Nothing Special   »   [go: up one dir, main page]

Product Data Sheet: Trihal Cast Resin Dry Type Transformer 800 kVA 10 KV GOST Dyn11 IP00

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Product data sheet

Specifications

Trihal Cast Resin dry type


transformer 800 kVA 10 kV GOST
Dyn11 IP00
TRI0800175498IP000

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product range Trihal

Product or component type Dry type transformer

Network type AC

Directives 2015/2014/548/EC- ecodesign

Type of installation Indoor

Maximum altitude < 1000 m

Cooling mode AN (air natural)

Winding material Aluminium

Insulation material Cast resin (HV)


Pre-impregnated (LV)

Degree of protection IP00 GOST

Mounting mode Fixed

Complementary
Phase 3 phases

Rated power 800 kVA

Rated frequency 50 Hz

Rated primary voltage 10 kV

Secondary voltage ( at no-load) No load: 400 V

Insulation voltage to industrial 17.5 kV AC primary


frequency ( 50 Hz 1 mn) 1.1 kV AC secondary

Rated insulation level Primary circuit: 38 kV AC


Secondary circuit: 10 kV AC

Lighting impulse whistand 95 kV


voltage ( BIL) , 1.2/50 µs

Vector group Dyn11

HV tappings (off circuit) +/- 2 x 2.5 %

Short circuit impedance 6 %

No-load losses 2000 W

Load losses at 75°C/120 °C 10000 W at 120 °C

Temperature rise of windings 100 K (winding)

Mar 3, 2022 1
Thermal class F

Sound power level 72 dB at 1 m

Protective relay 6.0 PTC relay


1.0 Ziehl relay

Height 1685 mm

Width 831 mm

Length 1558 mm

Total weight 1873 kg

Environment
Ambient air temperature for -25…40 °C for C4
operation

Ambient air temperature for -50…40 °C C4


storage

Environmental certification 0…95 % (E4)

Fire certificate F1

Standards IEC 60076-11:2018

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Weight 1190 kg

Package 1 Height 143.7 cm

Package 1 width 79.5 cm

Package 1 Length 126.3 cm

Offer Sustainability
EU RoHS Directive Not applicable, out of EU RoHS legal scope

2
Mar 3, 2022

You might also like