En Acs800 17 Hwman e Scrres
En Acs800 17 Hwman e Scrres
En Acs800 17 Hwman e Scrres
Hardware Manual
ACS800-17 Drives (55 to 2500 kW / 75 to 2800 hp)
List of related manuals
Drive hardware manuals and guides
ACS800-17 Drives (55 to 2500 kW / 75 to 2800 hp) 3AFE68397260
Hardware Manual
You can find manuals and other product documents in PDF format on the Internet. See section
Document library on the Internet on the inside of the back cover. For manuals not available in the
Document library, contact your local ABB representative.
ACS800-17 manuals
ACS800-17 Drives
55 to 2500 kW (75 to 2800 hp)
Hardware Manual
3AFE68397260 REV E EN
EFFECTIVE: 2013-02-14
Safety instructions
Safety instructions
6
WARNING!
• Only qualified electricians are allowed to install and maintain the drive.
• The main switch on the cabinet door does not remove the voltage from the input
busbars of the drive. Before working on the drive, isolate the whole drive from
the supply.
• Never work on the drive, the motor cable or the motor when main power is
applied. After switching off the input power, always wait for 5 min to let the
intermediate circuit capacitors discharge before you start working on the drive,
the motor or the motor cable. Measure the voltage between terminals UDC+
and UDC- (L+ and L–) with a multimeter (impedance at least 1 Mohm) to
ensure that the drive is discharged before beginning work.
• Do not work on the control cables when power is applied to the drive or to the
external control circuits. Externally supplied control circuits may cause
dangerous voltages to exist inside the drive even when the main power of the
drive is switched off.
• Do not make any insulation or voltage withstand tests on the drive or drive
modules.
• When reconnecting the motor cable, always check that the phase order is
correct.
• When joining shipping splits (if any), check the cable connections at the joints
before switching on the supply voltage.
• Live parts on the inside of the doors are protected against direct contact.
Special attention shall be paid when handling metallic shrouds.
• Do not change the electrical installations of the drive except for the essential
control and power connections. Changes may affect the safety performance or
operation of the drive unexpectedly. All customer-made changes are on the
customer's responsibility.
Note:
• The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
Safety instructions
7
• The Safe torque off function (option +Q968) does not remove the voltage from
the main and auxiliary circuits.
Safety instructions
8
WARNING! Ignoring the following instructions can cause physical injury or death, or
damage to the equipment.
• Use extreme caution when manoeuvring an inverter, supply or filter module that
runs on wheels. The modules are heavy and have a high centre of gravity. They
topple over easily if handled carelessly.
• Do not use the ramp which is supplied with the drive with heights over 50 mm
(the standard plinth height of ABB cabinets). The ramp is designed for a plinth
height of 50 mm.
Support the top and Do not tilt! Extend the support legs outside the
bottom of the module cabinet!
while removing!
max 50 mm
Lift the module by the upper part only Mind your fingers! Keep fingers away from the Support the top and bottom
using the lifting hole(s) at the top! edges of the front flange of the module! of the module while
replacing!
Safety instructions
9
• When removing a module which is equipped with wheels, pull the module
carefully out of the cubicle along the ramp. Make sure that the wires do not
catch. While pulling on the handle, keep a constant pressure with one foot on
the base of the module to prevent the module from falling on its back.
• When replacing a module which is equipped with wheels, push the module up
the ramp and back into the cubicle. Keep your fingers away from the edge of
the module front plate to avoid pinching them between the module and the
cubicle. Also, keep a constant pressure with one foot on the base of the module
to prevent the module from falling on its back.
• Electrically conductive dust inside the unit may cause damage or lead to
malfunction. Make sure that dust from drilling does not enter the drive when
installing.
• Cooling fans may continue to rotate for a while after the disconnection of the
electrical supply.
Grounding
These instructions are intended for all who are responsible for the grounding of the
drive. Incorrect grounding can cause physical injury, death or equipment malfunction
and increase electromagnetic interference.
WARNING!
• Ground the drive, the motor and adjoining equipment to ensure personnel
safety in all circumstances, and to reduce electromagnetic emission and pick-
up.
Safety instructions
10
• Power cable shields are suitable for equipment grounding conductors only
when adequately sized to meet safety regulations.
WARNING!
• Handle the fibre optic cables with care. When unplugging optic cables, always
grab the connector, not the cable itself. Do not touch the ends of the fibres with
bare hands as the fibre is extremely sensitive to dirt. The minimum allowed
bend radius is 35 mm (1.4 in.).
Safety instructions
11
Operation
These warnings are intended for all who plan the operation of the drive or operate
the drive. Ignoring the instructions can cause physical injury or death or damage the
equipment.
WARNING!
• Before adjusting the drive and putting it into service, make sure that the motor
and all driven equipment are suitable for operation throughout the speed range
provided by the drive. The drive can be adjusted to operate the motor at
speeds above and below the speed provided by connecting the motor directly
to the power line.
• Do not activate automatic fault reset functions of the Standard Control Program
if dangerous situations can occur. When activated, these functions will reset
the drive and resume operation after a fault.
• Do not control the motor with the disconnecting device (means); instead, use
the control panel keys and , or commands via the I/O board of the drive.
The maximum allowed number of charging cycles of the DC capacitors (i.e.
power-ups by applying power) is five in ten minutes.
• Do not use the Prevention of unexpected start-up function (option +Q950) for
stopping the drive when the inverter unit(s) is running. Give a Stop command
instead.
• The Safe torque off function (option +Q968) can be used for stopping the drive
in emergency stop situations. In the normal operating mode, use the Stop
command instead.
Note:
• If an external source for start command is selected and it is ON, the drive (with
Standard Control Program) will start immediately after fault reset unless the
drive is configured for 3-wire (a pulse) start/stop.
• When the control location is not set to Local (L not shown in the status row of
the display), the stop key on the control panel will not stop the drive. To stop
the drive using the control panel, press the LOC/REM key and then the stop
key .
Safety instructions
12
WARNING! Do not work on the drive when the permanent magnet motor is rotating.
Also when the supply power is switched off, a rotating permanent magnet motor
feeds power to the intermediate circuit of the drive and also the supply connections
become live (even when the inverter is stopped!).
Operation
Do not run the motor above the rated speed. Motor overspeed leads to overvoltage
which may result in explosion of the capacitors in the intermediate circuit of the drive.
Safety instructions
13
Table of contents
Safety instructions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Usage of warnings and notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fibre optic cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Permanent magnet motor drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Inverter control program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table of contents
The ACS800-17
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
The ACS800-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Cabinet line-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Frame R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Frame R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Frame R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Swing-out frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Cabling direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Single-line circuit diagram of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Operation principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Line-side converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
AC voltage and current waveforms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Motor-side converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Frame R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Frame R7 and up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Control interfaces of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Table of contents
14
Mechanical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Required tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Moving the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
…by crane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
…by fork-lift or pallet truck . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
…on rollers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Laying the unit on its back . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Final placement of the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Fastening the cabinet to the floor (Non-marine units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Clamping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Holes inside the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Fastening the unit to the floor and wall (Marine units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Joining the shipping splits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Connecting the DC busbars and the PE busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
DC busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
PE busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Cable conduit in the floor below the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Cooling air intake through bottom of cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Electric welding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Table of contents
15
Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Option coding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Checking the insulation of the assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Supply cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Motor and motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
IT (ungrounded) systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
EMC filter +E202 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
EMC filter +E200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
EMC filter +E210 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Input power connection – Frame R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Input power connection – Frame R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Table of contents
16
Table of contents
17
Maintenance
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Reduced run capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Checking and replacing the air filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Quick connectors (Frame R8i and up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Cooling fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Supply/Inverter module cooling fan replacement (Frame R6) . . . . . . . . . . . . . . . . . . . . . . . 118
Supply/Inverter module cooling fan replacement (Frame R7i) . . . . . . . . . . . . . . . . . . . . . . . 119
LCL filter module cooling fan replacement (Frame R7i) . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Supply and inverter module cooling fan replacement (Frame R8i and up) . . . . . . . . . . . . . 121
Module fan replacement procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
LCL filter cooling fan replacement (Frame R8i and up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
LCL filter fan replacement procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Cabinet fan replacement (Frame R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Cabinet fan replacement (Frame R8i with IP21-42) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Cabinet fan replacement (Frame 2xR8i and up with IP21-42) . . . . . . . . . . . . . . . . . . . . . . . 124
Cabinet fan replacement (Frame R8i and up with IP54) . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Heatsinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Reforming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Capacitor replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Table of contents
18
Fault tracing
Faults and warnings displayed by the CDP-312R Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . .133
Warning/Fault message from unit not being monitored by control panel . . . . . . . . . . . . . . .133
Conflicting ID numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
LEDs of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
Technical data
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135
IEC ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
Altitude derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
NEMA ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
ACS800-17 frame sizes and power module types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
AC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
DC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .142
Input power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .143
Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Degrees of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .149
Tightening torques for power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150
Applicable standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151
Compliance with the European Low Voltage Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151
Compliance with the European EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151
Compliance with the European Machinery directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151
Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .152
Compliance with EN 61800-3:2004 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
Category C2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
Category C3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
Category C4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .155
“C-tick” marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .155
Table of contents
19
Dimensions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Cabinet line-ups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
2×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
3×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
4×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
5×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
6×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Frame R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Frame R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Frame R7i with +E202/+E205/+H359 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Frame R7i, marine construction (+C121) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Frame R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Frame R8i with +E202/+H359 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Frame 2×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Frame 3×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Frame 4×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Frame 5×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Frame 6×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Further information
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Table of contents
20
Table of contents
21
Target audience
This manual is intended for people who plan the installation, install, commission, use
and service the drive. Read the manual before working on the drive. The reader is
expected to know the fundamentals of electricity, wiring, electrical components and
electrical schematic symbols.
The manual is written for readers worldwide. Both SI and imperial units are shown.
Special US instructions for installations within the United States that must be
installed per the National Electrical Code and local codes are marked with (US).
Contents
The chapters of this manual are briefly described below.
Safety instructions gives safety instructions for the installation, commissioning,
operation and maintenance of the drive.
About this manual introduces this manual.
The ACS800-17 describes the drive.
Mechanical installation instructs how to move, place and mount the drive.
Planning the electrical installation provides advice on motor and cable selection, the
protective functions of the drive, and cable routing.
Electrical installation describes the cabling and wiring of the drive.
Motor control and I/O board (RMIO) shows external control connections to the motor
control and I/O board and its specifications.
Installation checklist and start-up helps in checking the mechanical and electrical
installation of the drive.
Maintenance contains preventive maintenance instructions.
Fault tracing contains troubleshooting instructions.
Technical data contains the technical specifications of the drive, e.g. ratings, frame
sizes and technical requirements, provisions for fulfilling the requirements for CE
and other markings and warranty policy.
Dimensions contains information on the dimensions of the drive.
Task See
Check the insulation of the motor and the motor Electrical installation: Checking the insulation of
cable. the assembly
Connect the power cables. Connect the control and Mechanical installation, Planning the electrical
the auxiliary control cables. installation, Electrical installation
Inquiries
Address any inquiries about the product to the local ABB representative, quoting the
type code and serial number of the unit. If the local ABB representative cannot be
contacted, address inquiries to ABB Oy, AC Drives, PO Box 184, 00381 Helsinki,
Finland.
AGPS Gate driver power supply board. An optional board within drives, used to
implement the Prevention of unexpected start-up function.
ASTO An optional board within drives, used to implement the Safe torque off
function.
Torque
II I
Speed
III IV
Frame (size) Relates to the construction type of the component in question. For
example, several drive types with different power ratings may have the
same basic construction, and this term is used in reference to all those
drive types.
With the ACS800-17, the frame size of the drive indicates the quantity and
frame size of the inverter modules, e.g. “2×R8i”.
To determine the frame size of a drive type, see the rating tables in
chapter Technical data.
Term/Abbreviation Explanation
IGBT supply module Bidirectional IGBT bridge and related components enclosed inside a metal
frame or enclosure. Intended for cabinet installation. Used as the supply
module in regenerative and low-harmonic drives.
Inverter module Inverter bridge, related components and drive DC link capacitors enclosed
inside a metal frame or enclosure. Intended for cabinet installation.
Line-side converter A converter that is connected to the supply network and is capable of
transferring energy from the network to the DC link of the drive, or from
the DC link of the drive to the network. With ACS800-17 drives of frame
size R8i and above, the line-side converter is also called the (IGBT)
supply unit or the ISU.
Motor-side converter A converter that is connected to the motor and controls the motor
operation. With ACS800-17 drives of frame size R8i and above, the
motor-side converter is also called the inverter unit or INU.
PPCS Power Plate Communication System; a protocol used in the optical fibre
link that controls the output semiconductors of an inverter module.
RDCU Drive control unit. The RDCU is a separate unit consisting of an RMIO
board built in a plastic housing.
RMIO Motor control and I/O board. Contains the principal inputs and outputs of
the drive. The RMIO is contained within the RDCU drive control unit.
The ACS800-17
The ACS800-17
The ACS800-17 is a four-quadrant, cabinet-mounted drive for controlling
asynchronous AC induction motors and generators, and permanent magnet
synchronous motors and generators.
Cabinet line-up
The drive consists of one or more cubicles that contain the supply and motor
terminals, 1 to 6 IGBT supply module(s) forming the line-side converter, 1 to 6
inverter modules forming the motor-side converter, and optional equipment. (Frame
R6 drives employ an integrated supply/inverter module.) The actual arrangement of
the cubicles varies from type to type and the selected options. See also chapter
Dimensions for the different line-up variations.
The ACS800-17
28
Frame R6
The picture below shows the main components of a frame R6 drive with the door
open, and with the swing-out frame closed (left) and open (right).
3 3
No. Description
1 Swing-out frame (see page 31)
12 12 2 Cable entries for power and control cables (bottom
cable entry/exit models)
3 Cable entries for power and control cables (top cable
8 10 8 10 entry/exit models)
4 Switch fuse
4 4
5 Auxiliary voltage transformer
6 Integrated line-side/motor-side converter module
7 Input terminals (bottom cable entry/exit models)
8 Input terminals (top cable entry/exit models)
9 Output terminals (bottom cable entry/exit models)
10 Output terminals (top cable entry/exit models)
6 11 Control unit (RDCU) for motor-side converter
12 Cabinet cooling fan
11
1
7 9
5 5
2 2
The ACS800-17
29
Frame R7i
The picture below shows the main components of a frame R7i drive with the door
and the swing-out frame open.
No. Description
1 Swing-out frame (see page 31) (not shown). The drive
control units for both converter modules are installed on
the swing-out frame.
2 Cable entries for power and control cables (bottom
cable entry/exit models)
8 6 1 3 Cable entries for power and control cables (top cable
entry/exit models)
4 Switch fuse
5 Auxiliary voltage transformer
6 Line-side converter module
10 7 LCL filter
8 Motor-side converter module
9 Input terminals
10 Output terminals
9 4
5 7
The ACS800-17
30
Frame R8i
The picture below shows the main components of a frame R8i drive with the doors
open.
No. Description
1 Swing-out frame (see picture on page 31)
2 Supply unit controller (RDCU)
4 3 Inverter unit controller (RDCU)
5 4 Switch-disconnector*
8 5 Input contactor*
6 LCL filter
7 IGBT supply module
2
8 Intermediate DC link
3
9 Inverter module
6 7 9 10 Cooling fan for LCL filter
11 Cooling fan for IGBT supply module
12 Cooling fan for inverter module
13 Auxiliary voltage transformer (accessible by opening
14 the swing-out frame)
1 14 Auxiliary voltage circuitry (relays etc.)
13 *In larger drives, an air circuit breaker is used instead of the
switch-disconnector/contactor combination.
10 11 12
The ACS800-17
31
Swing-out frame
The swing-out frame provides space for the control circuitry of the drive as well as
optional electrical equipment. The frame can be opened by removing the locking
screws (arrowed in the picture below) and moving the swing-out frame aside.
Depending on the frame size of the drive, the actual equipment of the drive may
differ from what is depicted.
The ACS800-17
32
The following is a generic device layout diagram for the swing-out frame (drive frame
size R8i). The diagram is also attached to the inside of the cubicle door, with
installed devices marked. Refer to the circuit diagrams delivered with the drive for
device designations.
The ACS800-17
33
Cabling direction
The drawings below show the available cabling directions of the drive.
Frame size R6
6 3 Description
2 5 1 Input/Motor output – Bottom entry
IP21-42 IP54
2 Input/Motor output – Top entry (IP21-42)
3 Input/Motor output – Top entry (IP54)
4 Signal cable input/output – Bottom entry
5 Signal cable input/output – Top entry (IP21-42)
6 Signal cable input/output – Top entry (IP54)
1 4 1 4
Description
2 4 1 Input/Motor output – Bottom entry
2 Input/Motor output – Top entry
3 Signal cable input/output – Bottom entry
4 Signal cable input/output – Top entry
1 3
The ACS800-17
34
Description
2
10 11
4 6 8 A Input/output cubicle
B Supply and inverter unit cubicle
C Common motor terminal cubicle*
2
10 Description
4 6
A Auxiliary control cubicle
B Incoming cubicle
C Inverter unit cubicle
D Common motor terminal cubicle (optional)
The ACS800-17
35
DC bus
3~
M
M
400 V AC
M
400 V AC
Charging
M
circuit
M
400 V AC
230/400 V AC
Main
Supply
The ACS800-17
36
Operation principle
The line-side and motor-side converters have their own RDCU control units and
control programs. The parameters of each program can be viewed and changed
using one control panel. The converter to be controlled can be selected using the
control panel; see section Controls below.
Line-side converter
The line-side converter rectifies three-phase AC current to direct current for the
intermediate DC link of the drive. The intermediate DC link is further supplying the
motor-side converter that runs the motor.
The LCL filter suppresses the AC voltage distortion and current harmonics.
The IGBT supply module is a four-quadrant switching-mode converter, i.e. the power
flow through the converter is reversible. By default, the converter controls the DC link
voltage to the peak value of the line-to-line voltage. The DC voltage reference can be
set also higher by a parameter. The control of the IGBT power semiconductors is
based on the Direct Torque Control (DTC) method also used in the motor control of
the drive. Two line currents and the DC link voltage are measured and used for the
control.
AC input Intermediate
DC link
The ACS800-17
37
Motor-side converter
The motor control is based on the Direct Torque Control (DTC) method. Two phase
currents and DC link voltage are measured and used for the control. The third phase
control is measured for earth fault (ground fault) protection.
Frame R6
The motor-side converter is controlled by an RDCU drive control unit located in the
integrated line-side/converter-side module.
Frame R7 and up
The motor-side converter is controlled by an RDCU drive control unit located in the
swing-out frame of the cabinet. The RDCU is connected to the inverter module(s) by
a fibre optic link, distributed through an optical branching unit. In the inverter
modules, the optic link connects to the AINT board, the terminals of which are
accessible through a hole on the front panel of the module.
The ACS800-17
38
Parameter setting and diagnostics through
CDP 312R Control Panel (and related
accessories).
Note: By default, the Control Panel of the
Controls
drive is set to control the inverter unit.
The ACS800-17
Drive Control Unit Drive Control Unit
(RDCU) (RDCU)
E
Y
or pulse encoder interface
(RTAC)
S TO P
Input power
= ~ To motor
~ =
Supply unit Inverter unit
The following diagram shows the control interfaces and I/O options of the drive.
39
Door switches
Main switch-disconnector (Q1 in frame size R6 to R8i)
The switch-disconnector handle switches the main and auxiliary voltages to the drive
on and off.
Air circuit breaker (Q1 in frame size 2×R8i and up)
The air circuit breaker controls the main supply voltage (phases L1, L2 and L3). For
more information on using the breaker, refer to its manual.
WARNING! Opening the air circuit breaker will not switch off the auxiliary voltages of
the drive.
The ACS800-17
40
Control panel
A control panel (type CDP-312R) is installed on the door of the drive. The CDP-312R
is the user interface of the supply unit (line-side converter) and the inverter unit
(motor-side converter) of the drive, providing the essential controls such as Start/
Stop/Direction/Reset/Reference, and the parameter settings for the units’ control
programs. More information on using the panel can be found in the Firmware Manual
delivered with the drive.
The control panel is wired to both the supply unit and the inverter unit using a
Y-splitter. The unit that is currently being controlled is indicated by the drive name on
the drive display; the suffix “MR” denotes inverter unit, “LR” denotes supply unit. The
control is switched between the units as follows:
To control the supply unit…
Step Action Press… Display (example)
IXXR7xxx
ID-NUMBER 2
3. To verify the change to the line-side converter and display 2 -> 380.0 V
the warning or fault text ACT ISU 800 0490_3LR
*** FAULT ***
DC OVERVOLT (3210)
WARNING! The drive does not stop by pressing the control panel Stop key in local
control mode.
ASXR7xxx
ID-NUMBER 1
The ACS800-17
41
AI3
FIELD BUS
The ACS800-17
42
Type code
The type code of the drive is indicated on the type designation label, attached on the
cabinet door. The type code contains information on the specifications and
configuration of the drive. The first digits from left express the basic configuration
(e.g. ACS800-17-0490-3). The optional selections are given thereafter, separated by
+ signs (e.g. +E202). The main selections are described below.
Note: The information below is for quick reference only and does not contain all
conditions and details. For more information, refer to ACS800 Ordering Information
(code: 64556568), available through ABB representatives.
Selection Alternatives
Product series ACS800 product series
Type 17 = cabinet-mounted
Default configuration: IP21 (UL Type 1); main switch/disconnector with aR-
type AC fuses; line contactor (optional for frame R6); 230 V AC auxiliary
voltage; RDCO-03 DDCS Communication Option; CDP-312R Control Panel;
EMC/RFI filtering for 2nd Environment (except frame R6); common mode
filtering (except frame R6); Standard Control Program; bottom entry/exit of
cables; coated circuit boards; set of English manuals.
Size Refer to Technical data: IEC ratings.
Voltage range 3 = 380/400/415 V AC
(nominal rating in bold) 5 = 380/400/415/440/460/480/500 V AC
7 = 525/575/600/690 V AC
+ options
I/O options Refer to ACS800 Ordering Information (code: 64556568 [English]).
Fieldbus adapter
Control program
Degree of protection B053 = IP22 (UL Type 1)
B054 = IP42 (UL Type 1)
B055 = IP54 (UL Type 12)
B059 = IP54R with connection to air outlet duct
Construction C121 = Marine construction (reinforced mechanical parts and fastening,
marking of conductors [A1], door handles, self-extinctive materials)
C129 = UL Listed
C134 = CSA Approved
Filters E200 = EMC/RFI filtering, Cat. C3, 2nd Environment, TN (grounded) system
(frame R6 only)
E202 = EMC/RFI filtering, Cat. C2, 1st Environment, TN (grounded) system.
Not available for 690 V.
E205 = du/dt filtering
E206 = Sine filter (frames R7i and R8i only) – Not available with +C121 or
+C129.
The ACS800-17
43
Selection Alternatives
Cabling H350 = Bottom entry (with +C129)
H351 = Top entry
H352 = Bottom exit (with +C129)
H353 = Top exit
H356 = DC cable connection busbars
H358 = US/UK gland/conduit plate (steel, 3 mm)
H359 = Common motor terminal cubicle – Frame R8i with +E202 only
H365 = US/UK gland/conduit plate (brass, 6 mm)
Auxiliary voltage G304 = 115 V AC – Standard with +C129 and +C134
Cabinet options G300 = Cabinet heaters (external supply) – Not available with +C129 or
+C134
G307 = Input terminals for external UPS-backed auxiliary voltage
G313 = Output for motor heater (external supply)
G330 = Halogen-free wiring and materials – Not available with +C129 or
+C134
G338 = Wire marking class A1
G339 = Wire marking class A2
G340 = Wire marking class A3
G341 = Wire marking class B1
G342 = Wire marking class C1
Language of manuals Rxxx
Refer to ACS800 Ordering Information (code: 64556568 [English]).
Starter of auxiliary M600 = 1 … 1.6 A (1 pc)
motor fan M601 = 1.6 … 2.5 A (1 pc)
M602 = 2.5 … 4 A (1 pc)
M603 = 4 … 6.3 A (1 pc)
M604 = 6.3 … 10 A (1 pc) – Not for frame R6
M605 = 10 … 16 A (1 pc) – Not for frame R6
Safety features Q950 = Prevention of unexpected start-up (Category 3)
Q951 = Emergency stop, Category 0 (with opening main contactor/breaker)
Q952 = Emergency stop, Category 1 (with opening main contactor/breaker)
Q954 = Earth fault monitoring for IT (ungrounded) system
Q963 = Emergency stop, Category 0 (without opening main contactor/
breaker)
Q964 = Emergency stop, Category 1 (without opening main contactor/
breaker)
Q968 = Safe torque off (STO) with a safety relay
Q971 = ATEX-certified safety function
Special P902 = Customised (specified in Technical appendix on ordering)
P904 = Extended warranty
P913 = Special colour (specified in Technical appendix on ordering)
Selection Alternatives
Product series ACS800 product series
Type 17 = cabinet-mounted
Default configuration: IP21 (UL Type 1); air circuit breaker; 230 V AC
auxiliary voltage; RDCO-03 DDCS Communication Option; CDP-312R
Control Panel; EMC/RFI filtering for 2nd Environment; du/dt filtering; common
mode filtering; Standard Control Program; bottom entry/exit of cables; coated
circuit boards; set of English manuals.
Size Refer to Technical data: IEC ratings.
The ACS800-17
44
Selection Alternatives
Voltage range 3 = 380/400/415 V AC
(nominal rating in bold) 5 = 380/400/415/440/460/480/500 V AC
7 = 525/575/600/690 V AC
+ options
I/O options Refer to ACS800 Ordering Information (code: 64556568 [English]).
Fieldbus adapter
Control program
Degree of protection B053 = IP22 (UL Type 1)
B054 = IP42 (UL Type 1)
B055 = IP54 (UL Type 12)
B059 = IP54R with connection to air outlet duct
Construction C121 = Marine construction (reinforced mechanical parts and fastening,
marking of conductors [A1], door handles, self-extinctive materials)
C129 = UL Listed
C134 = CSA Approved
Filters E202 = EMC/RFI filtering, Cat. C2, 1st Environment, TN (grounded) system.
Note: EMC/RFI filtering for 2nd Environment (+E210) is standard equipment.
E206 = Sine filter – Not available with +C121 or +C129.
Line options F259 = Earthing switch – Not available with +C129
Cabling H350 = Bottom entry (with +C129)
H351 = Top entry
H352 = Bottom exit (with +C129)
H353 = Top exit
H356 = DC cable connection busbars
H358 = US/UK gland/conduit plate (steel, 3 mm)
H359 = Common motor terminal cubicle
H365 = US/UK gland/conduit plate (brass, 6 mm)
Auxiliary voltage G304 = 115 V AC
Cabinet options G300 = Cabinet heaters (external supply) – Not available with +C134
G307 = Input terminals for external UPS-backed auxiliary voltage
G313 = Output for motor heater (external supply)
G317 = Busbar supply conductors
G330 = Halogen-free wiring and materials – Not available with +C129 or
+C134
G338 = Wire marking class A1
G339 = Wire marking class A2
G340 = Wire marking class A3
G341 = Wire marking class B1
G342 = Wire marking class C1
Language of manuals Rxxx
Refer to ACS800 Ordering Information (code: 64556568 [English]).
Starter of auxiliary M602 = 2.5 … 4 A (1, 2 or 4 pcs)
motor fan M603 = 4 … 6.3 A (1, 2 or 4 pcs)
M604 = 6.3 … 10 A (1, 2 or 4 pcs)
M605 = 10 … 16 A (1 or 2 pcs)
M606 = 17 … 25 A (1 pc)
The ACS800-17
45
Selection Alternatives
Safety features Q950 = Prevention of unexpected start-up (Category 3)
Q951 = Emergency Stop, Category 0 (with opening main contactor/breaker)
Q952 = Emergency Stop, Category 1 (with opening main contactor/breaker)
Q954 = Earth fault monitoring for IT (ungrounded) system
Q963 = Emergency Stop, Category 0 (without opening main contactor/
breaker)
Q964 = Emergency Stop, Category 1 (without opening main contactor/
breaker)
Q968 = Safe torque off (STO) with a safety relay
Q971 = ATEX-certified safety function
Special P902 = Customised (specified in Technical appendix on ordering)
P904 = Extended warranty
P913 = Special colour (specified in Technical appendix on ordering)
The ACS800-17
46
The ACS800-17
47
Mechanical installation
General
See chapter Technical data for allowable operating conditions and requirements for
free space around the unit.
The unit should be installed in an upright vertical position.
The floor that the unit is installed on should be of non-flammable material, as
smooth as possible, and strong enough to support the weight of the unit. The floor
flatness must be checked with a spirit level before the installation of the cabinets into
their final position. The maximum allowed deviation from the surface level is 5 mm in
every 3 metres. The installation site should be levelled, if necessary, as the cabinet
is not equipped with adjustable feet.
The wall behind the unit should be of non-flammable material.
Provide the drive with the amount of fresh cooling air given in Technical data.
Note: Very wide cabinet line-ups (> 4200 mm) are delivered as shipping splits.
Required tools
The tools required for moving the unit to its final position, fastening it to the floor and
tightening the connections are listed below.
• crane, fork-lift or pallet truck (check load capacity!); iron bar, jack and rollers
• Pozidrive and Torx (2.5–6 mm) screwdrivers for the tightening of the frame
screws
• torque wrench
• set of wrenches or sockets for joining shipping splits.
Mechanical installation
48
…by crane
Use the steel lifting lugs attached to the top of
the cabinet. Insert the lifting ropes or slings into
the holes of the lifting lugs.
The lifting lugs can be removed (not mandatory)
once the cabinet is in its final position. If the
lifting lugs are removed, the bolts must be
refastened to retain the degree of protection
of the cabinet.
IP54 units
Allowed minimum height of lifting ropes or slings
for IP54 units is 2 metres.
Mechanical installation
49
…on rollers
(Not allowed with Marine versions)
Remove the wooden bottom frame which is part
of the shipment.
Lay the unit on the rollers and move it carefully
until close to its final location.
Remove the rollers by lifting the unit with a
crane, fork-lift, pallet truck or jack as described
above.
Mechanical installation
50
Mechanical installation
51
Before installation
Delivery check
The drive delivery contains:
• drive cabinet line-up
• optional modules (if ordered) installed into the control rack at the factory
• ramp for extracting supply and inverter modules from the cabinet
• hardware manual
• appropriate firmware manuals and guides
• optional module manuals
• delivery documents.
Check that there are no signs of damage. Before attempting installation and
operation, check the information on the type designation label of the drive to verify
that the unit is of the correct type. The label includes an IEC and NEMA rating, C-UL
US, and CSA markings, a type code and a serial number, which allow individual
recognition of each unit. The first digit of the serial number refers to the
manufacturing plant. The next four digits refer to the unit’s manufacturing year and
week respectively. The remaining digits complete the serial number so that there are
no two units with the same serial number.
The type designation label is located on the supply unit door.
Each power module (i.e. supply and inverter module) is also individually labelled.
Mechanical installation
52
Installation procedure
1 See detailed instructions in the following few
pages.
(1) The cabinet can be installed with its back
against a wall, or back-to-back with another unit.
Fasten the unit (or first shipping split) to the floor
A with fastening clamps or through the holes inside
A
the cabinet. See section Fastening the cabinet to
the floor (Non-marine units).
With marine versions, fasten the unit (or first
shipping split) to the floor and wall/roof as
described in section Fastening the unit to the floor
and wall (Marine units).
Note: A clearance of 400 mm minimum above the
basic roof level of the cabinet (see inset on left) is
Top clearances required.
> 320 mm (12.3”)
for fan replace- Note: Leave some space at the left-hand and
ment
right-hand sides of the line-up (A) to allow the
> 400 mm > 400 mm
(15.75”) (15.75”) doors to open sufficiently.
IP22/42 IP54
Note: Any height adjustment must be done before
fastening the units or shipping splits together.
Height adjustment can be done by using metal
shims between the bottom frame and floor.
2
(2) Remove the lifting bars (if present). In marine
units, also replace the lifting lugs with L-profiles
(see below). Use the original bolts to block any
unused holes.
(3) If the line-up consists of shipping splits, fasten
the first split to the second. Each shipping split
includes a joining cubicle where the busbars
connect to the next split.
(4) Fasten the second shipping split to the floor.
(5) Join the DC busbars and the PE busbars.
(6) Repeat steps (2) to (5) for the remaining
3 shipping splits.
Mechanical installation
53
Clamping
Insert the clamps into the twin slots along the front and rear edges of the cabinet
frame body and fasten them to the floor with a bolt. The recommended maximum
distance between the clamps is 800 mm (31.5”).
If there is not enough working space behind the cabinet for mounting, replace the
lifting lugs at the top with L-brackets (not included) and fasten the top of the cabinet
to the wall.
L-bracket
M16 screw
Cabinet top
Mechanical installation
54
L-bracket
M16 screw
25 mm (0.985”)
Cabinet top
Mechanical installation
55
2 3
L-bracket
Mechanical installation
56
Procedure
7 7
• Fasten the front post of the joining section with 7 screws to the front frame post of
the next cubicle.
Mechanical installation
57
• Remove any intermediate or partitioning plates covering the rear posts of the
joining cubicle.
Partitioning
plate
• Fasten the rear post of the joining section with seven screws (below the busbar
joining part) to the rear post of the next cubicle.
• Replace all partitioning plates in the upper part of it after connecting the DC
busbars (see section Connecting the DC busbars and the PE busbar).
Mechanical installation
58
DC busbars
The DC busbar connection is shown below.
1 1 Joint pieces
1
1
PE busbar
The PE busbar runs continuously through the line-up near the floor at the back. The
connection is shown below. No separate nuts are needed.
Mechanical installation
59
Miscellaneous
With heavy
cabinets support
the structural C-
sections from
below.
This area can be used for a
cable conduit
Mechanical installation
60
Input fuse cubicle Diode supply cubicle Inverter cubicle Common motor
Cubicle width: 400 mm Cubicle width: 700 mm Cubicle width: 600 mm terminal cubicle
Air inlet size: Air inlet size: Air inlet size: (No air inlet required)
350 × 400 mm 650 × 505 mm 550 × 400 mm
Notes:
• The plinth of the cabinet must be supported all round.
• The air duct must be able to supply a sufficient volume of cooling air. The
minimum air flow values are given in the Technical data section of the Hardware
Manual.
• The cubicles of diode supply units require a larger air inlet area than other
cubicles.
• Some cubicles (mainly those without active, heat-generating components) require
no air inlet.
Mechanical installation
61
Electric welding
It is not recommended to fasten the cabinet by welding.
Cabinets without flat bars at the base
• Connect the return conductor of the welding equipment to the cabinet frame at
the bottom within 0.5 metres of the welding point.
Cabinets with flat bars at the base
• Weld only the flat bar under the cabinet, never the cabinet frame itself.
• Clamp the welding electrode onto the flat bar about to be welded or onto the floor
within 0.5 metres of the welding point.
WARNING! If the welding return wire is connected improperly, the welding circuit
may damage electronic circuits in the cabinet. The thickness of the zinc coating of
the cabinet frame is 100 to 200 micrometres; on the flat bars the coating is
approximately 20 micrometres. Ensure that the welding fumes are not inhaled.
Mechanical installation
62
Mechanical installation
63
4. Consult the motor manufacturer before using a motor in a drive system where the
motor nominal voltage differs from the AC power source voltage.
5. Ensure that the motor insulation system withstands the maximum peak voltage in
the motor terminals. See the Requirements table below for the required motor
insulation system and drive filtering.
Example 1: When the supply voltage is 440 V and the drive has a diode supply
and operates in motor mode only, the maximum peak voltage at the motor
terminals can be approximated as follows: 440 V × 1.35 × 2 = 1190 V. Check that
the motor insulation system withstands this voltage.
Example 2: When the supply voltage is 440 V and the drive is equipped with an
IGBT supply, the maximum peak voltage in the motor terminals can be
approximated as follows: 440 V × 1.41 × 2 = 1241 V. Check that the motor
insulation system withstands this voltage.
Requirements table
The following table shows how to select the motor insulation system and when an
optional ABB du/dt filter, insulated N-end (non-driven end) motor bearings and ABB
common mode filters are required. The motor manufacturer should be consulted
regarding the construction of the motor insulation and additional requirements for
explosion-safe (EX) motors. Failure of the motor to fulfil the following requirements
or improper installation may shorten motor life or damage the motor bearings.
Motor type Nominal mains Requirement for
voltage (AC line
Motor insulation ABB du/dt filter, insulated N-end bearing and ABB common mode
voltage) system filter
Manufacturer
Abbreviation Definition
UN nominal voltage of the supply network
ÛLL peak line-to-line voltage at motor terminals which the motor insulation must withstand
PN motor nominal power
du/dt du/dt filtering at the output of the drive (+E205)
CMF common mode filtering (+E208)
N N-end bearing: insulated motor non-driven end bearing
n.a. Motors of this power range are not available as standard units. Consult the motor manufacturer.
Note 8: Calculating the rise time and the peak line-to-line voltage
The peak line-to-line voltage at the motor terminals generated by the drive as well as the voltage rise
time depend on the cable length. The requirements for the motor insulation system given in the table
are “worst case” requirements covering installations with 30-metre and longer cables. The rise time can
be calculated as follows: t = 0.8 · ÛLL/(du/dt). Read ÛLL and du/dt from the diagrams below. Multiply
the values of the graph by the supply voltage (UN). In case of drives with an IGBT supply unit or resistor
braking, the ÛLL and du/dt values are approximately 20% higher.
3.0 3.0
ÛLL/U N ÛLL/U N
2.5 2.5
2.0 2.0
1.5 1.5
du/dt
------------- (1/μs)
UN
1.0 1.0
du/dt
------------- (1/μs)
UN
0.5 0.5
0.0 0.0
100 200 300 100 200 300
Cable length (m) Cable length (m)
With du/dt Filter (R6 and R7i) With du/dt Filter (R8i and nxR8i)
5.5
5.0
du/dt
------------- (1/μs)
4.5 UN
4.0
3.5
3.0
ÛLL/UN
2.5
2.0
1.5
1.0
100 200 300
The drive protects the motor cable and the motor in a short-circuit situation when the
motor cable is dimensioned according to the nominal current of the drive.
WARNING! The Prevention of unexpected start-up function does not disconnect the
voltage of the main and auxiliary circuits from the drive. Therefore maintenance work
on electrical parts of the drive can only be carried out after isolating the drive system
from the main supply.
WARNING! The Safe torque off function does not disconnect the voltage of the main
and auxiliary circuits from the drive. Therefore maintenance work on electrical parts
of the drive or the motor can only be carried out after isolating the drive system from
the main supply.
Note: It is not recommended to stop the drive by using the Safe torque off function. If
a running drive is stopped by using the Safe torque off function, the drive will stop by
coasting. If this causes danger or is not acceptable, the drive and machinery must be
stopped using the appropriate stopping mode before using the Safe torque off
function.
Note concerning permanent magnet motor drives in case of a multiple IGBT
power semiconductor failure: In spite of the activation of the Safe torque off
function, the drive system can produce an alignment torque which maximally rotates
the motor shaft by 180/p degrees. p denotes the pole pair number.
General rules
Dimension the supply (input power) and motor cables according to local
regulations:
• The cable must be able to carry the drive load current. See chapter Technical
data for the rated currents.
• The cable must be rated for at least 70 °C maximum permissible temperature of
conductor in continuous use. For US, see Additional US requirements on
page 74.
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
• 600 V AC cable is accepted for up to 500 V AC. For 690 V AC rated equipment,
the rated voltage between the conductors of the cable should be minimum 1 kV.
We recommend shielded symmetrical multicore cables for input cabling. Single-core
cables are also allowed, but unshielded single-core cables are not on IT
(ungrounded) networks.
Symmetrical shielded cable must be used for motor cabling; see section Alternative
power cable types on page 73.
Note: When continuous conduit is employed, shielded cable is not required.
To operate as a protective conductor, the shield conductivity must be as follows
when the protective conductor is made of the same metal as the phase conductors:
Cross-sectional area of the phase Minimum cross-sectional area of the
conductors corresponding protective conductor
S (mm2) Sp (mm 2)
S < 16 S
16 < S < 35 16
35 < S S/2
PE conductor
and shield Shield Shield
PE
PE
Shield
(PE)
Not allowed for motor cabling: Separate cables for Not allowed for motor cabling with phase
each phase and PE conductor cross-section larger than 10 mm 2 (motor
power > 30 kW): Asymmetric cable
PE
Shield
Cable core
Additional US requirements
Type MC continuous corrugated aluminum armor cable with symmetrical grounds or
shielded power cable must be used for the motor cables if metallic conduit is not
used. For the North American market, 600 V AC cable is accepted for up to
500 V AC. 1000 V AC cable is required above 500 V AC (below 600 V AC). For
drives rated over 100 amperes, the power cables must be rated for 75 °C (167 °F).
Conduit
Where conduits must be coupled together, bridge the joint with a ground conductor
bonded to the conduit on each side of the joint. Bond the conduits also to the drive
enclosure. Use separate conduits for input power, motor, brake resistors, and control
wiring. When conduit is employed, type MC continuous corrugated aluminum armor
cable or shielded cable is not required. A dedicated ground cable is always required.
Note: Do not run motor wiring from more than one drive in the same conduit.
Armored cable / shielded power cable
6-conductor (3 phases and 3 ground) type MC continuous corrugated aluminum
armor cable with symmetrical grounds is available from the following suppliers (trade
names in parentheses):
• Anixter Wire & Cable (Philsheath)
• BICC General Corp (Philsheath)
• Rockbestos Co. (Gardex)
• Oaknite (CLX).
Shielded power cables are available from Belden, Lapp Kabel (ÖLFLEX) and Pirelli,
among others.
If there are power factor compensation capacitors in parallel with the 3-phase input
of the drive:
1. Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
damage the drive.
2. If capacitor load is increased/decreased step by step when the AC drive is
connected to the power line, ensure that the connection steps are low enough not
to cause voltage transients that would trip the drive.
3. Check that the power factor compensation unit is suitable for use in systems with
AC drives i.e. harmonic generating loads. In such systems, the compensation unit
should typically be equipped with a blocking reactor or harmonic filter.
WARNING! Never connect the supply power to the drive output terminals U2, V2
and W2. If frequent bypassing is required, employ mechanically connected switches
or contactors. Mains (line) voltage applied to the output can result in permanent
damage to the unit.
Relay outputs
Varistor
RO (NC)
RO (C)
230 V AC
RO (NO)
RC filter
RO (NC)
230 V AC RO (C)
RO (NO)
Diode
RO (NC)
24 V DC RO (C)
RO (NO)
a b
Double-shielded twisted Single-shielded twisted
pair cable multipair cable
Relay cable
The cable type with braided metallic screen (e.g. ÖLFLEX by Lapp Kabel) has been
tested and approved by ABB.
WARNING! IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
conductive or conductive but not connected to the protective earth.
To fulfil this requirement, the connection of a thermistor (and other similar
components) to the digital inputs of the drive can be implemented in three alternate
ways:
1. There is double or reinforced insulation between the thermistor and live parts of
the motor.
2. Circuits connected to all digital and analogue inputs of the drive are protected
against contact and insulated with basic insulation (the same voltage level as the
drive main circuit) from other low voltage circuits.
3. An external thermistor relay is used. The insulation of the relay must be rated for
the same voltage level as the main circuit of the drive. For connection, see the
Firmware Manual.
Motor cable
Drive
min 300 mm (12 in.)
Power cable
Control cables
Electrical installation
WARNING! Only qualified electricians are allowed to carry out the work described in
this chapter. Follow the Safety instructions on the first pages of this manual. Ignoring
the safety instructions can cause injury or death.
Option coding
Some instructions contained within this chapter are intended for drives equipped
with certain options, marked with “plus codes” (e.g. +H359). The options included in
a drive are listed on its type code label. An option code listing is included in this
manual on page 42.
Electrical installation
82
Before installation
U1
M
V1
3~
ohm W1
PE
IT (ungrounded) systems
EMC filter +E202
EMC filter +E202 is not suitable for use in an IT (ungrounded) system. If the drive is
equipped with EMC filter +E202, disconnect the ground connection of the filter
before connecting the drive to the supply network. For detailed instructions on how
to do this, please contact your local ABB representative. See also section
Compliance with EN 61800-3:2004 on page 154.
Electrical installation
83
WARNING! If a drive of frame size R6 equipped with EMC filter +E200 is installed on
an IT system [an ungrounded power system or a high resistance-grounded (over
30 ohms) power system], the system will be connected to ground potential through
the EMC filter capacitors of the drive. This may cause danger, or damage the unit.
Electrical installation
84
Connection diagram
Q1 K1 U1
L1
L2
L3
PE
Connection procedure
Note: Before making the cable connections, check that the input of the auxiliary
voltage transformer (T10) is selected correctly according to the supply voltage.
1. Open the door of the cabinet.
2. Remove any shrouds that protect the input busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
85
Connection diagram
Q1 K1 L1 U1
L1
L2
L3
PE
Connection procedure
Note: Before making the cable connections, check that the input of the auxiliary
voltage transformer (T10) is selected correctly according to the supply voltage.
1. Open the door of the cabinet.
2. Remove any shrouds that protect the input busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
86
Connection diagram
Q1 K1 L1 U1
L1
L2
L3
PE
Connection procedure
Note: Before making the cable connections, check that the tap settings of the
auxiliary voltage transformer (T10, located in the input/output cubicle) are correct in
regard to the supply voltage. See instructions on page 99.
1. Open the door of the input/output cubicle (see section Cabling direction starting on
page 33).
2. Remove any shrouds that protect the input busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
87
Connection diagram
U<
Q1
L1
L2
L3
PE
Connection procedure
Note: Before making the cable connections, check that the tap settings of the
auxiliary voltage transformer (T10, located in the auxiliary control cubicle) are correct
in regard to the supply voltage. See instructions on page 99.
1. Open the door of the incoming cubicle (see section Cabling direction starting on
page 33).
2. Remove any shrouds that protect the input busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
88
Connection diagram
PE
U2
V2
U1
V1
M
W2
W1 3~
PE
Connection procedure
1. Open the cabinet door.
2. Remove any shrouds that protect the output busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
89
Connection diagram
PE
U2
V2
U1
V1
M
W2
W1 3~
PE
Connection procedure
1. Open the cabinet door.
2. Remove any shrouds that protect the output busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
90
Connection diagram
PE
U2
V2
U1
V1
M
W2
W1 3~
PE
Connection procedure
1. Open the door of the input/output cubicle (see section Cabling direction starting on
page 33).
2. Remove any shrouds that protect the output busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
91
Motor connection – Frame R8i with option +E202 but without +H359
Output busbars
The motor cables are to be connected to the output busbars behind the inverter
module. For the location and dimensions of the busbars, see chapter Dimensions.
Connection diagram
PE
U2
V2
U1
V1
M
W2
W1 3~
PE
Connection procedure
WARNING! Obey the safety instructions when you handle the heavy module! See
section Power module replacement (Frame R8i and up) on page 127. Ignoring these
instructions can cause physical injury or death, or damage to the equipment.
1. Extract the inverter module from the cubicle as described in section Extracting the
module from the cubicle on page 128.
2. Lead the cables into the cabinet at the inverter module. Make the 360° earthing
arrangement at the cable entry as shown below.
Electrical installation
92
Electrical installation
93
Connection diagram
PE
U2
V2
U1
V1
M
W2
W1 3~
PE
Connection procedure
1. Open the door of the common motor terminal cubicle (see section Cabling
direction starting on page 33).
2. Remove any shrouds that protect the output busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 360°
grounding of the cable shields at the entry as shown below.
Electrical installation
94
Output busbars
The motor cables are to be connected to the output busbars behind each inverter
module. For the location and dimensions of the busbars, see chapter Dimensions.
Connection diagram
PE
U2
V2
W2
U1
V1
M
W1 3~
U2 PE
V2
W2
WARNING! The cabling from all inverter modules to the motor must be physically
identical considering cable type, cross-sectional area, and length.
PE
U2
V2
W2
U1
V1
M
W1 3~
U2 PE
V2
W2
Electrical installation
95
Connection procedure
WARNING! Obey the safety instructions when you handle the heavy module! See
section Power module replacement (Frame R8i and up) on page 127. Ignoring these
instructions can cause physical injury or death, or damage to the equipment.
1. Extract each inverter module from the cubicle as described in section Extracting
the module from the cubicle on page 128.
2. Lead the cables into the cabinet at the inverter module. Make the 360° earthing
arrangement at the cable entry as shown below.
Electrical installation
96
Control connections
Connection procedure
Open the cabinet door(s).
Remove the locking screws at the edge of the swing-out frame and open the frame.
Remove any shrouds that limit access to the cable lead-throughs and cable trunking.
Run the cables into the inside of the cabinet through the grommets provided.
Top entry units only: If several cables need to be run through one grommet, use Loctite 5221 (cat. no.
25551) under the grommet to seal the cable entry.
Electrical installation
97
Side view
Strain relief EMI conductive
cushions
If the outer surface of a cable shield is non-conductive, turn the shield inside out as shown below and
apply copper foil to keep the shielding continuous. Do not cut the grounding wire (if present).
Copper foil
Grounding wire
On top entry units, sort the cables so that the thinnest and thickest cables are at opposite ends of the
opening.
Top view
Run the cables to the appropriate terminals. Wherever possible, use the existing cable trunking in the
cabinet. Use sleeving wherever the cables are laid against sharp edges. When running cables to the
swing-out frame, leave some slack in the cable at the hinge to allow the frame to open fully. Tie the cables
to the cable supports wherever necessary.
Cut the cables to suitable length. Strip the cables and conductors.
Twist the cable shields into bundles and connect them to the ground terminal nearest to the terminal block.
Keep the unshielded portion of the cables as short as possible.
Connect the conductors to appropriate terminals (see chapter Motor control and I/O board (RMIO) and the
circuit diagrams delivered with the unit).
Refit any shrouds removed earlier. Close the swing-out frame, refasten, and close the cabinet door(s).
Electrical installation
98
Module
Keep unshielded portion as
short as possible
Shield
1
2
3
4
To nearest PE terminal
CHASSIS
RTAC-01
PULSE ENCODER INTERFACE
GND
Note 1: If the encoder is of unisolated
12345678 123456
SHLD
F01
type, ground the encoder cable at the
DE
23 6
SHLD
C
45
AB
789
CHA
CHB
CHA-
X2
Keep unshielded portion as
WD/
CHB-
NODE ID
CHZ-
shaft and the stator frame, ground the
0V
0V
encoder cable shield at the drive and
the encoder end.
1
2
3
4
VOUT
+15V
X1
VIN
+24V
Note 2: Twist the pair cable wires.
Electrical installation
99
Tap settings of the auxiliary voltage transformer (Frame R8i and up)
Primary
Secondary 3~ Input
Output
Supply Tap settings Supply 230 V 115 V 400 V (50 Hz) 320 V (60 Hz)
Terminals
voltage A1 to... B1 to… C1 to… voltage Terminals Tap setting Terminals Tap setting Terminals Terminals
690 V A1, B1, C1 C2 A2 B2 690 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
660 V A1, B1, C1 C2 A2 B2 660 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
600 V A1, B1, C1 C3 A3 B3 600 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
575 V A1, B1, C1 C3 A3 B3 575 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
525 V A1, B1, C1 C4 A4 B4 525 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
500 V A1, B1, C1 C4 A4 B4 500 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
480 V A1, B1, C1 C5 A5 B5 480 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
460 V A1, B1, C1 C5 A5 B5 460 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
440 V A1, B1, C1 C6 A6 B6 440 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
415 V A1, B1, C1 C6 A6 B6 415 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
400 V A1, B1, C1 C7 A7 B7 400 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
380 V A1, B1, C1 C7 A7 B7 380 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
Electrical installation
100
Electrical installation
101
Analogue outputs
Two programmable current outputs: 0 (4) to 20 mA, RL < 700 ohm
Resolution 0.1 % (10 bit)
Inaccuracy ± 1 % (Full Scale Range) at 25 °C (77 °F). Temperature coefficient: ± 200 ppm/°C
(± 111 ppm/°F) max.
Digital inputs
With Standard Control Program six programmable digital inputs (common ground: 24
V DC, -15 % to +20 %) and a start interlock input. Group isolated, can be divided in
two isolated groups (see Isolation and grounding diagram below).
Thermistor input: 5 mA, < 1.5 kohm “1” (normal temperature), > 4 kohm “0”
(high temperature), open circuit “0” (high temperature).
Internal supply for digital inputs (+24 V DC): short circuit proof. An external 24 V DC
supply can be used instead of the internal supply.
Isolation test voltage 500 V AC, 1 min
Logical thresholds < 8 V DC “0”, > 12 V DC “1”
Input current DI1 to DI 5: 10 mA, DI6: 5 mA
Filtering time constant 1 ms
Relay outputs
Three programmable relay outputs
Switching capacity 8 A at 24 V DC or 250 V AC, 0.4 A at 120 V DC
Minimum continuous current 5 mA rms at 24 V DC
Maximum continuous current 2 A rms
Isolation test voltage 4 kV AC, 1 minute
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 61800-5-1 provided that the external circuits connected to the terminals
also fulfil the requirements, and that the installation site is below 2000 m (6562 ft) in altitude. For installation at higher
altitudes, see page 78.
9 AO1+
10 AO1-
11 AO2+
12 AO2-
X22
1 DI1
2 DI2
3 DI3
4 DI4
Jumper J1 settings:
9 DGND1
Installation checklist
Check the mechanical and electrical installation of the drive before start-up. Go
through the checklist below together with another person.
WARNING! Only qualified electricians are allowed to commission the drive. Read
and follow the Safety instructions on the first pages of this manual. Neglecting the
safety instructions can cause injury or death.
Check…
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. See Electrical installation, Technical data: IEC ratings or Ambient
conditions.
The motor and the driven equipment are ready for start.
The EMC filter (option +E202) is disconnected if the drive is connected to an IT (ungrounded) system.
The supply (input power) voltage matches the nominal input voltage of the drive.
The supply (input power) connection to the input terminals are OK and the phase order is correct.
There are no tools, foreign objects or dust from drilling inside the drive.
Supply (input power) voltage cannot be applied to the output of the drive (with a bypass connection).
Check…
For drives with the stop category 1 Emergency stop function (option +Q952 or +Q964): The delay time of the
safety relay and the deceleration time of the Emergency stop function have been set to a suitable value.
Start-up procedure
Action Additional information
WARNING! Ensure that the disconnector of the supply transformer is
locked to open position, i.e. no voltage is, or cannot be connected to
drive inadvertently. Check also by measuring that there is no voltage
connected.
Basic checks with no voltage connected
If the unit is equipped with an air circuit breaker, check the current trip Optional device. See the delivery-
limits of the breaker (preset at the factory). specific circuit diagrams.
General rule
Ensure the selectivity condition is fulfilled i.e. the breaker trips at a lower
current than the protection device of the supplying network, and that the
limit is high enough not to cause unnecessary trips during the
intermediate DC circuit load peak at start.
Long-term current limit
As a rule of thumb, this should be set to the rated AC current of the drive.
Peak current limit
As a rule of thumb, this should be set to a value 3-4 times the rated AC
current of the drive.
Check the settings of the relays and breakers/switches of the auxiliary Optional devices. See delivery
circuits. specific circuit diagrams.
Disconnect any unfinished or unchecked 230/115 V AC cables that lead
from the terminal blocks to the outside of the equipment.
For drive types ACS800-17-0640-3/0780-5/0790-7 and up: Locate the These drive types have two PPCS
APBU-xx PPCS branching units. Enable memory backup battery on branching units, one for the supply
each branching unit by setting actuator 6 of switch S3 to ON. unit, one for the inverter unit. By
default, memory backup is switched
off to save the battery.
Connecting voltage to input terminals and auxiliary circuit
WARNING! When voltage is connected to the input terminals, voltage
may also be connected to the auxiliary circuits of the drive.
Make sure that it is safe to apply voltage. Ensure that:
• nobody is working on the unit or circuits that are wired from outside into
the cabinets
• cabinet doors are closed
• covers of motor terminal boxes are in place.
Open the earthing/grounding switch (Q9) if present. The earthing/grounding switch and
the main disconnecting device are
either mechanically or electrically
interlocked so that the earthing/
grounding switch can only be closed
when the main disconnecting switch
is open, and vice versa.
Parameters
No. Name/Value Description T./FbEq Def.
16 SYSTEM CTR Parameter lock, parameter back-up etc.
INPUTS
16.15 START MODE Selects start mode. B EDGE
LEVEL Starts converter by level of control command. Control command is 0
selected by parameter 98.01 COMMAND SEL and 98.02 COMM.
MODULE.
WARNING! After a fault reset, the converter will start if the
start signal is on.
Term Definition
Actual signal Signal measured or calculated by the drive. Can be monitored by the
user. No user setting possible.
FbEq Fieldbus equivalent: The scaling between the value shown on the control
panel and the integer used in serial communication.
Actual signals and parameters of the supply unit control program visible also in
the inverter control program
No. Name/Value Description FbEq Def.
09 ACTUAL SIGNALS Signals from the supply unit (line-side converter).
09.12 LCU ACT SIGNAL 1 Line-side converter signal selected by par. 95.08 LCU PAR1 SEL. 1=1 106
09.13 LCU ACT SIGNAL 2 Line-side converter signal selected by par. 95.09 LCU PAR2 SEL. 1=1 110
95 HARDWARE SPECIF Line-side converter references and actual signal selections.
95.06 LCU Q PW REF Reactive power reference for the line-side converter i.e. the value 0
for par. 24.02 Q POWER REF2 in the IGBT Supply Control
Program.
Scaling example 1: 10000 equals to a value of 10000 of parameter
24.02 Q POWER REF2 and 100% of par. 24.01 Q POWER REF
(i.e. 100% of the converter nominal power given in par. 04.06
CONV NOM POWER) when par. 24.03 Q POWER REF2 SEL is
set to PERCENT.
Scaling example 2: Par. 24.03 Q POWER REF2 SEL is set to kVAr.
A value of 1000 of par. 95.06 equals to 1000 kVAr of par. 24.02 Q
POWER REF2. Value of par. 24.01 Q POWER REF is then 100 ·
(1000 kVAr divided by converter nominal power in kVAr)%.
Scaling example 3: Par. 24.03 Q POWER REF2 SEL is set to PHI.
A value of 10000 of par. 95.06 equals to a value of 100 deg of
parameter 24.02 Q POWER REF2 which is limited to 30 deg. The
value of par. 24.01 Q POWER REF will be determined
approximately according to the following equation where P is read
from actual signal 1.09 POWER:
S
P P Q
cos 30 = --- = -----------------------
S 2 2 30 deg
P +Q
P
Positive reference 30 deg denotes capacitive load.
Negative reference 30 deg denotes inductive load.
Maintenance
Safety instructions
Only a qualified electrician is allowed to perform the maintenance.
Before starting work inside the cabinet,
• isolate the drive from the power supply (note that any switch-disconnector
installed in the drive does not switch off the voltage from the input terminals)
• wait for 5 minutes to let the intermediate circuit capacitors discharge
• open the cabinet doors
• ensure there is no dangerous voltage present by measuring the voltage of the
input terminals and the intermediate circuit terminals.
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Maintenance
116
Consult your local ABB Service representative for more details on the maintenance.
On the Internet, go to http://www.abb.com/drivesservices.
Maintenance
117
Maintenance
118
Cooling fans
4
3
2 6
2
5
Maintenance
119
Maintenance
120
2 2
Maintenance
121
Supply and inverter module cooling fan replacement (Frame R8i and up)
The actual lifespan of the fan depends on the running time of the fan, ambient
temperature and dust concentration. Each supply and inverter module has its own
cooling fan. Replacements are available from ABB. Do not use other than ABB
specified spare parts.
The supply and inverter control programs keep track of the running times of the
cooling fans of the supply and inverter modules respectively. See the Firmware
Manuals delivered with the drive for the actual signals which indicate the running
time.
Module fan replacement procedure
1. Read and repeat the steps in section Safety instructions on page 115.
2. Disconnect the fan wiring plug (1).
3. Remove the locking screws (2).
4. Pull the fan out along its sliding rails (3).
5. Install a new fan in reverse order.
Maintenance
122
ALCL-1x ALCL-2x
2 2
1
3
Maintenance
123
Fan holder
1. Remove the eight screws attaching the fan holder to the cabinet roof.
2. Lift the fan holder until the fan cable can be disconnected.
3. Disconnect the fan cable.
4. Remove the fan from the fan holder.
5. Fasten a new fan to the fan holder.
6. Reconnect the fan cable.
7. Insert the fan holder into the aperture in the cabinet roof. Make sure the gasket
is not displaced while doing this.
8. Fasten the eight screws attaching the fan holder.
Maintenance
124
WARNING! Read and follow the instructions in chapter Safety instructions. Ignoring
the instructions can cause physical injury or death, or damage to the equipment.
1. Switch off the power to the unit and open the main disconnecting device. Close
the grounding switch (option +F259) if there is one.
2. Let the intermediate circuit DC capacitors discharge for five minutes. Ensure by
measuring that the drive is not live before starting the work.
3. Remove the grating (A) and the two fans by undoing the four screws (B).
4. If necessary, undo the four screws (C) to remove the airflow guide (D).
B
B C
D
C
Maintenance
125
2 2 4
1
3
2
2
3
7
6
5
5
Maintenance
126
10
9
8
8
9
8 8
12
11 11
Heatsinks
The heatsink fins of the power modules pick up dust from the cooling air. The module
runs into overtemperature warnings and faults if the heatsinks are not clean. In a
“normal” environment (not especially dusty nor clean) the heatsinks should be
checked annually, in a dusty environment more often.
Whenever necessary, clean the heatsinks as follows:
1. Remove the cooling fan (see section Cooling fans on page 118).
2. Blow dry clean compressed air from bottom to top and simultaneously use a
vacuum cleaner at the air outlet to trap the dust. Note: Prevent the dust from
entering adjoining equipment.
3. Refit the cooling fan.
Capacitors
The inverter modules employ several electrolytic capacitors. Their actual lifespan
depends on the operating time of the drive, loading and ambient temperature.
Capacitor life can be prolonged by lowering the ambient temperature.
It is not possible to predict capacitor failure. Capacitor failure is usually followed by
damage to the unit and an input cable fuse failure, or a fault trip. Contact ABB if
capacitor failure is suspected.
Reforming
Reform (re-age) spare part capacitors once a year according to Converter module
capacitor reforming instructions (code: 64059629 [English], available through your
local ABB representative.
Capacitor replacement
Contact an ABB service representative.
Maintenance
127
WARNING! Ignoring the following instructions can cause physical injury or death,
or damage to the equipment.
• Do not use the ramp which is supplied with the drive with heights over 50 mm
(the standard plinth height of ABB cabinets). The ramp is designed for a plinth
height of 50 mm.
Support the top and Do not tilt! Extend the support legs outside the
bottom of the module cabinet!
while removing!
max 50 mm
Lift the module by the upper part Mind your fingers! Keep fingers away from the Support the top and
only using the lifting hole(s) at the edges of the front flange of the module! bottom of the module while
top! replacing!
Maintenance
128
WARNING! Do not use the ramp which is supplied with the drive with heights over
50 mm (the standard plinth height of ABB cabinets). The ramp is designed for a
plinth height of 50 mm.
WARNING! Make sure that the wires do not catch. While pulling on the handle, keep
a constant pressure with one foot on the base of the module to prevent the module
from falling on its back. Use safety shoes with metal toe cap to avoid foot injury.
11. Extend the support legs of the module. Keep the legs extended until the module
is about to be inserted back into the cubicle.
Maintenance
129
5 6
7b
8
7a
Maintenance
130
Maintenance
131
WARNING! Keep your fingers away from the edge of the module front plate to avoid
pinching them between the module and the cubicle. Also, keep a constant pressure
with one foot on the base of the module to prevent the module from falling on its
back.
3. Fasten the module fixing screws at the top and reconnect the DC busbars.
4. Connect the cables (X50, fibre optic cables).
5. Loosen the fastening screws at the base of the module and remove the pull-out
ramp. Flip the module fastening bracket into the down position and tighten the
screws.
6. Fasten the shroud and close the cubicle door.
Maintenance
132
Maintenance
133
Fault tracing
To display the warning or fault identification text, switch the control panel to view the
line-side converter as described in section Control panel on page 40.
Conflicting ID numbers
If the ID numbers of the line-side and the motor-side converters are set equal, the
control panel stops functioning. To clear the situation:
• Disconnect the panel cable from the RMIO board of the motor-side converter.
• Set the ID number of the line-side converter RMIO board to 2. For the setting
procedure, see the inverter control program (e.g. Standard Control Program)
Firmware Manual.
• Connect the disconnected cable to the RMIO board of the motor-side converter
again and set the ID number to 1.
Fault tracing
134
Fault tracing
135
Technical data
IEC ratings
The ratings for the ACS800-17 with a 50 Hz supply are given below. The symbols
are described below the table.
No-over- Light- Heavy-duty Heat dissi- Air Noise
Nominal ratings
load use overload use use pation flow level
ACS800-17 type
I1N Icont.max Imax Pcont.max I2N PN I2hd Phd
A A A kW A kW A kW kW m3/h dBA
Three-phase supply voltage 380 V, 400 V or 415 V
ACS800-17-0060-3 112 120 168 55 114 55 88 45 1.8 500 73
ACS800-17-0070-3 140 150 234 75 142 75 117 55 2.4 500 73
ACS800-17-0100-3 153 165 264 90 157 75 132 75 2.8 500 73
ACS800-17-0140-3 182 202 293 110 194 90 151 75 6 1300 74
ACS800-17-0170-3 224 250 363 132 240 132 187 90 7 1300 74
ACS800-17-0210-3 263 292 400 160 280 160 218 110 7 3160 75
ACS800-17-0260-3 333 370 506 200 355 200 277 132 9 3160 75
ACS800-17-0320-3 423 469 642 250 450 250 351 200 11 3160 75
ACS800-17-0390-3 509 565 773 315 542 315 423 250 14 3160 75
ACS800-17-0490-3 630 704 963 400 675 355 526 250 19 3160 75
ACS800-17-0640-3 828 919 1258 500 882 500 688 355 22 6400 77
ACS800-17-0770-3 1001 1111 1521 630 1067 630 831 450 28 6400 77
ACS800-17-0960-3 1235 1379 1888 800 1324 710 1031 560 36 6400 77
ACS800-17-1070-3 1383 1535 2102 900 1474 800 1149 630 39 10240 78
ACS800-17-1370-3 1833 1978 2707 1200 1899 1100 1479 800 51 10240 78
ACS800-17-1810-3 2419 2610 3573 1600 2506 1400 1953 1100 67 12800 78
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACS800-17-0070-5 112 120 168 75 114 75 88 55 2.4 500 73
ACS800-17-0100-5 129 139 234 90 132 90 114 75 2.8 500 73
ACS800-17-0120-5 145 156 264 110 148 (1 90 125 75 3.4 500 73
ACS800-17-0170-5 180 200 291 132 192 132 150 90 6 1300 74
ACS800-17-0210-5 220 245 356 160 235 (2 160 183 110 8 1300 74
ACS800-17-0260-5 270 302 438 200 289 (3 200 226 132 8 3160 75
ACS800-17-0320-5 329 365 530 250 350 (4 250 273 160 10 3160 75
ACS800-17-0400-5 410 455 660 315 437 315 340 200 12 3160 75
ACS800-17-0460-5 473 525 762 355 504 355 393 250 14 3160 75
ACS800-17-0510-5 536 595 863 400 571 400 445 315 16 3160 75
ACS800-17-0580-5 600 670 972 500 643 450 501 315 19 3160 75
ACS800-17-0780-5 803 892 1294 630 856 630 667 450 24 6400 77
ACS800-17-0870-5 900 1005 1458 710 965 630 752 500 28 6400 77
ACS800-17-1140-5 1176 1313 1906 900 1261 900 982 710 36 6400 77
ACS800-17-1330-5 1376 1528 2217 1120 1467 1120 1143 800 41 10240 78
Technical data
136
Symbols
Nominal ratings
I1N Nominal input current
Icont.max Continuous RMS output current. No overloadability at 40 °C (104 °F).
Imax Maximum output current. Allowable for 10 seconds at start, otherwise as long as allowed
by drive temperature.
Typical ratings for no-overload use
Pcont.max Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for light-overload use (10% overloadability)
I2N Continuous rms current. 10% overload is allowed for 1 minute every 5 minutes.
PN Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for heavy-duty use (50% overloadability)
I2hd Continuous rms current. 50% overload is allowed for 1 minute every 5 minutes.
Phd Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres
(3281 ft), or if the ambient temperature exceeds 40 °C (104 °F).
Technical data
137
Temperature derating
In the temperature range +40 °C (+104 °F) to +50 °C (+122 °F), the rated output current is decreased
by 1% for every additional 1 °C (1.8 °F). The output current is calculated by multiplying the current
given in the rating table by the derating factor.
Example If the ambient temperature is 50 °C (+122 °F), the derating factor is 100 % - 1 % · 10 °C =
90% or 0.90. The output current is then 0.90 × I or 0.90 × I . °C
2N cont.max
Altitude derating
At altitudes from 1000 to 4000 m (3281 to 13123 ft) above sea level, the derating is 1% for every 100 m
(328 ft). For a more accurate derating, use the DriveSize PC tool. If the installation site is higher than
2000 m (6600 ft) above sea level, please contact your local ABB distributor or office for further
information.
Technical data
138
NEMA ratings
The ratings for the ACS800-17 with a 60 Hz supply are given below. The symbols
are described below the table.
Heavy-duty Heat dis- Noise
Nominal ratings Normal use Air flow
use sipation level
ACS800-17 type
I1N Imax Pcont.max I2N PN I2hd Phd
A A hp A hp A hp kW ft3/min dBA
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V or 480 V
ACS800-17-0070-5 112 168 75 114 75 88 60 2.4 295 73
ACS800-17-0100-5 129 234 100 132 100 114 75 2.8 295 73
ACS800-17-0120-5 145 264 125 148 (1 125 125 100 3.4 295 73
ACS800-17-0170-5 180 291 150 192 150 156 100 6 765 74
ACS800-17-0210-5 220 356 200 235 (2 200 183 150 8 765 74
ACS800-17-0260-5 270 438 250 289 (3 250 226 150 8 1860 75
ACS800-17-0320-5 329 530 300 350 (4 300 273 200 10 1860 75
ACS800-17-0400-5 410 660 350 437 350 340 250 12 1860 75
ACS800-17-0460-5 473 762 450 504 400 393 300 14 1860 75
ACS800-17-0510-5 536 863 500 571 450 445 350 16 1860 75
ACS800-17-0580-5 600 972 550 643 500 501 400 19 1860 75
ACS800-17-0780-5 803 1294 750 856 700 667 550 24 3770 77
ACS800-17-0870-5 900 1458 900 965 800 752 650 28 3770 77
ACS800-17-1140-5 1176 1906 1150 1261 1050 982 850 36 3770 77
ACS800-17-1330-5 1376 2217 1300 1467 1250 1143 1000 41 6030 78
ACS800-17-1640-5 1746 2734 1650 1809 1550 1409 1250 52 6030 78
ACS800-17-2160-5 2304 3608 2150 2387 2050 1860 1600 68 7530 79
Three-phase supply voltage 525 V, 575 V or 600 V
ACS800-17-0060-7 53 86 60 54 50 43 40 1.8 295 73
ACS800-17-0070-7 73 120 75 75 60 60 50 2.4 295 73
ACS800-17-0100-7 86 142 100 88 75 71 60 2.8 295 73
ACS800-17-0160-7 119 192 125 127 125 99 100 7 765 74
ACS800-17-0200-7 135 218 150 144 150 112 100 8 765 74
ACS800-17-0260-7 180 301 200 193 200 150 150 11 1860 75
ACS800-17-0320-7 250 417 250 268 250 209 200 12 1860 75
ACS800-17-0400-7 300 502 350 322 300 251 250 16 1860 75
ACS800-17-0440-7 344 571 400 367 350 286 300 17 1860 75
ACS800-17-0540-7 400 668 450 429 450 334 350 18 1860 75
ACS800-17-0790-7 593 985 700 632 650 493 500 33 3770 77
ACS800-17-0870-7 657 1091 800 700 750 545 600 32 3770 77
ACS800-17-1050-7 784 1310 950 840 900 655 700 36 3770 77
ACS800-17-1330-7 1001 1663 1250 1067 1150 831 900 48 6030 78
ACS800-17-1510-7 1164 1879 1350 1206 1300 940 1050 51 6030 78
ACS800-17-1980-7 1536 2480 1850 1591 1750 1240 1350 67 7530 79
ACS800-17-2780-7 2091 3472 2600 2228 2450 1736 1900 94 10550 79
ACS800-17-2940-7 2280 3680 2800 2362 2550 1840 2000 99 11300 79
(1) 156 A allowed at 460 V
(2) 240 A allowed at 460 V
(3) 302 A allowed at 460 V
(4) 361 A allowed at 460 V
PDM-184674-E51
Technical data
139
Symbols
Nominal ratings
I1N Nominal input current
Imax Maximum output current. Allowable for 10 seconds at start, otherwise as long as allowed
by drive temperature.
Pcont.max Typical motor power. The power ratings apply to most 4-pole NEMA-rated motors at
nominal voltage (460 or 575 V).
Normal use (10% overloadability)
I2N Continuous rms current. 10% overload is allowed for 1 minute every 5 minutes.
PN Typical motor power. The power ratings apply to most 4-pole NEMA-rated motors at
nominal voltage (460 or 575 V).
Heavy-duty use (50% overloadability)
I2hd Continuous rms current. 50% overload is allowed for 1 minute every 5 minutes.
Phd Typical motor power. The power ratings apply to most 4-pole NEMA-rated motors at
nominal voltage (460 or 575 V).
Technical data
140
AC fuses
Notes:
• Larger fuses must not be used.
• Fuses from other manufacturers can be used if they meet the ratings.
• The recommended fuses are for branch circuit protection per NEC as required for
UL approval.
AC fuse information
Drive type aR, IEC aR, UL Recognized
Qty In
Bussmann Mersen Bussmann Mersen
400 V
ACS800-17-0060-3 3 160 170M3814 – 170M3014 –
ACS800-17-0070-3 3 200 170M3815 – 170M3015 –
ACS800-17-0100-3 3 250 170M3816 – 170M3016 –
ACS800-17-0140-3 3 315 170M3817 – 170M3017 –
ACS800-17-0170-3 3 400 170M5808 – 170M5008 –
ACS800-17-0210-3 3 450 170M5809 6.9URD2PV0450 170M5059 –
ACS800-17-0260-3 3 630 170M6810 6.9URD3PV0630 170M6210 –
ACS800-17-0320-3 3 800 170M8545 6.9URD3PV0800 170M6212 –
ACS800-17-0390-3 3 1000 170M6814 6.9URD3PV1000 170M6214 –
ACS800-17-0490-3 3 1000 170M6814 6.9URD3PV1000 170M6214 –
ACS800-17-0640-3 3 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-17-0770-3 3 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
ACS800-17-0960-3 3 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
ACS800-17-1070-3 6 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-17-1370-3 6 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-17-1810-3 6 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
Technical data
141
AC fuse information
Drive type aR, IEC aR, UL Recognized
Qty In
Bussmann Mersen Bussmann Mersen
500 V
ACS800-17-0070-5 3 160 170M3814 – 170M3014 –
ACS800-17-0100-5 3 200 170M3815 – 170M3015 –
ACS800-17-0120-5 3 250 170M3816 – 170M3016 –
ACS800-17-0170-5 3 315 170M3817 – 170M3017 –
ACS800-17-0210-5 3 400 170M5808 – 170M5008 –
ACS800-17-0260-5 3 450 170M5809 6.9URD2PV0450 170M5059 –
ACS800-17-0320-5 3 630 170M6810 6.9URD3PV0630 170M6210 –
ACS800-17-0400-5 3 800 170M8545 6.9URD3PV0800 170M6212 –
ACS800-17-0460-5 3 1000 170M6814 6.9URD3PV1000 170M6214 –
ACS800-17-0510-5 3 1000 170M6814 6.9URD3PV1000 170M6214 –
ACS800-17-0580-5 3 1000 170M6814 6.9URD3PV1000 170M6214 –
ACS800-17-0780-5 3 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-17-0870-5 3 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
ACS800-17-1140-5 3 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
ACS800-17-1330-5 6 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-17-1640-5 6 1600 170M6419 6URD33TTF1600 170M6419 6URD33TTF1600
ACS800-17-2160-5 6 2000 170M6421 5.5URD33TTF2000 170M6421 5.5URD33TTF2000
690 V
ACS800-17-0060-7 3 100 170M3812D – 170M3012 –
ACS800-17-0070-7 3 125 170M3813D – 170M3013 –
ACS800-17-0100-7 3 160 170M3814D – 170M3014 –
ACS800-17-0160-7 3 250 170M3816 – 170M3016 –
ACS800-17-0200-7 3 315 170M3817 – 170M3017 –
ACS800-17-0260-7 3 315 170M3817 6.9URD1PV0315 170M3017 –
ACS800-17-0320-7 3 450 170M5809 6.9URD2PV0450 170M5059 –
ACS800-17-0400-7 3 450 170M5809 6.9URD2PV0450 170M5059 –
ACS800-17-0440-7 3 630 170M6810 6.9URD3PV0630 170M6210 –
ACS800-17-0540-7 3 630 170M6810 6.9URD3PV0630 170M6210 –
ACS800-17-0790-7 3 1000 170M6414 6.9URD32TTF1000 170M6414 6.9URD32TTF1000
ACS800-17-0870-7 3 1250 170M6416 – 170M6416 –
ACS800-17-1050-7 3 1250 170M6416 – 170M6416 –
ACS800-17-1330-7 6 1000 170M6414 6.9URD32TTF1000 170M6414 6.9URD32TTF1000
ACS800-17-1510-7 6 1000 170M6414 6.9URD32TTF1000 170M6414 6.9URD32TTF1000
ACS800-17-1980-7 6 1250 170M6416 – 170M6416 –
ACS800-17-2780-7 9 1250 170M6416 – 170M6416 –
ACS800-17-2940-7 9 1250 170M6416 – 170M6416 –
PDM-184674-D
Technical data
142
DC fuses
Notes:
• Larger fuses must not be used.
• Fuses from other manufacturers can be used if they meet the ratings.
• The recommended fuses are for branch circuit protection per NEC as required for
UL approval.
DC fuse information
Drive type IEC UL Recognized
Qty
Bussmann Mersen In Bussmann In
400 V
ACS800-17-0060-3
… – – – – – –
ACS800-17-0490-3
ACS800-17-0640-3 8 170M8552 6.9URD3PV1000 1000 170M6215 1000
ACS800-17-0770-3 8 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-17-0960-3 8 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-17-1070-3 12 170M8552 6.9URD3PV1000 1000 170M6215 1000
ACS800-17-1370-3 12 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-17-1810-3 16 170M8547 6.9URD33PA1250 1250 170M6216 1250
500 V
ACS800-17-0070-5
… – – – – – –
ACS800-17-0580-5
ACS800-17-0780-5 8 170M8552 6.9URD3PV1000 1000 170M6215 1000
ACS800-17-0870-5 8 170M8552 6.9URD3PV1000 1000 170M6215 1000
ACS800-17-1140-5 8 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-17-1330-5 12 170M8547 6.9URD33PA1250 1250 170M6215 1250
ACS800-17-1640-5 12 170M8547 6.9URD33PA1250 1250 170M6216 1250
ACS800-17-2160-5 16 170M8547 6.9URD33PA1250 1250 170M6216 1250
690 V
ACS800-17-0060-7
… – – – – – –
ACS800-17-0540-7
ACS800-17-0790-7 8 170M8646 12URD73PA0700 700 170M8636 700
ACS800-17-0870-7 8 170M8647 11URD73PA0800 800 170M8637 800
ACS800-17-1050-7 8 170M8647 11URD73PA0800 800 170M8637 800
ACS800-17-1330-7 12 170M8647 11URD73PA0800 800 170M8637 800
ACS800-17-1510-7 12 170M8647 11URD73PA0800 800 170M8637 800
ACS800-17-1980-7 16 170M8647 11URD73PA0800 800 170M8637 800
ACS800-17-2780-7 24 170M8647 11URD73PA0800 800 170M8637 800
ACS800-17-2940-7 24 170M8647 11URD73PA0800 800 170M8637 800
PDM-184674-D
Technical data
143
Short-circuit withstand Units without grounding switch: Maximum allowable prospective short-circuit current is
strength (IEC 60439-1) 65 kA when protected by the fuses given in the fuse tables.
Units with grounding switch: Maximum allowable prospective short-circuit current is 50 kA
when protected by the fuses given in the fuse tables.
Short-circuit current The drive is suitable for use on a circuit capable of delivering not more than 100,000 rms
protection (UL 508A) symmetrical amperes at 600 V maximum when protected by the fuses given in the fuse
tables.
Short-circuit current The drive is suitable for use on a circuit capable of delivering not more than 65 kA rms
protection (CSA C22.2 No. symmetrical amperes at 600 V maximum when protected by the fuses given in the fuse
14-05) tables.
Frequency 48…63 Hz
Harmonic distortion Harmonics are below the limits defined in IEEE519 for all Isc/IL. Each individual harmonic
current fulfils IEEE519 table 10-3 for Isc/IL > 20. Current THD and each individual current
harmonic fulfil IEC 61000-3-4 table 5.2 for Rsce > 66. The values will be met if the supply
network voltage is not distorted by other loads and when the drive operates at the nominal
load.
Input power cable lead- Ø60 mm. For quantity and location, see chapter Dimensions.
throughs
Technical data
144
Technical data
145
Motor connection
Voltage (U2) 0 to U1, 3-phase symmetrical, Umax at the field weakening point
UNmains
fFWP = · fNmotor
UNmotor
where fFWP = frequency at field weakening point; UNmains = mains (input power) voltage;
UNmotor = rated motor voltage; fNmotor = rated motor frequency
Power limit 2 × Phd. After approximately 2 minutes at 2 × Phd, the limit is set at Pcont.max.
Motor cable lead-throughs 3 × Ø60 mm at each inverter module (units without common motor terminal cubicle)
Units with common motor terminal cubicle: See chapter Dimensions.
Technical data
146
Technical data
147
Cabling
direction
Cabling direction
68265631-B cabinet_400_generic.asm
Output terminals 8 × Ø13 mm per phase. Tightening torque: 70 Nm (52 lbf.ft). See chapter Dimensions.
Units with option +H359
(common motor terminal
cubicle)
Technical data
148
Efficiency
> 97% (at rated current and nominal supply voltage)
Cooling
Method Internal fans, flow direction from bottom to top
Degrees of protection
IP21; IP22; IP42; IP54, IP54R (with air outlet duct)
Ambient conditions
Environmental limits for the drive are given below. The drive must be used in a heated,
indoor controlled environment.
Operation Storage Transportation
installed for stationary use in the protective package in the protective package
Installation site altitude Supply voltage < 600 V AC: - -
max. 4000 m, except drives
with options +Q963, +Q964
and +Q968: max. 2000 m
Supply voltage > 600 V AC
(max. 690 V AC):
- IT (ungrounded) and
corner-grounded networks:
max. 2000 m
- TN (grounded) networks:
max. 4000, except drives
with options +Q963, +Q964
and +Q968: max. 2000 m
Note: Above 1000 m
(3281 ft), see section
Derating.
Air temperature -15 to +50 °C (5 to 122 °F), -40 to +70 °C (-40 to +158°F) -40 to +70 °C (-40 to +158°F)
no frost allowed. See section
Derating.
Technical data
149
Materials
Cabinet Hot-dip zinc-coated (thickness approx. 20 µm) steel sheet (thickness 1.5 mm) with
polyester thermosetting powder coating (thickness approx. 80 µm) on visible surfaces.
Colour: RAL 7035 (light grey, semigloss).
Fire safety of materials Insulating materials and non-metallic items: Mostly self-extinctive
(IEC 60332-1)
Disposal The drive contains raw materials that should be recycled to preserve energy and natural
resources. The package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or burned under
controlled circumstances, according to local regulations. Most recyclable parts are marked
with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
boards can be landfilled. The DC capacitors (C1-1 to C1-x) contain electrolyte and the
printed circuit boards contain lead, both of which are classified as hazardous waste within
the EU. They must be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling instructions,
please contact your local ABB distributor.
Technical data
150
Applicable standards
The drive complies with the following standards. The compliance with the European Low
Voltage Directive is verified according to standards EN 61800-5-1 and EN 60204-1.
• EN 61800-5-1:2007 Adjustable speed electrical drives. Part 5-1: Safety requirements. Electrical, thermal and
energy.
• EN 60204-1:2006 + Safety of machinery. Electrical equipment of machines. Part 1: General requirements.
A1:2009 Provisions for compliance: The final assembler of the machine is responsible for installing
- an emergency-stop device
- a supply disconnecting device
- the drive module into a cabinet.
• EN 60529:1991 (IEC 60529) Degrees of protection provided by enclosures (IP code)
• IEC 60664-1:2007 Insulation coordination for equipment within low-voltage systems. Part 1: Principles,
requirements and tests.
• EN 61800-3:2004 Adjustable speed electrical power drive systems. Part 3: EMC requirements and specific
test methods.
• UL 508C:2002, Third Edition UL Standard for Safety, Power Conversion Equipment
• CSA C22.2 No. 14-10 Industrial control equipment
Technical data
151
CE marking
A CE mark is attached to the drive to verify that the unit follows the provisions of the European Low
Voltage, and EMC Directives. The CE marking also verifies that the drive, in regard to its safety
functions (such as Safe torque off), conforms with the Machinery Directive as a safety component.
Technical data
152
Declaration of Conformity
Technical data
153
Technical data
154
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to
operate without problems within an electromagnetic environment. Likewise, the equipment must not
disturb or interfere with any other product or system within its locality.
First environment includes establishments connected to a low-voltage network which supplies buildings
used for domestic purposes.
Second environment includes establishments connected to a network not supplying domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed and
commissioned only by a professional when used in the first environment. Note: A professional is a
person or organisation having necessary skills in installing and/or commissioning power drive systems,
including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the second
environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current equal to or above
400 A, or intended for use in complex systems in the second environment.
Category C2
The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter +E202.
2. The motor and control cables are selected as specified in the Hardware Manual.
3. The drive is installed according to the instructions given in the Hardware Manual.
4. Maximum motor cable length is 100 metres (328 ft).
WARNING! The drive may cause radio interference if used in a residential or domestic environment.
The user is required to take measures to prevent interference, in addition to the requirements for CE
compliance listed above, if necessary.
Note: It is not allowed to install a drive equipped with EMC filter +E202 on IT (ungrounded) systems.
The supply network becomes connected to ground potential through the EMC filter capacitors which
may cause danger or damage the unit. See also section IT (ungrounded) systems on page 82.
Category C3
The drive complies with the standard with the following provisions:
1. The drive of frame size R6 is equipped with optional EMC filter +E200. (Frame sizes R7i and R8i
have EMC filter +E210 as standard equipment, and thus, they meet the Category 3 requirements as
default.) See also section IT (ungrounded) systems on page 82.
1. The motor and control cables are selected as specified in the Hardware Manual.
2. The drive is installed according to the instructions given in the Hardware Manual.
3. Maximum motor cable length is 100 metres (328 ft).
WARNING! A drive of category C3 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.
Note: It is not allowed to install a drive equipped with EMC filter +E200 on IT (ungrounded) systems.
The supply network becomes connected to ground potential through the EMC filter capacitors which
may cause danger or damage the unit. See also section IT (ungrounded) systems on page 82.
Technical data
155
Category C4
If the provisions under Category C3 cannot be met, the use of the drive in the second environment is
also possible if:
1. It is ensured that no excessive emission is propagated to neighbouring low-voltage networks. In
some cases, the natural suppression in transformers and cables is sufficient. If in doubt, the supply
transformer with static screening between the primary and secondary windings can be used.
Neighbouring network
Static screen
Point of measurement
Equipment Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available
from the local ABB representative.
3. The motor and control cables are selected as specified in the Hardware Manual.
4. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.
“C-tick” marking
“C-tick” marking is required in Australia and New Zealand. A “C-tick” mark is attached to each drive in
order to verify compliance with the relevant standard (IEC 61800-3:2004 – Adjustable speed electrical
power drive systems. Part 3: EMC product standard including specific test methods), mandated by the
Trans-Tasman Electromagnetic Compatibility Scheme. See section Compliance with EN 61800-3:2004
on page 154.
Technical data
156
Technical data
157
Dimensions
Cabinet line-ups
The drive consists of cubicles built into a cabinet line-up. The tables below show the
composition of cabinet line-ups for each frame size and the standard combinations
of options. The dimensions are in millimetres.
Notes:
• The side panels increase the total line-up width by 30 millimetres (1.2”).
• The standard depth of the cabinet line-up is 650 mm (excluding door equipment
such as switches and air inlet gratings). This is increased by 130 millimetres
(5.1”) with top entry/exit models as well as units with cooling air intake through the
bottom of the cabinet.
• The measurements given apply to 6-pulse-input, non-UL/CSA units. For
dimensions of 12-pulse-input or UL/CSA units, contact your local ABB
representative.
The tables are followed by example dimensional drawings.
R6
Width Net weight
(kg approx.)
400 300
R7i
Drive Common Sine filter Line-up Net weight
motor cubicle width (kg approx.)
terminal
cubicle*
600 600 400
600 300** 300 900 480
600 400** 1000 650
*Added with filter options +E202 or +E205 if option +E206 (sine filter)
is not present. +H359 is not available without +E202/+E205.
**The output (motor) terminals are contained within this cubicle.
Dimensions
158
R8i
Input/Output Supply and Common Sine filter Line-up Net weight
cubicle inverter motor cubicle width (kg approx.)
unit cubicle terminal
cubicle*
400 800 1200 950
400 800 300** 1500 1030
400 800 400** 1600 1200
*Added with filter option +E202 if option +E206 (sine filter) is not present.
+H359 is not available without +E202.
**The output (motor) terminals are contained within this cubicle.
2×R8i
Incoming cubicle
Auxiliary control/
terminal cubicle
Common motor
Shipping split 1
Shipping split 2
Joining cubicle
EMC/RFI filter
Line-up width
(kg approx.)
Inverter unit
Supply unit
Net weight
Sine filter
Sine filter
cubicle 1
cubicle 2
cubicle
cubicle
cubicle
width
width
1000 800 600 2400 2400 1910
1000 800 600 300 2700 2700 1975
1000 300 800 600 2700 2700 1990
1000 300 800 600 300 3000 3000 2070
1000 800 600 1000 3400 3400 2360
1000 300 800 600 1000 3700 3700 2440
1000 800 600 300 1000 1000 2400 2300 4700 2875
3×R8i
Incoming cubicle
Auxiliary control/
terminal cubicle
Common motor
Shipping split 1
Shipping split 2
Joining cubicle
Line-up width
(kg approx.)
Inverter unit
Supply unit
Supply unit
Net weight
Sine filter
Sine filter
cubicle 1
cubicle 2
cubicle 1
cubicle 2
cubicle
width
width
Dimensions
159
4×R8i
Incoming cubicle
Auxiliary control/
terminal cubicle
Common motor
Shipping split 1
Shipping split 2
Joining cubicle
Line-up width
(kg approx.)
Inverter unit
Inverter unit
Supply unit
Supply unit
Net weight
Sine filter
Sine filter
Sine filter
Top entry
cubicle 1
cubicle 2
cubicle 1
cubicle 2
cubicle 1
cubicle 2
cubicle 3
width
width
1000 800 800 600 600 3800 3800 3380
1000 300 800 800 600 600 4100 4100 3460
1000 800 800 600 600 400 4200 4200 3455
1000 300 800 800 600 600 * 400* 3900 600 4500 3535
1000 800 800 600 600 300 1000 1000 3800 2300 6100 4360
1000 300 800 800 600 600 300 1000 1000 4100 2300 6400 4440
1000 800 800 600 600 300 1000 1000 1000 3800 3300 7100 4810
1000 300 800 800 600 600 300 1000 1000 1000 4100 3300 7400 4890
*The common motor terminal cubicle also acts as a joining cubicle.
5×R8i
Incoming cubicle
Joining cubicle 1
Joining cubicle 2
Auxiliary control/
terminal cubicle
Common motor
Shipping split 1
Shipping split 2
Shipping split 3
Line-up width
(kg approx.)
Inverter unit
Inverter unit
Supply unit
Supply unit
Supply unit
Net weight
Sine filter
Sine filter
Sine filter
Top entry
cubicle 1
cubicle 2
cubicle 3
cubicle 1
cubicle 2
cubicle 1
cubicle 2
cubicle 3
width
width
width
1000 800 800 800 800 600 300 3700 1400 5100 4270
1000 300 800 800 800 800 600 300 4000 1400 5400 4350
1000 800 800 800 800 600 * 600* 3400 2000 5400 4305
1000 300 800 800 800 800 600 * 600* 3700 2000 5700 4385
1000 800 800 800 800 600 300 300 1000 1000 1000 3700 1400 3300 8400 5700
1000 300 800 800 800 800 600 300 300 1000 1000 1000 4000 1400 3300 8700 5780
*The common motor terminal cubicle also acts as a joining cubicle.
6×R8i
Incoming cubicle
Joining cubicle 1
Joining cubicle 2
Auxiliary control/
terminal cubicle
Common motor
Shipping split 1
Shipping split 2
Shipping split 3
Line-up width
(kg approx.)
Inverter unit
Inverter unit
Supply unit
Supply unit
Supply unit
Net weight
Sine filter
Sine filter
Sine filter
Top entry
cubicle 1
cubicle 2
cubicle 3
cubicle 1
cubicle 2
cubicle 1
cubicle 2
cubicle 3
width
width
width
1000 800 800 800 800 800 300 3700 1600 5300 4420
1000 300 800 800 800 800 800 300 4000 1600 5600 4500
1000 800 800 800 800 800 * 600* 3400 2200 5600 4455
1000 300 800 800 800 800 800 * 600* 3700 2200 5900 4535
1000 800 800 800 800 800 300 300 1000 1000 1000 3700 1600 3300 8600 5850
1000 300 800 800 800 800 800 300 300 1000 1000 1000 4000 1600 3300 8900 5930
*The common motor terminal cubicle also acts as a joining cubicle.
Dimensions
160
Frame R6
Dimensions
161
[Frame R6 continued]
Dimensions
162
Frame R7i
Dimensions
163
Dimensions
164
Dimensions
165
Dimensions
166
Dimensions
167
Dimensions
168
Dimensions
169
Dimensions
170
Dimensions
171
Dimensions
172
Dimensions
173
Dimensions
174
Dimensions
175
Dimensions
176
Dimensions
177
Dimensions
178
Frame R8i
Dimensions
179
Dimensions
180
Dimensions
181
Dimensions
182
Dimensions
183
Dimensions
184
Dimensions
185
Dimensions
186
Frame 2×R8i
Dimensions
187
Dimensions
188
Dimensions
189
Dimensions
190
Dimensions
191
Dimensions
192
Dimensions
193
Dimensions
194
Dimensions
195
Dimensions
196
Frame 3×R8i
Dimensions
197
Dimensions
198
Dimensions
199
Dimensions
200
Dimensions
201
Dimensions
202
Frame 4×R8i
Dimensions
203
Dimensions
204
Dimensions
205
Dimensions
206
Dimensions
207
Dimensions
208
Frame 5×R8i
Dimensions
209
Dimensions
210
Dimensions
211
Dimensions
212
Dimensions
213
Dimensions
214
Dimensions
215
Dimensions
216
Dimensions
217
Dimensions
218
Dimensions
219
Dimensions
220
Frame 6×R8i
Dimensions
221
Dimensions
222
Dimensions
223
Dimensions
224
Dimensions
225
Dimensions
226
Dimensions
227
Dimensions
228
Dimensions
229
Dimensions
230
Dimensions
231
Dimensions
232
Dimensions
233
234
Further information
Product and service inquiries
Address any inquiries about the product to your local ABB representative, quoting the type
designation and serial number of the unit in question. A listing of ABB sales, support and service
contacts can be found by navigating to www.abb.com/drives and selecting Sales, Support and
Service network.
Product training
For information on ABB product training, navigate to www.abb.com/drives and select Training
courses.