Nothing Special   »   [go: up one dir, main page]

Application Manual-Cement

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Cement, Stone & Mining

Application Solutions with

RVS-DN Digital Soft Starters


8-2700A, 220-1000V
RVS-DN Digital Soft Starter
Range : 8-2700A, 220-1000V, 40-65Hz

This heavy duty, fully featured line is Solcon's second


generation of digital soft starters. The RVS-DN
incorporates superior start-stop characteristics
providing solutions for the most demanding applications
in a cement plant and quarry industries.
The comprehensive motor protection package included
in this starter guarantees long term reliability, while the Quarry Conveyor 220KW
robust design ensures excellent performance in harsh
environments.

Advantages at a Glance
Supervision & Operation
• Heavy duty, Fully rated design (ambient 50°C)
• Robust construction
Interactive LCD Display
• Smooth, stepless acceleration & deceleration
English, French, German, Spanish
• Reduced inrush current & mechanical shock
• Superior starting and stopping characteristics
Advanced Statistical Data Menu
• Comprehensive motor protection
Enhancing operation and maintenance
• Maintenance free - all solid state
• Easy installation and operation supervision.
• Unique optional features: Motor Insulation Tester
RS-485 Communication Communication
Analogue Output RS-485 for full control and supervision.
Thermistor Input Supervision & Operation
Tachometer Control
Starting from Diesel Generator
Special starting parameters while
frequency variates 40-65Hz and
voltage drops.

Torque and Current Control


Designed to prevent:
• Convyor belt strech during starting
• Eliminates balance weight fluctuation while starting

Slow Speed with Electronic Reversing


Motor operates at slow speed of 1/6 nominal speed for
30 sec. with selectable Forward / Reverse directions
Excellent for conveyor, pocket elevators, maintenance
and hammermill positioning.
Fan & Blowers (450KW Fan) Conveyor Belts (Three 250KW motors) Air Compressors (250-450KW)

Comprehensive Motor Protection Package


• Too many starts & start inhibit time
• Long start time (stall protection)
• Electronic fuse with adjustable shear-pin
• Electronic overload with selectable curves
• Under current Hammer-Mills 250KW
• Phase loss
• Phase sequence and Under/Over frequency
• Under/Over voltage
• Load loss (motor not connected)
• External fault
• Shorted SCR
• Starter over temperature protection
• Motor Insulation Alarm/Trip - Early
warning, automatic, low motor insulation
level - for online and communication
monitoring (option)
• Motor Thermistor – measures thermistor's
resistance and provides on-line data Transportable Systems (90KW)
(option)

Typical Applications
• Conveyors
• Compressors
• Pocket Elevetors
• Fans and Blowers
• Crushers and Hammer mills
• Pumps (Cement and Crude material handeling)
• Starting from Diesel Generators (at remote
locations) HRVS-DN
Medium Voltage Digital Soft Starters
1000 - 50A, 2300 - 7200V.
Including Intelligent Pump Control.
See our HRVS-DN Medium Voltage
Soft-Starters Catalogue .
Selector Guide 8-2700A, 220-1000V
Starter Motor KW Frame
Type (Ampere) 480-440V Size
RVS-DN 8 4
RVS-DN 17 7.5 A B
RVS-DN 31 15
RVS-DN 44 22 A
RVS-DN 58 30
RVS-DN 72 37
RVS-DN 105 55
RVS-DN 145 75 B
RVS-DN 170 90
RVS-DN 210 110
RVS-DN 310 160 C
RVS-DN 390 200
C D
RVS-DN 460 250
RVS-DN 580 315 D
RVS-DN 820 450
RVS-DN 1100 630
RVS-DN 1400 800 E
RVS-DN 1800 950
RVS-DN 2150 1250 F
RVS-DN 2400 1400 G
RVS-DN 2700 1550

Dimensions (mm) & Weight (Kg)


Size Width Height Depth Weight
A 150 310 170-217 4.5-7.4
B 274 370 222 15
C 536-590 500 290 45 E F
D 623 660 290 65
E 723 1100 361 170
F 750 1300 392 235
G 900 1300 360 350

Office : Plant :
Solcon Industries Ltd. Solcon Industries Ltd.
16 Haminhara Street, Herzliya 46586, Israel 6 Hacarmel Street, Yokneam 20692, Israel
Tel. +972-9-9588460, Fax +972-9-9500799 Tel. +972-4-9890311, Fax +972-4-9890233
e-mail: office@solcon.co.il e-mail : plant@solcon.co.il
site: www.solcon.co.il site: www.solcon.co.il

M:\Catalogs and Marketing materials\Applications\Cement\cement-application-manual-GT.doc