Outlet Isolation Valve Close 28 HWP(A) Outlet Isol Vlv Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS W03 ○ ---- ○ ---- ○ ----

539 * LCA 31 AA 001 XG 05 HWP(A) Outlet Isolation Valve Remote Mode 29 HWP(A) Outlet Isol Vlv Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS *DCS W03 ○ ---- ○ ---- ○ ----

540 * LCA 31 AA 001 XG 06 HWP(A) Outlet Isolation Valve Loss of Power Source 31 HWP(A) Outlet Isol Vlv Pow Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W03 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

541 * LCA 22 CG 081 XG 01 HWP(B) Suction Valve Open 25 HWP(B) Suction Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS W04 ---- ---- ○ ---- ○ ----

NO
542 * LCA 22 AP 001 YB 01 HWP(B) start 12 HWP(B) start OFF/START ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG W04 ---- ---- ○ ---- ○ ----
PULSE
NC
543 * LCA 22 AP 001 YB 02 HWP(B) Stop 11 HWP(B) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG W04 ---- ---- ○ ---- ○ ----
PULSE

544 * LCA 22 AP 001 XG 01 HWP(B) Running Indication 25 HWP(B) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *TPR NA *DCS W04 ---- ---- ○ ---- ○ ----

545 * LCA 22 AP 001 XG 02 HWP(B) Remote Mode Selected 27 HWP(B) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) W04 ○ ---- ---- ---- ○ ----

546 * LCA 22 AP 001 XG 03 HWP(B) Trip Indication 22 HWP(B) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) W04 ---- P1 ○ ---- ○ ○ Rev.4a ANN level is corrected 4a

547 * LCA 22 AP 001 XG 04 HWP(B) Rack-in Position 23 HWP(B) Rack-in Position OFF/ON ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) W04 ○ ---- ---- ---- ○ ----

548 * LCA 22 AP 001 XG 05 HWP(B) Trip Circuit Healthy 27 HWP(B) Trip Circuit Healthy HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) W04 ○ ---- ---- ---- ○ ----

1003 * LCA 22 AP 001 XG 06 HWP(B) Control Power healthy 28 HWP(B) Control Power healthy HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) W04 ○ ---- ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

NO
549 * LCA 24 AA 001 YB 01 HWP(B) Minimum Flow Valve Open Command 30 HWP(B) Min Flow Valve Open Cmd OFF/OPEN ---- DOL DC24 2W ---- *DCS U0-ARS F W05 ---- ---- ○ ---- ○ ----
LATCH
NO
550 * LCA 24 AA 001 YB 02 HWP(B) Minimum Flow Valve Close Command 31 HWP(B) Min Flow Valve Close Cmd OFF/CLOSE ---- DOL DC24 2W ---- *DCS U0-ARS F W05 ---- ---- ○ ---- ○ ----
LATCH

551 * LCA 24 AA 001 XG 01 HWP(B) Minimum Flow Valve Failure 29 HWP(B) Min Flow Valve Failure NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W05 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

552 * LCA 24 AA 001 XG 02 HWP(B) Minimum Flow Valve Torque Over 31 HWP(B) Min Flow Valve Trq Over NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W05 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

553 * LCA 24 CG 081 XG 03 HWP(B) Minimum Flow Valve Open 30 HWP(B) Minimum Flow Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS W05 ○ ---- ○ ---- ○ ----

554 * LCA 24 CG 082 XG 04 HWP(B) Minimum Flow Valve Close 31 HWP(B) Minimum Flow Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS W05 ○ ---- ○ ---- ○ ----

555 * LCA 24 AA 001 XG 05 HWP(B) Minimum Flow Valve Remote Mode 28 HWP(B) Min Flow Valve Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS *DCS W05 ○ ---- ○ ---- ○ ----

556 * LCA 24 AA 001 XG 06 HWP(B) Minimum Flow Valve Loss of Power Source 30 HWP(B) Min Flow Valve Pow Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W05 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
557 * LCA 32 AA 001 YB 01 HWP(B) Outlet Isolation Valve Open Command 31 HWP(B) Outlet Isol Vlv Open Cmd OFF/OPEN ---- DOL DC24 2W ---- *DCS U0-ARS F W06 ---- ---- ○ ---- ○ ----
LATCH
NO
558 * LCA 32 AA 001 YB 02 HWP(B) Outlet Isolation Valve Close Command 32 HWP(B) Outlet Isol Vlv Close Cmd OFF/CLOSE ---- DOL DC24 2W ---- *DCS U0-ARS F W06 ---- ---- ○ ---- ○ ----
LATCH

559 * LCA 32 AA 001 XG 01 HWP(B) Outlet Isolation Valve Failure 30 HWP(B) Outlet Isol Vlv Failure NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W06 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

560 * LCA 32 AA 001 XG 02 HWP(B) Outlet Isolation Valve Torque Over 32 HWP(B) Outlet Isol Vlv Trq Over NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W06 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

561 * LCA 32 CG 081 XG 03 HWP(B) Outlet Isolation Valve Open 29 HWP(B) Outlet Isol Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS W06 ○ ---- ○ ---- ○ ----

562 * LCA 32 CG 082 XG 04 HWP(B) Outlet Isolation Valve Close 30 HWP(B) Outlet Isol Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS W06 ○ ---- ○ ---- ○ ----

563 * LCA 32 AA 001 XG 05 HWP(B) Outlet Isolation Valve Remote Mode 31 HWP(B) Outlet Isol Valve Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS *DCS W06 ○ ---- ○ ---- ○ ----

564 * LCA 32 AA 001 XG 06 HWP(B) Outlet Isolation Valve Loss of Power Source 31 HWP(B) Outlet Isol Vlv Pow Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS *DCS W06 ---- P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
565 * PGB 11 AP 001 YB 01 ACWP(A) start 13 ACWP(A) start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB W09 ---- ---- ○ ---- ○ ----
PULSE
NC
566 * PGB 11 AP 001 YB 02 ACWP(A) Stop 12 ACWP(A) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB W09 ---- ---- ○ ---- ○ ----
PULSE

567 * PGB 11 AP 001 XG 01 ACWP(A) Running Indication 26 ACWP(A) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *TPR NA *DCS W09 ○ P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

568 * PGB 11 AP 001 XG 02 ACWP(A) Remote Mode Selected 28 ACWP(A) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) W09 ○ ---- ○ ---- ○ ----

569 * PGB 11 AP 001 XG 03 ACWP(A) Trip Indication 23 ACWP(A) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) W09 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

570 * PGB 11 AP 001 XG 04 ACWP(A) Rack-in Position 24 ACWP(A) Rack-in Position OFF/ON DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) W09 ○ ---- ---- ---- ○ ----

NO
571 * PGB 12 AP 001 YB 01 ACWP(B) start 13 ACWP(B) start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB W10 ---- ---- ○ ---- ○ ----
PULSE
NC
572 * PGB 12 AP 001 YB 02 ACWP(B) Stop 12 ACWP(B) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB W10 ---- ---- ○ ---- ○ ----
PULSE

573 * PGB 12 AP 001 XG 01 ACWP(B) Running Indication 26 ACWP(B) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *TPR NA *DCS W10 ○ P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

574 * PGB 12 AP 001 XG 02 ACWP(B) Remote Mode Selected 28 ACWP(B) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) W10 ○ ---- ○ ---- ○ ----

575 * PGB 12 AP 001 XG 03 ACWP(B) Trip Indication 23 ACWP(B) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) W10 ---- P1 ○ ---- ○ ---- Rev.4a Contact type is corrected 4a

576 * PGB 12 AP 001 XG 04 ACWP(B) Rack-in Position 24 ACWP(B) Rack-in Position OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) W10 ○ ---- ○ ---- ○ ----

NO
577 * PAD 01 AN 001 YB 01 Cooling Tower Fan (A) Start 27 Cooling Tower Fan (A) Start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W15 ---- ---- ○ ---- ○ ----
PULSE
NC
578 * PAD 01 AN 001 YB 02 Cooling Tower Fan (A) Stop 26 Cooling Tower Fan (A) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W15 ---- ---- ○ ---- ○ ----
PULSE

579 * PAD 01 AN 001 XG 01 Cooling Tower Fan (A) Running Indication 28 CT Fan(A) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W15 ○ ---- ○ ---- ○ ----

580 * PAD 01 AN 001 XG 02 Cooling Tower Fan(A) Remote Mode Selected 30 CT Fan(A) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W15 ○ ---- ---- ---- ○ ----

18 7.0
581 * PAD 01 AN 001 XG 03 Cooling Tower Fan(A) Trip Indication 25 CT Fan(A) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) W15 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P1) (P2)

582 * PAD 01 AN 001 XG 04 Cooling Tower Fan (A) Rack-in Position 27 CT Fan (A) Rack-in Position OFF/ON ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W15 ○ ---- ---- ---- ○ ----

NO
583 * PAD 02 AN 001 YB 01 Cooling Tower Fan (B) Start 27 Cooling Tower Fan (B) Start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W16 ---- ---- ○ ---- ○ ----
PULSE
NC
584 * PAD 02 AN 001 YB 02 Cooling Tower Fan (B) Stop 26 Cooling Tower Fan (B) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W16 ---- ---- ○ ---- ○ ----
PULSE

585 * PAD 02 AN 001 XG 01 Cooling Tower Fan (B) Running Indication 28 CT Fan(B) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W16 ○ ---- ○ ---- ○ ----

586 * PAD 02 AN 001 XG 02 Cooling Tower Fan(B) Remote Mode Selected 30 CT Fan(B) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W16 ○ ---- ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL

587 * PAD 02 AN 001 XG 03 Cooling Tower Fan(B) Trip Indication 25 CT Fan(B) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) W16 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

588 * PAD 02 AN 001 XG 04 Cooling Tower Fan (B) Rack-in Position 27 CT Fan (B) Rack-in Position OFF/ON DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W16 ○ ---- ---- ---- ○ ----

NO
589 * PAD 03 AN 001 YB 01 Cooling Tower Fan (C) Start 27 Cooling Tower Fan (C) Start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W17 ---- ---- ○ ---- ○ ----
PULSE
NC
590 * PAD 03 AN 001 YB 02 Cooling Tower Fan (C) Stop 26 Cooling Tower Fan (C) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W17 ---- ---- ○ ---- ○ ----
PULSE

591 * PAD 03 AN 001 XG 01 Cooling Tower Fan (C) Running Indication 28 CT Fan(C) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W17 ○ ---- ○ ---- ○ ----

592 * PAD 03 AN 001 XG 02 Cooling Tower Fan(C) Remote Mode Selected 30 CT Fan(C) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W17 ○ ---- ---- ---- ○ ----

593 * PAD 03 AN 001 XG 03 Cooling Tower Fan(C) Trip Indication 25 CT Fan(C) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) W17 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

594 * PAD 03 AN 001 XG 04 Cooling Tower Fan (C) Rack-in Position 27 CT Fan (C) Rack-in Position OFF/ON DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W17 ○ ---- ---- ---- ○ ----

NO
595 * PAD 04 AN 001 YB 01 Cooling Tower Fan (D) Start 27 Cooling Tower Fan (D) Start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W18 ---- ---- ○ ---- ○ ----
PULSE
NC
596 * PAD 04 AN 001 YB 02 Cooling Tower Fan (D) Stop 26 Cooling Tower Fan (D) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W18 ---- ---- ○ ---- ○ ----
PULSE

597 * PAD 04 AN 001 XG 01 Cooling Tower Fan (D) Running Indication 28 CT Fan(D) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W18 ○ ---- ○ ---- ○ ----

598 * PAD 04 AN 001 XG 02 Cooling Tower Fan(D) Remote Mode Selected 30 CT Fan(D) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W18 ○ ---- ---- ---- ○ ----

599 * PAD 04 AN 001 XG 03 Cooling Tower Fan(D) Trip Indication 25 CT Fan(D) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) W18 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

600 * PAD 04 AN 001 XG 04 Cooling Tower Fan (D) Rack-in Position 27 CT Fan (D) Rack-in Position OFF/ON DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W18 ○ ---- ---- ---- ○ ----

NO
601 * PAD 05 AN 001 YB 01 Cooling Tower Fan (E) Start 27 Cooling Tower Fan (E) Start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W19 ---- ---- ○ ---- ○ ----
PULSE
NC
602 * PAD 05 AN 001 YB 02 Cooling Tower Fan (E) Stop 26 Cooling Tower Fan (E) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W19 ---- ---- ○ ---- ○ ----
PULSE

603 * PAD 05 AN 001 XG 01 Cooling Tower Fan (E) Running Indication 28 CT Fan(E) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W19 ○ ---- ○ ---- ○ ----

604 * PAD 05 AN 001 XG 02 Cooling Tower Fan(E) Remote Mode Selected 30 CT Fan(E) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W19 ○ ---- ---- ---- ○ ----

605 * PAD 05 AN 001 XG 03 Cooling Tower Fan(E) Trip Indication 25 CT Fan(E) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) W19 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

606 * PAD 05 AN 001 XG 04 Cooling Tower Fan (E) Rack-in Position 26 CT Fan(E) Rack-in Position OFF/ON DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W19 ○ ---- ---- ---- ○ ----

NO
607 * PAD 06 AN 001 YB 01 Cooling Tower Fan (F) Start 27 Cooling Tower Fan (F) Start OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W20 ---- ---- ○ ---- ○ ----
PULSE
NC
608 * PAD 06 AN 001 YB 02 Cooling Tower Fan (F) Stop 26 Cooling Tower Fan (F) Stop OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG W20 ---- ---- ○ ---- ○ ----
PULSE

609 * PAD 06 AN 001 XG 01 Cooling Tower Fan (F) Running Indication 28 CT Fan(F) Running Indication STOP/RUN ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W20 ○ ---- ○ ---- ○ ----

610 * PAD 06 AN 001 XG 02 Cooling Tower Fan(F) Remote Mode Selected 30 CT Fan(F) Remote Mode Selected LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W20 ○ ---- ---- ---- ○ ----

611 * PAD 06 AN 001 XG 03 Cooling Tower Fan(F) Trip Indication 25 CT Fan(F) Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) W20 ---- P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

612 * PAD 06 AN 001 XG 04 Cooling Tower Fan (F) Rack-in Position 26 CT Fan(F) Rack-in Position OFF/ON DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) W20 ○ ---- ---- ---- ○ ----

NO
613 * LCA 81 AA 001 YB 01 MCW Condensate Zone Inlet Valve (A) Control 30 MCW Cond Zone Inl Vlv (A) Ctrl OFF/CONTROL ---- DOW DC110 25W ---- *DCS U0-ARS F W27 ---- ---- ○ ---- ○ ----
LATCH
NO
614 * LCA 82 AA 001 YB 01 MCW Condensate Zone Inlet Valve (B) Control 30 MCW Cond Zone Inl Vlv (B) Ctrl OFF/CONTROL ---- DOW DC110 25W ---- *DCS U0-ARS F W27 ---- ---- ○ ---- ○ ----
LATCH
NO
615 * LCA 70 AA 001 YB 01 Siphon Breaker Valve Open Command A 31 Siphon Breaker Valve Open Cmd A OFF/OPEN ---- DOW DC110 20W ---- *DCS U0-ARS F W28 ---- ---- ○ ---- ○ ----
LATCH
NO
991 * LCA 70 AA 002 YB 01 Siphon Breaker Valve Open Command B 31 Siphon Breaker Valve Open Cmd B OFF/OPEN ---- DOW DC110 20W ---- *DCS U0-ARS F W28 ---- ---- ○ ---- ○ ----
LATCH

616 * LCA 70 CG 081 XG 01 Siphon Breaker Valve Open 25 Siphon Breaker Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS W28 ○ ---- ○ ---- ○ ----

617 * LCA 70 CG 082 XG 02 Siphon Breaker Valve Close 26 Siphon Breaker Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS W28 ○ ---- ○ ---- ○ ----

NO
618 * GMF 11 AP 001 YB 01 GRS U Seal Pit Sump Pump (A) Start 30 U Seal Pit Sump Pump (A) Start OFF/START ---- DOL DC24 1W ---- *MCCRIO(LV) NA *LVESWB W35 ---- ---- ○ ---- ○ ----
PULSE
NC
619 * GMF 11 AP 001 YB 02 GRS U Seal Pit Sump Pump (A) Stop 29 U Seal Pit Sump Pump (A) Stop OFF/STOP ---- DOL DC24 1W ---- *MCCRIO(LV) NA *LVESWB W35 ---- ---- ○ ---- ○ ----
PULSE

620 * GMF 11 AP 001 XG 01 GRS U Seal Pit Sump Pump (A) Running Indication 32 U Seal Pit Sump Pump (A) Running STOP/RUN ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) W35 ○ ---- ---- ---- ○ ----

621 * GMF 11 AP 001 XG 02 GRS U Seal Pit Sump Pump (A) Fault Trip 29 U Seal Pit Sump Pump (A) Trip OFF/TRIP ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) W35 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

622 * GMF 11 AP 001 XG 03 GRS U Seal Pit Sump Pump (A) Remote Mode Selected 31 U Seal Pit Sump Pump (A) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) W35 ○ ---- ○ ---- ○ ----

623 * GMF 11 AP 001 XG 04 GRS U Seal Pit Sump Pump (A) Rack-in Position 32 U Seal Sump Pump (A) Rack-in Pos OFF/ON DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) W35 ○ ---- ---- ---- ○ ----

NO
624 * GMF 11 AP 002 YB 01 GRS U Seal Pit Sump Pump (B) Start 30 U Seal Pit Sump Pump (B) Start OFF/START ---- DOL DC24 1W ---- *MCCRIO(LV) NA *LVESWB W36 ---- ---- ○ ---- ○ ----
PULSE
NC
625 * GMF 11 AP 002 YB 02 GRS U Seal Pit Sump Pump (B) Stop 29 U Seal Pit Sump Pump (B) Stop OFF/STOP ---- DOL DC24 1W ---- *MCCRIO(LV) NA *LVESWB W36 ---- ---- ○ ---- ○ ----
PULSE

626 * GMF 11 AP 002 XG 01 GRS U Seal Pit Sump Pump (B) Running 32 U Seal Pit Sump Pump (B) Running STOP/RUN ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) W36 ○ ---- ---- ---- ○ ----

627 * GMF 11 AP 002 XG 02 GRS U Seal Pit Sump Pump (B) Fault Trip 29 U Seal Pit Sump Pump (B) Trip OFF/TRIP ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) W36 ---- P1 ○ ---- ○ ---- Rev.4a Contact type is corrected 4a

628 * GMF 11 AP 002 XG 03 GRS U Seal Pit Sump Pump (B) Remote Mode 31 U Seal Pit Sump Pump (B) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) W36 ○ ---- ○ ---- ○ ----

629 * GMF 11 AP 002 XG 04 GRS U Seal Pit Sump Pump (B) Rack-in Position 32 U Seal Sump Pump (B) Rack-in Pos OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) W36 ○ ---- ---- ---- ○ ----

NO
630 * QCH 51 AA 001 YB 01 NaOH Dosing Stop Valve Open Command 31 NaOH Dosing Stop Valve Open Cmd OFF/OPEN ---- DOW DC110 10W ---- *DCS U0-ARS F W44 ---- ---- ○ ---- ○ ----
LATCH

631 * QCH 51 CG 081 XG 01 NaOH Dosing Stop Valve Open 27 NaOH Dosing Stop Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS W44 ○ ---- ○ ---- ○ ----

632 * QCH 51 CG 082 XG 02 NaOH Dosing Stop Valve Close 28 NaOH Dosing Stop Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS W44 ○ ---- ○ ---- ○ ----

NO
633 * MAJ 60 AA 001 YB 01 Cooling Tower (A) NCG Discharge Valve Open Command 31 CT (A) NCG Discg Valve Open Cmd CLOSE/OPEN ---- DOW DC110 20W ---- *CTRIO U0-ARS F W47 ---- ---- ○ ---- ○ ----
LATCH

634 * MAJ 60 CG 081 XG 01 Cooling Tower (A) NCG Discharge Valve Open 31 CT (A) NCG Discharge Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F NA *CTRIO W47 ○ ---- ○ ---- ○ ----

635 * MAJ 60 CG 082 XG 02 Cooling Tower (A) NCG Discharge Valve Close 32 CT (A) NCG Discharge Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F NA *CTRIO W47 ○ ---- ○ ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL
NO
636 * MAJ 60 AA 002 YB 01 Cooling Tower (B) NCG Discharge Valve Open Command 31 CT (B) NCG Discg Valve Open Cmd CLOSE/OPEN ---- DOW DC110 20W ---- *CTRIO U0-ARS F W48 ---- ---- ○ ---- ○ ----
LATCH

637 * MAJ 60 CG 083 XG 01 Cooling Tower (B) NCG Discharge Valve Open 31 CT (B) NCG Discharge Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F NA *CTRIO W48 ○ ---- ○ ---- ○ ----

638 * MAJ 60 CG 084 XG 02 Cooling Tower (B) NCG Discharge Valve Close 32 CT (B) NCG Discharge Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F NA *CTRIO W48 ○ ---- ○ ---- ○ ----

NO
639 * MAJ 60 AA 003 YB 01 Cooling Tower (C) NCG Discharge Valve Open Command 31 CT (C) NCG Discg Valve Open Cmd CLOSE/OPEN ---- DOW DC110 20W ---- *CTRIO U0-ARS F W49 ---- ---- ○ ---- ○ ----
LATCH

640 * MAJ 60 CG 085 XG 01 Cooling Tower (C) NCG Discharge Valve Open 31 CT (C) NCG Discharge Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F NA *CTRIO W49 ○ ---- ○ ---- ○ ----

641 * MAJ 60 CG 086 XG 02 Cooling Tower (C) NCG Discharge Valve Close 32 CT (C) NCG Discharge Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F NA *CTRIO W49 ○ ---- ○ ---- ○ ----

NO
642 * MAJ 60 AA 004 YB 01 Cooling Tower (D) NCG Discharge Valve Open Command 31 CT (D) NCG Discg Valve Open Cmd CLOSE/OPEN ---- DOW DC110 20W ---- *CTRIO U0-ARS F W50 ---- ---- ○ ---- ○ ----
LATCH

643 * MAJ 60 CG 087 XG 01 Cooling Tower (D) NCG Discharge Valve Open 31 CT (D) NCG Discharge Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F NA *CTRIO W50 ○ ---- ○ ---- ○ ----

644 * MAJ 60 CG 088 XG 02 Cooling Tower (D) NCG Discharge Valve Close 32 CT (D) NCG Discharge Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F NA *CTRIO W50 ○ ---- ○ ---- ○ ----

NO
645 * MAJ 60 AA 005 YB 01 Cooling Tower (E) NCG Discharge Valve Open Command 31 CT (E) NCG Discg Valve Open Cmd CLOSE/OPEN ---- DOW DC110 20W ---- *CTRIO U0-ARS F W51 ---- ---- ○ ---- ○ ----
LATCH

646 * MAJ 60 CG 089 XG 01 Cooling Tower (E) NCG Discharge Valve Open 31 CT (E) NCG Discharge Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F NA *CTRIO W51 ○ ---- ○ ---- ○ ----

647 * MAJ 60 CG 090 XG 02 Cooling Tower (E) NCG Discharge Valve Close 32 CT (E) NCG Discharge Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F NA *CTRIO W51 ○ ---- ○ ---- ○ ----

NO
648 * MAJ 60 AA 006 YB 01 Cooling Tower (F) NCG Discharge Valve Open Command 31 CT (F) NCG Discg Valve Open Cmd CLOSE/OPEN ---- DOW DC110 20W ---- *CTRIO U0-ARS F W52 ---- ---- ○ ---- ○ ----
LATCH

649 * MAJ 60 CG 091 XG 01 Cooling Tower (F) NCG Discharge Valve Open 31 CT (F) NCG Discharge Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F NA *CTRIO W52 ○ ---- ○ ---- ○ ----

650 * MAJ 60 CG 092 XG 02 Cooling Tower (F) NCG Discharge Valve Close 32 CT (F) NCG Discharge Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F NA *CTRIO W52 ○ ---- ○ ---- ○ ----

NO
984 * PBN 31 AA 001 YB 01 Biocide Dosing Stop Valve Open Command 32 Biocide Dosing Stop Vlv Open Cmd CLOSE/OPEN ---- DOW DC110 20W ---- *DCS U0-ARS F W46 ---- ---- ○ ---- ○ ----
LATCH

985 * PBN 31 CG 081 XG 01 Biocide Dosing Stop Valve Open 30 Biocide Dosing Stop Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS W46 ○ ---- ○ ---- ○ ----

986 * PBN 31 CG 082 XG 01 Biocide Dosing Stop Valve Close 31 Biocide Dosing Stop Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS W46 ○ ---- ○ ---- ○ ----

NO
655 * CJJ 10 GH 001 YB 01 65F Raise 9 65F Raise OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG101 ---- ---- ○ ---- ○ ----
PULSE
NO
656 * CJJ 10 GH 001 YB 02 65F Lower 9 65F Lower OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG101 ---- ---- ○ ---- ○ ----
PULSE

657 * CJJ 10 GH 001 XQ 01 65F SET POINT 13 65F SET POINT 0-3600 rpm AIX ---- ---- ---- ---- *TGR NA *DCS TG101 ○ ---- ○ ---- ○ ----

658 * CJJ 10 GH 001 XG 01 Over Speed Test ON 18 Over Speed Test ON OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG101 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
659 * CJJ 10 GH 001 YB 03 COLD MODE ON 12 COLD MODE ON OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG102 ---- ---- ○ ---- ○ ----
PULSE
NO
660 * CJJ 10 GH 001 YB 04 HOT MODE ON 11 HOT MODE ON OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG102 ---- ---- ○ ---- ○ ----
PULSE
NO
661 * CJJ 10 GH 001 YB 05 ATSD ON 6 ATS ON OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG102 ---- ---- ○ ---- ○ ----
PULSE
NO
662 * CJJ 10 GH 001 YB 06 65F RATED SPEED 16 65F RATED SPEED OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG102 ---- ---- ○ ---- ○ ----
PULSE
NO
663 * CJJ 10 GH 001 YB 07 65F HEAT SOAK SPEED 19 65F HEAT SOAK SPEED OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG102 ---- ---- ○ ---- ○ ----
PULSE

664 * CJJ 10 GH 001 XG 02 COLD MODE 10 COLD MODE OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG102 ---- ---- ---- ---- ○ ----

665 * CJJ 10 GH 001 XG 03 HOT MODE 9 HOT MODE OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG102 ○ ---- ---- ---- ○ ----

666 * CJJ 10 GH 001 XG 04 HEAT SOAK SPEED COMPLETED 26 HEAT SOAK SPEED COMPLETED OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG102 ○ ---- ○ ---- ○ ----

667 * CJJ 10 GH 001 XG 05 RAITED SPEED SET 15 RATED SPEED SET OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG102 ○ ---- ---- ---- ○ ----

668 * CJJ 10 GH 001 XG 06 HEAT SOAK SPEED SET 20 HEAT SOAK SPEED SET OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG102 ○ ---- ---- ---- ○ ----

669 * CJJ 10 GH 001 XQ 02 SPEED DETECTION 15 SPEED DETECTION 0-3600 rpm AIX ---- ---- ---- ---- *TGR NA *DCS TG103 ○ ---- ○ ---- ○ ----

670 * CJJ 10 GH 001 XG 07 OVER TIME OF CONTINUANCE OPERATION SPEED 30 OVER TIME OF CONTINU OPE SPEED OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG103 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

671 * CJJ 10 GH 001 XG 08 GEN OVER FREQUENCY 81H 22 GEN OVER FREQUENCY 81H OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG103 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

672 * CJJ 10 GH 001 XG 09 GEN UNDER FREQUENCY 81L 23 GEN UNDER FREQUENCY 81L OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG103 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
673 * CJJ 10 GH 001 YB 08 ATSD ON 8 ATSD ON OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG111 ---- ---- ○ ---- ○ ----
PULSE
NO
674 * CJJ 10 GH 001 YB 09 65P RAISE 10 65P RAISE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG111 ---- ---- ○ ---- ○ ----
PULSE
NO
675 * CJJ 10 GH 001 YB 10 65P LOWER 10 65P LOWER OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG111 ---- ---- ○ ---- ○ ----
PULSE
NO
676 * CJJ 10 GH 001 YB 11 65P RUNBACK REDUCTION 21 65P RUNBACK REDUCTION OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG111 ---- ---- ○ ---- ○ ----
PULSE

677 * CJJ 10 GH 001 XQ 03 65P SET POINT 13 65P SET POINT 0-80 MW AIX ---- ---- ---- ---- *TGR NA *DCS TG111 ○ ---- ○ ---- ○ ----

NO
965 * CJJ 10 GH 001 YB 55 POWER CHANGE RATE RAISE 23 POWER CHANGE RATE RAISE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG111 ○ ---- ○ ---- ○ ----
PULSE
NO
966 * CJJ 10 GH 001 YB 56 POWER CHANGE RATE LOWER 23 POWER CHANGE RATE LOWER OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG111 ○ ---- ○ ---- ○ ----
PULSE

967 * CJJ 10 GH 001 XQ 22 POWER CHANGE RATE SETTING 21 POWER CHANGE RATE SET 0-49.2 MW/min AIX ---- ---- ---- ---- *TGR NA *DCS TG111 ○ ---- ○ ---- ○ ----

678 * CJJ 10 GH 001 XQ 04 POWER DETECTION 14 GENERATOR LOAD 0-80 MW AIX ---- ---- ---- ---- *TGR NA *DCS TG112 ○ ---- ---- ---- ○ ----

NO
679 * CJJ 10 GH 001 YB 12 77E RAISE 10 77E RAISE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG121 ---- ---- ○ ---- ○ ----
PULSE
NO
680 * CJJ 10 GH 001 YB 13 77E LOWER 9 77E LOWER OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG121 ---- ---- ○ ---- ○ ----
PULSE

681 * CJJ 10 GH 001 XQ 05 77E SET POINT 13 77E SET POINT 0-100 % AIX ---- ---- ---- ---- *TGR NA *DCS TG121 ○ ---- ○ ---- ○ ----

682 * CJJ 10 GH 001 XG 10 FOR ATS ABNORMAL CONDITION 26 FOR ATS ABNORMAL CONDITION OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG121 ---- ---- ○ ---- ○ ----

683 * CJJ 10 GH 001 XG 11 LOAD SHEDDING ACTION 20 LOAD SHEDDING ACTION OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG122 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL

684 * CJJ 10 GH 001 XQ 06 HPCV(L) POSITION DETECTION 26 HPCV(L) POSITION DETECTION 0-100 % AIX ---- ---- ---- ---- *TGR NA *DCS TG123 ○ ---- ○ ---- ○ ----

685 * CJJ 10 GH 001 XQ 07 HPCV(R) POSITION DETECTION 26 HPCV(R) POSITION DETECTION 0-100 % AIX ---- ---- ---- ---- *TGR NA *DCS TG123 ○ ---- ○ ---- ○ ----

686 * CJJ 10 GH 001 XQ 08 LPCV(L) POSITION DETECTION 26 LPCV(L) POSITION DETECTION 0-100 % AIX ---- ---- ---- ---- *TGR NA *DCS TG123 ○ ---- ○ ---- ○ ----

687 * CJJ 10 GH 001 XQ 09 LPCV(R) POSITION DETECTION 26 LPCV(R) POSITION DETECTION 0-100 % AIX ---- ---- ---- ---- *TGR NA *DCS TG123A ○ ---- ○ ---- ○ ----

688 * CJJ 10 GH 001 XQ 10 GOVERNOR OUTPUT 15 GOVERNOR OUTPUT 0-100 % AIX ---- ---- ---- ---- *TGR NA *DCS TG124 ○ ---- ---- ---- ○ ----

NO
689 * CJJ 10 GH 001 YB 14 DROOP USE 9 DROOP USE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG131 ---- ---- ○ ---- ○ ----
PULSE
NO
690 * CJJ 10 GH 001 YB 15 DROOP OFF 9 DROOP OFF OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG131 ---- ---- ○ ---- ○ ----
PULSE

691 * CJJ 10 GH 001 XG 12 DROOP USE 9 DROOP USE OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG131 ---- ---- ○ ---- ○ ----

692 * CJJ 10 GH 001 XG 13 HOUSE LOAD OPERATION 20 HOUSE LOAD OPERATION OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG131 ○ ---- ---- ---- ○ ----

NO
693 * CJJ 10 GH 001 YB 16 HPIPC RAISE 12 HPIPC RAISE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG141 ---- ---- ○ ---- ○ ----
PULSE
NO
694 * CJJ 10 GH 001 YB 17 HPIPC LOWER 12 HPIPC LOWER OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG141 ---- ---- ○ ---- ○ ----
PULSE
NO
695 * CJJ 10 GH 001 YB 18 HPIPC ON 8 HPIPC ON OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG141 ---- ---- ○ ---- ○ ----
PULSE
NO
696 * CJJ 10 GH 001 YB 19 HPIPC OFF 9 HPIPC OFF OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG141 ---- ---- ○ ---- ○ ----
PULSE

697 * CJJ 10 GH 001 XQ 11 HPIPC SET VALUE 15 HPIPC SET VALUE 0-10 barg AIX ---- ---- ---- ---- *TGR NA *DCS TG141 ○ ---- ---- ---- ○ ----

698 * CJJ 10 GH 001 XG 14 HPIPC CONTROL MODE 18 HPIPC CONTROL MODE OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG141 ○ ---- ○ ---- ○ ----

699 * CJJ 10 GH 001 XQ 12 HPLPC SET POINT 15 HPLPC SET VALUE 0-10 barg AIX ---- ---- ---- ---- *TGR NA *DCS TG151 ○ ---- ---- ---- ○ ----

700 * CJJ 10 GH 001 XG 15 STEAM PRESSURE LIMITTER ON 27 STEAM PRESSURE LIMITTER ON OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG151 ○ ---- ---- ---- ○ ----

701 * CJJ 10 GH 001 XG 16 STEAM PRESSURE LIMITTER ACTION 30 STEAM PRESSURE LIMITTER ACTION OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG151 ○ ---- ---- ---- ○ ----

NO
702 * CJJ 10 GH 001 YB 20 LPIPC CONTROL AUTO 18 LPIPC CONTROL AUTO OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG161 ---- ---- ○ ---- ○ ----
PULSE
NO
703 * CJJ 10 GH 001 YB 21 LPIPC CONTROL MANUAL 20 LPIPC CONTROL MANUAL OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG161 ---- ---- ○ ---- ○ ----
PULSE
NO
704 * CJJ 10 GH 001 YB 22 ATSD LPCV CLOSE COMMAND 22 ASD LPCV CLOSE COMMAND OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG161 ---- ---- ○ ---- ○ ----
PULSE

705 * CJJ 10 GH 001 XG 17 LPIPC CONTROL AUTO 18 LPIPC CONTROL AUTO OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG161 ○ ---- ○ ---- ○ ----

NO
706 * CJJ 10 GH 001 YB 23 LPIPC AUTO SETPOINT RAISE 25 LPIPC AUTO SETPOINT RAISE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG162 ---- ---- ○ ---- ○ ----
PULSE
NO
707 * CJJ 10 GH 001 YB 24 LPIPC AUTO SETPOINT LOWSER 25 LPIPC AUTO SETPOINT LOWER OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG162 ---- ---- ○ ---- ○ ----
PULSE
NO
708 * CJJ 10 GH 001 YB 25 LPIPC MANUAL MV RAISE 21 LPIPC MANUAL MV RAISE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG162 ---- ---- ○ ---- ○ ----
PULSE
NO
709 * CJJ 10 GH 001 YB 26 LPIPC MANUAL MV LOWER 21 LPIPC MANUAL MV LOWER OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG162 ---- ---- ○ ---- ○ ----
PULSE

710 * CJJ 10 GH 001 XQ 13 LPIPC AUTO SET POINT 20 LPIPC AUTO SET POINT 0-5 barg AIX ---- ---- ---- ---- *TGR NA *DCS TG162 ○ ---- ---- ---- ○ ----

711 * CJJ 10 GH 001 XQ 14 LPIPC POSITION DEMAND 14 LPIPC POSITION 0-100 % AIX ---- ---- ---- ---- *TGR NA *DCS TG162 ○ ---- ○ ---- ○ ----

712 * CJJ 10 GH 001 XQ 15 LPIPC MANUAL SET POINT 22 LPIPC MANUAL SET VALUE 0-100 % AIX ---- ---- ---- ---- *TGR NA *DCS TG162 ○ ---- ---- ---- ○ ----

NO
713 * CJJ 10 GH 001 YB 27 EHG PRIMARY 11 EHG PRIMARY OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG170 ---- ---- ○ ---- ○ ----
PULSE
NO
968 * CJJ 10 GH 001 YB 57 EHG SECONDARY 13 EHG SECONDARY OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG170 ---- ---- ○ ---- ○ ----
PULSE

714 * CJJ 10 GH 001 XG 18 EHG PRIMARY 11 EHG PRIMARY OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG170 ○ ---- ---- ---- ○ ----

NO
715 * CJJ 10 GH 001 YB 28 90A RAISE 10 90A RAISE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG201 ---- ---- ○ ---- ○ ----
PULSE
NO
716 * CJJ 10 GH 001 YB 29 90A LOWER 9 90A LOWER OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG201 ---- ---- ○ ---- ○ ----
PULSE
NO
717 * CJJ 10 GH 001 YB 30 MODE SELECTION AVR 18 MODE SELECTION AVR OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG201 ---- ---- ○ ---- ○ ----
PULSE
NO
718 * CJJ 10 GH 001 YB 31 MODE SELECTION MVR 18 MODE SELECTION MVR OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG201 ---- ---- ○ ---- ○ ----
PULSE

719 * CJJ 10 GH 001 XQ 16 90A SET POINT 13 90A SET POINT 8.8-12.1 Kv AIX ---- ---- ---- ---- *TGR NA *DCS TG201 ○ ---- ---- ---- ○ ----

720 * CJJ 10 GH 001 XG 19 AVR MODE 8 AVR MODE OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG201 ○ ---- ○ ---- ○ ----

NO
721 * CJJ 10 GH 001 YB 32 90M RAISE 9 90M RAISE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG202 ---- ---- ○ ---- ○ ----
PULSE
NO
722 * CJJ 10 GH 001 YB 33 90M LOWER 9 90M LOWER OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG202 ---- ---- ○ ---- ○ ----
PULSE

723 * CJJ 10 GH 001 XQ 17 90M SET POINT 13 90M SET POINT 0-16.5 A AIX ---- ---- ---- ---- *TGR NA *DCS TG202 ○ ---- ---- ---- ○ ----

724 * CJJ 10 GH 001 XQ 18 FIELD CURRENT 13 FIELD CURRENT 0-30 A AIX ---- ---- ---- ---- *TGR NA *DCS TG205 ○ ---- ---- ---- ○ ---- Rev.4 Rangei is updated 4

725 * CJJ 10 GH 001 XQ 19 FIELD VOLTAGE 13 FIELD VOLTAGE 0-160 V AIX ---- ---- ---- ---- *TGR NA *DCS TG205 ○ ---- ---- ---- ○ ----

NO
726 * CJJ 10 GH 001 YB 34 FIELD CB 41 ON 14 FIELD CB 41 ON OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG211 ---- ---- ○ ---- ○ ----
PULSE
NO
727 * CJJ 10 GH 001 YB 35 FIELD CB 41 OFF 15 FIELD CB 41 OFF OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG211 ---- ---- ○ ---- ○ ----
PULSE

728 * CJJ 10 GH 001 XG 20 41 ON 5 41 ON OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG212 ○ ---- ○ ---- ○ ----

NO
729 * CJJ 10 GH 001 YB 36 AQR ON 6 AQR ON OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG221 ---- ---- ○ ---- ○ ----
PULSE
NO
730 * CJJ 10 GH 001 YB 37 AQR OFF 7 AQR OFF OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG221 ---- ---- ○ ---- ○ ----
PULSE
NO
731 * CJJ 10 GH 001 YB 38 AQR RAISE 9 AQR RAISE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG221 ---- ---- ○ ---- ○ ----
PULSE
NO
732 * CJJ 10 GH 001 YB 39 AQR LOWER 9 AQR LOWER OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG221 ---- ---- ○ ---- ○ ----
PULSE
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL
NO
733 * CJJ 10 GH 001 YB 40 APfR ON 7 APfR ON OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG221 ---- ---- ○ ---- ○ ----
PULSE
NO
734 * CJJ 10 GH 001 YB 41 APfR OFF 8 APfR OFF OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG221 ---- ---- ○ ---- ○ ----
PULSE
NO
735 * CJJ 10 GH 001 YB 42 APfR RAISE 11 APfR RAISE OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG221 ---- ---- ○ ---- ○ ----
PULSE
NO
736 * CJJ 10 GH 001 YB 43 APfR LOWER 10 APfR LOWER OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG221 ---- ---- ○ ---- ○ ----
PULSE

737 * CJJ 10 GH 001 XG 21 AQR ON 6 AQR ON OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG221 ○ ---- ---- ---- ○ ----

738 * CJJ 10 GH 001 XQ 20 AQR SETTING 10 AQR ETTING -57.9~+57.9 MVAR AIX ---- ---- ---- ---- *TGR NA *DCS TG221 ○ ---- ---- ---- ○ ---- Rev.4 Range is updated 4

739 * CJJ 10 GH 001 XG 22 APfR USE 8 APfR USE OFF/ON ---- DI ---- ---- NO ---- *TGR NA *DCS TG221 ○ ---- ---- ---- ○ ----

740 * CJJ 10 GH 001 XQ 21 APfR SETTING 12 APfR SETTING -0.5-1-0.5 ---- AIX ---- ---- ---- ---- *TGR NA *DCS TG221 ○ ---- ---- ---- ○ ----

NO
741 * CJJ 10 GH 001 YB 44 PSS ON 6 PSS ON OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG231 ---- ---- ○ ---- ○ ----
PULSE
NO
742 * CJJ 10 GH 001 YB 45 PSS OFF 7 PSS OFF OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TG231 ---- ---- ○ ---- ○ ----
PULSE

743 * CJJ 10 GH 001 XG 23 CPU-A STOP 11 CPU-A STOP OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG301 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

744 * CJJ 10 GH 001 XG 24 CPU-B STOP 11 CPU-B STOP OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG301 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

Rev.4 Alarm level is changed


745 * CJJ 10 GH 001 XG 25 BOTH CPU STOP 13 BOTH CPU STOP OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG302 ---- P1 ---- ---- ○ ---- 4
(Change to P1)

746 * CJJ 10 GH 001 XG 26 DC24V P/S F1,F2 TRIP 20 DC24V P/S F1,F2 TRIP OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG302 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

747 * CJJ 10 GH 001 XG 27 DC24V P/S M1,M2 TRIP 20 DC24V P/S M1,M2 TRIP OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG302 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

Rev.4 Alarm level is changed


748 * CJJ 10 GH 001 XG 28 EHG MAJOR FAULT 15 EHG MAJOR FAULT OFF/TRIP ---- DI ---- ---- NC ---- *TGR NA *DCS TG302 ---- P1 ○ ---- ○ ○ 4
(Change to P1)
Rev.4 Alarm level is changed
749 * CJJ 10 GH 001 XG 29 AVR MAJOR FAULT 16 AVR MAJOR FAULT OFF/TRIP ---- DI ---- ---- NO ---- *TGR NA *DCS TG302 ---- P1 ○ ---- ○ ○ 4
(Change to P1)

750 * CJJ 10 GH 001 XG 30 TGR MINOR FAULT 15 TGR MINOR FAULT OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG303 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

751 * CJJ 10 GH 001 XG 31 EHG MINOR FAULT 15 EHG MINOR FAULT OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG304 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

752 * CJJ 10 GH 001 XG 32 AVR MINOR FAULT 15 AVR MINOR FAULT OFF/ALARM ---- DI ---- ---- NO ---- *TGR NA *DCS TG304 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

NO
753 * CJJ 10 GH 001 YB 46 AVT OPERATION ON 16 AVT OPERATION ON OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TT033 ---- ---- ○ ---- ○ ----
PULSE
NO
754 * CJJ 10 GH 001 YB 47 AVT OPERATION OFF 17 AVT OPERATION OFF OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TT033 ---- ---- ○ ---- ○ ----
PULSE
NO
755 * CJJ 10 GH 001 YB 48 AVT OPERATION SKIP 18 AVT OPERATION SKIP OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TT033 ---- ---- ○ ---- ○ ----
PULSE
NO
756 * CJJ 10 GH 001 YB 49 AVT SELECTION HPSV(L) GROUP 27 AVT SELECTION HPSV(L) GROUP OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TT035 ---- ---- ○ ---- ○ ----
PULSE
NO
757 * CJJ 10 GH 001 YB 50 AVT SELECTION HPSV(R) GROUP 27 AVT SELECTION HPSV(R) GROUP OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TT035 ---- ---- ○ ---- ○ ----
PULSE
NO
758 * CJJ 10 GH 001 YB 51 AVT SELECTION LPSV(L) GROUP 27 AVT SELECTION LPSV(L) GROUP OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TT035 ---- ---- ○ ---- ○ ----
PULSE
NO
759 * CJJ 10 GH 001 YB 52 AVT SELECTION LPSV(R) GROUP 27 AVT SELECTION LPSV(R) GROUP OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TT035 ---- ---- ○ ---- ○ ----
PULSE
NO
760 * CJJ 10 GH 001 YB 53 AVT OPERATION TEST 18 AVT OPERATION TEST OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TT036 ---- ---- ○ ---- ○ ----
PULSE
NO
761 * CJJ 10 GH 001 YB 54 AVT OPERATION RETEST 20 AVT OPERATION RETEST OFF/ON ---- DOL DC24 1W ---- *DCS NA *TGR TT036 ---- ---- ○ ---- ○ ----
PULSE
NO
762 * CHA 10 GH 001 YB 01 RESET COMMAND FOR 3-86 22 RESET COMMAND FOR 3-86 OFF/ON ---- DOH DC110 1W ---- *DCS NA *GPR GT01 ---- ---- ○ ---- ○ ----
PULSE

978 * CHA 10 GH 001 XG 10 LOCKOUT RELAY-A 15 LOCKOUT RELAY-A OFF/ON ---- DI NO ---- *GPR NA *DCS GT01 ---- P1 ---- ---- ○ ○ Rev.4 Change to SOE 4

979 * CHA 10 GH 001 XG 11 LOCKOUT RELAY-B 15 LOCKOUT RELAY-B OFF/ON ---- DI NO ---- *GPR NA *DCS GT02 ---- P1 ---- ---- ○ ○ Rev.4 Change to SOE 4

980 * CHA 10 GH 001 XG 12 PROTECTION RELAY FAILER 23 PROTECTION RELAY FAILER OFF/ON ---- DI NO ---- *GPR NA *DCS GT04 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

981 * CHA 10 GH 001 XG 13 LOSS OF POWER SOURCE 20 LOSS OF POWER SOURCE OFF/ON ---- DI NO ---- *GPR NA *DCS GT04 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

982 * CHA 10 GH 001 XG 14 UNIT LOCKOUT RELAY-A 20 UNIT LOCKOUT RELAY-A OFF/ON ---- DI NO ---- *GPR NA *DCS GT05 ---- P1 ---- ---- ○ ○ Rev.4 Change to SOE 4

983 * CHA 10 GH 001 XG 15 UNIT LOCKOUT RELAY-B 20 UNIT LOCKOUT RELAY-B OFF/ON ---- DI NO ---- *GPR NA *DCS GT06 ---- P1 ---- ---- ○ ○ Rev.4 Change to SOE 4

763 * CHA 10 GH 001 XG 01 52G CLOSE 9 52G CLOSE OFF/ON ---- DI ---- ---- NO ---- *GPR NA *DCS GT11 ○ ---- ○ ---- ○ ----

764 * CHA 10 GH 001 XG 02 52G OPEN 8 52G OPEN OFF/ON ---- DI ---- ---- NO ---- *GPR NA *DCS GT11 ○ ---- ---- ---- ○ ----

987 * CHA 10 GH 001 XG 16 52G HEALTHY 11 52G HEALTHY OFF/ON ---- DI NO ---- *GSWG NA *DCS GT11 ---- ---- ○ ○ ○ ----

765 * CHA 10 GH 001 XG 03 52R CLOSE 9 52R CLOSE OFF/ON ---- DI ---- ---- NO ---- *GPR NA *DCS GT12 ○ ---- ○ ---- ○ ----

766 * CHA 10 GH 001 XG 04 52R OPEN 8 52R OPEN OFF/ON ---- DI ---- ---- NO ---- *GPR NA *DCS GT12 ○ ---- ---- ---- ○ ----

NO
767 * CJA 10 GH 001 YB 05 ASY ON COMMAND FROM ATS 24 ASY ON COMMAND FROM ATS OFF/SYNC ---- DOH DC110 1W ---- *DCS NA *SYN GT21 ---- ---- ○ ---- ○ ---- Rev.4a Signal type is corrected 4a
PULSE

768 * CJA 10 GH 001 XG 06 52G ATS MODE SELECTED 22 52G ATS MODE SELECTED OFF/ON ---- DI ---- ---- NO ---- *SYN NA *DCS GT21 ---- ---- ○ ---- ○ ----

769 * CJA 10 GH 001 XG 07 SYNCHRONIZING OPERATION 23 SYNCHRONIZING OPERATION OFF/ON ---- DI ---- ---- NO ---- *SYN NA *DCS GT21 ○ ---- ---- ---- ○ ----

770 * CJA 10 GH 001 XG 08 SYNCHRONIZING FAILURE 21 SYNCHRONIZING FAILURE OFF/ALARM ---- DI ---- ---- NC ---- *SYN NA *DCS GT21 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

771 * CJA 10 GH 001 XG 09 ASY SYSTEM LOSS OF POWER SOURCE 31 ASY SYSTEM LOSS OF POWER SOURCE OFF/ALARM ---- DI ---- ---- NO ---- *SYN NA *DCS GT21 ---- P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

776 * LBA 91 AA 182 XG 01 Rupture Disc at LP scrubber outlet 32 Rupture Disc at LP scrub outlet OFF/ON ---- DI ---- ---- NC ---- F U0-ARS *DCS ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

777 * LBA 91 AA 185 XG 01 Rupture Disc at LP scrubber outlet 32 Rupture Disc at LP scrub outlet OFF/ON ---- DI ---- ---- NC ---- F U0-ARS *DCS ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

778 * LBA 91 AA 188 XG 01 Rupture Disc at LP scrubber outlet 32 Rupture Disc at LP scrub outlet OFF/ON ---- DI ---- ---- NC ---- F U0-ARS *DCS ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

780 * LBA 71 CP 001 XQ 01 HP Scrubber Inlet Steam Pressure 30 HP Scrubber Inlet Steam Press 0-20 barg AIX ---- ---- ---- ---- F U0-ARS *DCS R14 ○ ---- ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. SERVICE SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH
within 32 Chara CONTACT BAND SHEET NO IND ANN CONT ATS LOG SOE HHH HH H L LL

781 * LBA 91 CP 001 XQ 01 LP Scrubber Inlet Steam Pressure 29 LP Scrubber Inlet Steam Press 0-15 barg AIX ---- ---- ---- ---- F U0-ARS *DCS R14 ○ ---- ---- ---- ○ ----

977 * MAJ 50 CP 001 XQ 01 After condenser NCG Outlet Pressure 32 After condenser NCG Outlet Press 0-1 barg AIX ---- ---- ---- ---- F U0-ARS *DCS ---- ○ ---- ---- ---- ○ ---- Rev.4 Range is updated 4

997 * LCA 41 AA 101 YJ 01 Cooling Tower Basin Level Control Valve MV 31 CT Basin Level Control Valve MV 0-100 % AOX ---- ---- ---- ---- *DCS U0-ARS F C09 ○ ---- ○ ---- ○ ----

998 * LCA 41 CG 101 XQ 01 Cooling Tower Basin Level Control Valve Position 32 CT Basin Level Control Valve Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS *DCS C09 ○ ---- ○ ---- ○ ----

Rev.4a Signal from PSD box is not


999 * LBA 91 AA 081 XG 01 Rupture Disc at LP scrubber outlet Switch 31 Rupture Disc at LP scrub Switch OFF/ON ---- DI ---- ---- ---- ---- F U0-ARS *DCS ---- ○ ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
1000 * LBA 91 AA 082 XG 01 Rupture Disc at LP scrubber outlet Switch 31 Rupture Disc at LP scrub Switch OFF/ON ---- DI ---- ---- ---- ---- F U0-ARS *DCS ---- ○ ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
1001 * LBA 91 AA 083 XG 01 Rupture Disc at LP scrubber outlet Switch 31 Rupture Disc at LP scrub Switch OFF/ON ---- DI ---- ---- ---- ---- F U0-ARS *DCS ---- ○ ○ ---- ---- ○ ---- 4a
existing.

1006 * CKA 10 GH 011 XG 02 Unit-* System Cabinet PSU Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

1007 * CKA 10 GH 011 XG 01 Unit-* System Cabinet Fan or Thermostat Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

1008 * CKA 10 GH 012 XG 02 Unit-* System Cabinet PSU Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

1009 * CKA 10 GH 012 XG 01 Unit-* System Cabinet Fan or Thermostat Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

1010 * CJU 02 GH 011 XG 03 Unit-* CT RIO Cabinet Door Switch Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

1011 * CJU 02 GH 011 XG 02 Unit-* CT RIO Cabinet PSU Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

1012 * CJU 02 GH 011 XG 01 Unit-* CT RIO Cabinet Thermostat Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

1013 * CJU 01 GH 012 XG 02 Unit-* MCC LV RIO Cabinet PSU Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

1014 * CJU 01 GH 012 XG 01 Unit-* MCC LV RIO Cabinet PSU Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

1015 * CJU 01 GH 011 XG 02 Unit-* MCC MV RIO Cabinet PSU Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

1016 * CJU 01 GH 011 XG 01 Unit-* MCC MV RIO Cabinet PSU Alarm 0 NORMAL/ALARM ---- DI ---- ---- ---- ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

NO
1017 * PGB 21 AA 003 YB 01 Intercondenser Auxiliary Cooling Water Supply Stop Valve Open Command 31 GRS ACW Stop Valve Open Command OPEN/CLOSE ---- DOW 110V 20W ---- *DCS U0-ARS F S51 ---- ---- ○ ---- ○ ---- Rev.4a Signal type is corrected 4a
LATCH

1018 * PGB 21 CG 081 XG 01 Intercondenser Auxiliary Cooling Water Supply Stop Valve Open 23 GRS ACW Stop Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S51 ○ ---- ○ ---- ○ ---- Rev.4a Miswriting is corrected 4a

1019 * PGB 21 CG 082 XG 01 Intercondenser Auxiliary Cooling Water Supply Stop Valve Close 24 GRS ACW Stop Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S51 ○ ---- ---- ---- ○ ---- Rev.4a Miswriting is corrected 4a

NO
1020 * PGB 51 AA 011 YB 01 Vacuum Pumps Auxiliary Cooling Water Supply Stop Valve Open Command 30 VP ACW Stop Valve Open Command OPEN/CLOSE ---- DOW 110V 20W ---- *DCS U0-ARS F S50 ---- ---- ○ ---- ○ ---- Rev.4a Signal type is corrected 4a
LATCH

1021 * PGB 51 CG 081 XG 01 Vacuum Pumps Auxiliary Cooling Water Supply Stop Valve Open 22 VP ACW Stop Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS *DCS S50 ○ ---- ○ ---- ○ ----

1022 * PGB 51 CG 082 XG 01 Vacuum Pumps Auxiliary Cooling Water Supply Stop Valve Close 23 VP ACW Stop Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS *DCS S50 ○ ---- ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO *DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
NO
3772 * BAT 10 YB 01 GENERATOR TRANSFORMER OLTC POSITION COMMAND LOWER 28 GSUT OLTC POSITION CMD LOWER OFF/ON ---- DOH 110VDC 100W ---- *DCS U0-ARS *GSUT REK ○ ---- ---- ---- ○ ----
PULSE
NO
3773 * BAT 10 YB 02 GENERATOR TRANSFORMER OLTC POSITION COMMAND RISE 27 GUST OLTC POSITION CMD RISE OFF/ON ---- DOH 110VDC 100W ---- *DCS U0-ARS *GSUT REK ○ ---- ---- ---- ○ ----
PULSE
NO
3774 * BBT 10 YB 01 UNIIT AUXILIARY TRANSFORMER OLTC POSITION COMMAND LOWER 27 UAT OLTC POSITION CMD LOWER OFF/ON ---- DOH 110VDC 100W ---- *DCS U0-ARS *UAT REK ○ ---- ---- ---- ○ ----
PULSE
NO
3775 * BBT 10 YB 02 UNIIT AUXILIARY TRANSFORMER OLTC POSITION COMMAND RISE 26 UAT OLTC POSITION CMD RISE OFF/ON ---- DOH 110VDC 100W ---- *DCS U0-ARS *UAT REK ---- ---- ---- ---- ○ ----
PULSE

3776 * BFT 10 XG 01 UNIT SERVICE TRANSFORMER OIL TEMPERATURE H 21 UST OIL TEMPERATURE H OFF/HIGH ---- DI ---- ---- NO ---- *UST U0-ARS *DCS REK ---- ○ ---- ---- ----

(P2)

3777 * BFT 10 XG 02 UNIT SERVICE TRANSFORMER OIL TEMPERATURE HH 22 UST OIL TEMPERATURE HH OFF/HHIGH ---- DI ---- ---- NO ---- *UST U0-ARS *DCS REK ---- ---- ---- ○ ○
(P2)

3778 * BFT 10 XG 03 UNIT SERVICE TRANSFORMER WINDING TEMPERATURE H 25 UST WINDING TEMPERATURE H OFF/HIGH ---- DI ---- ---- NO ---- *UST U0-ARS *DCS REK ○ ---- ---- ○ ----
(P2)

3779 * BFT 10 XG 04 UNIT SERVICE TRANSFORMER WINDING TEMPERATURE HH 26 UST WINDING TEMPERATURE HH OFF/HHIGH ---- DI ---- ---- NO ---- *UST U0-ARS *DCS REK ○ ---- ----
○ ○ ○
(P2)
3780 * BFT 10 XG 05 UNIT SERVICE TRANSFORMER OIL LEVEL MAIN TANK 23 UST OIL LEVEL MAIN TANK OFF/LOW ---- DI ---- ---- NO ---- *UST U0-ARS *DCS REK ○ ---- ----
○ ○ ○
(P2)
3781 * BFT 10 XG 06 UNIT SERVICE TRANSFORMER PRESSURE RELIEF DEVICE 26 UST PRESSURE RELIEF DEVICE OFF/ALARM ---- DI ---- ---- NO ---- *UST U0-ARS *DCS REK ---- ○ ---- ---- ○ ○
(P2)
3782 * BJT 10 XG 01 LIGHTING TRANSFORMER 150 KVA OIL TEMPERATURE H 27 LT 150KVA OIL TEMPERATURE H OFF/HIGH ---- DI ---- ---- NO ---- *LT U0-ARS *DCS REK ---- ○ ---- ---- ----

(P2)
3783 * BJT 10 XG 02 LIGHTING TRANSFORMER 150 KVA OIL TEMPERATURE HH 28 LT 150KVA OIL TEMPERATURE HH OFF/HHIGH ---- DI ---- ---- NO ---- *LT U0-ARS *DCS REK ---- ○ ---- ---- ○ ○
(P2)
3784 * BJT 10 XG 03 LIGHTING TRANSFORMER 150 KVA WINDING TEMPERATURE H 31 LT 150KVA WINDING TEMPERATURE H OFF/HIGH ---- DI ---- ---- NO ---- *LT U0-ARS *DCS REK ○ ---- ---- ----
○ ○
(P2)
3785 * BJT 10 XG 04 LIGHTING TRANSFORMER 150 KVA WINDING TEMPERATURE HH 32 LT 150KVA WINDING TEMPERATURE HH OFF/HHIGH ---- DI ---- ---- NO ---- *LT U0-ARS *DCS REK ○ ---- ----
○ ○ ○
(P2)

3786 * BJT 10 XG 05 LIGHTING TRANSFORMER 150 KVA OIL LEVEL MAIN TANK 30 LT 150KVA OIL LEVEL MAIN TANK OFF/LOW ---- DI ---- ---- NO ---- *LT U0-ARS *DCS REK ○ ---- ---- ○ ○
(P2)
3787 * BJT 10 XG 06 LIGHTING TRANSFORMER 150 KVA PRESSURE RELIEF DEVICE 32 LT 150KVA PRESSURE RELIEF DEVICE OFF/ALARM ---- DI ---- ---- NO ---- *LT U0-ARS *DCS REK ---- ○ ---- ---- ○ ○
(P2)
3788 * BAC 10 XG 01 52G-# CB CLOSE INDICATION 25 52G-# CB CLOSE INDICATION OFF/ON ---- DI ---- ---- NO ---- *GSWG NA *DCS REK ○ ---- ---- ---- ○ ○ Note; # is 1 for unit1,2 for unit2

3789 * BAC 10 XG 02 52G-# LOCAL MODE SELECTED 25 52G-# LOCAL MODE SELECTED OFF/ON ---- DI ---- ---- NO ---- *GSWG NA *DCS REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3790 * BAC 10 XG 03 52G-# REMOTE MODE SELECTED 26 52G-# REMOTE MODE SELECTED OFF/ON ---- DI ---- ---- NO ---- *GSWG NA *DCS REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3793 * BAC 10 XG 04 52G-# RACK-IN POSITION 22 52G-# RACK-IN POSITION OFF/ON ---- DI ---- ---- NO ---- *GSWG NA *DCS REK ---- ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2

(P2)
NO
3797 * BBT 10 YB 05 UAT DUMMY CB OPEN COMMAND 26 UAT DUMMY CB OPEN COMMAND OFF/OPEN ---- DOH 110VDC 250W ---- *DCS U0-ARS *UAT REK ---- ---- ○ ---- ○ ----
PULSE
NO
3798 * BBT 10 YB 06 UAT DUMMY CB CLOSE COMMAND 27 UAT DUMMY CB CLOSE COMMAND OFF/CLOSE ---- DOH 110VDC 250W ---- *DCS U0-ARS *UAT REK ---- ---- ○ ---- ○ ----
PULSE

3799 * BBT 10 XG 06 UAT DUMMY CB CLOSED INDICATION 30 UAT DUMMY CB CLOSED INDICATION OPEN/CLOSE ---- DI ---- ---- NO ---- *UAT U0-ARS *DCS REK ○ ---- ---- ---- ○ ----

3800 * BAC 10 XG 07 ES BUS CLOSE CONDITION 22 ES BUS CLOSE CONDITION OPEN/CLOSE ---- DI ---- ---- NO ---- *GSWG NA *DCS REK ○ ---- ---- ---- ○ ----

3801 * BAC 10 XG 08 ES CLOSE CONDITION 18 ES CLOSE CONDITION OPEN/CLOSE ---- DI ---- ---- NO ---- *GSWG NA *DCS REK ○ ---- ---- ---- ○ ----

NO
3802 * BAC 10 YB 07 SPARE CLOSE COMMAND 20 SPARE CLOSE COMMAND OFF/CLOSE ---- DOH 110VDC 250W ---- *DCS NA *GSWG REK ○ ---- ---- ---- ○ ----
PULSE

3803 * BAC 10 XG 09 SPARE CLOSED INDICATION 23 SPARE CLOSED INDICATION ON/OFF ---- DI ---- ---- NO ---- *GSWG NA *DCS REK ---- ---- ---- ---- ○ ----

NO
3804 * BAC 10 YB 08 SPARE OPEN COMMAND 19 SPARE OPEN COMMAND OFF/OPEN ---- DOH 110VDC 250W ---- *DCS NA *GSWG REK ○ ---- ---- ---- ○ ----
PULSE
NO
3805 * BAC 10 YB 09 SPARE CLOSE COMMAND 20 SPARE CLOSE COMMAND OFF/CLOSE ---- DOH 110VDC 250W ---- *DCS NA *GSWG REK ○ ---- ---- ---- ○ ----
PULSE

3806 * BAC 10 XG 10 SPARE CLOSED INDICATION 23 SPARE CLOSED INDICATION ON/OFF ---- DI ---- ---- NO ---- *GSWG NA *DCS REK ○ ---- ---- ---- ○ ----

3807 * BBA 10 XQ 01 6.3kV SWITCHGEAR BUS VOLTAGE 28 6.3kV SWITCHGEAR BUS VOLTAGE 0-6300 V AIX ---- ---- ---- ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

NO
3808 * BBA 10 YB 01 INCOMING FROM UNIT AUXILIARY TRANSFORMER (52H-#) CB OPEN COMMAND 31 IC FROM UAT (52H-#) CB OPN CMD OFF/OPEN ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE
NO
3809 * BBA 10 YB 02 INCOMING FROM UNIT AUXILIARY TRANSFORMER (52H-#) CB CLOSE COMMAND 31 IC FROM UAT (52H-#) CB CLS CMD OFF/CLOSE ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG REK ○ ---- ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE

3810 * BBA 10 XG 01 ST SPARE FEEDER (52HD-0) CB CLOSE COMMAND 28 IC FROM UAT (52H-#) CB TRIP OFF/TRIP ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) REK ○
○ ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2
(P1)

3811 * BBA 10 XG 02 INCOMING FROM UNIT AUXILIARY TRANSFORMER (52H-#) TRIP CIRCUIT HEALTHY 32 IC FRM UAT (52H-#) TRP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) REK ○ ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2
(P1)

3812 * BBA 10 XG 03 INCOMING FROM UNIT AUXILIARY TRANSFORMER (52H-#) CB CLOSED INDICATION 29 IC FROM UAT (52H-#) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3813 * BBA 10 XG 04 INCOMING FROM UNIT AUXILIARY TRANSFORMER (52H-#) ES CLOSED INDICATION 29 IC FROM UAT (52H-#) ES CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3814 * BBA 10 XG 05 INCOMING FROM UNIT AUXILIARY TRANSFORMER (52H-#) REMOTE MODE SELECTED 27 IC FROM UAT (52H-#) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2

NO
3815 * BBA 10 YB 11 OUTGOING TO UNIT SERVICE TRANSFORMER (52HA-#) CB OPEN COMMAND 30 OG TO UST (52HA-#) CB OPEN CMD OFF/OPEN ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG REK ○ ---- ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE
NO
3816 * BBA 10 YB 12 OUTGOING TO UNIT SERVICE TRANSFORMER (52HA-#) CB CLOSE COMMAND 31 OG TO UST (52HA-#) CB CLOSE CMD OFF/CLOSE ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG REK ○ ---- ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE

3817 * BBA 10 XG 11 OUTGOING TO UNIT SERVICE TRANSFORMER (52HA-#) CB TRIP INDICATION 26 OG TO UST (52HA-#) CB TRIP OFF/TRIP ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) REK ○
○ ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2
(P1)

3818 * BBA 10 XG 12 OUTGOING TO UNIT SERVICE TRANSFORMER (52HA-#) TRIP CIRCUIT HEALTHY 32 OG TO UST (52HA-#) TRIP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) REK ○
○ ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2
(P1)

3819 * BBA 10 XG 13 OUTGOING TO UNIT SERVICE TRANSFORMER (52HA-#) CB CLOSED INDICATION 27 OG TO UST (52HA-#) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3820 * BBA 10 XG 14 OUTGOING TO UNIT SERVICE TRANSFORMER (52HA-#) ES CLOSED INDICATION 27 OG TO UST (52HA-#) ES CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3821 * BBA 10 XG 15 OUTGOING TO UNIT SERVICE TRANSFORMER (52HA-#) REMOTE MODE SELECTED 25 OG TO UST (52HA-#) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2

NO
3822 * BBA 10 YB 21 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-#) CB OPEN COMMAND 31 OG TO MVSWG (52HB-#) CB OPN CMD OFF/OPEN ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG REK ○ ---- ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE
NO
3823 * BBA 10 YB 22 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-#) CB CLOSE COMMAND 31 OG TO MVSWG (52HB-#) CB CLS CMD OFF/CLOSE ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG REK ○ ---- ○ ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE

3824 * BBA 10 XG 21 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-#) CB TRIP INDICATION 28 OG TO MVSWG (52HB-#) CB TRIP OFF/TRIP ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2
○ ○
(P1)
3825 * BBA 10 XG 22 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-#) TRIP CIRCUIT HEALTHY 29 OG TO MVSWG (52HB-#) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2
○ ○
(P1)
3826 * BBA 10 XG 23 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-#) CB CLOSED INDICATION 29 OG TO MVSWG (52HB-#) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO *DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
3827 * BBA 10 XG 24 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-#) ES CLOSED INDICATION 29 OG TO MVSWG (52HB-#) ES CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3828 * BBA 10 XG 25 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-#) REMOTE MODE SELECTED 27 OG TO MVSWG (52HB-#) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

NO
3829 * BBA 10 YB 23 SPARE MOTOR (550 kW) STOP COMMAND 29 SPARE MOTOR (550 kW) STOP CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG REK ○ ---- ○ ---- ○ ----
PULSE
NC
3830 * BBA 10 YB 24 SPARE MOTOR (550 kW) START COMMAND 30 SPARE MOTOR (550 kW) START CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(MV) NA *MVSWG REK ○ ---- ○ ---- ○ ----
PULSE

3831 * BBA 10 XG 26 SPARE MOTOR (550 kW) RUNNING INDICATION 28 SPARE MOTOR (550 kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3832 * BBA 10 XG 27 SPARE MOTOR (550 kW) RACK-IN POSITION 32 SPARE MOTOR (550 kW) RACK-IN POS OFF/ON ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3833 * BBA 10 XG 28 SPARE MOTOR (550 kW) REMOTE MODE SELECTED 27 SPARE MOTOR (550 kW) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3834 * BBA 10 XG 29 SPARE MOTOR (550 kW) TRIP CIRCUIT HEALTHY 29 SPARE MOTOR (550 kW) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ----
○ ○
(P1)
3835 * BBA 10 XG 30 SPARE MOTOR (550 kW) TRIP INDICATION 25 SPARE MOTOR (550 kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ----
○ ○
(P1)
NO
3836 * BFA 10 YB 01 INCOMING FROM UNIT SERVICE TRANSFORMER (52LA-#) OPEN COMMAND 29 IC FROM UST (52LA-#) OPEN CMD OFF/OPEN ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE
NO
3837 * BFA 10 YB 02 INCOMING FROM UNIT SERVICE TRANSFORMER (52LA-#) CLOSE COMMAND 30 IC FROM UST (52LA-#) CLOSE CMD OFF/CLOSE ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE

3838 * BFA 10 XG 01 INCOMING FROM UNIT SERVICE TRANSFORMER (52LA-#) TRIP INDICATION 25 IC FROM UST (52LA-#) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2
○ ○
(P1)
3839 * BFA 10 XG 02 INCOMING FROM UNIT SERVICE TRANSFORMER (52LA-#) TRIP CIRCUIT HEALTHY 29 IC FROM UST (52LA-#) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2
○ ○
(P1)
3840 * BFA 10 XG 03 INCOMING FROM UNIT SERVICE TRANSFORMER (52LA-#) CB CLOSED INDICATION 29 IC FROM UST (52LA-#) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3841 * BFA 10 XG 04 INCOMING FROM UNIT SERVICE TRANSFORMER (52LA-#) REMOTE MODE SELECTED 27 IC FROM UST (52LA-#) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

NO
3842 * BFA 10 YB 11 OUTGOING TO UNIT-# ESSENTIAL BOARD (52LB-#) CB OPEN COMMAND 31 OG TO U#EB (52LB-#) CB OPEN CMD OFF/OPEN ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE
NO
3843 * BFA 10 YB 12 OUTGOING TO UNIT-# ESSENTIAL BOARD (52LB-#) CB CLOSE COMMAND 32 OG TO U#EB (52LB-#) CB CLOSE CMD OFF/CLOSE ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE

3844 * BFA 10 XG 11 OUTGOING TO UNIT-# ESSENTIAL BOARD (52LB-#) TRIP INDICATION 24 OG TO U#EB (52LB-#) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2
○ ○
(P1)
3845 * BFA 10 XG 12 OUTGOING TO UNIT-# ESSENTIAL BOARD (52LB-#) TRIP CIRCUIT HEALTHY 28 OG TO U#EB (52LB-#) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2
○ ○
(P1)
3846 * BFA 10 XG 13 OUTGOING TO UNIT-# ESSENTIAL BOARD (52LB-#) CB CLOSE INDICATION 28 OG TO U#EB (52LB-#) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3847 * BFA 10 XG 14 OUTGOING TO UNIT-# ESSENTIAL BOARD (52LB-#) REMOTE MODE SELECTED 26 OG TO U#EB (52LB-#) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3848 * BFA 10 XQ 11 OUTGOING TO UNIT-# ESSENTIAL BOARD (52LB-#) CURRENT 27 OG TO U#EB (52LB-#) CURRENT 0-630 A AIX ---- ---- ---- ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

NO
3849 * BFA 10 YB 21 OUTGOING TO COMMON STATION LV SWITCHGEAR (52LC-#) CB OPEN COMMAND 32 OG TO LVSWG (52LC-#) CB OPEN CMD OFF/OPEN ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE
NO
3850 * BFA 10 YB 22 OUTGOING TO COMMON STATION LV SWITCHGEAR (52LC-#) CB CLOSE COMMAND 31 OG TO LVSWG (52LC-#) CB CLS CMD OFF/CLOSE ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE

3851 * BFA 10 XG 21 OUTGOING TO COMMON STATION LV SWITCHGEAR (52LC-#) TRIP INDICATION 25 OG TO LVSWG (52LC-#) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2
○ ○
(P1)
3852 * BFA 10 XG 22 OUTGOING TO COMMON STATION LV SWITCHGEAR (52LC-#) TRIP CIRCUIT HEALTHY 29 OG TO LVSWG (52LC-#) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2
○ ○
(P1)
3853 * BFA 10 XG 23 OUTGOING TO COMMON STATION LV SWITCHGEAR (52LC-#) CB CLOSE INDICATION 29 OG TO LVSWG (52LC-#) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3854 * BFA 10 XG 24 OUTGOING TO COMMON STATION LV SWITCHGEAR (52LC-#) REMOTE MODE SELECTED 27 OG TO LVSWG (52LC-#) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

NO
3855 * BFA 10 YB 31 OUTGOING TO UNIT-# NON ESSENTIAL BOARD (52LD-#) CB OPEN COMMAND 32 OG TO U#NEB (52LD-#) CB OPEN CMD OFF/OPEN ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE
NO
3856 * BFA 10 YB 32 OUTGOING TO UNIT-# NON ESSENTIAL BOARD (52LD-#) CB CLOSE COMMAND 31 OG TO U#NEB (52LD-#) CB CLS CMD OFF/CLOSE ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
PULSE

3857 * BFA 10 XG 31 OUTGOING TO UNIT-# NON ESSENTIAL BOARD (52LD-#) TRIP INDICATION 25 OG TO U#NEB (52LD-#) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2
○ ○
(P1)
3858 * BFA 10 XG 32 OUTGOING TO UNIT-# NON ESSENTIAL BOARD (52LD-#) TRIP CIRCUIT HEALTHY 29 OG TO U#NEB (52LD-#) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- Note; # is 1 for unit1,2 for unit2
○ ○
(P1)
3859 * BFA 10 XG 33 OUTGOING TO UNIT-# NON ESSENTIAL BOARD (52LD-#) CB CLOSE INDICATION 29 OG TO U#NEB (52LD-#) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3860 * BFA 10 XG 34 OUTGOING TO UNIT-# NON ESSENTIAL BOARD (52LD-#) REMOTE MODE SELECTED 27 OG TO U#NEB (52LD-#) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

3861 * BFA 10 XQ 31 OUTGOING TO UNIT-# NON ESSENTIAL BOARD (52LD-#) CURRENT 28 OG TO U#NEB (52LD-#) CURRENT 0-630 A AIX ---- ---- ---- ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2

NO
3862 * BFA 10 YB 33 SPARE MOTOR STARTER (250 kW) START COMMAND 31 SPR MTR STRTR (250 kW) STRT CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG REK ○ ---- ○ ---- ○ ----
PULSE
NC
3863 * BFA 10 YB 34 SPARE MOTOR STARTER (250 kW) STOP COMMAND 31 SPR MTR STRTR (250 kW) STOP CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVSWG REK ○ ---- ○ ---- ○ ----
PULSE

3864 * BFA 10 XG 35 SPARE MOTOR STARTER (250 kW) RUNNING INDICATION 32 SPARE MTR STRTR (250 kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3865 * BFA 10 XG 36 SPARE MOTOR STARTER (250 kW) RACK-IN POSITION 31 SPR MTR STRTR (250 kW) RACK POS OFF/ON ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ○ ---- ○ ----

3866 * BFA 10 XG 37 SPARE MOTOR STARTER (250 kW) REMOTE MODE SELECTED 31 SPARE MTR STRTR (250 kW) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ○ ---- ○ ----

3867 * BFA 10 XG 38 SPARE MOTOR STARTER (250 kW) TRIP INDICATION 31 SPARE MOTOR STRTR (250 kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○
○ ○ ---- ○ ----
(P1)

3868 * BFB 20 XG 01 DS/CB DUMMY FROM UNIT-1 LV SWITCHGEAR CLOSED INDICATION 30 DS/CB DUMMY FROM U1LVSWG CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ○ Rev.4 Change to SOE 4

3869 * BFB 20 XG 11 HWP (A) DISCHARGE ISOLATION VALVE MCCB CLOSE INDICATION 31 HWP (A) DISCG ISOL VLV MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3965 * BFB 20 XG 33 HWP (A) DISCHARGE ISOLATION VALVE MCCB TRIP INDICATION 32 HWP (A) DISCG ISOL VLV MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3870 * BFB 20 XG 12 HWP (B) DISCHARGE ISOLATION VALVE MCCB CLOSE INDICATION 31 HWP (B) DISCG ISOL VLV MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3966 * BFB 20 XG 34 HWP (B) DISCHARGE ISOLATION VALVE MCCB TRIP INDICATION 32 HWP (B) DISCG ISOL VLV MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3871 * BFB 20 XG 13 STEAM EJECTOR (A) NCG INLET VALVE MCCB CLOSE INDICATION 30 EJCTR (A) NCG INL VLV MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3967 * BFB 20 XG 35 STEAM EJECTOR (A) NCG INLET VALVE MCCB TRIP INDICATION 31 EJCTR (A) NCG INL VLV MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3872 * BFB 20 XG 14 STEAM EJECTOR (B) NCG INLET VALVE MCCB CLOSE INDICATION 30 EJCTR (B) NCG INL VLV MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ○ ---- ○ ----

3968 * BFB 20 XG 36 STEAM EJECTOR (B) NCG INLET VALVE MCCB TRIP INDICATION 31 EJCTR (B) NCG INL VLV MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○
○ ○ ---- ○ ----
(P1)
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO *DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
3873 * BFB 20 XG 15 STEAM EJECTOR (C) NCG INLET VALVE MCCB CLOSE INDICATION 30 EJCTR (C) NCG INL VLV MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ○ ---- ○ ----


3969 * BFB 20 XG 37 STEAM EJECTOR (C) NCG INLET VALVE MCCB TRIP INDICATION 31 EJCTR (C) NCG INL VLV MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ○ ---- ○ ----
(P1)

3874 * BFB 20 XG 16 VACUUM PUMP (A) SEAL WATER ISOLATING VALVE MCCB CLOSE INDICATION 32 VP(A) SL WATER ISOL VLV MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ○ ---- ○ ----

3970 * BFB 20 XG 38 VACUUM PUMP (A) SEAL WATER ISOLATING VALVE MCCB TRIP INDICATION 32 VP(A) SL WATER ISOL VLV MCCB TRP NORMAL/TRIP ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○
○ ○ ---- ○ ----
(P1)

3875 * BFB 20 XG 17 VACUUM PUMP (B) SEAL WATER ISOLATING VALVE MCCB CLOSE INDICATION 32 VP(B) SL WATER ISOL VLV MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ○ ---- ○ ----

3971 * BFB 20 XG 39 VACUUM PUMP (B) SEAL WATER ISOLATING VALVE MCCB TRIP INDICATION 32 VP(B) SL WATER ISOL VLV MCCB TRP NORMAL/TRIP ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○
○ ○ ---- ○ ----
(P1)

3877 * BFB 20 XG 19 OIL PURIFIER MCCB CLOSE INDICATION 23 OIL PURIFIER MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ○ ---- ○ ----

3974 * BFB 20 XG 40 OIL PURIFIER MCCB TRIP INDICATION 22 OIL PURIFIER MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○
○ ○ ---- ○ ----
(P1)

3878 * BFB 20 XG 20 HWP (A) MINI FLOW VALVE MCCB CLOSE INDICATION 32 HWP (A) MINI FLOW VALVE MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3879 * BFB 20 XG 21 HWP (A) MINI FLOW VALVE MCCB TRIP INDICATION 32 HWP (A) MINI FLOW VALVE MCCB TRP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3880 * BFB 20 XG 22 HWP (B) MINI FLOW VALVE MCCB CLOSE INDICATION 32 HWP (B) MINI FLOW VALVE MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----


3881 * BFB 20 XG 23 HWP (B) MINI FLOW VALVE MCCB TRIP INDICATION 32 HWP (B) MINI FLOW VALVE MCCB TRP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ○ ----
(P1)
3975 * BFB 20 XG 50 BACKUP EJECTOR NCG INLET VALVE CLOSE INDICATION 32 BACKUP EJECTOR NCG INLET VLV CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3976 * BFB 20 XG 51 BACKUP EJECTOR NCG INLET VALVE TRIP INDICATION 32 BACKUP EJECTOR NCG INLET VLV TRP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)

3884 * BFB 20 XG 26 INTAKE SCREEN ELECTRIC TROLLEY HOIST MCCB CLOSE INDICATION 28 INTAKE SCREEN HOIST MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3885 * BFB 20 XG 27 INTAKE SCREEN ELECTRIC TROLLEY HOIST MCCB TRIP INDICATION 30 INTAKE SCREEN HOIST MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3886 * BFB 20 XG 28 LIGHTING FOR STG ENCLOSURE MCCB CLOSE INDICATION 30 STG ENCLOSURE LIGHT MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3887 * BFB 20 XG 29 LIGHTING FOR STG ENCLOSURE MCCB TRIP INDICATION 29 STG ENCLOSURE LIGHT MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)

3888 * BFB 20 XG 30 LIGHTING TRANSFORMER U1LVB-NE (150 kVA) MCCB CLOSE INDICATION 32 LT U1LVB-NE (150 kVA) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3889 * BFB 20 XG 31 LIGHTING TRANSFORMER U1LVB-NE (150 kVA) TRIP INDICATION 26 LT U1LVB-NE (150 kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3890 * BFB 20 XQ 32 LIGHTING TRANSFORMER U1LVB-NE (150 kVA) CURRENT 29 LT U1LVB-NE (150 kVA) CURRENT 0-300 A AIX ---- ---- ---- ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3891 * BFB 20 XG 52 SPARE FEEDER (3 kW) MCCB CLOSE INDICATION 30 SPARE FEEDER (3 kW) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3892 * BFB 20 XG 53 SPARE FEEDER (3 kW) TRIP CLOSE INDICATION 30 SPARE FEEDER (3 kW) TRIP CLOSE NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3893 * BFB 20 XG 54 SPARE FEEDER (3 kW) MCCB CLOSE INDICATION 30 SPARE FEEDER (3 kW) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----


3894 * BFB 20 XG 55 SPARE FEEDER (3 kW) TRIP CLOSE INDICATION 30 SPARE FEEDER (3 kW) TRIP CLOSE OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ○ ----
(P1)
3895 * BFB 20 XG 56 SPARE FEEDER (150 kVA) MCCB CLOSE INDICATION 31 SPARE FEEDER (150 kVA) MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3896 * BFB 20 XG 57 SPARE FEEDER (150kVA) TRIP INDICATION 26 SPARE FEEDER (150kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3897 * BFB 20 XQ 33 SPARE FEEDER (150kVA) CURRENT 29 SPARE FEEDER (150kVA) CURRENT 0-300 A AIX ---- ---- ---- ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

NO
3898 * BFB 20 YB 01 SPARE FEEDER WITH CONTACTOR (0.75 kW) START COMMAND 32 SPARE CNTCTR (0.75 kW) START CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB REK ○ ---- ---- ---- ○ ----
PULSE
NC
3899 * BFB 20 YB 02 SPARE FEEDER WITH CONTACTOR (0.75 kW) STOP COMMAND 31 SPARE CNTCTR (0.75 kW) STOP CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB REK ○ ---- ---- ---- ○ ----
PULSE

3900 * BFB 20 XG 58 SPARE FEEDER WITH CONTACTOR (0.75 kW) RUNNING INDICATION 30 SPARE CNTCTR (0.75 kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3901 * BFB 20 XG 59 SPARE FEEDER WITH CONTACTOR (0.75 kW) SPARE 28 SPARE CNTCTR (0.75 kW) SPARE OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3882 * BFB 20 XG 24 U1 SPARE MOTOR STARTER (0.75 kW) REMOTE MODE SELECTED 27 SPARE CNTCTR (22 kW) REMOTE OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3902 * BFB 20 XG 60 SPARE FEEDER WITH CONTACTOR (0.75 kW) TRIP INDICATION 27 SPARE CNTCTR (0.75 kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3883 * BFB 20 XG 25 U1 SPARE MOTOR STARTER (0.75 kW) RACK-IN POSITION 30 SPARE CNTCTR (0.75 kW) RACK-IN OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

NO
3903 * BFB 20 YB 03 SPARE FEEDER WITH CONTACTOR (15.5 kW) START COMMAND 32 SPARE CNTCTR (15.5 kW) START CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB REK ○ ---- ---- ---- ○ ----
PULSE
NC
3904 * BFB 20 YB 04 SPARE FEEDER WITH CONTACTOR (15.5 kW) STOP COMMAND 31 SPARE CNTCTR (15.5 kW) STOP CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB REK ○ ---- ---- ---- ○ ----
PULSE

3905 * BFB 20 XG 61 SPARE FEEDER WITH CONTACTOR (15.5 kW) RUNNING INDICATION 30 SPARE CNTCTR (15.5 kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3906 * BFB 20 XG 62 SPARE FEEDER WITH CONTACTOR (15.5 kW) SPARE 28 SPARE CNTCTR (15.5 kW) SPARE OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

4004 * BFB 20 XG 78 SPARE FEEDER WITH CONTACTOR (15.5 kW) REMOTE MODE SELECTED 28 SPARE CNTCTR (15.5kW) REMOTE OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3907 * BFB 20 XG 63 SPARE FEEDER WITH CONTACTOR (15.5 kW) TRIP INDICATION 27 SPARE CNTCTR (15.5 kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
4005 * BFB 20 XG 79 SPARE FEEDER WITH CONTACTOR (15.5 kW) RACK-IN POSITION 30 SPARE CNTCTR (15.5 kW) RACK-IN OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

NO
3908 * BFB 20 YB 05 SPARE FEEDER WITH CONTACTOR (15 kW) START COMMAND 31 SPARE CNTCTR (15 kW) START CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB REK ○ ---- ---- ---- ○ ----
PULSE
NC
3909 * BFB 20 YB 06 SPARE FEEDER WITH CONTACTOR (15 kW) STOP COMMAND 29 SPARE CNTCTR (15 kW) STOP CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB REK ○ ---- ---- ---- ○ ----
PULSE

3910 * BFB 20 XG 64 SPARE FEEDER WITH CONTACTOR (15 kW) RUNNING INDICATION 28 SPARE CNTCTR (15 kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3911 * BFB 20 XG 65 SPARE FEEDER WITH CONTACTOR (15 kW) SPARE 26 SPARE CNTCTR (15 kW) SPARE OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

4006 * BFB 20 XG 80 SPARE FEEDER WITH CONTACTOR (15 kW) REMOTE MODE SELECTED 26 SPARE CNTCTR (15kW) REMOTE OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3912 * BFB 20 XG 66 SPARE FEEDER WITH CONTACTOR (15 kW) TRIP INDICATION 25 SPARE CNTCTR (15 kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
4007 * BFB 20 XG 81 SPARE FEEDER WITH CONTACTOR (15 kW) RACK-IN POSITION 28 SPARE CNTCTR (15 kW) RACK-IN OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

NO
3977 * BFB 20 YB 07 SPARE FEEDER WITH CONTACTOR (15 kW) START COMMAND 30 SPARE CNTCTR (15 kW) START CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB REK ○ ---- ○ ---- ○ ----
PULSE
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO *DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
NC
3978 * BFB 20 YB 08 SPARE FEEDER WITH CONTACTOR (15 kW) STOP COMMAND 29 SPARE CNTCTR (15 kW) STOP CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB REK ○ ---- ○ ---- ○ ----
PULSE

3979 * BFB 20 XG 67 SPARE FEEDER WITH CONTACTOR (15 kW) RUNNING INDICATION 28 SPARE CNTCTR (15 kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ○ ---- ○ ----

3980 * BFB 20 XG 68 SPARE FEEDER WITH CONTACTOR (15 kW) SPARE 26 SPARE CNTCTR (15 kW) SPARE OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

4008 * BFB 20 XG 82 SPARE FEEDER WITH CONTACTOR (15 kW) REMOTE MODE SELECTED 26 SPARE CNTCTR (15kW) REMOTE OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3981 * BFB 20 XG 69 SPARE FEEDER WITH CONTACTOR (15 kW) TRIP INDICATION 25 SPARE CNTCTR (15 kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
4009 * BFB 20 XG 83 SPARE FEEDER WITH CONTACTOR (15 kW) RACK-IN POSITION 28 SPARE CNTCTR (15 kW) RACK-IN OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

NO
3915 * BFB 20 YB 09 SPARE MOTOR STARTER (22 kW) START COMMAND 32 SPARE MTR STRTR (22 kW) STRT CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB REK ○ ---- ---- ---- ○ ----
PULSE
NC
3916 * BFB 20 YB 10 SPARE MOTOR STARTER (22 kW) STOP COMMAND 31 SPARE MTR STRTR (22 kW) STP CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVNESWB REK ○ ---- ---- ---- ○ ----
PULSE

3917 * BFB 20 XG 70 SPARE MOTOR STARTER (22 kW) RUNNING INDICATION 31 SPARE MTR STRTR (22 kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3918 * BFB 20 XG 71 SPARE MOTOR STARTER (22 kW) SPARE 31 SPARE MOTOR STRTR (22 kW) SPARE OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3919 * BFB 20 XG 72 SPARE MOTOR STARTER (22 kW) REMOTE MODE SELECTED 32 SPARE MOTOR STRTR (22 kW) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3920 * BFB 20 XG 73 SPARE MOTOR STARTER (22 kW) TRIP INDICATION 32 SPARE MOTOR STARTER (22 kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3921 * BFB 20 XG 74 SPARE MOTOR STARTER (22 kW) RACK-IN POSITION 31 SPARE MTR STRTR (22 kW) RACK-IN OFF/ON ---- DI ---- ---- NO ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3922 * BFB 20 XQ 75 SPARE MOTOR STARTER (22 kW) CURRENT 31 SPARE MTR STRTR (22 kW) CURRENT 0-100 A AIX ---- ---- ---- ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

Note; # is 1 for unit1,2 for unit2


3923 * BFB 10 XG 01 DS/CB DUMMY FROM UNIT-# LV SWITCHGEAR CLOSED INDICATION 30 DS/CB DUMMY FROM U#LVSWG CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ○ 4
Rev.4 Change to SOE

3924 * BFB 10 XG 02 DS/ACB DUMMY TO COMMON STATION ESSENTIAL BOARD CLOSED INDICATION 31 DS/ACB DUMMY TO COM ST EB CLOSE OPEN/CLOSE ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ○ Rev.4 Change to SOE 4

3925 * BFB 10 XG 11 GENERATOR SPACE HEATER MCCB CLOSE INDICATION 27 GEN SPACE HEATER MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3926 * BFB 10 XG 12 GENERATOR EXCITER SPACE HEATER MCCB CLOSE INDICATION 31 GEN EXCTR SPACE HEATER MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3927 * BFB 10 XG 13 AC UPS SYSTEM A MCCB CLOSE INDICATION 27 AC UPS SYSTEM A MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3928 * BFB 10 XG 14 AC UPS SYSTEM A TRIP INDICATION 20 AC UPS SYSTEM A TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO *DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
3929 * BFB 10 XG 15 DC SYSTEM A MCCB CLOSE INDICATION 22 DC SYSTEM A MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ---- ---- ---- ---- ○ ----


3930 * BFB 10 XG 16 DC SYSTEM A TRIP INDICATION 16 DC SYSTEM A TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ○ ----
(P1)
3931 * BFB 10 XG 17 GENERATOR TRANSFORMER PACKAGE MCCB CLOSE INDICATION 21 GT PACKAGE MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3982 * BFB 10 XG 19 GENERATOR TRANSFORMER PACKAGE MCCB TRIP INDICATION 20 GT PACKAGE MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)

3932 * BFB 10 XG 18 GCB PACKAGE MCCB CLOSE INDICATION 22 GCB PACKAGE MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3983 * BFB 10 XG 20 GCB PACKAGE MCCB TRIP INDICATION 21 GCB PACKAGE MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3933 * BFB 10 XG 21 SPARE FEEDER (3.3kW) MCCB CLOSE INDICATION 31 SPARE FEEDER (3.3kW) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3984 * BFB 10 XG 22 SPARE FEEDER (3.3kW) MCCB TRIP INDICATION 30 SPARE FEEDER (3.3kW) MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)

3985 * BFB 10 XG 23 SPARE FEEDER (60kVA) MCCB CLOSE INDICATION 31 SPARE FEEDER (60kVA) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3986 * BFB 10 XG 24 SPARE FEEDER (60kVA) MCCB TRIP INDICATION 30 SPARE FEEDER (60kVA) MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
NO
3987 * BFB 10 YB 01 SPARE MOTOR STARTER (2.2kW) START COMMAND 32 SPARE MTR STRTR (2.2kW) STRT CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB REK ---- ---- ---- ---- ○ ----
PULSE
NC
3988 * BFB 10 YB 02 SPARE MOTOR STARTER (2.2kW) STOP COMMAND 31 SPARE MTR STRTR (2.2kW) STP CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB REK ---- ---- ---- ---- ○ ----
PULSE

3989 * BFB 10 XG 25 SPARE MOTOR STARTER (2.2kW) RUNNING INDICATION 31 SPARE MTR STRTR (2.2kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3990 * BFB 10 XG 26 SPARE MOTOR STARTER (2.2kW) SPARE 31 SPARE MTR STARTER (2.2kW) SPARE OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3991 * BFB 10 XG 27 SPARE MOTOR STARTER (2.2kW) RACK-IN POSITION 31 SPARE MTR STRTR (2.2kW) RACK-IN LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3992 * BFB 10 XG 28 SPARE MOTOR STARTER (2.2kW) REMOTE MODE SELECTED 32 SPARE MTR STARTER (2.2kW) REMOTE OFF/TRIP ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3993 * BFB 10 XG 29 SPARE MOTOR STARTER (2.2kW) TRIP INDICATION 32 SPARE MOTOR STARTER (2.2kW) TRIP OFF/ON ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
NO
3994 * BFB 10 YB 03 SPARE MOTOR STARTER (5.5kW) START COMMAND 32 SPARE MTR STRTR (5.5kW) STRT CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB REK ---- ---- ---- ---- ○ ----
PULSE
NC
3995 * BFB 10 YB 04 SPARE MOTOR STARTER (5.5kW) STOP COMMAND 32 SPARE MTR STRTR (5.5kW) STOP CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB REK ---- ---- ---- ---- ○ ----
PULSE

3996 * BFB 10 XG 30 SPARE MOTOR STARTER (5.5kW) RUNNING INDICATION 31 SPARE MTR STRTR (5.5kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3997 * BFB 10 XG 31 SPARE MOTOR STARTER (5.5kW) SPARE 31 SPARE MTR STARTER (5.5kW) SPARE OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3998 * BFB 10 XG 32 SPARE MOTOR STARTER (5.5kW) RACK-IN POSITION 31 SPARE MTR STRTR (5.5kW) RACK-IN LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3999 * BFB 10 XG 33 SPARE MOTOR STARTER (5.5kW) REMOTE MODE SELECTED 32 SPARE MOTOR STRTR (5.5kW) REMOTE OFF/TRIP ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

4000 * BFB 10 XG 34 SPARE MOTOR STARTER (5.5kW) TRIP INDICATION 32 SPARE MOTOR STARTER (5.5kW) TRIP OFF/ON ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
NO
3934 * BFB 10 YB 05 SPARE MOTOR STARTER (30kW) START COMMAND 32 SPARE MTR STRTR (30kW) START CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB REK ---- ---- ---- ---- ○ ----
PULSE
NC
3935 * BFB 10 YB 06 SPARE MOTOR STARTER (30kW) STOP COMMAND 31 SPARE MTR STRTR (30kW) STOP CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) NA *LVESWB REK ---- ---- ---- ---- ○ ----
PULSE

3936 * BFB 10 XG 35 SPARE MOTOR STARTER (30kW) RUNNING INDICATION 32 SPARE MTR STARTER (30kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3937 * BFB 10 XG 36 SPARE MOTOR STARTER (30kW) SPARE 30 SPARE MTR STARTER (30kW) SPARE OFF/ON ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3938 * BFB 10 XG 37 SPARE MOTOR STARTER (30kW) RACK-IN POSITION 30 SPARE MTR STRTR (30kW) RACK-IN LOCAL/REMOTE ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3939 * BFB 10 XG 38 SPARE MOTOR STARTER (30kW) REMOTE MODE SELECTED 31 SPARE MTR STARTER (30kW) REMOTE OFF/TRIP ---- DI ---- ---- NO ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3940 * BFB 10 XG 39 SPARE MOTOR STARTER (30kW) TRIP INDICATION 31 SPARE MOTOR STARTER (30kW) TRIP OFF/ON ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3941 * BFB 10 XQ 01 SPARE MOTOR STARTER (30kW) CURRENT 32 SPARE MTR STARTER (30kW) CURRENT 0-150 A AIX ---- ---- ---- ---- *LVESWB NA *MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3 Wire System (with 24VDC from


3942 * CYQ 01 CQ 001 XQ 01 Gas Detector At The Bottom Of Cooling Tower Staircase 26 GAS DETECTOR AT CT STATION 0 - 100 ppm AIX ---- ---- ---- ---- F U0-ARS *DCS REK ○ ---- ---- ---- ○ ----
*DCS)
3 Wire System (with 24VDC from
3943 * CYQ 01 CQ 002 XQ 02 Gas Detector Near The Gas Extraction System 19 GAS DETECTOR AT GES 0 - 100 ppm AIX ---- ---- ---- ---- F U0-ARS *DCS REK ○ ---- ---- ---- ○ ----
*DCS)
3 Wire System (with 24VDC from
3944 * CYQ 01 CQ 003 XQ 03 Gas Detector Near Condenser 25 GAS DETECTOR AT CONDENSER 0 - 100 ppm AIX ---- ---- ---- ---- F NA *DCS REK ○ ---- ---- ---- ○ ----
*DCS)
2.DCS IO LIST FOR HARD WIRE
2-1.POWER PLANT FOR EACH UNIT AREA

APPLIED ALARM ILD or IBD


NC/NO *DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
3 Wire System (with 24VDC from
3945 * CYQ 01 CQ 004 XQ 04 Gas Detector Near Turbine Generator Area 19 GAS DETECTOR AT T/G 0 - 100 ppm AIX ---- ---- ---- ---- F NA *DCS REK ○ ---- ---- ---- ○ ----
*DCS)
NO
3946 * CYQ 01 EJ 001 YB 01 Sounder and Beacon Unit # Area 20 UNIT# SOUNDER&BEACON OFF/ON ---- DOW 110V 5W ---- *DCS U0-ARS F REK ---- ---- ---- ---- ○ ---- Note; # is 1 for unit1,2 for unit2
LATCH

3947 * LBA 71 CT 001 XQ 01 HP Scrubber Outlet Steam Temperature 29 HP Scrubber Outlet Steam Temp 0 - 220 DegC RTD ---- ---- ---- ---- F U0-ARS *DCS REK ○ ---- ---- ---- ○ ---- Rev.4;Signal Type is changed 4

3948 * LBA 91 CT 001 XQ 01 LP Scrubber Outlet Steam Temperature 29 LP Scrubber Outlet Steam Temp 0 - 200 DegC RTD ---- ---- ---- ---- F U0-ARS *DCS REK ○ ---- ---- ---- ○ ---- Rev.4;Signal Type is changed 4

3949 * LBA 71 CF 001 XQ 01 Flow Transmitter from Unit * HP Steam Header to RD01-LFC-10-BB-001 26 FT from U# HP Steam Header 0 - 100 Kg/s AII ---- ---- ---- ---- F U0-ARS *DCS R08 ○ ---- ---- ---- ○ ----

3950 * LBA 71 CF 002 XQ 01 Flow Transmitter from Unit * HP Steam Header to RD01-LFC-10-BB-001 29 FT from Unit* HP Steam Header 0 - 100 Kg/s AII ---- ---- ---- ---- F U0-ARS *DCS R08 ○ ---- ---- ---- ○ ----

3951 * LBA 91 CF 001 XQ 01 Flow Transmitter from Unit * LP Steam Header to RD01-LFC-10-BB-001 29 FT from Unit* LP Steam Header 0 - 100 Kg/s AII ---- ---- ---- ---- F U0-ARS *DCS REK ○ ---- ---- ---- ○ ----

3952 * LBA 91 CF 002 XQ 01 Flow Transmitter from Unit * LP Steam Header to RD01-LFC-10-BB-001 29 FT from Unit* LP Steam Header 0 - 100 Kg/s AII ---- ---- ---- ---- F U0-ARS *DCS REK ○ ---- ---- ---- ○ ----

NO
3953 * GUB 01 AP 001 YB 01 HWP Pit Submersible Pump A Start Command 31 HWP Pit Submrsbl Pmp A Strt CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) U0-ARS STLVESWB W55 ---- ---- ---- ---- ○ ----
PULSE
NC
3954 * GUB 01 AP 001 YB 02 HWP Pit Submersible Pump A Stop Command 30 HWP Pit Submrsbl Pmp A Stp CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) U0-ARS STLVESWB W55 ---- ---- ---- ---- ○ ----
PULSE

3955 * GUB 01 AP 001 XG 01 HWP Pit Submersible Pump A Running Indication 30 HWP Pit Submersible Pump A Run STOP/RUN ---- DI ---- ---- NO ---- STLVESWB U0-ARS *MCCRIO(LV) W55 ○ ---- ---- ---- ○ ----

3956 * GUB 01 AP 001 XG 02 HWP Pit Submersible Pump A Trip Indication 31 HWP Pit Submersible Pump A Trip OFF/TRIP ---- DI ---- ---- NC ---- STLVESWB U0-ARS *MCCRIO(LV) W55 ---- ○ ---- ---- ----

(P2)
3957 * GUB 01 AP 001 XG 03 HWP Pit Submersible Pump A Remote Mode Selected 30 HWP Pit Submrsbl Pump A Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVESWB U0-ARS *MCCRIO(LV) W55 ○ ---- ---- ---- ○ ----

3958 * GUB 01 AP 001 XG 04 HWP Pit Submersible Pump A Rack-in Position 31 HWP Pit Submrsbl Pump A Rack-in OFF/ON ---- DI ---- ---- NO ---- STLVESWB U0-ARS *MCCRIO(LV) W55 ○ ---- ---- ---- ○ ----

NO
3959 * GUB 01 AP 002 YB 01 HWP Pit Submersible Pump B Start Command 32 HWP Pit Submrsbl Pump B Strt CMD OFF/START ---- DOL DC24 2W ---- *MCCRIO(LV) U0-ARS STLVESWB W56 ---- ---- ---- ---- ○ ----
PULSE
NC
3960 * GUB 01 AP 002 YB 02 HWP Pit Submersible Pump B Stop Command 31 HWP Pit Submrsbl Pump B Stp CMD OFF/STOP ---- DOL DC24 2W ---- *MCCRIO(LV) U0-ARS STLVESWB W56 ---- ---- ---- ---- ○ ----
PULSE

3961 * GUB 01 AP 002 XG 01 HWP Pit Submersible Pump B Running Indication 30 HWP Pit Submersible Pump B Run STOP/RUN ---- DI ---- ---- NO ---- STLVESWB U0-ARS *MCCRIO(LV) W56 ○ ---- ---- ---- ○ ----

3962 * GUB 01 AP 002 XG 02 HWP Pit Submersible Pump B Trip Indication 31 HWP Pit Submersible Pump B Trip OFF/TRIP ---- DI ---- ---- NC ---- STLVESWB U0-ARS *MCCRIO(LV) W56 ---- ○ ---- ---- ----

(P2)
3963 * GUB 01 AP 002 XG 03 HWP Pit Submersible Pump B Remote Mode Selected 30 HWP Pit Submrsbl Pump B Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVESWB U0-ARS *MCCRIO(LV) W56 ○ ---- ---- ---- ○ ----

3964 * GUB 01 AP 002 XG 04 HWP Pit Submersible Pump B Rack-in Position 31 HWP Pit Submrsbl Pump B Rack-in OFF/ON ---- DI ---- ---- NO ---- STLVESWB U0-ARS *MCCRIO(LV) W56 ○ ---- ---- ---- ○ ----

4010 * GUB 01 CL 001 XQ 01 HWP SUMP PIT LEVEL 18 HWP SUMP PIT LEVEL 0 - 8000 mm AII ---- ---- ---- 1% F U0-ARS *DCS R84 ○ ---- ---- ---- EL-6000 EL-6500 EL-7000 EL-7280
○ ○
(P2)

4011 * BBA 10 XG 10 6.3kV SWITCHGEAR UNDERVOLTAGE TRIP 22 6.3kV SWG UNDERVOLTAGE HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ----
○ ○
(P1)
4012 * BFA 10 XG 10 UNIT-# LV SWITCHGEAR UNDERVOLTAGE TRIP 18 LVSWG UNDERVOLTAGE HEALTHY/FAULT ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
4013 * BFB 20 XG 10 UNIT-# LV NON-ESSENTIAL BOARD UNDERVOLTAGE TRIP 18 LVNEB UNDERVOLTAGE HEALTHY/FAULT ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)

4014 * BFB 10 XG 10 UNIT-# LV ESSENTIAL BOARD UNDERVOLTAGE TRIP 17 LVEB UNDERVOLTAGE HEALTHY/FAULT ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
4015 * BBA 10 XG 40 U1 6.3kV SWITCHGEAR LOSS OF CONTROL SUPPLY 32 6.3kV SWG LOSS OF CONTROL SUPPLY HEALTHY/FAULT ---- DI ---- ---- NC ---- *MVSWG NA *MCCRIO(MV) REK ○ ---- ---- ----
○ ○
(P1)
4016 * BFA 10 XG 30 U1 LV SWITCHGEAR LOSS OF CONTROL SUPPLY 28 LVSWG LOSS OF CONTROL SUPPLY HEALTHY/FAULT ---- DI ---- ---- NC ---- *LVSWG NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
4017 * BFB 20 XG 90 U1 NON-ESSENTIAL SWITCHBOARD LOSS OF CONTROL SUPPLY 28 LVNEB LOSS OF CONTROL SUPPLY HEALTHY/FAULT ---- DI ---- ---- NC ---- *LVNESWB NA *MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
4018 * BFB 10 XG 40 U1 ESSENTIAL SWITCHBOARD LOSS OF CONTROL SUPPLY 27 LVEB LOSS OF CONTROL SUPPLY HEALTHY/FAULT ---- DI ---- ---- NC ---- *LVESWB NA *MCCRIO(LV) REK ○ ○ ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-2.POWER PLANT FOR COMMON AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
L 11.4
1 RD00 LCE 30 CP 001 XQ 01 Wash Water Pump Discharge Pressure 23 WWP Discharge Pressure 0-25 barg AII ---- ---- ---- 1% F U0-ARS RD00DCS R22 ○ ○ ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2) (P2)
HH/H/ BTM+1500 BTM+150 BTM+100
2 RD00 QCH 30 CL 001 XQ 01 Dilution NaOH Tank level 24 Dilution NaOH Tank level 0-1950 mm AIX ---- ---- ---- 1% NAOHLCP U0-ARS RD00DCS R87 ○ ○ ---- ○ ---- Rev.4 Filled Range 4
L (P2) (P2) (P2)
HH/H/ BTM+1800 BTM+150 BTM+100
432 RD00 QCH 11 CL 001 XQ 01 Concentrated NaOH Tank Level 28 Concentrated NaOH Tank Level 0-2350 mm AIX ---- ---- ---- 1% NAOHLCP U0-ARS RD00DCS R87 ○ ○ ---- ○ ---- Rev.4 Filled Range 4
L (P2) (P2) (P2)
L
3 RD00 PBN 20 CL 081 XQ 01 Biocide-1 Tank Level L 22 Biocide-1 Tank Level L NORMAL/LOW ---- DI ---- ---- NC ---- NAOHLCP U0-ARS RD00DCS R87 ○ ○ ---- ○ ---- Rev.4; From lodation is corrected 4
(P2)
L
4 RD00 PBN 24 CL 081 XQ 01 Biocide-2 Tank Level L 22 Biocide-2 Tank Level L NORMAL/LOW ---- DI ---- ---- NC ---- NAOHLCP U0-ARS RD00DCS R87 ○ ○ ---- ○ ---- Rev.4; From lodation is corrected 4
(P2)
H
5 RD00 MAV 90 CL 081 XG 01 Clean Lubrication Oil Storage Tank Level (A) 29 Clean Lube Oil Tank Level (A) NORMAl/HIGH ---- DI ---- ---- NC ---- F U0-ARS RD00DCS R89 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
H
6 RD00 MAV 90 CL 082 XG 01 Clean Lubrication Oil Storage Tank Level (B) 29 Clean Lube Oil Tank Level (B) NORMAl/LOW ---- DI ---- ---- NC ---- F U0-ARS RD00DCS R89 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
H
7 RD00 MAV 90 CL 083 XG 01 Dirty Lubrication Oil Storage Tank Level (A) 29 Dirty Lube Oil Tank Level (A) NORMAl/HIGH ---- DI ---- ---- NC ---- F U0-ARS RD00DCS R89 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
H
8 RD00 MAV 90 CL 084 XG 01 Dirty Lubrication Oil Storage Tank Level (B) 29 Dirty Lube Oil Tank Level (B) NORMAl/LOW ---- DI ---- ---- NC ---- F U0-ARS RD00DCS R89 ○ ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
(P2)
HH/H/ BTM+2100 BTM+1300
9 RD00 GMA 10 CL 001 XG 01 Scrubber Area Sump Pit Level 29 Scrubber Area Sump Pit Level BTM-BTM+2600 mm AII ---- ---- ---- 1% F U0-ARS RD00DCS R89 ○ ---- ---- ○ ---- Rev.4 Filled Range 4
L/LL (P2) (P2)
NO
13 RD00 LCE 21 AP 001 YB 01 WWP(A) Start Command 20 WWP(A) START COMMAND OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NA STLVNESWB W33 ---- ---- ○ ---- ○ ----
PULSE
NC
14 RD00 LCE 21 AP 001 YB 02 WWP(A) Stop Command 19 WWP(A) STOP COMMAND OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NA STLVNESWB W33 ---- ---- ○ ---- ○ ----
PULSE

15 RD00 LCE 21 AP 001 XG 01 WWP(A) Running Indication 14 WWP(A) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W33 ○ P2 ○ ---- ○ ----

16 RD00 LCE 21 AP 001 XG 02 WWP(A) Trip Indication 11 WWP(A) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W33 ---- P1 ○ ---- ○ ----

17 RD00 LCE 21 AP 001 XG 03 WWP(A) Remote Mode Selected 26 WWP(A) RMOTE MODE SELECTED LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W33 ○ ---- ○ ---- ○ ----

18 RD00 LCE 21 AP 001 XG 04 WWP(A) Rack-in Position 23 WWP(A) RACK-IN POSITION OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W33 ○ ---- ---- ---- ○ ----

NO
19 RD00 LCE 22 AP 001 YB 01 WWP(B) Start Command 20 WWP(B) START COMMAND OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NA STLVNESWB W34 ---- ---- ○ ---- ○ ----
PULSE
NC
20 RD00 LCE 22 AP 001 YB 02 WWP(B) Stop Command 19 WWP(B) STOP COMMAND OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NA STLVNESWB W34 ---- ---- ○ ---- ○ ----
PULSE

21 RD00 LCE 22 AP 001 XG 01 WWP(B) Running Indication 14 WWP(B) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W34 ○ P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

22 RD00 LCE 22 AP 001 XG 02 WWP(B) Trip Indication 11 WWP(B) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W34 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

23 RD00 LCE 22 AP 001 XG 03 WWP(B) Remote Mode Selected 27 WWP(B) REMOTE MODE SELECTED LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W34 ○ ---- ○ ---- ○ ----

24 RD00 LCE 22 AP 001 XG 04 WWP(B) Rack-in Position 23 WWP(B) RACK-IN POSITION OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W34 ○ ---- ---- ---- ○ ----

NO
25 RD00 MAV 90 AP 001 YB 01 Clean and Dirty Lube Oil Transfer Pump Start Command 30 CLN&DRT OIL TRANS PMP STRT CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NA STLVNESWB W37 ---- ---- ○ ---- ○ ----
PULSE
NC
26 RD00 MAV 90 AP 001 YB 02 Clean and Dirty Lube Oil Transfer Pump Stop Command 29 CLN&DRT OIL TRANS PMP STP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NA STLVNESWB W37 ---- ---- ○ ---- ○ ----
PULSE

27 RD00 MAV 90 AP 001 XG 01 Clean and Dirty Lube Oil Transfer Pump Running Indication 30 CLN&DRT OIL TRANS PUMP RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W37 ○ ---- ---- ---- ○ ----

28 RD00 MAV 90 AP 001 XG 02 Clean and Dirty Lube Oil Transfer Pump Trip Indication 30 CLN&DRT OIL TRANSFER PUMP TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W37 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

29 RD00 MAV 90 AP 001 XG 03 Clean and Dirty Lube Oil Transfer Pump Remote Mode Selected 32 CLN&DRT OIL TRANSFER PUMP REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W37 ○ ---- ---- ---- ○ ----

30 RD00 MAV 90 AP 001 XG 04 Clean and Dirty Lube Oil Transfer Pump Rack-in Position 32 CLN&DRT OIL TRANSFER PMP RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W37 ○ ---- ---- ---- ○ ----

NO
31 RD00 GMA 10 AP 001 YB 01 Scrubber Area Sump Pit Sump Pump (A) Start Command 32 SCRUB PIT SUMP PUMP (A) STRT CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NA STLVESWB W39 ---- ---- ○ ---- ○ ---- Rev.4;Description updated 4
PULSE
NC
32 RD00 GMA 10 AP 001 YB 02 Scrubber Area Sump Pit Sump Pump (A) Stop Command 32 SCRUB PIT SUMP PUMP (A) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NA STLVESWB W39 ---- ---- ○ ---- ○ ---- Rev.4;Description updated 4
PULSE

33 RD00 GMA 10 AP 001 XG 01 Scrubber Area Sump Pit Sump Pump (A) Running Indication 31 SCRUB PIT SUMP PUMP (A) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) W39 ○ ---- ---- ---- ○ ---- Rev.4;Description updated 4

34 RD00 GMA 10 AP 001 XG 02 Scrubber Area Sump Pit Sump Pump (A) Trip Indication 28 SCRUB PIT SUMP PUMP (A) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) W39 ---- P1 ---- ---- ○ ---- Rev.4;Description updated 4

35 RD00 GMA 10 AP 001 XG 03 Scrubber Area Sump Pit Sump Pump (A) Remote Mode Selected 30 SCRUB PIT SUMP PUMP (A) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) W39 ○ ---- ---- ---- ○ ---- Rev.4;Description updated 4

36 RD00 GMA 10 AP 001 XG 04 ST SPARE FEEDER (52HD-0) CB CLOSE COMMAND 31 SCRUB PIT SUMP PUMP (A) RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) W39 ○ ---- ---- ---- ○ ---- Rev.4;Description updated 4

NO
37 RD00 GMA 10 AP 002 YB 01 Scrubber Area Sump Pit Sump Pump (B) Start Command 32 SCRUB PIT SUMP PUMP (B) STRT CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NA STLVESWB W40 ---- ---- ○ ---- ○ ---- Rev.4;Description updated 4
PULSE
NC
38 RD00 GMA 10 AP 002 YB 02 Scrubber Area Sump Pit Sump Pump (B) Stop Command 32 SCRUB PIT SUMP PUMP (B) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NA STLVESWB W40 ---- ---- ○ ---- ○ ---- Rev.4;Description updated 4
PULSE

39 RD00 GMA 10 AP 002 XG 01 Scrubber Area Sump Pit Sump Pump (B) Running Indication 31 SCRUB PIT SUMP PUMP (B) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) W40 ○ ---- ---- ---- ○ ---- Rev.4;Description updated 4

40 RD00 GMA 10 AP 002 XG 02 Scrubber Area Sump Pit Sump Pump (B) Trip Indication 28 SCRUB PIT SUMP PUMP (B) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) W40 ---- P1 ---- ---- ○ ---- Rev.4;Description updated 4

41 RD00 GMA 10 AP 002 XG 03 Scrubber Area Sump Pit Sump Pump (B) Remote Mode Selected 30 SCRUB PIT SUMP PUMP (B) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) W40 ○ ---- ---- ---- ○ ---- Rev.4;Description updated 4

42 RD00 GMA 10 AP 002 XG 04 Scrubber Area Sump Pit Sump Pump (B) Rack-in Position 31 SCRUB PIT SUMP PUMP (B) RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) W40 ○ ---- ---- ---- ○ ---- Rev.4;Description updated 4

NO
43 RD00 QCH 41 AP 001 YB 01 NaOH Dosing Pump (A) Start Command 30 NaOH Dosing Pump (A) START CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W41 ---- ---- ○ ---- ○ ----
PULSE
NC
44 RD00 QCH 41 AP 001 YB 02 NaOH Dosing Pump (A) Stop Command 29 NaOH Dosing Pump (A) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W41 ---- ---- ○ ---- ○ ----
PULSE

45 RD00 QCH 41 AP 001 XG 01 NaOH Dosing Pump (A) Running Indication 28 NaOH Dosing Pump (A) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W41 ○ P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

46 RD00 QCH 41 AP 001 XG 02 NaOH Dosing Pump (A) Trip Indication 25 NaOH Dosing Pump (A) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W41 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

47 RD00 QCH 41 AP 001 XG 03 NaOH Dosing Pump (A) Remote Mode Selected 27 NaOH Dosing Pump (A) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W41 ○ ---- ○ ---- ○ ----

48 RD00 QCH 41 AP 001 XG 04 NaOH Dosing Pump (A) Rack-in Position 32 NaOH Dosing Pump (A) Rack-in POS OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W41 ○ ---- ---- ---- ○ ----

NO
49 RD00 QCH 42 AP 001 YB 01 NaOH Dosing Pump (B) Start Command 30 NaOH Dosing Pump (B) START CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W42 ---- ---- ○ ---- ○ ----
PULSE
NC
50 RD00 QCH 42 AP 001 YB 02 NaOH Dosing Pump (B) Stop Command 29 NaOH Dosing Pump (B) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W42 ---- ---- ○ ---- ○ ----
PULSE

51 RD00 QCH 42 AP 001 XG 01 NaOH Dosing Pump (B) Running Indication 28 NaOH Dosing Pump (B) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W42 ○ P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

52 RD00 QCH 42 AP 001 XG 02 NaOH Dosing Pump (B) Trip Indication 25 NaOH Dosing Pump (B) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W42 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a
2.DCS IO LIST FOR HARD WIRE
2-2.POWER PLANT FOR COMMON AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
53 RD00 QCH 42 AP 001 XG 03 NaOH Dosing Pump (B) Remote Mode Selected 27 NaOH Dosing Pump (B) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W42 ○ ---- ○ ---- ○ ----

54 RD00 QCH 42 AP 001 XG 04 NaOH Dosing Pump (B) Rack-in Position 32 NaOH Dosing Pump (B) Rack-in POS OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W42 ○ ---- ---- ---- ○ ----

NO
55 RD00 QCH 43 AP 001 YB 01 NaOH Dosing Pump (C) Start Command 30 NaOH Dosing Pump (C) START CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W43 ---- ---- ○ ---- ○ ----
PULSE
NC
56 RD00 QCH 43 AP 001 YB 02 NaOH Dosing Pump (C) Stop Command 29 NaOH Dosing Pump (C) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W43 ---- ---- ○ ---- ○ ----
PULSE

57 RD00 QCH 43 AP 001 XG 01 NaOH Dosing Pump (C) Running Indication 28 NaOH Dosing Pump (C) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W43 ○ P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

58 RD00 QCH 43 AP 001 XG 02 NaOH Dosing Pump (C) Trip Indication 25 NaOH Dosing Pump (C) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W43 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

59 RD00 QCH 43 AP 001 XG 03 NaOH Dosing Pump (C) Remote Mode Selected 27 NaOH Dosing Pump (C) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W43 ○ ---- ○ ---- ○ ----

60 RD00 QCH 43 AP 001 XG 04 NaOH Dosing Pump (C) Rack-in Position 32 NaOH Dosing Pump (C) Rack-in POS OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W43 ○ ---- ---- ---- ○ ----

NO
61 RD00 QCH 53 FH 002 YB 01 NaOH Dosing Stop Valve Open Command 31 NaOH Dosing STOP Valve OPEN CMD CLOSE/OPEN ---- DOW DC110 20W ---- RD00DCS U0-ARS F W44A ---- ---- ○ ---- ○ ----
LATCH

62 RD00 QCH 53 CG 081 XG 01 NaOH Dosing Stop Valve Open 27 NaOH Dosing STOP Valve OPEN OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS RD00DCS W44A ○ ---- ○ ---- ○ ----

63 RD00 QCH 53 CG 082 XG 02 NaOH Dosing Stop Valve Close 28 NaOH Dosing STOP Valve CLOSE OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS RD00DCS W44A ○ ---- ○ ---- ○ ----

90 RD00 QCH 30 BB 001 XG 01 NaOH Dilution Completed 23 NaOH Dilution Completed OFF/ON ---- DI ---- ---- NO ---- NAOHLCP U0-ARS RD00DCS W60 ○ ---- ○ ---- ○ ----

128 RD00 QCH 30 BB 001 XG 02 Chemical dosing system LCP REMOTE 31 CHEMICAL DOSING LCP REMOTE MODE LOCAL/REMOTE ---- DI ---- ---- NO ---- NAOHLCP U0-ARS RD00DCS W60 ---- P2 ---- ---- ○ ---- Rev.4;This signal is added 4

129 RD00 QCH 30 BB 001 XG 03 Chemical dosing system LCP Alarm 25 CHEMICAL DOSING LCP ALARM OFF/ON ---- DI ---- ---- NO ---- NAOHLCP U0-ARS RD00DCS W60 ---- P1 ---- ---- ○ ---- Rev.4;This signal is added 4

91 RD00 PGB 11 CF 501 XG 01 Emergency Shower and Eye Wash Active 31 Emgc Shower and Eye Wash Active OFF/ON ---- DI ---- ---- NO ---- NAOHLCP U0-ARS RD00DCS ---- ○ ---- ---- ---- ○ ---- Rev.4;From location is corrected 4

92 RD00 QCH 30 AA 001 XG 01 NaOH Dilution Water Stop Valve Open 32 NaOH Dilution Water Stop Vlv Opn OFF/OPEN ---- DI ---- ---- NO ---- NAOHLCP U0-ARS RD00DCS W60 ○ ---- ---- ---- ○ ----

93 RD00 QCH 30 AA 001 XG 02 NaOH Dilution Water Stop Valve Close 32 NaOH Dilution Water Stop Vlv Cls OFF/CLOSE ---- DI ---- ---- NC ---- NAOHLCP U0-ARS RD00DCS W60 ○ ---- ---- ---- ○ ----

94 RD00 QCH 23 AA 001 XG 01 NaOH Transfer Stop Valve Open 29 NaOH Transfer Stop Valve Open OFF/OPEN ---- DI ---- ---- NO ---- NAOHLCP U0-ARS RD00DCS W60 ○ ---- ---- ---- ○ ----

95 RD00 QCH 23 AA 001 XG 02 NaOH Transfer Stop Valve Close 30 NaOH Transfer Stop Valve Close OFF/CLOSE ---- DI ---- ---- NC ---- NAOHLCP U0-ARS RD00DCS W60 ○ ---- ---- ---- ○ ----

NO
64 RD00 PBN 21 AP 001 YB 01 Bioside-1 Dosing Pump (A) Start Command 32 Bioside1 Dosing Pmp (A) STRT CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W45 ---- ---- ○ ---- ○ ----
PULSE
NC
65 RD00 PBN 21 AP 001 YB 02 Bioside-1 Dosing Pump (A) Stop Command 32 Bioside1 Dosing Pmp (A) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W45 ---- ---- ○ ---- ○ ----
PULSE

66 RD00 PBN 21 AP 001 XG 01 Bioside-1 Dosing Pump (A) Running Indication 32 Bioside1 Dosing Pump (A) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45 ---- ---- ○ ---- ○ ----

67 RD00 PBN 21 AP 001 XG 02 Bioside-1 Dosing Pump (A) Trip Indication 29 Bioside1 Dosing Pump (A) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W45 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

68 RD00 PBN 21 AP 001 XG 03 Bioside-1 Dosing Pump (A) Remote Mode Selected 31 Bioside1 DOSING Pump (A) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45 ○ ---- ---- ---- ○ ----

69 RD00 PBN 21 AP 001 XG 04 Bioside-1 Dosing Pump (A) Rack-in Position 32 Bioside1 Dosing Pump (A) Rack-in OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45A ○ ---- ---- ---- ○ ----

NO
70 RD00 PBN 22 AP 001 YB 01 Bioside-1 Dosing Pump (B) Start Command 32 Bioside1 Dosing Pmp (B) STRT CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W45A ---- ---- ○ ---- ○ ----
PULSE
NC
71 RD00 PBN 22 AP 001 YB 02 Bioside-1 Dosing Pump (B) Stop Command 32 Bioside1 Dosing Pmp (B) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W45A ---- ---- ○ ---- ○ ----
PULSE

72 RD00 PBN 22 AP 001 XG 01 Bioside-1 Dosing Pump (B) Running Indication 32 Bioside1 Dosing Pump (B) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45A ---- ---- ○ ---- ○ ----

73 RD00 PBN 22 AP 001 XG 02 Bioside-1 Dosing Pump (B) Trip Indication 29 Bioside1 Dosing Pump (B) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W45A ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

74 RD00 PBN 22 AP 001 XG 03 Bioside-1 Dosing Pump (B) Remote Mode Selected 31 Bioside1 DOSING Pump (B) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45A ○ ---- ---- ---- ○ ----

75 RD00 PBN 22 AP 001 XG 04 Bioside-1 Dosing Pump (B) Rack-in Position 32 Bioside1 Dosing Pump (B) Rack-in OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45A ○ ---- ---- ---- ○ ----

NO
100 RD00 PBN 25 AP 001 YB 01 Bioside-2 Dosing Pump (A) Start Command 32 Bioside2 Dosing Pmp (A) STRT CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W45B ---- ---- ○ ---- ○ ----
PULSE
NC
101 RD00 PBN 25 AP 001 YB 02 Bioside-2 Dosing Pump (A) Stop Command 32 Bioside2 Dosing Pmp (A) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W45B ---- ---- ○ ---- ○ ----
PULSE

102 RD00 PBN 25 AP 001 XG 01 Bioside-2 Dosing Pump (A) Running Indication 32 Bioside2 Dosing Pump (A) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45B ---- ---- ○ ---- ○ ----

103 RD00 PBN 25 AP 001 XG 02 Bioside-2 Dosing Pump (A) Trip Indication 29 Bioside2 Dosing Pump (A) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W45B ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

104 RD00 PBN 25 AP 001 XG 03 Bioside-2 Dosing Pump (A) Remote Mode Selected 31 Bioside2 DOSING Pump (A) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45B ○ ---- ---- ---- ○ ----

105 RD00 PBN 25 AP 001 XG 04 Bioside-2 Dosing Pump (A) Rack-in Position 32 Bioside2 Dosing Pump (A) Rack-in OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45B ○ ---- ---- ---- ○ ----

NO
106 RD00 PBN 26 AP 001 YB 01 Bioside-2 Dosing Pump (B) Start 32 Bioside2 Dosing Pmp (B) STRT CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W45C ---- ---- ○ ---- ○ ----
PULSE
NC
107 RD00 PBN 26 AP 001 YB 02 Bioside-2 Dosing Pump (B) Stop 32 Bioside2 Dosing Pmp (B) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W45C ---- ---- ○ ---- ○ ----
PULSE

108 RD00 PBN 26 AP 001 XG 01 Bioside-2 Dosing Pump (B) Running Indication 32 Bioside2 Dosing Pump (B) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45C ---- ---- ○ ---- ○ ----

109 RD00 PBN 26 AP 001 XG 02 Bioside-2 Dosing Pump (B) Trip Indication 29 Bioside2 Dosing Pump (B) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W45C ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

110 RD00 PBN 26 AP 001 XG 03 Bioside-2 Dosing Pump (B) Remote Mode Selected 31 Bioside2 DOSING Pump (B) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45C ○ ---- ---- ---- ○ ----

111 RD00 PBN 26 AP 001 XG 04 Bioside-2 Dosing Pump (B) Rack-in Position 32 Bioside2 Dosing Pump (B) Rack-in OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W45C ○ ---- ---- ---- ○ ----

76 RD00 QCH 30 AM 001 XG 01 NaOH Tank Agitator Run 22 NaOH Tank Agitator Run STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00DCS W60 ○ ---- ---- ---- ○ ---- Rev.4 Location is updated 4

77 RD00 QCH 30 AM 001 XG 02 NaOH Tank Agitator Fault 24 NaOH Tank Agitator Fault OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00DCS W60 ---- P1 ---- ---- ○ ---- Rev.4 Location is updated 4

NO
78 RD00 QCH 21 AP 001 YB 01 NaOH Transfer Pump (A) Start Command 32 NaOH TRANSFER PUMP (A) START CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W61 ---- ---- ○ ---- ○ ----
PULSE
NC
79 RD00 QCH 21 AP 001 YB 02 NaOH Transfer Pump (A) Stop Command 31 NaOH TRANSFER PUMP (A) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W61 ---- ---- ○ ---- ○ ----
PULSE

80 RD00 QCH 21 AP 001 XG 01 NaOH Transfer Pump (A) Running Indication 30 NaOH TRANSFER PUMP (A) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W61 ○ P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

81 RD00 QCH 21 AP 001 XG 02 NaOH Transfer Pump (A) Trip Indication 27 NaOH TRANSFER PUMP (A) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W61 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

82 RD00 QCH 21 AP 001 XG 03 NaOH Transfer Pump (A) Remote Mode Selected 29 NaOH TRANSFER PUMP (A) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W61 ○ ---- ○ ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-2.POWER PLANT FOR COMMON AREA

APPLIED ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
83 RD00 QCH 21 AP 001 XG 04 NaOH Transfer Pump (A) Rack-in Position 30 NaOH TRANSFER PUMP (A) RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W61 ○ ---- ---- ---- ○ ----

NO
84 RD00 QCH 22 AP 001 YB 01 NaOH Transfer Pump (B) Start Command 32 NaOH TRANSFER PUMP (B) START CMD OFF/START ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W61 ---- ---- ○ ---- ○ ----
PULSE
NC
85 RD00 QCH 22 AP 001 YB 02 NaOH Transfer Pump (B) Stop Command 31 NaOH TRANSFER PUMP (B) STOP CMD OFF/STOP ---- DOL DC24 2W ---- RD00MCCRIO(LV) NAOHLCP STLVNESWB W61 ---- ---- ○ ---- ○ ----
PULSE

86 RD00 QCH 22 AP 001 XG 01 NaOH Transfer Pump (B) Running Indication 30 NaOH TRANSFER PUMP (B) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W61 ○ P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

87 RD00 QCH 22 AP 001 XG 02 NaOH Transfer Pump (B) Trip Indication 27 NaOH TRANSFER PUMP (B) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W61 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

88 RD00 QCH 22 AP 001 XG 03 NaOH Transfer Pump (B) Remote Mode Selected 29 NaOH TRANSFER PUMP (B) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W61 ○ ---- ○ ---- ○ ----

89 RD00 QCH 22 AP 001 XG 04 NaOH Transfer Pump (B) Rack-in Position 30 NaOH TRANSFER PUMP (B) RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W61 ○ ---- ---- ---- ○ ----

96 RD00 QCH 11 AP 001 XG 01 NaOH Filling Pump Running Indication 31 NaOH FILLING TRANS PUMP RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W62 ○ P2 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

97 RD00 QCH 11 AP 001 XG 02 NaOH Filling Pump Trip Indication 31 NaOH FILLING TRANSFER PUMP TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) W62 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

98 RD00 QCH 11 AP 001 XG 03 NaOH Filling Pump Remote Mode Selected 32 NaOH FILLING TRANSFER PMP REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W62 ○ ---- ---- ---- ○ ----

99 RD00 QCH 11 AP 001 XG 04 NaOH Filling Pump Rack-in Position 31 NaOH FILLING TRANS PUMP RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) W62 ○ ---- ---- ---- ○ ----

114 RD00 QCH 11 AH 001 XG 01 Condensate NaOH Tank Heater Running Indication 24 NaOH TANK HEATER RUNNING STOP/RUN ---- DI ---- ---- NO ---- NAOHLCP U0-ARS RD00DCS W60 ○ P2 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

115 RD00 QCH 11 AH 001 XG 02 Condensate NaOH Tank Heater Stop Indication 21 NaOH TANK HEATER STOP STOP/RUN ---- DI ---- ---- NC ---- NAOHLCP U0-ARS RD00DCS W60 ○ P1 ○ ---- ○ ---- Rev.4 signal tyoe is changed 4

116 RD00 QCH 11 AH 001 XG 03 Condensate NaOH Tank Heater Trip Indication 21 NaOH TANK HEATER TRIP OFF/TRIP ---- DI ---- ---- NC ---- NAOHLCP U0-ARS RD00DCS W60 ---- ○ ○ ---- ○ ---- Rev.4 Deletec 4

117 RD00 CKA 10 GH 031 XG 02 Common Server Cabinet GPS Alarm NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

118 RD00 CKA 10 GH 031 XG 01 Common Server Cabinet Alarm NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

119 RD00 CKA 10 GH 032 XG 01 Common Station Cabinet Alarm NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

120 RD00 CKA 10 GH 033 XG 01 Common Network Cabinet Alarm NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

121 RD00 CKA 10 GH 011 XG 02 Common System Cabinet PSU Alarm NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

122 RD00 CKA 10 GH 011 XG 01 Common System Cabinet Fan or Thermostat Alarm NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

123 RD00 CJU 01 GH 012 XG 02 Common MCC LV RIO Cabinet PSU Alarm NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

124 RD00 CJU 01 GH 012 XG 01 Common MCC LV RIO Cabinet Fan or Thermostat Alarm NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

125 RD00 CJU 01 GH 011 XG 02 Common MCC MV RIO Cabinet PSU or FWL Alarm NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

126 RD00 CJU 01 GH 011 XG 01 Common MCC MV RIO Cabinet Fan or Thermostat Alarm NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA *DCS ---- ---- ○ ---- ---- ○ ----

7.5 6.0
127 RD00 HAN 10 CQ 001 XQ 01 PH ANALYSER FOR REINJECTION LINE 32 PH ANALYSER FOR REINJECTION LINE 0-14 pH AII ---- ---- ---- 1% F U0-ARS DCSRDB R81 ○ H/L ---- ---- ○ ----
(P2) (P2)
2.DCS IO LIST FOR HARD WIRE
2-2.POWER PLANT FOR COMMON AREA

APPLIED ALARM ILD or IBD


NC/NO RD00DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
3078 RD00 BBA 10 XQ 01 ST COMMON STATION MV SWITCHGEAR BUS VOLTAGE 24 COMMON MVSWG BUS VOLTAGE 0-6300 V AIX ---- ---- ---- ---- STMVSWG NA RD00MCCRIO(MV) REK 〇 ---- ---- ---- ○ ----

3079 RD00 BBA 10 XG 01 ST COMMON STATION MV SWITCHGEAR SYNCHRONIZE INDICATION 24 COMMON MVSWG SYNCHRONIZE OFF/ON ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ---- ---- ---- ○ ○

3080 RD00 BBA 10 XG 02 ST DS/CB DUMMY FROM UNIT-1 MV SWITCHGEAR CLOSED INDICATION 30 DS/CB DUMMY FROM U1MVSWG CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3081 RD00 BBA 10 XG 03 ST DS/CB DUMMY FROM UNIT-2 MV SWITCHGEAR CLOSED INDICATION 30 DS/CB DUMMY FROM U2MVSWG CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ---- ---- ---- ○ ○
NO
3082 RD00 BBA 10 YB 11 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) CB OPEN COMMAND 31 OG TO STST (52HA-0) CB OPEN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(MV) NA STMVSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3083 RD00 BBA 10 YB 12 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) CB CLOSE COMMAND 32 OG TO STST (52HA-0) CB CLOSE CMD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(MV) NA STMVSWG REK ---- ---- ○ ---- ○ ----
PULSE

3084 RD00 BBA 10 XG 11 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) TRIP INDICATION 24 OG TO STST (52HA-0) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ○ ---- ---- ----

(P1)

3085 RD00 BBA 10 XG 12 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) TRIP CIRCUIT HEALTHY 32 OG TO STST (52HA-0) TRP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ---- ---- ○ ----
(P1)

3086 RD00 BBA 10 XG 13 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) CB CLOSED INDICATION 28 OG TO STST (52HA-0) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3087 RD00 BBA 10 XG 14 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) ES CLOSED INDICATION 28 OG TO STST (52HA-0) ES CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3088 RD00 BBA 10 XG 15 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) REMOTE MODE SELECTED 26 OG TO STST (52HA-0) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

NO
3089 RD00 BBA 10 YB 21 ST OUTGOING TO PAD RD-B RMU (52HB-0) CB OPEN COMMAND 32 OG PAD-B RMU (52HB-0) CB OPN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(MV) NA STMVSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3090 RD00 BBA 10 YB 22 ST OUTGOING TO PAD RD-B RMU (52HB-0) CB CLOSE COMMAND 32 OG PAD-B RMU (52HB-0) CB CLS CMD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(MV) NA STMVSWG REK ---- ---- ○ ---- ○ ----
PULSE

3091 RD00 BBA 10 XG 21 ST OUTGOING TO PAD RD-B RMU (52HB-0) CB TRIP INDICATION 32 OG TO PAD-B RMU (52HB-0) CB TRIP OFF/TRIP ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ○ ---- ---- ----

(P1)
3092 RD00 BBA 10 XG 22 ST OUTGOING TO PAD RD-B RMU (52HB-0) TRIP CIRCUIT HEALTHY 30 OG PAD-B RMU (52HB-0) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ○ ---- ---- ----

(P1)
3093 RD00 BBA 10 XG 23 ST OUTGOING TO PAD RD-B RMU (52HB-0) CB CLOSE INDICATION 31 OG TO PAD-B RMU (52HB-0) CB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3094 RD00 BBA 10 XG 24 ST OUTGOING TO PAD RD-B RMU (52HB-0) ES CLOSE INDICATION 32 OG TO PAD-B RMU (52HB-0) ES CLOS OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3095 RD00 BBA 10 XG 25 ST OUTGOING TO PAD RD-B RMU (52HB-0) REMOTE MODE SELECTED 31 OG TO PAD-B RMU (52HB-0) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

NO
3096 RD00 BBA 10 YB 31 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) CB OPEN COMMAND 31 OG SSMVSWG (52HC-0) CB OPEN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(MV) NA STMVSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3097 RD00 BBA 10 YB 32 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) CB CLOSE COMMAND 32 OG SSMVSWG (52HC-0) CB CLOSE CMD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(MV) NA STMVSWG REK ---- ---- ○ ---- ○ ----
PULSE

3098 RD00 BBA 10 XG 31 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) CB TRIP INDICATION 30 OG TO SSMVSWG (52HC-0) CB TRIP OFF/TRIP ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ---- ---- ○ ----
(P1)

3099 RD00 BBA 10 XG 32 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) TRIP CIRCUIT HEALTHY 32 OG SSMVSWG (52HC-0) TRP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ---- ---- ○ ----
(P1)
3100 RD00 BBA 10 XG 33 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) CB CLOSE INDICATION 31 OG TO SSMVSWG (52HC-0) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3101 RD00 BBA 10 XG 34 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) ES CLOSE INDICATION 32 ONG TO SSMVSWG (52HC-0) ES CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3102 RD00 BBA 10 XG 35 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) REMOTE MODE SELECTED 29 OG TO SSMVSWG (52HC-0) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

NO
3103 RD00 BBA 10 YB 41 ST OUTGOING TO ACCOMODATION BLOCK CB OPEN COMMAND 30 OG TO ACCOMODATION CB OPEN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(MV) NA STMVSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3104 RD00 BBA 10 YB 42 ST OUTGOING TO ACCOMODATION BLOCK CB CLOSE COMMAND 31 OG TO ACCOMODATION CB CLOSE CMD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(MV) NA STMVSWG REK ---- ---- ○ ---- ○ ----
PULSE

3105 RD00 BBA 10 XG 41 ST OUTGOING TO ACCOMODATION BLOCK CB TRIP INDICATION 32 OG TO ACCOMODATION BLOCK CB TRIP OFF/TRIP ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ○ ---- ---- ----

(P1)

3106 RD00 BBA 10 XG 42 ST OUTGOING TO ACCOMODATION BLOCK TRIP CIRCUIT HEALTHY 32 OG TO ACCOMODATION BLOCK CB TRIP HEALTHY/FAULT ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ○ ---- ---- ----

(P1)
3107 RD00 BBA 10 XG 43 ST OUTGOING TO ACCOMODATION BLOCK CB CLOSED INDICATION 31 OG TO ACCOMODATION BLOCK CB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3108 RD00 BBA 10 XG 44 ST OUTGOING TO ACCOMODATION BLOCK ES CLOSED INDICATION 31 OG TO ACCOMODATION BLOCK ES CLS OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3109 RD00 BBA 10 XG 45 ST OUTGOING TO ACCOMODATION BLOCK CB REMOTE MODE SELECTED 28 OG TO ACCOMODATION CB REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

NO
3110 RD00 BBA 10 YB 43 ST SPARE FEEDER (52HD-0) CB OPEN COMMAND 32 SPARE FEEDER (52HD-0) CB OPN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(MV) NA STMVSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3111 RD00 BBA 10 YB 44 ST SPARE FEEDER (52HD-0) CB CLOSE COMMAND 32 SPARE FEEDER (52HD-0) CB CLS CMD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(MV) NA STMVSWG REK ---- ---- ○ ---- ○ ----
PULSE

3112 RD00 BBA 10 XG 46 ST SPARE FEEDER (52HD-0) CB TRIP INDICATION 29 SPARE FEEDER (52HD-0) CB TRIP OFF/TRIP ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ○ ---- ---- ----

(P1)
3113 RD00 BBA 10 XG 47 ST SPARE FEEDER (52HD-0) TRIP CIRCUIT HEALTHY 30 SPARE FEEDER (52HD-0) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ---- ○ ---- ---- ----

(P1)
3114 RD00 BBA 10 XG 48 ST SPARE FEEDER (52HD-0) CB CLOSED INDICATION 30 SPARE FEEDER (52HD-0) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3115 RD00 BBA 10 XG 49 ST SPARE FEEDER (52HD-0) ES CLOSED INDICATION 30 SPARE FEEDER (52HD-0) ES CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3116 RD00 BBA 10 XG 50 ST SPARE FEEDER (52HD-0) REMOTE MODE SELECTED 28 SPARE FEEDER (52HD-0) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

NO
3117 RD00 BBA 20 YB 01 SS RMU MV OUTGOING FROM SGS SERVICE TRANSFORMER (52H-4) OPEN COMMAND 32 RMUMV OG FRM SST (52H-4) OPN CMD OFF/OPEN ---- DOL DC24 2W ---- RD00MCCRIO(MV) NA RMUSGSSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3118 RD00 BBA 20 YB 02 SS RMU MV OUTGOING FROM SGS SERVICE TRANSFORMER (52H-4) CLOSE COMMAND 32 RMUMV OG FRM SST (52H-4) CLS CMD OFF/CLOSE ---- DOL DC24 2W ---- RD00MCCRIO(MV) NA RMUSGSSWG REK ---- ---- ○ ---- ○ ----
PULSE

3119 RD00 BBA 20 XG 01 SS RMU MV OUTGOING FROM SGS SERVICE TRANSFORMER (52H-4) LOSS OF POWER CONTROL SOURCE 32 RMUMV OG FRM SST (52H-4) PW LOSS NORMAL/ALARM ---- DI ---- ---- NC ---- RMUSGSSWG NA RD00MCCRIO(MV) REK ---- ---- ---- ○ ----
(P1)
3120 RD00 BBA 20 XG 02 SS RMU MV UTGOING FROM SGS SERVICE TRANSFORMER (52H-4) REMOTE MODE SELECTED 32 RMUMV OG FROM SST (52H-4) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- RMUSGSSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3121 RD00 BBA 20 XG 03 SS RMU MV LBS CLOSE INDICATION 15 RMUMV LBS CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- RMUSGSSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3122 RD00 BBA 20 XG 04 SS RMU MV LBS OPEN INDICATION 14 RMUMV LBS OPEN OPEN/CLOSE ---- DI ---- ---- NO ---- RMUSGSSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3123 RD00 BBA 20 XG 05 SS RMU MV LBS EARTH ON INDICATION 18 RMUMV LBS EARTH ON OFF/ON ---- DI ---- ---- NO ---- RMUSGSSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ---- ○ ----

3124 RD00 BFA 10 XG 01 ST COMMON STATION LV SWITCHGEAR SYNCHRONIZE INDICATION 26 COMMON STLVSWG SYNCHRONIZE OFF/ON ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ○ ○
(P2)
NO
3125 RD00 BFA 10 YB 11 ST INCOMING LV COMMON STATION LV SWITCHGEAR (52LA-0) CB OPEN COMMAND 29 IC LVSWG (52LA-0) CB OPEN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3126 RD00 BFA 10 YB 12 ST INCOMING LV COMMON STATION LV SWITCHGEAR (52LA-0) CB CLOSE COMMAND 30 IC LVSWG (52LA-0) CB CLOSE CMD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVSWG REK ---- ---- ○ ---- ○ ----
PULSE

3127 RD00 BFA 10 XG 11 ST INCOMING LV COMMON STATION LV SWITCHGEAR (52LA-0) TRIP INDICATION 22 IC LVSWG (52LA-0) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
2.DCS IO LIST FOR HARD WIRE
2-2.POWER PLANT FOR COMMON AREA

APPLIED ALARM ILD or IBD


NC/NO RD00DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
3128 RD00 BFA 10 XG 12 ST INCOMING LV COMMON STATION LV SWITCHGEAR (52LA-0) TRIP CIRCUIT HEALTHY 31 IC LVSWG (52LA-0) TRIP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)

3129 RD00 BFA 10 XG 13 ST INCOMING LV COMMON STATION LV SWITCHGEAR (52LA-0) CB CLOSE INDICATION 26 IC LVSWG (52LA-0) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3130 RD00 BFA 10 XG 14 ST INCOMING LV COMMON STATION LV SWITCHGEAR (52LA-0) REMOTE MODE SELECTED 24 IC LVSWG (52LA-0) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

NO
3131 RD00 BFA 10 YB 21 ST OUTGOING TO COMMON STATION NON-ESSENTIAL BOARD (52LD-0) CB OPEN COMMAND 30 OG TO NEB (52LD-0) CB OPEN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3132 RD00 BFA 10 YB 22 ST OUTGOING TO COMMON STATION NON-ESSENTIAL BOARD (52LD-0) CB CLOSE COMMAND 30 OG TO NEB (52LD-0) CB CLOSE MD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVSWG REK ---- ---- ○ ---- ○ ----
PULSE

3133 RD00 BFA 10 XG 21 ST OUTGOING TO COMMON STATION NON-ESSENTIAL BOARD (52LD-0) TRIP INDICATION 23 OG TO NEB (52LD-0) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ---- ---- ○ ----
(P1)

3134 RD00 BFA 10 XG 22 ST OUTGOING TO COMMON STATION NON-ESSENTIAL BOARD (52LD-0) TRIP CIRCUIT HEALTHY 32 OG TO NEB (52LD-0) TRIP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ---- ---- ○ ----
(P1)

3135 RD00 BFA 10 XG 23 ST OUTGOING TO COMMON STATION NON-ESSENTIAL BOARD (52LD-0) CB CLOSE INDICATION 27 OG TO NEB (52LD-0) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3136 RD00 BFA 10 XG 24 ST OUTGOING TO COMMON STATION NON-ESSENTIAL BOARD (52LD-0) REMOTE MODE SELECTED 25 OG TO NEB (52LD-0) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3137 RD00 BFA 10 XQ 21 ST OUTGOING TO COMMON STATION NON-ESSENTIAL BOARD (52LD-0) CURRENT 31 OG TO NE BOARD (52LD-0) CURRENT 0-630 A AIX ---- ---- ---- ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

NO
3138 RD00 BFA 10 YB 31 ST OUTGOING TO COMMON STATION ESSENTIAL BOARD (52LB-0) CB OPEN COMMAND 29 OG TO EB (52LB-0) CB OPEN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3139 RD00 BFA 10 YB 32 ST OUTGOING TO COMMON STATION ESSENTIAL BOARD (52LB-0) CB CLOSE COMMAND 30 OG TO EB (52LB-0) CB CLOSE CMD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVSWG REK ---- ---- ○ ---- ○ ----
PULSE

3140 RD00 BFA 10 XG 31 ST OUTGOING TO COMMON STATION ESSENTIAL BOARD (52LB-0)TRIP INDICATION 21 OG TO EB (52LB-0)TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)

3141 RD00 BFA 10 XG 32 ST OUTGOING TO COMMON STATION ESSENTIAL BOARD (52LB-0) TRIP CIRCUIT HEALTHY 31 OG TO EB (52LB-0) TRIP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ---- ---- ○ ----
(P1)
3142 RD00 BFA 10 XG 33 ST OUTGOING TO COMMON STATION ESSENTIAL BOARD (52LB-0) CB CLOSE INDICATION 26 OG TO EB (52LB-0) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3143 RD00 BFA 10 XG 34 ST OUTGOING TO COMMON STATION ESSENTIAL BOARD (52LB-0) REMOTE MODE SELECTED 24 OG TO EB (52LB-0) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3144 RD00 BFA 10 XQ 31 ST OUTGOING TO COMMON STATION ESSENTIAL BOARD (52LB-0) CURRENT 25 OG TO EB (52LB-0) CURRENT 0-630 A AIX ---- ---- ---- ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3145 RD00 BFA 10 XG 41 ST DS/CB DUMMY FROM UNIT-1 LV SWITCHGEAR CLOSED INDICATION 30 DS/CB DUMMY FROM U1LVSWG CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3146 RD00 BFA 10 XG 51 ST DS/CB DUMMY FROM UNIT-2 LV SWITCHGEARCLOSED INDICATION 30 DS/CB DUMMY FROM U2LVSWG CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ○ ○
NO
3147 RD00 BFA 10 YB 33 ST SPARE FEEDER 1 CB OPEN COMMAND 30 SPARE FEEDER 1 CB OPEN COMMAND OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3148 RD00 BFA 10 YB 34 ST SPARE FEEDER 1 CB CLOSE COMMAND 31 SPARE FEEDER 1 CB CLOSE COMMAND OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVSWG REK ---- ---- ○ ---- ○ ----
PULSE

3149 RD00 BFA 10 XG 52 ST SPARE FEEDER 1 TRIP INDICATION 30 SPARE FEEDER 1 TRIP INDICATION OFF/TRIP ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3150 RD00 BFA 10 XG 53 ST SPARE FEEDER 1 TRIP CIRCUIT HEALTHY 28 SPARE FEEDER 1 TRIP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3151 RD00 BFA 10 XG 54 ST SPARE FEEDER 1 CB CLOSE INDICATION 23 SPARE FEEDER 1 CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3152 RD00 BFA 10 XG 55 ST SPARE FEEDER 1 REMOTE MODE SELECTED 21 SPARE FEEDER 1 REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3153 RD00 BFA 10 XQ 32 ST SPARE FEEDER 1 CURRENT 22 SPARE FEEDER 1 CURRENT 0-630 A AIX ---- ---- ---- ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

NO
3154 RD00 BFA 10 YB 35 ST SPARE FEEDER 2 CB OPEN COMMAND 30 SPARE FEEDER 2 CB OPEN COMMAND OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVSWG REK ---- ---- ○ ---- ○ ----
PULSE
NO
3155 RD00 BFA 10 YB 36 ST SPARE FEEDER 2 CB CLOSE COMMAND 31 SPARE FEEDER 2 CB CLOSE COMMAND OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVSWG REK ---- ---- ○ ---- ○ ----
PULSE

3156 RD00 BFA 10 XG 56 ST SPARE FEEDER 2 TRIP INDICATION 30 SPARE FEEDER 2 TRIP INDICATION OFF/TRIP ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3157 RD00 BFA 10 XG 57 ST SPARE FEEDER 2 TRIP CIRCUIT HEALTHY 28 SPARE FEEDER 2 TRIP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3158 RD00 BFA 10 XG 58 ST SPARE FEEDER 2 CB CLOSE INDICATION 23 SPARE FEEDER 2 CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3159 RD00 BFA 10 XG 59 ST SPARE FEEDER 2 REMOTE MODE SELECTED 21 SPARE FEEDER 2 REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3160 RD00 BFA 10 XQ 33 ST SPARE FEEDER 2 CURRENT 22 SPARE FEEDER 2 CURRENT 0-630 A AIX ---- ---- ---- ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3161 RD00 BFB 20 XG 01 ST DS/CB DUMMY FROM COMMON STATION LV SWITCHGEAR CLOSED INDICATION 30 DS/CB DUMMY FROM STLVSWG CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ○ ○

3168 RD00 BFB 20 XG 41 ST WORKSHOP OVERHEAD CRANE MCCB CLOSE INDICATION 32 WORKSHOP OVERHEAD CRANE MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3169 RD00 BFB 20 XG 42 ST WORKSHOP OVERHEAD CRANE MCCB TRIP INDICATION 32 WORKSHOP OVERHEAD CRANE MCCB TRP OPEN/CLOSE ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3174 RD00 BFB 20 XG 71 ST LIGHTING TRANSFORMER RD00LVB-NE MCCB CLOSE INDICATION 24 LT RD00LVB-NE MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3175 RD00 BFB 20 XG 72 ST LIGHTING TRANSFORMER RD00LVB-NE TRIP INDICATION 18 LT RD00LVB-NE TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)

3176 RD00 BFB 20 XQ 71 ST LIGHTING TRANSFORMER STLVNESWB CURRENT 20 LT STLVNESWB CURRENT 0-630 A AIX ---- ---- ---- 1% STLVNESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ○ ----

3177 RD00 BFB 20 XG 73 ST SPARE FEEDER (300kVA) MCCB CLOSE INDICATION 32 SPARE FEEDER (300kVA) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----


3178 RD00 BFB 20 XG 74 ST SPARE FEEDER (300kVA) TRIP INDICATION 26 SPARE FEEDER (300kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ○ ----
(P1)
3179 RD00 BFB 20 XQ 72 ST SPARE FEEDER (300kVA) CURRENT 29 SPARE FEEDER (300kVA) CURRENT 0-630 A AIX ---- ---- ---- 1% STLVNESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

NO
3180 RD00 BFB 20 YB 37 ST SPARE MOTOR STARTER (7.5kW) START COMMAND 32 SPARE MTR STRTR (7.5kW) STRT CMD OFF/START ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ---- ---- ○ ---- ○ ----
PULSE
NC
3181 RD00 BFB 20 YB 38 ST SPARE MOTOR STARTER (7.5kW) STOP COMMAND 32 SPARE MTR STRTR (7.5kW) STOP CMD OFF/STOP ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ---- ---- ○ ---- ○ ----
PULSE

3182 RD00 BFB 20 XG 75 ST SPARE MOTOR STARTER (7.5kW) RUNNING INDICATION 31 SPARE MTR STRTR (7.5kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3183 RD00 BFB 20 XG 76 ST SPARE MOTOR STARTER (7.5kW) SPARE 29 SPARE MTR STRTR (7.5kW) SPARE OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3184 RD00 BFB 20 XG 77 ST SPARE MOTOR STARTER (7.5kW) REMOTE MODE SELECTED 32 SPARE MTR STARTER (7.5kW) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3185 RD00 BFB 20 XG 78 ST SPARE MOTOR STARTER (7.5kW) TRIP INDICATION 32 SPARE MOTOR STARTER (7.5kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3186 RD00 BFB 20 XG 79 ST SPARE MOTOR STARTER (7.5kW) RACK-IN POSITION 31 SPARE MTR STRTR (7.5kW) RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ---- ----

NO
3187 RD00 BFB 20 YB 39 ST SPARE MOTOR STARTER (2.2kW) START COMMAND 32 SPARE MTR STRTR (2.2kW) STRT CMD OFF/START ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ---- ---- ○ ---- ○ ----
PULSE
2.DCS IO LIST FOR HARD WIRE
2-2.POWER PLANT FOR COMMON AREA

APPLIED ALARM ILD or IBD


NC/NO RD00DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
NC
3188 RD00 BFB 20 YB 40 ST SPARE MOTOR STARTER (2.2kW) STOP COMMAND 32 SPARE MTR STRTR (2.2kW) STOP CMD OFF/STOP ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ---- ---- ○ ---- ○ ----
PULSE

3189 RD00 BFB 20 XG 80 ST SPARE MOTOR STARTER (2.2kW) RUNNING INDICATION 31 SPARE MTR STRTR (2.2kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3190 RD00 BFB 20 XG 81 ST SPARE MOTOR STARTER (2.2kW) SPARE 31 SPARE MTR STARTER (2.2kW) SPARE OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3191 RD00 BFB 20 XG 82 ST SPARE MOTOR STARTER (2.2kW) REMOTE MODE SELECTED 32 SPARE MTR STARTER (2.2kW) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3192 RD00 BFB 20 XG 83 ST SPARE MOTOR STARTER (2.2kW) TRIP INDICATION 32 SPARE MOTOR STARTER (2.2kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3193 RD00 BFB 20 XG 84 ST SPARE MOTOR STARTER (2.2kW) RACK-IN POSITION 31 SPARE MTR STRTR (2.2kW) RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ---- ----

NO
3194 RD00 BFB 20 YB 41 ST SPARE MOTOR STARTER (0.25kW) START COMMAND 31 SPR MTR STRTR (0.25kW) STRT CMD OFF/START ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ---- ---- ○ ---- ○ ----
PULSE
NC
3195 RD00 BFB 20 YB 42 ST SPARE MOTOR STARTER (0.25kW) STOP COMMAND 32 SPARE MTR STRTR (0.25kW) STP CMD OFF/STOP ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ---- ---- ○ ---- ○ ----
PULSE

3196 RD00 BFB 20 XG 85 ST SPARE MOTOR STARTER (0.25kW) RUNNING INDICATION 32 SPARE MTR STRTR (0.25kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3197 RD00 BFB 20 XG 86 ST SPARE MOTOR STARTER (0.25kW) SPARE 30 SPARE MTR STRTR (0.25kW) SPARE OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3198 RD00 BFB 20 XG 87 ST SPARE MOTOR STARTER (0.25kW) REMOTE MODE SELECTED 31 SPARE MTR STRTR (0.25kW) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3199 RD00 BFB 20 XG 88 ST SPARE MOTOR STARTER (0.25kW) TRIP INDICATION 29 SPARE MTR STRTR (0.25kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3200 RD00 BFB 20 XG 89 ST SPARE MOTOR STARTER (0.25kW) RACK-IN POSITION 32 SPARE MTR STRTR (0.25kW) RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ---- ----

NO
3201 RD00 BFB 20 YB 43 ST SPARE MOTOR STARTER (0.75kW) START COMMAND 31 SPR MTR STRTR (0.75kW) STRT CMD OFF/START ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ---- ---- ○ ---- ○ ----
PULSE
NC
3202 RD00 BFB 20 YB 44 ST SPARE MOTOR STARTER (0.75kW) STOP COMMAND 32 SPARE MTR STRTR (0.75kW) STP CMD OFF/STOP ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ---- ---- ○ ---- ○ ----
PULSE

3203 RD00 BFB 20 XG 90 ST SPARE MOTOR STARTER (0.75kW) RUNNING INDICATION 32 SPARE MTR STRTR (0.75kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3204 RD00 BFB 20 XG 91 ST SPARE MOTOR STARTER (0.75kW) SPARE 30 SPARE MTR STRTR (0.75kW) SPARE OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3205 RD00 BFB 20 XG 92 ST SPARE MOTOR STARTER (0.75kW) REMOTE MODE SELECTED 31 SPARE MTR STRTR (0.75kW) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3206 RD00 BFB 20 XG 93 ST SPARE MOTOR STARTER (0.75kW) TRIP INDICATION 29 SPARE MTR STRTR (0.75kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)

3207 RD00 BFB 20 XG 94 ST SPARE MOTOR STARTER (0.75kW) RACK-IN POSITION 32 SPARE MTR STRTR (0.75kW) RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ---- ----

3426 RD00 BFB 20 XG 95 ST SPARE FEEDER (20kVA) MCCB CLOSE INDICATION 31 SPARE FEEDER (20kVA) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3427 RD00 BFB 20 XG 96 ST SPARE FEEDER (20kVA) TRIP INDICATION 25 SPARE FEEDER (20kVA) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3208 RD00 BFB 10 XG 01 ST DS/ACB DUMMY FROM COMMON STATION LV SWITCHGEAR CLOSED INDICATION 31 DS/ACB DUMMY FROM STLVSWG CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ○

3209 RD00 BFB 10 XG 02 ST COMMON STATION ESSENTIAL BOARD SYNCHRONIZE INDICATION 16 STEB SYNCHRONIZE OFF/ON ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ○ ○
(P2)
NO
3210 RD00 BFB 10 YB 11 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) OPEN COMMAND 32 IC STEB FROM EDG (52DG) OPEN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVESWB REK ---- ---- ○ ---- ○ ----
PULSE
NO
3211 RD00 BFB 10 YB 12 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) CLOSE COMMAND 31 IC STEB FROM EDG (52DG) CLS CMD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVESWB REK ---- ---- ○ ---- ○ ----
PULSE

3212 RD00 BFB 10 XG 11 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) TRIP INDICATION 28 IC STEB FROM EDG (52DG) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ○ ----
(P1)

3213 RD00 BFB 10 XG 12 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) TRIP CIRCUIT HEALTHY 32 IC STEB FROM EDG (52DG) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ○ ----
(P1)

3214 RD00 BFB 10 XG 13 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) LOSS OF CONTROL POWER SOURCE 32 IC STEB FROM EDG (52DG) POW LOSS NORMAL/ALARM ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ○ ----
(P1)
3215 RD00 BFB 10 XG 14 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) CB CLOSED INDICATION 32 IC STEB FROM EDG (52DG) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3216 RD00 BFB 10 XG 15 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) REMOTE MODE SELECTED 30 IC STEB FROM EDG (52DG) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3217 RD00 BFB 10 XG 16 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) RACK-IN POSITION 31 IC STEB FROM EDG (52DG) RACK-IN OFF/ON ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

NO
3218 RD00 BFB 10 YB 21 ST OUTGOING TO UNIT-1 ESSENTIAL BOAD (52DG-1) OPEN COMMAND 28 OG TO U1EB (52DG-1) OPEN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVESWB REK ---- ---- ○ ---- ○ ----
PULSE
NO
3219 RD00 BFB 10 YB 22 ST OUTGOING TO UNIT-1 ESSENTIAL BOAD (52DG-1) CLOSE COMMAND 29 OG TO U1EB (52DG-1) CLOSE CMD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVESWB REK ---- ---- ○ ---- ○ ----
PULSE

3220 RD00 BFB 10 XG 21 ST OUTGOING TO UNIT-1 ESSENTIAL BOAD (52DG-1) TRIP INDICATION 24 OG TO U1EB (52DG-1) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)

3221 RD00 BFB 10 XG 22 ST OUTGOING TO UNIT-1 ESSENTIAL BOAD (52DG-1) TRIP CIRCUIT HEALTHY 28 OG TO U1EB (52DG-1) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3222 RD00 BFB 10 XG 23 ST OUTGOING TO UNIT-1 ESSENTIAL BOAD (52DG-1) CB CLOSED INDICATION 29 OG TO U1EB (52DG-1) CB CLOSED OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3223 RD00 BFB 10 XG 24 ST OUTGOING TO UNIT-1 ESSENTIAL BOAD (52DG-1) REMOTE MODE SELECTED 26 OG TO U1EB (52DG-1) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3224 RD00 BFB 10 XG 25 ST OUTGOING TO UNIT-1 ESSENTIAL BOAD (52DG-1) RACK-IN POSITION 31 OG TO U1EB (52DG-1) RACK-IN POS OFF/ON ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

NO
3225 RD00 BFB 10 YB 31 ST OUTGOING TO UNIT-2 ESSENTIAL BOAD (52DG-2) OPEN COMMAND 28 OG TO U2EB (52DG-2) OPEN CMD OFF/OPEN ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVESWB REK ---- ---- ○ ---- ○ ----
PULSE
NO
3226 RD00 BFB 10 YB 32 ST OUTGOING TO UNIT-2 ESSENTIAL BOAD (52DG-2) CLOSE COMMAND 29 OG TO U2EB (52DG-2) CLOSE CMD OFF/CLOSE ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVESWB REK ---- ---- ○ ---- ○ ----
PULSE

3227 RD00 BFB 10 XG 31 ST OUTGOING TO UNIT-2 ESSENTIAL BOAD (52DG-2) TRIP INDICATION 24 OG TO U2EB (52DG-2) TRIP OFF/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3228 RD00 BFB 10 XG 32 ST OUTGOING TO UNIT-2 ESSENTIAL BOAD (52DG-2) TRIP CIRCUIT HEALTHY 32 OG TO U2EB (52DG-2) TRP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3229 RD00 BFB 10 XG 33 ST OUTGOING TO UNIT-2 ESSENTIAL BOAD (52DG-2) CB CLOSED INDICATION 29 OG TO U2 EB (52DG-2) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3230 RD00 BFB 10 XG 34 ST OUTGOING TO UNIT-2 ESSENTIAL BOAD (52DG-2) REMOTE MODE SELECTED 26 OG TO U2EB (52DG-2) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3231 RD00 BFB 10 XG 35 ST OUTGOING TO UNIT-2 ESSENTIAL BOAD (52DG-2) RACK-IN POSITION 31 OG TO U2EB (52DG-2) RACK-IN POS OFF/ON ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3232 RD00 BFB 10 XG 61 ST TURBINE GENERATOR OVERHEAD CRANE MCCB CLOSE INDICATION 29 T/G OVERHEAD CRANE MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3233 RD00 BFB 10 XG 62 ST TURBINE GENERATOR OVERHEAD CRANE TRIP CLOSE INDICATION 29 T/G OVERHEAD CRANE TRIP CLOSE NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3234 RD00 BFB 10 XG 63 ST INSTRUMENT AIR COMPRESSOR (A) MCCB CLOSE INDICATION 30 INST AIR CMPRSR (A) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3235 RD00 BFB 10 XG 64 ST INSTRUMENT AIR COMPRESSOR (A) MCCB TRIP INDICATION 29 INST AIR CMPRSR (A) MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
2.DCS IO LIST FOR HARD WIRE
2-2.POWER PLANT FOR COMMON AREA

APPLIED ALARM ILD or IBD


NC/NO RD00DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
3236 RD00 BFB 10 XG 65 ST INSTRUMENT AIR COMPRESSOR (B) MCCB CLOSE INDICATION 30 INST AIR CMPRSR (B) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----


3237 RD00 BFB 10 XG 66 ST INSTRUMENT AIR COMPRESSOR (B) MCCB TRIP INDICATION 29 INST AIR CMPRSR (B) MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ○ ----
(P1)
3428 RD00 BFB 10 XG 67 ST INSTRUMENT AIR COMPRESSOR (C) MCCB CLOSE INDICATION 30 INST AIR CMPRSR (C) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3429 RD00 BFB 10 XG 68 ST INSTRUMENT AIR COMPRESSOR (C) MCCB TRIP INDICATION 29 INST AIR CMPRSR (C) MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)

3431 RD00 BFB 10 XG 03 DEG AUXILIARY LOAD MCCB CLOSE INDICATION 29 DEG AUXILIARY LOAD MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3432 RD00 BFB 10 XG 04 DEG AUXILIARY LOAD TRIP INDICATION 23 DEG AUXILIARY LOAD TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3242 RD00 BFB 10 XG 71 ST HVAC FOR POWER HOUSE MCCB CLOSE INDICATION 31 HVAC FOR POWER HOUSE MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3243 RD00 BFB 10 XG 72 ST HVAC FOR POWER HOUSE TRIP INDICATION 25 HVAC FOR POWER HOUSE TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)

3244 RD00 BFB 10 XQ 73 ST HVAC FOR POWER HOUSE CURRENT 28 HVAC FOR POWER HOUSE CURRENT 0-400 A AIX ---- ---- ---- 1% STLVESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3245 RD00 BFB 10 XG 74 ST ELECTRIC FIRE PUMP MCCB CLOSE INDICATION 28 ELECTRIC FIRE PUMP MCCB CLOS OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3246 RD00 BFB 10 XG 75 ST ELECTRIC FIRE PUMP TRIP INDICATION 23 ELECTRIC FIRE PUMP TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3247 RD00 BFB 10 XQ 76 ST ELECTRIC FIRE PUMP CURRENT 26 ELECTRIC FIRE PUMP CURRENT 0-250 A AIX ---- ---- ---- 1% STLVESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3248 RD00 BFB 10 XG 77 ST SPARE FEEDER (10kVA) MCCB CLOSE INDICATION 30 SPARE FEERE (10kVA) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3249 RD00 BFB 10 XG 78 ST SPARE FEEDER (10kVA) TRIP INDICATION 24 SPARE FEERE (10kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3250 RD00 BFB 10 XG 79 ST JOCKEY PUMP MCCB CLOSE INDICATION 22 JOCKEY PUMP MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3251 RD00 BFB 10 XG 80 ST JOCKEY PUMP MCCB TRIP INDICATION 21 JOCKEY PUMP MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3252 RD00 BFB 10 XG 81 ST DC SYSTEM (BACK-UP) MCCB CLOSE INDICATION 30 DC SYSTEM (BACK-UP) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3253 RD00 BFB 10 XG 82 ST DC SYSTEM (BACK-UP) TRIP INDICATION 24 DC SYSTEM (BACK-UP) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3254 RD00 BFB 10 XG 83 ST BYPASS AC UPS SYSTEM A MCCB CLOSE INDICATION 31 BYPASS AC UPS SYSTEM A MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3255 RD00 BFB 10 XG 84 ST BYPASS AC UPS SYSTEM A TRIP INDICATION 27 BYPASS AC UPS SYSTEM A TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)

3256 RD00 BFB 10 XG 85 ST BYPASS AC UPS SYSTEM B MCCB CLOSE INDICATION 31 BYPASS AC UPS SYSTEM B MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3257 RD00 BFB 10 XG 86 ST BYPASS AC UPS SYSTEM B TRIP INDICATION 27 BYPASS AC UPS SYSTEM B TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3258 RD00 BFB 10 XG 87 ST DISTRIBUTION BOARD OF 150 KV SWITCHYARD MCCB CLOSE INDICATION 32 DB OF 150 KV SWITCHYARD MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3259 RD00 BFB 10 XG 88 ST DISTRIBUTION BOARD OF 150 KV SWITCHYARD TRIP INDICATION 28 DB OF 150 KV SWITCHYARD TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)

3260 RD00 BFB 10 XG 89 ST LIGHTING TRANSFORMER RD00LVB-E (150 kVA) MCCB CLOSE INDICATION 31 LT RD00LVB-E (150 kVA) MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3261 RD00 BFB 10 XG 90 ST LIGHTING TRANSFORMER RD00LVB-E (150 kVA) TRIP INDICATION 27 LT RD00LVB-E (150 kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3262 RD00 BFB 10 XQ 91 ST LIGHTING TRANSFORMER RD00LVB-E (150 kVA) CURRENT 30 LT RD00LVB-E (150 kVA) CURRENT 0-400 A AIX ---- ---- ---- 1% STLVESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3263 RD00 BFB 10 XG 92 ST OUTGOING TO SGS SERVICE TRASNFORMER MCCB CLOSE INDICATION 21 OG TO SSST MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3264 RD00 BFB 10 XG 93 ST OUTGOING TO SGS SERVICE TRASNFORMER TRIP INDICATION 15 OG TO SSST TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3265 RD00 BFB 10 XQ 94 ST OUTGOING TO SGS SERVICE TRASNFORMER CURRENT 18 OG TO SSST CURRENT 0-400 A AIX ---- ---- ---- 1% STLVESWB NA RD00MCCRIO(LV) REK ---- ---- ---- ---- ○ ----

3435 RD00 BFB 10 XG 98 ST SPARE FEEDER (30kVA) MCCB CLOSE INDICATION 30 SPARE FEERE (30kVA) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3436 RD00 BFB 10 XG 99 ST SPARE FEEDER (30kVA) TRIP INDICATION 24 SPARE FEERE (30kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3266 RD00 BFB 10 XG 94 ST SPARE FEEDER (60kVA) MCCB CLOSE INDICATION 31 SPARE FEEDER (60kVA) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3267 RD00 BFB 10 XG 95 ST SPARE FEEDER (60kVA) TRIP INDICATION 25 SPARE FEEDER (60kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3268 RD00 BFB 10 XG 96 ST SPARE FEEDER (150kVA) MCCB CLOSE INDICATION 32 SPARE FEEDER (150kVA) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3269 RD00 BFB 10 XG 97 ST SPARE FEEDER (150kVA) TRIP INDICATION 26 SPARE FEEDER (150kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3270 RD00 BFB 10 XQ 95 ST SPARE FEEDER (150kVA) TRIP CURRENT 29 SPARE FEEDER (150kVA) CURRENT 0-400 A AIX ---- ---- ---- 1% STLVESWB NA RD00MCCRIO(LV) REK ---- ○ ---- ---- ----

(P1)
3271 RD00 XJY 20 XG 01 ST EDG RUNNING INDICATION 11 EDG RUNNING OFF/RUN ---- DI ---- ---- NO ---- EDGRCP NA RD00DCS REK ○ ---- ---- ---- ○ ----

3272 RD00 XJY 20 XG 02 ST EDG FAULT INDICATION 9 EDG FAULT NORMAL/FAULT ---- DI ---- ---- NO ---- EDGRCP NA RD00DCS REK ---- ○ ---- ---- ----

(P1)
3273 RD00 XJY 20 XG 03 ST EDG STOP INDICATION 8 EDG STOP OFF/STOP ---- DI ---- ---- NO ---- EDGRCP NA RD00DCS REK ○ ---- ---- ---- ○ ----

3274 RD00 XJY 20 XG 04 ST EDG REMOTE MODE SELECTED 10 EDG REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- EDGRCP NA RD00DCS REK ○ ---- ---- ---- ○ ----


3275 RD00 XJY 20 XG 05 ST EDG LOSS OF POWER CONTROL SOURCE 23 EDG POWER LOSS OF POWER OFF/FAULT ---- DI ---- ---- NO ---- EDGRCP NA RD00DCS REK ---- ---- ---- ○ ----
(P1)
3276 RD00 XJY 20 XG 06 ST EDG DAILY FUEL LEVEL L 22 EDG DAILY FUEL LEVEL L NORMAL/LOW ---- DI ---- ---- NO ---- EDGRCP NA RD00DCS REK ---- ○ ---- ---- ----

(P2)
3407 RD00 XJY 20 XG 07 ST EDG DAILY FUEL LEVEL H 22 EDG DAILY FUEL LEVEL H NORMAL/LOW ---- DI ---- ---- NO ---- EDGRCP NA RD00DCS REK ---- ○ ---- ---- ----

(P2)
3277 RD00 BRA 10 XQ 01 UPS SYSTEM DB-01 BUS VOLTAGE 28 UPS SYSTEM DB-01 BUS VOLTAGE 0-230 V AIX ---- ---- ---- ---- UPSMDB NA RD00DCS REK ○ ---- ---- ---- ○ ----

3278 RD00 BRA 10 XG 01 UPS SYSTEM DB-01 COMMON OUTPUT FEEDER TRIP 32 UPS SYS DB-01 OUTPUT FEEDER TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- UPSMDB NA RD00DCS REK ---- ○ ---- ---- ----

(P1)
3279 RD00 BRA 10 XQ 02 UPS SYSTEM DB-02 BUS VOLTAGE 28 UPS SYSTEM DB-02 BUS VOLTAGE 0-230 V AIX ---- ---- ---- ---- UPSMDB NA RD00DCS REK ○ ---- ---- ---- ○ ----

3280 RD00 BRA 10 XG 02 UPS SYSTEM DB-02 COMMON OUTPUT FEEDER TRIP 32 UPS SYS DB-02 OUTPUT FEEDER TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- UPSMDB NA RD00DCS REK ---- ○ ---- ---- ----

(P1)
3281 RD00 BUA 10 XQ 01 DC SYSTEM DB-01 BUS VOLTAGE 27 DC SYSTEM DB-01 BUS VOLTAGE 0-110 VDC AIX ---- ---- ---- ---- DCMDB NA RD00DCS REK ○ ---- ---- ---- ○ ----

3282 RD00 BUA 10 XG 01 DC SYSTEM DB-01 COMMON OUTPUT FEEDER TRIP 31 DC SYS DB-01 OUTPUT FEEDER TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- DCMDB NA RD00DCS REK ---- ○ ---- ---- ----

(P1)
2.DCS IO LIST FOR HARD WIRE
2-2.POWER PLANT FOR COMMON AREA

APPLIED ALARM ILD or IBD


NC/NO RD00DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
3283 RD00 BUA 10 XQ 02 DC SYSTEM DB-02 BUS VOLTAGE 27 DC SYSTEM DB-02 BUS VOLTAGE 0-110 VDC AIX ---- ---- ---- ---- DCMDB NA RD00DCS REK ○ ---- ---- ---- ○ ----


3284 RD00 BUA 10 XG 02 DC SYSTEM DB-02 COMMON OUTPUT FEEDER TRIP 31 DC SYS DB-02 OUTPUT FEEDER TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- DCMDB NA RD00DCS REK ---- ---- ---- ○ ----
(P1)
3285 RD00 BFT 10 XG 01 COMMON SERVICE TRANSFORMER OIL TEMPERATURE H 20 COMMON ST OIL TEMP H NORMAL/HIGH ---- DI ---- ---- NO ---- SST U0-ARS RD00DCS REK ---- ○ ---- ---- ----

(P2)
3286 RD00 BFT 10 XG 02 COMMON SERVICE TRANSFORMER OIL TEMPERATURE HH 21 COMMON ST OIL TEMP HH NORMAL/HHGH ---- DI ---- ---- NO ---- SST U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3287 RD00 BFT 10 XG 03 COMMON SERVICE TRANSFORMER WINDING TEMPERATURE H 24 COMMON ST WINDING TEMP H NORMAL/HIGH ---- DI ---- ---- NO ---- SST U0-ARS RD00DCS REK ---- ○ ---- ---- ----

(P2)
3288 RD00 BFT 10 XG 04 COMMON SERVICE TRANSFORMER WINDING TEMPERATURE HH 25 COMMON ST WINDING TEMP HH NORMAL/HHGH ---- DI ---- ---- NO ---- SST U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3289 RD00 BFT 10 XG 05 COMMON SERVICE TRANSFORMER OIL LEVEL MAIN TANK 29 COMMON ST OIL LEVEL MAIN TANK NORMAL/LOW ---- DI ---- ---- NO ---- SST U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3290 RD00 BFT 10 XG 06 COMMON SERVICE TRANSFORMER PRESSURE RELIEF DEVICE 32 COMMON ST PRESSURE RELIEF DEVICE NORMAL/ALARM ---- DI ---- ---- NO ---- SST U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3291 RD00 BFT 20 XG 01 SGS SERVICE TRANSFORMER OIL TEMPERATURE H 17 SGS ST OIL TEMP H NORMAL/HIGH ---- DI ---- ---- NO ---- SGST U0-ARS RD00DCS REK ---- ○ ---- ---- ----

(P2)
3292 RD00 BFT 20 XG 02 SGS SERVICE TRANSFORMER OIL TEMPERATURE HH 18 SGS ST OIL TEMP HH NORMAL/HHGH ---- DI ---- ---- NO ---- SGST U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3293 RD00 BFT 20 XG 03 SGS SERVICE TRANSFORMER WINDING TEMPERATURE H 21 SGS ST WINDING TEMP H NORMAL/HIGH ---- DI ---- ---- NO ---- SGST U0-ARS RD00DCS REK ---- ○ ---- ---- ----

(P2)

3294 RD00 BFT 20 XG 04 SGS SERVICETRANSFORMER WINDING TEMPERATURE HH 22 SGS ST WINDING TEMP HH NORMAL/HHGH ---- DI ---- ---- NO ---- SGST U0-ARS RD00DCS REK ---- ---- ---- ○ ○
(P2)
3295 RD00 BFT 20 XG 05 SGS SERVICE TRANSFORMER OIL LEVEL MAIN TANK 26 SGS ST OIL LEVEL MAIN TANK NORMAL/LOW ---- DI ---- ---- NO ---- SGST U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3296 RD00 BFT 20 XG 06 SGS SERVICE TRANSFORMER PRESSURE RELIEF DEVICE 29 SGS ST PRESSURE RELIEF DEVICE NORMAL/ALARM ---- DI ---- ---- NO ---- SGST U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)

3297 RD00 BFT 30 XG 01 ACCOMODATION BLOCK TRANSFORMER OIL TEMPERATURE H 29 ACCOMODATION TRANS OIL TEMP H NORMAL/HIGH ---- DI ---- ---- NO ---- ACCBT U0-ARS RD00DCS REK ---- ○ ---- ---- ----

(P2)
3298 RD00 BFT 30 XG 02 ACCOMODATION BLOCK TRANSFORMER OIL TEMPERATURE HH 30 ACCOMODATION TRANS OIL TEMP HH NORMAL/HHGH ---- DI ---- ---- NO ---- ACCBT U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)

3299 RD00 BFT 30 XG 03 ACCOMODATION BLOCKTRANSFORMER WINDING TEMPERATURE H 30 ACCMDTION TRANS WINDING TEMP H NORMAL/HIGH ---- DI ---- ---- NO ---- ACCBT U0-ARS RD00DCS REK ---- ---- ---- ○ ----
(P2)
3300 RD00 BFT 30 XG 04 ACCOMODATION BLOCK TRANSFORMER WINDING TEMPERATURE HH 31 ACCMDTION TRANS WINDING TEMP HH NORMAL/HHGH ---- DI ---- ---- NO ---- ACCBT U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3301 RD00 BFT 30 XG 05 ACCOMODATION BLOCK TRANSFORMER OIL LEVEL MAIN TANK 32 ACCMDTION TRANS OIL LVL MAIN TNK NORMAL/LOW ---- DI ---- ---- NO ---- ACCBT U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3302 RD00 BFT 30 XG 06 ACCOMODATION BLOCK TRANSFORMER PRESSURE RELIEF DEVICE 32 ACCMDTION TRANS PRESS RELIEF DVC NORMAL/ALARM ---- DI ---- ---- NO ---- ACCBT U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)

3303 RD00 BJT 20 XG 01 ST NORMAL LIGHTING TRANSFORMER 150 kVA OIL TEMPERATURE H 27 NORMAL LT 150kVA OIL TEMP H NORMAL/HIGH ---- DI ---- ---- NO ---- STNELT U0-ARS RD00DCS REK ---- ---- ---- ○ ----
(P2)

3304 RD00 BJT 20 XG 02 ST NORMAL LIGHTING TRANSFORMER 150 kVA OIL TEMPERATURE HH 28 NORMAL LT 150kVA OIL TEMP HH NORMAL/HHGH ---- DI ---- ---- NO ---- STNELT U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3305 RD00 BJT 20 XG 03 ST NORMAL LIGHTING TRANSFORMER 150 kVA WINDING TEMPERATURE H 31 NORMAL LT 150kVA WINDING TEMP H NORMAL/HIGH ---- DI ---- ---- NO ---- STNELT U0-ARS RD00DCS REK ---- ○ ---- ---- ----

(P2)
3306 RD00 BJT 20 XG 04 ST NORMAL LIGHTING TRANSFORMER 150 kVA WINDING TEMPERATURE HH 30 NORM LT 150kVA WINDING TEMP HH NORMAL/HHGH ---- DI ---- ---- NO ---- STNELT U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3307 RD00 BJT 20 XG 05 ST NORMAL LIGHTING TRANSFORMER 150 kVA OIL LEVEL 27 NORMAL LT 150kVA OIL LEVEL NORMAL/LOW ---- DI ---- ---- NO ---- STNELT U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3308 RD00 BJT 20 XG 06 ST NORMAL LIGHTING TRANSFORMER 150 kVA PRESSURE RELIEF DEVICE 29 NORMAL LT 150kVA PRESS RELIEF NORMAL/ALARM ---- DI ---- ---- NO ---- STNELT U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3309 RD00 BJT 10 XG 01 ST EMERGENCY LIGHTING TRANSFORMER 150 kVA OIL TEMPERATURE H 30 EMERGENCY LT 150kVA OIL TEMP H NORMAL/HIGH ---- DI ---- ---- NO ---- STELT U0-ARS RD00DCS REK ---- ○ ---- ---- ----

(P2)

3310 RD00 BJT 10 XG 02 ST EMERGENCY LIGHTING TRANSFORMER 150 kVA OIL TEMPERATURE HH 31 EMERGENCY LT 150kVA OIL TEMP HH NORMAL/HHGH ---- DI ---- ---- NO ---- STELT U0-ARS RD00DCS REK ---- ---- ---- ○ ○
(P2)
3311 RD00 BJT 10 XG 03 ST EMERGENCY LIGHTING TRANSFORMER 150 kVA WINDING TEMPERATURE H 29 EMGC LT 150kVA WINDING TEMP H NORMAL/HIGH ---- DI ---- ---- NO ---- STELT U0-ARS RD00DCS REK ---- ○ ---- ---- ----

(P2)

3312 RD00 BJT 10 XG 04 ST EMERGENCY LIGHTING TRANSFORMER 150 kVA WINDING TEMPERATURE HH 30 EMGC LT 150kVA WINDING TEMP HH NORMAL/HHGH ---- DI ---- ---- NO ---- STELT U0-ARS RD00DCS REK ---- ---- ---- ○ ○
(P2)
3313 RD00 BJT 10 XG 05 ST EMERGENCY LIGHTING TRANSFORMER 150 kVA OIL LEVEL 30 EMERGENCY LT 150kVA OIL LEVEL NORMAL/LOW ---- DI ---- ---- NO ---- STELT U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3314 RD00 BJT 10 XG 06 ST EMERGENCY LIGHTING TRANSFORMER 150 kVA PRESSURE RELIEF DEVICE 32 EMERGENCY LT 150kVA PRESS RELIEF NORMAL/ALARM ---- DI ---- ---- NO ---- STELT U0-ARS RD00DCS REK ---- ○ ---- ---- ○ ○
(P2)
3315 RD00 SAA 10 GH 001 XG 01 HVAC SYSTEM SHUTDOWN 20 HVAC SYSTEM SHUTDOWN OFF/SHUTDOWN ---- DI ---- ---- NC ---- HVAC NA RD00DCS REK ○ ---- ---- ----
○ ○
(P2)
6.0
3318 RD00 QFB 20 CP 001 XQ 01 SEPARATOR STATION AIR RECEIVER PRESSURE 30 SEP STATION AIR RECEIVER PRESS 0-10 barg AII ---- ---- ---- 1% F U0-ARS RD00DCS REK ○ L ---- ---- ○ ---- Rev.4;Move to PAD-E 4
(P2)
6.0
3319 RD00 QFB 30 CP 001 XQ 01 VENT STATION AIR RECEIVER PRESSURE 31 VENT STATION AIR RECEIVER PRESS 0-10 barg AII ---- ---- ---- 1% F U0-ARS RD00DCS REK ○ L ---- ---- ○ ----
(P2)
4.2 2.0
3320 RD00 GDK 30 CP 001 XQ 01 Utility Water Header Pressure 26 Utility Water Header Press 0-10 barg AII ---- ---- ---- 1% F U0-ARS RD00DCS REK ○ H/L ---- ---- ○ ----
(P2) (P2)
10.5 5.0
3321 RD00 GHD 10 CP 001 XQ 01 Domestic Water Header Pressure 19 Domstic Water Press 0-15 barg AII ---- ---- ---- 1% F U0-ARS RD00DCS REK ○ H/L ---- ---- ○ ----
(P2) (P2)
NO
3322 RD00 GAC 30 AA 101 YB 01 RAW WATER SUPPLY ISOLATION VALVE OPEN COMMAND 31 RAW WATER SUP ISOL VLV OPEN CMD CLOSE/OPEN ---- DOW DC110 5W ---- RD00DCS U0-ARS F REK ○ ---- ○ ---- ○ ---- DC 110 FROM RD00DCS
LATCH

3324 RD00 GAC 30 CG 101 XG 01 RAW WATER SUPPLY ISOLATION VALVE OPEN 27 RAW WATER SUP ISOL VLV OPEN OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ---- ○ ----

3325 RD00 GAC 30 CG 101 XG 02 RAW WATER SUPPLY ISOLATION VALVE CLOSE 28 RAW WATER SUP ISOL VLV CLOSE OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ---- ○ ----

3326 RD00 GAD 10 CL 081 XG 01 RAW WATER STORAGE POND LEVEL HIGH 31 RAW WATER STORAGE POND LVL HIGH NORMAL/HIGH ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ----
○ ○
(P2)
3405 RD00 GAD 10 CL 081 XG 02 RAW WATER STORAGE POND LEVEL LOW 32 RAW WATER STORAGE POND LEVEL LOW OFF/ON ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
NO
3327 RD00 GDK 10 AA 101 YB 01 FRESH WATER SUPPLY ISOLATION VALVE OPEN COMMAND 32 FRESH WATER SUP ISOL VLV OPN CMD CLOSE/OPEN ---- DOW DC110 5W ---- RD00DCS U0-ARS F REK ○ ---- ○ ---- ○ ---- DC 110 FROM RD00DCS
LATCH

3329 RD00 GDK 10 CG 101 XG 01 FRESH WATER SUPPLY ISOLATION VALVE OPEN 29 FRESH WATER SUP ISOL VLV OPEN OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ---- ○ ----

3330 RD00 GDK 10 CG 101 XG 02 FRESH WATER SUPPLY ISOLATION VALVE CLOSE 30 FRESH WATER SUP ISOL VLV CLOSE OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ---- ○ ----

3332 RD00 SGA 10 AP 003 XG 01 Jockey Pump - Running Indication 32 Jockey Pump - Running Indication STOP/RUN ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ---- ○ ----

3333 RD00 SGA 10 AP 003 XG 02 Jockey Pump - Fault Indication 30 Jockey Pump - Fault Indication NORMAL/FAULT ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ----
○ ○
(P2)
3334 RD00 SGA 10 AP 002 XG 01 Electric Pump - Running Indication 34 Electric Pump - Running Indication STOP/RUN ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ---- ○ ----

3335 RD00 SGA 10 AP 002 XG 02 Electric Pump - Fault Indication 32 Electric Pump - Fault Indication NORMAL/FAULT ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ----
○ ○
(P2)
Revise DOH to DOL, @ Diesel
3336 RD00 SGA 10 AP 001 YB 01 Diesel Pump - Start Command 27 Diesel Pump - Start Command STOP/START ---- DOL DC24V HOLD LATCH ---- RD00DCS U0-ARS F REK ○ ---- ○ ---- ○ ----
Pump, DOL : 24 VAC NC
2.DCS IO LIST FOR HARD WIRE
2-2.POWER PLANT FOR COMMON AREA

APPLIED ALARM ILD or IBD


NC/NO RD00DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
3337 RD00 SGA 10 AP 001 XG 02 Diesel Pump - Running Indication 32 Diesel Pump - Running Indication STOP/RUN ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ---- ○ ----


3338 RD00 SGA 10 AP 001 XG 03 Diesel Pump - Fault Indication 30 Diesel Pump - Fault Indication NORMAL/FAULT ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ○ ----
(P2)
NC
3346 RD00 GDK 10 AP 001 YB 02 Utility Supply Pump - Stop Command 28 UTILITY SUPPLY PUMP STOP CMD OFF/STOP ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ○ ---- ○ ---- ○ ----
PULSE

3347 RD00 GDK 10 AP 001 XG 01 Utility Supply Pump - Remote Indication 39 Utility Supply Pump - Remote Indication LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3348 RD00 GDK 10 AP 001 XG 02 Utility Supply Pump - Running Indication 40 Utility Supply Pump - Running Indication STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3349 RD00 GDK 10 AP 001 XG 03 Utility Supply Pump - Trip Indication 37 Utility Supply Pump - Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ----
○ ○
(P2)
3430 RD00 GDK 10 AP 001 XG 04 Utility Supply Pump - Rack-in Position indication 49 Utility Supply Pump - Rack-in Position indication OFF/ON ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ----
○ ○
(P2)
NO
3350 RD00 GDK 10 AP 002 YB 01 Backwash Pump - Start Command 23 BACKWASH PUMP START CMD OFF/START ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ○ ---- ○ ---- ○ ----
PULSE
NC
3351 RD00 GDK 10 AP 002 YB 02 Backwash Pump - Stop Command 22 BACKWASH PUMP STOP CMD OFF/STOP ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ○ ---- ○ ---- ○ ----
PULSE

3352 RD00 GDK 10 AP 002 XG 01 Backwash Pump - Remote Indication 33 Backwash Pump - Remote Indication LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3353 RD00 GDK 10 AP 002 XG 02 Backwash Pump - Running Indication 34 Backwash Pump - Running Indication STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----


3354 RD00 GDK 10 AP 002 XG 03 Backwash Pump - Trip Indication 31 Backwash Pump - Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ○ ----
(P2)
3355 RD00 GDK 10 AP 002 XG 04 Backwash Pump Rack-In Position 30 Backwash Pump Rack-In Position OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P2)
NO
3356 RD00 GHD 10 AP 001 YB 01 Utility Water Distribution Pump Start Command 28 UTILITY WATER PUMP START CMD OFF/START ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ○ ---- ○ ---- ○ ----
PULSE
NC
3357 RD00 GHD 10 AP 001 YB 02 Utility Water Distribution Pump Stop Command 27 UTILITY WATER PUMP STOP CMD OFF/STOP ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ○ ---- ○ ---- ○ ----
PULSE

3358 RD00 GHD 10 AP 001 XG 01 Utility Water Distribution Pump Remote Indication 49 Utility Water Distribution Pump Remote Indication LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3359 RD00 GHD 10 AP 001 XG 02 Utility Water Distribution Pump Running Indication 50 Utility Water Distribution Pump Running Indication STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3360 RD00 GHD 10 AP 001 XG 03 Utility Water Distribution Pump Trip Indication 47 Utility Water Distribution Pump Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P2)
3361 RD00 GHD 10 AP 001 XG 04 Utility Water Distribution Pump Rack-In Position 48 Utility Water Distribution Pump Rack-In Position OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P2)
3374 RD00 GDB 10 AT 001 XG 01 WTP - Rinse Indication 22 WTP - Rinse Indication STOP/RUN ---- DI ---- ---- NO ---- WTP LCP U0-ARS RD00DCS REK ○ ---- ---- ---- ○ ----

3375 RD00 GDB 10 AT 001 XG 02 WTP - Backwash Indication 25 WTP - Backwash Indication STOP/RUN ---- DI ---- ---- NO ---- WTP LCP U0-ARS RD00DCS REK ○ ---- ---- ----
○ ○
(P2)
3376 RD00 GDB 10 AT 001 XG 03 WTP - Production Indication 27 WTP - Production Indication OFF/ON ---- DI ---- ---- NO ---- WTP LCP U0-ARS RD00DCS REK ○ ---- ---- ---- ○ ----

3378 RD00 GDB 10 BB 001 XG 01 Fresh Water Tank (A) - High Level 31 Fresh Water Tank (A) High Level NORMAL/HIGH ---- DI ---- ---- NC ---- WTP LCP U0-ARS RD00DCS REK ○ ---- ---- ----
○ ○
(P2)

3379 RD00 GDB 10 BB 001 XG 02 Fresh Water Tank (A) - Low Level 30 Fresh Water Tank (A) Low Level NORMAL/LOW ---- DI ---- ---- NC ---- WTP LCP U0-ARS RD00DCS REK ○ ---- ---- ----
○ ○
(P2)
3380 RD00 GDB 10 BB 001 XG 03 Fresh Water Tank (A) - Low-Low Level 29 Fresh Water Tank (A) LL Level NORMAL/LLOW ---- DI ---- ---- NC ---- WTP LCP U0-ARS RD00DCS REK ○ ---- ---- ----
○ ○
(P2)
875 250
3381 RD00 GQA 10 CL 001 XQ 01 OILY WATER SURGE BASIN LEVEL 28 OILY WATER SURGE BASIN LEVEL LATER mm AII ---- ---- ---- 1% F U0-ARS RD00DCS REK ○ H/L ---- ---- ○ ----
(P2) (P2)

3382 RD00 GQA 10 CL 081 XG 01 SLOP OIL BASIN LEVEL HIGH 25 SLOP OIL BASIN LEVEL HIGH NORMAL/HIGH ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ---- ----
○ ○
(P2)
NO
3383 RD00 GQA 10 AP 001 YB 01 Oily Water Submersible Pump - Start Command 25 OILY WATER PUMP START CMD OFF/START ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ○ ---- ○ ---- ○ ----
PULSE
NC
3384 RD00 GQA 10 AP 001 YB 02 Oily Water Submersible Pump - Stop Command 24 OILY WATER PUMP STOP CMD OFF/STOP ---- DOL 24V 2W ---- RD00MCCRIO(LV) NA STLVNESWB REK ○ ---- ○ ---- ○ ----
PULSE

3385 RD00 GQA 10 AP 001 XG 01 Oily Water Submersible Pump - Remote Indication 48 Oily Water Submersible Pump - Remote Indication LOCAL/REMOTE ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3386 RD00 GQA 10 AP 001 XG 02 Oily Water Submersible Pump - Running Indication 49 Oily Water Submersible Pump - Running Indication STOP/RUN ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3387 RD00 GQA 10 AP 001 XG 03 Oily Water Submersible Pump - Trip Indication 46 Oily Water Submersible Pump - Trip Indication OFF/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P2)
3439 RD00 GQA 10 AP 001 XG 04 Oily Water Submersible Pump - Rack in position 47 Oily Water Submersible Pump - Rack in position OFF/ON ---- DI ---- ---- NO ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ---- ○ ----

3388 RD00 GHD 10 CF 002 XG 02 Emergency Shower at Laboratory 24 LABORATORY EMG SHOWER ON OFF/ALARM ---- DI ---- ---- NO ---- FACP NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3389 RD00 GHD 10 CF 003 XG 03 Emergency Shower at Workshop / Store Building 22 WORKSHOP EMG SHOWER ON OFF/ALARM ---- DI ---- ---- NO ---- FACP NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3390 RD00 GHD 10 CF 004 XG 04 Emergency Shower at Battery Room 26 BATTERY ROOM EMG SHOWER ON OFF/ALARM ---- DI ---- ---- NO ---- FACP NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3406 RD00 GHD 10 CF 005 XG 05 Emergency Shower at CHEMICAL INJECTION UNIT 32 CHEMICAL INJECTION EMG SHOWER ON OFF/ON ---- DI ---- ---- NO ---- F U0-ARS RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3393 RD00 SGM 01 EA 209 XG 01 Electrical Room FM200 Gas Discharge 29 ELECTRICAL ROOM GAS DISCHARGE OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3394 RD00 SGM 01 EA 207 XG 01 Electrical Room FM200 Confirmed Fire 30 ELECTRICAL ROOM CONFIRMED FIRE OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3395 RD00 SGM 01 EA 208 XG 01 Electrical Room FM200 HSSD triggered 23 ELECTRICAL ROOM HSSD ON OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3396 RD00 SGM 02 EA 209 XG 01 Control Room FM200 Gas Discharge 26 CONTROL ROOM GAS DISCHARGE OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3397 RD00 SGM 02 EA 207 XG 01 Control Room FM200 Confirmed Fire 27 CONTROL ROOM CONFIRMED FIRE OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)

3398 RD00 SGM 02 EA 208 XG 01 Control Room FM200 HSSD triggered 20 CONTROL ROOM HSSD ON OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ---- ○ ○
(P2)
3399 RD00 SGM 03 EA 209 XG 01 Substation Room FM200 Gas Discharge 24 SUBSTATION GAS DISCHARGE OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3400 RD00 SGM 03 EA 207 XG 01 Substation Room FM200 Confirmed Fire 25 SUBSTATION CONFIRMED FIRE OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)

3401 RD00 SGM 03 EA 208 XG 01 Substation Room FM200 HSSD triggered 18 SUBSTATION HSSD ON OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3402 RD00 SGM 04 EA 209 XG 01 Relay Room FM200 Gas Discharge 24 RERAY ROOM GAS DISCHARGE OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3403 RD00 SGM 04 EA 207 XG 01 Relay Room FM200 Confirmed Fire 25 RELAY ROOM CONFIRMED FIRE OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
3404 RD00 SGM 04 EA 208 XG 01 Relay Room FM200 HSSD triggered 18 RERAY ROOM HSSD ON OFF/ALARM ---- DI ---- ---- NO ---- FM200 NA RD00DCS REK ○ ---- ----
○ ○ ○
(P2)
NO ○
3410 RD00 SES 01 YB 01 Emergency Shower Operation Annunciator 19 EMERGENCY SHOWER ON OFF/ON ---- DOW DC110 5W ---- RD00DCS U0-ARS F REK ---- ---- ---- ---- ----
LATCH (P2)
2.DCS IO LIST FOR HARD WIRE
2-2.POWER PLANT FOR COMMON AREA

APPLIED ALARM ILD or IBD


NC/NO RD00DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS Rev
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
6.0
3437 RD00 QEA 10 CP 001 XQ 01 POWER PLANT AIR RECEIVER A PRESSURE 23 AIR RECEIVER A PRESSURE 0-10 barg AII ---- ---- ---- 1% F U0-ARS RD00DCS REK ○ L ---- ---- ○ ----
(P2)
6.0
3438 RD00 QEA 10 CP 002 XQ 01 POWER PLANT AIR RECEIVER B PRESSURE 23 AIR RECEIVER B PRESSURE 0-10 barg AII ---- ---- ---- 1% F U0-ARS RD00DCS REK ○ L ---- ---- ○ ----
(P2)

3440 RD00 BBA 10 XG 10 ST COMMON STATION MV SWITCHGEAR UNDERVOLTAGE TRIP 20 STMVSWG UNDERVOLTAGE HEALTHY/TRIP ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ○ ---- ---- ----
○ ○
(P1)
3441 RD00 BFA 10 XG 10 ST COMMON STATION LV SWITCHGEAR UNDERVOLTAGE TRIP 20 STLVSWG UNDERVOLTAGE HEALTHY/TRIP ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)

3442 RD00 BFB 20 XG 10 ST COMMON STATION LV NON-ESSENTIAL BOARD UNDERVOLATGE TRIP 20 STLVNEB UNDERVOLTAGE HEALTHY/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)

3443 RD00 BFB 10 XG 20 ST COMMON STATION LV ESSENTIAL BOARD UNDERVOLATGE TRIP 18 STLVEB UNERVOLTAGE HEALTHY/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3444 RD00 BBA 10 XG 30 ST COMMON STATION MV SWITCHGEAR LOSS OF CONTROL SUPPLY 29 STMVSWG LOSS OF CONTROL POWER HEALTHY/TRIP ---- DI ---- ---- NC ---- STMVSWG NA RD00MCCRIO(MV) REK ○
○ ---- ---- ○ ----
(P1)

3445 RD00 BFA 10 XG 30 ST COMMON STATION LV SWITCHGEAR LOSS OF CONTROL SUPPLY 29 STLVSWG LOSS OF CONTROL POWER HEALTHY/TRIP ---- DI ---- ---- NC ---- STLVSWG NA RD00MCCRIO(LV) REK ○ ---- ---- ○ ----
(P1)

3446 RD00 BFB 20 XG 30 ST COMMON STATION NON-ESSENTIAL SWITCHBOARD LOSS OF CONTROL SUPPLY 29 STLVNEB LOSS OF CONTROL POWER HEALTHY/TRIP ---- DI ---- ---- NC ---- STLVNESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
3447 RD00 BFB 10 XG 30 ST COMMON STATION ESSENTIAL SWITCHBOARD LOSS OF CONTROL SUPPLY 28 STLVEB LOSS OF CONTRO; POWER HEALTHY/TRIP ---- DI ---- ---- NC ---- STLVESWB NA RD00MCCRIO(LV) REK ○ ---- ---- ----
○ ○
(P1)
2.DCS IO LIST FOR HARD WIRE
2-3.SEPARATOR & WELLPAD-E AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
8 RD00 BBB 10 XQ 01 SS 6.3kV SWITCHGEAR BUS VOLTAGE 21 6.3kV SWG BUS VOLTAGE 7200 V AIX ---- ---- ---- ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

NO
9 RD00 BBB 10 YB 11 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) CB OPEN COMMAND 32 IC FROM SSST (52HA-4) CB OPN CMD OFF/OPEN ---- DOH DC110 5W ---- DCSSEP NA SGSSMVSWG ---- ---- ---- ○ ---- ○ ----
PULSE
NO
10 RD00 BBB 10 YB 12 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) CB CLOSE COMMAND 32 IC FROM SSST (52HA-4) CB CLS CMD OFF/CLOSE ---- DOH DC110 5W ---- DCSSEP NA SGSSMVSWG ---- ---- ---- ○ ---- ○ ----
PULSE

11 RD00 BBB 10 XG 11 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) TRIP INDICATION 26 IC FROM SSST (52HA-4) TRIP OFF/TRIP ---- DI ---- ---- NC ---- SGSSMVSWG NA DCSSEP ---- ---- P1 ---- ---- ○ ----

12 RD00 BBB 10 XG 12 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) TRIP CIRCUIT HEALTHY 30 IC FROM SSST (52HA-4) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- SGSSMVSWG NA DCSSEP ---- ---- P1 ---- ---- ○ ----

13 RD00 BBB 10 XG 13 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) REMOTE MODE SELECTED 28 IC FROM SSST (52HA-4) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

14 RD00 BBB 10 XG 14 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) CB CLOSED INDICATION 29 IC FROM SSST (52HA-4)CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

15 RD00 BBB 10 XG 15 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) ES CLOSE INDICATION 30 IC FROM SSST (52HA-4) ES CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

NO
16 RD00 BBB 10 YB 21 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) CB OPEN COMMAND 32 IC FRM MVSWG (52HB-4) CB OPN CMD OFF/OPEN ---- DOH DC110 5W ---- DCSSEP NA SGSSMVSWG ---- ---- ---- ○ ---- ○ ----
PULSE
NO
17 RD00 BBB 10 YB 22 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) CB CLOSE COMMAND 32 IC FRM MVSWG (52HB-4) CB CLS CMD OFF/CLOSE ---- DOH DC110 5W ---- DCSSEP NA SGSSMVSWG ---- ---- ---- ○ ---- ○ ----
PULSE

18 RD00 BBB 10 XG 21 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) TRIP INDICATION 27 IC FROM MVSWG (52HB-4) TRIP OFF/TRIP ---- DI ---- ---- NC ---- SGSSMVSWG NA DCSSEP ---- ---- P1 ---- ---- ○ ----

19 RD00 BBB 10 XG 22 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) TRIP CIRCUIT HEALTHY 31 IC FROM MVSWG (52HB-4) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- SGSSMVSWG NA DCSSEP ---- ---- P1 ---- ---- ○ ----

20 RD00 BBB 10 XG 23 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) REMOTE MODE SELECTED 29 IC FROM MVSWG (52HB-4) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

21 RD00 BBB 10 XG 24 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) CB CLOSE INDICATION 29 IC FROM MVSWG (52HB-4) CB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

22 RD00 BBB 10 XG 25 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) ES CLOSE INDICATION 28 IC FRM MVSWG (52HB-4) ES CLS OPEN/CLOSE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

NO
23 RD00 BBB 10 YB 31 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) CB OPEN COMMAND 30 OG TO SSST (52HC-4) CB OPN CMD OFF/OPEN ---- DOH DC110 5W ---- DCSSEP NA SGSSMVSWG ---- ---- ---- ○ ---- ○ ----
PULSE
SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) CB CLOSE NO
24 RD00 BBB 10 YB 32 30 OG TO SSST (52HC-4) CB CLS CMD OFF/CLOSE ---- DOH DC110 5W ---- DCSSEP NA SGSSMVSWG ---- ---- ---- ○ ---- ○ ----
COMMAND PULSE

25 RD00 BBB 10 XG 31 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) TRIP INDICATION 24 OG TO SSST (52HC-4) TRIP OFF/TRIP ---- DI ---- ---- NC ---- SGSSMVSWG NA DCSSEP ---- ---- P1 ---- ---- ○ ----

26 RD00 BBB 10 XG 32 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) TRIP CIRCUIT HEALTHY 32 OG TO SSST (52HC-4) TRP CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- SGSSMVSWG NA DCSSEP ---- ---- P1 ---- ---- ○ ----

27 RD00 BBB 10 XG 33 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) CB REMOTE MODE SELECTED 29 OG TO SSST (52HC-4) CB REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

28 RD00 BBB 10 XG 34 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) CB CLOSE INDICATION 28 OG TO SSST (52HC-4) CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

29 RD00 BBB 10 XG 35 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) ES CLOSE INDICATION 28 OG TO SSST (52HC-4) ES CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

NO
30 RD00 BBB 10 YB 41 SS OUTGOING TO PAD-C RMU (52HD-4) CB OPEN COMMAND 32 OG PAD-C RMU (52HD-4) CB OPN CMD OFF/OPEN ---- DOH DC110 5W ---- DCSSEP NA SGSSMVSWG ---- ---- ---- ○ ---- ○ ----
PULSE
NO
31 RD00 BBB 10 YB 42 SS OUTGOING TO PAD-C RMU (52HD-4) CB CLOSE COMMAND 32 OG PAD-C RMU (52HD-4) CB CLS CMD OFF/CLOSE ---- DOH DC110 5W ---- DCSSEP NA SGSSMVSWG ---- ---- ---- ○ ---- ○ ----
PULSE

32 RD00 BBB 10 XG 41 SS OUTGOING TO PAD-C RMU (52HD-4) TRIP INDICATION 32 OG TO PAD-C RMU (52HD-4) TRP IND OFF/TRIP ---- DI ---- ---- NC ---- SGSSMVSWG NA DCSSEP ---- ---- ○ ---- ---- ○ ----

33 RD00 BBB 10 XG 42 SS OUTGOING TO PAD-C RMU (52HD-4) TRIP CIRCUIT HEALTHY 30 OG PAD-C RMU (52HD-4) CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- SGSSMVSWG NA DCSSEP ---- ---- ○ ---- ---- ○ ----

34 RD00 BBB 10 XG 43 SS OUTGOING TO PAD-C RMU (52HD-4) CB REMOTE MODE SELECTED 31 OG PAD-C RMU (52HD-4) CB REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

35 RD00 BBB 10 XG 44 SS OUTGOING TO PAD-C RMU (52HD-4) CB CLOSE INDICATION 31 OG TO PAD-C RMU (52HD-4) CB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

36 RD00 BBB 10 XG 45 SS OUTGOING TO PAD-C RMU (52HD-4) ES CLOSE INDICATION 31 OG TO PAD-C RMU (52HE-4) ES CLS OPEN/CLOSE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

NO
37 RD00 BBB 10 YB 43 SS SPARE FEEDER CB OPEN COMMAND 23 SPARE FEEDER CB OPN CMD OFF/OPEN ---- DOH DC110 5W ---- DCSSEP NA SGSSMVSWG ---- ---- ---- ○ ---- ○ ----
PULSE
NO
38 RD00 BBB 10 YB 44 SS SPARE FEEDER CB CLOSE COMMAND 23 SPARE FEEDER CB CLS CMD OFF/CLOSE ---- DOH DC110 5W ---- DCSSEP NA SGSSMVSWG ---- ---- ---- ○ ---- ○ ----
PULSE

39 RD00 BBB 10 XG 46 SS SPARE FEEDER TRIP INDICATION 17 SPARE FEEDER TRIP OFF/TRIP ---- DI ---- ---- NC ---- SGSSMVSWG NA DCSSEP ---- ---- P1 ---- ---- ○ ----

40 RD00 BBB 10 XG 47 SS SPARE FEEDER TRIP CIRCUIT HEALTHY 21 SPARE FEEDER CIRC HTY HEALTHY/FAULT ---- DI ---- ---- NC ---- SGSSMVSWG NA DCSSEP ---- ---- P1 ---- ---- ○ ----

41 RD00 BBB 10 XG 48 SS SPARE FEEDER CB REMOTE MODE SELECTED 22 SPARE FEEDER CB REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

42 RD00 BBB 10 XG 49 SS SPARE FEEDER CB CLOSE INDICATION 21 SPARE FEEDER CB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

43 RD00 BBB 10 XG 50 SS SPARE FEEDER ES CLOSE INDICATION 21 SPARE FEEDER ES CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ ---- ---- ---- ○ ----

50 RD00 BFV 10 XG 01 SS SEPARATOR STATION TRANSFORMER OIL TEMPERATURE ALARM 26 SSST OIL TEMPERATURE ALARM NORMAL/HIGH ---- DI ---- ---- NO ---- RD-SSTR U0-ARS-E DCSSEP ---- ---- P2 ---- ---- ○ ----

51 RD00 BFV 10 XG 02 SS SEPARATOR STATION TRANSFORMER OIL TEMPERATURE TRIP 25 SSST OIL TEMPERATURE TRIP OFF/TRIP ---- DI ---- ---- NO ---- RD-SSTR U0-ARS-E DCSSEP ---- ---- P1 ---- ---- ○ ○

52 RD00 BFV 10 XG 03 SS SEPARATOR STATION TRANSFORMER WINDING TEMPERATURE ALARM 30 SSST WINDING TEMPERATURE ALARM NORMAL/HIGH ---- DI ---- ---- NO ---- RD-SSTR U0-ARS-E DCSSEP ---- ---- P2 ---- ---- ○ ----

53 RD00 BFV 10 XG 04 SS SEPARATOR STATION TRANSFORMER WINDING TEMPERATURE TRIP 29 SSST WINDING TEMPERATURE TRIP OFF/TRIP ---- DI ---- ---- NO ---- RD-SSTR U0-ARS-E DCSSEP ---- ---- P1 ---- ---- ○ ○

54 RD00 BFV 10 XG 05 SS SEPARATOR STATION TRANSFORMER OIL LEVEL 14 SSST OIL LEVEL NORMAL/LOW ---- DI ---- ---- NO ---- RD-SSTR U0-ARS-E DCSSEP ---- ---- P1 ---- ---- ○ ○

55 RD00 BFV 10 XG 06 SS SEPARATOR STATION TRANSFORMER PRESSURE RELIEF DEVICE 27 SSST PRESSURE RELIEF DEVICE NORMAL/ALARM ---- DI ---- ---- NO ---- RD-SSTR U0-ARS-E DCSSEP ---- ---- P1 ---- ---- ○ ○

56 RD00 BFC 10 XG 01 SS INCOMING FROM COMMON STATION TRANSFORMER (52L-4) MCCB CLOSE INDICATION 29 IC FROM ST (52L-4) MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

57 RD00 BFC 10 XG 02 SS INCOMING FROM COMMON STATION TRANSFORMER (52L-4)TRIP INDICATION 23 IC FROM ST (52L-4) TRIP OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ---- P1 ---- ---- ○ ----

58 RD00 BFC 10 XG 11 SS MOV 1 - BRINE FROM HP SEPARATOR (1) MCCB CLOSE INDICATION 32 MOV1 BRIN FROM HPSEP(1) MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

59 RD00 BFC 10 XG 12 SS MOV 1 - BRINE FROM HP SEPARATOR (1) MCCB TRIP INDICATION 32 MOV1 BRIN FROM HPSEP(1) MCCB TRP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

60 RD00 BFC 10 XG 13 SS MOV 2 - BRINE FROM HP SEPARATOR (2) MCCB CLOSE INDICATION 32 MOV2 BRIN FROM HPSEP(2) MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

61 RD00 BFC 10 XG 14 SS MOV 2 - BRINE FROM HP SEPARATOR (2) MCCB TRIP INDICATION 32 MOV2 BRIN FROM HPSEP(2) MCCB TRP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

62 RD00 BFC 10 XG 15 SS MOV 1 - BRINE FROM LP SEPARATOR (1) MCCB CLOSE INDICATION 32 MOV1 BRIN FROM LPSEP(1) MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

63 RD00 BFC 10 XG 16 SS MOV 1 - BRINE FROM LP SEPARATOR (1) MCCB TRIP INDICATION 32 MOV1 BRIN FROM LPSEP(1) MCCB TRP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-3.SEPARATOR & WELLPAD-E AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
64 RD00 BFC 10 XG 17 SS MOV 2 - BRINE FROM LP SEPARATOR (2) MCCB CLOSE INDICATION 32 MOV2 BRIN FROM LPSEP(2) MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

65 RD00 BFC 10 XG 18 SS MOV 2 - BRINE FROM LP SEPARATOR (2) MCCB TRIP INDICATION 32 MOV2 BRIN FROM LPSEP(2) MCCB TRP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

66 RD00 BFC 10 XG 19 SS MOV 3 - BRINE TO LP SEPARATOR MCCB CLOSE INDICATION 30 MOV3 BRINE TO LPSEP MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

67 RD00 BFC 10 XG 20 SS MOV 3 - BRINE TO LP SEPARATOR MCCB TRIP INDICATION 29 MOV3 BRINE TO LPSEP MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

68 RD00 BFC 10 XG 21 SS MOV 4 - BRINE BYPASS LP SEPARATOR MCCB CLOSE INDICATION 32 MOV3 BRIN BYPASS LPSEP MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

69 RD00 BFC 10 XG 22 SS MOV 4 - BRINE BYPASS LP SEPARATOR MCCB TRIP INDICATION 32 MOV3 BRIN BYPASS LPSEP MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

70 RD00 BFC 10 XG 23 SS MOV 1 - BRINE FROM LP SEPARATOR(LP WELLS) MCCB CLOSE INDICATION 32 MOV1 BRIN FRM HPSEP(LW) MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

71 RD00 BFC 10 XG 24 SS MOV 1 - BRINE FROM LP SEPARATOR(LP WELLS) MCCB TRIP INDICATION 32 MOV1 BRIN FRM HPSEP(LW) MCCB TRP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

72 RD00 BFC 10 XG 25 SS MOV 2 - BRINE FROM LP SEPARATOR(LP WELLS) MCCB CLOSE INDICATION 32 MOV2 BRIN FRM HPSEP(LW) MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

73 RD00 BFC 10 XG 26 SS MOV 2 - BRINE FROM LP SEPARATOR(LP WELLS) MCCB TRIP INDICATION 32 MOV2 BRIN FRM HPSEP(LW) MCCB TRP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

74 RD00 BFC 10 XG 27 LIGHTING PANEL SEPARATOR STATION(5kVA) CLOSE INDICATION 31 SEP LIGHTING PANEL (5kVA) CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

75 RD00 BFC 10 XG 28 LIGHTING PANEL SEPARATOR STATION(5kVA) TRIP INDICATION 30 SEP LIGHTING PANEL (5kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

76 RD00 BFC 10 XG 29 SS DC UPS PAD RD MCCB CLOSE INDICATION 24 DC UPS PAD RD MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

77 RD00 BFC 10 XG 30 SS DC UPS PAD RD MCCB TRIP INDICATION 23 DC UPS PAD RD MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

78 RD00 BFC 10 XG 31 SS BACKUP DC UPS PAD RD MCCB CLOSE INDICATION 31 BACKUP DC UPS PAD RD MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

79 RD00 BFC 10 XG 32 SS BACKUP DC UPS PAD RD MCCB TRIP INDICATION 30 BACKUP DC UPS PAD RD MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

80 RD00 BFC 10 XG 33 LIGHTING PANEL WELLPAD E(5kVA) CLOSE INDICATION 32 PADE LIGHTING PANEL (5kVA) CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

81 RD00 BFC 10 XG 34 LIGHTING PANEL WELLPAD E(5kVA) TRIP INDICATION 31 PADE LIGHTING PANEL (5kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

NO
435 RD00 GAC 15 AP 001 YB 01 Separator Area Back up Cooling Water Pump Start 21 Back up CW Pump Start OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A45 ---- ---- ○ ---- ○ ----
PULSE
NC
436 RD00 GAC 15 AP 001 YB 02 Separator Area Back up Cooling Water Pump Stop 21 Back up C W Pump Stop OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A45 ---- ---- ○ ---- ○ ----
PULSE

437 RD00 GAC 15 AP 001 XG 01 Separator Area Back up Cooling Water Pump Running Indication 20 Back up C W Pump Run STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP A45 ○ ---- ○ ---- ○ ----

438 RD00 GAC 15 AP 001 XG 02 Separator Area Back up Cooling Water Pump Remote Mode Selected 22 Back up CW Pump Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP A45 ---- ---- ---- ---- ○ ----

439 RD00 GAC 15 AP 001 XG 03 Separator Area Back up Cooling Water Pump Trip Indication 20 Back up CW Pump Trip OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP A45 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

440 RD00 GAC 15 AP 001 XG 04 Separator Area Back up Cooling Water Pump Rack-in Position 32 Back up CW Pump Rack-in Position OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP A45 ○ ---- ---- ---- ○ ----

82 RD00 BFC 10 XG 63 SS SPARE FEEDER (5.0 kVA) MCCB CLOSE INDICATION 31 SPARE FEEDER (5.0 kVA) MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

83 RD00 BFC 10 XG 35 SS SPARE FEEDER (5.0 kVA) MCCB TRIP INDICATION 32 SPARE FEEDER (5.0 kVA) MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

NO
84 RD00 BFC 10 XG 36 SS SPARE MOTOR STARTER (1.5 kW) START COMMAND 31 SPR MTR STRTR (1.5 kW) STRT CMD OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB ---- ---- ---- ○ ---- ○ ----
PULSE
NC
85 RD00 BFC 10 XG 37 SS SPARE MOTOR STARTER (1.5 kW) STOP COMMAND 32 SPARE MTR STRTR (1.5 kW) STP CMD OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB ---- ---- ---- ○ ---- ○ ----
PULSE

86 RD00 BFC 10 XG 38 SS SPARE MOTOR STARTER (1.5 kW) RUNNING INDICATION 32 SPARE MTR STRTR (1.5 kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

87 RD00 BFC 10 XG 39 SS SPARE MOTOR STARTER (1.5 kW) REMOTE MODE SELECTED 31 SPARE MTR STRTR (1.5 kW) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

88 RD00 BFC 10 XG 40 SS SPARE MOTOR STARTER (1.5 kW) TRIP NDICATION 31 SPARE MTR STARTER (1.5 kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ---- P1 ---- ---- ○ ----

89 RD00 BFC 10 XG 41 SS SPARE MOTOR STARTER (1.5 kW) SPARE 32 SPARE MTR STARTER (1.5 kW) SPARE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

NO
90 RD00 BFC 10 XG 42 SS SPARE MOTOR STARTER (5.5 kW) START COMMAND 32 SPR MTR STRTR (5.5 kW) START CMD OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB ---- ---- ---- ○ ---- ○ ----
PULSE
NC
91 RD00 BFC 10 XG 43 SS SPARE MOTOR STARTER (5.5 kW) STOP COMMAND 32 SPARE MTR STRTR (5.5 kW) STP CMD OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB ---- ---- ---- ○ ---- ○ ----
PULSE

92 RD00 BFC 10 XG 44 SS SPARE MOTOR STARTER (5.5 kW) RUNNING INDICATION 32 SPARE MTR STRTR (5.5 kW) RUNNING STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

93 RD00 BFC 10 XG 45 SS SPARE MOTOR STARTER (5.5 kW) REMOTE MODE SELECTED 31 SPARE MTR STRTR (5.5 kW) REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

94 RD00 BFC 10 XG 46 SS SPARE MOTOR STARTER (5.5 kW) TRIP NDICATION 31 SPARE MTR STARTER (5.5 kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB NA DCSSEP ---- ---- P1 ---- ---- ○ ----

95 RD00 BFC 10 XG 47 SS SPARE MOTOR STARTER (5.5 kW) SPARE 32 SPARE MTR STARTER (5.5 kW) SPARE ---- DI ---- ---- NO ---- RD-SSLVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

98 RD00 BFC 10 XG 48 PAD-E MOV 1 - BRINE REINJECTION MCCB CLOSE INDICATION 32 PADE MOV1 BRIN REINJCTN MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

99 RD00 BFC 10 XG 49 PAD-E MOV 1 - BRINE REINJECTION MCCB TRIP INDICATION 32 PADE MOV1 BRIN REINJCTN MCCB TRP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-ELVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

100 RD00 BFC 10 XG 50 SEPARATOR STATION POWER OUTLET (20kVA) CLOSE INDICATION 30 SEP POWER OUTLET (20kVA) CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

101 RD00 BFC 10 XG 51 SEPARATOR STATION POWER OUTLET (20kVA) TRIP INDICATION 29 SEP POWER OUTLET (20kVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-ELVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

102 RD00 BFC 10 XG 52 WELLPAD E POWER OUTLET MCCB CLOSE INDICATION 28 PADE POWER OUTLET MCCB CLOSE OPEN/CLOSE ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

103 RD00 BFC 10 XG 53 WELLPAD E TO POWER OUTLET TRIP INDICATION 25 PADE TO POWER OUTLET TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-ELVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

104 RD00 BFC 10 XG 54 SS SPARE FEEDER (5.0 kVA) MCCB CLOSE INDICATION 31 SPARE FEEDER (5.0 kVA) MCCB CLS OPEN/CLOSE ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

105 RD00 BFC 10 XG 55 SS SPARE FEEDER (5.0 kVA) MCCB TRIP INDICATION 32 SPARE FEEDER (5.0 kVA) MCCB TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

NO
106 RD00 BFC 10 XG 56 SS SPARE MOTOR STARTER (22 kW) START COMMAND 32 SPARE MTR STRTR (22 kW) STRT CMD OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-ELVPDB ---- ○ ---- ---- ---- ○ ----
PULSE
NC
107 RD00 BFC 10 XG 57 SS SPARE MOTOR STARTER (22 kW) STOP COMMAND 32 SPARE MTR STRTR (22 kW) STOP CMD OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-ELVPDB ---- ○ ---- ---- ---- ○ ----
PULSE

108 RD00 BFC 10 XG 58 SS SPARE MOTOR STARTER (22 kW) RUNNING INDICATION 31 SPARE MTR STRTR (22 kW) RUNNING LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

109 RD00 BFC 10 XG 59 SS SPARE MOTOR STARTER (22 kW) REMOTE MODE SELECTED 30 SPARE MTR STRTR (22 kW) REMOTE STOP/RUN ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-3.SEPARATOR & WELLPAD-E AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
110 RD00 BFC 10 XG 60 SS SPARE MOTOR STARTER (22 kW) TRIP NDICATION 28 SPARE MTR STRTR (22 kW) TRIP OFF/TRIP ---- DI ---- ---- NC ---- RD-ELVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

111 RD00 BFC 10 XG 61 SS SPARE MOTOR STARTER (22 kW) RACK IN INDICATION 31 SPARE MTR STRTR (22 kW) RACK-IN OFF/ON ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----

112 RD00 BFC 10 XG 62 SS SPARE MOTOR STARTER (22 kW) CURRENT 31 SPARE MTR STRTR (22 kW) CURRENT 0-100 A AIX ---- ---- ---- ---- RD-ELVPDB NA DCSSEP ---- ○ ---- ---- ---- ○ ----
NO
113 RD00 HAN 10 AP 001 YB 01 WELLPAD E POND REINJECTION PUMP START COMMAND 32 PADE POND REINJCTN PUMP STRT CMD OFF/START ---- DOH DC110 5W
PULSE
---- DCSSEP NA RD-ELVPDB REK ○ ---- ○ ---- ○ ----
NC
114 RD00 HAN 10 AP 001 YB 02 WELLPAD E POND REINJECTION PUMP STOP COMMAND 32 PADE POND REINJCTN PUMP STOP CMD OFF/STOP ---- DOH DC110 5W
PULSE
---- DCSSEP NA RD-ELVPDB REK ○ ---- ○ ---- ○ ----

115 RD00 HAN 10 AP 001 XG 01 WELLPAD E POND REINJECTION PUMP - REMOTE INDICATION 30 PADE POND REINJCTN PUMP REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP REK ○ ---- ---- ---- ○ ----

116 RD00 HAN 10 AP 001 XG 02 WELLPAD E POND REINJECTION PUMP - RUNNING INDICATION 31 PADE POND REINJCTN PUMP RUNNING STOP/RUN ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP REK ○ P1 ---- ---- ○ ----

117 RD00 HAN 10 AP 001 XG 03 WELLPAD E POND REINJECTION PUMP - TRIP INDICATION 31 PADE POND REINJECTION PUMP TRIP OFF/TRIP ---- DI ---- ---- NC ---- RD-ELVPDB NA DCSSEP REK ○ ---- ---- ---- ○ ----

118 RD00 HAN 10 AP 001 XG 04 WELLPAD E POND REINJECTION PUMP - RACK IN INDICATION 31 PADE POND REINJCTN PUMP RACK-IN OFF/ON ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP REK ○ ---- ---- ---- ○ ----

119 RD00 HAN 10 AP 001 XQ 01 WELLPAD E POND REINJECTION PUMP - CURRENT 30 PADE POND REINJCTN PMP CURRENT 0-100 A AIX ---- ---- ---- ---- RD-ELVPDB NA DCSSEP REK ○ ---- ---- ---- ○ ----
NO
120 RD00 QCM 21 AP 001 YB 01 Primary Acid Dosing Pump (A) Start Command 32 Prim Acid Dos PUMP (A) START CMD OFF/START ---- DOH DC110 50W ---- DCSSEP NA VSD A01 ---- ---- ○ ---- ○ ----
PULSE
NC
121 RD00 QCM 21 AP 001 YB 02 Primary Acid Dosing Pump (A) Stop Command 31 Prim Acid Dos Pump (A) Stop CMD OFF/STOP ---- DOH DC110 50W ---- DCSSEP NA VSD A01 ---- ---- ○ ---- ○ ----
PULSE

122 RD00 QCM 21 AP 001 XG 01 Primary Acid Dosing Pump (A) Running Indication 32 Primary Acid Dos Pmp (A) Running STOP/RUN ---- DI ---- ---- NO ---- VSD NA DCSSEP A01 ○ ---- ○ ---- ○ ----

123 RD00 QCM 21 AP 001 XG 02 Primary Acid Dosing Pump (A) Remote Mode Selected 32 Primary Acid Dos Pump (A) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- VSD NA DCSSEP A01 ---- ---- ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

124 RD00 QCM 21 AP 001 XG 03 Primary Acid Dosing Pump (A) Inverter Fault 32 Prim Acid Dos Pmp (A) Invert FLT OFF/TRIP ---- DI ---- ---- NC ---- VSD NA DCSSEP A01 ○ P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

125 RD00 QCM 21 AP 001 XG 04 Primary Acid Dosing Pump (A) Rack-in Position 30 Prim Acid Dos Pump (A) Rack-in OFF/ON ---- DI ---- ---- NO ---- VSD NA DCSSEP ---- ○ ---- ---- ---- ○ ---- Rev.4 Deleted 4

NO
126 RD00 QCM 21 AP 002 YB 01 Primary Acid Dosing Pump (B) Start Command 32 Prim Acid Dos Pump (B) Start Cmd OFF/START ---- DOH DC110 50W ---- DCSSEP NA VSD A02 ---- ---- ○ ---- ○ ----
PULSE
NC
127 RD00 QCM 21 AP 002 YB 02 Primary Acid Dosing Pump (B) Stop Command 31 Prim Acid Dos Pump (B) Stop Cmd OFF/STOP ---- DOH DC110 50W ---- DCSSEP NA VSD A02 ---- ---- ○ ---- ○ ----
PULSE

128 RD00 QCM 21 AP 002 XG 01 Primary Acid Dosing Pump (B) Running Indication 32 Primary Acid Dos Pmp (B) Running STOP/RUN ---- DI ---- ---- NO ---- VSD NA DCSSEP A02 ○ ---- ○ ---- ○ ----

129 RD00 QCM 21 AP 002 XG 02 Primary Acid Dosing Pump (B) Remote Mode Selected 32 Primary Acid Dos Pump (B) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- VSD NA DCSSEP A02 ---- ---- ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

130 RD00 QCM 21 AP 002 XG 03 Primary Acid Dosing Pump (B) Inverter Fault 32 Prim Acid Dos Pmp (B) Invert Flt OFF/TRIP ---- DI ---- ---- NC ---- VSD NA DCSSEP A02 ○ P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

131 RD00 QCM 21 AP 002 XG 04 Primary Acid Dosing Pump (B) Rack-in Position 32 Primary Acid Dos Pmp (B) Rack-in OFF/ON ---- DI ---- ---- NO ---- VSD NA DCSSEP ---- ○ ---- ---- ---- ○ ---- Rev.4 Deleted 4

NO
132 RD00 HHU 12 AP 001 YB 01 HP Dilution Brine Pump (A) Start Command 32 HP Dilution Bri Pmp (A) Strt Cmd OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A03 ---- ---- ○ ---- ○ ----
PULSE
NC
133 RD00 HHU 12 AP 001 YB 02 HP Dilution Brine Pump (A) Stop Command 32 HP Dilution Brin Pmp (A) Stp Cmd OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A03 ---- ---- ○ ---- ○ ----
PULSE

134 RD00 HHU 12 AP 001 XG 01 HP Dilution Brine Pump (A) Running Indication 32 HP Dilution Brin Pmp (A) Running STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A03 ○ ---- ○ ---- ○ ----

135 RD00 HHU 12 AP 001 XG 02 HP Dilution Brine Pump (A) Remote Mode Selected 32 HP Dilution Brine Pmp (A) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A03 ---- ---- ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

136 RD00 HHU 12 AP 001 XG 03 HP Dilution Brine Pump (A) Trip Indication 31 HP Dilution Brine Pump (A) Trip OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB U0-ARS-E DCSSEP A03 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

137 RD00 HHU 12 AP 001 XG 04 HP Dilution Brine Pump (A) Rack-in Position 32 HP Dilution Brin Pmp (A) Rack-in OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A03 ○ ---- ---- ---- ○ ----

NO
138 RD00 HHU 12 AP 002 YB 01 HP Dilution Brine Pump (B) Start Command 32 HP Dilution Bri Pmp (B) Strt Cmd OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A04 ---- ---- ○ ---- ○ ----
PULSE
NC
139 RD00 HHU 12 AP 002 YB 02 HP Dilution Brine Pump (B) Stop Command 32 HP Dilution Brin Pmp (B) Stp Cmd OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A04 ---- ---- ○ ---- ○ ----
PULSE

140 RD00 HHU 12 AP 002 XG 01 HP Dilution Brine Pump (B) Running Indication 32 HP Dilution Brin Pmp (B) Running STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A04 ○ ---- ○ ---- ○ ----

141 RD01 HHU 12 AP 002 XG 02 HP Dilution Brine Pump (B) Remode Mode Selected 32 HP Dilution Brine Pmp (B) Remode LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A04 ---- ---- ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

142 RD00 HHU 12 AP 002 XG 03 HP Dilution Brine Pump (B) Trip Indication 31 HP Dilution Brine Pump (B) Trip OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB U0-ARS-E DCSSEP A04 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

143 RD00 HHU 12 AP 002 XG 04 HP Dilution Brine Pump (B) Rack-in Position 32 HP Dilution Brin Pmp (B) Rack-in OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A04 ○ ---- ---- ---- ○ ----

NO
144 RD00 QCM 11 AP 001 YB 01 Motor for Acid dosing unloading pump (A) Start 32 Acid Dos unload pmp (A) Strt Cmd OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A11 ---- ---- ○ ---- ○ ----
PULSE
NC
145 RD00 QCM 11 AP 001 YB 02 Motor for Acid dosing unloading pump (A) Stop 32 Acid Dos unload pmp (A) Stop Cmd OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A11 ---- ---- ○ ---- ○ ----
PULSE

146 RD00 QCM 11 AP 001 XG 01 Motor for Acid dosing unloading pump (A) Running Indication 32 Acid Dos unload pump (A) Running STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A11 ○ ---- ○ ---- ○ ----

147 RD00 QCM 11 AP 001 XG 02 Motor for Acid dosing unloading pump (A) Remote Mode Selected 31 Acid Dos unload pump (A) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A11 ---- ---- ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

148 RD00 QCM 11 AP 001 XG 03 Motor for Acid dosing unloading pump (A) Trip Indication 32 Acid Dos unloading pump (A) Trip OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB U0-ARS-E DCSSEP A11 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

149 RD00 QCM 11 AP 001 XG 04 Motor for Acid dosing unloading pump (A) Rack-in Position 32 Acid Dos unload pump (A) Rack-in OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A11 ○ ---- ---- ---- ○ ----

NO
150 RD00 HHU 12 AC 001 YB 01 Acid Dilution HP Brine Air Cooler (A) Start 32 Acid Diltn HPBrin CL (A) Strt Cm OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A07 ---- ---- ○ ---- ○ ----
PULSE
NC
151 RD00 HHU 12 AC 001 YB 02 Acid Dilution HP Brine Air Cooler (A) Stop 32 Acid Diltn HPBrin CL (A) Stp Cmd OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A07 ---- ---- ○ ---- ○ ----
PULSE

152 RD00 HHU 12 AC 001 XG 01 Acid Dilution HP Brine Air Cooler (A) Running Indication 32 Acid Diltn HPBrin CL (A) Running STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A07 ○ ---- ---- ---- ○ ----

153 RD00 HHU 12 AC 001 XG 02 Acid Dilution HP Brine Air Cooler (A) Remote Mode Selected 31 Acid Diltn HPBrin CL (A) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A07 ---- ---- ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

154 RD00 HHU 12 AC 001 XG 03 Acid Dilution HP Brine Air Cooler (A) Trip Indication 31 Acid Diltn HP Brine CL (A) Trip OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB U0-ARS-E DCSSEP A07 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

155 RD00 HHU 12 AC 001 XG 04 Acid Dilution HP Brine Air Cooler (A) Raclk-in Position 32 Acid Diltn HPBrin CL (A) Rack-in OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A07 ○ ---- ---- ---- ○ ----

NO
156 RD00 HHU 12 AC 002 YB 01 Acid Dilution HP Brine Air Cooler (B) Start 32 Acid Diltn HPBrin CL (B) Strt Cm OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A08 ---- ---- ○ ---- ○ ----
PULSE
NC
157 RD00 HHU 12 AC 002 YB 02 Acid Dilution HP Brine Air Cooler (B) Stop 32 Acid Diltn HPBrin CL (B) Stp Cmd OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A08 ---- ---- ○ ---- ○ ----
PULSE

158 RD00 HHU 12 AC 002 XG 01 Acid Dilution HP Brine Air Cooler (B) Running Indication 32 Acid Diltn HPBrin CL (B) Running STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A08 ○ ---- ---- ---- ○ ----

159 RD00 HHU 12 AC 002 XG 02 Acid Dilution HP Brine Air Cooler (B) Remote Mode Selected 31 Acid Diltn HPBrin CL (B) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A08 ---- ---- ---- ---- ○ ---- Rev.4a ANN level is corrected 4a
2.DCS IO LIST FOR HARD WIRE
2-3.SEPARATOR & WELLPAD-E AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
160 RD00 HHU 12 AC 002 XG 03 Acid Dilution HP Brine Air Cooler (B) Trip Indication 31 Acid Diltn HP Brine CL (B) Trip OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB U0-ARS-E DCSSEP A08 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

161 RD00 HHU 12 AC 002 XG 04 Acid Dilution HP Brine Air Cooler (B) Raclk-in Position 32 Acid Diltn HPBrin CL (B) Rack-in OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A08 ○ ---- ---- ---- ○ ----

NO
162 RD00 QCM 21 FH 101 YB 01 Primary Acid Dosing Pump (A) Discharge Valve Open Command 32 PRIME ACID INLET VLV(A) OPEN CMD CLOSE/OPEN ---- DOW DC110 10W ---- DCSSEP U0-ARS-E F A09 ---- ---- ○ ---- ○ ----
LATCH

163 RD00 QCM 21 CG 081 XG 01 Primary Acid Dosing Pump (A) Discharge Valve Open 29 Prim Acid Pmp(A) Dscg Vlv Opn OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A09 ○ ---- ○ ---- ○ ----

164 RD00 QCM 21 CG 082 XG 02 Primary Acid Dosing Pump (A) Discharge Valve Close 29 Prim Acid Pmp(A) Dscg Vlv Opn OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A09 ○ ---- ○ ○ ○ ----

NO
165 RD00 QCM 21 FH 102 YB 01 Primary Acid Dosing Pump (B) Discharge Valve Open Command 31 PRIME ACID INLET VLV(B) OPN CMD CLOSE/OPEN ---- DOW DC110 10W ---- DCSSEP U0-ARS-E F A10 ---- ---- ○ ---- ○ ----
LATCH

166 RD00 QCM 21 CG 083 XG 01 Primary Acid Dosing Pump (B) Discharge Valve Open 29 Prim Acid Pmp(B) Dscg Vlv Opn OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A10 ○ ---- ○ ---- ○ ----

167 RD00 QCM 21 CG 084 XG 02 Primary Acid Dosing Pump (B) Discharge Valve Close 29 Prim Acid Pmp(B) Dscg Vlv Opn OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A10 ○ ---- ○ ---- ○ ----

NO
168 RD00 QCM 31 AP 001 YB 01 Secondary Acid Dosing Pump (A) Start Command 32 Secon Acid Dos Pump (A) Strt Cmd OFF/START ---- DOH DC110 50W ---- DCSSEP NA VSD A21 ---- ---- ○ ---- ○ ----
PULSE
NC
169 RD00 QCM 31 AP 001 YB 02 Secondary Acid Dosing Pump (A) Stop Command 32 Secon Acid Dos Pump (A) Stop Cmd OFF/STOP ---- DOH DC110 50W ---- DCSSEP NA VSD A21 ---- ---- ○ ---- ○ ----
PULSE

170 RD00 QCM 31 AP 001 XG 01 Secondary Acid Dosing Pump (A) Running Indication 31 Secon Acid Dos Pump (A) Running STOP/RUN ---- DI ---- ---- NO ---- VSD NA DCSSEP A21 ---- ---- ○ ---- ○ ----

171 RD00 QCM 31 AP 001 XG 02 Secondary Acid Dosing Pump (A) Remote Mode Selected 30 Secon Acid Dos Pump (A) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- VSD NA DCSSEP A21 ○ ---- ---- ---- ○ ----

172 RD00 QCM 31 AP 001 XG 03 Secondary Acid Dosing Pump (A) Inverter Fault 32 Secon Acid Dos Pmp (A) Invrt Flt OFF/TRIP ---- DI ---- ---- NC ---- VSD NA DCSSEP A21 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

173 RD00 QCM 31 AP 001 XG 04 Secondary Acid Dosing Pump (A) Rack-in Position 31 Secon Acid Dos Pump (A) Rack-in OFF/ON ---- DI ---- ---- NO ---- VSD NA DCSSEP ---- ○ ---- ---- ---- ○ ---- Rev.4 Deleted 4

NO
174 RD00 QCM 31 AP 002 YB 01 Secondary Acid Dosing Pump (B) Start Command 32 Secon Acid Dos Pump (B) Strt Cmd OFF/START ---- DOH DC110 50W ---- DCSSEP NA VSD A22 ---- ---- ○ ---- ○ ----
PULSE
NC
175 RD00 QCM 31 AP 002 YB 02 Secondary Acid Dosing Pump (B) Stop Command 32 Secon Acid Dos Pump (B) Stop Cmd OFF/STOP ---- DOH DC110 50W ---- DCSSEP NA VSD A22 ---- ---- ○ ---- ○ ----
PULSE

176 RD00 QCM 31 AP 002 XG 01 Secondary Acid Dosing Pump (B) Running Indication 31 Secon Acid Dos Pump (B) Running STOP/RUN ---- DI ---- ---- NO ---- VSD NA DCSSEP A22 ---- ---- ○ ---- ○ ----

177 RD00 QCM 31 AP 002 XG 02 Secondary Acid Dosing Pump (B) Remote Mode Selected 30 Secon Acid Dos Pump (B) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- VSD NA DCSSEP A22 ○ ---- ---- ---- ○ ----

178 RD00 QCM 31 AP 002 XG 03 Secondary Acid Dosing Pump (B) Inverter Fault 32 Secon Acid Dos Pmp (B) Invrt Flt OFF/TRIP ---- DI ---- ---- NC ---- VSD NA DCSSEP A22 ---- P1 ---- ---- ○ ---- Rev.4a ANN level is corrected 4a

179 RD00 QCM 31 AP 002 XG 04 Secondary Acid Dosing Pump (B) Rack-in Position 31 Secon Acid Dos Pump (B) Rack-in OFF/ON ---- DI ---- ---- NO ---- VSD NA DCSSEP A22 ○ ---- ---- ---- ○ ---- Rev.4 Deleted 4

NO
180 RD00 HHU 22 AP 001 YB 01 LP Dilution Brine Pump (A) Start 32 LP Dilution Brine Pump (A) Start OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A23 ---- ---- ○ ---- ○ ----
PULSE
NC
181 RD00 HHU 22 AP 001 YB 02 LP Dilution Brine Pump (A) Stop 31 LP Dilution Brine Pump (A) Stop OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A23 ---- ---- ○ ---- ○ ----
PULSE

182 RD00 HHU 22 AP 001 XG 01 LP Dilution Brine Pump (A) Running Indication 32 LP Dilution Brin Pmp (A) Running STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A23 ○ ---- ○ ---- ○ ----

183 RD00 HHU 22 AP 001 XG 02 LP Dilution Brine Pump (A) Remode Mode Selected 32 LP Dilution Brine Pmp (A) Remode LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A23 ---- ---- ---- ---- ○ ----

184 RD00 HHU 22 AP 001 XG 03 LP Dilution Brine Pump (A) Trip Indication 31 LP Dilution Brine Pump (A) Trip OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB U0-ARS-E DCSSEP A23 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

185 RD00 HHU 22 AP 001 XG 04 LP Dilution Brine Pump (A) Rack-in Position 32 LP Dilution Brin Pmp (A) Rack-in OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP ---- ○ ---- ---- ---- ○ ----

NO
186 RD00 HHU 22 AP 002 YB 01 LP Dilution Brine Pump (B) Start 32 LP Dilution Brine Pump (B) Start OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A24 ---- ---- ○ ---- ○ ----
PULSE
NC
187 RD00 HHU 22 AP 002 YB 02 LP Dilution Brine Pump (B) Stop 31 LP Dilution Brine Pump (B) Stop OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A24 ---- ---- ○ ---- ○ ----
PULSE

188 RD00 HHU 22 AP 002 XG 01 LP Dilution Brine Pump (B) Running Indication 32 LP Dilution Brin Pmp (B) Running STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A24 ○ ---- ○ ---- ○ ----

189 RD00 HHU 22 AP 002 XG 02 LP Dilution Brine Pump (B) Remode Mode Selected 31 LP Dilution Brin Pmp (B) Remode LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A24 ---- ---- ---- ---- ○ ----

190 RD00 HHU 22 AP 002 XG 03 LP Dilution Brine Pump (B) Trip Indication 31 LP Dilution Brine Pump (B) Trip OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB U0-ARS-E DCSSEP A24 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

191 RD00 HHU 22 AP 002 XG 04 LP Dilution Brine Pump (B) Rack-in Position 32 LP Dilution Brin Pmp (B) Rack-in OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A24 ○ ---- ---- ---- ○ ----

NO
192 RD00 QCM 11 AP 002 YB 01 Acid dosing unloading pump (B) Start Command 32 Acid Dos unload pmp (B) Strt Cmd OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A12 ---- ---- ○ ---- ○ ----
PULSE
NC
193 RD00 QCM 11 AP 002 YB 02 Acid dosing unloading pump (B) Stop Command 32 Acid Dos unload pmp (B) Stop Cmd OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A12 ---- ---- ○ ---- ○ ----
PULSE

194 RD00 QCM 11 AP 002 XG 01 Acid dosing unloading pump (B) Running Indication 32 Acid Dos unload pump (B) Running STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A12 ○ ---- ○ ---- ○ ----

195 RD00 QCM 11 AP 002 XG 02 Acid dosing unloading pump (B) Remode Mode Selected 31 Acid Dos unload pump (B) Remote LOCAL/REMOTE ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A12 ---- ---- ---- ---- ○ ----

196 RD00 QCM 11 AP 002 XG 03 Acid dosing unloading pump (B) Trip Indication 32 Acid Dos unloading pump (B) Trip OFF/TRIP ---- DI ---- ---- NC ---- RD-SSLVPDB U0-ARS-E DCSSEP A12 ---- P1 ○ ---- ○ ---- Rev.4a ANN level is corrected 4a

197 RD00 QCM 11 AP 002 XG 04 Acid dosing unloading pump (B) Rack-in Position 32 Acid Dos unload pump (B) Rack-in OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A12 ○ ---- ---- ---- ○ ----

NO
198 RD00 HHU 22 AC 001 YB 01 Acid Dilution LP Brine Air Cooler (A) Start Command 32 Acid Diltn LPBrin CL (A) Strt Cm OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A27 ---- ---- ○ ---- ○ ----
PULSE
NC
199 RD00 HHU 22 AC 001 YB 02 Acid Dilution LP Brine Air Cooler (A) Stop Command 32 Acid Diltn LPBrin CL (A) Stp Cmd OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A27 ---- ---- ○ ---- ○ ----
PULSE

200 RD00 HHU 22 AC 001 XG 01 Acid Dilution LP Brine Air Cooler (A) Running Indication 32 Acid Diltn LPBrin CL (A) Running STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A27 ○ ---- ---- ---- ○ ----

201 RD00 HHU 22 AC 001 XG 02 Acid Dilution LP Brine Air Cooler (A) Trip Indication 31 Acid Diltn LPBrin CL (A) Remote LOCAL/REMOTE ---- DI ---- ---- NC ---- RD-SSLVPDB U0-ARS-E DCSSEP A27 ---- ---- ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

202 RD00 HHU 22 AC 001 XG 03 Acid Dilution LP Brine Air Cooler (A) Remote Mode Selected 31 Acid Diltn LP Brine CL (A) Trip OFF/TRIP ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A26 ---- P1 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

203 RD00 HHU 22 AC 001 XG 04 Acid Dilution LP Brine Air Cooler (A) Raclk-in Position 32 Acid Diltn LPBrin CL (A) Rack-in OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A26 ○ ---- ---- ---- ○ ----

NO
204 RD00 HHU 22 AC 002 YB 01 Acid Dilution LP Brine Air Cooler (B) Start Command 32 Acid Diltn LPBrin CL (B) Strt Cm OFF/START ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A28 ---- ---- ○ ---- ○ ----
PULSE
NC
205 RD00 HHU 22 AC 002 YB 02 Acid Dilution LP Brine Air Cooler (B) Stop Command 32 Acid Diltn LPBrin CL (B) Stp Cmd OFF/STOP ---- DOH DC110 5W ---- DCSSEP NA RD-SSLVPDB A28 ---- ---- ○ ---- ○ ----
PULSE

206 RD00 HHU 22 AC 002 XG 01 Acid Dilution LP Brine Air Cooler (B) Running Indication 32 Acid Diltn LPBrin CL (B) Running STOP/RUN ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A28 ○ ---- ---- ---- ○ ----

207 RD00 HHU 22 AC 002 XG 02 Acid Dilution LP Brine Air Cooler (B) Trip Indication 31 Acid Diltn LPBrin CL (B) Remote LOCAL/REMOTE ---- DI ---- ---- NC ---- RD-SSLVPDB U0-ARS-E DCSSEP A28 ---- ---- ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

208 RD00 HHU 22 AC 002 XG 03 Acid Dilution LP Brine Air Cooler (B) Remote Mode Selected 31 Acid Diltn LP Brine CL (B) Trip OFF/TRIP ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A28 ---- P1 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

209 RD00 HHU 22 AC 002 XG 04 Acid Dilution LP Brine Air Cooler (B) Raclk-in Position 32 Acid Diltn LPBrin CL (B) Rack-in OFF/ON ---- DI ---- ---- NO ---- RD-SSLVPDB U0-ARS-E DCSSEP A28 ○ ---- ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-3.SEPARATOR & WELLPAD-E AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
NO
210 RD00 QCM 31 AA 101 YB 01 Secondary Acid Dosing Pump (A) Discharge Valve Open Command 32 SECOND ACID INLET VLV(A) OPN CMD CLOSE/OPEN ---- DOW DC110 10W ---- DCSSEP U0-ARS-E F A29 ---- ---- ○ ---- ○ ----
LATCH

211 RD00 QCM 31 CG 081 XG 01 Secondary Acid Dosing Pump (A) Discharge Valve Open 30 Secon Acid Dos Sup Inl Vlv Opn OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A29 ○ ---- ○ ---- ○ ----

212 RD00 QCM 31 CG 082 XG 02 Secondary Acid Dosing Pump (A) Discharge Valve Close 30 Secon Acid Dos Sup Inl Vlv Cls OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A29 ---- ---- ○ ---- ○ ---- Rev.4a ANN is not needed 4a

NO
213 RD00 QCM 31 AA 102 YB 01 Secondary Acid Dosing Pump (B) Discharge Valve Open Command 32 SECOND ACID INLET VLV(B) OPN CMD CLOSE/OPEN ---- DOW DC110 10W ---- DCSSEP U0-ARS-E F A30 ---- ---- ○ ---- ○ ----
LATCH

214 RD00 QCM 31 CG 083 XG 01 Secondary Acid Dosing Pump (B) Discharge Valve Open 31 Secon Acid Dos Sup Byps Vlv Opn OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A30 ○ ---- ○ ---- ○ ----

215 RD00 QCM 31 CG 084 XG 02 Secondary Acid Dosing Pump (B) Discharge Valve Close 31 Secon Acid Dos Sup Byps Vlv Cls OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A30 ---- ---- ○ ---- ○ ---- Rev.4a ANN is not needed 4a

5.4 4.3
216 RD00 HHU 11 CQ 001 XQ 01 Primary Acid Dosing PH 22 Primary Acid Dosing PH 0-14 pH AIX ---- ---- ---- 1% PANEL U0-ARS-E DCSSEP C48 ○ H/L ○ ---- ○ ----
(P2) (P2)
5.4 4.3
217 RD00 HHU 11 CQ 002 XQ 01 Primary Acid Dosing PH 22 Primary Acid Dosing PH 0-14 pH AIX ---- ---- ---- 1% PANEL U0-ARS-E DCSSEP C48 ○ H/L ○ ---- ○ ----
(P2) (P2)

478 RD00 HHU 11 CQ 002 XG 01 Primary Acid Dosing PH Cleaning 31 Primary Acid Dosing PH Cleaning OFF/OPEN ---- DI ---- ---- NO ---- PANEL U0-ARS-E DCSSEP C48 ○ ---- ○ ---- ○ ----

NO
447 RD00 HHU 11 AA 701 YB 01 Primary Acid Dosing pH sample Flow Control Valve-1 Open Command 32 Pri Acd Dos pH Smpl FCV-1 Opn Cm CLOSE/OPEN ---- DOW DC110 25W ---- DCSSEP U0-ARS-E F A34 ---- ---- ○ ---- ○ ----
LATCH

448 RD00 HHU 11 CG 091 XG 01 Primary Acid Dosing pH sample Flow Control Valve-1 Open 32 Prim Acid Dos pH Smpl FCV-1 Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A34 ○ ---- ○ ---- ○ ----

449 RD00 HHU 11 CG 092 XG 01 Primary Acid Dosing pH sample Flow Control Valve-1 Close 31 Prim Acid Dos pH Smpl FCV-1 Cls OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A34 ---- ---- ○ ---- ○ ----

NO
450 RD00 HHU 11 AA 702 YB 01 Primary Acid Dosing pH sample Flow Control Valve-2 Open Command 32 Pri Acd Dos pH Smpl FCV-2 Opn Cm CLOSE/OPEN ---- DOW DC110 25W ---- DCSSEP U0-ARS-E F A35 ---- ---- ○ ---- ○ ----
LATCH

451 RD00 HHU 11 CG 093 XG 01 Primary Acid Dosing pH sample Flow Control Valve-2 Open 32 Prim Acid Dos pH Smpl FCV-2 Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A35 ○ ---- ○ ---- ○ ----

452 RD00 HHU 11 CG 094 XG 01 Primary Acid Dosing pH sample Flow Control Valve-2 Close 31 Prim Acid Dos pH Smpl FCV-2 Cls OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A35 ---- ---- ○ ---- ○ ---- Rev.4a ANN is not needed 4a

40
453 RD00 HHU 11 CT 051 XQ 01 Primary Acid Dosing pH sample temperature-1 30 Primary Acid Dos Sample Temp-1 0-200 degC AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R68 ○ H ○ ---- ○ ----
(P1)
24V Power is supplied from pH
454 RD00 HHU 11 CF 011 XQ 01 Primary Acid Dosing pH sample Flow 31 Primary Acid Dos pH sample Flow 0-2 kg/s AII ---- ---- ---- ---- F U0-ARS-E DCSSEP ---- ○ ○ ○ ---- ○ ----
System
5.2 4.5
218 RD00 HHU 21 CQ 003 XQ 01 Secondary Acid Dosing PH 24 Secondary Acid Dosing PH 0-14 pH AIX ---- ---- ---- 1% PANEL U0-ARS-E DCSSEP C49 ○ H/L ○ ---- ○ ----
(P2) (P2)
5.2 4.5
219 RD00 HHU 21 CQ 004 XQ 01 Secondary Acid Dosing PH 24 Secondary Acid Dosing PH 0-14 pH AIX ---- ---- ---- 1% PANEL U0-ARS-E DCSSEP C49 ○ H/L ○ ---- ○ ----
(P2) (P2)

479 RD00 HHU 21 CQ 003 XG 01 Secondary Acid Dosing PH Cleaning 30 Second Acid Dosing PH Cleaning OFF/OPEN ---- DI ---- ---- NO ---- PANEL U0-ARS-E DCSSEP C49 ○ ---- ○ ---- ○ ----

NO
455 RD00 HHU 21 AA 701 YB 01 Secondary Acid Dosing pH sample Flow Control Valve-1 Open Command 32 Secn Acd Dos pH Smpl FCV-1 Op Cm CLOSE/OPEN ---- DOW DC110 25W ---- DCSSEP U0-ARS-E F A36 ---- ---- ○ ---- ○ ----
LATCH

456 RD00 HHU 21 CG 091 XG 01 Secondary Acid Dosing pH sample Flow Control Valve-1 Open 32 Secon Acid Dos pH Smpl FCV-1 Opn OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A36 ○ ---- ○ ---- ○ ----

457 RD00 HHU 21 CG 092 XG 01 Secondary Acid Dosing pH sample Flow Control Valve-1 Close 32 Secon Acid Dos pH Smpl FCV-1 Cls OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A36 ---- ---- ○ ---- ○ ---- Rev.4a ANN is not needed 4a

NO
458 RD00 HHU 21 AA 702 YB 01 Secondary Acid Dosing pH sample Flow Control Valve-2 Open Command 32 Secn Acd Dos pH Smpl FCV-2 Op Cm CLOSE/OPEN ---- DOW DC110 25W ---- DCSSEP U0-ARS-E F A37 ---- ---- ○ ---- ○ ----
LATCH

459 RD00 HHU 21 CG 093 XG 01 Secondary Acid Dosing pH sample Flow Control Valve-2 Open 32 Secon Acid Dos pH Smpl FCV-2 Opn OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A37 ○ ---- ○ ---- ○ ----

460 RD00 HHU 21 CG 094 XG 01 Secondary Acid Dosing pH sample Flow Control Valve-2 Close 32 Secon Acid Dos pH Smpl FCV-2 Cls OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A37 ---- ---- ○ ---- ○ ---- Rev.4a ANN is not needed 4a

40
461 RD00 HHU 21 CT 051 XQ 01 Secondary Acid Dosing pH sample temperature-1 32 Secondary Acid Dos Sample Temp-1 0-200 degC AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R68 ○ H ○ ---- ○ ----
(P1)
24V Power is supplied from pH
462 RD00 HHU 21 CF 011 XQ 01 Secondary Acid Dosing pH sample Flow 31 Secondary Acid Dos pH Smpl Flow 0-2 kg/s AII ---- ---- ---- ---- F U0-ARS-E DCSSEP ---- ○ ○ ○ ---- ○ ----
System
5.2 4.5
426 RD00 HHU 21 CQ 001 XQ 01 LP Brine PH 11 LP Brine PH 0-14 pH AIX ---- ---- ---- 1% PANEL U0-ARS-E DCSSEP C49 ○ H/L ○ ---- ○ ----
(P2) (P2)
5.2 4.5
427 RD00 HHU 21 CQ 002 XQ 01 LP Brine PH 11 LP Brine PH 0-14 pH AIX ---- ---- ---- 1% PANEL U0-ARS-E DCSSEP C49 ○ H/L ○ ---- ○ ----
(P2) (P2)

480 RD00 HHU 21 CQ 002 XG 01 LP Brine PH Cleaning 20 LP Brine PH Cleaning OFF/OPEN ---- DI ---- ---- NO ---- PANEL U0-ARS-E DCSSEP C49 ○ ---- ○ ---- ○ ----

NO
463 RD00 HHU 21 AA 703 YB 01 LP Brine pH sample Flow Control Valve-1 Open Command 32 LP Brine pH Sample FCV-1 Opn Cmd CLOSE/OPEN ---- DOW DC110 25W ---- DCSSEP U0-ARS-E F A38 ---- ---- ○ ---- ○ ----
LATCH

464 RD00 HHU 21 CG 095 XG 01 LP Brine pH sample Flow Control Valve-1 Open 29 LP Brine pH Sample FCV-1 Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A38 ○ ---- ○ ---- ○ ----

465 RD00 HHU 21 CG 096 XG 01 LP Brine pH sample Flow Control Valve-1 Close 30 LP Brine pH Sample FCV-1 Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A38 ---- ---- ○ ---- ○ ---- Rev.4a ANN is not needed 4a

NO
466 RD00 HHU 21 AA 704 YB 01 LP Brine pH sample Flow Control Valve-2 Open Command 32 LP Brine pH Sample FCV-2 Opn Cmd CLOSE/OPEN ---- DOW DC110 25W ---- DCSSEP U0-ARS-E F A39 ---- ---- ○ ---- ○ ----
LATCH

467 RD00 HHU 21 CG 097 XG 01 LP Brine pH sample Flow Control Valve-2 Open 29 LP Brine pH Sample FCV-2 Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A39 ○ ---- ○ ---- ○ ----

468 RD00 HHU 21 CG 098 XG 01 LP Brine pH sample Flow Control Valve-2 Close 30 LP Brine pH Sample FCV-2 Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A39 ---- ---- ○ ---- ○ ---- Rev.4a ANN is not needed 4a

40
469 RD00 HHU 21 CT 052 XQ 01 LP Brine pH sample temperature-1 22 LP Brine Sample Temp-1 0-200 degC AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R68 ○ H ○ ---- ○ ----
(P1)
24V Power is supplied from pH
470 RD00 HHU 21 CF 012 XQ 01 LP Brine pH sample Flow 23 LP Brine pH sample Flow 0-2 kg/s AII ---- ---- ---- ---- F U0-ARS-E DCSSEP ---- ○ ○ ○ ---- ○ ----
System

220 RD00 QCM 21 AP 001 XQ 01 Primary Acid Dosing Pump (A) VSD Position 32 Prim Acid Dosing Pmp (A) VSD Pos 0-1800 rpm AII ---- ---- ---- ---- VSD U0-ARS-E DCSSEP C50 ○ ---- ○ ---- ○ ----

221 RD00 QCM 21 AP 001 YJ 01 Primary Acid Dosing Pump (A) VSD MV 32 Prim Acid Dosing Pump (A) VSD MV 0-1800 rpm AOX ---- ---- ---- ---- DCSSEP U0-ARS-E VSD C50 ---- ---- ○ ---- ○ ----

222 RD00 QCM 21 AP 002 XQ 01 Primary Acid Dosing Pump (B) VSD Position 32 Prim Acid Dosing Pmp (B) VSD Pos 0-1800 rpm AII ---- ---- ---- ---- VSD U0-ARS-E DCSSEP C50 ○ ---- ○ ---- ○ ----

223 RD00 QCM 21 AP 002 YJ 01 Primary Acid Dosing Pump (B) VSD MV 32 Prim Acid Dosing Pump (B) VSD MV 0-1800 rpm AOX ---- ---- ---- ---- DCSSEP U0-ARS-E VSD C50 ---- ---- ○ ---- ○ ----

224 RD00 HHU 12 CG 101 XQ 01 Primary Acid Dosing Brine Dilution Valve Position 31 Pri Acid Dos Brin Diltn Vlv Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C52 ---- ---- ○ ---- ○ ----

225 RD00 HHU 12 FH 101 YJ 01 Primary Acid Dosing Brine Dilution Valve MV 31 Pri Acd Dos Brin Diltn Valve MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C52 ○ H ○ ---- ○ ----

226 RD00 QCM 31 AP 001 XQ 01 Secondary Acid Dosing Pump (A) VSD Position 31 Secon Acid Dos Pump (A) VSD Pos 0-1800 rpm AII ---- ---- ---- ---- VSD U0-ARS-E DCSSEP C55 ○ ---- ○ ---- ○ ----

227 RD00 QCM 31 AP 001 YJ 01 Secondary Acid Dosing Pump (A) VSD MV 30 Secon Acid Dos Pump (A) VSD MV 0-1800 rpm AOX ---- ---- ---- ---- DCSSEP U0-ARS-E VSD C55 ○ ---- ---- ---- ○ ----

228 RD00 QCM 31 AP 002 XQ 01 Secondary Acid Dosing Pump (B) VSD Position 31 Secon Acid Dos Pump (B) VSD Pos 0-1800 rpm AII ---- ---- ---- ---- VSD U0-ARS-E DCSSEP C55 ○ ---- ○ ---- ○ ----

229 RD00 QCM 31 AP 002 YJ 01 Secondary Acid Dosing Pump (B) VSD MV 30 Secon Acid Dos Pump (B) VSD MV 0-1800 rpm AOX ---- ---- ---- ---- DCSSEP U0-ARS-E VSD C55 ○ ---- ---- ---- ○ ----

230 RD00 HHU 22 CG 101 XQ 01 Secondary Acid Dosing Brine Dilution Valve Position 32 Secn Acid Dos Brin Diltn Vlv Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C57 ---- ---- ○ ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-3.SEPARATOR & WELLPAD-E AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
231 RD00 HHU 22 FH 101 YJ 01 Secondary Acid Dosing Brine Dilution Valve MV 31 Secn Acd Dos Brn Diltn Valve MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C57 ○ H ---- ---- ○ ----

235 RD00 LBA 60 AA 192 XG 01 Rupture Disc at RD00-LAB-61-AT-001 32 RUPTR Disc at RD00-LAB-61-AT-001 OFF/ON ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

236 RD00 LBA 60 AA 195 XG 01 Rupture Disc at RD00-LAB-61-AT-001 32 RUPTR Disc at RD00-LAB-61-AT-001 OFF/ON ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

237 RD00 LBA 60 AA 198 XG 01 Rupture Disc at RD00-LAB-61-AT-001 32 RUPTR Disc at RD00-LAB-61-AT-001 OFF/ON ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

238 RD00 LBA 80 AA 192 XG 01 Rupture Disc at RD00-LAB-80-AT-001 32 RUPTR Disc at RD00-LAB-80-AT-001 OFF/ON ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

239 RD00 LBA 80 AA 195 XG 01 Rupture Disc at RD00-LAB-80-AT-001 32 RUPTR Disc at RD00-LAB-80-AT-001 OFF/ON ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

475 RD00 LBA 80 AA 198 XG 01 Rupture Disc at RD00-LAB-80-AT-001 32 RUPTR Disc at RD00-LAB-80-AT-001 OFF/ON ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

476 RD00 LBA 80 AA 201 XG 01 Rupture Disc at RD00-LAB-80-AT-001 32 RUPTR Disc at RD00-LAB-80-AT-001 OFF/ON ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

241 RD00 LBA 80 AA 182 XG 01 Rupture Disc at RD00-LAB-81-AT-001 32 RUPTR Disc at RD00-LAB-81-AT-001 OFF/ON ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

242 RD00 LBA 80 AA 185 XG 01 Rupture Disc at RD00-LAB-81-AT-001 32 RUPTR Disc at RD00-LAB-81-AT-001 OFF/ON ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

477 RD00 LBA 80 AA 188 XG 01 Rupture Disc at RD00-LAB-81-AT-001 32 RUPTR Disc at RD00-LAB-81-AT-001 OFF/ON ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ○ P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

244 RD00 HAN 11 CP 001 XQ 01 Pressure Transmitter at Injection well RD-E1 26 PT at Injection well RD-E1 0 - 20 Bar G AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R30E ○ ---- ---- ---- ○ ----

245 RD00 HAN 11 CP 002 XQ 01 Pressure Transmitter at Injection well RD-E1 26 PT at Injection well RD-E1 0 - 20 Bar G AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R30E ○ ---- ---- ---- ○ ----

11
246 RD00 LBA 60 CP 002 XQ 01 HP Separator Outlet Steam Pressure 31 HP Separator Outlet Steam Press 0 - 15 Bar G AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R27 ○ H ---- ---- ○ ---- Rev.4; Range is updated 4
(P2)

247 RD00 LBA 60 CP 001 XQ 01 HP Separator Inlet Anti-Surge tank Outlet Pressure 32 HP Sep Anti-Surg Tnk Outlt Press 0 - 15 Bar G AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R27 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

248 RD00 HHU 11 CP 001 XQ 01 HP Separator Outlet HP Brine Pressure 28 HP Sep Outlet HP Brine Press 0 - 15 Bar G AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R27 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

474 RD00 HHU 11 CP 002 XQ 01 LP Separator Inlet Two-phase Fluid Pressure 32 LP Sep Inlt Two-phas Fluid Press 0 - 15 Bar G AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R13 ○ ---- ---- ---- ○ ----

5.6
250 RD00 LBA 80 CP 001 XQ 01 LP Separator Outlet Steam Pressure 31 LP Separator Outlet Steam Press 0 - 15 Bar G AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R29 ○ H ---- ---- ○ ----
(P2)

251 RD00 HHU 21 CP 001 XQ 01 LP Separator Outlet LP Brine Pressure 28 LP Sep Outlet LP Brine Press 0 - 15 Bar G AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R29 ○ ---- ---- ---- ○ ----

252 RD00 LBA 40 CP 001 XQ 01 LP Separator (LP Wells) Inlet Steam Pressure 32 LP Sep (LP Well) Inlt Stm Press 0 - 15 Bar G AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R29 ○ ---- ---- ---- ○ ----

5.6
253 RD00 LBA 80 CP 002 XQ 01 LP Separator (LP Wells) Outlet Steam Pressure 32 LP Sep (LP Well) Outlt Stm Press 0 - 15 Bar G AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R29 ○ H ---- ---- ○ ----
(P2)

254 RD00 HHU 21 CP 002 XQ 01 LP Separator (LP Wells) Outlet LP Brine Pressure 32 LP Sep (LW) Outlt LP Brine Press 0 - 15 Bar G AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R29 ○ ---- ---- ---- ○ ----

255 RD00 QCM 21 CP 001 XQ 01 Primary Acid Dosing Pump discharge Pressure (A) 32 Pri Acid Dos Pmp Discg Press (A) 0 - 15 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R25 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

431 RD00 QCM 21 CP 002 XQ 01 Primary Acid Dosing Pump discharge Pressure (B) 32 Pri Acid Dos Pmp Discg Press (B) 0 - 15 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R25 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

256 RD00 HHU 12 CP 006 XQ 01 Primary Acid Dosing Brine Dilution Pressure 32 Prim Acid Dos Brine Diltn Press 0 - 15 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R25 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

257 RD00 QCM 31 CP 001 XQ 01 Secondary Acid Dosing Pump Discharge Pressure (A) 32 Secn Acd Dos Pmp Discg Press (A) 0 - 10 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R25 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

432 RD00 QCM 31 CP 002 XQ 01 Secondary Acid Dosing Pump Discharge Pressure (B) 32 Secn Acd Dos Pmp Discg Press (B) 0 - 10 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R25 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

258 RD00 HHU 22 CP 006 XQ 01 Secondary Acid Dosing Brine Dilution Pressure 32 Secon Acid Dos Brin Diltn Press 0 - 10 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R25 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

259 RD00 HHU 12 CP 001 XQ 01 HP Dilution Brine Pump (A) Discharge Pressure 32 HP Diltn Brn Pmp (A) Discg Press 0 - 15 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R26 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

260 RD00 HHU 12 CP 002 XQ 01 HP Dilution Brine Pump (B) Discharge Pressure 32 HP Diltn Brn Pmp (B) Discg Press 0 - 15 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R26 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

0.5
262 RD00 HHU 12 CP 004 XQ 01 HP Dilution Brine Header Strainer Differential Pressure 32 HP Diltn Brin Strainer Diff Pres 0 - 0.5 barg AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R26 ○ H ---- ---- ○ ---- Rev.4; Range is updated 4
(P2)
0.5
263 RD00 HHU 12 CP 005 XQ 01 Acid Dilution HP Brine Air Cooler differential pressure 32 Acid Diltn HP Brin CL Diff Press 0 - 0.5 barg AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R26 ○ H ---- ---- ○ ----
(P2)

265 RD00 HHU 22 CP 001 XQ 01 LP Dilution Brine Pump (A) Discharge Pressure 32 LP Diltn Brin Pmp (A) Discg Pres 0-5 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R28 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

266 RD00 HHU 22 CP 002 XQ 01 LP Dilution Brine Pump (B) Discharge Pressure 32 LP Diltn Brin Pmp (B) Discg Pres 0-5 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R28 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

0,5
268 RD00 HHU 22 CP 004 XQ 01 LP Dilution Brine Header Strainer Differential Pressure 32 LP Diltn Brin Strainer Diff Pres 0-0.5 barg AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R28 ○ H ---- ---- ○ ---- Rev.4; Range is updated 4
(P2)
0,5
269 RD00 HHU 22 CP 005 XQ 01 Acid Dilution LP Brine Air Cooler differential pressure 32 Acid Diltn LP Brine CL Diff Pres 0-0.5 barg AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R28 ○ H ---- ---- ○ ----
(P2)
5
271 RD00 QCM 11 CT 001 XQ 01 Sulphic Acid Storage Tank (A) Temperature 32 Sulph Acid Storage Tank (A) Temp 0-250 DegC AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R65 ○ L ---- ---- ○ ----
(P2)
5
272 RD00 QCM 11 CT 002 XQ 01 Sulphic Acid Storage Tank (B) Temperature 32 Sulph Acid Storage Tank (B) Temp 0-250 DegC AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R65 ○ L ---- ---- ○ ----
(P2)

273 RD00 QCM 21 CT 001 XQ 01 Primary Acid Dosing Supply Temperature (A) 32 Prim Acid Dosing Supply Temp (A) 0-250 DegC AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R65 ○ ---- ---- ---- ○ ----

433 RD00 QCM 21 CT 002 XQ 01 Primary Acid Dosing Supply Temperature (B) 32 Prim Acid Dosing Supply Temp (B) 0-250 DegC AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R65 ○ ---- ---- ---- ○ ----

275 RD00 QCM 31 CT 001 XQ 01 Secondary Acid Dosing Supply Temperature (A) 30 Secon Acid Dos Supply Temp (A) 0-250 DegC AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R66 ○ ---- ---- ---- ○ ----

434 RD00 QCM 31 CT 002 XQ 01 Secondary Acid Dosing Supply Temperature (B) 30 Secon Acid Dos Supply Temp (B) 0-250 DegC AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R66 ○ ---- ---- ---- ○ ----

277 RD00 HAN 11 CT 001 XQ 01 Temperature Transmitter at Injection well RD-E1 25 Injection well RD-E1 Temp 0-220 DegC AII ---- ---- ---- ---- F U0-ARS-E DCSSEP ---- ○ ---- ---- ---- ○ ----

278 RD00 HHU 11 CT 001 XQ 01 HP Separator Outlet HP Brine Temperature 27 HP Sep Outlet HP Brine Temp 0-250 DegC AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R67 ○ ---- ---- ---- ○ ----

279 RD00 HHU 21 CT 001 XQ 01 LP Separator outlet LP Brine Temperature 27 LP Sep outlet LP Brine Temp 0-200 DegC AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R67 ○ ---- ---- ---- ○ ----

280 RD00 LBA 40 CT 001 XQ 01 LP Separator (LP Wells) Inlet Steam Temperature 32 LP Sep (LP Wells) Inlet Stm Temp 0-200 DegC AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R67 ○ ---- ---- ---- ○ ----

281 RD00 HHU 21 CT 002 XQ 01 LP Separator (LP Wells) Outlet LP Brine Temperature 31 LP Sep (LW) Outlt LP Brine Temp 0-200 DegC AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R67 ○ ---- ---- ---- ○ ----

282 RD00 HAN 11 CF 001 XQ 01 Flow Transmitter at Injection well RD-E1 25 Injection well RD-E1 Flow 0-312 Kg/h AII ---- ---- ---- ---- F U0-ARS-E DCSSEP ---- ○ ---- ---- ---- ○ ----

283 RD00 HHU 11 CF 001 XQ 01 HP Separator Outlet HP Brine Flow 27 HP Sep Outlet HP Brine Flow 0-600 kg/s AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R06 ○ ---- ○ ---- ○ ----

10 2.0
284 RD00 HHU 12 CF 001 XQ 01 Primary Acid Dosing Brine Dilution Flow 32 Prim Acid Dosing Brin Diltn Flow 0-11 kg/s AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R06 ○ ---- ○ ---- ○ ----
(P2) (P2)
2.DCS IO LIST FOR HARD WIRE
2-3.SEPARATOR & WELLPAD-E AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
0.03 0.025
285 RD00 QCM 21 CF 001 XQ 01 Primary Acid Dosing Supply Flow (A) 32 Prim Acid Dosing Supply Flow (A) 0-2 kg/s AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R06 ○ H/L ○ ---- ○ ---- 24V power supply from DCS
(P2) (P2)
0.03 0.025
429 RD00 QCM 21 CF 002 XQ 01 Primary Acid Dosing Supply Flow (B) 32 Prim Acid Dosing Supply Flow (B) 0-2 kg/s AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R06 ○ H/L ○ ---- ○ ---- 24V power supply from DCS
(P2) (P2)
6.0 2.0
286 RD00 HHU 22 CF 001 XQ 01 Secondary Acid Dosing Brine Dilution Flow 31 Secon Acid Dos Brine Diltn Flow 0-8 kg/s AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R07 ○ ---- ○ ---- ○ ----
(P2) (P2)
0.015 0.01
287 RD00 QCM 31 CF 001 XQ 01 Secondary Acid Dosing Supply Flow (A) 30 Secon Acid Dosing Sup Flow (A) 0-2 kg/s AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R07 ○ ---- ○ ---- ○ ---- 24V power supply from DCS
(P2) (P2)
0.015 0.01
430 RD00 QCM 31 CF 002 XQ 01 Secondary Acid Dosing Supply Flow (B) 30 Secon Acid Dosing Sup Flow (B) 0-2 kg/s AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R07 ○ ---- ○ ---- ○ ---- 24V power supply from DCS
(P2) (P2)

288 RD00 HHU 21 CF 001 XQ 01 LP Separator Outlet LP Brine Flow 27 LP Sep Outlet LP Brine Flow 0-600 kg/s AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R07 ○ L ○ ---- ○ ----

289 RD00 HHU 21 CF 002 XQ 01 LP Separator (LP Well) Outlet LP Brine Flow 31 LP Sep (LW) Outlt LP Brine Flow 0-300 kg/s AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R07 ○ L ○ ---- ○ ----

290 RD00 LBA 30 CP 001 XQ 01 HP Separator Inlet Anti-Surge Tank Inlet Two-Phase Pressure 32 HP Sep Anti-Surge Tank Inlt Pres 0 - 15 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP R13 ○ ---- ---- ---- ○ ---- Rev.4; Range is updated 4

EH/HH 2950 2250 2100 1720 1150


291 RD00 HHU 11 CL 001 XQ 01 HP Separator Tank Level (A) 27 HP Separator Tank Level (A) 0 - 6900 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP C20 ○ ○ ---- ○ ----
/H/L (P1) (P1) (P1) (P1) (P1)
EH/HH 2950 2250 2100 1720 1150
292 RD00 HHU 11 CL 002 XQ 01 HP Separator Tank Level (B) 27 HP Separator Tank Level (B) 0 - 6900 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP C20 ○ ○ ---- ○ ----
/H/L (P1) (P1) (P1) (P1) (P1)
EH/HH 2950 2250 2100 1720 1150
293 RD00 HHU 11 CL 003 XQ 01 HP Separator Tank Level (C) 27 HP Separator Tank Level (C) 0 - 6900 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP C20 ○ ○ ---- ○ ----
/H/L (P1) (P1) (P1) (P1) (P1)
EH/HH 5800 5000 4500 1700 1400
294 RD00 HHU 21 CL 001 XQ 01 LP Separator Tank Level (A) 27 LP Separator Tank Level (A) 0 - 6900 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP C25 ○ ○ ---- ○ ----
/H/L (P1) (P1) (P1) (P1) (P1)
EH/HH 5800 5000 4500 1700 1400
295 RD00 HHU 21 CL 002 XQ 01 LP Separator Tank Level (B) 27 LP Separator Tank Level (B) 0 - 6900 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP C25 ○ ○ ---- ○ ----
/H/L (P1) (P1) (P1) (P1) (P1)
EH/HH 5800 5000 4500 1700 1400
296 RD00 HHU 21 CL 003 XQ 01 LP Separator Tank Level (C) 27 LP Separator Tank Level (C) 0 - 6900 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP C25 ○ ○ ---- ○ ----
/H/L (P1) (P1) (P1) (P1) (P1)
EH/HH 5800 5000 4500 1700 1400
297 RD00 HHU 21 CL 004 XQ 01 LP Separator (LP Well) Tank Level (A) 31 LP Sep (LP Well) Tank Level (A) 0 - 6900 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP C28 ○ ○ ---- ○ ----
/H/L (P1) (P1) (P1) (P1) (P1)
EH/HH 5800 5000 4500 1700 1400
298 RD00 HHU 21 CL 005 XQ 01 LP Separator (LP Well) Tank Level (B) 31 LP Sep (LP Well) Tank Level (B) 0 - 6900 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP C28 ○ ○ ---- ○ ----
/H/L (P1) (P1) (P1) (P1) (P1)
EH/HH 5800 5000 4500 1700 1400
299 RD00 HHU 21 CL 006 XQ 01 LP Separator (LP Well) Tanl Levek (C) 31 LP Sep (LP Well) Tanl Levek (C) 0 - 6900 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP C28 ○ ○ ---- ○ ----
/H/L (P1) (P1) (P1) (P1) (P1)
HH/H/ BTM+2850 BTM+2800 BTM+1500 BTM+200
300 RD00 QCM 11 CL 001 XQ 01 Sulphuric Acid Storage Tank (A) Level 31 Sulph Acid Storage Tank (A) Lvl 0-3500 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R89A ○ ○ ---- ○ ----
L/LL (P1) (P2) (P2) (P1)
HH/H/ BTM+2850 BTM+2800 BTM+1500 BTM+200
301 RD00 QCM 11 CL 002 XQ 01 Sulphuric Acid Storage Tank (B) Level 31 Sulph Acid Storage Tank (B) Lvl 0-3500 mm AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R89A ○ ○ ---- ○ ----
L/LL (P1) (P2) (P2) (P1)
H
302 RD00 QCM 11 CL 081 XG 01 Sulphuric Acid Storage Tank (A) Level HH 32 Sulph Acd Storage Tnk (A) Lvl HH NORMAl/HIGH ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP R89B ○ ---- ---- ○ ---- Rev.4a Signal type is corrected 4a
(P1)
H
303 RD00 QCM 11 CL 082 XG 01 Sulphuric Acid Storage Tank (B) Level HH 32 Sulph Acd Storage Tnk (B) Lvl HH NORMAl/HIGH ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP R89B ○ ---- ---- ○ ---- Rev.4a Signal type is corrected 4a
(P1)

481 RD00 HAN 11 FH 101 YJ 01 MOV RD-E1 MV 12 MOV RD-E1 MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F REK ○ ---- ○ ---- ○ ----

482 RD00 HAN 11 CG 101 XQ 01 MOV RD-E1 Position 18 MOV RD-E1 Position 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP REK ○ ---- ○ ---- ○ ----

306 RD00 HAN 11 CG 101 XG 01 VALVE OPEN POSITION -MOV RD-E1 30 VALVE OPEN POSITION -MOV RD-E1 OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP REK ○ ---- ---- ---- ○ ----

307 RD00 HAN 11 CG 101 XG 02 VALVE CLOSE POSITION- MOV RD-E1 31 VALVE CLOSE POSITION- MOV RD-E1 OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP REK ○ ---- ---- ---- ○ ----

308 RD00 HAN 11 AA 101 XG 01 TORQUE OVER INDICATION -MOV RD-E1 30 TRQ OVER INDICATION -MOV RD-E1 NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP REK ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

309 RD00 HAN 11 AA 101 XG 02 REMOTE MODE SELECTED -MOV RD-E1 31 REMOTE MODE SELECTED -MOV RD-E1 LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP REK ○ ---- ---- ---- ○ ----

310 RD00 HAN 11 AA 101 XG 03 VALVE FAILURE -MOV RD-E1 24 VALVE FAILURE -MOV RD-E1 NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP REK ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

311 RD00 HAN 11 AA 101 XG 04 LOSS OF POWER SOURCE -MOV RD-E1 31 LOSS OF POWER SOURCE -MOV RD-E1 NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP REK ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

312 RD00 HHU 11 FH 101 YJ 01 HP Separator EDV (A) MV 23 HP Separator EDV (A) MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C22 ---- ---- ○ ---- ○ ----

313 RD00 HHU 11 CG 101 XQ 01 HP Separator EDV (A) Position 29 HP Separator EDV (A) Position 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C22 ○ ---- ○ ---- ○ ----

NO
317 RD00 HHU 11 FH 501 YB 01 HP Separator EDV (A) Isolation MOV OPEN COMMAND 32 HP Sep EDV (A) Isol MOV OPEN Cmd OFF/OPEN ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P01A ○ ---- ○ ---- ○ ----
LATCH
NO
318 RD00 HHU 11 FH 501 YB 02 HP Separator EDV (A) Isolation MOV CLOSE COMMAND 31 HP Sep EDV (A) Isol MOV Cls Cmd OFF/CLOSE ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P01A ○ ---- ○ ---- ○ ----
LATCH

319 RD00 HHU 11 CG 081 XG 01 HP Separator EDV (A) Isolation MOV OPEN POSITION 32 HP Sep EDV (A) Isol MOV OPEN Pos OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P01A ○ ---- ---- ---- ○ ----

320 RD00 HHU 11 CG 082 XG 02 HP Separator EDV (A) Isolation MOV CLOSE POSITION 31 HP Sep EDV (A) Isol MOV Cls Pos OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P01A ○ ---- ---- ---- ○ ----

321 RD00 HHU 11 AA 501 XG 01 HP Separator EDV (A) Isolation MOV TORQUE OVER INDICATION 32 HP Sep EDV (A) Isol MOV TRQ OVER NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P01A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

322 RD00 HHU 11 AA 501 XG 02 HP Separator EDV (A) Isolation MOV REMOTE MODE SELECTED 30 HP Sep EDV (A) Isol MOV REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P01A ○ ---- ---- ---- ○ ----

323 RD00 HHU 11 AA 501 XG 03 HP Separator EDV (A) Isolation MOV VALVE FAILURE 32 HP Sep EDV (A) Isol MOV VLV FAIL NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P01A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

324 RD00 HHU 11 AA 501 XG 04 HP Separator EDV (A) Isolation MOV LOSS OF POWER SOURCE 32 HP Sep EDV (A) Isol MOV Pow LOSS NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P01A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

325 RD00 HHU 11 FH 102 YJ 01 HP Separator EDV (B) MV 23 HP Separator EDV (B) MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C22 ---- ---- ○ ---- ○ ----

326 RD00 HHU 11 CG 102 XQ 01 HP Separator EDV (B) Position 29 HP Separator EDV (B) Position 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C22 ○ ---- ○ ---- ○ ----

NO
330 RD00 HHU 11 FH 503 YB 01 HP Separator EDV (B) Isolation MOV OPEN COMMAND 32 HP Sep EDV (B) Isol MOV OPEN Cmd OFF/OPEN ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P02A ○ ---- ○ ---- ○ ----
LATCH
NO
331 RD00 HHU 11 FH 503 YB 02 HP Separator EDV (B) Isolation MOV CLOSE COMMAND 31 HP Sep EDV (B) Isol MOV Cls Cmd OFF/CLOSE ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P02A ○ ---- ○ ---- ○ ----
LATCH

332 RD00 HHU 11 CG 083 XG 01 HP Separator EDV (B) Isolation MOV OPEN POSITION 32 HP Sep EDV (B) Isol MOV OPEN Pos OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P02A ○ ---- ---- ---- ○ ----

333 RD00 HHU 11 CG 084 XG 02 HP Separator EDV (B) Isolation MOV CLOSE POSITION 31 HP Sep EDV (B) Isol MOV Cls Pos OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P02A ○ ---- ---- ---- ○ ----

334 RD00 HHU 11 AA 503 XG 01 HP Separator EDV (B) Isolation MOV TORQUE OVER INDICATION 32 HP Sep EDV (B) Isol MOV TRQ OVER NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P02A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

335 RD00 HHU 11 AA 503 XG 02 HP Separator EDV (B) Isolation MOV REMOTE MODE SELECTED 30 HP Sep EDV (B) Isol MOV REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P02A ○ ---- ---- ---- ○ ----

336 RD00 HHU 11 AA 503 XG 03 HP Separator EDV (B) Isolation MOV VALVE FAILURE 32 HP Sep EDV (B) Isol MOV VLV FAIL NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P02A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

337 RD00 HHU 11 AA 503 XG 04 HP Separator EDV (B) Isolation MOV LOSS OF POWER SOURCE 32 HP Sep EDV (B) Isol MOV Pow LOSS NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P02A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

338 RD00 HHU 11 FH 103 YJ 01 HP Separator Level Control Valve (A) MV 23 HP Separator LCV (A) MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C21 ---- ---- ○ ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-3.SEPARATOR & WELLPAD-E AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
339 RD00 HHU 11 CG 103 XQ 01 HP Separator Level Control Valve (A) Position 24 HP Separator LCV (A) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C21 ○ ---- ○ ---- ○ ----

340 RD00 HHU 11 FH 104 YJ 01 HP Separator Level Control Valve (B) MV 23 HP Separator LCV (B) MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C21 ---- ---- ○ ---- ○ ----

341 RD00 HHU 11 CG 104 XQ 01 HP Separator Level Control Valve (B) Position 24 HP Separator LCV (B) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C21 ○ ---- ○ ---- ○ ----

342 RD00 HHU 21 FH 101 YJ 01 LP Separator EDV (A) MV 23 LP Separator EDV (A) MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C27 ---- ---- ○ ---- ○ ----

343 RD00 HHU 21 CG 101 XQ 01 LP Separator EDV (A) Position 29 LP Separator EDV (A) Position 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C27 ○ ○ ○ ---- ○ ----

NO
347 RD00 HHU 21 FH 501 YB 01 LP Separator EDV (A) Isolation MOV OPEN COMMAND 32 LP Sep EDV (A) Isltn MOV Opn Cmd OFF/OPEN ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P03A ○ ---- ○ ---- ○ ----
LATCH
NO
348 RD00 HHU 21 FH 501 YB 02 LP Separator EDV (A) Isolation MOV CLOSE COMMAND 32 LP Sep EDV (A) Isltn MOV Cls Cmd OFF/CLOSE ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P03A ○ ---- ○ ---- ○ ----
LATCH

349 RD00 HHU 21 CG 081 XG 01 LP Separator EDV (A) Isolation MOV OPEN POSITION 32 LP Sep EDV (A) Isltn MOV Opn Pos OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P03A ○ ---- ---- ---- ○ ----

350 RD00 HHU 21 CG 082 XG 02 LP Separator EDV (A) Isolation MOV CLOSE POSITION 32 LP Sep EDV (A) Isltn MOV Cls Pos OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P03A ○ ---- ---- ---- ○ ----

351 RD00 HHU 21 AA 501 XG 01 LP Separator EDV (A) Isolation MOV TORQUE OVER INDICATION 32 LP Sep EDV (A) Isltn MOV TRQ OVR NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P03A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

352 RD00 HHU 21 AA 501 XG 02 LP Separator EDV (A) Isolation MOV REMOTE MODE SELECTED 31 LP Sep EDV (A) Isltn MOV REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P03A ○ ---- ---- ---- ○ ----

353 RD00 HHU 21 AA 501 XG 03 LP Separator EDV (A) Isolation MOV VALVE FAILURE 32 LP Sep EDV (A) Isltn MOV VLV FLT NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P03A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

354 RD00 HHU 21 AA 501 XG 04 LP Separator EDV (A) Isolation MOV LOSS OF POWER SOURCE 32 LP Sep EDV (A) Isltn MOV Pw Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P03A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

355 RD00 HHU 21 FH 102 YJ 01 LP Separator EDV (B) MV 23 LP Separator EDV (B) MV 0-100 % AOX ---- ---- DCSSEP U0-ARS-E F C27 ---- ---- ○ ---- ○ ----

356 RD00 HHU 21 CG 102 XQ 01 LP Separator EDV (B) Position 29 LP Separator EDV (B) Position 0-100 % AII ---- ---- F U0-ARS-E DCSSEP C27 ○ ○ ○ ---- ○ ----

NO
360 RD00 HHU 21 FH 503 YB 01 LP Separator EDV (B) Isolation MOV OPEN COMMAND 32 LP Sep EDV (B) Isltn MOV Opn Cmd OFF/OPEN ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P04A ○ ---- ○ ---- ○ ----
LATCH
NO
361 RD00 HHU 21 FH 503 YB 02 LP Separator EDV (B) Isolation MOV CLOSE COMMAND 32 LP Sep EDV (B) Isltn MOV Cls Cmd OFF/CLOSE ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P04A ○ ---- ○ ---- ○ ----
LATCH

362 RD00 HHU 21 CG 083 XG 01 LP Separator EDV (B) Isolation MOV OPEN POSITION 32 LP Sep EDV (B) Isltn MOV Opn Pos OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P04A ○ ---- ---- ---- ○ ----

363 RD00 HHU 21 CG 084 XG 02 LP Separator EDV (B) Isolation MOV CLOSE POSITION 32 LP Sep EDV (B) Isltn MOV Cls Pos OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P04A ○ ---- ---- ---- ○ ----

364 RD00 HHU 21 AA 503 XG 01 LP Separator EDV (B) Isolation MOV TORQUE OVER INDICATION 32 LP Sep EDV (B) Isltn MOV TRQ OVR NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P04A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

365 RD00 HHU 21 AA 503 XG 02 LP Separator EDV (B) Isolation MOV REMOTE MODE SELECTED 31 LP Sep EDV (B) Isltn MOV REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P04A ○ ---- ---- ---- ○ ----

366 RD00 HHU 21 AA 503 XG 03 LP Separator EDV (B) Isolation MOV VALVE FAILURE 32 LP Sep EDV (B) Isltn MOV VLV FLT NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P04A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

367 RD00 HHU 21 AA 503 XG 04 LP Separator EDV (B) Isolation MOV LOSS OF POWER SOURCE 32 LP Sep EDV (B) Isltn MOV Pw Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P04A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

368 RD00 HHU 21 FH 103 YJ 01 LP Separator Control Valve MV 29 LP Separator Control Valve MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C26 ---- ---- ○ ---- ○ ----

369 RD00 HHU 21 CG 103 XQ 01 LP Separator Control Valve Position 30 LP Separator Control Valve Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C26 ○ ○ ○ ---- ○ ----

NO
374 RD00 HHU 21 FH 104 YB 01 LP Separator to Brine Injection MOV OPEN COMMAND 32 LP Sep to Brn Injctn MOV Opn Cmd OFF/OPEN ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P11 ○ ---- ○ ---- ○ ---- Rdv.4;Change to AO 4
LATCH

3430 RD00 HHU 21 FH 104 YJ 01 LP Separator to Brine Injection MOV MV 26 LP Sep to INJECTION MOV MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C26 ○ ---- ○ ---- ○ ---- Rev.4;AO is added 4

NO
375 RD00 HHU 21 FH 104 YB 02 LP Separator to Brine Injection MOV CLOSE COMMAND 32 LP Sep to Brn Injctn MOV Cls Cmd OFF/CLOSE ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P11 ○ ---- ○ ---- ○ ---- Rev.4;Change to AO 4
LATCH

3431 RD00 HHU 21 CG 104 XQ 01 LP Separator to Brine Injection MOV POSITION 32 LP Sep to INJECTION MOV POSITION 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C26 ○ ○ ○ ---- ○ ---- Rev.4;AI is added 4

376 RD00 HHU 21 CG 085 XG 01 LP Separator to Brine Injection MOV OPEN POSITION 32 LP Sep to Brn Injctn MOV Opn Pos OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P11 ○ ---- ---- ---- ○ ----

377 RD00 HHU 21 CG 086 XG 02 LP Separator to Brine Injection MOV CLOSE POSITION 32 LP Sep to Brn Injctn MOV Cls Pos OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P11 ○ ---- ---- ---- ○ ----

378 RD00 HHU 21 AA 104 XG 01 LP Separator to Brine Injection MOV TORQUE OVER INDICATION 32 LP Sep to Brn Injctn MOV TRQ OVR NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P11 ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

379 RD00 HHU 21 AA 104 XG 02 LP Separator to Brine Injection MOV REMOTE MODE SELECTED 32 LP Sep to Brin Injctn MOV REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P11 ○ ---- ---- ---- ○ ----

380 RD00 HHU 21 AA 104 XG 03 LP Separator to Brine Injection MOV VALVE FAILURE 32 LP Sep to Brn Injctn MOV VLV FLT NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P11 ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

381 RD00 HHU 21 AA 104 XG 04 LP Separator to Brine Injection MOV LOSS OF POWER SOURCE 32 LP Sep to Brn Injctn MOV Pw Loss NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P11 ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

382 RD00 HHU 21 FH 105 YJ 01 LP Separator Brine Bypass to AFT MOV MV 30 LP Brine to AFT Cntrl Valve MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C31 ○ ---- ○ ---- ○ ----

384 RD00 HHU 21 CG 105 XQ 01 LP Separator Brine Bypass to AFT MOV POSITION 28 LP Sep Brine to AFT MOV Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C31 ○ ---- ---- ---- ○ ----

390 RD00 HHU 21 FH 106 YJ 01 LP Separator (LP Well) EDV (A) MV 27 LP Sep (LP Well) EDV (A) MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C30 ---- ---- ○ ---- ○ ----

391 RD00 HHU 21 CG 106 XQ 01 LP Separator (LP Well) EDV (A) Position 28 LP Sep (LP Well) EDV (A) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C30 ○ ○ ○ ---- ○ ----

NO
396 RD00 HHU 21 FH 507 YB 01 LP Separator (LP Well) EDV(A) Isolation MOV OPEN COMMAND 32 LP Sep(LW) EDV(A) Isol MOV Op Cm OFF/OPEN ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P05A ○ ---- ---- ---- ○ ----
LATCH
NO
397 RD00 HHU 21 FH 507 YB 02 LP Separator (LP Well) EDV(A) Isolation MOV CLOSE COMMAND 32 LP Sep(LW) EDV(A) Isol MOV Cl Cm OFF/CLOSE ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P05A ○ ---- ---- ---- ○ ----
LATCH

398 RD00 HHU 21 CG 089 XG 01 LP Separator (LP Well) EDV(A) Isolation MOV OPEN POSITION 32 LPSep(LW) EDV(A) Isol MOV Op Pos OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P05A ○ ---- ---- ---- ○ ----

399 RD00 HHU 21 CG 090 XG 02 LP Separator (LP Well) EDV(A) Isolation MOV CLOSE POSITION 32 LPSep(LW) EDV(A) Isol MOV Cl Pos OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P05A ○ ---- ---- ---- ○ ----

400 RD00 HHU 21 AA 507 XG 01 LP Separator (LP Well) EDV(A) Isolation MOV TORQUE OVER INDICATION 32 LPSp(LW) EDV(A) Isol MOV TRQ OVR NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P05A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

401 RD00 HHU 21 AA 507 XG 02 LP Separator (LP Well) EDV(A) Isolation MOV REMOTE MODE SELECTED 32 LPSep(LW) EDV(A) Isol MOV REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P05A ○ ---- ---- ---- ○ ----

402 RD00 HHU 21 AA 507 XG 03 LP Separator (LP Well) EDV(A) Isolation MOV VALVE FAILURE 32 LPSep(LW) EDV(A) Isol MOV VLV FL NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P05A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

403 RD00 HHU 21 AA 507 XG 04 LP Separator (LP Well) EDV(A) Isolation MOV LOSS OF POWER SOURCE 32 LPSep(LW) EDV(A) Isol MOV Pw Los NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P05A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

404 RD00 HHU 21 FH 107 YJ 01 LP Separator (LP Well) EDV (B) MV 27 LP Sep (LP Well) EDV (B) MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C30 ---- ---- ○ ---- ○ ----

405 RD00 HHU 21 CG 107 XQ 01 LP Separator (LP Well) EDV (B) Position 28 LP Sep (LP Well) EDV (B) Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C30 ○ ○ ○ ---- ○ ----

NO
410 RD00 HHU 21 FH 509 YB 01 LP Separator (LP Well) EDV(B) Isolation MOV OPEN COMMAND 32 LP Sep(LW) EDV(B) Isol MOV Op Cm OFF/OPEN ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P06A ○ ---- ○ ---- ○ ----
LATCH
2.DCS IO LIST FOR HARD WIRE
2-3.SEPARATOR & WELLPAD-E AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
NO
411 RD00 HHU 21 FH 509 YB 02 LP Separator (LP Well) EDV(B) Isolation MOV CLOSE COMMAND 32 LP Sep(LW) EDV(B) Isol MOV Cl Cm OFF/CLOSE ---- DOL DC24 2W ---- DCSSEP U0-ARS-E F P06A ○ ---- ○ ---- ○ ----
LATCH

412 RD00 HHU 21 CG 091 XG 02 LP Separator (LP Well) EDV(B) Isolation MOV OPEN POSITION 32 LPSep(LW) EDV(B) Isol MOV Op Pos OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P06A ○ ---- ---- ---- ○ ----

413 RD00 HHU 21 CG 092 XG 02 LP Separator (LP Well) EDV(B) Isolation MOV CLOSE POSITION 32 LPSep(LW) EDV(B) Isol MOV Cl Pos OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P06A ○ ---- ---- ---- ○ ----

414 RD00 HHU 21 AA 509 XG 01 LP Separator (LP Well) EDV(B) Isolation MOV TORQUE OVER INDICATION 32 LPSp(LW) EDV(B) Isol MOV TRQ OVR NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P06A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

415 RD00 HHU 21 AA 509 XG 02 LP Separator (LP Well) EDV(B) Isolation MOV REMOTE MODE SELECTED 32 LPSep(LW) EDV(B) Isol MOV REMOTE LOCAL/REMOTE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P06A ○ ---- ---- ---- ○ ----

416 RD00 HHU 21 AA 509 XG 03 LP Separator (LP Well) EDV(B) Isolation MOV VALVE FAILURE 32 LPSep(LW) EDV(B) Isol MOV VLV FL NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P06A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

417 RD00 HHU 21 AA 509 XG 04 LP Separator (LP Well) EDV(B) Isolation MOV LOSS OF POWER SOURCE 32 LPSep(LW) EDV(B) Isol MOV Pw Los NORMAL/ALARM ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP P06A ○ P2 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

418 RD00 HHU 21 FH 108 YJ 01 LP Separator (LP Well) Control Valve MV 29 LP Sep (LP Well) Ctl Valve MV 0-100 % AOX ---- ---- ---- ---- DCSSEP U0-ARS-E F C29 ---- ---- ○ ---- ○ ----

419 RD00 HHU 21 CG 108 XQ 01 LP Separator (LP Well) Control Valve Position 30 LP Sep (LP Well) Ctl Valve Pos 0-100 % AII ---- ---- ---- ---- F U0-ARS-E DCSSEP C29 ○ ○ ○ ---- ○ ----

424 RD00 BRT 10 XQ 03 SS DC UPS SYSTEM 110VDC BUS VOLTAGE 32 SS DC UPS SYS 110VDC BUS VOLTAGE 0-110 VDC AIX ---- ---- ---- ---- F NA DCSSEP ---- ○ ---- ---- ---- ○ ----

425 RD00 BRT 10 XG 03 SS DC UPS SYSTEM 110VDC COMMON OUTPUT FEEDER TRIP 31 DC UPS SYS 110VDC OUTPT FDR TRP NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSSEP ---- ---- P1 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

471 RD00 HHU 11 CT 002 XQ 01 LP Separator Inlet Two-phase Fluid Temperature 32 LP Sep Inlt Two-phase Fluid Temp 0 - 200 degC AIX ---- ---- ---- ---- F U0-ARS-E DCSSEP R67 ○ ---- ○ ---- ○ ----

472 RD00 GAC 15 CL 001 XQ 01 Cooling Water Reservoir Tank Level 32 Cooling Water Reservoir Tank Lvl 0-1500 mm AIX ---- ---- ---- ---- F U0-ARS-E DCSSEP R89D ○ ---- ○ ---- ○ ----

8.0
473 RD00 GAC 15 CP 001 XQ 01 Separator area back up cooling water pressure 23 Domestic Water Pressure 0-15 barg AIX ---- ---- ---- 1% F U0-ARS-E DCSSEP R40 ○ L ○ ---- ○ ----
(P2)

3395 RD00 HHU 21 CP 003 XQ 01 LP Separator Outlet to AFT Pressure 32 LP Separator Outlet to AFT Press 0-15 barg AIX ---- ---- ---- ---- F U0-ARS-E DCSSEP R29 ○ ---- ○ ---- ○ ----

3396 RD00 QCM 21 CP 081 XG 01 Primary acid dosing pump (A) diaphram failure detector 32 Prim acid dos pump (A) diaph FLT ON/OFF ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ---- P1 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

3397 RD00 QCM 21 CP 082 XG 01 Primary acid dosing pump (B) diaphram failure detector 32 Prim acid dos pump (B) diaph FLT ON/OFF ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ---- P1 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

3398 RD00 QCM 32 CP 081 XG 01 Secondary acid dosing pump (A) diaphram failure detector 32 Secon acid dos pmp (A) diaph FLT ON/OFF ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ---- P1 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

3399 RD00 QCM 32 CP 082 XG 01 Secondary acid dosing pump (B) diaphram failure detector 32 Secon acid dos pmp (B) diaph FLT ON/OFF ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ---- P1 ---- ---- ○ ---- Rev.4a Signal type is corrected 4a

3400 RD00 HHU 21 AA 182 XG 01 Rupture Disc at PAD-E 22 Ruputure Disc at PAD-E ON/OFF ---- DI ---- ---- NC ---- F U0-ARS-E DCSSEP ---- ---- P1 ---- ---- ○ ---- Rev.4a Contact type is corrected 4a

Rev.4a Signal from PSD box is not


3401 RD00 LBA 60 AA 081 XG 01 Rupture Disc at RD00-LAB-61-AT-001 Switch 22 Rupture Disc at Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
3402 RD00 LBA 60 AA 082 XG 01 Rupture Disc at RD00-LAB-61-AT-001 Switch 22 Rupture Disc at Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
3403 RD00 LBA 60 AA 083 XG 01 Rupture Disc at RD00-LAB-61-AT-001 Switch 22 Rupture Disc at Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
3404 RD00 LBA 80 AA 081 XG 01 Rupture Disc at RD00-LAB-80-AT-001 Switch 22 Rupture Disc at Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
3405 RD00 LBA 80 AA 082 XG 01 Rupture Disc at RD00-LAB-80-AT-001 Switch 22 Rupture Disc at Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
3406 RD00 LBA 80 AA 083 XG 01 Rupture Disc at RD00-LAB-80-AT-001 Switch 22 Rupture Disc at Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
3407 RD00 LBA 80 AA 084 XG 01 Rupture Disc at RD00-LAB-80-AT-001 Switch 22 Rupture Disc at Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
3408 RD00 LBA 80 AA 085 XG 01 Rupture Disc at RD00-LAB-81-AT-001 Switch 22 Rupture Disc at Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
3409 RD00 LBA 80 AA 086 XG 01 Rupture Disc at RD00-LAB-81-AT-001 Switch 22 Rupture Disc at Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
3410 RD00 LBA 80 AA 087 XG 01 Rupture Disc at RD00-LAB-81-AT-001 Switch 22 Rupture Disc at Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.
Rev.4a Signal from PSD box is not
3411 RD00 HHU 21 AA 081 XG 01 Rupture Disc at PAD-E Switch 28 Rupture Disc at PAD-E Switch ON/OFF ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ---- ○ ---- ---- ○ ---- 4a
existing.

3412 RD00 GAC 16 CP 001 XQ 01 Back up Cooling Water Pump Discharge Pressure 31 Back up CW Pump Discharge Press 0-15 barg AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R40 ○ L ○ ---- ○ ---- LATER

3413 RD00 GAC 16 CP 002 XG 01 Pressure Transmitter for Domestic water system 31 Press for Domestic water system 0-10 barg AII ---- ---- ---- ---- F U0-ARS-E DCSSEP ---- ○ ---- ○ ---- ○ ----

3414 RD00 CYE 10 GA 002 XG 01 Fire Alarm PAD E Substation 27 Fire Alarm PAD E Substation NORMAL/ALARM ---- DI ---- ---- NO ---- FACP NA DCSSEP ---- ○ P1 ---- ---- ○ ○ Rev.4 Change to SOE 4

3415 RD00 HAN 10 CL 001 XQ 01 Level Transmitter at water Wellpad E Pond 24 Level at water PadE Pond 0-4000 mm AII ---- ---- NO ---- FACP U0-ARS-E DCSSEP ---- ○ ---- ---- ---- ○ ----

NO
3416 RD00 GAC 15 AA 011 YB 01 Separator Station Cooling Water Reservor Tank Raw Water Inlet Valve Open Command 31 Tank Water Inlet Valve Open Cmd OFF/OPEN ---- DOW DC110 10W ---- DCSSEP U0-ARS-E F A46 ○ ---- ○ ---- ○ ----
LATCH

3417 RD00 GAC 15 CG 082 XG 01 Separator Station Cooling Water Reservor Tank Raw Water Inlet Valve Open 27 Tank Water Inlet Valve Open OFF/OPEN ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A46 ○ ---- ○ ---- ○ ----

3418 RD00 GAC 15 CG 082 XG 02 Separator Station Cooling Water Reservor Tank Raw Water Inlet Valve Close 28 Tank Water Inlet Valve Close OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP A46 ○ ---- ○ ---- ○ ----

3419 RD00 GKC 10 CF 081 XG 01 Safety shower & eye washer 26 Safety shower & eye washer OFF/CLOSE ---- DI ---- ---- NO ---- F U0-ARS-E DCSSEP ---- ○ ---- ○ ---- ○ ----

3420 RD00 CJU 10 GH 001 XG 02 WellPAD-E System Cabinet PSU or FWL Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSSEP ---- ---- ○ ---- ---- ○ ----

3421 RD00 CJU 10 GH 001 XG 01 WellPAD-E System Cabinet Fan or Thermostat Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSSEP ---- ---- ○ ---- ---- ○ ----

3422 RD00 CJU 10 GH 002 XG 02 WellPAD-E Network Cabinet PSU or FWL Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSSEP ---- ---- ○ ---- ---- ○ ----

3423 RD00 CJU 10 GH 002 XG 01 WellPAD-E Network Cabinet Fan or Thermostat Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSSEP ---- ---- ○ ---- ---- ○ ----

3424 RD00 BBB 10 XG 30 SS 6.3kV SWITCHGEAR LOSS OF CONTROL SUPPLY 31 6.3kV SSSWG CONTROL SUPPLY LOSS HEALTHY/TRIP ---- DI ---- ---- NO ---- SGSSMVSWG NA DCSSEP ---- ○ P1 ---- ---- ○ ----

3425 RD00 BFC 10 XG 70 SS SEPARATOR STATION LV DISTRIBUTION BOARD LOSS OF CONTROL SUPPLY 32 SSLVDB CONTROL POWER SUPPLY LOSS HEALTHY/TRIP ---- DI ---- ---- NO ---- RD-ELVPDB NA DCSSEP ---- ○ P1 ---- ---- ○ ----

40
3426 RD00 HHU 11 CT 051 XQ 02 Primary Acid Dosing pH sample temperature-2 30 Primary Acid Dos Sample Temp-2 0-200 degC AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R68 ○ H ○ ---- ○ ----
(P1)
40
3427 RD00 HHU 21 CT 051 XQ 02 Secondary Acid Dosing pH sample temperature-2 32 Secondary Acid Dos Sample Temp-2 0-200 degC AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R68 ○ H ○ ---- ○ ----
(P1)
40
3428 RD00 HHU 21 CT 052 XQ 02 LP Brine pH sample temperature-2 22 LP Brine Sample Temp-2 0-200 degC AII ---- ---- ---- 1% F U0-ARS-E DCSSEP R68 ○ H ○ ---- ○ ----
(P1)
6.0
3429 RD00 QFB 20 CP 001 XQ 01 SEPARATOR STATION AIR RECEIVER PRESSURE 30 SEP STATION AIR RECEIVER PRESS 0-10 barg AII ---- ---- ---- 1% F U0-ARS-E RD00DCS ---- ○ L ---- ---- ○ ---- Rev.4;Moved from COM 4
(P2)
2.DCS IO LIST FOR HARD WIRE
2-4.WELLPAD-I AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
NO
1 RD00 BBB 30 YB 01 PAD-I INCOMING LBS CLOSE COMMAND 32 PAD-I INCOMING LBS CLOSE COMMAND ---- ---- DOH DC110 5W ---- DCSRDI NA RD-IRMU ---- ---- ---- ○ ---- ○ ----
PULSE
NO
2 RD00 BBB 30 YB 02 PAD-I INCOMING LBS OPEN COMMAND 31 PAD-I INCOMING LBS OPEN COMMAND ---- ---- DOH DC110 5W ---- DCSRDI NA RD-IRMU ---- ---- ---- ○ ---- ○ ----
PULSE

3 RD00 BBB 30 XG 01 PAD-I INCOMING LOSS OF POWER CONTROL SOURCE 23 PAD-I INCOMING POW LOSS NORMAL/ALARM ---- DI ---- ---- NC ---- RD-IRMU NA DCSRDI ---- ---- ○ ---- ---- ----

(P1)

4 RD00 BBB 30 XG 02 PAD-I INCOMING REMOTE MODE SELECTED 21 PAD-I INCOMING REMOTE OFF/ON ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

5 RD00 BBB 30 XG 03 PAD-I INCOMING LBS CLOSE INDICATION 24 PAD-I INCOMING LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

6 RD00 BBB 30 XG 04 PAD-I INCOMING LBS OPEN INDICATION 23 PAD-I INCOMING LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

7 RD00 BBB 30 XG 05 PAD-I INCOMING LBS EARTH ON INDICATION 24 PAD-I INCOMING LBS EARTH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ---- ○ ---- ---- ----

(P2)
8 RD00 BBB 30 XG 15 PAD-I INCOMING SPARE 20 PAD-I INCOMING SPARE ---- ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ---- ---- ---- ---- ---- ----

NO
9 RD00 BBB 30 YB 03 PAD-I OUTGOING TO PAD-I DISTRIBUTION TRANSFORMER SPARE 31 PAD-I OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDI NA RD-IRMU ---- ---- ---- ○ ---- ○ ----
PULSE
NO
10 RD00 BBB 30 YB 04 PAD-I OUTGOING TO PAD-I DISTRIBUTION TRANSFORMER SPARE 32 PAD-I OG TO DISTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDI NA RD-IRMU ---- ---- ---- ○ ---- ○ ----
PULSE

11 RD00 BBB 30 XG 06 PAD-I OUTGOING TO PAD-I DISTRIBUTION TRANSFORMER LBS CLOSE INDICATION 32 PAD-I OG TO DSTRBTN TR LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

12 RD00 BBB 30 XG 07 PAD-I OUTGOING TO PAD-I DISTRIBUTION TRANSFORMER LBS OPEN INDICATION 32 PAD-I OG TO DSTRBTN TRA LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

13 RD00 BBB 30 XG 08 PAD-I OUTGOING TO PAD-I DISTRIBUTION TRANSFORMER LBS EATH ON INDICATION 32 PAD-I OG TO DSTRBTN TRA LBS EATH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ---- ○ ---- ---- ○ ----

14 RD00 BBB 30 XG 16 PAD-I OUTGOING TO PAD-I DISTRIBUTION TRANSFORMER SPARE 31 PAD-I OG TO DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

NO
15 RD00 BBB 30 YB 05 PAD-I OUTGOING TO PAD-L RMU SPARE 27 PAD-I OG TO PAD-L RMU SPARE ---- ---- DOH DC110 5W ---- DCSRDI NA RD-IRMU ---- ---- ---- ○ ---- ○ ----
PULSE
NO
16 RD00 BBB 30 YB 06 PAD-I OUTGOING TO PAD-L RMU SPARE 27 PAD-I OG TO PAD-L RMU SPARE ---- ---- DOH DC110 5W ---- DCSRDI NA RD-IRMU ---- ---- ---- ○ ---- ○ ----
PULSE

17 RD00 BBB 30 XG 09 PAD-I OUTGOING TO PAD-L RMU LBS CLOSE INDICATION 31 PAD-I OG TO PAD-L RMU LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

18 RD00 BBB 30 XG 10 PAD-I OUTGOING TO PAD-L RMU LBS OPEN INDICATION 30 PAD-I OG TO PAD-L RMU LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

19 RD00 BBB 30 XG 11 PAD-I OUTGOING TO PAD-L RMU LBS EARTH ON INDICATION 31 PAD-I OG TO PAD-L RMU LBS EARTH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ---- ○ ---- ---- ○ ----

20 RD00 BBB 30 XG 17 PAD-I OUTGOING TO PAD-L RMU SPARE 27 PAD-I OG TO PAD-L RMU SPARE ---- ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

NO
21 RD00 BBB 30 YB 07 PAD-I OUTGOING TO PAD-M RMU SPARE 27 PAD-I OG TO PAD-M RMU SPARE ---- ---- DOH DC110 5W ---- DCSRDI NA RD-IRMU ---- ---- ---- ○ ---- ○ ----
PULSE
NO
22 RD00 BBB 30 YB 08 PAD-I OUTGOING TO PAD-M RMU SPARE 27 PAD-I OG TO PAD-M RMU SPARE ---- ---- DOH DC110 5W ---- DCSRDI NA RD-IRMU ---- ---- ---- ○ ---- ○ ----
PULSE

23 RD00 BBB 30 XG 12 PAD-I OUTGOING TO PAD-M RMU LBS CLOSE INDICATION 31 PAD-I OG TO PAD-M RMU LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

24 RD00 BBB 30 XG 13 PAD-I OUTGOING TO PAD-M RMU LBS OPEN INDICATION 30 PAD-I OG TO PAD-M RMU LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ○ ---- ---- ---- ○ ----

25 RD00 BBB 30 XG 14 PAD-I OUTGOING TO PAD-M RMU LBS EARTH ON INDICATION 31 PAD-I OG TO PAD-M RMU LBS EARTH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ---- ○ ---- ---- ----

(P2)
26 RD00 BBB 30 XG 18 PAD-I OUTGOING TO PAD-M RMU SPARE 27 PAD-I OG TO PAD-M RMU SPARE ---- ---- DI ---- ---- NO ---- RD-IRMU NA DCSRDI ---- ---- ---- ---- ---- ---- ----

NO
27 RD00 BBB 30 YB 09 PAD-I INCOMING FROM PAD-I DISTRIBUTION TRANSFORMER (52L-I) SPARE 32 PAD-I IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDI NA RD-IRMU ---- ---- ---- ○ ---- ○ ----
PULSE
NO
28 RD00 BBB 30 YB 10 PAD-I INCOMING FROM PAD-I DISTRIBUTION TRANSFORMER (52L-I) SPARE 32 PAD-I IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDI NA RD-IRMU ---- ---- ---- ○ ---- ○ ----
PULSE

29 RD00 BFC 30 XG 01 PAD-I INCOMING FROM PAD-I DISTRIBUTION TRANSFORMER (52L-I) TRIP INDICATION 31 PAD-I IC FRM DSTRBTN TRANS TRIP ---- ---- DI ---- ---- NC ---- RD-ILVPDB NA DCSRDI ---- ---- ○ ---- ---- ----

(P1)
30 RD00 BFC 30 XG 02 PAD-I INCOMING FROM PAD-I DISTRIBUTION TRANSFORMER (52L-I) MCCB CLOSE INDICATION 31 PAD-I IC FRM DSTRBTN TRA CB CLS OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ○ ----

31 RD00 BFC 30 XG 26 PAD-I INCOMING FROM PAD-I DISTRIBUTION TRANSFORMER (52L-I) SPARE 32 PAD-I IC FRM DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ○ ----

NO
32 RD00 BFC 30 YB 01 PAD-I INCOMING FROM FUTURE GENERATOR (52LA-I) SPARE 30 PAD-I IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDI NA RD-ILVPDB ---- ---- ---- ○ ---- ○ ----
PULSE
NO
33 RD00 BFC 30 YB 02 PAD-I INCOMING FROM FUTURE GENERATOR (52LA-I) SPARE 30 PAD-I IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDI NA RD-ILVPDB ---- ---- ---- ○ ---- ○ ----
PULSE

34 RD00 BFC 30 XG 04 PAD-I INCOMING FROM FUTURE GENERATOR (52LA-I) TRIP INDICATION 29 PAD-I IC FROM FUTURE GEN TRIP ---- ---- DI ---- ---- NC ---- RD-ILVPDB NA DCSRDI ---- ---- ○ ---- ---- ----

(P1)
35 RD00 BFC 30 XG 05 PAD-I INCOMING FROM FUTURE GENERATOR (52LA-I) MCCB CLOSE INDICATION 32 PAD-I IC FRM FUTURE GEN MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ○ ----

36 RD00 BFC 30 XG 27 PAD-I INCOMING FROM FUTURE GENERATOR (52LA-I) SPARE 30 PAD-I IC FROM FUTURE GEN SPARE ---- ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ○ ----

37 RD00 BFC 30 XG 06 FEEDER TO POWER OUTLET MCCB CLOSE INDICATION 31 FEEDER TO POWER OUTLET MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ○ ----

38 RD00 BFC 30 XG 07 FEEDER TO POWER OUTLET TRIP INDICATION 27 FEEDER TO POWER OUTLET TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ----
○ ○
(P1)
39 RD00 BFC 30 XG 08 PAD-I OUTGOING TO LIGHTING PANEL PAD RD- MCCB CLOSE INDICATION 29 PAD-I OG TO LGHT PNL MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ○ ----

40 RD00 BFC 30 XG 09 PAD-I OUTGOING TO LIGHTING PANEL PAD RD- TRIP INDICATION 31 PAD-I OG TO LIGHTING PANEL TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ----
○ ○
(P1)
41 RD00 BFC 30 XG 10 PAD-I DC UPS MCCB CLOSE INDICATION 23 PAD-I DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ○ ----

42 RD00 BFC 30 XG 11 PAD-I DC UPS TRIP INDICATION 17 PAD-I DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ----
○ ○
(P1)
43 RD00 BFC 30 XG 12 PAD-I BACKUP DC UPS MCCB CLOSE INDICATION 30 PAD-I BACKUP DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ○ ----

44 RD00 BFC 30 XG 13 PAD-I BACKUP DC UPS TRIP INDICATION 24 PAD-I BACKUP DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ----
○ ○
(P1)
45 RD00 BFC 30 XG 14 PAD-I SPARE FEEDER (5 KVA) MCCB CLOSE INDICATION 32 PAD-I SAPRE FDR (5 KVA) MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ○ ----

46 RD00 BFC 30 XG 15 PAD-I SPARE FEEDER (5 KVA) TRIP INDICATION 31 PAD-I SPARE FEEDER (5 KVA) TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ----
○ ○
(P1)
47 RD00 BFC 30 XG 16 PAD-I MOV 1 - PRODUCTION WELL (1) MCCB CLOSE INDICATION 32 PAD-I MOV1 PRDCTN WELL1 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ---- ----

48 RD00 BFC 30 XG 17 PAD-I MOV 1 - PRODUCTION WELL (1) TRIP INDICATION 29 PAD-I MOV1 PRDCTN WELL1 TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ----

(P1)
49 RD00 BFC 30 XG 18 PAD-I MOV 2 - PRODUCTION WELL (2) MCCB CLOSE INDICATION 32 PAD-I MOV2 PRDCTN WLL2 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ---- ----

50 RD00 BFC 30 XG 19 PAD-I MOV 2 - PRODUCTION WELL (2) TRIP INDICATION 29 PAD-I MOV2 PRDCTN WELL2 TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ----

(P1)
2.DCS IO LIST FOR HARD WIRE
2-4.WELLPAD-I AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
51 RD00 BFC 30 XG 20 PAD-I MOV 3 - PRODUCTION WELL (3) MCCB CLOSE INDICATION 32 PAD-I MOV3 PRDCTN WLL3 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ---- ----


52 RD00 BFC 30 XG 21 PAD-I MOV 3 - PRODUCTION WELL (3) TRIP INDICATION 29 PAD-I MOV3 PRDCTN WELL3 TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ----
(P1)
53 RD00 BFC 30 XG 22 PAD-I MOV 4 - PRODUCTION WELL (4) MCCB CLOSE INDICATION 32 PAD-I MOV4 PRDCTN WLL4 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ---- ----

54 RD00 BFC 30 XG 23 PAD-I MOV 4 - PRODUCTION WELL (4) TRIP INDICATION 29 PAD-I MOV4 PRDCTN WELL4 TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ----

(P1)

55 RD00 BFC 30 XG 24 PAD-I MOV 5 - PRODUCTION WELL (5) MCCB CLOSE INDICATION 32 PAD-I MOV5 PRDCTN WLL5 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ---- ----

56 RD00 BFC 30 XG 25 PAD-I MOV 5 - PRODUCTION WELL (5) TRIP INDICATION 29 PAD-I MOV5 PRDCTN WELL5 TRIP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-ILVPDB NA DCSRDI ---- ○ ---- ---- ---- ----

(P1)
57 RD00 BFV 30 XG 01 PAD-I DISTRIBUTION TRANSFORMER OIL TEMPERATURE ALARM 31 PAD-I DSTRBTNN TRA OIL TEMP ANN OFF/ON ---- DI ---- ---- NO ---- RD-ITR NA DCSRDI ---- ---- ○ ---- ---- ----

(P2)
58 RD00 BFV 30 XG 02 PAD-I DISTRIBUTION TRANSFORMER OIL TEMPERATURE TRIP 32 PAD-I DSTRBTNN TRA OIL TEMP TRIP OFF/ON ---- DI ---- ---- NO ---- RD-ITR NA DCSRDI ---- ---- ○ ---- ---- ○ ○
(P1)
59 RD00 BFV 30 XG 03 PAD-I DISTRIBUTION TRANSFORMER WINDING TEMPERATURE ALARM 32 PAD-I DSTRBTNN TR WNDNG TEMP ANN OFF/ON ---- DI ---- ---- NO ---- RD-ITR NA DCSRDI ---- ---- ○ ---- ---- ----

(P2)
60 RD00 BFV 30 XG 04 PAD-I DISTRIBUTION TRANSFORMER WINDING TEMPERATURE TRIP 32 PAD-I DSTRBTNN TR WNDNG TEMP TRP OFF/ON ---- DI ---- ---- NO ---- RD-ITR NA DCSRDI ---- ---- ○ ---- ---- ○ ○
(P1)

61 RD00 BFV 30 XG 05 PAD-I DISTRIBUTION TRANSFORMER OIL LEVEL 29 PAD-I DSTRBTN TRANS OIL LEVEL OFF/ON ---- DI ---- ---- NO ---- RD-ITR NA DCSRDI ---- ---- ---- ---- ○ ○
(P1)
62 RD00 BFV 30 XG 06 PAD-I DISTRIBUTION TRANSFORMER PRESSURE RELIEF DEVICE 32 PAD-I DSTRBTN TRANS PRESS RELIEF OFF/ON ---- DI ---- ---- NO ---- RD-ITR NA DCSRDI ---- ---- ○ ---- ---- ○ ○
(P1)
63 RD00 BFV 30 XG 07 PAD-I DISTRIBUTION TRANSFORMER SPARE 31 PAD-I DSTRBTN TRANSFORMER SPARE ---- ---- DI ---- ---- NO ---- RD-ITR NA DCSRDI ---- ---- ---- ---- ---- ○ ○

64 RD00 BFV 30 XG 08 PAD-I DISTRIBUTION TRANSFORMER SPARE 25 PAD-I DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-ITR NA DCSRDI ---- ---- ---- ---- ---- ○ ○

65 RD00 BRT 30 XQ 01 PAD-I DC UPS SYSTEM 110VDC BUS VOLTAGE 32 PAD-I DC UPS SYS 110VDC BUS VLTG 0-110 VDC AIX ---- ---- ---- ---- F NA DCSRDI ---- ○ ---- ---- ---- ○ ----


66 RD00 BRT 30 XG 09 PAD-I DC UPS SYSTEM 110VDC COMMON OUTPUT FEEDER TRIP 32 PAD-I DC UPS 110VDC OTPT FDR TRP NORMAL/ALARM ---- DI ---- ---- NC ---- F NA DCSRDI ---- ---- ---- ---- ○ ----
(P1)

67 RD00 CYE 30 GA 002 XG 01 Fire Alarm PAD I Substation 27 Fire Alarm PAD I Substation NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI ---- ---- ○ ---- ---- ○ ○
(P1)
9.0
68 RDI1 LBA 11 CP 001 XQ 01 Pressure Transmitter at Production Well RD-I1 27 Production Well RD-I1 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDI R30 ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
69 RDI1 LBA 11 CP 002 XQ 01 Pressure Transmitter at Production Well RD-I1 27 Production Well RD-I1 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDI R30 ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
70 RDI2 LBA 12 CP 001 XQ 01 Pressure Transmitter at Production Well RD-I2 27 Production Well RD-I2 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDI ---- ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
71 RDI2 LBA 12 CP 002 XQ 01 Pressure Transmitter at Production Well RD-I2 27 Production Well RD-I2 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDI R30 ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
72 RDI3 LBA 13 CP 001 XQ 01 Pressure Transmitter at Production Well RD-I3 27 Production Well RD-I3 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDI ---- ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
73 RDI3 LBA 13 CP 002 XQ 01 Pressure Transmitter at Production Well RD-I3 27 Production Well RD-I3 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDI R30 ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
74 RDI4 LBA 14 CP 001 XQ 01 Pressure Transmitter at Production Well RD-I4 27 Production Well RD-I4 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDI ---- ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
75 RDI4 LBA 14 CP 002 XQ 01 Pressure Transmitter at Production Well RD-I4 27 Production Well RD-I4 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDI R30 ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
76 RDI5 LBA 15 CP 001 XQ 01 Pressure Transmitter at Production Well RD-I5 27 Production Well RD-I5 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDI ---- ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
77 RDI5 LBA 15 CP 002 XQ 01 Pressure Transmitter at Production Well RD-I5 27 Production Well RD-I5 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDI R30 ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
o
78 RDI1 LBA 11 CT 001 XQ 01 Temperature Transmitter at Production Well RD-I1 26 Production Well RD-I1 TEMP 0 - 300 C AII ---- ---- ---- ---- F NA DCSRDI ---- ○ ---- ---- ---- ○ ----

o
79 RDI2 LBA 12 CT 001 XQ 01 Temperature Transmitter at Production Well RD-I2 26 Production Well RD-I2 TEMP 0 - 300 C AII ---- ---- ---- ---- F NA DCSRDI ---- ○ ---- ---- ---- ○ ----

o
80 RDI3 LBA 13 CT 001 XQ 01 Temperature Transmitter at Production Well RD-I3 26 Production Well RD-I3 TEMP 0 - 300 C AII ---- ---- ---- ---- F NA DCSRDI ---- ○ ---- ---- ---- ○ ----

o
81 RDI4 LBA 14 CT 001 XQ 01 Temperature Transmitter at Production Well RD-I4 26 Production Well RD-I4 TEMP 0 - 300 C AII ---- ---- ---- ---- F NA DCSRDI ---- ○ ---- ---- ---- ○ ----

o
82 RDI5 LBA 15 CT 001 XQ 01 Temperature Transmitter at Production Well RD-I5 26 Production Well RD-I5 TEMP 0 - 300 C AII ---- ---- ---- ---- F NA DCSRDI ---- ○ ---- ---- ---- ○ ----

40.5
83 RDI1 LBA 11 CF 001 XQ 01 Flow Transmitter at Production Well RD-I1 26 Production Well RD-I1 FLOW 0 - 45 kg/s AII ---- ---- ---- 1% F NA DCSRDI ---- ○ H ---- ---- ○ ----
(P2)
94.5
84 RDI2 LBA 12 CF 001 XQ 01 Flow Transmitter at Production Well RD-I2 26 Production Well RD-I2 FLOW 0 - 45 kg/s AII ---- ---- ---- 1% F NA DCSRDI ---- ○ H ---- ---- ○ ----
(P2)
40.5
85 RDI3 LBA 13 CF 001 XQ 01 Flow Transmitter at Production Well RD-I3 26 Production Well RD-I3 FLOW 0 - 45 kg/s AII ---- ---- ---- 1% F NA DCSRDI ---- ○ H ---- ---- ○ ----
(P2)
40.5
86 RDI4 LBA 14 CF 001 XQ 01 Flow Transmitter at Production Well RD-I4 26 Production Well RD-I4 FLOW 0 - 45 kg/s AII ---- ---- ---- 1% F NA DCSRDI ---- ○ H ---- ---- ○ ----
(P2)
40.5
87 RDI5 LBA 15 CF 001 XQ 01 Flow Transmitter at Production Well RD-I5 26 Production Well RD-I5 FLOW 0 - 45 kg/s AII ---- ---- ---- 1% F NA DCSRDI ---- ○ H ---- ---- ○ ----
(P2)

88 RDI1 LBA 11 FH 101 YJ 01 VALVE OPEN & CLOSE COMMAND MOV FCV-I1 26 HP WHCV RD-I1 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDI NA F C75 ○ ---- ○ ---- ○ ----

89 RDI1 LBA 11 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-I1 30 VALVE OPEN POSITION MOV FCV-I1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

90 RDI1 LBA 11 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-I1 31 VALVE CLOSE POSITION MOV FCV-I1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

91 RDI1 LBA 11 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-I1 22 HP WHCV RD-I1 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

92 RDI1 LBA 11 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-I1 22 TORQUE OVER MOV FCV-I1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ○ ---- ---- ○ ----

93 RDI1 LBA 11 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-I1 31 REMOTE MODE SELECTED MOV FCV-I1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

94 RDI1 LBA 11 AA 101 XG 03 VALVE FAILURE -MOV FCV-I1 24 VALVE FAILURE MOV FCV-I1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ○ ---- ---- ○ ----

95 RDI1 LBA 11 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-I1 31 LOSS OF POWER SOURCE MOV FCV-I1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ○ ---- ---- ○ ----

96 RDI2 LBA 12 FH 101 YJ 01 VALVE OPEN & CLOSE COMMAND MOV FCV-I2 26 HP WHCV RD-I2 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDI NA F C75 ○ ---- ○ ---- ○ ----

97 RDI2 LBA 12 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-I2 30 VALVE OPEN POSITION MOV FCV-I2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

98 RDI2 LBA 12 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-I2 31 VALVE CLOSE POSITION MOV FCV-I2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

99 RDI2 LBA 12 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-I2 22 HP WHCV RD-I2 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

100 RDI2 LBA 12 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-I2 22 TORQUE OVER MOV FCV-I2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ○ ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-4.WELLPAD-I AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
101 RDI2 LBA 12 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-I2 31 REMOTE MODE SELECTED MOV FCV-I2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

102 RDI2 LBA 12 AA 101 XG 03 VALVE FAILURE -MOV FCV-I2 24 VALVE FAILURE MOV FCV-I2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ○ ---- ---- ○ ----

103 RDI2 LBA 12 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-I2 31 LOSS OF POWER SOURCE MOV FCV-I2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ○ ---- ---- ○ ----

104 RDI3 LBA 13 FH 101 YJ 01 VALVE OPEN & CLOSE COMMAND MOV FCV-I3 26 HP WHCV RD-I3 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDI NA F C75 ○ ---- ○ ---- ○ ----

105 RDI3 LBA 13 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-I3 30 VALVE OPEN POSITION MOV FCV-I3 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

106 RDI3 LBA 13 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-I3 31 VALVE CLOSE POSITION MOV FCV-I3 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

107 RDI3 LBA 13 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-I3 22 HP WHCV RD-I3 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

108 RDI3 LBA 13 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-I3 22 TORQUE OVER MOV FCV-I3 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ○ ---- ---- ○ ----

109 RDI3 LBA 13 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-I3 31 REMOTE MODE SELECTED MOV FCV-I3 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ---- ---- ---- ○ ----

110 RDI3 LBA 13 AA 101 XG 03 VALVE FAILURE -MOV FCV-I3 24 VALVE FAILURE MOV FCV-I3 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ○ ---- ---- ○ ----

111 RDI3 LBA 13 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-I3 31 LOSS OF POWER SOURCE MOV FCV-I3 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C75 ○ ○ ---- ---- ○ ----

112 RDI4 LBA 14 FH 101 YJ 01 VALVE OPEN & CLOSE COMMAND MOV FCV-I4 26 HP WHCV RD-I4 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDI NA F C76 ○ ---- ○ ---- ○ ----

113 RDI4 LBA 14 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-I4 30 VALVE OPEN POSITION MOV FCV-I4 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ---- ---- ---- ○ ----

114 RDI4 LBA 14 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-I4 31 VALVE CLOSE POSITION MOV FCV-I4 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ---- ---- ---- ○ ----

115 RDI4 LBA 14 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-I4 22 HP WHCV RD-I4 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDI C76 ○ ---- ---- ---- ○ ----

116 RDI4 LBA 14 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-I4 22 TORQUE OVER MOV FCV-I4 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ○ ---- ---- ○ ----

117 RDI4 LBA 14 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-I4 31 REMOTE MODE SELECTED MOV FCV-I4 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ---- ---- ---- ○ ----

118 RDI4 LBA 14 AA 101 XG 03 VALVE FAILURE -MOV FCV-I4 24 VALVE FAILURE MOV FCV-I4 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ○ ---- ---- ○ ----

119 RDI4 LBA 14 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-I4 31 LOSS OF POWER SOURCE MOV FCV-I4 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ○ ---- ---- ○ ----

120 RDI5 LBA 15 FH 101 YJ 01 VALVE OPEN & CLOSE COMMAND MOV FCV-I5 26 HP WHCV RD-I5 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDI NA F C76 ○ ---- ○ ---- ○ ----

121 RDI5 LBA 15 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-I5 30 VALVE OPEN POSITION MOV FCV-I5 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ---- ---- ---- ○ ----

122 RDI5 LBA 15 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-I5 31 VALVE CLOSE POSITION MOV FCV-I5 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ---- ---- ---- ○ ----

123 RDI5 LBA 15 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-I5 22 HP WHCV RD-I5 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDI C76 ○ ---- ---- ---- ○ ----

124 RDI5 LBA 15 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-I5 22 TORQUE OVER MOV FCV-I5 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ○ ---- ---- ○ ----

125 RDI5 LBA 15 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-I5 31 REMOTE MODE SELECTED MOV FCV-I5 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ---- ---- ---- ○ ----

126 RDI5 LBA 15 AA 101 XG 03 VALVE FAILURE -MOV FCV-I5 24 VALVE FAILURE MOV FCV-I5 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ○ ---- ---- ○ ----

127 RDI5 LBA 15 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-I5 31 LOSS OF POWER SOURCE MOV FCV-I5 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDI C76 ○ ○ ---- ---- ○ ----

128 RD00 LBA 30 CP 002 XQ 01 PRESSURE TRANSMITTER TO 2 PHASE HEADER 23 PRESS TO 2 PHASE HEADER 0 -20 Bar G AII ---- ---- ---- ---- F NA DCSRDI R30 ○ H ---- ---- ○ ----

129 RD00 CJU 30 GH 001 XG 02 WellPAD-I System Cabinet PSU or FWL Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSRDI ---- ---- ○ ---- ---- ○ ----

130 RD00 CJU 30 GH 001 XG 01 WellPAD-I System Cabinet Fan or Thermostat Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSRDI ---- ---- ○ ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-5.WELLPAD-L AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
1 RD00 BBB 40 XG 01 PAD-L INCOMING LBS CLOSE INDICATION 24 PAD-L INCOMING LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ○ ---- ---- ---- ○ ----

2 RD00 BBB 40 XG 02 PAD-L INCOMING LBS OPEN INDICATION 23 PAD-L INCOMING LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ○ ---- ---- ---- ○ ----

3 RD00 BBB 40 XG 03 PAD-L INCOMING LBS EARTH ON INDICATION 24 PAD-L INCOMING LBS EARTH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ---- ○ ---- ---- ----

(P2)

4 RD00 BBB 40 XG 07 PAD-L INCOMING SPARE 20 PAD-L INCOMING SPARE ---- ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ---- ---- ---- ---- ---- ----

NO
5 RD00 BBB 40 YB 01 PAD-L OUTGOING TO PAD-L DISTRIBUTION TRANSFORMER SPARE 31 PAD-L OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDL RD-LRMU ---- ---- ○ ---- ○ ----
PULSE
NO
6 RD00 BBB 40 YB 02 PAD-L OUTGOING TO PAD-L DISTRIBUTION TRANSFORMER SPARE 31 PAD-L OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDL RD-LRMU ---- ---- ○ ---- ○ ----
PULSE

7 RD00 BBB 40 XG 04 PAD-L OUTGOING TO PAD-L DISTRIBUTION TRANSFORMER LBS CLOSE INDICATION 32 PAD-L OG TO DSTRBTN TR LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ---- ---- ---- ---- ○ ----

8 RD00 BBB 40 XG 05 PAD-L OUTGOING TO PAD-L DISTRIBUTION TRANSFORMER LBS OPEN INDICATION 32 PAD-L OG TO DSTRBTN TRA LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ---- ---- ---- ---- ○ ----

9 RD00 BBB 40 XG 06 PAD-L OUTGOING TO PAD-L DISTRIBUTION TRANSFORMER LBS EATH ON INDICATION 32 PAD-L OG TO DSTRBTN TRA LBS EATH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ○ ---- ---- ----
○ ○
(P2)

10 RD00 BBB 40 XG 08 PAD-L OUTGOING TO PAD-L DISTRIBUTION TRANSFORMER SPARE 31 PAD-L OG TO DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ○ ---- ---- ---- ○ ----

NO
11 RD00 BBB 40 YB 03 PAD-L SPARE FEEDER FUTURE CLOSE COMMAND 31 PAD-L SPR FEEDER FUTURE CLS CMD ---- ---- DOH DC110 5W ---- DCSRDL RD-LRMU ---- ---- ○ ---- ○ ----
PULSE
NO
12 RD00 BBB 40 YB 04 PAD-L SPARE FEEDER FUTURE OPEN COMMAND 32 PAD-L SPR FEEDER FUTURE OPEN CMD ---- ---- DOH DC110 5W ---- DCSRDL RD-LRMU ---- ---- ○ ---- ○ ----
PULSE

13 RD00 BBB 40 XG 09 PAD-L SPARE FEEDER FUTURE TRIP INDICATION 30 PAD-L SPARE FEEDER FUTURE TRIP ---- ---- DI ---- ---- NC ---- RD-LRMU DCSRDL ---- ○ ---- ---- ----

(P1)

14 RD00 BBB 40 XG 10 PAD-L SPARE FEEDER FUTURE LOSS OF POWER CONTROL SOURCE 32 PAD-L SPR FEEDER FUTURE POW LOSS ---- ---- DI ---- ---- NC ---- RD-LRMU DCSRDL ---- ---- ---- ○ ----
(P1)
15 RD00 BBB 40 XG 11 PAD-L SPARE FEEDER FUTURE REMOTE MODE SELECTED 32 PAD-L SPARE FEEDER FUTURE REMOTE ---- ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ○ ---- ---- ---- ○ ----

16 RD00 BBB 40 XG 12 PAD-L SPARE FEEDER FUTURE LBS CLOSE INDICATION 31 PAD-L SPR FEEDER FUTURE LBS CLS ---- ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ○ ---- ---- ---- ○ ----

17 RD00 BBB 40 XG 13 PAD-L SPARE FEEDER FUTURE LBS OPEN INDICATION 32 PAD-L SPR FEEDER FUTURE LBS OPEN ---- ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ○ ---- ---- ---- ○ ----

18 RD00 BBB 40 XG 14 PAD-L SPARE FEEDER FUTURE LBS EARTH ON INDICATION 32 PAD-L SPARE FDR FUTURE LBS EARTH ---- ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ○ ---- ---- ---- ○ ----

19 RD00 BBB 40 XG 15 PAD-L SPARE FEEDER FUTURE SPARE 31 PAD-L SPARE FEEDER FUTURE SPARE ---- ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ○ ---- ---- ---- ○ ----

20 RD00 BBB 40 XG 16 PAD-L SPARE FEEDER FUTURE SPARE 31 PAD-L SPARE FEEDER FUTURE SPARE ---- ---- DI ---- ---- NO ---- RD-LRMU DCSRDL ---- ---- ---- ---- ---- ----

NO
21 RD00 BBB 40 YB 05 PAD-L INCOMING FROM PAD-L DISTRIBUTION TRANSFORMER (52L-L) SPARE 32 PAD-L IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDL RD-LVPDB ---- ---- ○ ---- ○ ----
PULSE
NO
22 RD00 BBB 40 YB 06 PAD-L INCOMING FROM PAD-L DISTRIBUTION TRANSFORMER (52L-L) SPARE 32 PAD-L IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDL RD-LVPDB ---- ---- ○ ---- ○ ----
PULSE

23 RD00 BFC 40 XG 01 PAD-L INCOMING FROM PAD-L DISTRIBUTION TRANSFORMER (52L-L) TRIP INDICATION 31 PAD-L IC FRM DSTRBTN TRANS TRIP NORMAL/ALARM ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ---- ○ ---- ---- ----

(P1)
24 RD00 BFC 40 XG 02 PAD-L INCOMING FROM PAD-L DISTRIBUTION TRANSFORMER (52L-L) MCCB CLOSE INDICATION 31 PAD-L IC FRM DSTRBTN TRA CB CLS OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

25 RD00 BFC 40 XG 23 PAD-L INCOMING FROM PAD-L DISTRIBUTION TRANSFORMER (52L-L) SPARE 32 PAD-L IC FRM DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

NO
26 RD00 BFC 40 YB 01 PAD-L INCOMING FROM FUTURE GENERATOR (52LA-L) SPARE 30 PAD-L IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDL RD-LLVPDB ---- ---- ○ ---- ○ ----
PULSE
NO
27 RD00 BFC 40 YB 02 PAD-L INCOMING FROM FUTURE GENERATOR (52LA-L) SPARE 30 PAD-L IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDL RD-LLVPDB ---- ---- ○ ---- ○ ----
PULSE

28 RD00 BFC 40 XG 03 PAD-L INCOMING FROM FUTURE GENERATOR (52LA-L) TRIP INDICATION 29 PAD-L IC FROM FUTURE GEN TRIP NORMAL/ALARM ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ---- ---- ---- ○ ----
(P1)
29 RD00 BFC 40 XG 04 PAD-L INCOMING FROM FUTURE GENERATOR (52LA-L) MCCB CLOSE INDICATION 32 PAD-L IC FRM FUTURE GEN MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

30 RD00 BFC 40 XG 24 PAD-L INCOMING FROM FUTURE GENERATOR (52LA-L) SPARE 30 PAD-L IC FROM FUTURE GEN SPARE ---- ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

31 RD00 BFC 40 XG 05 FEEDER TO POWER OUTLET MCCB CLOSE INDICATION 31 FEEDER TO POWER OUTLET MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

32 RD00 BFC 40 XG 06 FEEDER TO POWER OUTLET TRIP INDICATION 27 FEEDER TO POWER OUTLET TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ○ ---- ---- ----
○ ○
(P1)
33 RD00 BFC 40 XG 07 PAD-L OUTGOING TO LIGHTING PANEL PAD RD- MCCB CLOSE INDICATION 29 PAD-L OG TO LGHT PNL MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

34 RD00 BFC 40 XG 08 PAD-L OUTGOING TO LIGHTING PANEL PAD RD- TRIP INDICATION 31 PAD-L OG TO LIGHTING PANEL TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ○ ---- ---- ----
○ ○
(P1)
35 RD00 BFC 40 XG 09 PAD-L DC UPS MCCB CLOSE INDICATION 23 PAD-L DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

36 RD00 BFC 40 XG 10 PAD-L DC UPS TRIP INDICATION 17 PAD-L DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ○ ---- ---- ----
○ ○
(P1)
37 RD00 BFC 40 XG 11 PAD-L BACKUP DC UPS MCCB CLOSE INDICATION 30 PAD-L BACKUP DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

38 RD00 BFC 40 XG 12 PAD-L BACKUP DC UPS TRIP INDICATION 24 PAD-L BACKUP DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ○ ---- ---- ----
○ ○
(P1)
39 RD00 BFC 40 XG 25 PAD-L SPARE FEEDER (5 KVA) MCCB CLOSE INDICATION 32 PAD-L SAPRE FDR (5 KVA) MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

40 RD00 BFC 40 XG 26 PAD-L SPARE FEEDER (5 KVA) TRIP INDICATION 31 PAD-L SPARE FEEDER (5 KVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ○ ---- ---- ----
○ ○
(P1)
41 RD00 BFC 40 XG 13 PAD-L MOV 1 - PRODUCTION WELL (1) MCCB CLOSE INDICATION 32 PAD-L MOV1 PRDCTN WELL1 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

42 RD00 BFC 40 XG 14 PAD-L MOV 1 - PRODUCTION WELL (1) TRIP INDICATION 29 PAD-L MOV1 PRDCTN WELL1 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ○ ---- ---- ----
○ ○
(P1)
43 RD00 BFC 40 XG 15 PAD-L MOV 2 - PRODUCTION WELL (2) MCCB CLOSE INDICATION 32 PAD-L MOV2 PRDCTN WLL2 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

44 RD00 BFC 40 XG 16 PAD-L MOV 2 - PRODUCTION WELL (2) TRIP INDICATION 29 PAD-L MOV2 PRDCTN WELL2 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ○ ---- ---- ----
○ ○
(P1)
45 RD00 BFC 40 XG 17 PAD-L MOV 3 - PRODUCTION WELL (3) MCCB CLOSE INDICATION 32 PAD-L MOV3 PRDCTN WLL3 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

46 RD00 BFC 40 XG 18 PAD-L MOV 3 - PRODUCTION WELL (3) TRIP INDICATION 29 PAD-L MOV3 PRDCTN WELL3 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ○ ---- ---- ----
○ ○
(P1)
47 RD00 BFC 40 XG 19 PAD-L MOV 4 - PRODUCTION WELL (4) MCCB CLOSE INDICATION 32 PAD-L MOV4 PRDCTN WLL4 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----

48 RD00 BFC 40 XG 20 PAD-L MOV 4 - PRODUCTION WELL (4) TRIP INDICATION 29 PAD-L MOV4 PRDCTN WELL4 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ○ ---- ---- ----
○ ○
(P1)
49 RD00 BFC 40 XG 21 PAD-L MOV 5 - PRODUCTION WELL (5) MCCB CLOSE INDICATION 32 PAD-L MOV5 PRDCTN WLL5 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-LLVPDB DCSRDL ○ ---- ---- ---- ○ ----


50 RD00 BFC 40 XG 22 PAD-L MOV 5 - PRODUCTION WELL (5) TRIP INDICATION 29 PAD-L MOV5 PRDCTN WELL5 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-LLVPDB DCSRDL ○ ---- ---- ○ ----
(P1)
2.DCS IO LIST FOR HARD WIRE
2-5.WELLPAD-L AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
51 RD00 BFV 40 XG 01 PAD L DISTRIBUTION TRANSFORMER OIL TEMPERATURE ALARM 31 PAD-L DSTRBTNN TRA OIL TEMP ANN NORMAL/ALARM ---- DI ---- ---- NO ---- RD-LTR DCSRDL ---- ○ ---- ---- ----

(P2)

52 RD00 BFV 40 XG 02 PAD L DISTRIBUTION TRANSFORMER OIL TEMPERATURE TRIP 32 PAD-L DSTRBTNN TRA OIL TEMP TRIP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-LTR DCSRDL ---- ---- ---- ○ ○
(P1)
53 RD00 BFV 40 XG 03 PAD L DISTRIBUTION TRANSFORMER WINDING TEMPERATURE ALARM 32 PAD-L DSTRBTNN TR WNDNG TEMP ANN NORMAL/ALARM ---- DI ---- ---- NO ---- RD-LTR DCSRDL ---- ○ ---- ---- ----

(P2)

54 RD00 BFV 40 XG 04 PAD L DISTRIBUTION TRANSFORMER WINDING TEMPERATURE TRIP 32 PAD-L DSTRBTNN TR WNDNG TEMP TRP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-LTR DCSRDL ---- ---- ---- ○ ○
(P1)

55 RD00 BFV 40 XG 05 PAD L DISTRIBUTION TRANSFORMER OIL LEVEL 29 PAD-L DSTRBTN TRANS OIL LEVEL NORMAL/ALARM ---- DI ---- ---- NO ---- RD-LTR DCSRDL ---- ---- ---- ○ ○
(P1)
56 RD00 BFV 40 XG 06 PAD L DISTRIBUTION TRANSFORMER PRESSURE RELIEF DEVICE 32 PAD-L DSTRBTN TRANS PRESS RELIEF NORMAL/ALARM ---- DI ---- ---- NO ---- RD-LTR DCSRDL ---- ○ ---- ---- ○ ○
(P1)
57 RD00 BFV 40 XG 07 PAD-L DISTRIBUTION TRANSFORMER SPARE 31 PAD-L DSTRBTN TRANSFORMER SPARE ---- ---- DI ---- ---- NO ---- RD-LTR DCSRDL ---- ---- ---- ---- ○ ○

58 RD00 BFV 40 XG 08 PAD-L DISTRIBUTION TRANSFORMER SPARE 25 PAD-L DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-LTR DCSRDL ---- ---- ---- ---- ○ ○

59 RD00 BRT 40 XQ 01 PAD-L DC UPS SYSTEM 110VDC BUS VOLTAGE 32 PAD-L DC UPS SYS 110VDC BUS VLTG 0-110 VDC AIX ---- ---- ---- ---- F DCSRDL ○ ---- ---- ---- ○ ----

60 RD00 BRT 40 XG 01 PAD-L DC UPS SYSTEM 110VDC COMMON OUTPUT FEEDER TRIP 32 PAD-L DC UPS 110VDC OTPT FDR TRP NORMAL/ALARM ---- DI ---- ---- NC ---- F DCSRDL ---- ○ ---- ---- ----

(P1)
61 RD00 CYE 40 GA 002 XG 01 Fire Alarm PAD L Substation 27 Fire Alarm PAD L Substation NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL ---- ○ ---- ---- ○ ○
(P1)
9.0
62 RDL1 LBA 11 CP 001 XQ 01 Pressure Transmitter at Production Well RD-L1 27 Production Well RD-L1 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F DCSRDL ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
63 RDL1 LBA 11 CP 002 XQ 01 Pressure Transmitter at Production Well RD-L1 27 Production Well RD-L1 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F DCSRDL R30A ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
64 RDL2 LBA 12 CP 001 XQ 01 Pressure Transmitter at Production Well RD-L2 27 Production Well RD-L2 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F DCSRDL ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
65 RDL2 LBA 12 CP 002 XQ 01 Pressure Transmitter at Production Well RD-L2 27 Production Well RD-L2 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F DCSRDL R30A ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
66 RDL3 LBA 13 CP 001 XQ 01 Pressure Transmitter at Production Well RD-L3 27 Production Well RD-L3 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F DCSRDL ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
67 RDL3 LBA 13 CP 002 XQ 01 Pressure Transmitter at Production Well RD-L3 27 Production Well RD-L3 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F DCSRDL R30A ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
68 RDL4 LBA 14 CP 001 XQ 01 Pressure Transmitter at Production Well RD-L4 27 Production Well RD-L4 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F DCSRDL ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
69 RDL4 LBA 14 CP 002 XQ 01 Pressure Transmitter at Production Well RD-L4 27 Production Well RD-L4 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F DCSRDL R30A ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
70 RDL5 LBA 15 CP 001 XQ 01 Pressure Transmitter at Production Well RD-L5 27 Production Well RD-L5 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F DCSRDL ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
71 RDL5 LBA 15 CP 002 XQ 01 Pressure Transmitter at Production Well RD-L5 27 Production Well RD-L5 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F DCSRDL R30A ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
o
72 RDL1 LBA 11 CT 001 XQ 01 Temperature Transmitter at Production Well RD-L1 26 Production Well RD-L1 TEMP 0 - 300 C AII ---- ---- ---- ---- F DCSRDL ○ ---- ---- ---- ○ ----

o
73 RDL2 LBA 12 CT 001 XQ 01 Temperature Transmitter at Production Well RD-L2 26 Production Well RD-L2 TEMP 0 - 300 C AII ---- ---- ---- ---- F DCSRDL ○ ---- ---- ---- ○ ----

o
74 RDL3 LBA 13 CT 001 XQ 01 Temperature Transmitter at Production Well RD-L3 26 Production Well RD-L3 TEMP 0 - 300 C AII ---- ---- ---- ---- F DCSRDL ○ ---- ---- ---- ○ ----

o
75 RDL4 LBA 14 CT 001 XQ 01 Temperature Transmitter at Production Well RD-L4 26 Production Well RD-L4 TEMP 0 - 300 C AII ---- ---- ---- ---- F DCSRDL ○ ---- ---- ---- ○ ----

o
76 RDL5 LBA 15 CT 001 XQ 01 Temperature Transmitter at Production Well RD-L5 26 Production Well RD-L5 TEMP 0 - 300 C AII ---- ---- ---- ---- F DCSRDL ○ ---- ---- ---- ○ ----

40.5
77 RDL1 LBA 11 CF 001 XQ 01 Flow Transmitter at Production Well RD-L1 26 Production Well RD-L1 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F DCSRDL ○ H ---- ---- ○ ----
(P2)
40.5
78 RDL2 LBA 12 CF 001 XQ 01 Flow Transmitter at Production Well RD-L2 26 Production Well RD-L2 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F DCSRDL ○ H ---- ---- ○ ----
(P2)
40.5
79 RDL3 LBA 13 CF 001 XQ 01 Flow Transmitter at Production Well RD-L3 26 Production Well RD-L3 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F DCSRDL ○ H ---- ---- ○ ----
(P2)
40.5
80 RDL4 LBA 14 CF 001 XQ 01 Flow Transmitter at Production Well RD-L4 26 Production Well RD-L4 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F DCSRDL ○ H ---- ---- ○ ----
(P2)
40.5
81 RDL5 LBA 15 CF 001 XQ 01 Flow Transmitter at Production Well RD-L5 26 Production Well RD-L5 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F DCSRDL ○ H ---- ---- ○ ----
(P2)

82 RDL1 LBA 11 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-L1 26 HP WHCV RD-L1 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDL F C77 ○ ---- ○ ---- ○ ----

83 RDL1 LBA 11 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-L1 30 VALVE OPEN POSITION MOV FCV-L1 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----

84 RDL1 LBA 11 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-L1 31 VALVE CLOSE POSITION MOV FCV-L1 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----

85 RDL1 LBA 11 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-L1 22 HP WHCV RD-L1 POSITION 0 -100 % AIX ---- ---- ---- ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----

86 RDL1 LBA 11 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-L1 22 TORQUE OVER MOV FCV-L1 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ○ ---- ---- ○ ----

87 RDL1 LBA 11 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-L1 31 REMOTE MODE SELECTED MOV FCV-L1 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----

88 RDL1 LBA 11 AA 101 XG 03 VALVE FAILURE -MOV FCV-L1 24 VALVE FAILURE MOV FCV-L1 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ○ ---- ---- ○ ----

89 RDL1 LBA 11 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-L1 31 LOSS OF POWER SOURCE MOV FCV-L1 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ○ ---- ---- ○ ----

90 RDL2 LBA 12 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-L2 26 HP WHCV RD-L2 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDL F C77 ○ ---- ○ ---- ○ ----

91 RDL2 LBA 12 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-L2 30 VALVE OPEN POSITION MOV FCV-L2 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----

92 RDL2 LBA 12 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-L2 31 VALVE CLOSE POSITION MOV FCV-L2 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----

93 RDL2 LBA 12 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-L2 22 HP WHCV RD-L2 POSITION 0 -100 % AIX ---- ---- ---- 1% F DCSRDL C77 ○ ---- ---- ---- ○ ----

94 RDL2 LBA 12 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-L2 22 TORQUE OVER MOV FCV-L2 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ○ ---- ---- ○ ----

95 RDL2 LBA 12 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-L2 31 REMOTE MODE SELECTED MOV FCV-L2 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----

96 RDL2 LBA 12 AA 101 XG 03 VALVE FAILURE -MOV FCV-L2 24 VALVE FAILURE MOV FCV-L2 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ○ ---- ---- ○ ----

97 RDL2 LBA 12 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-L2 31 LOSS OF POWER SOURCE MOV FCV-L2 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ○ ---- ---- ○ ----

98 RDL3 LBA 13 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-L3 26 HP WHCV RD-L3 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDL F C77 ○ ---- ○ ---- ○ ----

99 RDL3 LBA 13 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-L3 30 VALVE OPEN POSITION MOV FCV-L3 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----

100 RDL3 LBA 13 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-L3 31 VALVE CLOSE POSITION MOV FCV-L3 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-5.WELLPAD-L AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
101 RDL3 LBA 13 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-L3 22 HP WHCV RD-L3 POSITION 0 -100 % AIX ---- ---- ---- ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----

102 RDL3 LBA 13 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-L3 22 TORQUE OVER MOV FCV-L3 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ○ ---- ---- ○ ----

103 RDL3 LBA 13 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-L3 31 REMOTE MODE SELECTED MOV FCV-L3 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ---- ---- ---- ○ ----

104 RDL3 LBA 13 AA 101 XG 03 VALVE FAILURE -MOV FCV-L3 24 VALVE FAILURE MOV FCV-L3 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ○ ---- ---- ○ ----

105 RDL3 LBA 13 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-L3 31 LOSS OF POWER SOURCE MOV FCV-L3 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C77 ○ ○ ---- ---- ○ ----

106 RDL4 LBA 14 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-L4 26 HP WHCV RD-L4 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDL F C78 ○ ---- ○ ---- ○ ----

107 RDL4 LBA 14 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-L4 30 VALVE OPEN POSITION MOV FCV-L4 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ---- ---- ---- ○ ----

108 RDL4 LBA 14 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-L4 31 VALVE CLOSE POSITION MOV FCV-L4 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ---- ---- ---- ○ ----

109 RDL4 LBA 14 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-L4 22 HP WHCV RD-L4 POSITION 0 -100 % AIX ---- ---- ---- ---- F DCSRDL C78 ○ ---- ---- ---- ○ ----

110 RDL4 LBA 14 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-L4 22 TORQUE OVER MOV FCV-L4 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ○ ---- ---- ○ ----

111 RDL4 LBA 14 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-L4 31 REMOTE MODE SELECTED MOV FCV-L4 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ---- ---- ---- ○ ----

112 RDL4 LBA 14 AA 101 XG 03 VALVE FAILURE -MOV FCV-L4 24 VALVE FAILURE MOV FCV-L4 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ○ ---- ---- ○ ----

113 RDL4 LBA 14 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-L4 31 LOSS OF POWER SOURCE MOV FCV-L4 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ○ ---- ---- ○ ----

114 RDL5 LBA 15 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-L5 26 HP WHCV RD-L5 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDL F C78 ○ ---- ○ ---- ○ ----

115 RDL5 LBA 15 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-L5 30 VALVE OPEN POSITION MOV FCV-L5 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ---- ---- ---- ○ ----

116 RDL5 LBA 15 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-L5 31 VALVE CLOSE POSITION MOV FCV-L5 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ---- ---- ---- ○ ----

117 RDL5 LBA 15 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-L5 22 HP WHCV RD-L5 POSITION 0 -100 % AIX ---- ---- ---- ---- F DCSRDL C78 ○ ---- ---- ---- ○ ----

118 RDL5 LBA 15 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-L5 22 TORQUE OVER MOV FCV-L5 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ○ ---- ---- ○ ----

119 RDL5 LBA 15 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-L5 31 REMOTE MODE SELECTED MOV FCV-L5 OFF/ON ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ---- ---- ---- ○ ----

120 RDL5 LBA 15 AA 101 XG 03 VALVE FAILURE -MOV FCV-L5 24 VALVE FAILURE MOV FCV-L5 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ○ ---- ---- ○ ----

121 RDL5 LBA 15 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-L5 31 LOSS OF POWER SOURCE MOV FCV-L5 NORMAL/ALARM ---- DI ---- ---- NO ---- F DCSRDL C78 ○ ○ ---- ---- ○ ----

122 RD00 LBA 30 CP 003 XQ 01 PRESSURE TRANSMITTER TO HP SEPARATOR 21 HP SEPARATOR PRESSURE 0 - 20 Bar G AII ---- ---- ---- ---- F DCSRDL R30A ○ H ---- ---- ○ ----

123 RD00 CJU 40 GH 001 XG 02 WellPAD-L System Cabinet PSU or FWL Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET DCSRDL ---- ○ ---- ---- ○ ----

124 RD00 CJU 40 GH 001 XG 01 WellPAD-L System Cabinet Fan or Thermostat Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET DCSRDL ---- ○ ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-6.WELLPAD-M AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
1 RD00 BBB 50 XG 01 PAD-M INCOMING LBS CLOSE INDICATION 24 PAD-M INCOMING LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ---- ○ ----

2 RD00 BBB 50 XG 02 PAD-M INCOMING LBS OPEN INDICATION 23 PAD-M INCOMING LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ---- ○ ----

3 RD00 BBB 50 XG 03 PAD-M INCOMING LBS EARTH ON INDICATION 24 PAD-M INCOMING LBS EARTH OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ----
○ ○
(P2)

4 RD00 BBB 50 XG 10 PAD-M INCOMING SPARE 20 PAD-M INCOMING SPARE ---- ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ---- ---- ---- ---- ---- ----

NO
5 RD00 BBB 50 YB 01 PAD-M OUTGOING TO PAD-M DISTRIBUTION TRANSFORMER SPARE 31 PAD-M OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MRMU ---- ---- ○ ---- ○ ----
PULSE
NO
6 RD00 BBB 50 YB 02 PAD-M OUTGOING TO PAD-M DISTRIBUTION TRANSFORMER SPARE 31 PAD-M OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MRMU ---- ---- ○ ---- ○ ----
PULSE

7 RD00 BBB 50 XG 04 PAD-M OUTGOING TO PAD-M DISTRIBUTION TRANSFORMER LBS CLOSE INDICATION 32 PAD-M OG TO DSTRBTN TR LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ---- ---- ---- ---- ○ ----

8 RD00 BBB 50 XG 05 PAD-M OUTGOING TO PAD-M DISTRIBUTION TRANSFORMER LBS OPEN INDICATION 32 PAD-M OG TO DSTRBTN TRA LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ---- ---- ---- ---- ○ ----

9 RD00 BBB 50 XG 06 PAD-M OUTGOING TO PAD-M DISTRIBUTION TRANSFORMER LBS EATH ON INDICATION 32 PAD-M OG TO DSTRBTN TRA LBS EATH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ----
○ ○
(P2)

10 RD00 BBB 50 XG 11 PAD-M OUTGOING TO PAD-M DISTRIBUTION TRANSFORMER SPARE 31 PAD-M OG TO DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ---- ○ ----

NO
11 RD00 BBB 50 YB 03 PAD-M OUTGOING TO PAD-N RMU LBS SPARE 31 PAD-M OUTGOING TO RMU LBS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MRMU ---- ---- ○ ---- ○ ----
PULSE

12 RD00 BBB 50 XG 07 PAD-M OUTGOING TO PAD-N RMU LBS CLOSE INDICATION 31 PAD-M OG TO PAD-N RMU LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ---- ---- ---- ---- ○ ----

13 RD00 BBB 50 XG 08 PAD-M OUTGOING TO PAD-N RMU LBS OPEN INDICATION 30 PAD-M OG TO PAD-N RMU LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ---- ---- ---- ---- ○ ----

14 RD00 BBB 50 XG 09 PAD-M OUTGOING TO PAD-N RMU LBS EARTH ON INDICATION 31 PAD-M OG TO PAD-N RMU LBS EARTH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ----
○ ○
(P2)
15 RD00 BBB 50 XG 12 PAD-M OUTGOING TO PAD-N RMU LBS SPARE 31 PAD-M OUTGOING TO RMU LBS SPARE ---- ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ---- ○ ----

NO
16 RD00 BBB 50 YB 04 PAD-M OUTGOING TO PAD-N RMU LBS SPARE 31 PAD-M OUTGOING TO RMU LBS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MLVPDB ---- ---- ○ ---- ○ ----
PULSE
NO
17 RD00 BBB 50 YB 05 PAD-M INCOMING FROM PAD-M DISTRIBUTION TRANSFORMER (52L-M) SPARE 32 PAD-M IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MLVPDB ---- ---- ○ ---- ○ ----
PULSE
NO
18 RD00 BBB 50 YB 06 PAD-M INCOMING FROM PAD-M DISTRIBUTION TRANSFORMER (52L-M) SPARE 32 PAD-M IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MLVPDB ---- ---- ○ ---- ○ ----
PULSE

19 RD00 BFC 50 XG 01 PAD-M INCOMING FROM PAD-M DISTRIBUTION TRANSFORMER (52L-M) TRIP INDICATION 31 PAD-M IC FRM DSTRBTN TRANS TRIP NORMAL/ALARM ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ---- ○ ---- ---- ----

(P1)

20 RD00 BFC 50 XG 02 PAD-M INCOMING FROM PAD-M DISTRIBUTION TRANSFORMER (52L-M) MCCB CLOSE INDICATION 31 PAD-M IC FRM DSTRBTN TRA CB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

21 RD00 BFC 50 XG 23 PAD-M INCOMING FROM PAD-M DISTRIBUTION TRANSFORMER (52L-M) SPARE 32 PAD-M IC FRM DSTRBTN TRANS SPARE OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

NO
22 RD00 BFC 50 YB 01 PAD-M INCOMING FROM FUTURE GENERATOR (52LA-M) SPARE 30 PAD-M IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MLVPDB ---- ---- ○ ---- ○ ----
PULSE
NO
23 RD00 BFC 50 YB 02 PAD-M INCOMING FROM FUTURE GENERATOR (52LA-M) SPARE 30 PAD-M IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MLVPDB ---- ---- ○ ---- ○ ----
PULSE

24 RD00 BFC 50 XG 03 PAD-M INCOMING FROM FUTURE GENERATOR (52LA-M) TRIP INDICATION 29 PAD-M IC FROM FUTURE GEN TRIP NORMAL/ALARM ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ---- ○ ---- ---- ----

(P1)
25 RD00 BFC 50 XG 04 PAD-M INCOMING FROM FUTURE GENERATOR (52LA-M) MCCB CLOSE INDICATION 32 PAD-M IC FRM FUTURE GEN MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

26 RD00 BFC 50 XG 24 PAD-M INCOMING FROM FUTURE GENERATOR (52LA-M) SPARE 30 PAD-M IC FROM FUTURE GEN SPARE ---- ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

27 RD00 BFC 50 XG 05 FEEDER TO POWER OUTLET MCCB CLOSE INDICATION 31 FEEDER TO POWER OUTLET MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

28 RD00 BFC 50 XG 06 FEEDER TO POWER OUTLET TRIP INDICATION 27 FEEDER TO POWER OUTLET TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)

29 RD00 BFC 50 XG 07 PAD-M OUTGOING TO LIGHTING PANEL PAD RD- MCCB CLOSE INDICATION 29 PAD-M OG TO LGHT PNL MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

30 RD00 BFC 50 XG 08 PAD-M OUTGOING TO LIGHTING PANEL PAD RD- TRIP INDICATION 31 PAD-M OG TO LIGHTING PANEL TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
31 RD00 BFC 50 XG 09 PAD-M DC UPS MCCB CLOSE INDICATION 23 PAD-M DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

32 RD00 BFC 50 XG 10 PAD-M DC UPS TRIP INDICATION 17 PAD-M DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
33 RD00 BFC 50 XG 11 PAD-M BACKUP DC UPS MCCB CLOSE INDICATION 30 PAD-M BACKUP DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

34 RD00 BFC 50 XG 12 PAD-M BACKUP DC UPS TRIP INDICATION 24 PAD-M BACKUP DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
35 RD00 BFC 50 XG 25 PAD-M SPARE FEEDER (5 KVA) MCCB CLOSE INDICATION 32 PAD-M SAPRE FDR (5 KVA) MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

36 RD00 BFC 50 XG 26 PAD-M SPARE FEEDER (5 KVA) TRIP INDICATION 31 PAD-M SPARE FEEDER (5 KVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)

37 RD00 BFC 50 XG 13 PAD-M MOV 1 - PRODUCTION WELL (1) MCCB CLOSE INDICATION 32 PAD-M MOV1 PRDCTN WELL1 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

38 RD00 BFC 50 XG 14 PAD-M MOV 1 - PRODUCTION WELL (1) TRIP INDICATION 29 PAD-M MOV1 PRDCTN WELL1 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
39 RD00 BFC 50 XG 15 PAD-M MOV 2 - PRODUCTION WELL (2) MCCB CLOSE INDICATION 32 PAD-M MOV2 PRDCTN WLL2 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

40 RD00 BFC 50 XG 16 PAD-M MOV 2 - PRODUCTION WELL (2) TRIP INDICATION 29 PAD-M MOV2 PRDCTN WELL2 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
41 RD00 BFC 50 XG 17 PAD-M MOV 3 - PRODUCTION WELL (3) MCCB CLOSE INDICATION 32 PAD-M MOV3 PRDCTN WLL3 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

42 RD00 BFC 50 XG 18 PAD-M MOV 3 - PRODUCTION WELL (3) TRIP INDICATION 29 PAD-M MOV3 PRDCTN WELL3 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
43 RD00 BFC 50 XG 19 PAD-M MOV 4 - PRODUCTION WELL (4) MCCB CLOSE INDICATION 32 PAD-M MOV4 PRDCTN WLL4 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

44 RD00 BFC 50 XG 20 PAD-M MOV 4 - PRODUCTION WELL (4) TRIP INDICATION 29 PAD-M MOV4 PRDCTN WELL4 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
45 RD00 BFC 50 XG 21 PAD-M MOV 5 - PRODUCTION WELL (5) MCCB CLOSE INDICATION 32 PAD-M MOV5 PRDCTN WLL5 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----


46 RD00 BFC 50 XG 22 PAD-M MOV 5 - PRODUCTION WELL (5) TRIP INDICATION 29 PAD-M MOV5 PRDCTN WELL5 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ○ ----
(P1)
47 RD00 BFV 50 XG 01 PAD M DISTRIBUTION TRANSFORMER OIL TEMPERATURE ALARM 31 PAD-M DSTRBTNN TRA OIL TEMP ANN OFF/ON ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ----

(P2)
48 RD00 BFV 50 XG 02 PAD M DISTRIBUTION TRANSFORMER OIL TEMPERATURE TRIP 32 PAD-M DSTRBTNN TRA OIL TEMP TRIP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ○ ○
(P1)
49 RD00 BFV 50 XG 03 PAD M DISTRIBUTION TRANSFORMER WINDING TEMPERATURE ALARM 32 PAD-M DSTRBTNN TR WNDNG TEMP ANN OFF/ON ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ----

(P2)
50 RD00 BFV 50 XG 04 PAD M DISTRIBUTION TRANSFORMER WINDING TEMPERATURE TRIP 32 PAD-M DSTRBTNN TR WNDNG TEMP TRP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ○ ○
(P1)
2.DCS IO LIST FOR HARD WIRE
2-6.WELLPAD-M AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
51 RD00 BFV 50 XG 05 PAD M DISTRIBUTION TRANSFORMER OIL LEVEL 29 PAD-M DSTRBTN TRANS OIL LEVEL OFF/ON ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ○ ○
(P1)
52 RD00 BFV 50 XG 06 PAD M DISTRIBUTION TRANSFORMER PRESSURE RELIEF DEVICE 32 PAD-M DSTRBTN TRANS PRESS RELIEF OFF/ON ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ○ ○
(P1)
53 RD00 BRT 50 XQ 01 PAD-M DC UPS SYSTEM 110VDC BUS VOLTAGE 32 PAD-M DC UPS SYS 110VDC BUS VLTG 0-110 VDC AIX ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

54 RD00 BRT 50 XG 01 PAD-M DC UPS SYSTEM 110VDC COMMON OUTPUT FEEDER TRIP 32 PAD-M DC UPS 110VDC OTPT FDR TRP NORMAL/ALARM ---- DI ---- ---- NC ---- F NA DCSRDM ---- ○ ---- ---- ----

(P1)

55 RD00 CYE 50 GA 002 XG 01 Fire Alarm PAD M Substation 27 Fire Alarm PAD M Substation NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM ---- ---- ---- ○ ○
(P1)
56 RDM1 LBA 11 CP 001 XQ 01 Pressure Transmitter at Production Well RD-M1 27 Production Well RD-M1 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDM ○ ○ ---- ---- ○ ---- Rev.4 Range is updated 4

9.0
57 RDM1 LBA 11 CP 002 XQ 01 Pressure Transmitter at Production Well RD-M1 27 Production Well RD-M1 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDM R30B ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
58 RDM2 LBA 12 CP 001 XQ 01 Pressure Transmitter at Production Well RD-M2 27 Production Well RD-M2 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
59 RDM2 LBA 12 CP 002 XQ 01 Pressure Transmitter at Production Well RD-M2 27 Production Well RD-M2 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDM R30B ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
60 RDM3 LBA 13 CP 001 XQ 01 Pressure Transmitter at Production Well RD-M3 27 Production Well RD-M3 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
61 RDM3 LBA 13 CP 002 XQ 01 Pressure Transmitter at Production Well RD-M3 27 Production Well RD-M3 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDM R30B ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
62 RDM4 LBA 14 CP 001 XQ 01 Pressure Transmitter at Production Well RD-M4 27 Production Well RD-M4 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
63 RDM4 LBA 14 CP 002 XQ 01 Pressure Transmitter at Production Well RD-M4 27 Production Well RD-M4 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDM R30B ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
64 RDM5 LBA 15 CP 001 XQ 01 Pressure Transmitter at Production Well RD-M5 27 Production Well RD-M5 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
9.0
65 RDM5 LBA 15 CP 002 XQ 01 Pressure Transmitter at Production Well RD-M5 27 Production Well RD-M5 PRESS 0 - 10 Bar G AII ---- ---- ---- 1% F NA DCSRDM R30B ○ H ---- ---- ○ ---- Rev.4 Range is updated 4
(P2)
o
66 RDM1 LBA 11 CT 001 XQ 01 Temperature Transmitter at Production Well RD-M1 26 Production Well RD-M1 TEMP 0 - 300 C AII ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

o
67 RDM2 LBA 12 CT 001 XQ 01 Temperature Transmitter at Production Well RD-M2 26 Production Well RD-M2 TEMP 0 - 300 C AII ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

o
68 RDM3 LBA 13 CT 001 XQ 01 Temperature Transmitter at Production Well RD-M3 26 Production Well RD-M3 TEMP 0 - 300 C AII ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

o
69 RDM4 LBA 14 CT 001 XQ 01 Temperature Transmitter at Production Well RD-M4 26 Production Well RD-M4 TEMP 0 - 300 C AII ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

o
70 RDM5 LBA 15 CT 001 XQ 01 Temperature Transmitter at Production Well RD-M5 26 Production Well RD-M5 TEMP 0 - 300 C AII ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

40.5
71 RDM1 LBA 11 CF 001 XQ 01 Flow Transmitter at Production Well RD-M1 26 Production Well RD-M1 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
40.5
72 RDM2 LBA 12 CF 001 XQ 01 Flow Transmitter at Production Well RD-M2 26 Production Well RD-M2 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
40.5
73 RDM3 LBA 13 CF 001 XQ 01 Flow Transmitter at Production Well RD-M3 26 Production Well RD-M3 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
40.5
74 RDM4 LBA 14 CF 001 XQ 01 Flow Transmitter at Production Well RD-M4 26 Production Well RD-M4 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
40.5
75 RDM5 LBA 15 CF 001 XQ 01 Flow Transmitter at Production Well RD-M5 26 Production Well RD-M5 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)

76 RDM1 LBA 11 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-M1 26 LP WHCV RD-M1 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDM NA F C79 ○ ---- ○ ---- ○ ----

77 RDM1 LBA 11 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-M1 30 VALVE OPEN POSITION MOV FCV-M1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

78 RDM1 LBA 11 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-M1 31 VALVE CLOSE POSITION MOV FCV-M1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

79 RDM1 LBA 11 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-M1 22 LP WHCV RD-M1 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

80 RDM1 LBA 11 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-M1 22 TORQUE OVER MOV FCV-M1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ○ ---- ---- ○ ----

81 RDM1 LBA 11 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-M1 31 REMOTE MODE SELECTED MOV FCV-M1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

82 RDM1 LBA 11 AA 101 XG 03 VALVE FAILURE -MOV FCV-M1 24 VALVE FAILURE MOV FCV-M1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ○ ---- ---- ○ ----

83 RDM1 LBA 11 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-M1 31 LOSS OF POWER SOURCE MOV FCV-M1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ○ ---- ---- ○ ----

84 RDM2 LBA 12 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-M2 26 LP WHCV RD-M2 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDM NA F C79 ○ ---- ○ ---- ○ ----

85 RDM2 LBA 12 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-M2 30 VALVE OPEN POSITION MOV FCV-M2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

86 RDM2 LBA 12 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-M2 31 VALVE CLOSE POSITION MOV FCV-M2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

87 RDM2 LBA 12 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-M2 22 LP WHCV RD-M2 POSITION 0 -100 % AIX ---- ---- ---- 1% F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

88 RDM2 LBA 12 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-M2 22 TORQUE OVER MOV FCV-M2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ○ ---- ---- ○ ----

89 RDM2 LBA 12 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-M2 31 REMOTE MODE SELECTED MOV FCV-M2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

90 RDM2 LBA 12 AA 101 XG 03 VALVE FAILURE -MOV FCV-M2 24 VALVE FAILURE MOV FCV-M2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ○ ---- ---- ○ ----

91 RDM2 LBA 12 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-M2 31 LOSS OF POWER SOURCE MOV FCV-M2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ○ ---- ---- ○ ----

92 RDM3 LBA 13 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-M3 26 HP WHCV RD-M3 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDM NA F C79 ○ ---- ○ ---- ○ ----

93 RDM3 LBA 13 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-M3 30 VALVE OPEN POSITION MOV FCV-M3 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

94 RDM3 LBA 13 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-M3 31 VALVE CLOSE POSITION MOV FCV-M3 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

95 RDM3 LBA 13 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-M3 22 HP WHCV RD-M3 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

96 RDM3 LBA 13 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-M3 22 TORQUE OVER MOV FCV-M3 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ○ ---- ---- ○ ----

97 RDM3 LBA 13 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-M3 31 REMOTE MODE SELECTED MOV FCV-M3 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ---- ---- ---- ○ ----

98 RDM3 LBA 13 AA 101 XG 03 VALVE FAILURE -MOV FCV-M3 24 VALVE FAILURE MOV FCV-M3 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ○ ---- ---- ○ ----

99 RDM3 LBA 13 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-M3 31 LOSS OF POWER SOURCE MOV FCV-M3 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C79 ○ ○ ---- ---- ○ ----

100 RDM4 LBA 14 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-M4 26 HP WHCV RD-M4 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDM NA F C80 ○ ---- ○ ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-6.WELLPAD-M AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
101 RDM4 LBA 14 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-M4 30 VALVE OPEN POSITION MOV FCV-M4 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ---- ---- ---- ○ ----

102 RDM4 LBA 14 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-M4 31 VALVE CLOSE POSITION MOV FCV-M4 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ---- ---- ---- ○ ----

103 RDM4 LBA 14 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-M4 22 HP WHCV RD-M4 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDM C80 ○ ---- ---- ---- ○ ----

104 RDM4 LBA 14 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-M4 22 TORQUE OVER MOV FCV-M4 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ○ ---- ---- ○ ----

105 RDM4 LBA 14 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-M4 31 REMOTE MODE SELECTED MOV FCV-M4 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ---- ---- ---- ○ ----

106 RDM4 LBA 14 AA 101 XG 03 VALVE FAILURE -MOV FCV-M4 24 VALVE FAILURE MOV FCV-M4 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ○ ---- ---- ○ ----

107 RDM4 LBA 14 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-M4 31 LOSS OF POWER SOURCE MOV FCV-M4 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ○ ---- ---- ○ ----

108 RDM5 LBA 15 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-M5 26 HP WHCV RD-M5 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDM NA F C80 ○ ---- ○ ---- ○ ----

109 RDM5 LBA 15 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-M5 30 VALVE OPEN POSITION MOV FCV-M5 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ---- ---- ---- ○ ----

110 RDM5 LBA 15 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-M5 31 VALVE CLOSE POSITION MOV FCV-M5 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ---- ---- ---- ○ ----

111 RDM5 LBA 15 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-M5 22 HP WHCV RD-M5 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDM C80 ○ ---- ---- ---- ○ ----

112 RDM5 LBA 15 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-M5 22 TORQUE OVER MOV FCV-M5 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ○ ---- ---- ○ ----

113 RDM5 LBA 15 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-M5 31 REMOTE MODE SELECTED MOV FCV-M5 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ---- ---- ---- ○ ----

114 RDM5 LBA 15 AA 101 XG 03 VALVE FAILURE -MOV FCV-M5 24 VALVE FAILURE MOV FCV-M5 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ○ ---- ---- ○ ----

115 RDM5 LBA 15 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-M5 31 LOSS OF POWER SOURCE MOV FCV-M5 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C80 ○ ○ ---- ---- ○ ----

116 RD00 LBA 30 CP 004 XQ 01 PRESSURE TRANSMITTER TO HP SEPARATOR 21 HP SEPARATOR PRESSURE 0 - 20 Bar G AII ---- ---- ---- ---- F NA DCSRDM R30B ○ H ---- ---- ○ ----

117 RD00 CJU 50 GH 001 XG 02 WellPAD-M System Cabinet PSU or FWL Alarm 21 HP SEPARATOR PRESSURE NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSRDM ---- ---- ○ ---- ---- ○ ----

118 RD00 CJU 50 GH 001 XG 01 WellPAD-M System Cabinet Fan or Thermostat Alarm 21 HP SEPARATOR PRESSURE NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSRDM ---- ---- ○ ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-7.WELLPAD-C AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
NO
1 RD00 BBB 20 YB 01 PAD-C INCOMING FROM SEPARATOR STATION TRANSFORMER SPARE 28 PAD-C IC FROM ST TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDC NA RD-CRMU ---- ---- ○ ---- ○ ----
PULSE
NO
2 RD00 BBB 20 YB 02 PAD-C INCOMING FROM SEPARATOR STATION TRANSFORMER SPARE 28 PAD-C IC FROM ST TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDC NA RD-CRMU ---- ---- ○ ---- ○ ----
PULSE

3 RD00 BBB 20 XG 01 PAD-C INCOMING FROM SEPARATOR STATION TRANSFORMER LBS CLOSE INDICATION 32 PAD-C IC FROM ST TRANS LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ○ ---- ---- ---- ○ ----

4 RD00 BBB 20 XG 02 PAD-C INCOMING FROM SEPARATOR STATION TRANSFORMER LBS OPEN INDICATION 31 PAD-C IC FROM ST TRANS LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ○ ---- ---- ---- ○ ----


5 RD00 BBB 20 XG 03 PAD-C INCOMING FROM SEPARATOR STATION TRANSFORMER LBS EARTH ON INDICATION 32 PAD-C IC FROM ST TRANS LBS EARTH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ---- ---- ---- ○ ----
(P2)

6 RD00 BBB 20 XG 07 PAD-C INCOMING FROM SEPARATOR STATION TRANSFORMER LBS SPARE 32 PAD-C IC FROM ST TRANS LBS SPARE ---- ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ---- ---- ---- ---- ---- ----

NO
7 RD00 BBB 20 YB 03 PAD-C OUTGOING TO PAD-C DISTRIBUTION TRANSFORMER SPARE 31 PAD-C OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDC NA RD-CRMU ---- ---- ○ ---- ○ ----
PULSE
NO
8 RD00 BBB 20 YB 04 PAD-C OUTGOING TO PAD-C DISTRIBUTION TRANSFORMER SPARE 31 PAD-C OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDC NA RD-CRMU ---- ---- ○ ---- ○ ----
PULSE

9 RD00 BBB 20 XG 04 PAD-C OUTGOING TO PAD-C DISTRIBUTION TRANSFORMER LBS CLOSE INDICATION 32 PAD-C OG TO DSTRBTN TR LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ○ ---- ---- ---- ○ ----

10 RD00 BBB 20 XG 05 PAD-C OUTGOING TO PAD-C DISTRIBUTION TRANSFORMER LBS OPEN INDICATION 32 PAD-C OG TO DSTRBTN TRA LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ○ ---- ---- ---- ○ ----

11 RD00 BBB 20 XG 06 PAD-C OUTGOING TO PAD-C DISTRIBUTION TRANSFORMER LBS EARTH ON INDICATION 32 PAD-C OG TO DSTRBTN TRA LBS EATH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ---- ○ ---- ---- ----

(P2)
12 RD00 BBB 20 XG 08 PAD-C OUTGOING TO PAD-C DISTRIBUTION TRANSFORMER LBS SPARE 32 PAD-C OG TO DSTRBTN TRAN LBS SPR ---- ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ○ ---- ---- ---- ○ ----

13 RD00 BBB 20 XG 10 PAD-C OUTGOING TO PAD-I RMU LBS CLOSE INDICATION 31 PAD-C OG TO PAD-I RMU LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ○ ---- ---- ---- ○ ----

14 RD00 BBB 20 XG 11 PAD-C OUTGOING TO PAD-I RMU LBS OPEN INDICATION 30 PAD-C OG TO PAD-I RMU LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ○ ---- ---- ---- ○ ----

15 RD00 BBB 20 XG 12 PAD-C OUTGOING TO PAD-I RMU LBS EARTH ON INDICATION 31 PAD-C OG TO PAD-I RMU LBS EARTH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ---- ○ ---- ---- ----

(P2)

16 RD00 BBB 20 XG 09 PAD-C OUTGOING TO PAD-I RMU LBS SPARE 31 PAD-C OG TO PAD-I RMU LBS SPARE ---- ---- DI ---- ---- NO ---- RD-CRMU NA DCSRDC ---- ---- ---- ---- ---- ----

NO
17 RD00 BBB 20 YB 05 PAD-C OUTGOING TO PAD-I RMU LBS SPARE 31 PAD-C OG TO PAD-I RMU LBS SPARE ---- ---- DOH DC110 5W ---- DCSRDC NA RD-CRMU ---- ---- ○ ---- ○ ----
PULSE
NO
18 RD00 BBB 20 YB 06 PAD-C OUTGOING TO PAD-I RMU LBS SPARE 31 PAD-C OG TO PAD-I RMU LBS SPARE ---- ---- DOH DC110 5W ---- DCSRDC NA RD-CRMU ---- ---- ○ ---- ○ ----
PULSE
NO
19 RD00 BFC 20 YB 01 PAD-C INCOMING FROM PAD-C DISTRIBUTION TRANSFORMER (52L-C) SPARE 32 PAD-C IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDC NA RD-CLVPDB ---- ---- ○ ---- ○ ----
PULSE
NO
20 RD00 BFC 20 YB 02 PAD-C INCOMING FROM PAD-C DISTRIBUTION TRANSFORMER (52L-C) SPARE 32 PAD-C IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDC NA RD-CLVPDB ---- ---- ○ ---- ○ ----
PULSE

21 RD00 BFC 20 XG 01 PAD-C INCOMING FROM PAD-C DISTRIBUTION TRANSFORMER (52L-C) TRIP INDICATION 31 PAD-C IC FRM DSTRBTN TRANS TRIP NORMAL/ALARM ---- DI ---- ---- NC ---- RD-CLVPDB NA DCSRDC ---- ---- ---- ○ ----
(P1)
22 RD00 BFC 20 XG 02 PAD-C INCOMING FROM PAD-C DISTRIBUTION TRANSFORMER (52L-C) MCCB CLOSE INDICATION 31 PAD-C IC FRM DSTRBTN TRA CB CLS OFF/ON ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

23 RD00 BFC 20 XG 20 PAD-C INCOMING FROM PAD-C DISTRIBUTION TRANSFORMER (52L-C) SPARE 32 PAD-C IC FRM DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

NO
24 RD00 BFC 20 YB 03 PAD-C INCOMING FROM FUTURE GENERATOR (52LA-C) SPARE 30 PAD-C IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDC NA RD-CLVPDB ---- ---- ○ ---- ○ ----
PULSE
NO
25 RD00 BFC 20 YB 04 PAD-C INCOMING FROM FUTURE GENERATOR (52LA-C) SPARE 30 PAD-C IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDC NA RD-CLVPDB ---- ---- ○ ---- ○ ----
PULSE

26 RD00 BFC 20 XG 03 PAD-C INCOMING FROM FUTURE GENERATOR (52LA-C) TRIP INDICATION 29 PAD-C IC FROM FUTURE GEN TRIP NORMAL/ALARM ---- DI ---- ---- NC ---- RD-CLVPDB NA DCSRDC ---- ○ ---- ---- ----

(P1)
27 RD00 BFC 20 XG 04 PAD-C INCOMING FROM FUTURE GENERATOR (52LA-C) MCCB CLOSE INDICATION 32 PAD-C IC FRM FUTURE GEN MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

28 RD00 BFC 20 XG 17 PAD-C INCOMING FROM FUTURE GENERATOR (52LA-C) SPARE 30 PAD-C IC FROM FUTURE GEN SPARE ---- ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

29 RD00 BFC 20 XG 05 FEEDER TO POWER OUTLET MCCB CLOSE INDICATION 31 FEEDER TO POWER OUTLET MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

30 RD00 BFC 20 XG 06 FEEDER TO POWER OUTLET TRIP INDICATION 27 FEEDER TO POWER OUTLET TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ----
○ ○
(P1)

31 RD00 BFC 20 XG 07 PAD-C MOV 1 - PRODUCTION WELL (1) MCCB CLOSE INDICATION 32 PAD-C MOV1 PRDCTN WELL1 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

32 RD00 BFC 20 XG 08 PAD-C MOV 1 - PRODUCTION WELL (1) TRIP INDICATION 29 PAD-C MOV1 PRDCTN WELL1 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ----
○ ○
(P1)
33 RD00 BFC 20 XG 09 PAD-C MOV 2 - PRODUCTION WELL (2) MCCB CLOSE INDICATION 32 PAD-C MOV2 PRDCTN WLL2 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

34 RD00 BFC 20 XG 10 PAD-C MOV 2 - PRODUCTION WELL (2) TRIP INDICATION 29 PAD-C MOV2 PRDCTN WELL2 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ----
○ ○
(P1)
35 RD00 BFC 20 XG 11 PAD-C OUTGOING TO LIGHTING PANEL PAD RD- MCCB CLOSE INDICATION 29 PAD-C OG TO LGHT PNL MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

36 RD00 BFC 20 XG 12 PAD-C OUTGOING TO LIGHTING PANEL PAD RD- TRIP INDICATION 31 PAD-C OG TO LIGHTING PANEL TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ----
○ ○
(P1)
37 RD00 BFC 20 XG 13 PAD-C DC UPS MCCB CLOSE INDICATION 23 PAD-C DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

38 RD00 BFC 20 XG 14 PAD-C DC UPS TRIP INDICATION 17 PAD-C DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ----
○ ○
(P1)

39 RD00 BFC 20 XG 15 PAD-C BACKUP DC UPS MCCB CLOSE INDICATION 30 PAD-C BACKUP DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

40 RD00 BFC 20 XG 16 PAD-C BACKUP DC UPS TRIP INDICATION 24 PAD-C BACKUP DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ----
○ ○
(P1)
41 RD00 BFC 20 XG 18 PAD-C SPARE FEEDER (5 kVA) MCCB CLOSE INDICATION 32 PAD-C SAPRE FDR (5 KVA) MCCB CLS ---- ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ---- ○ ----

42 RD00 BFC 20 XG 19 PAD-C SPARE FEEDER (5 kVA) MCCB TRIP INDICATION 32 PAD-C SPR FEEDER (5kVA) MCCB TRP NORMAL/TRIP ---- DI ---- ---- NO ---- RD-CLVPDB NA DCSRDC ○ ---- ---- ----
○ ○
(P1)
43 RD00 BFV 20 XG 01 PAD-C DISTRIBUTION TRANSFORMER OIL TEMPERATURE ALARM 31 PAD-C DSTRBTNN TRA OIL TEMP ANN NORMAL/ALARM ---- DI ---- ---- NO ---- RD-CTR NA DCSRDC ---- ○ ---- ---- ----

(P2)
44 RD00 BFV 20 XG 02 PAD-C DISTRIBUTION TRANSFORMER OIL TEMPERATURE TRIP 32 PAD-C DSTRBTNN TRA OIL TEMP TRIP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-CTR NA DCSRDC ---- ○ ---- ---- ○ ○
(P1)

45 RD00 BFV 20 XG 03 PAD-C DISTRIBUTION TRANSFORMER WINDING TEMPERATURE ALARM 32 PAD-C DSTRBTNN TR WNDNG TEMP ANN NORMAL/ALARM ---- DI ---- ---- NO ---- RD-CTR NA DCSRDC ---- ---- ---- ○ ----
(P2)
46 RD00 BFV 20 XG 04 PAD-C DISTRIBUTION TRANSFORMER WINDING TEMPERATURE TRIP 32 PAD-C DSTRBTNN TR WNDNG TEMP TRP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-CTR NA DCSRDC ---- ○ ---- ---- ○ ○
(P1)
47 RD00 BFV 20 XG 05 PAD-C DISTRIBUTION TRANSFORMER OIL LEVEL 29 PAD-C DSTRBTN TRANS OIL LEVEL NORMAL/ALARM ---- DI ---- ---- NO ---- RD-CTR NA DCSRDC ---- ○ ---- ---- ○ ○
(P1)

48 RD00 BFV 20 XG 06 PAD-C DISTRIBUTION TRANSFORMER PRESSURE RELIEF DEVICE 32 PAD-C DSTRBTN TRANS PRESS RELIEF NORMAL/ALARM ---- DI ---- ---- NO ---- RD-CTR NA DCSRDC ---- ---- ---- ○ ○
(P1)
49 RD00 BFV 20 XG 07 PAD-C DISTRIBUTION TRANSFORMER SPARE 31 PAD-C DSTRBTN TRANSFORMER SPARE ---- ---- DI ---- ---- NO ---- RD-CTR NA DCSRDC ---- ---- ---- ---- ○ ○

50 RD00 BFV 20 XG 08 PAD-C DISTRIBUTION TRANSFORMER SPARE 25 PAD-C DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-CTR NA DCSRDC ---- ---- ---- ---- ○ ○
2.DCS IO LIST FOR HARD WIRE
2-7.WELLPAD-C AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
51 RD00 BRT 20 XQ 01 PAD C UPS SYSTEM 110VDC BUS VOLTAGE 32 PAD-C UPS SYS 110VDC BUS VOLTAGE 0-110 VDC AIX ---- ---- ---- ---- F NA DCSRDC ○ ---- ---- ---- ○ ----


52 RD00 BRT 20 XG 01 PAD C UPS SYSTEM 110VDC COMMON OUTPUT FEEDER TRIP 29 PAD-C UPS SYS 110VDC FDR TRIP NORMAL/ALARM ---- DI ---- ---- NC ---- F NA DCSRDC ---- ---- ---- ○ ----
(P1)
53 RD00 CYE 20 GA 002 XG 01 Fire Alarm PAD C Substation 27 Fire Alarm PAD C Substation NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDC ---- ○ ---- ---- ○ ○
(P1)
4.5
54 RDC1 LBA 21 CP 001 XQ 01 Pressure Transmitter at Production Well RD-C1 27 Production Well RD-C1 PRESS 0 - 40 Bar G AII ---- ---- ---- 1% F NA DCSRDC ○ H ---- ---- ○ ----
(P2)
4.5
55 RDC1 LBA 21 CP 002 XQ 01 Pressure Transmitter at Production Well RD-C1 27 Production Well RD-C1 PRESS 0 - 40 Bar G AII ---- ---- ---- 1% F NA DCSRDC R30C ○ H ---- ---- ○ ----
(P2)
4.5
56 RDC2 LBA 22 CP 001 XQ 01 Pressure Transmitter at Production Well RD-C2 27 Production Well RD-C2 PRESS 0 - 40 Bar G AII ---- ---- ---- 1% F NA DCSRDC ○ H ---- ---- ○ ----
(P2)
4.5
57 RDC2 LBA 22 CP 002 XQ 01 Pressure Transmitter at Production Well RD-C2 27 Production Well RD-C2 PRESS 0 - 40 Bar G AII ---- ---- ---- 1% F NA DCSRDC R30C ○ H ---- ---- ○ ----
(P2)
o
58 RDC1 LBA 21 CT 001 XQ 01 Temperature Transmitter at Production Well RD-C1 26 Production Well RD-C1 TEMP 0 - 260 C AII ---- ---- ---- ---- F NA DCSRDC ○ ---- ---- ---- ○ ----

o
59 RDC2 LBA 22 CT 001 XQ 01 Temperature Transmitter at Production Well RD-C2 26 Production Well RD-C2 TEMP 0 - 260 C AII ---- ---- ---- ---- F NA DCSRDC ○ ---- ---- ---- ○ ----

137.7
60 RDC1 LBA 21 CF 001 XQ 01 Flow Transmitter at Production Well RD-C1 26 Production Well RD-C1 FLOW 0 -153 kg/h AII ---- ---- ---- 1% F NA DCSRDC ○ H ---- ---- ○ ----
(P2)
137.7
61 RDC2 LBA 22 CF 001 XQ 01 Flow Transmitter at Production Well RD-C2 26 Production Well RD-C2 FLOW 0 -153 kg/h AII ---- ---- ---- 1% F NA DCSRDC ○ H ---- ---- ○ ----
(P2)

62 RDC1 LBA 21 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-C1 26 LP WHCV RD-C1 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDC NA F C83 ○ ---- ○ ---- ○ ----

63 RDC1 LBA 21 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-C1 30 VALVE OPEN POSITION MOV FCV-C1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ---- ---- ---- ○ ----

64 RDC1 LBA 21 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-C1 31 VALVE CLOSE POSITION MOV FCV-C1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ---- ---- ---- ○ ----

65 RDC1 LBA 21 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-C1 22 LP WHCV RD-C1 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDC C83 ○ ---- ---- ---- ○ ----

66 RDC1 LBA 21 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-C1 22 TORQUE OVER MOV FCV-C1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ○ ---- ---- ○ ----

67 RDC1 LBA 21 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-C1 31 REMOTE MODE SELECTED MOV FCV-C1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ---- ---- ---- ○ ----

68 RDC1 LBA 21 AA 101 XG 03 VALVE FAILURE -MOV FCV-C1 24 VALVE FAILURE MOV FCV-C1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ○ ---- ---- ○ ----

69 RDC1 LBA 21 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-C1 31 LOSS OF POWER SOURCE MOV FCV-C1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ○ ---- ---- ○ ----

70 RDC2 LBA 22 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-C2 26 LP WHCV RD-C2 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDC NA F C83 ○ ---- ○ ---- ○ ----

71 RDC2 LBA 22 CG 101 XG 01 VALVE OPEN POSITION -MOV FCV-C2 30 VALVE OPEN POSITION MOV FCV-C2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ---- ---- ---- ○ ----

72 RDC2 LBA 22 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-C2 31 VALVE CLOSE POSITION MOV FCV-C2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ---- ---- ---- ○ ----

73 RDC2 LBA 22 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-C2 19 LP WHCV-C2 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDC C83 ○ ---- ---- ---- ○ ----

74 RDC2 LBA 22 AA 101 XG 01 TORQUE OVER INDICATION -MOV FCV-C2 22 TORQUE OVER MOV FCV-C2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ○ ---- ---- ○ ----

75 RDC2 LBA 22 AA 101 XG 02 REMOTE MODE SELECTED -MOV FCV-C2 31 REMOTE MODE SELECTED MOV FCV-C2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ---- ---- ---- ○ ----

76 RDC2 LBA 22 AA 101 XG 03 VALVE FAILURE -MOV FCV-C2 24 VALVE FAILURE MOV FCV-C2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ○ ---- ---- ○ ----

77 RDC2 LBA 22 AA 101 XG 04 LOSS OF POWER SOURCE -MOV FCV-C2 31 LOSS OF POWER SOURCE MOV FCV-C2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDC C83 ○ ○ ---- ---- ○ ----

78 RD00 LBA 40 CP 002 XQ 01 PRESSURE TRANSMITTER TO LP SEPARATOR 22 LP SEPARATOR PRESSURE 0 - 20 Bar G AIX ---- ---- ---- ---- F NA DCSRDC R30C ○ H ---- ---- ○ ----

83 RD00 CJU 20 GH 001 XG 02 WellPAD-C System Cabinet PSU or FWL Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSRDC ---- ---- ○ ---- ---- ○ ----

84 RD00 CJU 20 GH 001 XG 01 WellPAD-C System Cabinet Fan or Thermostat Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSRDC ---- ---- ○ ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-8.WELLPAD-B AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
1 RD00 BBB 70 XG 01 PAD-B INCOMING LBS CLOSE INDICATION 24 PAD-B INCOMING LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ○ ---- ---- ---- ○ ○

2 RD00 BBB 70 XG 02 PAD-B INCOMING LBS OPEN INDICATION 23 PAD-B INCOMING LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ○ ---- ---- ---- ○ ----

3 RD00 BBB 70 XG 03 PAD-B INCOMING LBS EARTH ON INDICATION 24 PAD-B INCOMING LBS EARTH OFF/ON ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ---- ○ ---- ----
○ ○
(P2)
4 RD00 BBB 70 XG 07 PAD-B INCOMING SPARE 20 PAD-B INCOMING SPARE ---- ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ○ ---- ---- ---- ○ ----

NO
5 RD00 BBB 70 YB 01 PAD-B OUTGOING TO PAD-B DISTRIBUTION TRANSFORMER SPARE 31 PAD-B OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDB NA RD-BRMU ---- ---- ---- ---- ○ ----
PULSE
NO
6 RD00 BBB 70 YB 02 PAD-B OUTGOING TO PAD-B DISTRIBUTION TRANSFORMER SPARE 31 PAD-B OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDB NA RD-BRMU ---- ---- ---- ---- ○ ----
PULSE

7 RD00 BBB 70 XG 04 PAD-B OUTGOING TO PAD-B DISTRIBUTION TRANSFORMER LBS CLOSE INDICATION 32 PAD-B OG TO DSTRBTN TR LBS CLOSE NORMAL/ALARM ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ---- ○ ---- ---- ○ ----

8 RD00 BBB 70 XG 05 PAD-B OUTGOING TO PAD-B DISTRIBUTION TRANSFORMER LBS OPEN INDICATION 32 PAD-B OG TO DSTRBTN TRA LBS OPEN NORMAL/ALARM ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ---- ○ ---- ---- ○ ----


9 RD00 BBB 70 XG 06 PAD-B OUTGOING TO PAD-B DISTRIBUTION TRANSFORMER LBS EATH ON INDICATION 32 PAD-B OG TO DSTRBTN TRA LBS EATH OFF/ON ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ○ ---- ---- ○ ----
(P2)

10 RD00 BBB 70 XG 08 PAD-B OUTGOING TO PAD-B DISTRIBUTION TRANSFORMER SPARE 31 PAD-B OG TO DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ○ ---- ---- ---- ○ ----

NO
11 RD00 BBB 70 YB 03 PAD-B SPARE FEEDER FUTURE CLOSE COMMAND 31 PAD-B SPR FEEDER FUTURE CLS CMD ---- ---- DOH DC110 5W ---- DCSRDB NA RD-BRMU ---- ---- ---- ---- ○ ----
PULSE
NO
12 RD00 BBB 70 YB 04 PAD-B SPARE FEEDER FUTURE OPEN COMMAND 31 PAD-B SPR FEEDER FUTURE OPN CMD ---- ---- DOH DC110 5W ---- DCSRDB NA RD-BRMU ---- ---- ---- ---- ○ ----
PULSE

13 RD00 BBB 70 XG 09 PAD-B SPARE FEEDER FUTURE TRIP INDICATION 30 PAD-B SPARE FEEDER FUTURE TRIP ---- ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ---- ○ ---- ----
○ ○
(P1)

14 RD00 BBB 70 XG 10 PAD-B SPARE FEEDER FUTURE LOSS OF POWER CONTROL SOURCE 32 PAD-B SPR FEEDER FUTURE POW LOSS ---- ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ---- ○ ---- ○ ----
(P1)
15 RD00 BBB 70 XG 11 PAD-B SPARE FEEDER FUTURE REMOTE MODE SELECTED 32 PAD-B SPARE FEEDER FUTURE REMOTE ---- ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ○ ---- ---- ---- ○ ----

16 RD00 BBB 70 XG 12 PAD-B SPARE FEEDER FUTURE LBS CLOSE INDICATION 31 PAD-B SPR FEEDER FUTURE LBS CLS ---- ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ○ ---- ---- ---- ○ ----

17 RD00 BBB 70 XG 13 PAD-B SPARE FEEDER FUTURE LBS OPEN INDICATION 32 PAD-B SPR FEEDER FUTURE LBS OPEN ---- ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ○ ---- ---- ---- ○ ----

18 RD00 BBB 70 XG 14 PAD-B SPARE FEEDER FUTURE LBS EARTH ON INDICATION 32 PAD-B SPARE FDR FUTURE LBS EARTH ---- ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ---- ○ ---- ----
○ ○
(P2)
19 RD00 BBB 70 XG 15 PAD-B SPARE FEEDER FUTURE SPARE 31 PAD-B SPARE FEEDER FUTURE SPARE ---- ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ○ ---- ---- ---- ○ ----

20 RD00 BBB 70 XG 16 PAD-B SPARE FEEDER FUTURE SPARE 31 PAD-B SPARE FEEDER FUTURE SPARE ---- ---- DI ---- ---- NO ---- RD-BRMU NA DCSRDB ○ ---- ---- ---- ○ ----

NO
21 RD00 BFC 70 YB 01 PAD-B INCOMING FROM PAD-B DISTRIBUTION TRANSFORMER (52L-B) SPARE 32 PAD-B IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDB NA RD-BLVPDB ---- ---- ---- ---- ○ ----
PULSE
NO
22 RD00 BFC 70 YB 02 PAD-B INCOMING FROM PAD-B DISTRIBUTION TRANSFORMER (52L-B) SPARE 32 PAD-B IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDB NA RD-BLVPDB ---- ---- ---- ---- ○ ----
PULSE

23 RD00 BFC 70 XG 01 PAD-B INCOMING FROM PAD-B DISTRIBUTION TRANSFORMER (52L-B) TRIP INDICATION 31 PAD-B IC FRM DSTRBTN TRANS TRIP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ---- ○ ---- ----
○ ○
(P1)
24 RD00 BFC 70 XG 02 PAD-B INCOMING FROM PAD-B DISTRIBUTION TRANSFORMER (52L-B) MCCB CLOSE INDICATION 31 PAD-B IC FRM DSTRBTN TRA CB CLS OFF/ON ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

25 RD00 BFC 70 XG 17 PAD-B INCOMING FROM PAD-B DISTRIBUTION TRANSFORMER (52L-B) SPARE 32 PAD-B IC FRM DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

NO
26 RD00 BFC 70 YB 03 PAD-B INCOMING FROM FUTURE GENERATOR (52LA-B) SPARE 30 PAD-B IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDB NA RD-BLVPDB ---- ---- ---- ---- ○ ----
PULSE
NO
27 RD00 BFC 70 YB 04 PAD-B INCOMING FROM FUTURE GENERATOR (52LA-B) SPARE 30 PAD-B IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDB NA RD-BLVPDB ---- ---- ---- ---- ○ ----
PULSE

28 RD00 BFC 70 XG 03 PAD-B INCOMING FROM FUTURE GENERATOR (52LA-B) TRIP INDICATION 29 PAD-B IC FROM FUTURE GEN TRIP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ---- ○ ---- ○ ----
(P1)
29 RD00 BFC 70 XG 04 PAD-B INCOMING FROM FUTURE GENERATOR (52LA-B) MCCB CLOSE INDICATION 32 PAD-B IC FRM FUTURE GEN MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

30 RD00 BFC 70 XG 18 PAD-B INCOMING FROM FUTURE GENERATOR (52LA-B) SPARE 30 PAD-B IC FROM FUTURE GEN SPARE ---- ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

31 RD00 BFC 70 XG 05 FEEDER TO POWER OUTLET MCCB CLOSE INDICATION 31 FEEDER TO POWER OUTLET MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

32 RD00 BFC 70 XG 06 FEEDER TO POWER OUTLET TRIP INDICATION 27 FEEDER TO POWER OUTLET TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-BLVPDB NA DCSRDB ---- ○ ---- ----
○ ○
(P1)
33 RD00 BFC 70 XG 07 PAD-B MOV 1 - PRODUCTION WELL (1) MCCB CLOSE INDICATION 32 PAD-B MOV1 PRDCTN WELL1 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

34 RD00 BFC 70 XG 08 PAD-B MOV 1 - PRODUCTION WELL (1) TRIP INDICATION 29 PAD-B MOV1 PRDCTN WELL1 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-BLVPDB NA DCSRDB ---- ○ ---- ----
○ ○
(P1)
35 RD00 BFC 70 XG 09 PAD-B MOV 2 - PRODUCTION WELL (2) MCCB CLOSE INDICATION 32 PAD-B MOV2 PRDCTN WLL2 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

36 RD00 BFC 70 XG 10 PAD-B MOV 2 - PRODUCTION WELL (2) TRIP INDICATION 29 PAD-B MOV2 PRDCTN WELL2 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-BLVPDB NA DCSRDB ---- ○ ---- ----
○ ○
(P1)
37 RD00 BFC 70 XG 11 PAD-B OUTGOING TO LIGHTING PANEL PAD RD- MCCB CLOSE INDICATION 29 PAD-B OG TO LGHT PNL MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

38 RD00 BFC 70 XG 12 PAD-B OUTGOING TO LIGHTING PANEL PAD RD- TRIP INDICATION 31 PAD-B OG TO LIGHTING PANEL TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-BLVPDB NA DCSRDB ---- ○ ---- ----
○ ○
(P1)
39 RD00 BFC 70 XG 13 PAD-B DC UPS MCCB CLOSE INDICATION 23 PAD-B DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

40 RD00 BFC 70 XG 14 PAD-B DC UPS TRIP INDICATION 17 PAD-B DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-BLVPDB NA DCSRDB ---- ○ ---- ----
○ ○
(P1)

41 RD00 BFC 70 XG 15 PAD-B BACKUP DC UPS MCCB CLOSE INDICATION 30 PAD-B BACKUP DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

42 RD00 BFC 70 XG 16 PAD-B BACKUP DC UPS TRIP INDICATION 24 PAD-B BACKUP DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-BLVPDB NA DCSRDB ---- ○ ---- ----
○ ○
(P1)
43 RD00 BFC 70 XG 19 PAD-B SPARE FEEDER (5 kVA) MCCB CLOSE INDICATION 32 PAD-B SAPRE FDR (5 KVA) MCCB CLS ---- ---- DI ---- ---- NO ---- RD-BLVPDB NA DCSRDB ○ ---- ---- ---- ○ ----

44 RD00 BFC 70 XG 20 PAD-B SPARE FEEDER (5 kVA) TRIP INDICATION 31 PAD-B SPARE FEEDER (5 KVA) TRIP ---- ---- DI ---- ---- NC ---- RD-BLVPDB NA DCSRDB ---- ○ ---- ----
○ ○
(P1)
45 RD00 BFV 70 XG 01 PAD B DISTRIBUTION TRANSFORMER OIL TEMPERATURE ALARM 31 PAD-B DSTRBTNN TRA OIL TEMP ANN NORMAL/ALARM ---- DI ---- ---- NO ---- RD-BTR NA DCSRDB ---- ○ ---- ----
○ ○
(P2)
46 RD00 BFV 70 XG 02 PAD B DISTRIBUTION TRANSFORMER OIL TEMPERATURE TRIP 32 PAD-B DSTRBTNN TRA OIL TEMP TRIP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-BTR NA DCSRDB ---- ○ ----
○ ○ ○
(P1)
47 RD00 BFV 70 XG 03 PAD B DISTRIBUTION TRANSFORMER WINDING TEMPERATURE ALARM 32 PAD-B DSTRBTNN TR WNDNG TEMP ANN NORMAL/ALARM ---- DI ---- ---- NO ---- RD-BTR NA DCSRDB ---- ○ ---- ----
○ ○
(P2)

48 RD00 BFV 70 XG 04 PAD B DISTRIBUTION TRANSFORMER WINDING TEMPERATURE TRIP 32 PAD-B DSTRBTNN TR WNDNG TEMP TRP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-BTR NA DCSRDB ---- ○ ---- ○ ○
(P1)

49 RD00 BFV 70 XG 05 PAD B DISTRIBUTION TRANSFORMER OIL LEVEL 29 PAD-B DSTRBTN TRANS OIL LEVEL NORMAL/ALARM ---- DI ---- ---- NO ---- RD-BTR NA DCSRDB ---- ○ ---- ○ ○
(P1)
50 RD00 BFV 70 XG 06 PAD B DISTRIBUTION TRANSFORMER PRESSURE RELIEF DEVICE 32 PAD-B DSTRBTN TRANS PRESS RELIEF NORMAL/ALARM ---- DI ---- ---- NO ---- RD-BTR NA DCSRDB ---- ○ ----
○ ○ ○
(P1)
2.DCS IO LIST FOR HARD WIRE
2-8.WELLPAD-B AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
51 RD00 BRT 70 XQ 01 PAD-B DC UPS SYSTEM 110VDC BUS VOLTAGE 32 PAD-B DC UPS SYS 110VDC BUS VLTG 0-110 VDC AIX ---- ---- ---- ---- F NA DCSRDB ○ ---- ---- ---- ○ ----


52 RD00 BRT 70 XG 01 PAD-B DC UPS SYSTEM 110VDC COMMON OUTPUT FEEDER TRIP 32 PAD-B DC UPS 110VDC OTPT FDR TRP NORMAL/ALARM ---- DI ---- ---- NC ---- F NA DCSRDB ---- ○ ---- ○ ----
(P1)
53 RD00 CYE 70 GA 002 XG 01 Fire Alarm PAD B Substation 27 Fire Alarm PAD B Substation NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDB ---- ○ ----
○ ○ ○
(P1)
54 RD00 HAN 01 CP 001 XQ 01 Pressure Transmitter at Reinjection Pad B1 24 Reinjection Pad B1 Press 0 - 40 Bar G AII ---- ---- ---- ---- F NA DCSRDB ○ ---- ---- ---- ○ ---- LATER

55 RD00 HAN 01 CP 002 XQ 01 Pressure Transmitter at Reinjection Pad B1 24 Reinjection Pad B1 Press 0 - 40 Bar G AII ---- ---- ---- ---- F NA DCSRDB ○ ---- ---- ---- ○ ---- LATER

56 RD00 HAN 01 CP 003 XQ 01 Pressure Transmitter at Reinjection Pad B2 24 Reinjection Pad B2 Press 0 - 40 Bar G AII ---- ---- ---- ---- F NA DCSRDB ○ ---- ---- ---- ○ ---- LATER

57 RD00 HAN 01 CP 004 XQ 01 Pressure Transmitter at Reinjection Pad B2 24 Reinjection Pad B2 Press 0 - 40 Bar G AII ---- ---- ---- ---- F NA DCSRDB ○ ---- ---- ---- ○ ---- LATER

58 RD00 HAN 01 CT 001 XQ 01 Temperature Transmitter at Reinjection Pad B1 23 Reinjection Pad B1 Temp 0-260 DegC AII ---- ---- ---- ---- F NA DCSRDB ○ ---- ---- ---- ○ ----

59 RD00 HAN 01 CT 002 XQ 01 Temperature Transmitter at Reinjection Pad B2 23 Reinjection Pad B2 Temp 0-260 DegC AII ---- ---- ---- ---- F NA DCSRDB ○ ---- ---- ---- ○ ----

60 RD00 HAN 01 CF 001 XQ 01 Flow Transmitter at Reinjection Pad B1 23 Reinjection Pad B1 Flow 0 - 312 kg/h AII ---- ---- ---- ---- F NA DCSRDB ○ ○ ---- ---- ○ ----

61 RD00 HAN 01 CF 002 XQ 01 Flow Transmitter at Reinjection Pad B2 23 Reinjection Pad B2 Flow 0 - 312 kg/h AII ---- ---- ---- ---- F NA DCSRDB ○ ○ ---- ---- ○ ----

81 RD00 HAN 01 FH 101 YJ 01 VALVE OPEN & CLOSE COMMAND MOV FCV-B1 31 INJECTION WELL-B1 VALVE POS CMD 0-100 % AOX ---- ---- ---- ---- DCSRDB NA F ○ ---- ○ ---- ○ ----

82 RD00 HAN 01 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-B1 24 INJECTION WELL-B1 VALVE POSITION 0-100 % AIX ---- ---- ---- ---- F NA DCSRDB ○ ---- ○ ---- ○ ----

64 RD00 HAN 01 CG 101 XG 01 VALVE OPEN POSITION -MOV 1 25 VALVE OPEN POSITION MOV 1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDB ○ ---- ---- ---- ○ ----

65 RD00 HAN 01 CG 101 XG 02 VALVE CLOSE POSITION- MOV 1 26 VALVE CLOSE POSITION MOV 1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDB ○ ---- ---- ---- ○ ----

66 RD00 HAN 01 AA 101 XG 01 TORQUE OVER INDICATION -MOV 1 28 TORQUE OVER INDICATION MOV 1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDB ○ ○ ---- ---- ○ ----

67 RD00 HAN 01 AA 101 XG 02 REMOTE MODE SELECTED -MOV 1 26 REMOTE MODE SELECTED MOV 1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDB ○ ---- ---- ---- ○ ----

68 RD00 HAN 01 AA 101 XG 03 VALVE FAILURE -MOV 1 19 VALVE FAILURE MOV 1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDB ○ ○ ---- ---- ○ ----

69 RD00 HAN 01 AA 101 XG 04 LOSS OF POWER SOURCE -MOV 1 26 LOSS OF POWER SOURCE MOV 1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDB ○ ○ ---- ---- ○ ----

83 RD00 HAN 01 FH 102 YJ 01 VALVE OPEN & CLOSE COMMAND MOV FCV-B2 25 INJECTION WELL-B2 POS CMD 0-100 % AOX ---- ---- ---- ---- DCSRDB NA F ○ ---- ○ ---- ○ ----

84 RD00 HAN 01 CG 102 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-B2 32 INJECTION WELL-B2 VALVE POSITION 0-100 % AIX ---- ---- ---- ---- F NA DCSRDB ○ ---- ○ ---- ○ ----

72 RD00 HAN 01 CG 102 XG 01 VALVE OPEN POSITION -MOV 1 25 VALVE OPEN POSITION MOV 1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDB ○ ---- ---- ---- ○ ----

73 RD00 HAN 01 CG 102 XG 02 VALVE CLOSE POSITION- MOV 1 26 VALVE CLOSE POSITION MOV 1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDB ○ ---- ---- ---- ○ ----

74 RD00 HAN 01 AA 102 XG 01 TORQUE OVER INDICATION -MOV 1 28 TORQUE OVER INDICATION MOV 1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDB ○ ○ ---- ---- ○ ----

75 RD00 HAN 01 AA 102 XG 02 REMOTE MODE SELECTED -MOV 1 26 REMOTE MODE SELECTED MOV 1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDB ○ ---- ---- ---- ○ ----

76 RD00 HAN 01 AA 102 XG 03 VALVE FAILURE -MOV 1 19 VALVE FAILURE MOV 1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDB ○ ○ ---- ---- ○ ----

77 RD00 HAN 01 AA 102 XG 04 LOSS OF POWER SOURCE -MOV 1 26 LOSS OF POWER SOURCE MOV 1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDB ○ ○ ---- ---- ○ ----

79 RD00 CJU 60 GH 001 XG 02 WellPAD-B System Cabinet PSU or FWL Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSRDB ---- ---- ○ ---- ---- ○ ----

80 RD00 CJU 60 GH 001 XG 01 WellPAD-B System Cabinet Fan or Thermostat Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSRDB ---- ---- ○ ---- ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-9.WELLPAD-N AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
1 RD00 BBB 80 XG 01 PAD-N INCOMING LBS CLOSE INDICATION 24 PAD-N INCOMING LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ---- ○ ----

2 RD00 BBB 80 XG 02 PAD-N INCOMING LBS OPEN INDICATION 23 PAD-N INCOMING LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ---- ○ ----

3 RD00 BBB 80 XG 03 PAD-N INCOMING LBS EARTH ON INDICATION 24 PAD-N INCOMING LBS EARTH OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ----
○ ○
(P2)

4 RD00 BBB 80 XG 10 PAD-N INCOMING SPARE 20 PAD-N INCOMING SPARE ---- ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ---- ---- ---- ---- ---- ----

NO
5 RD00 BBB 80 YB 01 PAD-N OUTGOING TO PAD-N DISTRIBUTION TRANSFORMER SPARE 31 PAD-N OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MRMU ---- ---- ○ ---- ○ ----
PULSE
NO
6 RD00 BBB 80 YB 02 PAD-N OUTGOING TO PAD-N DISTRIBUTION TRANSFORMER SPARE 31 PAD-N OG TO DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MRMU ---- ---- ○ ---- ○ ----
PULSE

7 RD00 BBB 80 XG 04 PAD-N OUTGOING TO PAD-N DISTRIBUTION TRANSFORMER LBS CLOSE INDICATION 32 PAD-N OG TO DSTRBTN TR LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ---- ---- ---- ---- ○ ----

8 RD00 BBB 80 XG 05 PAD-N OUTGOING TO PAD-N DISTRIBUTION TRANSFORMER LBS OPEN INDICATION 32 PAD-N OG TO DSTRBTN TRA LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ---- ---- ---- ---- ○ ----

9 RD00 BBB 80 XG 06 PAD-N OUTGOING TO PAD-N DISTRIBUTION TRANSFORMER LBS EATH ON INDICATION 32 PAD-N OG TO DSTRBTN TRA LBS EATH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ----
○ ○
(P2)

10 RD00 BBB 80 XG 11 PAD-N OUTGOING TO PAD-N DISTRIBUTION TRANSFORMER SPARE 31 PAD-N OG TO DSTRBTN TRANS SPARE ---- ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ---- ○ ----

NO
11 RD00 BBB 80 YB 03 PAD-N OUTGOING TO PAD-N RMU LBS SPARE 31 PAD-N OG TO PAD-N RMU LBS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MRMU ---- ---- ○ ---- ○ ----
PULSE

12 RD00 BBB 80 XG 07 PAD-N OUTGOING TO PAD-N RMU LBS CLOSE INDICATION 31 PAD-N OG TO PAD-N RMU LBS CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ---- ---- ---- ---- ○ ----

13 RD00 BBB 80 XG 08 PAD-N OUTGOING TO PAD-N RMU LBS OPEN INDICATION 30 PAD-N OG TO PAD-N RMU LBS OPEN OFF/ON ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ---- ---- ---- ---- ○ ----

14 RD00 BBB 80 XG 09 PAD-N OUTGOING TO PAD-N RMU LBS EARTH ON INDICATION 31 PAD-N OG TO PAD-N RMU LBS EARTH NORMAL/ALARM ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ----
○ ○
(P2)
15 RD00 BBB 80 XG 12 PAD-N OUTGOING TO PAD-N RMU LBS SPARE 31 PAD-N OG TO PAD-N RMU LBS SPARE ---- ---- DI ---- ---- NO ---- RD-MRMU NA DCSRDM ○ ---- ---- ---- ○ ----

NO
16 RD00 BBB 80 YB 04 PAD-N OUTGOING TO PAD-N RMU LBS SPARE 31 PAD-N OG TO PAD-N RMU LBS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MLVPDB ---- ---- ○ ---- ○ ----
PULSE
NO
17 RD00 BBB 80 YB 05 PAD-N INCOMING FROM PAD-N DISTRIBUTION TRANSFORMER (52L-M) SPARE 32 PAD-N IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MLVPDB ---- ---- ○ ---- ○ ----
PULSE
NO
18 RD00 BBB 80 YB 06 PAD-N INCOMING FROM PAD-N DISTRIBUTION TRANSFORMER (52L-M) SPARE 32 PAD-N IC FRM DSTRBTN TRANS SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MLVPDB ---- ---- ○ ---- ○ ----
PULSE

19 RD00 BFC 80 XG 01 PAD-N INCOMING FROM PAD-N DISTRIBUTION TRANSFORMER (52L-M) TRIP INDICATION 31 PAD-N IC FRM DSTRBTN TRANS TRIP NORMAL/ALARM ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ---- ○ ---- ---- ----

(P1)

20 RD00 BFC 80 XG 02 PAD-N INCOMING FROM PAD-N DISTRIBUTION TRANSFORMER (52L-M) MCCB CLOSE INDICATION 31 PAD-N IC FRM DSTRBTN TRA CB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

21 RD00 BFC 80 XG 23 PAD-N INCOMING FROM PAD-N DISTRIBUTION TRANSFORMER (52L-M) SPARE 32 PAD-N IC FRM DSTRBTN TRANS SPARE OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

NO
22 RD00 BFC 80 YB 01 PAD-N INCOMING FROM FUTURE GENERATOR (52LA-M) SPARE 30 PAD-N IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MLVPDB ---- ---- ○ ---- ○ ----
PULSE
NO
23 RD00 BFC 80 YB 02 PAD-N INCOMING FROM FUTURE GENERATOR (52LA-M) SPARE 30 PAD-N IC FROM FUTURE GEN SPARE ---- ---- DOH DC110 5W ---- DCSRDM NA RD-MLVPDB ---- ---- ○ ---- ○ ----
PULSE

24 RD00 BFC 80 XG 03 PAD-N INCOMING FROM FUTURE GENERATOR (52LA-M) TRIP INDICATION 29 PAD-N IC FROM FUTURE GEN TRIP NORMAL/ALARM ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ---- ○ ---- ---- ----

(P1)
25 RD00 BFC 80 XG 04 PAD-N INCOMING FROM FUTURE GENERATOR (52LA-M) MCCB CLOSE INDICATION 32 PAD-N IC FRM FUTURE GEN MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

26 RD00 BFC 80 XG 24 PAD-N INCOMING FROM FUTURE GENERATOR (52LA-M) SPARE 30 PAD-N IC FROM FUTURE GEN SPARE ---- ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

27 RD00 BFC 80 XG 05 FEEDER TO POWER OUTLET MCCB CLOSE INDICATION 31 FEEDER TO POWER OUTLET MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

28 RD00 BFC 80 XG 06 FEEDER TO POWER OUTLET TRIP INDICATION 27 FEEDER TO POWER OUTLET TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)

29 RD00 BFC 80 XG 07 PAD-N OUTGOING TO LIGHTING PANEL PAD RD- MCCB CLOSE INDICATION 29 PAD-N OG TO LGHT PNL MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

30 RD00 BFC 80 XG 08 PAD-N OUTGOING TO LIGHTING PANEL PAD RD- TRIP INDICATION 31 PAD-N OG TO LIGHTING PANEL TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
31 RD00 BFC 80 XG 09 PAD-N DC UPS MCCB CLOSE INDICATION 23 PAD-N DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

32 RD00 BFC 80 XG 10 PAD-N DC UPS TRIP INDICATION 17 PAD-N DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
33 RD00 BFC 80 XG 11 PAD-N BACKUP DC UPS MCCB CLOSE INDICATION 30 PAD-N BACKUP DC UPS MCCB CLOSE OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

34 RD00 BFC 80 XG 12 PAD-N BACKUP DC UPS TRIP INDICATION 24 PAD-N BACKUP DC UPS TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
35 RD00 BFC 80 XG 25 PAD-N SPARE FEEDER (5 KVA) MCCB CLOSE INDICATION 32 PAD-N SAPRE FDR (5 KVA) MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

36 RD00 BFC 80 XG 26 PAD-N SPARE FEEDER (5 KVA) TRIP INDICATION 31 PAD-N SPARE FEEDER (5 KVA) TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)

37 RD00 BFC 80 XG 13 PAD-N MOV 1 - PRODUCTION WELL (1) MCCB CLOSE INDICATION 32 PAD-N MOV1 PRDCTN WELL1 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

38 RD00 BFC 80 XG 14 PAD-N MOV 1 - PRODUCTION WELL (1) TRIP INDICATION 29 PAD-N MOV1 PRDCTN WELL1 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
39 RD00 BFC 80 XG 15 PAD-N MOV 2 - PRODUCTION WELL (2) MCCB CLOSE INDICATION 32 PAD-N MOV2 PRDCTN WLL2 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

40 RD00 BFC 80 XG 16 PAD-N MOV 2 - PRODUCTION WELL (2) TRIP INDICATION 29 PAD-N MOV2 PRDCTN WELL2 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
41 RD00 BFC 80 XG 17 PAD-N MOV 3 - PRODUCTION WELL (3) MCCB CLOSE INDICATION 32 PAD-N MOV3 PRDCTN WLL3 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

42 RD00 BFC 80 XG 18 PAD-N MOV 3 - PRODUCTION WELL (3) TRIP INDICATION 29 PAD-N MOV3 PRDCTN WELL3 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
43 RD00 BFC 80 XG 19 PAD-N MOV 4 - PRODUCTION WELL (4) MCCB CLOSE INDICATION 32 PAD-N MOV4 PRDCTN WLL4 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----

44 RD00 BFC 80 XG 20 PAD-N MOV 4 - PRODUCTION WELL (4) TRIP INDICATION 29 PAD-N MOV4 PRDCTN WELL4 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ----
○ ○
(P1)
45 RD00 BFC 80 XG 21 PAD-N MOV 5 - PRODUCTION WELL (5) MCCB CLOSE INDICATION 32 PAD-N MOV5 PRDCTN WLL5 MCCB CLS OFF/ON ---- DI ---- ---- NO ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ---- ○ ----


46 RD00 BFC 80 XG 22 PAD-N MOV 5 - PRODUCTION WELL (5) TRIP INDICATION 29 PAD-N MOV5 PRDCTN WELL5 TRIP NORMAL/TRIP ---- DI ---- ---- NC ---- RD-MLVPDB NA DCSRDM ○ ---- ---- ○ ----
(P1)
47 RD00 BFV 80 XG 01 PAD N DISTRIBUTION TRANSFORMER OIL TEMPERATURE ALARM 31 PAD-N DSTRBTNN TRA OIL TEMP ANN OFF/ON ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ----

(P2)
48 RD00 BFV 80 XG 02 PAD N DISTRIBUTION TRANSFORMER OIL TEMPERATURE TRIP 32 PAD-N DSTRBTNN TRA OIL TEMP TRIP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ○ ○
(P1)
49 RD00 BFV 80 XG 03 PAD N DISTRIBUTION TRANSFORMER WINDING TEMPERATURE ALARM 32 PAD-N DSTRBTNN TR WNDNG TEMP ANN OFF/ON ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ----

(P2)
50 RD00 BFV 80 XG 04 PAD N DISTRIBUTION TRANSFORMER WINDING TEMPERATURE TRIP 32 PAD-N DSTRBTNN TR WNDNG TEMP TRP NORMAL/ALARM ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ○ ○
(P1)
2.DCS IO LIST FOR HARD WIRE
2-9.WELLPAD-N AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
51 RD00 BFV 80 XG 05 PAD N DISTRIBUTION TRANSFORMER OIL LEVEL 29 PAD-N DSTRBTN TRANS OIL LEVEL OFF/ON ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ○ ○
(P1)
52 RD00 BFV 80 XG 06 PAD N DISTRIBUTION TRANSFORMER PRESSURE RELIEF DEVICE 32 PAD-N DSTRBTN TRANS PRESS RELIEF OFF/ON ---- DI ---- ---- NO ---- RD-MTR NA DCSRDM ---- ○ ---- ---- ○ ○
(P1)
53 RD00 BRT 80 XQ 01 PAD-N DC UPS SYSTEM 110VDC BUS VOLTAGE 32 PAD-N DC UPS SYS 110VDC BUS VLTG 0-110 VDC AIX ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

54 RD00 BRT 80 XG 01 PAD-N DC UPS SYSTEM 110VDC COMMON OUTPUT FEEDER TRIP 32 PAD-N DC UPS 110VDC OTPT FDR TRP NORMAL/ALARM ---- DI ---- ---- NC ---- F NA DCSRDM ---- ○ ---- ---- ----

(P1)

55 RD00 CYE 80 GA 002 XG 01 Fire Alarm PAD N Substation 27 Fire Alarm PAD N Substation NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM ---- ---- ---- ○ ○
(P1)
13.5
56 RDN1 LBA 11 CP 001 XQ 01 Pressure Transmitter at Production Well RD-N1 27 Production Well RD-N1 PRESS 0 - 15 Bar G AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
13.5
57 RDN1 LBA 11 CP 002 XQ 01 Pressure Transmitter at Production Well RD-N1 27 Production Well RD-N1 PRESS 0 - 15 Bar G AII ---- ---- ---- 1% F NA DCSRDM R30D ○ H ---- ---- ○ ----
(P2)
13.5
58 RDN2 LBA 12 CP 001 XQ 01 Pressure Transmitter at Production Well RD-N2 27 Production Well RD-N2 PRESS 0 - 15 Bar G AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
13.5
59 RDN2 LBA 12 CP 002 XQ 01 Pressure Transmitter at Production Well RD-N2 27 Production Well RD-N2 PRESS 0 - 15 Bar G AII ---- ---- ---- 1% F NA DCSRDM R30D ○ H ---- ---- ○ ----
(P2)
13.5
60 RDN3 LBA 13 CP 001 XQ 01 Pressure Transmitter at Production Well RD-N3 27 Production Well RD-N3 PRESS 0 - 15 Bar G AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
13.5
61 RDN3 LBA 13 CP 002 XQ 01 Pressure Transmitter at Production Well RD-N3 27 Production Well RD-N3 PRESS 0 - 15 Bar G AII ---- ---- ---- 1% F NA DCSRDM R30D ○ H ---- ---- ○ ----
(P2)
13.5
62 RDN4 LBA 14 CP 001 XQ 01 Pressure Transmitter at Production Well RD-N4 27 Production Well RD-N4 PRESS 0 - 15 Bar G AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
13.5
63 RDN4 LBA 14 CP 002 XQ 01 Pressure Transmitter at Production Well RD-N4 27 Production Well RD-N4 PRESS 0 - 15 Bar G AII ---- ---- ---- 1% F NA DCSRDM R30D ○ H ---- ---- ○ ----
(P2)
13.5
64 RDN5 LBA 15 CP 001 XQ 01 Pressure Transmitter at Production Well RD-N5 27 Production Well RD-N5 PRESS 0 - 15 Bar G AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
13.5
65 RDN5 LBA 15 CP 002 XQ 01 Pressure Transmitter at Production Well RD-N5 27 Production Well RD-N5 PRESS 0 - 15 Bar G AII ---- ---- ---- 1% F NA DCSRDM R30D ○ H ---- ---- ○ ----
(P2)
o
66 RDN1 LBA 11 CT 001 XQ 01 Temperature Transmitter at Production Well RD-N1 26 Production Well RD-N1 TEMP 0 - 200 C AII ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

o
67 RDN2 LBA 12 CT 001 XQ 01 Temperature Transmitter at Production Well RD-N2 26 Production Well RD-N2 TEMP 0 - 200 C AII ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

o
68 RDN3 LBA 13 CT 001 XQ 01 Temperature Transmitter at Production Well RD-N3 26 Production Well RD-N3 TEMP 0 - 200 C AII ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

o
69 RDN4 LBA 14 CT 001 XQ 01 Temperature Transmitter at Production Well RD-N4 26 Production Well RD-N4 TEMP 0 - 200 C AII ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

o
70 RDN5 LBA 15 CT 001 XQ 01 Temperature Transmitter at Production Well RD-N5 26 Production Well RD-N5 TEMP 0 - 200 C AII ---- ---- ---- ---- F NA DCSRDM ○ ---- ---- ---- ○ ----

40.5
71 RDN1 LBA 11 CF 001 XQ 01 Flow Transmitter at Production Well RD-N1 26 Production Well RD-I1 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
40.5
72 RDN2 LBA 12 CF 001 XQ 01 Flow Transmitter at Production Well RD-N2 26 Production Well RD-I2 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
40.5
73 RDN3 LBA 13 CF 001 XQ 01 Flow Transmitter at Production Well RD-N3 26 Production Well RD-I3 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
40.5
74 RDN4 LBA 14 CF 001 XQ 01 Flow Transmitter at Production Well RD-N4 26 Production Well RD-I4 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)
40.5
75 RDN5 LBA 15 CF 001 XQ 01 Flow Transmitter at Production Well RD-N5 26 Production Well RD-I5 FLOW 0 - 45 kg/h AII ---- ---- ---- 1% F NA DCSRDM ○ H ---- ---- ○ ----
(P2)

76 RDN1 LBA 11 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-N1 26 HP WHCV RD-N1 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDM NA F C81 ○ ---- ○ ---- ○ ----

77 RDN1 LBA 11 CG 101 XG 01 VALVE OPEN POSITION -NOV FCV-N1 30 VALVE OPEN POSITION MOV FCV-I1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

78 RDN1 LBA 11 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-N1 31 VALVE CLOSE POSITION MOV FCV-I1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

79 RDN1 LBA 11 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-N1 22 HP WHCV RD-N1 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

80 RDN1 LBA 11 AA 101 XG 01 TORQUE OVER INDICATION -NOV FCV-N1 22 TORQUE OVER MOV FCV-I1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ○ ---- ---- ○ ----

81 RDN1 LBA 11 AA 101 XG 02 REMOTE MODE SELECTED -NOV FCV-N1 31 REMOTE MODE SELECTED MOV FCV-I1 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

82 RDN1 LBA 11 AA 101 XG 03 VALVE FAILURE -NOV FCV-N1 24 VALVE FAILURE MOV FCV-I1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ○ ---- ---- ○ ----

83 RDN1 LBA 11 AA 101 XG 04 LOSS OF POWER SOURCE -NOV FCV-N1 31 LOSS OF POWER SOURCE MOV FCV-I1 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ○ ---- ---- ○ ----

84 RDN2 LBA 12 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-N2 26 HP WHCV RD-N2 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDM NA F C81 ○ ---- ○ ---- ○ ----

85 RDN2 LBA 12 CG 101 XG 01 VALVE OPEN POSITION -NOV FCV-N2 30 VALVE OPEN POSITION MOV FCV-I2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

86 RDN2 LBA 12 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-N2 31 VALVE CLOSE POSITION MOV FCV-I2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

87 RDN2 LBA 12 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-N2 a HP WHCV RD-N2 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

88 RDN2 LBA 12 AA 101 XG 01 TORQUE OVER INDICATION -NOV FCV-N2 22 TORQUE OVER MOV FCV-I2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ○ ---- ---- ○ ----

89 RDN2 LBA 12 AA 101 XG 02 REMOTE MODE SELECTED -NOV FCV-N2 31 REMOTE MODE SELECTED MOV FCV-I2 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

90 RDN2 LBA 12 AA 101 XG 03 VALVE FAILURE -NOV FCV-N2 24 VALVE FAILURE MOV FCV-I2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ○ ---- ---- ○ ----

91 RDN2 LBA 12 AA 101 XG 04 LOSS OF POWER SOURCE -NOV FCV-N2 31 LOSS OF POWER SOURCE MOV FCV-I2 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ○ ---- ---- ○ ----

92 RDN3 LBA 13 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-N3 26 HP WHCV RD-N3 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDM NA F C81 ○ ---- ○ ---- ○ ----

93 RDN3 LBA 13 CG 101 XG 01 VALVE OPEN POSITION -NOV FCV-N3 30 VALVE OPEN POSITION MOV FCV-I3 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

94 RDN3 LBA 13 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-N3 31 VALVE CLOSE POSITION MOV FCV-I3 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

95 RDN3 LBA 13 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-N3 22 HP WHCV RD-N3 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

96 RDN3 LBA 13 AA 101 XG 01 TORQUE OVER INDICATION -NOV FCV-N3 22 TORQUE OVER MOV FCV-I3 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ○ ---- ---- ○ ----

97 RDN3 LBA 13 AA 101 XG 02 REMOTE MODE SELECTED -NOV FCV-N3 31 REMOTE MODE SELECTED MOV FCV-I3 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ---- ---- ---- ○ ----

98 RDN3 LBA 13 AA 101 XG 03 VALVE FAILURE -NOV FCV-N3 24 VALVE FAILURE MOV FCV-I3 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ○ ---- ---- ○ ----

99 RDN3 LBA 13 AA 101 XG 04 LOSS OF POWER SOURCE -NOV FCV-N3 31 LOSS OF POWER SOURCE MOV FCV-I3 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C81 ○ ○ ---- ---- ○ ----

100 RDN4 LBA 14 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-N4 26 HP WHCV RD-N4 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDM NA F C82 ○ ---- ○ ---- ○ ----
2.DCS IO LIST FOR HARD WIRE
2-9.WELLPAD-N AREA

APPLIED ALARM ILD or IBD


Tag No. NC/NO DCS APPLICATION ALARM SETPOINT
Number of VOLTAGE RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara ON DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
CONTACT BAND HHH HH H L LL
within 32 Chara
101 RDN4 LBA 14 CG 101 XG 01 VALVE OPEN POSITION -NOV FCV-N4 30 VALVE OPEN POSITION MOV FCV-I4 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ---- ---- ---- ○ ----

102 RDN4 LBA 14 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-N4 31 VALVE CLOSE POSITION MOV FCV-I4 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ---- ---- ---- ○ ----

103 RDN4 LBA 14 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-N4 22 HP WHCV RD-N4 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDM C82 ○ ---- ---- ---- ○ ----

104 RDN4 LBA 14 AA 101 XG 01 TORQUE OVER INDICATION -NOV FCV-N4 22 TORQUE OVER MOV FCV-I4 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ○ ---- ---- ○ ----

105 RDN4 LBA 14 AA 101 XG 02 REMOTE MODE SELECTED -NOV FCV-N4 31 REMOTE MODE SELECTED MOV FCV-I4 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ---- ---- ---- ○ ----

106 RDN4 LBA 14 AA 101 XG 03 VALVE FAILURE -NOV FCV-N4 24 VALVE FAILURE MOV FCV-I4 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ○ ---- ---- ○ ----

107 RDN4 LBA 14 AA 101 XG 04 LOSS OF POWER SOURCE -NOV FCV-N4 31 LOSS OF POWER SOURCE MOV FCV-I4 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ○ ---- ---- ○ ----

108 RDN5 LBA 15 FH 101 YB 01 VALVE OPEN & CLOSE COMMAND MOV FCV-N5 26 HP WHCV RD-N5 POSITION CMD 0 -100 % AOX ---- ---- ---- ---- DCSRDM NA F C82 ○ ---- ○ ---- ○ ----

109 RDN5 LBA 15 CG 101 XG 01 VALVE OPEN POSITION -NOV FCV-N5 30 VALVE OPEN POSITION MOV FCV-I5 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ---- ---- ---- ○ ----

110 RDN5 LBA 15 CG 101 XG 02 VALVE CLOSE POSITION- MOV FCV-N5 31 VALVE CLOSE POSITION MOV FCV-I5 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ---- ---- ---- ○ ----

111 RDN5 LBA 15 CG 101 XQ 01 VALVE OPENING INDICATION - 0% - 100 % - MOV FCV-N5 22 HP WHCV RD-N5 POSITION 0 -100 % AIX ---- ---- ---- ---- F NA DCSRDM C82 ○ ---- ---- ---- ○ ----

112 RDN5 LBA 15 AA 101 XG 01 TORQUE OVER INDICATION -NOV FCV-N5 22 TORQUE OVER MOV FCV-I5 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ○ ---- ---- ○ ----

113 RDN5 LBA 15 AA 101 XG 02 REMOTE MODE SELECTED -NOV FCV-N5 31 REMOTE MODE SELECTED MOV FCV-I5 OFF/ON ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ---- ---- ---- ○ ----

114 RDN5 LBA 15 AA 101 XG 03 VALVE FAILURE -NOV FCV-N5 24 VALVE FAILURE MOV FCV-I5 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ○ ---- ---- ○ ----

115 RDN5 LBA 15 AA 101 XG 04 LOSS OF POWER SOURCE -NOV FCV-N5 31 LOSS OF POWER SOURCE MOV FCV-I5 NORMAL/ALARM ---- DI ---- ---- NO ---- F NA DCSRDM C82 ○ ○ ---- ---- ○ ----

116 RD00 LBA 30 CP 005 XQ 01 PRESSURE TRANSMITTER TO HP SEPARATOR 21 HP SEPARATOR PRESSURE 0 - 20 Bar G AII ---- ---- ---- ---- F NA DCSRDM R30D ○ H ---- ---- ○ ----

117 RD00 CJU 70 GH 001 XG 02 WellPAD-N System Cabinet PSU or FWL Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSRDM ---- ---- ○ ---- ---- ○ ----

118 RD00 CJU 70 GH 001 XG 01 WellPAD-N System Cabinet Fan or Thermostat Alarm 0 NORMAL/ALARM ---- DI ---- ---- NO ---- CABINET NA DCSRDM ---- ---- ○ ---- ---- ○ ----
3.DCS IO LIST FOR COMMUNICATION
3-1.POWER PLANT FOR EACH UNIT AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
within 32 Chara
1 * CJJ 10 GH 001 XN 01 SPEED DETECTION #1 18 SPEED DETECTION #1 0-3600 rpm AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG103 ○ ---- ---- ---- ○ ----

2 * CJJ 10 GH 001 XN 02 SPEED DETECTION #2 18 SPEED DETECTION #2 0-3600 rpm AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG103 ○ ---- ---- ---- ○ ----

3 * CJJ 10 GH 001 XP 01 SPEED DETECTION #1 FAULT 24 SPEED DETECTION #1 FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG103 ---- P2 ---- ---- ○ ----

4 * CJJ 10 GH 001 XP 02 SPEED DETECTION #2 FAULT 24 SPEED DETECTION #2 FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG103 ---- P2 ---- ---- ○ ----

5 * CJJ 10 GH 001 XP 03 SPEED DETECTION HIGH 20 SPEED DETECTION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG103 ---- P2 ---- ---- ○ ----

6 * CJJ 10 GH 001 XN 03 SPEED LOOP POSITION DEMAND 26 SPEED LOOP POSITION DEMAND -100-+100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG104 ○ ---- ---- ---- ○ ----

242 * CJJ 10 GH 001 XP 78 TURBINE RUNBACK 15 TURBINE RUNBACK NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG111 ---- P2 ---- ---- ○ ----

7 * CJJ 10 GH 001 XP 04 POWER DETECTION #1 FAULT 24 POWER DETECTION #1 FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG112 ---- P2 ---- ---- ○ ----

8 * CJJ 10 GH 001 XP 05 POWER DETECTION #2 FAULT 24 POWER DETECTION #2 FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG112 ---- P2 ---- ---- ○ ----

9 * CJJ 10 GH 001 XP 06 POWER DEVIATION HIGH 20 POWER DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG112 ---- P2 ---- ---- ○ ----

10 * CJJ 10 GH 001 XN 04 DROOP OUTPUT 12 DROOP OUTPUT -80-+80 MW AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG113 ○ ---- ---- ---- ○ ----

11 * CJJ 10 GH 001 XN 05 POWER LOOP POSITION DEMAND 26 POWER LOOP POSITION DEMAND 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG113 ○ ---- ---- ---- ○ ----

12 * CJJ 10 GH 001 XN 06 POWER LOOP MW DEMAND 20 POWER LOOP MW DEMAND 0-80 MW AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG113 ○ ---- ---- ---- ○ ----

13 * CJJ 10 GH 001 XP 07 VOLTAGE BALANCE 60FL IN ACTION 30 VOLTAGE BALANCE 60FL IN ACTION OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG122 ○ ---- ---- ---- ○ ----

14 * CJJ 10 GH 001 XN 07 HPCV(L) POSITION DETECTION (A) 31 HPCV(L) POSITION DETECTION (A) 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG123 ○ ---- ---- ---- ○ ----

15 * CJJ 10 GH 001 XN 08 HPCV(L) POSITION DETECTION (B) 31 HPCV(L) POSITION DETECTION (B) 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG123 ○ ---- ---- ---- ○ ----

16 * CJJ 10 GH 001 XP 08 HPCV(L) POSITION DETECTION (B) FAULT 29 HPCV(L) POS DETECTION (B) FLT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

17 * CJJ 10 GH 001 XP 09 HPCV(L) POSITION DETECTION (A) FAULT 29 HPCV(L) POS DETECTION (A) FLT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

18 * CJJ 10 GH 001 XP 10 HPCV(L) POSITION DETECTION HIGH 31 HPCV(L) POSITION DETECTION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

19 * CJJ 10 GH 001 XN 09 HPCV(R) POSITION DETECTION (A) 31 HPCV(R) POSITION DETECTION (A) 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG123 ○ ---- ---- ---- ○ ----

20 * CJJ 10 GH 001 XN 10 HPCV(R) POSITION DETECTION (B) 31 HPCV(R) POSITION DETECTION (B) 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG123 ○ ---- ---- ---- ○ ----

21 * CJJ 10 GH 001 XP 11 HPCV(R) POSITION DETECTION (B) FAULT 29 HPCV(R) POS DETECTION (B) FLT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

22 * CJJ 10 GH 001 XP 12 HPCV(R) POSITION DETECTION (A) FAULT 29 HPCV(R) POS DETECTION (A) FLT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

23 * CJJ 10 GH 001 XP 13 HPCV(R) POSITION DETECTION HIGH 31 HPCV(R) POSITION DETECTION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

24 * CJJ 10 GH 001 XN 11 LPCV(L) POSITION DETECTION (A) 31 LPCV(L) POSITION DETECTION (A) 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG123 ○ ---- ---- ---- ○ ----

25 * CJJ 10 GH 001 XN 12 LPCV(L) POSITION DETECTION (B) 31 LPCV(L) POSITION DETECTION (B) 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG123 ○ ---- ---- ---- ○ ----

26 * CJJ 10 GH 001 XP 14 LPCV(L) POSITION DETECTION (B) FAULT 29 LPCV(L) POS DETECTION (B) FLT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

27 * CJJ 10 GH 001 XP 15 LPCV(L) POSITION DETECTION (A) FAULT 29 LPCV(L) POS DETECTION (A) FLT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

28 * CJJ 10 GH 001 XP 16 LPCV(L) POSITION DETECTION HIGH 31 LPCV(L) POSITION DETECTION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

29 * CJJ 10 GH 001 XN 13 LPCV(R) POSITION DETECTION (A) 31 LPCV(R) POSITION DETECTION (A) 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG123 ○ ---- ---- ---- ○ ----

30 * CJJ 10 GH 001 XN 14 LPCV(R) POSITION DETECTION (B) 31 LPCV(R) POSITION DETECTION (B) 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG123 ○ ---- ---- ---- ○ ----

31 * CJJ 10 GH 001 XP 17 LPCV(R) POSITION DETECTION (B) FAULT 29 LPCV(R) POS DETECTION (B) FLT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

32 * CJJ 10 GH 001 XP 18 LPCV(R) POSITION DETECTION (A) FAULT 29 LPCV(R) POS DETECTION (A) FLT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

33 * CJJ 10 GH 001 XP 19 LPCV(R) POSITION DETECTION HIGH 31 LPCV(R) POSITION DETECTION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG123 ---- P2 ---- ---- ○ ----

34 * CJJ 10 GH 001 XN 15 HPCV(L) POSITION COMMAND 24 HPCV(L) POSITION COMMAND 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG124 ○ ---- ---- ---- ○ ----

35 * CJJ 10 GH 001 XN 16 HPCV(R) POSITION COMMAND 24 HPCV(R) POSITION COMMAND 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG124 ○ ---- ---- ---- ○ ----

36 * CJJ 10 GH 001 XP 20 HPCV(L) CONTROL DEVIATION HIGH 31 HPCV(L) CONTROL DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG124 ---- P2 ---- ---- ○ ----

37 * CJJ 10 GH 001 XP 21 HPCV(R) CONTROL DEVIATION HIGH 30 HPCV(R) CONTROL DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG124 ---- P2 ---- ---- ○ ----

38 * CJJ 10 GH 001 XN 17 SPEED + POWER/MSP POSITION DEMAND 28 SPEED + POWER/MSP POS DEMAND -100-+100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG124 ○ ---- ---- ---- ○ ----

39 * CJJ 10 GH 001 XN 18 HPIPC LOOP POSITION DEMAND 26 HPIPC LOOP POSITION DEMAND 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG141 ○ ---- ---- ---- ○ ----

40 * CJJ 10 GH 001 XN 19 HPSP A DETECTION 16 HPSP A DETECTION 0-10 barg AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG142 ○ ---- ---- ---- ○ ---- Rev.4 Range is changed 4

41 * CJJ 10 GH 001 XN 20 HPSP B DETECTION 16 HPSP B DETECTION 0-10 barg AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG142 ○ ---- ---- ---- ○ ---- Rev.4 Range is changed 4

42 * CJJ 10 GH 001 XN 21 HPSP C DETECTION 16 HPSP C DETECTION 0-10 barg AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG142 ○ ---- ---- ---- ○ ---- Rev.4 Range is changed 4

43 * CJJ 10 GH 001 XN 22 HPSP DETECTION 14 HPSP DETECTION 0-10 barg AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG142 ○ ---- ---- ---- ○ ---- Rev.4 Range is changed 4

44 * CJJ 10 GH 001 XP 22 HPSP A DETECTION DEVIATION HIGH 31 HPSP A DETECTION DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

45 * CJJ 10 GH 001 XP 23 HPSP B DETECTION DEVIATION HIGH 31 HPSP B DETECTION DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

46 * CJJ 10 GH 001 XP 24 HPSP C DETECTION DEVIATION HIGH 31 HPSP C DETECTION DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

47 * CJJ 10 GH 001 XP 25 HPSP C DETECTION DEVIATION FAULT 22 HPSP C DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

48 * CJJ 10 GH 001 XP 26 HPSP B DETECTION DEVIATION FAULT 22 HPSP B DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

49 * CJJ 10 GH 001 XP 27 HPSP A DETECTION DEVIATION FAULT 22 HPSP A DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----
3.DCS IO LIST FOR COMMUNICATION
3-1.POWER PLANT FOR EACH UNIT AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
within 32 Chara
50 * CJJ 10 GH 001 XN 23 LPSP A DETECTION 16 LPSP A DETECTION 0-5 barg AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG142 ○ ---- ---- ---- ○ ---- Rev.4 Range is changed 4

51 * CJJ 10 GH 001 XN 24 LPSP B DETECTION 16 LPSP B DETECTION 0-5 barg AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG142 ○ ---- ---- ---- ○ ---- Rev.4 Range is changed 4

52 * CJJ 10 GH 001 XN 25 LPSP C DETECTION 16 LPSP C DETECTION 0-5 barg AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG142 ○ ---- ---- ---- ○ ---- Rev.4 Range is changed 4

53 * CJJ 10 GH 001 XN 26 LPSP DETECTION 14 LPSP DETECTION 0-5 barg AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG142 ○ ---- ---- ---- ○ ---- Rev.4 Range is changed 4

54 * CJJ 10 GH 001 XP 28 LPSP A DETECTION DEVIATION HIGH 31 LPSP A DETECTION DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

55 * CJJ 10 GH 001 XP 29 LPSP B DETECTION DEVIATION HIGH 31 LPSP B DETECTION DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

56 * CJJ 10 GH 001 XP 30 LPSP C DETECTION DEVIATION HIGH 31 LPSP C DETECTION DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

57 * CJJ 10 GH 001 XP 31 LPSP C DETECTION DEVIATION FAULT 22 LPSP C DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

58 * CJJ 10 GH 001 XP 32 LPSP B DETECTION DEVIATION FAULT 22 LPSP B DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

59 * CJJ 10 GH 001 XP 33 LPSP A DETECTION DEVIATION FAULT 22 LPSP A DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG142 ---- P2 ---- ---- ○ ----

60 * CJJ 10 GH 001 XN 27 HPLPC LOOP POSITION DEMAND 26 HPLPC LOOP POSITION DEMAND 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG151 ○ ---- ---- ---- ○ ----

61 * CJJ 10 GH 001 XP 34 LPCV(L) CONTROL DEVIATION H 30 LPCV(L) CONTROL DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG163 ---- P2 ---- ---- ○ ----

62 * CJJ 10 GH 001 XP 35 LPCV(R) CONTROL DEVIATION H 30 LPCV(R) CONTROL DEVIATION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG163 ---- P2 ---- ---- ○ ----

63 * CJJ 10 GH 001 XN 28 LPCV(L) CONTROL POSITION COMMAND 32 LPCV(L) CONTROL POSITION COMMAND 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG163 ○ ---- ---- ---- ○ ----

64 * CJJ 10 GH 001 XN 29 LPCV(R) CONTROL POSITION COMMAND 32 LPCV(R) CONTROL POSITION COMMAND 0-100 % AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG163 ○ ---- ---- ---- ○ ----

65 * CJJ 10 GH 001 XP 36 EHG PRIMARY / SECONDARY 23 EHG PRIMARY / SECONDARY OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG170 ○ ---- ---- ---- ○ ----

243 * CJJ 10 GH 001 XP 79 EHG ISLAND OPERATION SECONDARY 30 EHG ISLAND OPERATION SECONDARY OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG170 ○ ---- ○ ---- ○ ----

244 * CJJ 10 GH 001 XP 80 HOUSE LOAD OPERATION FROM SWITCHYARD 30 HOUSE LOAD OPE FROM SWITCHYARD OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG170 ○ ---- ○ ---- ○ ----

66 * CJJ 10 GH 001 XN 30 REACTIVE POWER DETECTION 24 REACTIVE POWER DETECTION 80-+80 MVAR AI TCP/IP ---- ---- *TGR ---- *DCS TG203 ○ ---- ---- ---- ○ ----

67 * CJJ 10 GH 001 XP 37 91Q LAG LIMIT 13 91Q LAG LIMIT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG203 ---- P2 ---- ---- ○ ----

68 * CJJ 10 GH 001 XP 38 91Q LEAD LIMIT 14 91Q LEAD LIMIT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG203 ---- P2 ---- ---- ○ ----

69 * CJJ 10 GH 001 XP 39 REACTIVE POWER DETECTION #1 FAULT 31 REACTIVE POWER DETECTION #1 FLT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG203 ---- P2 ---- ---- ○ ----

70 * CJJ 10 GH 001 XP 40 REACTIVE POWER DETECTION #2 FAULT 31 REACTIVE POWER DETECTION #2 FLT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG203 ---- P2 ---- ---- ○ ----

71 * CJJ 10 GH 001 XP 41 REACTIVE POWER DETECTION DEVIATION HIGH 31 REACTIVE POW DETECTION DEV HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG203 ---- P2 ---- ---- ○ ----

72 * CJJ 10 GH 001 XN 31 GEN VOLTAGE 11 GEN VOLTAGE 0-15 V AI TCP/IP ---- NO ---- *TGR ---- *DCS TG204 ○ ---- ---- ---- ○ ----

73 * CJJ 10 GH 001 XP 42 GEN OVER / UNDER VOLTAGE 24 GEN OVER / UNDER VOLTAGE NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG204 ---- P2 ---- ---- ○ ----

74 * CJJ 10 GH 001 XP 43 GEN VOLTAGE DETECTION #1 FAULT 30 GEN VOLTAGE DETECTION #1 FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG204 ---- P2 ---- ---- ○ ----

75 * CJJ 10 GH 001 XP 44 GEN VOLTAGE DETECTION #2 FAULT 30 GEN VOLTAGE DETECTION #2 FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG204 ---- P2 ---- ---- ○ ----

76 * CJJ 10 GH 001 XP 45 GEN VOLTAGE DETECTION HIGH 26 GEN VOLTAGE DETECTION HIGH NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG204 ---- P2 ---- ---- ○ ----

77 * CJJ 10 GH 001 XN 32 FIED CURRENT (CONTROL) 22 FIED CURRENT (CONTROL) 0-32 A AI TCP/IP ---- ---- ---- *TGR ---- *DCS TG205 ○ ---- ---- ---- ○ ---- Rev.4 Range is changed 4

78 * CJJ 10 GH 001 XP 46 FIELD CURRENT DETECTION FAULT 29 FIELD CURRENT DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG205 ---- P2 ---- ---- ○ ----

79 * CJJ 10 GH 001 XP 47 DIODE FAULT 11 DIODE FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG205 ---- P2 ---- ---- ○ ---- Rev.4 Duplicated. Deleted 4

80 * CJJ 10 GH 001 XP 48 AQR/APfR AUTO OFF 17 AQR/APfR AUTO OFF NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG221 ---- P2 ---- ---- ○ ----

81 * CJJ 10 GH 001 XP 49 PSS ABNOMAL 11 PSS ABNOMAL NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG231 ---- P2 ---- ---- ○ ----

82 * CJJ 10 GH 001 XP 50 DC24V P/S F1 TRIP 17 DC24V P/S F1 TRIP NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG301 ---- P2 ---- ---- ○ ----

83 * CJJ 10 GH 001 XP 51 DC24V P/S F2 TRIP 17 DC24V P/S F2 TRIP NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG301 ---- P2 ---- ---- ○ ----

84 * CJJ 10 GH 001 XP 52 DC24V P/S M1 TRIP 17 DC24V P/S M1 TRIP NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG301 ---- P2 ---- ---- ○ ----

85 * CJJ 10 GH 001 XP 53 DC24V P/S M2 TRIP 17 DC24V P/S M2 TRIP NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG301 ---- P2 ---- ---- ○ ----

86 * CJJ 10 GH 001 XP 54 BOTH SPEED DETECTION FAULT 26 BOTH SPEED DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

87 * CJJ 10 GH 001 XP 55 BOTH POWER DETECTION FAULT 26 BOTH POWER DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

88 * CJJ 10 GH 001 XP 56 BOTH HPCV(L) POS DETECTION FAULT 32 BOTH HPCV(L) POS DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

89 * CJJ 10 GH 001 XP 57 BOTH HPCV(R) POS DETECTION FAULT 32 BOTH HPCV(R) POS DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

90 * CJJ 10 GH 001 XP 58 BOTH LPCV(L) POS DETECTION FAULT 32 BOTH LPCV(L) POS DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

91 * CJJ 10 GH 001 XP 59 BOTH LPCV(R) POS DETECTION FAULT 32 BOTH LPCV(R) POS DETECTION FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

95 * CJJ 10 GH 001 XP 63 THYRISTOR FUSE TRIP 19 THYRISTOR FUSE TRIP NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

96 * CJJ 10 GH 001 XP 64 FAC UNIT P/S FAILURE 20 FAC UNIT P/S FAILURE NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

97 * CJJ 10 GH 001 XP 65 FAC UNIT PULSE FAULT 20 FAC UNIT PULSE FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

98 * CJJ 10 GH 001 XP 66 SYNCHRONOUS MCCB TRIP 21 SYNCHRONOUS MCCB TRIP NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

99 * CJJ 10 GH 001 XP 67 EXCITATION MCCB TRIP 20 EXCITATION MCCB TRIP NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

100 * CJJ 10 GH 001 XP 68 BOTH REACTIVE POWER FAULT 25 BOTH REACTIVE POWER FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4
3.DCS IO LIST FOR COMMUNICATION
3-1.POWER PLANT FOR EACH UNIT AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
within 32 Chara
101 * CJJ 10 GH 001 XP 69 DIODE FAULT 11 DIODE FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG302 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

102 * CJJ 10 GH 001 XP 70 TGR CPU-A OR B STOP 19 TGR CPU-A OR B STOP NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG303 ---- P2 ---- ---- ○ ----

103 * CJJ 10 GH 001 XP 71 TGR MICREXS ABNOMAL 19 TGR MICREXS ABNOMAL NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG303 ---- P2 ---- ---- ○ ----

104 * CJJ 10 GH 001 XP 72 TGR STATUS DISCREPANCY 22 TGR STATUS DISCREPANCY NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG303 ---- P2 ---- ---- ○ ----

106 * CJJ 10 GH 001 XP 74 TGR P/S ABNOMAL 15 TGR P/S ABNOMAL NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG303 ---- P2 ---- ---- ○ ----

108 * CJJ 10 GH 001 XP 76 AVR RETURN FAULT 16 AVR RETURN FAULT NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG304 ---- P2 ---- ---- ○ ----

109 * CJJ 10 GH 001 XP 77 AVR CONTROL POWER ABNOMAL 25 AVR CONTROL POWER ABNOMAL NORMAL/ALARM ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TG304 ---- P2 ---- ---- ○ ----

110 * CJJ 10 GH 002 XP 01 FOR STEP DELAY INDICATION ON [STATUS] STEP1 28 STEP DELAY ON [STATUS] STEP1 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

111 * CJJ 10 GH 002 XP 02 FOR STEP DELAY INDICATION ON [STATUS] STEP2 28 STEP DELAY ON [STATUS] STEP2 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

112 * CJJ 10 GH 002 XP 03 FOR STEP DELAY INDICATION ON [STATUS] STEP3 28 STEP DELAY ON [STATUS] STEP3 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

113 * CJJ 10 GH 002 XP 04 FOR STEP DELAY INDICATION ON [STATUS] STEP4 28 STEP DELAY ON [STATUS] STEP4 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

114 * CJJ 10 GH 002 XP 05 FOR STEP DELAY INDICATION ON [STATUS] STEP5 28 STEP DELAY ON [STATUS] STEP5 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

115 * CJJ 10 GH 002 XP 06 FOR STEP DELAY INDICATION ON [STATUS] STEP6 28 STEP DELAY ON [STATUS] STEP6 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

116 * CJJ 10 GH 002 XP 07 FOR STEP DELAY INDICATION ON [STATUS] STEP7 28 STEP DELAY ON [STATUS] STEP7 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

117 * CJJ 10 GH 002 XP 08 FOR STEP DELAY INDICATION ON [STATUS] STEP8 28 STEP DELAY ON [STATUS] STEP8 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

118 * CJJ 10 GH 002 XP 09 FOR STEP DELAY INDICATION ON [STATUS] STEP9 28 STEP DELAY ON [STATUS] STEP9 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

119 * CJJ 10 GH 002 XP 10 FOR STEP DELAY INDICATION ON [STATUS] STEP10 29 STEP DELAY ON [STATUS] STEP10 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

120 * CJJ 10 GH 002 XP 11 FOR STEP DELAY INDICATION ON [STATUS] STEP11 29 STEP DELAY ON [STATUS] STEP11 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

121 * CJJ 10 GH 002 XP 12 FOR STEP DELAY INDICATION ON [STATUS] STEP12 29 STEP DELAY ON [STATUS] STEP12 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

122 * CJJ 10 GH 002 XP 13 FOR RUNNING STEP INDICATION ON [STATUS] STEP1 30 RUNNING STEP ON [STATUS] STEP1 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

123 * CJJ 10 GH 002 XP 14 FOR RUNNING STEP INDICATION ON [STATUS] STEP2 30 RUNNING STEP ON [STATUS] STEP2 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

124 * CJJ 10 GH 002 XP 15 FOR RUNNING STEP INDICATION ON [STATUS] STEP3 30 RUNNING STEP ON [STATUS] STEP3 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

125 * CJJ 10 GH 002 XP 16 FOR RUNNING STEP INDICATION ON [STATUS] STEP4 30 RUNNING STEP ON [STATUS] STEP4 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

126 * CJJ 10 GH 002 XP 17 FOR RUNNING STEP INDICATION ON [STATUS] STEP5 30 RUNNING STEP ON [STATUS] STEP5 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

127 * CJJ 10 GH 002 XP 18 FOR RUNNING STEP INDICATION ON [STATUS] STEP6 30 RUNNING STEP ON [STATUS] STEP6 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

128 * CJJ 10 GH 002 XP 19 FOR RUNNING STEP INDICATION ON [STATUS] STEP7 30 RUNNING STEP ON [STATUS] STEP7 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

129 * CJJ 10 GH 002 XP 20 FOR RUNNING STEP INDICATION ON [STATUS] STEP8 30 RUNNING STEP ON [STATUS] STEP8 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

130 * CJJ 10 GH 002 XP 21 FOR RUNNING STEP INDICATION ON [STATUS] STEP9 30 RUNNING STEP ON [STATUS] STEP9 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

131 * CJJ 10 GH 002 XP 22 FOR RUNNING STEP INDICATION ON [STATUS] STEP10 31 RUNNING STEP ON [STATUS] STEP10 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

132 * CJJ 10 GH 002 XP 23 FOR RUNNING STEP INDICATION ON [STATUS] STEP11 31 RUNNING STEP ON [STATUS] STEP11 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

133 * CJJ 10 GH 002 XP 24 FOR RUNNING STEP INDICATION ON [STATUS] STEP12 31 RUNNING STEP ON [STATUS] STEP12 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

134 * CJJ 10 GH 002 XP 25 FOR RUNNING STEP INDICATION ON [STATUS] STEP13 31 RUNNING STEP ON [STATUS] STEP13 OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT032 ○ ---- ---- ---- ○ ----

135 * CJJ 10 GH 002 XP 26 AVT OPERATION ON 16 AVT OPERATION ON OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT033 ○ ---- ---- ---- ○ ----

136 * CJJ 10 GH 002 XP 27 AVT CONDITION OK 16 AVT CONDITION OK OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT034 ○ ---- ---- ---- ○ ----

137 * CJJ 10 GH 002 XP 28 AVT ABNOMAL 11 AVT ABNOMAL OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT034 ○ ---- ---- ---- ○ ----

138 * CJJ 10 GH 002 XP 29 HPSV(L) GROUP 13 HPSV(L) GROUP OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT035 ○ ---- ---- ---- ○ ----

139 * CJJ 10 GH 002 XP 30 HPSV(R) GROUP 13 HPSV(R) GROUP OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT035 ○ ---- ---- ---- ○ ----

140 * CJJ 10 GH 002 XP 31 LPSV(L) GROUP 13 LPSV(L) GROUP OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT035 ○ ---- ---- ---- ○ ----

141 * CJJ 10 GH 002 XP 32 LPSV(R) GROUP 13 LPSV(R) GROUP OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT035 ○ ---- ---- ---- ○ ----

142 * CJJ 10 GH 002 XP 33 AVT OPERATION TEST 18 AVT OPERATION TEST OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT036 ○ ---- ---- ---- ○ ----

143 * CJJ 10 GH 002 XP 34 AVT OPERATION RESET 19 AVT OPERATION RESET OFF/ON ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT036 ○ ---- ---- ---- ○ ----

144 * CJJ 10 GH 002 XP 35 HPSV(L) GROUP END 17 HPSV(L) GROUP END OFF/END ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT303 ○ ---- ---- ---- ○ ---- Rev.4; Status us changed 4

145 * CJJ 10 GH 002 XP 36 HPSV(R) GROUP END 17 HPSV(R) GROUP END OFF/END ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT313 ○ ---- ---- ---- ○ ---- Rev.4; Status us changed 4

146 * CJJ 10 GH 002 XP 37 LPSV(L) GROUP END 17 LPSV(L) GROUP END OFF/END ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT323 ○ ---- ---- ---- ○ ---- Rev.4; Status us changed 4

147 * CJJ 10 GH 002 XP 38 LPSV(R) GROUP END 17 LPSV(R) GROUP END OFF/END ---- DI TCP/IP ---- NO ---- *TGR ---- *DCS TT333 ○ ---- ---- ---- ○ ---- Rev.4; Status us changed 4

148 * CHA 10 GH 001 XP 01 GEN DISTANCE 21G-A 18 GEN DISTANCE 21G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

149 * CHA 10 GH 001 XP 02 GEN V/Hz 24G-A 14 GEN V/Hz 24G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

150 * CHA 10 GH 001 XP 03 GEN UNDERVOLTAGE 27G-A 22 GEN UNDERVOLTAGE 27G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

151 * CHA 10 GH 001 XP 04 GEN THERD HARMONIC NEUTRAL UNDERVOLTAGE 27TNG-A 30 GEN 3RD NTRL UNDERVOLT 27TNG-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

152 * CHA 10 GH 001 XP 05 GEN REVERSE POWER 32G-A 23 GEN REVERSE POWER 32G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4
3.DCS IO LIST FOR COMMUNICATION
3-1.POWER PLANT FOR EACH UNIT AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
within 32 Chara
153 * CHA 10 GH 001 XP 06 LOSS OF FIELD 40G-A 19 LOSS OF FIELD 40G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

154 * CHA 10 GH 001 XP 07 NEGATIVE SEQUENCE OVER-CURRENT 46G-A 31 NEGATIVE SEQ OVER-CURRENT 46G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

155 * CHA 10 GH 001 XP 08 GEN INADVERTENT ENEGIZING 50/27G-A 32 GEN INADVERTENT ENEGIZE 50/27G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

156 * CHA 10 GH 001 XP 09 GENERATOR OVER VOLTAGE 2ND STAGE 59G2-A 30 GEN OVER VOLT 2ND STAGE 59G2-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

157 * CHA 10 GH 001 XP 10 GENERATOR OVER VOLTAGE 2ND STAGE 59GNG2-A 32 GEN OVER VOLT 2ND STAGE 59GNG2-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

158 * CHA 10 GH 001 XP 11 GEN OUT OF STEP 78G-A 21 GEN OUT OF STEP 78G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

159 * CHA 10 GH 001 XP 12 GEN DIFFERENTIAL 87G-A 22 GEN DIFFERENTIAL 87G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

160 * CHA 10 GH 001 XP 13 GENE LOCKOUT RELAY-A 86G-A 26 GENE LOCKOUT RELAY-A 86G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT01 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

161 * CHA 10 GH 001 XP 14 GEN DISTANCE 21G-B 18 GEN DISTANCE 21G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

162 * CHA 10 GH 001 XP 15 GEN V/Hz 24G-B 14 GEN V/Hz 24G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

163 * CHA 10 GH 001 XP 16 GEN UNDERVOLTAGE 27G-B 22 GEN UNDERVOLTAGE 27G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

164 * CHA 10 GH 001 XP 17 GEN THERD HARMONIC NEUTRAL UNDERVOLTAGE 27TNG-B 30 GEN 3RD NTRL UNDERVOLT 27TNG-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

165 * CHA 10 GH 001 XP 18 GEN REVERSE POWER 32G-B 23 GEN REVERSE POWER 32G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

166 * CHA 10 GH 001 XP 19 LOSS OF FIELD 40G-B 19 LOSS OF FIELD 40G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

167 * CHA 10 GH 001 XP 20 NEGATIVE SEQUENCE OVER-CURRENT 46G-B 31 NEGATIVE SEQ OVER-CURRENT 46G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

168 * CHA 10 GH 001 XP 21 GEN INADVERTENT ENEGIZING 50/27G-B 32 GEN INADVERTENT ENEGIZE 50/27G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

169 * CHA 10 GH 001 XP 22 GENERATOR OVER VOLTAGE 2ND STAGE 59G2-B 30 GEN OVER VOLT 2ND STAGE 59G2-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

170 * CHA 10 GH 001 XP 23 GENERATOR OVER VOLTAGE 2ND STAGE 59GNG2-B 32 GEN OVER VOLT 2ND STAGE 59GNG2-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

171 * CHA 10 GH 001 XP 24 GEN OUT OF STEP 78G-B 21 GEN OUT OF STEP 78G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

172 * CHA 10 GH 001 XP 25 GEN DIFFERENTIAL 87G-B 22 GEN DIFFERENTIAL 87G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

173 * CHA 10 GH 001 XP 26 GENE LOCKOUT RELAY-B 86G-B 26 GENE LOCKOUT RELAY-B 86G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT02 ---- P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

174 * CHA 10 GH 001 XP 27 GEN BREAKER FAILURE 50F-A 25 GEN BREAKER FAILURE 50F-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT03 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

175 * CHA 10 GH 001 XP 28 GEN OVER-FREQUENCY HH 81HHG-A 29 GEN OVER-FREQUENCY HH 81HHG-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT03 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

176 * CHA 10 GH 001 XP 29 GEN OVER-FREQUENCY H 81HG-A 27 GEN OVER-FREQUENCY H 81HG-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT03 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

177 * CHA 10 GH 001 XP 30 GEN OVER-FREQUENCY L 81LG-A 27 GEN OVER-FREQUENCY L 81LG-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT03 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

178 * CHA 10 GH 001 XP 31 GEN OVER-FREQUENCY LL 81LLG-A 29 GEN OVER-FREQUENCY LL 81LLG-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT03 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

179 * CHA 10 GH 001 XP 32 GEN BREAKER FAILURE 50F-B 25 GEN BREAKER FAILURE 50F-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT03 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

180 * CHA 10 GH 001 XP 33 GEN OVER-FREQUENCY HH 81HHG-B 29 GEN OVER-FREQUENCY HH 81HHG-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT03 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

181 * CHA 10 GH 001 XP 34 GEN OVER-FREQUENCY H 81HG-B 27 GEN OVER-FREQUENCY H 81HG-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT03 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

182 * CHA 10 GH 001 XP 35 GEN OVER-FREQUENCY L 81LG-B 27 GEN OVER-FREQUENCY L 81LG-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT03 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

183 * CHA 10 GH 001 XP 36 GEN OVER-FREQUENCY LL 81LLG-B 29 GEN OVER-FREQUENCY LL 81LLG-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT03 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

184 * CHA 10 GH 001 XP 37 GEN OVER-VOLTAGE 1ST STAGE 59G1-A 30 GEN OVER-VOLT 1ST STAGE 59G1-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT04 ---- P2 ---- ---- ○ ----

185 * CHA 10 GH 001 XP 38 GEN NEUTRAL OVER-VOLTAGE 1ST STAGE 59GN1-A 32 GEN NTRL OVRVOLT 1ST STG 59GN1-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT04 ---- P2 ---- ---- ○ ----

186 * CHA 10 GH 001 XP 39 GEN VOLTAGE BALANCE 60G-A 25 GEN VOLTAGE BALANCE 60G-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT04 ---- P2 ---- ---- ○ ----

187 * CHA 10 GH 001 XP 40 GEN FIELD GROUND FAULT 64F 26 GEN FIELD GROUND FAULT 64F NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT04 ---- P2 ---- ---- ○ ----

188 * CHA 10 GH 001 XP 41 GEN OVER-VOLTAGE 1ST STAGE 59G1-B 32 GEN OVERVOLTAGE 1ST STAGE 59G1-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT04 ---- P2 ---- ---- ○ ----

189 * CHA 10 GH 001 XP 42 GEN NEUTRAL OVER-VOLTAGE 1ST STAGE 59GN1-B 32 GEN NTRL OVRVOLT 1ST STG 59GN1-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT04 ---- P2 ---- ---- ○ ----

190 * CHA 10 GH 001 XP 43 GEN VOLTAGE BALANCE 60G-B 25 GEN VOLTAGE BALANCE 60G-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT04 ---- P2 ---- ---- ○ ----

191 * CHA 10 GH 001 XP 44 GSUT BREAKER FAULT 50BFGT-A 27 GSUT BREAKER FAULT 50BFGT-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT05 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

192 * CHA 10 GH 001 XP 45 GSUT RESTRICTED EARTH FAULT 64REF-A 31 GSUT RESTRICT EARTH FLT 64REF-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT05 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

193 * CHA 10 GH 001 XP 46 GEN BUS DIFFERENTIAL 87GB 25 GEN BUS DIFFERENTIAL 87GB NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT05 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

194 * CHA 10 GH 001 XP 47 11kV BUS EARTH FAULT 64B 24 11kV BUS EARTH FAULT 64B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT05 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

195 * CHA 10 GH 001 XP 48 GSUT UNDER FREQUENCY 81O-A 26 GSUT UNDER FREQUENCY 81O-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT05 ○ P1 ---- ---- ○ ---- Rev.4 Misdescription is corrected 4

196 * CHA 10 GH 001 XP 49 GSUT UNDER FREQUENCY 81U-A 26 GSUT UNDER FREQUENCY 81U-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT05 ○ P1 ---- ---- ○ ---- Rev.4 Misdescription is corrected 4

Note)Either operated should be


197 * CHA 10 GH 001 XP 50 GSUT TIME CURRENT WITH INSTANEOUS ELEMENT 50/51GT-A 27 GSUT TIME CURRENT 50/51GT-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT05 ○ P1 ---- ---- ○ ---- 4
alarmed.
Note)Either operated should be
198 * CHA 10 GH 001 XP 51 GSUT TIME GROUND CURRENT WITH INSTANTANEOUS ELEMENT 50/51NGT-A 32 GSUT TIME GRND CURRNT 50/51NGT-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT05 ○ P1 ---- ---- ○ ---- 4
alarmed.

199 * CHA 10 GH 001 XP 52 GSUT DIFFERENTIAL 87GT-A 24 GSUT DIFFERENTIAL 87GT-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT05 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

200 * CHA 10 GH 001 XP 53 GSUT UNDER FREQUENCY 81O-B 26 GSUT UNDER FREQUENCY 81O-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT06 ○ P1 ---- ---- ○ ---- Rev.4 Misdescription is corrected 4

201 * CHA 10 GH 001 XP 54 GSUT UNDER FREQUENCY 81U-B 26 GSUT UNDER FREQUENCY 81U-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT06 ○ P1 ---- ---- ○ ---- Rev.4 Misdescription is corrected 4

Note)Either operated should be


202 * CHA 10 GH 001 XP 55 GSUT TIME CURRENT WITH INSTANEOUS ELEMENT 50/51GT-B 27 GSUT TIME CURRENT 50/51GT-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT06 ○ P1 ---- ---- ○ ---- 4
alarmed.
3.DCS IO LIST FOR COMMUNICATION
3-1.POWER PLANT FOR EACH UNIT AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Number of SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
Chara TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
within 32 Chara
Note)Either operated should be
203 * CHA 10 GH 001 XP 56 GSUT TIME GROUND CURRENT WITH INSTANTANEOUS ELEMENT 50/51NGT-B 32 GSUT TIME GRND CURRNT 50/51NGT-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT06 ○ P1 ---- ---- ○ ---- 4
alarmed.

204 * CHA 10 GH 001 XP 57 GSUT DIFFERENTIAL 87GT-B 24 GSUT DIFFERENTIAL 87GT-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT06 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

209 * CHA 10 GH 001 XP 62 GSUT BREAKER FAULT 50BFGT-B 27 GSUT BREAKER FAULT 50BFGT-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT06 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

210 * CHA 10 GH 001 XP 63 GSUT RESTRICTED EARTH FAULT 64REF-B 31 GSUT RESTRICT EARTH FLT 64REF-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT06 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

Note)Either operated should be


205 * CHA 10 GH 001 XP 58 UAT TIME CURRENT WITH INSTANTANEOUS ELEMENT 50/51UT-A 26 UAT TIME CURRENT 50/51UT-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT07 ○ P1 ---- ---- ○ ---- 4
alarmed.
Note)Either operated should be
206 * CHA 10 GH 001 XP 59 UAT TIME GROUND CURRENT WITH INSTANTANEOUS ELEMENT 50/51NUT-A 30 UAT TIME GROUND CUR 50/51NUT-A NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT07 ○ P1 ---- ---- ○ ---- 4
alarmed.

207 * CHA 10 GH 001 XP 60 UATDIFFERENTIAL 87UT 20 UATDIFFERENTIAL 87UT NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT07 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

208 * CHA 10 GH 001 XP 61 UAT GROUND DIFFERENTIAL 87NUT 29 UAT GROUND DIFFERENTIAL 87NUT NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT07 ○ P1 ---- ---- ○ ---- Rev.4; Alarm level is changed 4

Note)Either operated should be


245 * CHA 10 GH 001 XP 64 UAT TIME CURRENT WITH INSTANTANEOUS ELEMENT 50/51UT-B 26 UAT TIME CURRENT 50/51UT-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT07 ○ P1 ---- ---- ○ ----
alarmed.
Note)Either operated should be
246 * CHA 10 GH 001 XP 65 UAT TIME GROUND CURRENT WITH INSTANTANEOUS ELEMENT 50/51NUT-B 30 UAT TIME GROUND CUR 50/51NUT-B NORMAL/ALARM ---- DI IEC61850 ---- NO ---- *GPR ---- *DCS GT07 ○ P1 ---- ---- ○ ----
alarmed.

247 * CHA 10 GH 001 XP 80 Generator Trip 86G-A Communication Fail 31 GEN PROTECTION RELAY A COM FAIL NORMAL/ALARM ---- DI ---- ---- NO ---- ---- ---- ---- ---- ---- P2 ---- ---- ○ ----

248 * CHA 10 GH 001 XP 81 Generator Trip 86G-B Communication Fail 31 GEN PROTECTION RELAY B COM FAIL NORMAL/ALARM ---- DI ---- ---- NO ---- ---- ---- ---- ---- ---- P2 ---- ---- ○ ----

249 * CHA 10 GH 001 XP 82 Generator Step Up Transformer 86U-A Communication Fail 32 GSUT PROTECTION RELAY A COM FAIL NORMAL/ALARM ---- DI ---- ---- NO ---- ---- ---- ---- ---- ---- P2 ---- ---- ○ ----

250 * CHA 10 GH 001 XP 83 Generator Step Up Transformer 86U-B Communication Fail 32 GSUT PROTECTION RELAY B COM FAIL NORMAL/ALARM ---- DI ---- ---- NO ---- ---- ---- ---- ---- ---- P2 ---- ---- ○ ----

251 * CHA 10 GH 001 XP 84 Unit Auxiliary Transformer 86UAT Communication Fail 29 UAT PROTECTION RELAY COM FAIL NORMAL/ALARM ---- DI ---- ---- NO ---- ---- ---- ---- ---- ---- P2 ---- ---- ○ ----
3.DCS IO LIST FOR COMMUNICATION
3-1.POWER PLANT FOR EACH UNIT AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Tag No. SIGNAL RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
within 32 Chara
FO
209 * BAT 10 XP 01 U1 GENERATOR TRANSFORMER WINDING TEMPERATURE ALARM 30 GSUT WINDING TEMPERATURE ALARM NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ----
CABLE
FO
210 * BAT 10 XP 02 U1 GENERATOR TRANSFORMER WINDING TEMPERATURE TRIP 29 GSUT WINDING TEMPERATURE TRIP NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ○
CABLE
FO
213 * BAT 10 XP 05 U1 GENERATOR TRANSFORMER OIL TEMPERATURE ALARM 26 GSUT OIL TEMPERATURE ALARM NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ----
CABLE
FO
214 * BAT 10 XP 06 U1 GENERATOR TRANSFORMER OIL TEMPERATURE TRIP 25 GSUT OIL TEMPERATURE TRIP NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ○
CABLE
FO
215 * BAT 10 XN 01 U1 GENERATOR TRANSFORMER OLTC POSITION 18 GSUT OLTC POSITION 0-17 Tap AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
FO
216 * BAT 10 XP 07 U1 GENERATOR TRANSFORMER OLTC POSITION IN PROGRESS/INCOMPLETE TAP CHAN 29 GSUT OLTC POSITION TAP CHANGE NORMAL/ALARM ---- DI NO *GSUT *DCS ○ P2 ---- ---- ○ ----
CABLE
FO
217 * BAT 10 XP 08 U1 GENERATOR TRANSFORMER OLTC MOTOR TRIP 20 GSUT OLTC MOTOR TRIP NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ○
CABLE
FO
219 * BAT 10 XP 10 U1 GENERATOR TRANSFORMER OLTC TANK PRESSURE RELIEF DEVICE 30 GSUT OLTC TANK PRESSURE RELIEF NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ○
CABLE
FO
220 * BAT 10 XP 11 U1 GENERATOR TRANSFORMER OLTC TANK RS2001 RELAY 27 GSUT OLTC TANK RS2001 RELAY NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ○
CABLE
FO
221 * BAT 10 XP 12 U1 GENERATOR TRANSFORMER BUCHHOLZ 1ST STAGE 23 GSUT BUCHHOLZ 1ST STAGE NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ----
CABLE
FO
222 * BAT 10 XP 13 U1 GENERATOR TRANSFORMER BUCHHOLZ 2ND STAGE 23 GSUT BUCHHOLZ 2ND STAGE NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ○
CABLE
FO
223 * BAT 10 XP 14 U1 GENERATOR TRANSFORMER MAIN TANK PRESSURE RELIEF DEVICE TRIP 30 GSUT MAIN TANK PRESSURE RELIEF NORMAL/TRIP ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ○
CABLE
0 FO
225 * BAT 10 XN 02 U1 GT WINDING TEMPERATURE HV PHASE R 22 GSUT WINDING TEMP HV R 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
226 * BAT 10 XN 03 U1 GT WINDING TEMPERATURE LV PHASE R 22 GSUT WINDING TEMP LV R 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
227 * BAT 10 XN 04 U1 GT WINDING HOT SPOT TEMPERATURE HV PHASE R 28 GSUT WINDING HV PHASE R TEMP 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
228 * BAT 10 XN 05 U1 GT WINDING HOT SPOT TEMPERATURE HV PHASE S 28 GSUT WINDING HV PHASE S TEMP 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
229 * BAT 10 XN 06 U1 GT WINDING HOT SPOT TEMPERATURE HV PHASE T 28 GSUT WINDING LV PHASE T TEMP 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
230 * BAT 10 XN 07 U1 GT WINDING HOT SPOT TEMPERATURE LV PHASE R 28 GSUT WINDING LV PHASE R TEMP 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
231 * BAT 10 XN 08 U1 GT WINDING HOT SPOT TEMPERATURE LV PHASE S 28 GSUT WINDING LV PHASE S TEMP 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
232 * BAT 10 XN 09 U1 GT WINDING HOT SPOT TEMPERATURE LV PHASE T 28 GSUT WINDING LV PHASE T TEMP 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
233 * BAT 10 XN 10 U1 GT WINDING HOT SPOT TEMPERATURE CORE FE 25 GSUT WINDING CORE FE TEMP 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
234 * BAT 10 XN 11 U1 GT OIL TEMPERATURE FOR AMBIENT TEMPERATURE 21 GSUT AMBIENT OIL TEMP 0-130 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
235 * BAT 10 XN 12 U1 GT OIL TEMPERATURE FOR MAIN TANK TOP LEVEL 23 GSUT MAIN TANK OIL TEMP 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
0 FO
237 * BAT 10 XN 14 U1 GT OIL TEMPERATURE FOR OLTC TANK 23 GSUT OLTC TANK OIL TEMP 0-150 C AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
FO
239 * BAT 10 XP 17 U1 GT CONSERVATOR MAIN TANK OIL LEVEL LL 27 GSUT MAIN TANK OIL LEVEL LL NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ○
CABLE
FO
241 * BAT 10 XP 19 U1 GT CONSERVATOR OLTC TANK OIL LEVEL LL 27 GSUT OLTC TANK OIL LEVEL LL NORMAL/ALARM ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ○
CABLE
FO
242 * BAT 10 XP 20 U1 GT FAN GROUP RUNNING 22 GSUT FAN GROUP RUNNING OFF/ON ---- DI NO *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
FO
245 * BAT 10 XP 23 U1 GT FAN GROUP TRIP 19 GSUT FAN GROUP TRIP NORMAL/TRIP ---- DI NO *GSUT *DCS ---- P2 ---- ---- ○ ----
CABLE
FO
248 * BAT 10 XN 15 U1 GT GAS MOISTURE CONTENT H2 28 GSUT H2 GAS MOISTURE CONTENT 0-10 PPM AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
FO
249 * BAT 10 XN 16 U1 GT GAS MOISTURE CONTENT CO 28 GSUT CO GAS MOISTURE CONTENT 0-10 PPM AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
FO
252 * BAT 10 XN 19 U1 GT GAS MOISTURE CONTENT H2O 29 GSUT H2O GAS MOISTURE CONTENT 0-10 PPM AI - *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
FO
255 * BAT 10 XP 28 U1 GT OLTC REMOTE MODE 21 GSUT OLTC REMOTE MODE OFF/ON ---- DI NO *GSUT *DCS ○ ---- ---- ---- ○ ----
CABLE
FO
256 * BBT 10 XP 01 U1 UNIT AUXILIARY TRANSFORMER TOP OIL TEMPERATURE ALARM 29 UAT TOP OIL TEMPERATURE ALARM NORMAL/ALARM ---- DI NO *UAT *DCS ---- P2 ---- ---- ○ ----
CABLE
FO
257 * BBT 10 XP 02 U1 UNIT AUXILIARY TRANSFORMER TOP OIL TEMPERATURE TRIP 28 UAT TOP OIL TEMPERATURE TRIP NORMAL/ALARM ---- DI NO *UAT *DCS ---- P1 ---- ---- ○ ○
CABLE
FO
258 * BBT 10 XP 03 U1 UNIT AUXILIARY TRANSFORMER WINDING TEMPERATURE ALARM 29 UAT WINDING TEMPERATURE ALARM NORMAL/ALARM ---- DI NO *UAT *DCS ---- P2 ---- ---- ○ ----
CABLE
FO
259 * BBT 10 XP 04 U1 UNIT AUXILIARY TRANSFORMER WINDING TEMPERATURE TRIP 28 UAT WINDING TEMPERATURE TRIP NORMAL/ALARM ---- DI NO *UAT *DCS ---- P1 ---- ---- ○ ○
CABLE
FO
260 * BBT 10 XP 05 U1 UNIT AUXILIARY TRANSFORMER OIL LOW LEVEL MAIN TANK 27 UAT LOW OIL LEVEL MAIN TANK NORMAL/ALARM ---- DI NO *UAT *DCS ---- P2 ---- ---- ○ ○
CABLE
FO
261 * BBT 10 XP 06 U1 UNIT AUXILIARY TRANSFORMER PRESSURE RELIEF DEVICE 26 UAT PRESSURE RELIEF DEVICE NORMAL/ALARM ---- DI NO *UAT *DCS ---- P2 ---- ---- ○ ○
CABLE
FO
262 * BBT 10 XP 07 U1 UNIT AUXILIARY TRANSFORMER BUCHHOLZ 1ST STAGE 22 UAT BUCHHOLZ 1ST STAGE NORMAL/ALARM ---- DI NO *UAT *DCS ---- P2 ---- ---- ○ ----
CABLE
FO
263 * BBT 10 XP 08 U1 UNIT AUXILIARY TRANSFORMER BUCHHOLZ 2ND STAGE 22 UAT BUCHHOLZ 2ND STAGE NORMAL/ALARM ---- DI NO *UAT *DCS ---- P2 ---- ---- ○ ○
CABLE

264 * BBA 10 XN 01 U1 INCOMING FROM UNIT-1 AUXILIARY TRANSFORMER (52H-1) CURRENT 26 IC FROM AT (52H-1) CURRENT 0-600 A AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

265 * BBA 10 XN 02 U1 INCOMING FROM UNIT-1 AUXILIARY TRANSFORMER (52H-1) VOLTAGE 26 IC FROM AT (52H-1) VOLTAGE 0-6.6 KV AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

266 * BBA 10 XN 03 U1 INCOMING FROM UNIT-1 AUXILIARY TRANSFORMER (52H-1) ACTIVE POWER 31 IC FROM AT (52H-1) ACTIVE POWER 0-6000 KW AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

267 * BBA 10 XT 01 U1 INCOMING FROM UNIT-1 AUXILIARY TRANSFORMER (52H-1) WATT HOUR 28 IC FROM AT (52H-1) WATT HOUR 10 Pulse/kWh WHr PI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

268 * BBA 10 XN 04 U1 INCOMING FROM UNIT-1 AUXILIARY TRANSFORMER (52H-1) POWER FACTOR 31 IC FROM AT (52H-1) POWER FACTOR 0.7-1 PF AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

303 * BAC 10 XN 01 U1 UNIT-1 AUXILIARY TRANSFORMER (52H-1) CURRENT 18 AT (52H-1) CURRENT 0-600 A AI RS485 - *GSWG *DCS ○ ---- ---- ---- ○ ----

304 * BAC 10 XN 02 U1 UNIT-1 AUXILIARY TRANSFORMER (52H-1) VOLTAGE 18 AT (52H-1) VOLTAGE 0-6.6 KV AI RS485 - *GSWG *DCS ○ ---- ---- ---- ○ ----

305 * BAC 10 XN 03 U1 UNIT-1 AUXILIARY TRANSFORMER (52H-1) ACTIVE POWER 24 AT (52H-1) ACTIVE POWER 0-6000 KW AI RS485 - *GSWG *DCS ○ ---- ---- ---- ○ ----

306 * BAC 10 XT 01 U1 UNIT-1 AUXILIARY TRANSFORMER (52H-1) WATT HOUR 21 AT (52H-1) WATT HOUR 10 Pulse/kWh WHr PI RS485 - *GSWG *DCS ○ ---- ---- ---- ○ ----

307 * BAC 10 XT 02 U1 UNIT-1 AUXILIARY TRANSFORMER (52H-1) VAR HOUR 20 AT (52H-1) VAR HOUR 10 Pulse/kWh VarHr PI RS485 - *GSWG *DCS ○ ---- ---- ---- ○ ----
3.DCS IO LIST FOR COMMUNICATION
3-1.POWER PLANT FOR EACH UNIT AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM Through TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
within 32 Chara
308 * BAC 10 XN 04 U1 UNIT-1 AUXILIARY TRANSFORMER (52H-1) POWER FACTOR 24 AT (52H-1) POWER FACTOR 0.7-1 PF AI RS485 - *GSWG *DCS ○ ---- ---- ---- ○ ----

269 * BBA 10 XN 05 U1 OUTGOING TO UNIT-1 SERVICE TRANSFORMER (52HA-1) CURRENT 25 OG TO ST (52HA-1) CURRENT 0-400 A AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

270 * BBA 10 XN 06 U1 OUTGOING TO UNIT-1 SERVICE TRANSFORMER (52HA-1) VOLTAGE 25 OG TO ST (52HA-1) VOLTAGE 0-6.6 KV AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

271 * BBA 10 XN 07 U1 OUTGOING TO UNIT-1 SERVICE TRANSFORMER (52HA-1) ACTIVE POWER 30 OG TO ST (52HA-1) ACTIVE POWER 0-6000 KW AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

272 * BBA 10 XT 02 U1 OUTGOING TO UNIT-1 SERVICE TRANSFORMER (52HA-1) WATT HOUR 27 OG TO ST (52HA-1) WATT HOUR 10 Pulse/kWh WHr PI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

273 * BBA 10 XN 08 U1 OUTGOING TO UNIT-1 SERVICE TRANSFORMER (52HA-1) POWER FACTOR 30 OG TO ST (52HA-1) POWER FACTOR 0.7-1 PF AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

274 * BBA 10 XN 09 U1 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-1) CURRENT 30 OG TO COM STMVSWG (52HB-1) CRT 0-400 A AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

275 * BBA 10 XN 10 U1 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-1) VOLTAGE 31 OG TO COM STMVSWG (52HB-1) VOLT 0-6.6 KV AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

276 * BBA 10 XN 11 U1 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-1) ACTIVE POWER 30 OG TO COM STMVSWG (52HB-1) POW 0-6000 KW AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

278 * BBA 10 XN 12 U1 OUTGOING TO COMMON STATION MV SWITCHGEAR (52HB-1) POWER FACTOR 28 OG STMVSWG (52HB-1) PWR FCTR 0.7-1 PF AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

279 * BBA 10 XN 13 U1 HOTWELL PUMP (A) (590 kW) CURRENT 23 HWP(A) (590 kW) CURRENT 0-150 A AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

280 * BBA 10 XN 14 U1 HOTWELL PUMP (B) (590 kW) CURRENT 23 HWP(B) (590 kW) CURRENT 0-150 A AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

281 * BBA 10 XN 15 U1 VACUUM PUMP (A) (570 kW) CURRENT 32 VACUUM PUMP (A) (570 kW) CURRENT 0-150 A AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

282 * BBA 10 XN 16 U1 VACUUM PUMP (B) (570 kW) CURRENT 32 VACUUM PUMP (B) (570 kW) CURRENT 0-150 A AI TCP/IP - *MVSWG *MCCRIO ○ ---- ---- ---- ○ ----

284 * BFA 10 XN 01 U1 INCOMING FROM UNIT-1 SERVICE TRANSFORMER (52LA-1) CURRENT 27 IC FROM ST (52LA-1) CURRENT 0-4000 A AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

285 * BFA 10 XN 02 U1 INCOMING FROM UNIT-1 SERVICE TRANSFORMER (52LA-1) VOLTAGE 26 ICFROM ST (52LA-1) VOLTAGE 0-500 V AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

286 * BFA 10 XN 03 U1 INCOMING FROM UNIT-1 SERVICE TRANSFORMER (52LA-1) ACTIVE POWER 31 ICFROM ST (52LA-1) ACTIVE POWER 0-2000 KW AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

288 * BFA 10 XN 04 U1 INCOMING FROM UNIT-1 SERVICE TRANSFORMER (52LA-1) PF 21 ICFROM ST (52LA-1) PF 0.7-1 PF AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

289 * BFA 10 XN 05 U1 OUTGOING TO COMMON STATION LV SWITCHGEAR (52LC-1) CURRENT 31 OG TO COMM STLVSWG (52LC-1) CRT 0-630 A AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

290 * BFA 10 XN 06 U1 COOLING TOWER FAN A (132 kW) CURRENT 25 CT FAN A (132 kW) CURRENT 0-300 A AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

291 * BFA 10 XN 07 U1 COOLING TOWER FAN B (132 kW) CURRENT 25 CT FAN B (132 kW) CURRENT 0-300 A AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

292 * BFA 10 XN 08 U1 COOLING TOWER FAN C (132 kW) CURRENT 25 CT FAN C (132 kW) CURRENT 0-300 A AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

293 * BFA 10 XN 09 U1 COOLING TOWER FAN D (132 kW) CURRENT 25 CT FAN D (132 kW) CURRENT 0-300 A AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

294 * BFA 10 XN 10 U1 COOLING TOWER FAN E (132 kW) CURRENT 25 CT FAN E (132 kW) CURRENT 0-300 A AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

295 * BFA 10 XN 11 U1 COOLING TOWER FAN F (132 kW) CURRENT 25 CT FAN F (132 kW) CURRENT 0-300 A AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

296 * BFA 10 XN 12 U1 SPARE MOTOR STARTER (250 KW) CURRENT 30 MOTOR STARTER (250 KW) CURRENT 0-300 A AI TCP/IP - *LVSWG *MCCRIO ○ ---- ---- ---- ○ ----

297 * BFB 20 XN 01 U1 AUXILIARY COOLING WATER PUMP A (75 kW) CURRENT 22 ACWP A (75 kW) CURRENT 0-250 A AI TCP/IP - *LVNESWB *MCCRIO ○ ---- ---- ---- ○ ----

300 * BFB 20 XN 02 U1 AUXILIARY COOLING WATER PUMP B (75 kW) CURRENT 22 ACWP B (75 kW) CURRENT 0-250 A AI TCP/IP - *LVNESWB *MCCRIO ○ ---- ---- ---- ○ ----
3.DCS IO LIST FOR COMMUNICATION
3-2.POWER PLANT FOR COMMON AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Tag No. SIGNAL RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THTOUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
within 32 Chara
1 RD00 BBA 10 XN 01 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) CURRENT 24 OG TO ST(52HA-0) CURRENT 0-630 A AI TCP/IP - - - STMVSWG NA RD00DCS - ○ ---- ---- ---- ○ ----

2 RD00 BBA 10 XN 02 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) VOLTAGE 24 OG TO ST(52HA-0) VOLTAGE 0-6.6 KV AI TCP/IP - - - STMVSWG NA RD00DCS - ○ ---- ---- ---- ○ ----

3 RD00 BBA 10 XN 03 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) ACTIVE POWER 22 OG TO ST(52HA-0) POWER 0-6000 KW AI TCP/IP - - - STMVSWG NA RD00DCS - ○ ---- ---- ---- ○ ----

4 RD00 BBA 10 XT 01 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) WATT HOUR 26 OG TO ST(52HA-0) WATT HOUR 10 Pulse/kWh WHr AI TCP/IP - - - STMVSWG NA RD00DCS - ○ ---- ---- ---- ○ ----

5 RD00 BBA 10 XN 04 ST OUTGOING TO STATION SERVICE TRANSFORMER (52HA-0) POWER FACTOR 29 OG TO ST(52HA-0) POWER FACTOR 0.7-1 PF AI TCP/IP - - - STMVSWG NA RD00DCS - ○ ---- ---- ---- ○ ----

6 RD00 BBA 10 XN 05 ST OUTGOING TO PAD RD-B RMU (52HB-0) CURRENT 31 OG TO PAD RD-B RMU (52HB-0) CRT 0-630 A AI TCP/IP - - - STMVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

7 RD00 BBA 10 XN 06 ST OUTGOING TO PAD RD-B RMU (52HB-0) VOLTAGE 32 OG TO PAD RD-B RMU (52HB-0) VOLT 0-6.6 KV AI TCP/IP - - - STMVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

8 RD00 BBA 10 XN 07 ST OUTGOING TO PAD RD-B RMU (52HB-0) ACTIVE POWER 31 OG TO PAD RD-B RMU (52HB-0) PWR 0-6000 KW AI TCP/IP - - - STMVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

9 RD00 BBA 10 XT 02 ST OUTGOING TO PAD RD-B RMU (52HB-0) WATT HOUR 32 OG TO RDB RMU (52HB-0) WATT HOUR 10 Pulse/kWh WHr AI TCP/IP - - - STMVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

10 RD00 BBA 10 XN 08 ST OUTGOING TO PAD RD-B RMU (52HB-0) POWER FACTOR 31 OG TO RDB RMU (52HB-0) PWR FCTR 0.7-1 PF AI TCP/IP - - - STMVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

11 RD00 BBA 10 XN 09 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) CURRENT 30 OG TO SGS STMVSWG (52HC-0) CRT 0-630 A AI TCP/IP - - - STMVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

12 RD00 BBA 10 XN 10 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) VOLTAGE 31 OG TO SGS STMVSWG (52HC-0) VOLT 0-6.6 KV AI TCP/IP - - - STMVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

13 RD00 BBA 10 XN 11 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) ACTIVE POWER 32 OG TO SGS STMVSWG (52HC-0) POWER 0-6000 KW AI TCP/IP - - - STMVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

14 RD00 BBA 10 XT 03 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) WATT HOUR 30 OG SGS STMVSWG (52HC-0) WATT H 10 Pulse/kWh WHr AI TCP/IP - - - STMVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

15 RD00 BBA 10 XN 12 ST OUTGOING TO SGS SEPARATOR STATION MV SWITCHGEAR (52HC-0) POWER FACTOR 32 OG SGS STMVSWG (52HC-0) PWR FCTR 0.7-1 PF AI TCP/IP - - - STMVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

16 RD00 BBA 10 XN 13 ST OUTGOING TO ACCOMODATION BLOCK CURRENT 32 OG TO ACCOMODATION BLOCK CURRENT 0-400 A AI TCP/IP - - - STMVSWG NA RD01MCCRIO - ○ ---- ---- ---- ○ ----

17 RD00 BBA 10 XN 14 ST OUTGOING TO ACCOMODATION BLOCK VOLTAGE 32 OG TO ACCOMODATION BLOCK VOLTAGE 0-6.6 KV AI TCP/IP - - - STMVSWG NA RD02MCCRIO - ○ ---- ---- ---- ○ ----

18 RD00 BBA 10 XN 15 ST OUTGOING TO ACCOMODATION BLOCK ACTIVE POWER 30 OG TO ACCOMODATION BLOCK POWER 0-6000 KW AI TCP/IP - - - STMVSWG NA RD03MCCRIO - ○ ---- ---- ---- ○ ----

19 RD00 BBA 10 XT 04 ST OUTGOING TO ACCOMODATION BLOCK WATT HOUR 31 OG TO ACCOMODATION BLOCK WATT H 10 Pulse/kWh WHr AI TCP/IP - - - STMVSWG NA RD04MCCRIO - ○ ---- ---- ---- ○ ----

20 RD00 BBA 10 XN 16 ST OUTGOING TO ACCOMODATION BLOCK POWER FACTOR 32 OG TO ACCOMODATION BLCK PWR FCTR 0.7-1 PF AI TCP/IP - - - STMVSWG NA RD05MCCRIO - ○ ---- ---- ---- ○ ----

26 RD00 BFA 10 XN 01 ST INCOMING FROM STATION SERVICE TRANSFORMER (52LA-3) CURRENT 29 IC FROM STST (52LA-3) CURRENT 0-4000 A AI TCP/IP - - - STLVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

27 RD00 BFA 10 XN 02 ST INCOMING FROM STATION SERVICE TRANSFORMER (52LA-3) VOLTAGE 29 IC FROM STST (52LA-3) VOLTAGE 0-500 V AI TCP/IP - - - STLVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

28 RD00 BFA 10 XN 03 ST INCOMING FROM STATION SERVICE TRANSFORMER (52LA-3) ACTIVE POWER 27 IC FROM STST (52LA-3) POWER 0-2000 KW AI TCP/IP - - - STLVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

29 RD00 BFA 10 XT 01 ST INCOMING FROM STATION SERVICE TRANSFORMER (52LA-3) WATT HOUR 28 IC FROM STST (52LA-3) WATT H 10 Pulse/kWh WHr AI TCP/IP - - - STLVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

30 RD00 BFA 10 XN 04 ST INCOMING FROM STATION SERVICE TRANSFORMER (52LA-3) POWER FACTOR 29 IC FRM STST (52LA-3) PWR FCTR 0.7-1 PF AI TCP/IP - - - STLVSWG NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

31 RD00 BFB 10 XN 01 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) CURRENT 31 IC COM STEB FROM EDG (52DG) CRT 0-1250 A AI TCP/IP - - - STLVESWB NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

32 RD00 BFB 10 XN 02 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) VOLTAGE 32 IC COM STEB FROM EDG (52DG) VOLT 0-500 V AI TCP/IP - - - STLVESWB NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

33 RD00 BFB 10 XN 03 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) ACTIVE POWER 32 IC COM STEB FRM EDG (52DG) POWER 0-2000 KW AI TCP/IP - - - STLVESWB NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

34 RD00 BFB 10 XT 01 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) WATT HOUR 32 IC COM STEB FRM EDG (52DG) WAT H 10 Pulse/kWh WHr AI TCP/IP - - - STLVESWB NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

35 RD00 BFB 10 XN 04 ST INCOMING COMMON STATION ESSENTIAL BOARD FROM EDG (52DG) CPOWER FACTOR 32 IC CM STEB FRM EDG (52DG) PWR FC 0.7-1 PF AI TCP/IP - - - STLVESWB NA RD00MCCRIO - ○ ---- ---- ---- ○ ----

48 RD00 BTL 10 XP 01 DC SYSTEM BATTERY CHARGER (A) LOSS OF AC POWER SUPPLY 32 DCSYS BAT CHARGER (A) POWER LOSS NORMAL/ALARM ---- DI TCP/IP - NC - BCA NA RD00DCS - ---- ○ ---- ---- ----

(P1)
49 RD00 BTL 10 XP 02 DC SYSTEM BATTERY CHARGER (A) RECTIFIER FAILURE 32 DCSYS BAT CRGR (A) RECTIFIER FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCA NA RD00DCS - ---- ○ ---- ---- ----

(P1)
50 RD00 BTL 10 XP 03 DC SYSTEM BATTERY CHARGER (A) GROUND FAULT 30 DCSYS BAT CHARGER (A) GRND FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCA NA RD00DCS - ---- ○ ---- ---- ----

(P1)

51 RD00 BTL 10 XP 04 DC SYSTEM BATTERY CHARGER (A) DC UNDER VOLTAGE 32 DCSYS BAT CHARGER (A) UNDER VOLT NORMAL/ALARM ---- DI TCP/IP - NO - BCA NA RD00DCS - ---- ○ ---- ---- ----

(P1)
52 RD00 BTL 10 XP 05 DC SYSTEM BATTERY CHARGER (A) OVER TEMPERATURE 32 DCSYS BAT CHARGER (A) OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCA NA RD00DCS - ---- ○ ---- ---- ----

(P1)
53 RD00 BTL 10 XP 06 DC SYSTEM BATTERY (A) FAULT 27 DC SYSTEM BATTERY (A) FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCA NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1152 RD00 BTL 10 XN 01 DC SYSTEM BATTERY CHARGER (A) BATTERY VOLTAGE 29 DC SYSTEM BATTERY (A) VOLTAGE 0-150 V AI TCP/IP - - - BCA NA RD00DCS - ○ ---- ---- ---- ○ ----

225 RD00 BTL 20 XP 01 DC SYSTEM BATTERY CHARGER (B) LOSS OF AC POWER SUPPLY 32 DCSYS BAT CHARGER (B) POWER LOSS NORMAL/ALARM ---- DI TCP/IP - NC - BCB NA RD00DCS - ---- ○ ---- ---- ----

(P1)
226 RD00 BTL 20 XP 02 DC SYSTEM BATTERY CHARGER (B) RECTIFIER FAILURE 32 DCSYS BAT CRGR (B) RECTIFIER FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCB NA RD00DCS - ---- ○ ---- ---- ----

(P1)
227 RD00 BTL 20 XP 03 DC SYSTEM BATTERY CHARGER (B) GROUND FAULT 32 DCSYS BAT CHARGER (B) GRND FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCB NA RD00DCS - ---- ○ ---- ---- ----

(P1)
228 RD00 BTL 20 XP 04 DC SYSTEM BATTERY CHARGER (B) DC UNDER VOLTAGE 32 DCSYS BAT CHARGER (B) UNDER VOLT NORMAL/ALARM ---- DI TCP/IP - NO - BCB NA RD00DCS - ---- ○ ---- ---- ----

(P1)
229 RD00 BTL 20 XP 05 DC SYSTEM BATTERY CHARGER (B) OVER TEMPERATURE 32 DCSYS BAT CHARGER (B) OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCB NA RD00DCS - ---- ○ ---- ---- ----

(P1)

230 RD00 BTL 20 XP 06 DC SYSTEM BATTERY (B) FAULT 27 DC SYSTEM BATTERY (B) FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCB NA RD00DCS - ---- ---- ---- ○ ----
(P1)
1153 RD00 BTL 20 XN 01 DC SYSTEM BATTERY CHARGER (B) BATTERY VOLTAGE 29 DC SYSTEM BATTERY (B) VOLTAGE 0-150 V AI TCP/IP - - - BCB NA RD00DCS - ○ ---- ---- ---- ○ ----

402 RD00 BRU 10 GH 001 XP 01 UPS A LOSS OF AC POWER SUPPLY 26 UPS A LOSS OF POWER SUPPLY NORMAL/ALARM ---- DI TCP/IP - NC - UPS(A) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
403 RD00 BRU 10 GH 001 XP 02 UPS A RECTIFIER FAILURE 21 UPS A RECTIFIER FAULT NORMAL/ALARM ---- DI TCP/IP - NO - UPS(A) NA RD00DCS - ---- ○ ---- ---- ----

(P1)

404 RD00 BRU 10 GH 001 XP 03 UPS A GROUND FAULT 18 UPS A GROUND FAULT NORMAL/ALARM ---- DI TCP/IP - NO - UPS(A) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
405 RD00 BRU 10 GH 001 XP 04 UPS A DC UNDER VOLTAGE 19 UPS A UNDER VOLTAGE NORMAL/ALARM ---- DI TCP/IP - NO - UPS(A) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
406 RD00 BRU 10 GH 001 XP 05 UPS A BATTERY FAULT 19 UPS A BATTERY FAULT NORMAL/ALARM ---- DI TCP/IP - NO - UPS(A) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
407 RD00 BRU 10 GH 001 XP 06 UPS A OVER TEMPERATURE 22 UPS A OVER TEMPERATURE NORMAL/ALARM ---- DI TCP/IP - NO - UPS(A) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
3.DCS IO LIST FOR COMMUNICATION
3-2.POWER PLANT FOR COMMON AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THTOUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
within 32 Chara
408 RD00 BRU 10 GH 001 XP 07 UPS A FAN FAILURE 17 UPS A FAN FAILURE NORMAL/ALARM ---- DI TCP/IP - NO - UPS(A) NA RD00DCS - ---- ○ ---- ---- ----

(P1)

409 RD00 BRU 10 GH 001 XP 08 UPS A INVERTER FAULT 20 UPS A INVERTER FAULT NORMAL/ALARM ---- DI TCP/IP - NO - UPS(A) NA RD00DCS - ---- ---- ---- ○ ----
(P1)

410 RD00 BRU 10 GH 001 XP 09 UPS A LOSS OF SYNCHRONING SOURCE 32 UPS A LOSS OF SYNCHRONING SOURCE NORMAL/ALARM ---- DI TCP/IP - NO - UPS(A) NA RD00DCS - ---- ○ ---- ---- ----

(P1)

411 RD00 BRU 10 GH 001 XP 10 UPS A ALARM 18 UPS A COMMON ALARM NORMAL/ALARM ---- DI TCP/IP - NO - UPS(A) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1150 RD00 BRU 10 GH 001 XN 01 UPS (A) BATTERY VOLTAGE 21 UPS A BATTERY VOLTAGE 0-150 V AI TCP/IP - - - UPS(A) NA RD00DCS - ○ ---- ---- ---- ○ ----

583 RD00 BRU 10 GH 002 XP 01 UPS B LOSS OF AC POWER SUPPLY 26 UPS B LOSS OF POWER SUPPLY NORMAL/ALARM ---- DI TCP/IP - NC - UPS(B) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
584 RD00 BRU 10 GH 002 XP 02 UPS B RECTIFIER FAILURE 21 UPS B RECTIFIER FAULT NORMAL/ALARM ---- DI TCP/IP - NO - UPS(B) NA RD00DCS - ---- ○ ---- ---- ----

(P1)

585 RD00 BRU 10 GH 002 XP 03 UPS B GROUND FAULT 18 UPS B GROUND FAULT NORMAL/ALARM ---- DI TCP/IP - NO - UPS(B) NA RD00DCS - ---- ○ ---- ---- ----

(P1)

586 RD00 BRU 10 GH 002 XP 04 UPS B DC UNDER VOLTAGE 19 UPS B UNDER VOLTAGE NORMAL/ALARM ---- DI TCP/IP - NO - UPS(B) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
587 RD00 BRU 10 GH 002 XP 05 UPS B BATTERY FAULT 19 UPS B BATTERY FAULT NORMAL/ALARM ---- DI TCP/IP - NO - UPS(B) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
588 RD00 BRU 10 GH 002 XP 06 UPS B OVER TEMPERATURE 22 UPS B OVER TEMPERATURE NORMAL/ALARM ---- DI TCP/IP - NO - UPS(B) NA RD00DCS - ---- ○ ---- ---- ----

(P1)

589 RD00 BRU 10 GH 002 XP 07 UPS B FAN FAILURE 18 UPS B FAN FAILURE NORMAL/ALARM ---- DI TCP/IP - NO - UPS(B) NA RD00DCS - ---- ○ ---- ---- ----

(P1)

590 RD00 BRU 10 GH 002 XP 08 UPS B INVERTER FAULT 21 UPS B INVERTER FAULT NORMAL/ALARM ---- DI TCP/IP - NO - UPS(B) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
591 RD00 BRU 10 GH 002 XP 09 UPS B LOSS OF SYNCHRONING SOURCE 32 UPS B LOSS OF SYNCHRONING SOURCE NORMAL/ALARM ---- DI TCP/IP - NO - UPS(B) NA RD00DCS - ---- ○ ---- ---- ----

(P1)
592 RD00 BRU 10 GH 002 XP 10 UPS B ALARM 18 UPS B COMMON ALARM NORMAL/ALARM ---- DI TCP/IP - NO - UPS(B) NA RD00DCS - ---- ○ ---- ---- ----

(P1)

1151 RD00 BRU 10 GH 002 XN 01 UPS (B) BATTERY VOLTAGE 21 UPS B BATTERY VOLTAGE 0-150 V AI TCP/IP - - - UPS(B) NA RD00DCS - ○ ---- ---- ---- ○ ----

764 RD00 XJA 00 AJ 001 XN 01 ST EDG AC OUTPUT CURRENT 24 ST EDG AC OUTPUT CURRENT 0-4000 A AI TCP/IP - - - EDG NA RD00DCS - ○ ---- ---- ---- ○ ----

765 RD00 XJA 00 AJ 001 XN 02 ST EDG AC OUTPUT VOLTAGE 24 ST EDG AC OUTPUT VOLTAGE 0-500 V AI TCP/IP - - - EDG NA RD00DCS - ○ ---- ---- ---- ○ ----

766 RD00 XJA 00 AJ 001 XN 03 ST EDG AC OUTPUT ACTIVE POWER 29 ST EDG AC OUTPUT ACTIVE POWER 0-3000 KW AI TCP/IP - - - EDG NA RD00DCS - ○ ---- ---- ---- ○ ----

767 RD00 XJA 00 AJ 001 XN 04 ST EDG AC OUTPUT POWER FACTOR 29 ST EDG AC OUTPUT POWER FACTOR 0.7 - 1 PF AI TCP/IP - - - EDG NA RD00DCS - ○ ---- ---- ---- ○ ----

768 RD00 XJA 00 AJ 001 XT 01 ST EDG AC OUTPUT WATT HOUR 26 ST EDG AC OUTPUT WATT HOUR 10 Pulse/kWh WHr AI TCP/IP - - - EDG NA RD00DCS - ○ ---- ---- ---- ○ ----

769 RD00 XJA 00 AJ 001 XN 05 ST EDG AC OUTPUT FREQUENCY 26 ST EDG AC OUTPUT FREQUENCY 45 - 55 Hz AI TCP/IP - - - EDG NA RD00DCS - ○ ---- ---- ---- ○ ----

770 RD00 XJA 00 AJ 001 XT 02 ST EDG AC VAR HOUR 18 ST EDG AC VAR HOUR 10 Pulse/kvarh VarHr AI TCP/IP - - - EDG NA RD00DCS - ○ ---- ---- ---- ○ ----

1100 RD00 XJA 00 AJ 001 XP 01 ST EDG COMMON ALARM INDICATION 30 ST EDG COMMON ALARM INDICATION OFF/ALARM ---- DI TCP/IP - - - EDG NA RD00DCS - ---- ○ ---- ---- ○ ○

1101 RD00 XJA 00 AJ 001 XP 02 ST EDG RUN/STOP INDICATION 26 ST EDG RUN/STOP INDICATION OFF/ALARM ---- DI TCP/IP - - - EDG NA RD00DCS - ○ ---- ---- ---- ○ ----

771 RD00 SAA 10 GH 001 XP 01 AHU 1 (GROUND FLOOR) ON/OFF INDICATION 28 AHU 1 (GROUND FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

772 RD00 SAA 10 GH 001 XP 02 CDU 1 (GROUND FLOOR) ON/OFF INDICATION-1 28 CDU 1 (GROUND FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

774 RD00 SAA 10 GH 001 XP 04 AHU 2 (GROUND FLOOR) ON/OFF INDICATION 28 AHU 2 (GROUND FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

775 RD00 SAA 10 GH 001 XP 05 CDU 2 (GROUND FLOOR) ON/OFF INDICATION-1 28 CDU 2 (GROUND FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

777 RD00 SAA 10 GH 001 XP 07 AHU 3 (GROUND FLOOR) ON/OFF INDICATION 28 AHU 3 (GROUND FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

778 RD00 SAA 10 GH 001 XP 08 CDU 3 (GROUND FLOOR) ON/OFF INDICATION-1 28 CDU 3 (GROUND FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

780 RD00 SAA 10 GH 001 XP 10 AHU 4 (1ST FLOOR) ON/OFF INDICATION 25 AHU 4 (1ST FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

781 RD00 SAA 10 GH 001 XP 11 CDU 4 (1ST FLOOR) ON/OFF INDICATION-1 25 CDU 4 (1ST FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

783 RD00 SAA 10 GH 001 XP 13 AHU 5 (1ST FLOOR) ON/OFF INDICATION 25 AHU 5 (1ST FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

784 RD00 SAA 10 GH 001 XP 14 CDU 5 (1ST FLOOR) ON/OFF INDICATION-1 25 CDU 5 (1ST FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

786 RD00 SAA 10 GH 001 XP 16 AHU 6 (1ST FLOOR) ON/OFF INDICATION 25 AHU 6 (1ST FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

787 RD00 SAA 10 GH 001 XP 17 CDU 6 (1ST FLOOR) ON/OFF INDICATION-1 25 CDU 6 (1ST FLOOR) ON/OFF OFF/ON ---- DI RS485 - NO - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

789 RD00 SAA 10 GH 001 XP 19 AHU 1 (GROUND FLOOR) TRIPS INDICATION 27 AHU 1 (GROUND FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

790 RD00 SAA 10 GH 001 XP 20 CDU 1 (GROUND FLOOR) TRIPS INDICATION-1 27 CDU 1 (GROUND FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

792 RD00 SAA 10 GH 001 XP 22 AHU 2 (GROUND FLOOR) TRIPS INDICATION 27 AHU 2 (GROUND FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

793 RD00 SAA 10 GH 001 XP 23 CDU 2 (GROUND FLOOR) TRIPS INDICATION-1 27 CDU 2 (GROUND FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

795 RD00 SAA 10 GH 001 XP 25 AHU 3 (GROUND FLOOR) TRIPS INDICATION 27 AHU 3 (GROUND FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

796 RD00 SAA 10 GH 001 XP 26 CDU 3 (GROUND FLOOR) TRIPS INDICATION-1 27 CDU 3 (GROUND FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

798 RD00 SAA 10 GH 001 XP 28 AHU 4 (1ST FLOOR) TRIPS INDICATION 24 AHU 4 (1ST FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

799 RD00 SAA 10 GH 001 XP 29 CDU 4 (1ST FLOOR) TRIPS INDICATION-1 24 CDU 4 (1ST FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

801 RD00 SAA 10 GH 001 XP 31 AHU 5 (1ST FLOOR) TRIPS INDICATION 24 AHU 5 (1ST FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

802 RD00 SAA 10 GH 001 XP 32 CDU 5 (1ST FLOOR) TRIPS INDICATION-1 24 CDU 5 (1ST FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

804 RD00 SAA 10 GH 001 XP 34 AHU 6 (1ST FLOOR) TRIPS INDICATION 24 AHU 6 (1ST FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

805 RD00 SAA 10 GH 001 XP 35 CDU 6 (1ST FLOOR) TRIPS INDICATION-1 24 CDU 6 (1ST FLOOR) TRIPS NORMAL/TRIP ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

807 RD00 SAA 10 GH 001 XP 37 HVAC GROUND FLOOR SHUT DOWN FROM FIRE ALARM 27 HVAC GROUND FLOOR SHUT DOWN OFF/ON ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ----
○ ○
(P2)
3.DCS IO LIST FOR COMMUNICATION
3-2.POWER PLANT FOR COMMON AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THTOUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
within 32 Chara
808 RD00 SAA 10 GH 001 XP 38 HVAC 1ST FLOOR SHUT DOWN FROM FIRE ALARM 24 HVAC 1ST FLOOR SHUT DOWN OFF/ON ---- DI RS485 - NC - HVAC NA RD00DCS - ○ ---- ---- ----
○ ○
(P2)

809 RD00 SAA 10 GH 001 XN 01 TEMPERATURE INDICATION OF CONTROL ROOM 27 TEMPERATURE OF CONTROL ROOM 0 ~ 50 degC AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

810 RD00 SAA 10 GH 001 XN 02 HUMIDITY INDICATION OF CONTROL ROOM 24 HUMIDITY OF CONTROL ROOM 0 ~ 100 % AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

811 RD00 SAA 10 GH 001 XN 03 TEMPERATURE INDICATION OF GCB ROOM 2 26 TEMPERATURE OF GCB ROOM 2 0 ~ 50 degC AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

812 RD00 SAA 10 GH 001 XN 04 HUMIDITY INDICATION OF GCB ROOM 2 32 HUMIDITY INDICATIO OF GCB ROOM 2 0 ~ 100 % AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

813 RD00 SAA 10 GH 001 XN 05 TEMPERATURE INDICATION OF ELECTRICAL ROOM 31 TEMPERATURE OF ELECTRICAL ROOM 0 ~ 50 degC AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

814 RD00 SAA 10 GH 001 XN 06 HUMIDITY INDICATION OF ELECTRICAL ROOM 27 HUMIDITY OF ELECTRICAL ROOM 0 ~ 100 % AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

815 RD00 SAA 10 GH 001 XN 07 TEMPERATURE INDICATION OF GCB ROOM 1 26 TEMPERATURE OF GCB ROOM 1 0 ~ 50 degC AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

816 RD00 SAA 10 GH 001 XN 08 HUMIDITY INDICATION OF GCB ROOM 1 32 HUMIDITY INDICATIO OF GCB ROOM 1 0 ~ 100 % AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

817 RD00 SAA 10 GH 001 XN 09 TEMPERATURE INDICATION OF RELAY ROOM 26 TEMPERATURE OF RELAY ROOM 0 ~ 50 degC AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

818 RD00 SAA 10 GH 001 XN 10 HUMIDITY INDICATION OF RELAY ROOM 32 HUMIDITY INDICATIO OF RELAY ROOM 0 ~ 100 % AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

819 RD00 SAA 10 GH 001 XN 11 TEMPERATURE INDICATION OF SUBSTATION 26 TEMPERATURE OF SUBSTATION 0 ~ 50 degC AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

820 RD00 SAA 10 GH 001 XN 12 HUMIDITY INDICATION OF SUBSTATION 22 HUMIDITY OF SUBSTATION 0 ~ 100 % AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

821 RD00 SAA 10 GH 001 XN 13 TEMPERATURE INDICATION OF UPS BATTERY CHARGER ROOM 29 TEMP OF BATTERY CHARGER ROOM 0 ~ 50 degC AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

822 RD00 SAA 10 GH 001 XN 14 HUMIDITY INDICATION OF UPS BATTERY CHARGER ROOM 32 HUMIDITY OF BATTERY CHARGER ROOM 0 ~ 100 % AI RS485 - - - HVAC NA RD00DCS - ○ ---- ---- ---- ○ ----

823 RD00 QEA 10 AN 001 XP 01 Air Compressor A - Running Indication 27 Air Compressor A - Running OFF/ON ---- DI RS485 - - - F NA RD00DCS - ○ ---- ---- ---- ○ ----

824 RD00 QEA 10 AN 001 XP 02 Air Compressor A - Common Alarm 31 Air Compressor A - Common Alarm NORMAL/ALARM ---- DI RS485 - - - F NA RD00DCS - ○ ---- ---- ----
○ ○
(P2)
825 RD00 QEA 10 AN 002 XP 01 Air Compressor B - Running Indication 27 Air Compressor B - Running OFF/ON ---- DI RS485 - - - F NA RD00DCS - ○ ---- ---- ---- ○ ----

826 RD00 QEA 10 AN 002 XP 02 Air Compressor B - Common Alarm 31 Air Compressor B - Common Alarm NORMAL/ALARM ---- DI RS485 - - - F NA RD00DCS - ○ ---- ---- ----
○ ○
(P2)
827 RD00 QEA 10 AN 003 XP 01 Air Compressor C - Running Indication 27 Air Compressor C - Running OFF/ON ---- DI RS485 - - - F NA RD00DCS - ○ ---- ---- ---- ○ ----

828 RD00 QEA 10 AN 003 XP 02 Air Compressor C - Common Alarm 31 Air Compressor C - Common Alarm NORMAL/ALARM ---- DI RS485 - - - F NA RD00DCS - ○ ---- ---- ----
○ ○
(P2)
829 RD00 QFA 10 AT 003 XP 01 Air Dryer A - Running Indication 22 Air Dryer A - Running OFF/ON ---- DI RS485 - - - F NA RD00DCS - ○ ---- ---- ---- ○ ----

830 RD00 QFA 10 AT 003 XP 02 Air Dryer A - Common Alarm 26 Air Dryer A - Common Alarm NORMAL/ALARM ---- DI RS485 - - - F NA RD00DCS - ○ ---- ---- ----
○ ○
(P2)
831 RD00 QFA 10 AT 003 XN 01 Air Dryer A - Dew Point Analyzer 32 Air Dryer A - Dew Point Analyzer ---- ---- AI RS485 - - - F NA RD00DCS - ○ ---- ---- ---- ○ ----

832 RD00 QFA 10 AT 004 XP 01 Air Dryer B - Running Indication 22 Air Dryer B - Running OFF/ON ---- DI RS485 - - - F NA RD00DCS - ○ ---- ---- ---- ○ ----

833 RD00 QFA 10 AT 004 XP 02 Air Dryer B - Common Alarm 26 Air Dryer B - Common Alarm NORMAL/ALARM ---- DI RS485 - - - F NA RD00DCS - ○ ---- ---- ----
○ ○
(P2)
834 RD00 QFA 10 AT 004 XN 01 Air Dryer B - Dew Point Analyzer 32 Air Dryer B - Dew Point Analyzer ---- ---- AI RS485 - - - F NA RD00DCS - ○ ---- ---- ---- ○ ----

1129 RD00 CYE 10 GA 001 XP 03 Fire Alarm Zone 1 Power House Ground Floor 28 Fire Alarm Power House Gound NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1130 RD00 CYE 10 GA 001 XP 04 Fire Alarm Zone 12 Admin Complex 24 Fire Alarm Admin Complex NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1131 RD00 CYE 10 GA 001 XP 05 Fire Alarm Zone 2 Power House 1st Floor 32 Fire Alarm Power House 1st Floor NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1132 RD00 CYE 10 GA 001 XP 06 Fire Alarm Zone 3 Lube Oil U1 22 Fire Alarm Lube Oil U1 NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1133 RD00 CYE 10 GA 001 XP 07 Fire Alarm Zone 4 Lube Oil U2 & Clean Dirty Oil Tank 32 Fire Alarm Lube Oil U2, Oil Tank NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1134 RD00 CYE 10 GA 001 XP 08 Fire Alarm Zone 5 EDG Room, Air Compressor & EDG Fuel Tank 30 Fire Alarm EDG&Fuel Tank, Comp NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1135 RD00 CYE 10 GA 001 XP 09 Fire Alarm Zone 6 Workshop and Store Building 26 Fire Alarm Workshop, Store NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)

1136 RD00 CYE 10 GA 001 XP 10 Fire Alarm Zone 7 Laboratory Building 30 Fire Alarm Laboratory Building NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ---- ---- ○ ----
(P1)
1137 RD00 CYE 10 GA 001 XP 11 Fire Alarm Zone 8 WTP & Fire Building 30 Fire Alarm WTP & Fire Building NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1138 RD00 CYE 10 GA 001 XP 12 Fire Alarm Zone 9 Admin Building 25 Fire Alarm Admin Building NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1139 RD00 CYE 10 GA 001 XP 13 Fire Alarm Zone 10 Guard House 22 Fire Alarm Guard House NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)
1140 RD00 CYE 10 GA 001 XP 14 Fire Alarm Zone 11 Chemical Dosing Building 32 Fire Alarm Chemical Dosing Build NORMAL/ALARM ---- DI TCP/IP - NO - FACP NA RD00DCS - ---- ○ ---- ---- ----

(P1)
3.DCS IO LIST FOR COMMUNICATION
3-3.SEPARATOR & WELLPAD-E AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Tag No. SIGNAL RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
(with 32 word limitation)
1 RD00 BBB 10 XN 01 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) CURRENT 31 IC FROM SGS ST (52HA-4) CURRENT 0-630 A AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

2 RD00 BBB 10 XN 02 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) VOLTAGE 31 IC FROM SGS ST (52HA-4) VOLTAGE 0-6.6 kV AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

3 RD00 BBB 10 XN 03 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) ACTIVE POWER 29 IC FROM SGS ST (52HA-4) POWER 0-300 kW AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

4 RD00 BBB 10 XT 01 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) WATT HOUR 32 IC FRM SGS ST (52HA-4) WATT HOUR 10 Pulse/kWh WHr PI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

5 RD00 BBB 10 XN 04 SS INCOMING FROM SGS SERVICE TRANSFORMER (52HA-4) POWER FACTOR 32 IC FROM SGS ST (52HA-4) PWR FCTR 0.7-1 PF AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

6 RD00 BBB 10 XN 05 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) CURRENT 30 IC FROM MVSWG (52HB-4) CURRENT 0-630 A AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

7 RD00 BBB 10 XN 06 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) VOLTAGE 30 IC FROM MVSWG (52HB-4) VOLTAGE 0-6.6 kV AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

8 RD00 BBB 10 XN 07 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) ACTIVE POWER 28 IC FROM MVSWG (52HB-4) POWER 0-300 kW AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

9 RD00 BBB 10 XT 05 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) WATT HOUR 32 IC FROM MVSXG (52HB-4) WATT HOUR 10 Pulse/kWh WHr PI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

10 RD00 BBB 10 XN 19 SS INCOMING FROM COMMON STATION MV SWITCHGEAR (52HB-4) POWER FACTOR 31 IC FROM MVSWG (52HB-4) PWR FCTR 0.7-1 PF AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

11 RD00 BBB 10 XN 20 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) CURRENT 26 OG TO SST (52HC-4) CURRENT 0-630 A AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

12 RD00 BBB 10 XN 21 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) VOLTAGE 26 OG TO SST (52HC-4) VOLTAGE 0-6.6 kV AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

13 RD00 BBB 10 XN 08 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) ACTIVE POWER 31 OG TO SST (52HC-4) ACTIVE POWER 0-300 kW AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

14 RD00 BBB 10 XT 02 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) WATT HOUR 28 OG TO SST (52HC-4) WATT HOUR 10 Pulse/kWh WHr PI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

15 RD00 BBB 10 XN 09 SS OUTGOING TO SEPARATOR STATION TRANSFORMER (52HC-4) POWER FACTOR 31 OG TO SST (52HC-4) POWER FACTOR 0.7-1 PF AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

16 RD00 BBB 10 XN 15 SS SPARE FEEDER (52HD-4) CURRENT 29 SPARE FEEDER (52HD-4) CURRENT 0-630 A AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

17 RD00 BBB 10 XN 16 SS SPARE FEEDER (52HD-4) VOLTAGE 29 SPARE FEEDER (52HD-4) VOLTAGE 0-6.6 kV AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

18 RD00 BBB 10 XN 17 SS SPARE FEEDER (52HD-4) VOLTAGE 29 SPARE FEEDER (52HD-4) VOLTAGE 0-300 kW AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

19 RD00 BBB 10 XT 05 SS SPARE FEEDER (52HD-4) WATT HOUR 31 SPARE FEEDER (52HD-4) WATT HOUR 10 Pulse/kWh WHr PI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

20 RD00 BBB 10 XN 18 SS SPARE FEEDER (52HD-4) POWER FACTOR 30 SPARE FEEDER (52HD-4) PWR FCTR 0.7-1 PF AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

21 RD00 BBB 10 XN 10 SS OUTGOING TO PAD-C RMU (52HE-4) CURRENT 32 OG TO PAD-C RMU (52HE-4) CURRENT 0-630 A AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

22 RD00 BBB 10 XN 11 SS OUTGOING TO PAD-C RMU (52HE-4) VOLTAGE 32 OG TO PAD-C RMU (52HE-4) VOLTAGE 0-6.6 kV AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

23 RD00 BBB 10 XN 12 SS OUTGOING TO PAD-C RMU (52HE-4) ACTIVE POWER 30 OG TO PAD-C RMU (52HE-4) POWER 0-300 kW AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

24 RD00 BBB 10 XT 04 SS OUTGOING TO PAD-C RMU (52HE-4) WATT HOUR 31 OG TO PAD-C RMU (52HE-4) WATT H 10 Pulse/kWh WHr PI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

25 RD00 BBB 10 XN 13 SS OUTGOING TO PAD-C RMU (52HE-4) POWER FACTOR 32 OG TO PAD-C RMU (52HE-4) PW FCTR 0.7-1 PF AI TCP/IP - - - SGSSMVSWG NA DCSSEP --- ○ ---- ---- ---- ○ ----

26 RD00 BFC 10 XN 14 INCOMING FROM SEPARATOR STATION TRANSFORMER CURRENT 19 IC FROM SST CURRENT 0-150 A AI TCP/IP - - - RD-SSLVPDB NA DCSSEP --- ○ ---- ---- ---- ○ ----

32 RD00 BTM 10 GH 001 XP 01 SS DC SYSTEM BATTERY CHARGER (A) LOSS OF AC POWER SUPPLY 32 DC SYS BATT CHARG (A) POWER LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)

33 RD00 BTM 10 GH 001 XP 02 SS DC SYSTEM BATTERY CHARGER (A) RECTIFIER FAILURE 31 DC BATT CHARG (A) RECTIFIER FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-SS NA DCSSEP --- ---- ---- ---- ○ ----
(P1)
34 RD00 BTM 10 GH 001 XP 03 SS DC SYSTEM BATTERY CHARGER (A) GROUND FAULT 31 DC SYST BATT CHARG (A) GRND FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)
35 RD00 BTM 10 GH 001 XP 04 SS DC SYSTEM BATTERY CHARGER (A) DC UNDER VOLTAGE 32 DC SYS BATT CHARG (A) UNDER VOLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)
36 RD00 BTM 10 GH 001 XP 05 SS DC SYSTEM BATTERY CHARGER (A) OVER TEMPERATURE 32 DC SYST BATT CHRGR (A) OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)
37 RD00 BTM 10 GH 001 XP 06 SS DC SYSTEM BATTERY (A) FAULT 27 DC SYSTEM BATTERY (A) FAULT ---- ---- DI TCP/IP - NO - BCARD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)

38 RD00 BTM 10 GH 001 XP 07 SS DC SYSTEM BATTERY CHARGER (A) OPTION 1 ERROR (SPARE) 32 DC SYSTEM BATT CHARGER (A) SPARE ---- ---- DI TCP/IP - NO - BCARD-SS NA DCSSEP --- ---- ○ ---- ---- ---- ----
(P1)
39 RD00 BTM 10 GH 001 XP 08 SS DC SYSTEM BATTERY CHARGER (A) OPTION 2 ERROR (SPARE) 32 DC SYSTEM BATT CHARGER (A) SPARE ---- ---- DI TCP/IP - NO - BCARD-SS NA DCSSEP --- ---- ○ ---- ---- ---- ----
(P1)
40 RD00 BTM 10 GH 002 XP 01 SS DC SYSTEM BACKUP CONVERTER LOSS OF AC POWER SUPPLY 31 DC SYSTEM BU CONVERTER POW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)
41 RD00 BTM 10 GH 002 XP 02 SS DC SYSTEM BACKUP CONVERTER RECTIFIER FAILURE 31 DC SYS BU CONVRTR RECTIFIER FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)
42 RD00 BTM 10 GH 002 XP 03 SS DC SYSTEM BACKUP CONVERTER GROUND FAULT 31 DC SYSTEM BU CONVERTER GRND FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)
43 RD00 BTM 10 GH 002 XP 04 SS DC SYSTEM BACKUP CONVERTER DC UNDER VOLTAGE 32 DC SYST BU CONVRTR DC UNDER VOLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)
44 RD00 BTM 10 GH 002 XP 05 SS DC SYSTEM BACKUP CONVERTER OVER TEMPERATURE 32 DC SYSTEM BU CONVERTER OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)
47 RD00 BTM 10 GH 002 XP 06 SS DC SYSTEM BACKUP CONVERTER OPTION 1 ERROR (SPARE) 32 DC SYSTEM BACKUP CONVERTER SPARE ---- ---- DI TCP/IP - NO - BCARD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)
48 RD00 BTM 10 GH 002 XP 07 SS DC SYSTEM BACKUP CONVERTER SPARE OPTION 2 ERROR (SPARE) 32 DC SYSTEM BACKUP CONVERTER SPARE ---- ---- DI TCP/IP - NO - BCARD-SS NA DCSSEP --- ---- ○ ---- ---- ----

(P1)
3.DCS IO LIST FOR COMMUNICATION
3-4.WELLPAD-I AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Tag No. SIGNAL RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
(with 30 word limitation)
1 RD00 BFC 30 XN 01 PAD-I INCOMING FROM PAD-I DISTRIBUTION TRANSFORMER (52L-I) CURRENT 30 PAD-I IC FRM DSTRBTN TRANS CUR 0-100 A AI TCP/IP - - - RD-BLVPDI NA DCSRDI --- ○ ---- ---- ---- ○ ----

7 RD00 BTM 30 GH 001 XP 01 PAD-I DC SYSTEM BATTERY CHARGER (A) LOSS OF AC POWER SUPPLY 28 PAD-I DC SYS BAT (A) PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-I NA DCSRDI --- ---- ○ ---- ---- ----

(P1)
8 RD00 BTM 30 GH 001 XP 02 PAD-I DC SYSTEM BATTERY CHARGER (A) RECTIFIER FAILURE 30 PAD-I DC SYS BAT (A) RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-I NA DCSRDI --- ---- ○ ---- ---- ----

(P1)

9 RD00 BTM 30 GH 001 XP 03 PAD-I DC SYSTEM BATTERY CHARGER (A) GROUND FAULT 28 PAD-I DC SYS BAT (A) GRD FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-I NA DCSRDI --- ---- ○ ---- ---- ----

(P1)

10 RD00 BTM 30 GH 001 XP 04 PAD-I DC SYSTEM BATTERY CHARGER (A) DC UNDER VOLTAGE 32 PAD-I DC SYS BAT (A) DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-I NA DCSRDI --- ---- ---- ---- ○ ----
(P1)

11 RD00 BTM 30 GH 001 XP 05 PAD-I DC SYSTEM BATTERY CHARGER (A) OVER TEMPERATURE 30 PAD-I DC SYS BAT (A) OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-I NA DCSRDI --- ---- ○ ---- ---- ----

(P1)
12 RD00 BTM 30 GH 001 XP 06 PAD-I DC SYSTEM BATTERY (A) FAULT 26 PAD-I DC SYS BAT (A) FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-I NA DCSRDI --- ---- ○ ---- ---- ----

(P1)
15 RD00 BTM 30 GH 002 XP 01 PAD-I DC SYSTEM BACKUP CONVERTER LOSS OF AC POWER SUPPLY 29 PAD-I DC SYS BU CNVTR PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-I NA DCSRDI --- ---- ○ ---- ---- ----

(P1)
16 RD00 BTM 30 GH 002 XP 02 PAD-I DC SYSTEM BACKUP CONVERTER RECTIFIER FAILURE 31 PAD-I DC SYS BU CNVTR RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-I NA DCSRDI --- ---- ○ ---- ---- ----

(P1)
17 RD00 BTM 30 GH 002 XP 03 PAD-I DC SYSTEM BACKUP CONVERTER GROUND FAULT 32 PAD-I DC SYS BU CNVTR GRND FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-I NA DCSRDI --- ---- ○ ---- ---- ----

(P1)

18 RD00 BTM 30 GH 002 XP 04 PAD-I DC SYSTEM BACKUP CONVERTER DC UNDER VOLTAGE 32 PAD-I DC SYS BU CNVT DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-I NA DCSRDI --- ---- ○ ---- ---- ----

(P1)
19 RD00 BTM 30 GH 002 XP 05 PAD-I DC SYSTEM BACKUP CONVERTER OVER TEMPERATURE 32 PAD-I DC SYS BU CNVTR OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-I NA DCSRDI --- ---- ○ ---- ---- ----

(P1)
3.DCS IO LIST FOR COMMUNICATION
3-5.WELLPAD-L AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Tag No. SIGNAL RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
(with 30 word limitation)
1 RD00 BFC 40 XN 01 PAD-L INCOMING FROM PAD-L DISTRIBUTION TRANSFORMER (52L-L) CURRENT 30 PAD-L IC FRM DSTRBTN TRANS CUR 0-100 A AI TCP/IP - - - RD-BLVPDL NA DCSRDL --- ○ ---- ---- ---- ○ ----

7 RD00 BTM 40 GH 001 XP 01 PAD-L DC SYSTEM BATTERY CHARGER (A) LOSS OF AC POWER SUPPLY 28 PAD-L DC SYS BAT (A) PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-L NA DCSRDL --- ---- ○ ---- ---- ----

(P1)
8 RD00 BTM 40 GH 001 XP 02 PAD-L DC SYSTEM BATTERY CHARGER (A) RECTIFIER FAILURE 30 PAD-L DC SYS BAT (A) RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-L NA DCSRDL --- ---- ○ ---- ---- ----

(P1)

9 RD00 BTM 40 GH 001 XP 03 PAD-L DC SYSTEM BATTERY CHARGER (A) GROUND FAULT 28 PAD-L DC SYS BAT (A) GRD FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-L NA DCSRDL --- ---- ○ ---- ---- ----

(P1)

10 RD00 BTM 40 GH 001 XP 04 PAD-L DC SYSTEM BATTERY CHARGER (A) DC UNDER VOLTAGE 32 PAD-L DC SYS BAT (A) DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-L NA DCSRDL --- ---- ---- ---- ○ ----
(P1)

11 RD00 BTM 40 GH 001 XP 05 PAD-L DC SYSTEM BATTERY CHARGER (A) OVER TEMPERATURE 30 PAD-L DC SYS BAT (A) OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-L NA DCSRDL --- ---- ○ ---- ---- ----

(P1)
12 RD00 BTM 40 GH 001 XP 06 PAD-L DC SYSTEM BATTERY (A) FAULT 26 PAD-L DC SYS BAT (A) FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-L NA DCSRDL --- ---- ○ ---- ---- ----

(P1)
15 RD00 BTM 40 GH 002 XP 01 PAD-L DC SYSTEM BACKUP CONVERTER LOSS OF AC POWER SUPPLY 29 PAD-L DC SYS BU CNVTR PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-L NA DCSRDL --- ---- ○ ---- ---- ----

(P1)
16 RD00 BTM 40 GH 002 XP 02 PAD-L DC SYSTEM BACKUP CONVERTER RECTIFIER FAILURE 31 PAD-L DC SYS BU CNVTR RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-L NA DCSRDL --- ---- ○ ---- ---- ----

(P1)
17 RD00 BTM 40 GH 002 XP 03 PAD-L DC SYSTEM BACKUP CONVERTER GROUND FAULT 32 PAD-L DC SYS BU CNVTR GRND FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-L NA DCSRDL --- ---- ○ ---- ---- ----

(P1)

18 RD00 BTM 40 GH 002 XP 04 PAD-L DC SYSTEM BACKUP CONVERTER DC UNDER VOLTAGE 32 PAD-L DC SYS BU CNVT DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-L NA DCSRDL --- ---- ○ ---- ---- ----

(P1)
19 RD00 BTM 40 GH 002 XP 05 PAD-L DC SYSTEM BACKUP CONVERTER OVER TEMPERATURE 32 PAD-L DC SYS BU CNVTR OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-L NA DCSRDL --- ---- ○ ---- ---- ----

(P1)
3.DCS IO LIST FOR COMMUNICATION
3-6.WELLPAD-M AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Tag No. SIGNAL RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
(with 30 word limitation)
1 RD00 BFC 50 XN 01 PAD-M INCOMING FROM PAD-M DISTRIBUTION TRANSFORMER (52L-M) CURRENT 30 PAD-M IC FRM DSTRBTN TRANS CUR 0-100 A AI TCP/IP - - - RD-BLVPDM NA DCSRDM --- ○ ---- ---- ---- ○ ----

7 RD00 BTM 50 GH 001 XP 01 PAD-M DC SYSTEM BATTERY CHARGER (A) LOSS OF AC POWER SUPPLY 28 PAD-M DC SYS BAT (A) PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-M NA DCSRDM --- ---- ○ ---- ---- ----

(P1)
8 RD00 BTM 50 GH 001 XP 02 PAD-M DC SYSTEM BATTERY CHARGER (A) RECTIFIER FAILURE 30 PAD-M DC SYS BAT (A) RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-M NA DCSRDM --- ---- ○ ---- ---- ----

(P1)

9 RD00 BTM 50 GH 001 XP 03 PAD-M DC SYSTEM BATTERY CHARGER (A) GROUND FAULT 28 PAD-M DC SYS BAT (A) GRD FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-M NA DCSRDM --- ---- ○ ---- ---- ----

(P1)

10 RD00 BTM 50 GH 001 XP 04 PAD-M DC SYSTEM BATTERY CHARGER (A) DC UNDER VOLTAGE 32 PAD-M DC SYS BAT (A) DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-M NA DCSRDM --- ---- ---- ---- ○ ----
(P1)

11 RD00 BTM 50 GH 001 XP 05 PAD-M DC SYSTEM BATTERY CHARGER (A) OVER TEMPERATURE 30 PAD-M DC SYS BAT (A) OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-M NA DCSRDM --- ---- ○ ---- ---- ----

(P1)
12 RD00 BTM 50 GH 001 XP 06 PAD-M DC SYSTEM BATTERY (A) FAULT 26 PAD-M DC SYS BAT (A) FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-M NA DCSRDM --- ---- ○ ---- ---- ----

(P1)
15 RD00 BTM 50 GH 002 XP 01 PAD-M DC SYSTEM BACKUP CONVERTER LOSS OF AC POWER SUPPLY 29 PAD-M DC SYS BU CNVTR PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-M NA DCSRDM --- ---- ○ ---- ---- ----

(P1)
16 RD00 BTM 50 GH 002 XP 02 PAD-M DC SYSTEM BACKUP CONVERTER RECTIFIER FAILURE 31 PAD-M DC SYS BU CNVTR RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-M NA DCSRDM --- ---- ○ ---- ---- ----

(P1)
17 RD00 BTM 50 GH 002 XP 03 PAD-M DC SYSTEM BACKUP CONVERTER GROUND FAULT 32 PAD-M DC SYS BU CNVTR GRND FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-M NA DCSRDM --- ---- ○ ---- ---- ----

(P1)

18 RD00 BTM 50 GH 002 XP 04 PAD-M DC SYSTEM BACKUP CONVERTER DC UNDER VOLTAGE 32 PAD-M DC SYS BU CNVT DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-M NA DCSRDM --- ---- ○ ---- ---- ----

(P1)
19 RD00 BTM 50 GH 002 XP 05 PAD-M DC SYSTEM BACKUP CONVERTER OVER TEMPERATURE 32 PAD-M DC SYS BU CNVTR OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-M NA DCSRDM --- ---- ○ ---- ---- ----

(P1)
3.DCS IO LIST FOR COMMUNICATION
3-7.WELLPAD-C AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Tag No. SIGNAL RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
(with 30 word limitation)
1 RD00 BFC 20 XN 01 PAD-C INCOMING FROM PAD-C DISTRIBUTION TRANSFORMER (52L-C) CURRENT 30 PAD-C IC FRM DSTRBTN TRANS CUR 0-100 A AI TCP/IP - - - RD-BLVPDC NA DCSRDC --- ○ ---- ---- ---- ○ ----

7 RD00 BTM 20 GH 001 XP 01 PAD-C DC SYSTEM BATTERY CHARGER (A) LOSS OF AC POWER SUPPLY 28 PAD-C DC SYS BAT (A) PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-C NA DCSRDC --- ---- ○ ---- ---- ----

(P1)
8 RD00 BTM 20 GH 001 XP 02 PAD-C DC SYSTEM BATTERY CHARGER (A) RECTIFIER FAILURE 30 PAD-C DC SYS BAT (A) RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-C NA DCSRDC --- ---- ○ ---- ---- ----

(P1)

9 RD00 BTM 20 GH 001 XP 03 PAD-C DC SYSTEM BATTERY CHARGER (A) GROUND FAULT 28 PAD-C DC SYS BAT (A) GRD FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-C NA DCSRDC --- ---- ○ ---- ---- ----

(P1)

10 RD00 BTM 20 GH 001 XP 04 PAD-C DC SYSTEM BATTERY CHARGER (A) DC UNDER VOLTAGE 32 PAD-C DC SYS BAT (A) DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-C NA DCSRDC --- ---- ---- ---- ○ ----
(P1)

11 RD00 BTM 20 GH 001 XP 05 PAD-C DC SYSTEM BATTERY CHARGER (A) OVER TEMPERATURE 30 PAD-C DC SYS BAT (A) OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-C NA DCSRDC --- ---- ○ ---- ---- ----

(P1)
12 RD00 BTM 20 GH 001 XP 06 PAD-C DC SYSTEM BATTERY (A) FAULT 26 PAD-C DC SYS BAT (A) FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-C NA DCSRDC --- ---- ○ ---- ---- ----

(P1)
15 RD00 BTM 20 GH 002 XP 01 PAD-C DC SYSTEM BACKUP CONVERTER LOSS OF AC POWER SUPPLY 29 PAD-C DC SYS BU CNVTR PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-C NA DCSRDC --- ---- ○ ---- ---- ----

(P1)
16 RD00 BTM 20 GH 002 XP 02 PAD-C DC SYSTEM BACKUP CONVERTER RECTIFIER FAILURE 31 PAD-C DC SYS BU CNVTR RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-C NA DCSRDC --- ---- ○ ---- ---- ----

(P1)
17 RD00 BTM 20 GH 002 XP 03 PAD-C DC SYSTEM BACKUP CONVERTER GROUND FAULT 32 PAD-C DC SYS BU CNVTR GRND FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-C NA DCSRDC --- ---- ○ ---- ---- ----

(P1)

18 RD00 BTM 20 GH 002 XP 04 PAD-C DC SYSTEM BACKUP CONVERTER DC UNDER VOLTAGE 32 PAD-C DC SYS BU CNVT DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-C NA DCSRDC --- ---- ○ ---- ---- ----

(P1)
19 RD00 BTM 20 GH 002 XP 05 PAD-C DC SYSTEM BACKUP CONVERTER OVER TEMPERATURE 32 PAD-C DC SYS BU CNVTR OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-C NA DCSRDC --- ---- ○ ---- ---- ----

(P1)
3.DCS IO LIST FOR COMMUNICATION
3-8.WELLPAD-C AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Tag No. SIGNAL RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
(with 30 word limitation)
1 RD00 BFC 70 XN 01 PAD-B INCOMING FROM PAD-B DISTRIBUTION TRANSFORMER (52L-B) CURRENT 30 PAD-B IC FRM DSTRBTN TRANS CUR v A AI TCP/IP - - - RD-BLVPDB NA DCSRDB --- ○ ---- ---- ---- ○ ----

7 RD00 BTM 70 GH 001 XP 01 PAD-B DC SYSTEM BATTERY CHARGER (A) LOSS OF AC POWER SUPPLY 28 PAD-B DC SYS BAT (A) PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
8 RD00 BTM 70 GH 001 XP 02 PAD-B DC SYSTEM BATTERY CHARGER (A) RECTIFIER FAILURE 30 PAD-B DC SYS BAT (A) RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)

9 RD00 BTM 70 GH 001 XP 03 PAD-B DC SYSTEM BATTERY CHARGER (A) GROUND FAULT 28 PAD-B DC SYS BAT (A) GRD FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)

10 RD00 BTM 70 GH 001 XP 04 PAD-B DC SYSTEM BATTERY CHARGER (A) DC UNDER VOLTAGE 32 PAD-B DC SYS BAT (A) DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ---- ---- ○ ----
(P1)

11 RD00 BTM 70 GH 001 XP 05 PAD-B DC SYSTEM BATTERY CHARGER (A) OVER TEMPERATURE 30 PAD-B DC SYS BAT (A) OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
12 RD00 BTM 70 GH 001 XP 06 PAD-B DC SYSTEM BATTERY (A) FAULT 26 PAD-B DC SYS BAT (A) FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
15 RD00 BTM 70 GH 002 XP 01 PAD-B DC SYSTEM BACKUP CONVERTER LOSS OF AC POWER SUPPLY 29 PAD-B DC SYS BU CNVTR PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
16 RD00 BTM 70 GH 002 XP 02 PAD-B DC SYSTEM BACKUP CONVERTER RECTIFIER FAILURE 31 PAD-B DC SYS BU CNVTR RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
17 RD00 BTM 70 GH 002 XP 03 PAD-B DC SYSTEM BACKUP CONVERTER GROUND FAULT 32 PAD-B DC SYS BU CNVTR GRND FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)

18 RD00 BTM 70 GH 002 XP 04 PAD-B DC SYSTEM BACKUP CONVERTER DC UNDER VOLTAGE 32 PAD-B DC SYS BU CNVT DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
19 RD00 BTM 70 GH 002 XP 05 PAD-B DC SYSTEM BACKUP CONVERTER OVER TEMPERATURE 32 PAD-B DC SYS BU CNVTR OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
3.DCS IO LIST FOR COMMUNICATION
3-9.WELLPAD-N AREA

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
Tag No. SIGNAL RETURN
No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
BAND HHH HH H L LL
(with 30 word limitation)
1 RD00 BFC 80 XN 01 PAD-N INCOMING FROM PAD-N DISTRIBUTION TRANSFORMER (52L-M) CURRENT 30 PAD-N IC FRM DSTRBTN TRANS CUR 0-100 A AI TCP/IP - - - RD-BLVPDB NA DCSRDB --- ○ ---- ---- ---- ○ ----

7 RD00 BTM 80 GH 001 XP 01 PAD-N DC SYSTEM BATTERY CHARGER (A) LOSS OF AC POWER SUPPLY 28 PAD-N DC SYS BAT (A) PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
8 RD00 BTM 80 GH 001 XP 02 PAD-N DC SYSTEM BATTERY CHARGER (A) RECTIFIER FAILURE 30 PAD-N DC SYS BAT (A) RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)

9 RD00 BTM 80 GH 001 XP 03 PAD-N DC SYSTEM BATTERY CHARGER (A) GROUND FAULT 28 PAD-N DC SYS BAT (A) GRD FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)

10 RD00 BTM 80 GH 001 XP 04 PAD-N DC SYSTEM BATTERY CHARGER (A) DC UNDER VOLTAGE 32 PAD-N DC SYS BAT (A) DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ---- ---- ○ ----
(P1)

11 RD00 BTM 80 GH 001 XP 05 PAD-N DC SYSTEM BATTERY CHARGER (A) OVER TEMPERATURE 30 PAD-N DC SYS BAT (A) OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
12 RD00 BTM 80 GH 001 XP 06 PAD-N DC SYSTEM BATTERY (A) FAULT 26 PAD-N DC SYS BAT (A) FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCARD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
15 RD00 BTM 80 GH 002 XP 01 PAD-N DC SYSTEM BACKUP CONVERTER LOSS OF AC POWER SUPPLY 29 PAD-N DC SYS BU CNVTR PW LOSS NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
16 RD00 BTM 80 GH 002 XP 02 PAD-N DC SYSTEM BACKUP CONVERTER RECTIFIER FAILURE 31 PAD-N DC SYS BU CNVTR RCTFR FLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
17 RD00 BTM 80 GH 002 XP 03 PAD-N DC SYSTEM BACKUP CONVERTER GROUND FAULT 32 PAD-N DC SYS BU CNVTR GRND FAULT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)

18 RD00 BTM 80 GH 002 XP 04 PAD-N DC SYSTEM BACKUP CONVERTER DC UNDER VOLTAGE 32 PAD-N DC SYS BU CNVT DC UNDR VLT NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
19 RD00 BTM 80 GH 002 XP 05 PAD-N DC SYSTEM BACKUP CONVERTER OVER TEMPERATURE 32 PAD-N DC SYS BU CNVTR OVER TEMP NORMAL/ALARM ---- DI TCP/IP - NO - BCBRD-B NA DCSRDB --- ---- ○ ---- ---- ----

(P1)
3.DCS IO LIST FOR COMMUNICATION
3-8.SWITCH YARD

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
within 32 Chara BAND

835 RD01 AEA 10 XN 01 LINE BAY U1 CURRENT 17 LINE BAY1 CURRENT 0-1250 A AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

836 RD01 AEA 10 XN 02 LINE BAY U1 VOLTAGE 17 LINE BAY1 VOLTAGE 0-170 kV AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

837 RD01 AEA 10 XN 03 LINE BAY U1 ACTIVE POWER (MAIN) 29 LINE BAY1 ACTIVE POWER (MAIN) 0-250 MW AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

838 RD01 AEA 10 XN 04 LINE BAY U1 REACTIVE POWER (MAIN) 29 LINE BAY1 REACTIVE PWR (MAIN) 0-250 MVAR AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

839 RD01 AEA 10 XN 05 LINE BAY U1 FREQUENCY 19 LINE BAY1 FREQUENCY 45-55 Hz AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

840 RD01 AEA 10 XT 01 LINE BAY U1 WATT HOUR (MAIN) 26 LINE BAY1 WATT HOUR (MAIN) 0 - 999,999,999,999 kWh AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

841 RD01 AEA 10 XT 02 LINE BAY U1 VAR HOUR (MAIN) 25 LINE BAY1 VAR HOUR (MAIN) 0 - 999,999,999,999 kVARh AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1102 RD01 AEA 10 XN 06 LINE BAY U1 ACTIVE POWER (CHECK) 30 LINE BAY1 ACTIVE POWER (CHECK) 0-250 MW AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1103 RD01 AEA 10 XN 07 LINE BAY U1 REACTIVE POWER (CHECK) 30 LINE BAY1 REACTIVE PWR (CHECK) 0-250 MVAR AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1104 RD01 AEA 10 XT 03 LINE BAY U1 WATT HOUR (CHECK) 27 LINE BAY1 WATT HOUR (CHECK) - 376 - + 376 kWh AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1105 RD01 AEA 10 XT 04 LINE BAY U1 VAR HOUR (CHECK) 26 LINE BAY1 VAR HOUR (CHECK) - 376 - + 376 kVARh AI IEC61850 - - - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

842 RD01 AEA 10 YP 01 LINE BAY U1 150 KV CB OPEN COMMAND 27 LINE BAY1 150KV CB OPEN CMD ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY1 - ○ ---- ○ ---- ○ ----

843 RD01 AEA 10 YP 02 LINE BAY U1 150 KV CB CLOSE COMMAND 29 LINE BAY1 150 KV CB CLOSE CMD ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY1 - ○ ---- ○ ---- ○ ----

844 RD01 AEA 10 XP 01 LINE BAY U1 150 KV CB OPEN INDICATION 25 LINE BAY1 150 KV CB OPEN OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

845 RD01 AEA 10 XP 02 LINE BAY U1 150 KV CB CLOSED INDICATION 27 LINE BAY1 150 KV CB CLOSED OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

846 RD01 AEA 10 XP 03 LINE BAY U1 150 KV CB SF6 LOW (ALARM) 30 LINE BAY1 150kV CB SF6 Low Alm OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

848 RD01 AEA 10 XP 05 LINE BAY U1 150 KV CB SF6 LOW (TRIP) 27 LINE BAY1 150kV CB SF6 Low OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

849 RD01 AEA 10 XP 06 LINE BAY U1 150 KV CB MOTOR DRIVING FAULT 30 LINE BAY1 150kV CB Motor Fault OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ○ ----
(P1)

850 RD01 AEA 10 XP 07 LINE BAY U1 MCB TRIP-1/2 CIRCUIT FAILURE 30 LINE BAY1 Trip Circuit 1 Alarm NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

852 RD01 AEA 10 XP 09 LINE BAY U1 MAIN PROTECTION INOPERATIVE 28 LINE BAY1 MPU Rly. Not Ready NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

853 RD01 AEA 10 XP 10 LINE BAY U1 BACK UP PROTECTION INOPERATIVE 28 LINE BAY1 BPU Rly. Not Ready OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

854 RD01 AEA 10 XP 11 LINE BAY U1 RELAY 21 1P OPR 25 LINE BAY1 RELAY 21 1P OPR OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

856 RD01 AEA 10 XP 13 LINE BAY U1 AUTO RECLOSER IN PROGRESS 29 LINE BAY1 Autoreclose Lockout NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ---- ○ ----

857 RD01 AEA 10 XP 14 LINE BAY U1 CHECK SYNCHRO IN PROGRESS 21 LINE BAY1 SYNCROCHECK OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

858 RD01 AEA 10 XP 15 LINE BAY U1 AUTO RECLOSER OPERATED 23 LINE BAY1 AUTO RECLOSER OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

861 RD01 AEA 10 XP 16 LINE BAY U1 EARTHING ES-TL1 OPEN INDICATION 30 LINE BAY1 EARTHING ES-TL1 OPEN OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

862 RD01 AEA 10 XP 17 LINE BAY U1 EARTHING ES-TL1 CLOSED INDICATION 29 LINE BAY1 EARTHING ES-TL1 CLS OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

863 RD01 AEA 10 YP 05 LINE BAY U1 LINE DSE-TL1 OPEN COMMAND 30 LINE BAY1 LINE DSE-TL1 OPN CMD ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY1 - ---- ---- ○ ---- ○ ----

864 RD01 AEA 10 YP 06 LINE BAY U1 LINE DSE-TL1 CLOSE COMMAND 30 LINE BAY1 LINE DSE-TL1 CLS CMD ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY1 - ---- ---- ○ ---- ○ ----

865 RD01 AEA 10 XP 18 LINE BAY U1 LINE DSE-TL1 OPEN INDICATION 27 LINE BAY1 LINE DSE-TL1 OPEN OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

866 RD01 AEA 10 XP 19 LINE BAY U1 LINE DSE-TL1 CLOSED INDICATION 29 LINE BAY1 LINE DSE-TL1 CLOSED OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1127 RD01 AEA 10 XP 36 LINE BAY U1 EARTHING SWITCH DSE-TL1 OPEN INDICATION 30 LINE BAY1 EARTH SW DSE-TL1 OPN OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1128 RD01 AEA 10 XP 37 LINE BAY U1 EARTHING SWITCH DSE-TL1 CLOSED INDICATION 30 LINE BAY1 EARTH SW DSE-TL1 CLS OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

867 RD01 AEA 10 YP 07 LINE BAY U1 DISCONNECTING SWITCH DS-TL11 OPEN COMMAND 32 LINE BAY1 DSCN SW DS-TL11 OPN CM ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY1 - ---- ---- ○ ---- ○ ----

868 RD01 AEA 10 YP 08 LINE BAY U1 DISCONNECTING SWITCH DS-TL11 CLOSE COMMAND 32 LINE BAY1 DSCN SW DS-TL11 CLS CM ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY1 - ---- ---- ○ ---- ○ ----

869 RD01 AEA 10 XP 20 LINE BAY U1 DISCONNECTING SWITCH DS-TL11 OPEN INDICATION 30 LINE BAY1 DSCN SW DS-TL11 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

870 RD01 AEA 10 XP 21 LINE BAY U1 DISCONNECTING SWITCH DS-TL11 CLOSED INDICATION 29 LINE BAY1 DSCN SW DS-TL11 CLS NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

873 RD01 AEA 10 XP 22 LINE BAY U1 BUS-1 EARTHING SWITCH DS-TL21 OPEN INDICATION 32 LINE1 BUS-1 EARTH SW DS-TL11 OPN NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ---- ○ ----

874 RD01 AEA 10 XP 23 LINE BAY U1 BUS-1 EARTHING SWITCH DS-TL21 CLOSED INDICATION 32 LINE1 BUS-1 EARTH SW DS-TL11 CLS NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ---- ○ ----

875 RD01 AEA 10 YP 11 LINE BAY U1 DISCONNECTING SWITCH DS-TL22 OPEN COMMAND 32 LINE BAY1 DSCN SW DS-TL12 OPN CM ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY1 - ---- ---- ○ ---- ○ ----

876 RD01 AEA 10 YP 12 LINE BAY U1 DISCONNECTING SWITCH DS-TL22 CLOSE COMMAND 32 LINE BAY1 DSCN SW DS-TL12 CLS CM ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY1 - ---- ---- ○ ---- ○ ----

877 RD01 AEA 10 XP 24 LINE BAY U1 DISCONNECTING SWITCH DS-TL22 OPEN INDICATION 30 LINE BAY1 DSCN SW DS-TL12 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ---- ○ ----

878 RD01 AEA 10 XP 25 LINE BAY U1 DISCONNECTING SWITCH DS-TL22 CLOSED INDICATION 29 LINE BAY1 DSCN SW DS-TL12 CLS NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ---- ○ ----

881 RD01 AEA 10 XP 26 LINE BAY U1 EARTHING SWITCH DS-TL12 OPEN INDICATION 30 LINE BAY1 EARTH SW DS-TL12 OPN NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ---- ○ ----

882 RD01 AEA 10 XP 27 LINE BAY U1 EARTHING SWITCH DS-TL12 CLOSED INDICATION 30 LINE BAY1 EARTH SW DS-TL12 CLS NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ---- ○ ----


883 RD01 AEA 10 XP 28 OHL TO LUMUT BALAI LINE 1 CB FAILURE PROT. OPR 19 BALAI LINE1 CB Fail NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

884 RD01 AEA 10 XP 29 OHL TO LUMUT BALAI LINE 1 MAIN PROTECTION OPERATED 24 BALAI LINE1 MPU Rly. OPR OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

885 RD01 AEA 10 XP 30 OHL TO LUMUT BALAI LINE 1 MCB VT FAILURE 24 BALAI LINE1 MCB CT Fault OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

886 RD01 AEA 10 XP 31 OHL TO LUMUT BALAI LINE 1 BACK UP PROTECTION OPERATED 24 BALAI LINE1 BPU Rly. OPR OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

887 RD01 AEA 10 XP 32 OHL TO LUMUT BALAI LINE 1 BAY IN SUPERVISORY MODE 28 BALAI LINE1 Supervisory Mode OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----
3.DCS IO LIST FOR COMMUNICATION
3-8.SWITCH YARD

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
within 32 Chara BAND

888 RD01 AEA 10 XP 33 OHL TO LUMUT BALAI LINE 1 BAY IN LOCAL MODE 22 BALAI LINE1 Local Mode OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

889 RD01 AEA 10 XP 34 OHL TO LUMUT BALAI LINE 1 DC SUPPLY (C1) FAILURE 31 BALAI LINE1 DC Supply (C1) Fail NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

890 RD01 AEA 10 XP 35 OHL TO LUMUT BALAI LINE 1 DC (P1 OR P2) LOSE 28 BALAI LINE1 DC (P1orP2) Lose OFF/ON ---- DI IEC61850 - NO - LINEBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)
899 RD01 AEA 20 XN 07 TRAFO BAY U1 CURRENT 19 TRAFO BAY1 CURRENT 0-3150 A AI IEC61850 - - - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

900 RD01 AEA 20 XN 08 TRAFO BAY U1 VOLTAGE 19 TRAFO BAY1 VOLTAGE 0-170 kV AI IEC61850 - - - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

901 RD01 AEA 20 XN 09 TRAFO BAY U1 ACTIVE POWER 24 TRAFO BAY1 ACTIVE POWER 0-60 MW AI IEC61850 - - - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

902 RD01 AEA 20 XN 10 TRAFO BAY U1 REACTIVE POWER 26 TRAFO BAY1 REACTIVE POWER 0-60 MVAR AI IEC61850 - - - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

903 RD01 AEA 20 XN 11 TRAFO BAY U1 FREQUENCY 21 TRAFO BAY1 FREQUENCY 45-55 Hz AI IEC61850 - - - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

904 RD01 AEA 20 XT 03 TRAFO BAY U1 NETT WATT HOUR 26 TRAFO BAY1 NETT WATT HOUR 0 - 999,999,999,999 kWh AI IEC61850 - - - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

905 RD01 AEA 20 XT 04 TRAFO BAY U1 NETT VAR HOUR 25 TRAFO BAY1 NETT VAR HOUR 0 - 999,999,999,999 kVARh AI IEC61850 - - - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

907 RD01 AEA 20 YP 01 TRAFO BAY U1 CB-TR1 CB OPEN COMMAND 29 TRAFO BAY1 CB-TR1 CB OPEN CMD ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY1 - ○ ---- ○ ---- ○ ----

908 RD01 AEA 20 YP 02 TRAFO BAY U1 CB-TR1 CB CLOSE COMMAND 30 TRAFO BAY1 CB-TR1 CB CLOSE CMD ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY1 - ○ ---- ○ ---- ○ ----

909 RD01 AEA 20 XP 01 TRAFO BAY U1 CB-TR1 CBOPEN INDICATION 24 TRAFO BAY1 CB-TR1 CBOPEN OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ---- ---- ---- ---- ○ ----

910 RD01 AEA 20 XP 02 TRAFO BAY U1 CB-TR1 CB CLOSED INDICATION 27 TRAFO BAY1 CB-TR1 CB CLOSED OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ---- ---- ---- ---- ○ ----

911 RD01 AEA 20 XP 03 TRAFO BAY U1 150 KV CB SF6 LOW (ALARM) 31 TRAFO BAY1 150kV CB SF6 Low Alm OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----


913 RD01 AEA 20 XP 05 TRAFO BAY U1 150 KV CB SF6 LOW (TRIP) 28 TRAFO BAY1 150kV CB SF6 Low OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

914 RD01 AEA 20 XP 06 TRAFO BAY U1 150 KV CB MOTOR DRIVING FAULT 31 TRAFO BAY1 150kV CB Motor Fault OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----


915 RD01 AEA 20 XP 07 TRAFO BAY U1 MCB TRIP-1/2 CIRCUIT FAILURE 31 TRAFO BAY1 Trip Circuit 1 Alarm NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

918 RD01 AEA 20 XP 10 TRAFO BAY U1 BACK UP PROTECTION INOPERATIVE 30 TRAFO BAY1 BPU Rly. Not Ready OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

921 RD01 AEA 20 XP 13 TRAFO BAY U1 CHECK SYNCHRO IN PROGRESS 22 TRAFO BAY1 SYNCROCHECK OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

922 RD01 AEA 20 YP 03 TRAFO BAY U1 DISCONNECTING SWITCH DS-TR11 OPEN COMMAND 32 TRAFO BAY1 DSCN SW DS-TR11 OP CM NORMAL/ALARM ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY1 - ---- ---- ○ ---- ○ ----

923 RD01 AEA 20 YP 04 TRAFO BAY U1 DISCONNECTING SWITCH DS-TR11 CLOSE COMMAND 32 TRAFO BAY1 DSCN SW DS-TR11 CL CM ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY1 - ---- ---- ○ ---- ○ ----

924 RD01 AEA 20 XP 14 TRAFO BAY U1 DISCONNECTING SWITCH DS-TR11 OPEN INDICATION 31 TRAFO BAY1 DSCN SW DS-TR11 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

925 RD01 AEA 20 XP 15 TRAFO BAY U1 DISCONNECTING SWITCH DS-TR11 CLOSED INDICATION 32 TRAFO BAY1 DSCN SW DS-TR11 CLOSE NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

928 RD01 AEA 20 XP 16 TRAFO BAY U1 EARTHING SWITCH DS-TR11 OPEN INDICATION 32 TRAFO BAY U1 EARTH SW DS-TR11 OP NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

929 RD01 AEA 20 XP 17 TRAFO BAY U1 EARTHING SWITCH DS-TR11 CLOSED INDICATION 32 TRAFO BAY U1 EARTH SW DS-TR11 CL NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

930 RD01 AEA 20 YP 07 TRAFO BAY U1 DISCONNECTING SWITCH DS-TR12 OPEN COMMAND 32 TRAFO BAY1 DSCN SW DS-TR12 OP CM ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY1 - ---- ---- ○ ---- ○ ----

931 RD01 AEA 20 YP 08 TRAFO BAY U1 DISCONNECTING SWITCH DS-TR12 CLOSE COMMAND 32 TRAFO BAY1 DSCN SW DS-TR12 CL CM ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY1 - ---- ---- ○ ---- ○ ----

932 RD01 AEA 20 XP 18 TRAFO BAY U1 DISCONNECTING SWITCH DS-TR12 OPEN INDICATION 31 TRAFO BAY1 DSCN SW DS-TR12 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

933 RD01 AEA 20 XP 19 TRAFO BAY U1 DISCONNECTING SWITCH DS-TR12 CLOSED INDICATION 32 TRAFO BAY1 DSCN SW DS-TR12 CLOSE NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

936 RD01 AEA 20 XP 20 TRAFO BAY U1 EARTHING SWITCH DS-TR12 OPEN INDICATION 32 TRAFO BAY1 EARTH SW DS-TR12 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

937 RD01 AEA 20 XP 21 TRAFO BAY U1 EARTHING SWITCH DS-TR12 CLOSED INDICATION 31 TRAFO BAY1 EARTH SW DS-TR12 CLS NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----


938 RD01 AEA 20 XP 22 TRAFO BAY U1 CB FAILURE PROT. OPR 18 TRAFO BAY1 CB Fail NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

940 RD01 AEA 20 XP 24 TRAFO BAY U1 MCB VT FAILURE 23 TRAFO BAY1 MCB VT Fault OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

941 RD01 AEA 20 XP 25 TRAFO BAY U1 BACK UP PROTECTION OPERATED 23 TRAFO BAY1 BPU Rly. OPR OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

942 RD01 AEA 20 XP 26 TRAFO BAY U1 BAY IN SUPERVISORY MODE 27 TRAFO BAY1 Supervisory Mode OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

943 RD01 AEA 20 XP 27 TRAFO BAY U1 BAY IN LOCAL MODE 21 TRAFO BAY1 Local Mode OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----


944 RD01 AEA 20 XP 28 TRAFO BAY U1 DC SUPPLY (C1) FAILURE 30 TRAFO BAY1 DC Supply (C1) Fail NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

945 RD01 AEA 20 XP 29 TRAFO BAY U1 DC (P1 OR P2) LOSE 27 TRAFO BAY1 DC (P1orP2) Lose OFF/ON ---- DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ○ ----
(P1)

1106 RD01 AEA 20 XP 30 TRAFO BAY U1 EARTHING SWITCH DSE-TR1 OPEN INDICATION 32 TRAFO BAY1 EARTH SW DSE-TR1 OPEN OFF/ON DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1107 RD01 AEA 20 XP 31 TRAFO BAY U1 EARTHING SWITCH DSE-TR1 CLOSED INDICATION 31 TRAFO BAY1 EARTH SW DSE-TR1 CLS OFF/ON DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1108 RD01 AEA 20 XP 32 TRAFO BAY U1 EARTHING SWITCH ES-TR1 OPEN INDICATION 31 TRAFO BAY1 EARTH SW ES-TR1 OPEN OFF/ON DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1109 RD01 AEA 20 XP 33 TRAFO BAY U1 EARTHING SWITCH ES-TR1 CLOSED INDICATION 32 TRAFO BAY1 EARTH SW ES-TR1 CLOSE OFF/ON DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1110 RD01 AEA 20 XP 34 TRAFO BAY U1 DISCONNECTING SWITCH DSE-TR1 OPEN INDICATION 31 TRAFO BAY1 DSCN SW DSE-TR1 OPEN OFF/ON DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1111 RD01 AEA 20 XP 35 TRAFO BAY U1 DISCONNECTING SWITCH DSE-TR1 CLOSED INDICATION 32 TRAFO BAY1 DSCN SW DSE-TR1 CLOSE OFF/ON DI IEC61850 - NO - TRAFOBAY1 NA RD00DCS - ○ ---- ---- ---- ○ ----

1112 RD01 AEA 20 YP 09 TRAFO BAY U1 DISCONNECTING SWITCH DSE-TR1 OPEN COMMAND 32 TRAFO BAY1 DSCN SW DSE-TR1 OP CM ---- DOH IEC61850 - NO - RD00DCS NA TRAFOBAY1 - ---- ---- ○ ---- ○ ----

1113 RD01 AEA 20 YP 10 TRAFO BAY U1 DISCONNECTING SWITCH DSE-TR1 CLOSE COMMAND 32 TRAFO BAY1 DSCN SW DSE-TR1 CL CM ---- DOH IEC61850 - NO - RD00DCS NA TRAFOBAY1 - ---- ---- ○ ---- ○ ----

946 RD02 AEA 20 XN 01 LINE BAY U2 CURRENT 17 LINE BAY2 CURRENT 0-1250 A AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

947 RD02 AEA 20 XN 02 LINE BAY U2 VOLTAGE 17 LINE BAY2 VOLTAGE 0-170 kV AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

948 RD02 AEA 20 XN 03 LINE BAY U2 ACTIVE POWER (MAIN) 29 LINE BAY2 ACTIVE POWER (MAIN) 0-250 MW AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----
3.DCS IO LIST FOR COMMUNICATION
3-8.SWITCH YARD

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
within 32 Chara BAND

949 RD02 AEA 20 XN 04 LINE BAY U2 REACTIVE POWER (MAIN) 29 LINE BAY2 REACTIVE PWR (MAIN) 0-250 MVAR AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

950 RD02 AEA 20 XN 05 LINE BAY U2 FREQUENCY 19 LINE BAY2 FREQUENCY 45-55 Hz AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

951 RD02 AEA 20 XT 01 LINE BAY U2 WATT HOUR (MAIN) 26 LINE BAY2 WATT HOUR (MAIN) 0 - 999,999,999,999 kWh AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

952 RD02 AEA 20 XT 02 LINE BAY U2 VAR HOUR (MAIN) 25 LINE BAY2 VAR HOUR (MAIN) 0 - 999,999,999,999 kVARh AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1114 RD01 AEA 20 XN 12 LINE BAY U2 ACTIVE POWER (CHECK) 30 LINE BAY2 ACTIVE POWER (CHECK) 0-250 MW AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1115 RD01 AEA 20 XN 13 LINE BAY U2 REACTIVE POWER (CHECK) 30 LINE BAY2 REACTIVE PWR (CHECK) 0-250 MVAR AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1116 RD01 AEA 20 XT 07 LINE BAY U2 WATT HOUR (CHECK) 27 LINE BAY2 WATT HOUR (CHECK) - 376 - + 376 kWh AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1117 RD01 AEA 20 XT 06 LINE BAY U2 VAR HOUR (CHECK) 26 LINE BAY2 VAR HOUR (CHECK) - 376 - + 376 kVARh AI IEC61850 - - - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

953 RD02 AEA 20 YP 11 LINE BAY U2 150 KV CB OPEN COMMAND 27 LINEBAY2 150 KV CB OPEN CMD ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY2 - ---- ---- ○ ---- ○ ----

954 RD02 AEA 20 YP 12 LINE BAY U2 150 KV CB CLOSE COMMAND 28 LINEBAY2 150 KV CB CLOSE CMD ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY2 - ---- ---- ○ ---- ○ ----

955 RD02 AEA 20 XP 01 LINE BAY U2 150 KV CB OPEN INDICATION 23 LINEBAY2 150 KV CB OPEN OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

956 RD02 AEA 20 XP 02 LINE BAY U2 150 KV CB CLOSED INDICATION 25 LINEBAY2 150 KV CB CLOSED OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----


957 RD02 AEA 20 XP 03 LINE BAY U2 150 KV CB SF6 LOW (ALARM) 29 LINEBAY2 150kV CB SF6 Low Alm OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ○ ----
(P1)

959 RD02 AEA 20 XP 05 LINE BAY U2 150 KV CB SF6 LOW (TRIP) 31 LINEBAY2 150 KV CB SF6 L (TRIP) OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

960 RD02 AEA 20 XP 06 LINE BAY U2 150 KV CB MOTOR DRIVING FAULT 29 LINEBAY2 150kV CB Motor Fault OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ○ ----
(P1)

961 RD02 AEA 20 XP 07 LINE BAY U2 MCB TRIP-1/2 CIRCUIT FAILURE 29 LINEBAY2 Trip Circuit 1 Alarm NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

963 RD02 AEA 20 XP 09 LINE BAY U2 MAIN PROTECTION INOPERATIVE 27 LINEBAY2 MPU Rly. Not Ready NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

964 RD02 AEA 20 XP 10 LINE BAY U2 BACK UP PROTECTION INOPERATIVE 28 LINEBAY2 BPU Rly. Not Ready OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

965 RD02 AEA 20 XP 11 LINE BAY U2 RELAY 21 1P OPR 24 LINEBAY2 Relay 21 1P OPR OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

966 RD02 AEA 20 XP 12 LINE BAY U2 RELAY 67 / 79 FAULTY 26 LINEBAY2 Relay 67/79 Fault NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

967 RD02 AEA 20 XP 13 LINE BAY U2 AUTO RECLOSER IN PROGRESS 28 LINEBAY2 Autoreclose Lockout NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

968 RD02 AEA 20 XP 14 LINE BAY U2 CHECK SYNCHRO IN PROGRESS 23 LINE BAY U1 SYNCROCHECK OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

969 RD02 AEA 20 XP 15 LINE BAY U2 AUTO RECLOSER OPERATED 25 LINE BAY U1 AUTO RECLOSER OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

972 RD02 AEA 20 XP 16 LINE BAY U2 EARTHING ES-TL2 OPEN INDICATION 27 LINE BAY2 EARTH ES-TL2 OPEN OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

973 RD02 AEA 20 XP 17 LINE BAY U2 EARTHING ES-TL2 CLOSED INDICATION 29 LINE BAY2 EARTH ES-TL2 CLOSED OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

974 RD02 AEA 20 YP 15 LINE BAY U2 DISCONNECTING SWITCH DSE-TL2 OPEN COMMAND 32 LINE BAY2 DSCN SW DSE-TL2 OPN CM ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY2 - ○ ---- ○ ---- ○ ----

975 RD02 AEA 20 YP 16 LINE BAY U2 DISCONNECTING SWITCH DSE-TL2 CLOSE COMMAND 32 LINE BAY2 DSCN SW DSE-TL2 CLS CM ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY2 - ○ ---- ○ ---- ○ ----

976 RD02 AEA 20 XP 18 LINE BAY U2 DISCONNECTING SWITCH DSE-TL2 OPEN INDICATION 30 LINE BAY2 DSCN SW DSE-TL2 OPEN OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

977 RD02 AEA 20 XP 19 LINE BAY U2 DISCONNECTING SWITCH DSE-TL2 CLOSED INDICATION 29 LINE BAY2 DSCN SW DSE-TL2 CLS OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1118 RD02 AEA 20 XP 36 LINE BAY U2 EARTHING SWITCH DSE-TL2 OPEN INDICATION 30 LINE BAY2 EARTH SW DSE-TL2 OPN OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1119 RD02 AEA 20 XP 37 LINE BAY U2 EARTHING SWITCH DSE-TL2 CLOSED INDICATION 30 LINE BAY2 EARTH SW DSE-TL2 CLS OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

978 RD02 AEA 20 YP 17 LINE BAY U2 DISCONNECTING SWITCH DS-TL21 OPEN COMMAND 32 LINE BAY2 DSCN SW DS-TL21 OPN CM ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY2 - ○ ---- ○ ---- ○ ----

979 RD02 AEA 20 YP 18 LINE BAY U2 DISCONNECTING SWITCH DS-TL21 CLOSE COMMAND 32 LINE BAY2 DSCN SW DS-TL21 CLS CM ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY2 - ○ ---- ○ ---- ○ ----

980 RD02 AEA 20 XP 20 LINE BAY U2 DISCONNECTING SWITCH DS-TL21 OPEN INDICATION 30 LINE BAY2 DSCN SW DS-TL21 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ○ ---- ---- ○ ----

981 RD02 AEA 20 XP 21 LINE BAY U2 DISCONNECTING SWITCH DS-TL21 CLOSED INDICATION 29 LINE BAY2 DSCN SW DS-TL21 CLS NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ○ ---- ---- ○ ----

984 RD02 AEA 20 XP 22 LINE BAY U2 BUS-1 EARTHING SWITCH DS-TL21 OPEN INDICATION 31 LINE BAY2 BUS-1 ESW DS-TL21 OPN NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

985 RD02 AEA 20 XP 23 LINE BAY U2 BUS-1 EARTHING SWITCH DS-TL21 CLOSED INDICATION 31 LINE BAY2 BUS-1 ESW DS-TL21 CLS NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

986 RD02 AEA 20 YP 21 LINE BAY U2 DISCONNECTING SWITCH DS-TL22 OPEN COMMAND 32 LINE BAY2 DSCN SW DS-TL22 OPN CM ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY2 - ---- ---- ○ ---- ○ ----

987 RD02 AEA 20 YP 22 LINE BAY U2 DISCONNECTING SWITCH DS-TL22 CLOSE COMMAND 32 LINE BAY2 DSCN SW DS-TL22 CLS CM ---- ---- DO IEC61850 - NO - RD00DCS NA LINEBAY2 - ---- ---- ○ ---- ○ ----

988 RD02 AEA 20 XP 24 LINE BAY U2 DISCONNECTING SWITCH DS-TL22 OPEN INDICATION 30 LINE BAY2 DSCN SW DS-TL22 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

989 RD02 AEA 20 XP 25 LINE BAY U2 DISCONNECTING SWITCH DS-TL22 CLOSED INDICATION 29 LINE BAY2 DSCN SW DS-TL22 CLS NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

992 RD02 AEA 20 XP 26 LINE BAY U2 EARTHING SWITCH DS-TL22 OPEN INDICATION 30 LINE BAY2 EARTH SW DS-TL22 OPN NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

993 RD02 AEA 20 XP 27 LINE BAY U2 EARTHING SWITCH DS-TL22 CLOSED INDICATION 30 LINE BAY2 EARTH SW DS-TL22 CLS NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----


994 RD02 AEA 20 XP 28 OHL TO LUMUT BALAI LINE 2 CB FAILURE PROT. OPR 17 LINE BAY2 CB Fail NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

995 RD02 AEA 20 XP 29 OHL TO LUMUT BALAI LINE 2 MAIN PROTECTION OPERATED 22 LINE BAY2 MPU Rly. OPR OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

996 RD02 AEA 20 XP 30 OHL TO LUMUT BALAI LINE 2 MCB VT FAILURE 22 LINE BAY2 MCB VT Fault OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

997 RD02 AEA 20 XP 31 OHL TO LUMUT BALAI LINE 2 BACK UP PROTECTION OPERATED 22 LINE BAY2 BPU Rly. OPR OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

998 RD02 AEA 20 XP 32 OHL TO LUMUT BALAI LINE 2 BAY IN SUPERVISORY MODE 26 LINE BAY2 Supervisory Mode OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

999 RD02 AEA 20 XP 33 OHL TO LUMUT BALAI LINE 2 BAY IN LOCAL MODE 20 LINE BAY2 Local Mode OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----


1000 RD02 AEA 20 XP 34 OHL TO LUMUT BALAI LINE 2 DC SUPPLY (C1) FAILURE 29 LINE BAY2 DC Supply (C1) Fail NORMAL/ALARM ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)
3.DCS IO LIST FOR COMMUNICATION
3-8.SWITCH YARD

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
within 32 Chara BAND

1001 RD02 AEA 20 XP 35 OHL TO LUMUT BALAI LINE 2 DC (P1 OR P2) LOSE 26 LINE BAY2 DC (P1orP2) Lose OFF/ON ---- DI IEC61850 - NO - LINEBAY2 NA RD00DCS - ○ ---- ---- ○ ----
(P1)

1010 RD02 AEA 10 XN 07 TRAFO BAY U2 CURRENT 19 TRAFO BAY2 CURRENT 0-1250 A AI IEC61850 - - - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1011 RD02 AEA 10 XN 08 TRAFO BAY U2 VOLTAGE 19 TRAFO BAY2 VOLTAGE 0-170 kV AI IEC61850 - - - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1012 RD02 AEA 10 XN 09 TRAFO BAY U2 ACTIVE POWER 24 TRAFO BAY2 ACTIVE POWER 0-60 MW AI IEC61850 - - - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1013 RD02 AEA 10 XN 10 TRAFO BAY U2 REACTIVE POWER 26 TRAFO BAY2 REACTIVE POWER 0-60 MVAR AI IEC61850 - - - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1014 RD02 AEA 10 XN 11 TRAFO BAY U2 FREQUENCY 21 TRAFO BAY2 FREQUENCY 45-55 Hz AI IEC61850 - - - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1015 RD02 AEA 10 XT 05 TRAFO BAY U2 NETT WATT HOUR 26 TRAFO BAY2 NETT WATT HOUR 0 - 999,999,999,999 kWh AI IEC61850 - - - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1016 RD02 AEA 10 XT 06 TRAFO BAY U2 NETT VAR HOUR 25 TRAFO BAY2 NETT VAR HOUR 0 - 999,999,999,999 kVARh AI IEC61850 - - - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1018 RD02 AEA 10 YP 25 TRAFO BAY U2 CB-TR1 CB OPEN COMMAND 29 TRAFO BAY2 CB-TR1 CB OPEN CMD ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY2 - ---- ---- ○ ---- ○ ----

1019 RD02 AEA 10 YP 26 TRAFO BAY U2 CB-TR1 CB CLOSE COMMAND 30 TRAFO BAY2 CB-TR1 CB CLOSE CMD ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY2 - ---- ---- ○ ---- ○ ----

1020 RD02 AEA 10 XP 01 TRAFO BAY U2 CB-TR1 CBOPEN INDICATION 24 TRAFO BAY2 CB-TR1 CBOPEN OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1021 RD02 AEA 10 XP 02 TRAFO BAY U2 CB-TR1 CB CLOSED INDICATION 27 TRAFO BAY2 CB-TR1 CB CLOSED OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----


1022 RD02 AEA 10 XP 03 TRAFO BAY U2 150 KV CB SF6 LOW (ALARM) 31 TRAFO BAY2 150kV CB SF6 Low Alm OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ○ ----
(P1)

1024 RD02 AEA 10 XP 05 TRAFO BAY U2 150 KV CB SF6 LOW (TRIP) 28 TRAFO BAY2 150kV CB SF6 Low OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1025 RD02 AEA 10 XP 06 TRAFO BAY U2 150 KV CB MOTOR DRIVING FAULT 31 TRAFO BAY2 150kV CB Motor Fault OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ○ ----
(P1)

1026 RD02 AEA 10 XP 07 TRAFO BAY U2 MCB TRIP-1/2 CIRCUIT FAILURE 31 TRAFO BAY2 Trip Circuit 1 Alarm NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1029 RD02 AEA 10 XP 10 TRAFO BAY U2 BACK UP PROTECTION INOPERATIVE 32 TRAFO BAY U2 BPU Rly. Not Ready OFF/ON ---- DI IEC61850 - NO - RD00DCS NA TRAFOBAY2 - ---- ---- ---- ○ ----
(P1)

1033 RD02 AEA 10 XP 14 TRAFO BAY U2 CHECK SYNCHRO IN PROGRESS 22 TRAFO BAY2 SYNCROCHECK OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1035 RD02 AEA 10 YP 27 TRAFO BAY U2 DISCONNECTING SWITCH DS-TR11 OPEN COMMAND 32 TRAFO BAY2 DSCN SW DS-TR11 OP CM ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY2 - ---- ---- ○ ---- ○ ----

1036 RD02 AEA 10 YP 28 TRAFO BAY U2 DISCONNECTING SWITCH DS-TR11 CLOSE COMMAND 32 TRAFO BAY2 DSCN SW DS-TR11 CL CM ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY2 - ---- ---- ○ ---- ○ ----

1037 RD02 AEA 10 XP 16 TRAFO BAY U2 DISCONNECTING SWITCH DS-TR11 OPEN INDICATION 31 TRAFO BAY2 DSCN SW DS-TR11 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1038 RD02 AEA 10 XP 17 TRAFO BAY U2 DISCONNECTING SWITCH DS-TR11 CLOSED INDICATION 30 TRAFO BAY2 DSCN SW DS-TR11 CLS NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1041 RD02 AEA 10 XP 18 TRAFO BAY U2 EARTHING SWITCH DS-TR11 OPEN INDICATION 32 TRAFO BAY2 EARTH SW DS-TR11 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1042 RD02 AEA 10 XP 19 TRAFO BAY U2 EARTHING SWITCH DS-TR11 CLOSED INDICATION 31 TRAFO BAY2 EARTH SW DS-TR11 CLS NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1043 RD02 AEA 10 YP 31 TRAFO BAY U2 DISCONNECTING SWITCH DS-TR12 OPEN COMMAND 32 TRAFO BAY2 DSCN SW DS-TR12 OP CM ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY2 - ---- ---- ○ ---- ○ ----

1044 RD02 AEA 10 YP 32 TRAFO BAY U2 DISCONNECTING SWITCH DS-TR12 CLOSE COMMAND 32 TRAFO BAY2 DSCN SW DS-TR12 CL CM ---- ---- DO IEC61850 - NO - RD00DCS NA TRAFOBAY2 - ---- ---- ○ ---- ○ ----

1045 RD02 AEA 10 XP 20 TRAFO BAY U2 DISCONNECTING SWITCH DS-TR12 OPEN INDICATION 31 TRAFO BAY2 DSCN SW DS-TR12 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1046 RD02 AEA 10 XP 21 TRAFO BAY U2 DISCONNECTING SWITCH DS-TR12 CLOSED INDICATION 30 TRAFO BAY2 DSCN SW DS-TR12 CLS NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1049 RD02 AEA 10 XP 22 TRAFO BAY U2 EARTHING SWITCH DS-TR12 OPEN INDICATION 32 TRAFO BAY U2 EARTH SW DS-TR12 OP NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1050 RD02 AEA 10 XP 23 TRAFO BAY U2 EARTHING SWITCH DS-TR12 CLOSED INDICATION 32 TRAFO BAY U2 EARTH SW DS-TR12 CL NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----


1051 RD02 AEA 10 XP 24 TRAFO BAY U2 CB FAILURE PROT. OPR 18 TRAFO BAY2 CB Fail NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1053 RD02 AEA 10 XP 26 TRAFO BAY U2 MCB VT FAILURE 23 TRAFO BAY2 MCB VT Fault OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1054 RD02 AEA 10 XP 27 TRAFO BAY U2 BACK UP PROTECTION OPERATED 23 TRAFO BAY2 BPU Rly. OPR OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1055 RD02 AEA 10 XP 28 TRAFO BAY U2 BAY IN SUPERVISORY MODE 27 TRAFO BAY2 Supervisory Mode OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1056 RD02 AEA 10 XP 29 TRAFO BAY U2 BAY IN LOCAL MODE 21 TRAFO BAY2 Local Mode OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----


1057 RD02 AEA 10 XP 30 TRAFO BAY U2 DC SUPPLY (C1) FAILURE 30 TRAFO BAY2 DC Supply (C1) Fail NORMAL/ALARM ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1058 RD02 AEA 10 XP 31 TRAFO BAY U2 DC (P1 OR P2) LOSE 27 TRAFO BAY2 DC (P1orP2) Lose OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ○ ----
(P1)

1120 RD02 AEA 10 XP 32 TRAFO BAY U2 EARTHING SWITCH DSE-TR1 OPEN INDICATION 32 TRAFO BAY2 EARTH SW DSE-TR1 OPEN OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1121 RD02 AEA 10 XP 33 TRAFO BAY U2 EARTHING SWITCH DSE-TR1 CLOSED INDICATION 31 TRAFO BAY2 EARTH SW DSE-TR1 CLS OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1122 RD02 AEA 10 XP 34 TRAFO BAY U2 EARTHING SWITCH ES-TR1 OPEN INDICATION 31 TRAFO BAY2 EARTH SW ES-TR1 OPEN OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1123 RD02 AEA 10 XP 35 TRAFO BAY U2 EARTHING SWITCH ES-TR1 CLOSED INDICATION 30 TRAFO BAY2 EARTH SW ES-TR1 CLS OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1124 RD02 AEA 10 XP 36 TRAFO BAY U2 DISCONNECTING SWITCH DSE-TR1 OPEN INDICATION 31 TRAFO BAY2 DSCN SW DSE-TR1 OPEN OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1125 RD02 AEA 10 XP 37 TRAFO BAY U2 DISCONNECTING SWITCH DSE-TR1 CLOSED INDICATION 30 TRAFO BAY2 DSCN SW DSE-TR1 CLS OFF/ON ---- DI IEC61850 - NO - TRAFOBAY2 NA RD00DCS - ○ ---- ---- ---- ○ ----

1126 RD02 AEA 10 YP 33 TRAFO BAY U2 DISCONNECTING SWITCH DSE-TR1 OPEN COMMAND 32 TRAFO BAY2 DSCN SW DSE-TR1 OP CM ---- ---- DO IEC61850 - ---- - RD00DCS NA TRAFOBAY2 - ---- ---- ---- ○ ○ ----

1127 RD02 AEA 10 YP 34 TRAFO BAY U2 DISCONNECTING SWITCH DSE-TR1 CLOSE COMMAND 32 TRAFO BAY2 DSCN SW DSE-TR1 CL CM ---- ---- DO IEC61850 - ---- - RD00DCS NA TRAFOBAY2 - ---- ---- ---- ○ ○ ----

1059 RD00 AEA 10 YP 35 COUPLER BAY CB-CPL CB OPEN COMMAND 30 COUPLER BAY CB-CPL CB OPEN CMD ---- ---- DO IEC61850 - NO - RD00DCS NA COUPLERBAY - ---- ---- ○ ---- ○ ----

1060 RD00 AEA 10 YP 36 COUPLER BAY CB-CPL CB CLOSE COMMAND 31 COUPLER BAY CB-CPL CB CLOSE CMD ---- ---- DO IEC61850 - NO - RD00DCS NA COUPLERBAY - ---- ---- ○ ---- ○ ----

1061 RD00 AEA 10 XP 01 COUPLER BAY CB-CPL CB OPEN INDICATION 26 COUPLER BAY CB-CPL CB OPEN OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----

1062 RD00 AEA 10 XP 02 COUPLER BAY CB-CPL CB CLOSED INDICATION 28 COUPLER BAY CB-CPL CB CLOSED OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----

1063 RD00 AEA 10 XP 03 COUPLER BAY 150 KV CB SF6 LOW (ALARM) 32 COUPLER BAY 150kV CB SF6 Low Alm OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----
3.DCS IO LIST FOR COMMUNICATION
3-8.SWITCH YARD

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
within 32 Chara BAND

1065 RD00 AEA 10 XP 05 COUPLER BAY 150 KV CB SF6 LOW (TRIP) 29 COUPLER BAY 150kV CB SF6 Low OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1066 RD00 AEA 10 XP 06 COUPLER BAY 150 KV CB MOTOR DRIVING FAULT 32 COUPLER BAY 150kV CB Motor Fault OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ○ ----
(P1)

1067 RD00 AEA 10 XP 07 COUPLER BAY MCB TRIP-1/2 CIRCUIT FAILURE 32 COUPLER BAY Trip Circuit 1 Alarm NORMAL/ALARM ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1069 RD00 AEA 10 XP 09 COUPLER BAY MAIN PROTECTION INOPERATIVE 30 COUPLER BAY MPU Rly. Not Ready NORMAL/ALARM ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1070 RD00 AEA 10 XP 10 COUPLER BAY BACK UP PROTECTION INOPERATIVE 31 COUPLER BAY BPU Rly. Not Ready OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1071 RD00 AEA 10 XP 11 COUPLER BAY BPU RELAY 51 3P OPERATED 31 COUPLER BAY BPU Relay 51 3P OPR OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1074 RD00 AEA 10 XP 14 COUPLER BAY CHECK SYNCHRO IN PROGRESS 24 COUPLER BAY SYNCHROCHECK OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----


1075 RD00 AEA 10 XP 15 COUPLER BAY MPU RELAY 87B OPERATED 29 COUPLER BAY MPU Relay 87B OPR OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1078 RD00 AEA 10 XP 16 COUPLER BAY DS EARTHING SWITCH ES-A OPEN INDICATION 30 CPLR BAY DS EARTH SW ES-A OPEN OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----

1079 RD00 AEA 10 XP 17 COUPLER BAY DS EARTHING SWITCH ES-A CLOSED INDICATION 32 CPLR BAY DS EARTH SW ES-A CLOSED OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----

1082 RD00 AEA 10 XP 18 COUPLER BAY DS EARTHING SWITCH ES-B OPEN INDICATION 30 CPLR BAY DS EARTH SW ES-B OPEN OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----

1083 RD00 AEA 10 XP 19 COUPLER BAY DS EARTHING SWITCH ES-B CLOSED INDICATION 31 CPLR BAY DS EARTH SW ES-B CLOSE OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----

1084 RD00 AEA 10 YP 03 COUPLER BAY DISCONNECTING SWITCH DS-CPL1 OPEN COMMAND 32 CPLR BAY DSCN SW DS-CPL1 OPN CMD ---- ---- DO IEC61850 - NO - RD00DCS NA COUPLERBAY - ---- ---- ○ ---- ○ ----

1085 RD00 AEA 10 YP 04 COUPLER BAY DISCONNECTING SWITCH DS-CPL1 CLOSE COMMAND 32 CPLR BAY DSCN SW DS-CPL1 CLS CMD ---- ---- DO IEC61850 - NO - RD00DCS NA COUPLERBAY - ---- ---- ○ ---- ○ ----

1086 RD00 AEA 10 XP 20 COUPLER BAY DISCONNECTING SWITCH DS-CPL1 OPEN INDICATION 32 COUPLER BAY DSCN SW DS-CPL1 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----

1087 RD00 AEA 10 XP 21 COUPLER BAY DISCONNECTING SWITCH DS-CPL1 CLOSED INDICATION 31 COUPLER BAY DSCN SW DS-CPL1 CLS NORMAL/ALARM ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----

1088 RD00 AEA 10 YP 05 COUPLER BAY DISCONNECTING SWITCH DS-CPL2 OPEN COMMAND 32 CPLR BAY DSCN SW DS-CPL2 OPN CMD ---- ---- DO IEC61850 - NO - RD00DCS NA COUPLERBAY - ---- ---- ○ ---- ○ ----

1089 RD00 AEA 10 YP 06 COUPLER BAY DISCONNECTING SWITCH DS-CPL2 CLOSE COMMAND 32 CPLR BAY DSCN SW DS-CPL2 CLS CMD ---- ---- DO IEC61850 - NO - RD00DCS NA COUPLERBAY - ---- ---- ○ ---- ○ ----

1090 RD00 AEA 10 XP 22 COUPLER BAY DISCONNECTING SWITCH DS-CPL2 OPEN INDICATION 32 COUPLER BAY DSCN SW DS-CPL2 OPEN NORMAL/ALARM ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----

1091 RD00 AEA 10 XP 23 COUPLER BAY DISCONNECTING SWITCH DS-CPL2 CLOSED INDICATION 30 COUPLER BAY DSCN SW DS-CPL2 CS NORMAL/ALARM ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----


1092 RD00 AEA 10 XP 24 COUPLER BAY CB FAILURE PROT. OPR 32 COUPLER BAY CB FAILURE PROT. OPR NORMAL/ALARM ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1094 RD00 AEA 10 XP 26 COUPLER BAY BVTA MCB TRIP 25 COUPLER BAY BVTA MCB TRIP OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1095 RD00 AEA 10 XP 27 COUPLER BAY BVTB MCB TRIP 25 COUPLER BAY BVTB MCB TRIP OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1096 RD00 AEA 10 XP 28 COUPLER BAY BAY IN SUPERVISORY MODE 28 COUPLER BAY Supervisory Mode OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----

1097 RD00 AEA 10 XP 29 COUPLER BAY BAY IN LOCAL MODE 22 COUPLER BAY Local Mode OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ---- ○ ----


1098 RD00 AEA 10 XP 30 COUPLER BAY DC SUPPLY (C1) FAILURE 31 COUPLER BAY DC Supply (C1) Fail NORMAL/ALARM ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ---- ---- ---- ○ ----
(P1)

1099 RD00 AEA 10 XP 31 COUPLER BAY DC (P1 OR P2) LOSE 28 COUPLER BAY DC (P1orP2) Lose OFF/ON ---- DI IEC61850 - NO - COUPLERBAY NA RD00DCS - ○ ---- ---- ○ ----
(P1)
Send RD01CJJ10GH001YB14
1144 RD01 AEA 10 YP 37 U1 LOAD FREQUENCY REQUEST ON COMMAND 24 U1 LOAD FREQ. REQUEST ON ---- ---- DO IEC61850 - NO - RTU NA RD00DCS - ○ ---- ---- ---- ○ ----
DROOP ON COMMAND
Send RD01CJJ10GH001YB15
1145 RD01 AEA 10 YP 38 U1 LOAD FREQUENCY REQUEST OFF COMMAND 25 U1 LOAD FREQ. REQUEST OFF ---- ---- DO IEC61850 - NO - RTU NA RD00DCS - ○ ---- ---- ---- ○ ----
DROOP OFF COMMAND
Send RD01CHA10GH001XQ07
1146 RD01 MKA 10 YN 01 GENERATOR U1 ACTIVE POWER 21 U1 GROSS ACTIVE POWER 0-60 MW AO IEC61850 - - - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
ACTIVE POWER
Send RD01CHA10GH001XQ08
1147 RD01 MKA 10 YN 02 GENERATOR U1 GROSS REACTIVE POWER 23 U1 GROSS REACTIVE POWER 0-60 MVAR AO IEC61850 - - - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
REACTIVE POWER
Send RD01CJJ10GH001XQ03
1150 RD01 MKA 10 YN 03 U1 REAL POWER SET POINT 15 U1 SET POINT MW 0-60 MW AO IEC61850 - - - RD00DCS NA RTU - ○ ---- ---- ---- ○ ----
65P SET POINT
1151 RD01 MKA 10 YN 04 U1 MAX POWER VARIATION SET POINT 22 U1 SET POINT MAX POWER 0-60 MW AO IEC61850 - - - RD00DCS NA RTU - ○ ---- ---- ---- ○ ---- NOT AVAIRABLE IN DCS
Send Middle select value of
1152 RD01 MKA 10 YN 05 GENERATOR U1 VOLTAGE 20 U1 GENERATOR VOLTAGE 0-15 kV AO IEC61850 - - - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
RD01CHA10GH001XQ04 &
Sent RD01CHA10GH001XG10,
1153 RD01 MKA 10 XP 01 GENERATOR U1 TRIP 17 U1 GENERATOR TRIP ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
RD01CHA10GH001XG11
1154 RD01 MKA 10 XP 02 U1 LOAD FREQUENCY REQUEST ON INDICATION 24 U1 LOAD FREQ. REQUEST ON ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ---- NOT AVAILABLE IN DCS

1155 RD01 MKA 10 XP 03 U1 LOAD FREQUENCY REQUEST OFF INDICATION 25 U1 LOAD FREQ. REQUEST OFF ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ---- NOT AVAILABLE IN DCS

1156 RD01 MKA 10 XP 04 U1 LOAD FREQUENCY AVAILABLE INDICATION 23 U1 LOAD FREQ. AVAILABLE ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ---- NOT AVAILABLE IN DCS
Send RD01CJJ10GH001XG12
1158 RD01 MKA 10 XP 06 U1 LOAD FREQUENCY CONTROL ON INDICATION 24 U1 LOAD FREQ. CONTROL ON ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
DROOP ON INDICATION
1159 RD01 MKA 10 XP 07 U1 LOAD FREQUENCY CONTROL OFF INDICATION 25 U1 LOAD FREQ. CONTROL OFF ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ---- NOT AVAILABLE IN DCS

1160 RD01 MKA 10 XP 08 U1 LOAD FREQUENCY CONTROL FAILURE INDICATION 29 U1 LOAD FREQ. CONTROL FAILURE ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ---- NOT AVAILABLE IN DCS
Send RD01CJJ10GH001XG14
1161 RD01 MKA 10 XP 09 U1 POWER SET ON INDICATION 15 U1 POWER SET ON ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
NOT HPIPC MODE
Send RD01CJJ10GH001XG14
1162 RD01 MKA 10 XP 10 U1 POWER SET OFF INDICATION 16 U1 POWER SET OFF ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
HPIPC MODE
Send RD01CJJ10GH001XG12
1163 RD01 MKA 10 XP 11 U1 FREE ACTING GOVERNOR ACTIVE INDICATION 26 U1 FREE ACTIVE GOV. ACTIVE ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
DROOP ON INDICATION
Send RD01CJJ10GH001XG19
1164 RD01 MKA 10 XP 12 U1 AUTOMATIC VOLTAGE REGULATOR ACTIVE INDICATION 13 U1 AVR ACTIVE ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
AVR MODE
Semd RD01CJJ10GH001YB40
1165 RD01 MKA 10 XP 13 U1 AUTOMATIC POWER FACTOR REGULATOR ACTIVE INDICATION 13 U1 AQR ACTIVE ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
APfR MODE
Send RD02CJJ10GH001YB14
1166 RD02 AEA 10 YP 37 U2 LOAD FREQUENCY REQUEST ON COMMAND 24 U2 LOAD FREQ. REQUEST ON ---- ---- DO IEC61850 - NO - RTU NA RD00DCS - ○ ---- ---- ---- ○ ----
DROOP ON COMMAND
Send RD02CJJ10GH001YB15
1167 RD02 AEA 10 YP 38 U2 LOAD FREQUENCY REQUEST OFF COMMAND 25 U2 LOAD FREQ. REQUEST OFF ---- ---- DO IEC61850 - NO - RTU NA RD00DCS - ○ ---- ---- ---- ○ ----
DROOP OFF COMMAND
Send RD02CHA10GH001XQ07
1168 RD02 MKA 10 YN 01 GENERATOR U2 ACTIVE POWER 21 U2 GROSS ACTIVE POWER 0-60 MW AO IEC61850 - - - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
ACTIVE POWER
Send RD02CHA10GH001XQ08
1169 RD02 MKA 10 YN 02 GENERATOR U2 GROSS REACTIVE POWER 23 U2 GROSS REACTIVE POWER 0-60 MVAR AO IEC61850 - - - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
REACTIVE POWER
3.DCS IO LIST FOR COMMUNICATION
3-8.SWITCH YARD

ALARM ILD or IBD


NC/NO DCS APPLICATION ALARM SETPOINT
SIGNAL RETURN
No. Tag No. DESCRIPTION SERVICE RANGE UNIT SIGNAL RAITING PULSE/ FROM THROUGH TO DIAGRAM REMARKS
TYPE DEAD
LATCH SHEET NO IND ANN CONT ATS LOG SOE
within 32 Chara BAND
Send RD02CJJ10GH001XQ03
1172 RD02 MKA 10 YN 03 U2 REAL POWER SET POINT 15 U2 SET POINT MW 0-60 MW AO IEC61850 - - - RD00DCS NA RTU - ○ ---- ---- ---- ○ ----
65P SET POINT
1173 RD02 MKA 10 YN 04 U2 MAX POWER VARIATION SET POINT 22 U2 SET POINT MAX POWER 0-60 MW AO IEC61850 - - - RD00DCS NA RTU - ○ ---- ---- ---- ○ ---- NOT AVAIRABLE IN DCS
Send Middle select value of
1174 RD02 MKA 10 YN 05 GENERATOR U2 VOLTAGE 20 U2 GENERATOR VOLTAGE 0-15 kV AO IEC61850 - - - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
RD02CHA10GH001XQ04 &
Sent RD02CHA10GH001XG10,
1175 RD02 MKA 10 XP 01 GENERATOR U2 TRIP 17 U2 GENERATOR TRIP ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
RD02CHA10GH001XG11
1176 RD02 MKA 10 XP 02 U2 LOAD FREQUENCY REQUEST ON INDICATION 24 U2 LOAD FREQ. REQUEST ON ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ---- NOT AVAILABLE IN DCS

1177 RD02 MKA 10 XP 03 U2 LOAD FREQUENCY REQUEST OFF INDICATION 25 U2 LOAD FREQ. REQUEST OFF ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ---- NOT AVAILABLE IN DCS

1178 RD02 MKA 10 XP 04 U2 LOAD FREQUENCY AVAILABLE INDICATION 23 U2 LOAD FREQ. AVAILABLE ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ---- NOT AVAILABLE IN DCS
Send RD02CJJ10GH001XG12
1180 RD02 MKA 10 XP 06 U2 LOAD FREQUENCY CONTROL ON INDICATION 24 U2 LOAD FREQ. CONTROL ON ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
DROOP ON INDICATION
1181 RD02 MKA 10 XP 07 U2 LOAD FREQUENCY CONTROL OFF INDICATION 25 U2 LOAD FREQ. CONTROL OFF ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ---- NOT AVAILABLE IN DCS

1182 RD02 MKA 10 XP 08 U2 LOAD FREQUENCY CONTROL FAILURE INDICATION 29 U2 LOAD FREQ. CONTROL FAILURE ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ---- NOT AVAILABLE IN DCS
Send RD02CJJ10GH001XG14
1183 RD02 MKA 10 XP 09 U2 POWER SET ON INDICATION 15 U2 POWER SET ON ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
NOT HPIPC MODE
Send RD02CJJ10GH001XG14
1184 RD02 MKA 10 XP 10 U2 POWER SET OFF INDICATION 16 U2 POWER SET OFF ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
HPIPC MODE
Send RD02CJJ10GH001XG12
1185 RD02 MKA 10 XP 11 U2 FREE ACTING GOVERNOR ACTIVE INDICATION 26 U2 FREE ACTIVE GOV. ACTIVE ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
DROOP ON INDICATION
Send RD02CJJ10GH001XG19
1186 RD02 MKA 10 XP 12 U2 AUTOMATIC VOLTAGE REGULATOR ACTIVE INDICATION 13 U2 AVR ACTIVE ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
AVR MODE
Semd RD02CJJ10GH001YB40
1187 RD02 MKA 10 XP 13 U2 AUTOMATIC POWER FACTOR REGULATOR ACTIVE INDICATION 13 U2 AQR ACTIVE ---- ---- DO IEC61850 - NO - RD00DCS NA RTU - ---- ---- ○ ---- ○ ----
APfR MODE