Dear Gaurav,
This has reference to tagging system for cable and cable tray.
Please find the tagging procedure as we have discussed now.
You may please update and resend wherever further correction is required.
1
iii) Source Panel with area code-Destination Panel with area code-C0-Sequence number
MRSS2-33KVSWB12-CRM2-UTL-33KVSWBD5-C0-XXX
i) Power Cable
CGL4.E1-Source Panel-Destination pane/equipment tag-P0-Sequence number
Example: CGL4.E1-LVDB1-P16-P1-XXX
(It is going from Entry ECR LVDB 1 to Pump-16)
AMNS Comment:
CGL4.E1-Source Panel-Destination pane.Feeder number/equipment tag-P0-Sequence number
CGL4.E1-LVDB1.F02-P16-P1-XXX
(It is going from Entry ECR LVDB 1 (Feeder F02) to Pump-16)
AMNS Comment:
CGL4.E1-Source Panel.Terminal Number-Destination pane/equipment tag-P0-Sequence number
Example: CGL4.E1-RIO1.X001-P16-C1-XXX
E1=Entry ECR
E2-Intermediate ECR
E3=Exit ECR
Area Code-Route Number-Tray Layer (bottom most being /Left most being 1)-H/M/L/C/S
H= 33 KV Cable Tray
M=6.6 kV Cable Tray
L= 415 V Cable Tray
C=Control Cable Tray
S=Signal Cable Tray
2
Example: CGL4.F.1.6-S
( It is at CGL#4 furnace area route 1 and 6 number tray from bottom and carrying signal cable).
Regards,
Sukamal Ghosh
Dear All,
We need to finalise the cable and cable tray numbering system for CRM-2 plant.
Please share if there is any existing designation system
Lets take CRM-2 number as 178 in AMNS Hazira. You may inform if there is any other number.
Plant Number: PLTCM-1, CGAL-2, CGL#3-3 and CGL#4-4, Utility area-5, Finishing area-6.
ECR Designation: CGL#4 has three ECR so, entry will be 1, intermediate will 2 and exit will be 3. Utility has one ECR so
it will be 1.
Voltage Code: 0 is MV cable, 1 is LV cable, 2 is control cable 110 V, 3 is instrument cable 24 V.
Example:
LV Power cable coming from CGL#4 entry ECR:
CRM2.4.E1.SWBD1-Destination tag-P0-Sequence number
Regards,
Sukamal Ghosh
3
From: Banerjee, Biplab <biplab.banerjee@primetals.com>
Sent: 21 February 2022 12:03
To: Ghosh, Sukamal <sukamal.ghosh@arcelormittal.com>
Cc: Kundu, Kinkini <kinkini.kundu@primetals.com>
Subject: RE: C.ETMT: Cable Tray/Route designation system
Please give us if you have any reference for Route and Tray numbering system.
Best regards,
Biplab Banerjee
-----Original Appointment-----
From: Banerjee, Biplab
Sent: 18 February 2022 13:00
To: Banerjee, Biplab; Ghosh, Sukamal; Kundu, Kinkini
Subject: C.ETMT: Cable Tray/Route designation system
When: 18 February 2022 17:00-17:30 (UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi.
Where: Microsoft Teams Meeting
________________________________________________________________________________
________________________________________________________________________________