1 IEC applications
1.1 General notes
Protection for safety must be provided in accordance with
• IEC 60364 standard series
• any additional local standards and regulations for electrical installations.
The tables below provide information for each drive type and article number on the
following items:
• Suitable protective devices.
The specification includes the type and the maximum rated current of the branch
circuit protective devices.
• Maximum ICC (conditional short circuit current)
This is the maximum RMS value of a prospective short circuit current, available from a
supply source.
• Minimum enclosure volume.
In the end application, the drive shall be installed in an outer enclosure or control
cabinet which shall meet the minimum enclosure volume requirement.
16 A 3RV1031-4AA.. ¹⁾ 65 kA
14 A 3RV2031-4SA.. 65 kA
0.55 kW 6SL3210-1PB13-0...
16 A 3RV2011-4AA.. 65 kA
16 A 3RV2021-4AA.. 65 kA
FSA 0.03 m³ 1.06 ft³
16 A 3RV1031-4AA.. ¹⁾ 65 kA
6SL3210-1PB13-8... 14 A 3RV2031-4SA.. 65 kA
0.75 kW
6SL3211-1PB13-8... 16 A 3RV2011-4AA.. 65 kA
16 A 3RV2021-4AA.. 65 kA
32 A 3RV1031-4EA.. ¹⁾ 65 kA
1.1 kW 6SL3210-1PB15-5... 32 A 3RV2021-4EA.. 65 kA
32 A 3RV2031-4EA.. 65 kA
32 A 3RV1031-4EA.. ¹⁾ 65 kA
FSB 1.5 kW 6SL3210-1PB17-4... 32 A 3RV2021-4EA.. 65 kA 0.06 m³ 2.12 ft³
32 A 3RV2031-4EA.. 65 kA
32 A 3RV1031-4EA.. ¹⁾ 65 kA
6SL3210-1PB21-0…
2.2 kW 32 A 3RV2021-4EA.. 65 kA
6SL3211-1PB21-0…
32 A 3RV2031-4EA.. 65 kA
50 A 3RV1031-4HA.. ¹⁾ 65 kA
3.0 kW 6SL3210-1PB21-4... 50 A 3RV1041-4HA.. ¹⁾ 65 kA
45 A 3RV2031-4VA.. 65 kA
50 A 3RV1031-4HA.. ¹⁾ 65 kA
6SL3210-1PB21-8…
4.0 kW 50 A 3RV1041-4HA.. ¹⁾ 65 kA
6SL3211-1PB21-8…
45 A 3RV2031-4VA.. 65 kA
FSC 0.144 m³ 5.085 ft³
50 A 3RV1031-4HA.. ¹⁾ 65 kA
6SL3210-1PC22-2…
5.5 kW 50 A 3RV1041-4HA.. ¹⁾ 65 kA
6SL3211-1PC22-2…
45 A 3RV2031-4VA.. 65 kA
50 A 3RV1031-4HA.. ¹⁾ 65 kA
6SL3210-1PC22-8…
7.5 kW 50 A 3RV1041-4HA.. ¹⁾ 65 kA
6SL3211-1PC22-8…
45 A 3RV2031-4VA.. 65 kA
50 A 3RV1031-4HA.. ¹⁾ 65 kA
65 A 3RV2031-4JA.. 65 kA
65 A 3RV2032-4JA.. 65 kA
11.0 kW 6SL3210-1PC24-2... 63 A 3RV1041-4JA.. ¹⁾ 65 kA
63 A 3RV1042-4JA.. ¹⁾ 65 kA
63 A 3RV2041-4JA.. 65 kA
63 A 3RV2042-4JA.. 65 kA
73 A 3RV2031-4KA.. 65 kA
73 A 3RV2032-4KA.. 65 kA
FSD 75 A 3RV1041-4KA.. ¹⁾ 65 kA - -
15.0 kW 6SL3210-1PC25-4...
75 A 3RV1042-4KA.. ¹⁾ 65 kA
75 A 3RV2041-4KA.. 65 kA
75 A 3RV2042-4KA.. 65 kA
73 A 3RV2031-4KA.. 65 kA
73 A 3RV2032-4KA.. 65 kA
6SL3210-1PC26-8… 90 A 3RV1042-4LA.. ¹⁾ 65 kA
18.5 kW
6SL3211-1PC26-8… 90 A 3RV1041-4LA.. ¹⁾ 65 kA
93 A 3RV2041-4YA.. 65 kA
93 A 3RV2042-4YA.. 65 kA
1) The protective device is not recommended for future use, because already phased-out or will be soon.
2) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical regulations
may be used, if suitable for application.
Note:
ICC values are only valid for supply grids with grounded star point (solidly grounded wye TN or TT systems).
20 A 3RV1031-4BA.. 1) 12 kA
11.0 kW 6SL3210-1PH21-4… 20 A 3RV2031-4BA.. 12 kA
20 A 3RV2032-4BA.. 18 kA
32 A 3RV1031-4EA.. 1) 10 kA
15.0 kW 6SL3210-1PH22-0… 32 A 3RV2031-4EA.. 10 kA
32 A 3RV2032-4EA.. 15 kA
32 A 3RV1031-4EA.. 1) 10 kA
18.5 kW 6SL3210-1PH22-3… 32 A 3RV2031-4EA.. 10 kA
32 A 3RV2032-4EA.. 15 kA
40 A 3RV1031-4FA.. 1) 10 kA
40 A 3RV1041-4FA.. 1) 12 kA
40 A 3RV1042-4FA.. 1) 18 kA
22.0 kW 6SL3210-1PH22-7… 40 A 3RV2031-4UA.. 10 kA
40 A 3RV2032-4UA.. 15 kA
40 A 3RV2041-4FA.. 12 kA
40 A 3RV2042-4FA.. 18 kA
FSD - -
50 A 3RV1031-4HA.. 1) 10 kA
50 A 3RV1041-4HA.. 1) 12 kA
50 A 3RV1042-4HA.. 1) 15 kA
30.0 kW 6SL3210-1PH23-5… 52 A 3RV2031-4WA.. 8 kA
52 A 3RV2032-4WA.. 10 kA
50 A 3RV2041-4HA.. 12 kA
50 A 3RV2042-4HA.. 15 kA
50 A 3RV1031-4HA.. 1) 10 kA
63 A 3RV1041-4JA.. 1) 12 kA
63 A 3RV1042-4JA.. 1) 15 kA
52 A 3RV2031-4WA.. 10 kA
37.0 kW 6SL3210-1PH24-2… 52 A 3RV2032-4WA.. 15 kA
59 A 3RV2031-4XA.. 8 kA
59 A 3RV2032-4XA.. 10 kA
63 A 3RV2041-4JA.. 12 kA
63 A 3RV2042-4JA.. 15 kA
1) The protective device is not recommended for future use, because already phased-out or will be soon.
2) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical regulations
may be used, if suitable for application.
Note:
ICC values are only valid for supply grids with grounded star point (solidly grounded wye TN or TT systems).
20 A 3VL1702-2D… ¹⁾ 30 kA
11.0 kW 6SL3210-1PH21-4... 20 A 3VA1020-4ED... 16 kA
20 A 3VA1120-6E... 20 kA
32 A 3VL1703-2D… ¹⁾ 30 kA
15.0 kW 6SL3210-1PH22-0... 32 A 3VA1032-4ED... 16 kA
32 A 3VA1132-6E... 20 kA
32 A 3VL1703-2D… ¹⁾ 30 kA
18.5 kW 6SL3210-1PH22-3... 32 A 3VA1032-4ED... 16 kA
32 A 3VA1132-6E... 20 kA
40 A 3VL1704-2D… ¹⁾ 30 kA
FSD - -
22.0 kW 6SL3210-1PH22-7... 40 A 3VA1040-4ED... 16 kA
40 A 3VA1140-6E... 20 kA
50 A 3VL1705-2D… ¹⁾ 30 kA
50 A 3VL2705-3DC… ¹⁾ 50 kA
30.0 kW 6SL3210-1PH23-5...
50 A 3VA1050-4ED... 16 kA
50 A 3VA1150-6E... 20 kA
63 A 3VL1706-2D… ¹⁾ 30 kA
63 A 3VL2706-3DC… ¹⁾ 50 kA
37.0 kW 6SL3210-1PH24-2...
63 A 3VA1063-4ED... 16 kA
63 A 3VA1163-6E... 20 kA
80 A 3VL1708-2D… ¹⁾ 30 kA
80 A 3VL2708-3DC… ¹⁾ 50 kA
45.0 kW 6SL3210-1PH25-2...
80 A 3VA1080-4ED... 16 kA
80 A 3VA1180-6E... 20 kA
FSE 0.2 m³ 7.06 ft³
100 A 3VL1710-2D… ¹⁾ 30 kA
100 A 3VL2710-3DC… ¹⁾ 50 kA
55.0 kW 6SL3210-1PH26-2...
100 A 3VA1010-4ED... 16 kA
100 A 3VA1110-6E... 20 kA
125 A 3VL1712-2D… ¹⁾ 30 kA
75.0 kW 6SL3210-1PH28-0... 125 A 3VL2712-3DC… ¹⁾ 50 kA
125 A 3VA1112-6E... 20 kA
125 A 3VL1712-2D… ¹⁾ 30 kA
90.0 kW 6SL3210-1PH31-0... 125 A 3VL2712-3DC… ¹⁾ 50 kA
125 A 3VA1112-6E... 20 kA
FSF 0.6 m³ 21.19 ft³
160 A 3VL1716-2D… ¹⁾ 30 kA
160 A 3VL2716-3DC… ¹⁾ 50 kA
110.0 kW 6SL3210-1PH31-2...
160 A 3VA1116-6E... 10 kA
160 A 3VA1216-6EF... 15 kA
200 A 3VL3720-3DC… ¹⁾ 50 kA
132.0 kW 6SL3210-1PH31-4...
200 A 3VA1220-6EF... 15 kA
1) The protective device is not recommended for future use, because already phased-out or will be soon.
2) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical regulations
may be used, if suitable for application.
2 UL/CSA applications
2.1 General notes
Branch circuit protection must be provided in accordance with
• the National Electrical Code (NEC) for USA
• the Canadian Electrical Code (CEC) Part I for Canada
• any additional local codes and regulations.
The tables below provide information for each drive type and article number on the
following items:
• Suitable protective devices.
The specification includes the type and the maximum rated current of the branch
circuit protective devices.
• Maximum SCCR (Short-Circuit Current Rating).
This is the maximum prospective symmetrical fault current at the specified voltage to
which the drive system can be connected without sustaining damage exceeding
defined acceptance criteria. The specified SCCR applies to the complete drive module
including built-in EMI filters and pluggable terminals (where applicable).
• Minimum enclosure volume.
In the end application, the drive shall be installed in an outer enclosure or control
cabinet which shall meet the minimum enclosure volume requirement.
Notes on the selection of protective devices (in accordance with NEC and CEC)
• Suitable Protective devices of the same type as specified in the tables with a lower
ampere rating may be used, if suitable for the application.
• Protective devices of the same type as specified in the tables with a lower
interrupting rating than the specified SCCR may be used, if suitable for the
application. In such case, this lower interrupting current rating of a protective device
shall be specified as the SCCR of a drive and protective device combination.
• The voltage rating of the protective device must be at least the voltage rating of the
supply circuit.
The Power Modules provide:
• Integral Motor Overload Protection which reduces the output current flow under
overload conditions. Refer to manual for adjustments.
• Integral Output Short-Circuit Protection.
According to UL 508A Edition 3, components on the load side of a drive module with
built-in short circuit protection are not required to have a short-circuit current rating.
UL File-Numbers
FSA, FSB, FSC: 240 V UL-File E121068, Vol. 2 Sec. 29
FSA, FSB, FSC: 480 V UL-File E121068, Vol. 2 Sec. 27
FSD, FSE, FSF, FSG: 240 V/480 V/600 V UL-File E355661, Vol. 6 Sec. 4
Note:
The power modules are investigated to the US standard UL 61800-5-1. Please note that
the FSA-C were previously investigated to the US standard UL 508C, which has
meanwhile been withdrawn. This may entail restrictions in terms of suitable protective
devices, SCCR and cabinet size data compared to previous information.
Note:
3RV20 motor starter protectors are approved in accordance with UL 508/UL60947-4-1 in combination with the terminal blocks listed below:
− 3RV2011 and 3RV2021 with 3RV2928-1H
− 3RV203. with 3RV2938-1K
− 3RV204. with 3RT2946-4GA07
Not necessary for CSA
3RV104 motor starter protectors are approved in accordance with UL 508/UL60947-4-1 in combination with the 3RT1946-4GA07
terminal blocks.
10 A 5 HP 3RV2011-1JA.. 65 kA
10 A 5 HP 3RV2021-1JA.. 65 kA
0.55 kW 6SL3210-1PE11-8...
14 A 10 HP 3RV2031-4SA.. 65 kA
14 A 10 HP 3RV2032-4SA.. 100 kA
10 A 5 HP 3RV2011-1JA.. 65 kA
10 A 5 HP 3RV2021-1JA.. 65 kA
0.75 kW 6SL3210-1PE12-3...
14 A 10 HP 3RV2031-4SA.. 65 kA
14 A 10 HP 3RV2032-4SA.. 100 kA
17 A 15 HP 3RV2031-4TA 65 kA
17 A 15 HP 3RV2032-4TA1 100 kA
1.1 kW 6SL3210-1PE13-2...
16 A 10 HP 3RV2011-4AA.. 65 kA
16 A 10 HP 3RV2021-4AA.. 65 kA
FSA 0.06 m³ 2.12 ft³
17 A 15 HP 3RV2031-4TA.. 65 kA
17 A 15 HP 3RV2032-4TA1 100 kA
1.5 kW 6SL3210-1PE14-3…
16 A 10 HP 3RV2011-4AA.. 65 kA
16 A 10 HP 3RV2021-4AA.. 65 kA
17 A 15 HP 3RV2031-4TA.. 65 kA
17 A 15 HP 3RV2032-4TA1 100 kA
2.2 kW 6SL3210-1PE16-1...
16 A 10 HP 3RV2011-4AA.. 65 kA
16 A 10 HP 3RV2021-4AA.. 65 kA
17 A 15 HP 3RV2031-4TA.. 65 kA
6SL3210-1PE18-0… 17 A 15 HP 3RV2032-4TA1 100 kA
3.0 kW
6SL3211-1PE18-0… 16 A 10 HP 3RV2011-4AA.. 65 kA
16 A 10 HP 3RV2021-4AA.. 65 kA
17 A 15 HP 3RV2031-4TA.. 65 kA ³⁾
25 A 15 HP 3RV2021-4DA.. 65 kA ³⁾
4.0 kW 6SL3210-1PE21-1... 32 A 20 HP 3RV2021-4EA.. 50 kA ³⁾
32 A 25 HP 3RV2031-4EA.. 65 kA ³⁾
32 A 25 HP 3RV2032-4EA.. 65 kA ³⁾
25 A 15 HP 3RV2021-4DA.. 65 kA ³⁾
FSB 32 A 20 HP 3RV2021-4EA.. 50 kA ³⁾ 0.144 m³ 5.085 ft³
5.5 kW 6SL3210-1PE21-4...
32 A 25 HP 3RV2031-4EA.. 65 kA ³⁾
32 A 25 HP 3RV2032-4EA.. 65 kA ³⁾
25 A 15 HP 3RV2021-4DA.. 65 kA ³⁾
6SL3210-1PE21-8… 32 A 20 HP 3RV2021-4EA.. 50 kA ³⁾
7.5 kW
6SL3211-1PE21-8… 32 A 25 HP 3RV2031-4EA.. 65 kA ³⁾
32 A 25 HP 3RV2032-4EA.. 65 kA ³⁾
52 A 40 HP 3RV2031-4WA1.. 65 kA ³⁾
11.0 kW 6SL3210-1PE22-7...
52 A 40 HP 3RV2032-4WA1.. 65 kA ³⁾
FSC 0.144 m³ 5.085 ft³
6SL3210-1PE23-3… 52 A 40 HP 3RV2031-4WA1.. 65 kA ³⁾
15.0 kW
6SL3211-1PE23-3… 52 A 40 HP 3RV2032-4WA1.. 65 kA ³⁾
63 A 50 HP 3RV1041-4JA.. ¹⁾ 65 kA
63 A 50 HP 3RV1042-4JA.. ¹⁾ 65 kA
65 A 50 HP 3RV2031-4JA.. 20 kA
FSD 18.5 kW 6SL3210-1PE23-8... - -
65 A 50 HP 3RV2032-4JA.. 30 kA
63 A 50 HP 3RV2041-4JA.. 65 kA
63 A 50 HP 3RV2042-4JA.. 65 kA
1) The protective device is not recommended for future use, because already phased-out or will be soon.
2) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
and regulations may be used, if suitable for application.
3) For SCCR up to 5 kA no line reactor is required. For SCCR > 5 kA dedicated line reactor is required. Refer to manual.
4) For details and more article numbers, please refer to the catalog links in section 3.
Note:
3RV20 motor starter protectors are approved in accordance with UL 508/UL60947-4-1 in combination with the terminal blocks listed below:
− 3RV2011 and 3RV2021 with 3RV2928-1H
− 3RV203. with 3RV2938-1K
− 3RV204. with 3RT2946-4GA07
Not necessary for CSA
3RV104 motor starter protectors are approved in accordance with UL 508/UL60947-4-1 in combination with the 3RT1946-4GA07
terminal blocks.
75 A 60 HP 3RV1041-4KA.. ¹⁾ 65 kA
75 A 60 HP 3RV1042-4KA.. ¹⁾ 65 kA
73 A 60 HP 3RV2031-4KA.. 20 kA
22.0 kW 6SL3210-1PE24-5...
73 A 60 HP 3RV2032-4KA.. 30 kA
75 A 60 HP 3RV2041-4KA.. 65 kA
75 A 60 HP 3RV2042-4KA.. 65 kA
90 A 75 HP 3RV1041-4LA.. ¹⁾ 65 kA
FSD - -
90 A 75 HP 3RV1042-4LA.. ¹⁾ 65 kA
30.0 kW 6SL3210-1PE26-0...
93 A 75 HP 3RV2041-4YA.. 65 kA
93 A 75 HP 3RV2042-4YA.. 65 kA
100 A 75 HP 3RV1041-4MA.. ¹⁾ 65 kA
6SL3210-1PE27-5… 100 A 75 HP 3RV1042-4MA.. ¹⁾ 65 kA
37.0 kW
6SL3211-1PE27-5… 100 A 75 HP 3RV2041-4MA.. 65 kA
100 A 75 HP 3RV2042-4MA.. 65 kA
1) The protective device is not recommended for future use, because already phased-out or will be soon.
2) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
and regulations may be used, if suitable for application.
3) For details and more article numbers, please refer to the catalog links in section 3.
Note:
3RV20 motor starter protectors are approved in accordance with UL 508/UL60947-4-1 in combination with the terminal blocks listed below:
− 3RV2011 and 3RV2021 with 3RV2928-1H
− 3RV203. with 3RV2938-1K
− 3RV204. with 3RT2946-4GA07
Not necessary for CSA
3RV104 motor starter protectors are approved in accordance with UL 508/UL60947-4-1 in combination with the 3RT1946-4GA07
terminal blocks.
20 A 20 HP 3RV1031-4BA.. ¹⁾ 25 kA
11.0 kW 6SL3210-1PH21-4… 20 A 20 HP 3RV2031-4BA.. 25 kA
20 A 20 HP 3RV2032-4BA.. 25 kA
32 A 30 HP 3RV1031-4EA.. ¹⁾ 25 kA
15.0 kW 6SL3210-1PH22-0… 32 A 30 HP 3RV2031-4EA.. 25 kA
32 A 30 HP 3RV2032-4EA.. 25 kA
32 A 30 HP 3RV1031-4EA.. ¹⁾ 25 kA
18.5 kW 6SL3210-1PH22-3… 32 A 30 HP 3RV2031-4EA.. 25 kA
32 A 30 HP 3RV2032-4EA.. 25 kA
40 A 40 HP 3RV1031-4FA.. ¹⁾ 25 kA
40 A 40 HP 3RV1041-4FA.. ¹⁾ 30 kA
40 A 40 HP 3RV1042-4FA.. ¹⁾ 30 kA
22.0 kW 6SL3210-1PH22-7… 40 A 40 HP 3RV2031-4UA.. 22 kA
40 A 40 HP 3RV2032-4UA.. 22 kA
40 A 40 HP 3RV2041-4FA.. 30 kA
FSD - -
40 A 40 HP 3RV2042-4FA.. 30 kA
50 A 50 HP 3RV1031-4HA.. ¹⁾ 25 kA
50 A 50 HP 3RV1041-4HA.. ¹⁾ 30 kA
50 A 50 HP 3RV1042-4HA.. ¹⁾ 30 kA
30.0 kW 6SL3210-1PH23-5… 52 A 50 HP 3RV2031-4WA.. 22 kA
52 A 50 HP 3RV2032-4WA.. 22 kA
50 A 50 HP 3RV2041-4HA.. 30 kA
50 A 50 HP 3RV2042-4HA.. 30 kA
50 A 50 HP 3RV1031-4HA.. ¹⁾ 25 kA
63 A 60 HP 3RV1041-4JA.. ¹⁾ 30 kA
63 A 60 HP 3RV1042-4JA.. ¹⁾ 30 kA
37.0 kW 6SL3210-1PH24-2… 52 A 50 HP 3RV2031-4WA.. 22 kA
52 A 50 HP 3RV2032-4WA.. 22 kA
63 A 60 HP 3RV2041-4JA.. 30 kA
63 A 60 HP 3RV2042-4JA.. 30 kA
1) The protective device is not recommended for future use, because already phased-out or will be soon.
2) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
and regulations may be used, if suitable for application.
3) For details and more article numbers, please refer to the catalog links in section 3.
Note:
3RV20 motor starter protectors are approved in accordance with UL 508/UL60947-4-1 in combination with the terminal blocks listed below:
− 3RV2011 and 3RV2021 with 3RV2928-1H
− 3RV203. with 3RV2938-1K
− 3RV204. with 3RT2946-4GA07
Not necessary for CSA
3RV104 motor starter protectors are approved in accordance with UL 508/UL60947-4-1 in combination with the 3RT1946-4GA07
terminal blocks.
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
90 A NGG - 65 kA
90 A HGG - 65 kA
90 A LGG - 65 kA
90 A NCGA 3VL1191-1KM.. ⁴⁾ 65 kA
90 A HCGA 3VL1191-2KM.. ⁴⁾ 65 kA
90 A NDGB 3VL2591-1KN.. ⁴⁾ 65 kA
90 A HDGB 3VL2591-2KN.. ⁴⁾ 65 kA
90 A LDGB 3VL2591-3KN.. ⁴⁾ 65 kA
90 A CED6 - 100 kA
90 A FXD6-A - 65 kA
90 A FD6-A - 65 kA
90 A HFD6 - 100 kA
6SL3210-1PC26-8... 90 A HFXD6 - 100 kA
FSD 18.5 kW - -
6SL3211-1PC26-8... 90 A HHFD6 - 100 kA
90 A HHFXD6 - 100 kA
90 A CFD6 - 100 kA
100 A SEAS (3VA51) 3VA5110-4E.. 65 kA
100 A MEAS (3VA51) 3VA5110-5E.. 85 kA
100 A HEAS (3VA51) 3VA5110-6E.. 100 kA
MDAE, HDAE, CDAE,
100 A 3VA6110-.... 100 kA
LDAE, EDAE (3VA61)
100 A MFAS (3VA52) 3VA5210-5E.. 85 kA
100 A HFAS (3VA52) 3VA5210-6E.. 100 kA
100 A CFAS (3VA52) 3VA5210-7E.. 100 kA
MFAE-Y, HFAE-Y, CFAE-Y,
100 A 3VA6210-.... 100 kA
LFAE-Y, EFAE-Y (3VA62)
100 A NCGA 3VL1110-1KM.. ⁴⁾ 65 kA
100 A HCGA 3VL1110-2KM.. ⁴⁾ 65 kA
110 A NGG - 65 kA
110 A HGG - 65 kA
110 A LGG - 65 kA
110 A NDGB 3VL2511-1KN.. ⁴⁾ 65 kA
110 A HDGB 3VL2511-2KN.. ⁴⁾ 65 kA
110 A LDGB 3VL2511-3KN.. ⁴⁾ 65 kA
110 A LGG - 65 kA
110 A NFGB 3VL3511-1KN.. ⁴⁾ 65 kA
110 A HFGB 3VL3511-2KN.. ⁴⁾ 65 kA
110 A LFGB 3VL3511-3KN.. ⁴⁾ 65 kA
110 A CED6 - 100 kA
FSE 22.0 kW 6SL3210-1PC28-0... 0.2 m³ 7.06 ft³
110 A FXD6-A - 65 kA
110 A FD6-A - 65 kA
110 A HFD6 - 100 kA
110 A HFXD6 - 100 kA
110 A HHFD6 - 100 kA
110 A HHFXD6 - 100 kA
110 A CFD6 - 100 kA
110 A SEAS (3VA51) 3VA5111-4E.. 65 kA
110 A MEAS (3VA51) 3VA5111-5E.. 85 kA
110 A HEAS (3VA51) 3VA5111-6E.. 100 kA
110 A MFAS (3VA52) 3VA5211-5E.. 85 kA
110 A HFAS (3VA52) 3VA5211-6E.. 100 kA
110 A CFAS (3VA52) 3VA5211-7E.. 100 kA
1) NCGA and HCGA are UL listed 3VL11 series (Siemens type VL150x UL) circuit breakers shown in the European circuit breaker
catalog LV 16. Other Frame Sizes alike.
2) For details and more article numbers, please refer to the catalog links in section 3.
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
15 A 3RV2742 3RV2742-5BD.. 5 kA 4)
0.55 kW 6SL3210-1PE11-8...
15 A 3RV2711 3RV2711-4AD.. --- 65 kA
15 A 3RV2742 3RV2742-5BD.. 5 kA 4)
0.75 kW 6SL3210-1PE12-3...
15 A 3RV2711 3RV2711-4AD.. --- 65 kA
15 A 3RV2742 3RV2742-5BD.. 5 kA 4)
1.1 kW 6SL3210-1PE13-2...
15 A 3RV2711 3RV2711-4AD.. --- 65 kA
FSA 0.06 m³ 2.12 ft³
15 A 3RV2742 3RV2742-5BD.. 5 kA 4)
1.5 kW 6SL3210-1PE14-3...
15 A 3RV2711 3RV2711-4AD.. --- 65 kA
15 A 3RV2742 3RV2742-5BD.. 5 kA 4)
2.2 kW 6SL3210-1PE16-1...
15 A 3RV2711 3RV2711-4AD.. --- 65 kA
6SL3210-1PE18-0... 15 A 3RV2742 3RV2742-5BD.. 5 kA 4)
3.0 kW
6SL3211-1PE18-0... 15 A 3RV2711 3RV2711-4AD.. --- 65 kA
4.0 kW 6SL3210-1PE21-1... 35 A 3RV2742 3RV27452-5FD.. 5 kA 4)
FSC 6SL3210-1PE23-3... 4)
0.144 m³ 5.085 ft³
15.0 kW 50 A 3RV2742 3RV2742-5JD.. 5 kA
6SL3211-1PE23-3...
60 A 3RV1742 3RV1742-5LD.. ⁵⁾ --- 65 kA
60 A 3RV2742 3RV2742-5LD.. --- 65 kA
60 A NGG - 25 kA 4)
60 A HGG - 35 kA 4)
60 A LGG - 65 kA 4)
60 A NCGA 3VL1106-1KM.. ⁵⁾ 35 kA 4)
60 A HCGA 3VL1106-2KM.. ⁵⁾ 65 kA 4)
60 A NDGB 3VL2506-1KN.. ⁵⁾ 35 kA 4)
60 A CED6 - 100 kA 4)
1) NCGA and HCGA are UL listed 3VL11 series (Siemens type VL150x UL) circuit breakers shown in the European circuit breaker
catalog LV 16. Other Frame Sizes alike.
2) For details and more breaker article numbers, please refer to the catalog links in section 3.
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
100 A NGG - 25 kA 4)
100 A HGG - 35 kA 4)
100 A LGG - 65 kA 4)
100 A FXD6-A - 35 kA 4)
100 A FD6-A - 35 kA 4)
100 A HFD6 - 65 kA 4)
100 A HFXD6 - 65 kA 4)
LDAE, EDAE 4)
100 A 3VA6110-8.... 100 kA
(3VA61)
100 A MFAS (3VA52) 3VA5210-5E.. 35 kA 4)
LFAE-Y, EFAE-Y 4)
100 A 3VA6210-8... 100 kA
(3VA62)
1) NCGA and HCGA are UL listed 3VL11 series (Siemens type VL150x UL) circuit breakers shown in the European circuit breaker
catalog LV 16. Other Frame Sizes alike.
2) For details and more breaker article numbers, please refer to the catalog links in section 3.
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
4)
125 A NGG - 25 kA
4)
125 A HGG - 35 kA
4)
125 A LGG - 65 kA
4)
125 A NCGA 3VL1112-1KM.. ⁵⁾ 35 kA
4)
125 A HCGA 3VL1112-2KM.. ⁵⁾ 65 kA
4)
125 A NDGB 3VL2512-1KN.. ⁵⁾ 35 kA
4)
125 A HDGB 3VL2512-2KN.. ⁵⁾ 65 kA
4)
125 A LDGB 3VL2512-3KN.. ⁵⁾ 65 kA
4)
125 A NFGB 3VL3512-1KN.. ⁵⁾ 35 kA
4)
125 A HFGB 3VL3512-2KN.. ⁵⁾ 65 kA
4)
125 A LFGB 3VL3512-3KN.. ⁵⁾ 65 kA
4)
125 A CED6 - 100 kA
45.0 kW 6SL3210-1PE28-8... 125 A FXD6-A - 35 kA 4) 0.2 m³ 7.06 ft³
4)
125 A FD6-A - 35 kA
4)
125 A HFD6 - 65 kA
4)
125 A HFXD6 - 65 kA
4)
125 A HHFD6 - 100 kA
4)
125 A HHFXD6 - 100 kA
4)
125 A CFD6 - 100 kA
4)
125 A SEAS (3VA51) 3VA5112-4E.. 25 kA
4)
125 A MEAS (3VA51) 3VA5112-5E.. 35 kA
4)
125 A HEAS (3VA51) 3VA5112-6E.. 65 kA
4)
125 A MFAS (3VA52) 3VA5212-5E.. 35 kA
4)
125 A HFAS (3VA52) 3VA5212-6E.. 65 kA
FSE 4)
125 A CFAS (3VA52) 3VA5212-7E.. 100 kA
4)
150 A NCGA 3VL1115-1KM.. ⁵⁾ 35 kA
4)
150 A HCGA 3VL1115-2KM.. ⁵⁾ 65 kA
4)
150 A NDGB 3VL2515-1KN.. ⁵⁾ 35 kA
4)
150 A HDGB 3VL2515-2KN.. ⁵⁾ 65 kA
4)
150 A LDGB 3VL2515-3KN.. ⁵⁾ 65 kA
4)
150 A NFGB 3VL3515-1KN.. ⁵⁾ 35 kA
4)
150 A HFGB 3VL3515-2KN.. ⁵⁾ 65 kA
4)
150 A LFGB 3VL3515-3KN.. ⁵⁾ 65 kA
4)
150 A FXD6-A - 35 kA
4)
150 A FD6-A - 35 kA
4)
150 A HFD6 - 65 kA
6SL3210-1PE31-1…
55.0 kW 150 A HFXD6 - 65 kA 4) 0.2 m³ 7.06 ft³
6SL3211-1PE31-1… 4)
150 A HHFD6 - 100 kA
4)
150 A HHFXD6 - 100 kA
4)
150 A CFD6 - 100 kA
4)
150 A MDAE (3VA61) 3VA6115-5.... 35 kA
4)
150 A HDAE (3VA61) 3VA6115-6.... 65 kA
4)
150 A CDAE (3VA61) 3VA6115-7.... 100 kA
LDAE, EDAE
150 A 3VA6115-8.... 100 kA 4)
(3VA61)
4)
150 A MFAS (3VA52) 3VA5215-5E.. 35 kA
4)
150 A HFAS (3VA52) 3VA5215-6E.. 65 kA
4)
150 A CFAS (3VA52) 3VA5215-7E.. 100 kA
1) NCGA and HCGA are UL listed 3VL11 series (Siemens type VL150x UL) circuit breakers shown in the European circuit breaker
catalog LV 16. Other Frame Sizes alike.
2) For details and more breaker article numbers, please refer to the catalog links in section 3.
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
400 A JXD6-A - 35 kA 4)
400 A JD6-A - 35 kA 4)
400 A HJD6-A - 65 kA 4)
400 A HJXD6-A - 65 kA 4)
400 A LD6-A - 35 kA 4)
450 A LXD6-A - 35 kA 4)
400 A HLD6-A - 65 kA 4)
400 A HLXD6-A - 65 kA 4)
160.0 kW 6SL3210-1PE33-0… 0.6 m³ 21.19 ft³
400 A HHLD6 - 100 kA 4)
500 A LD6-A - 35 kA 4)
500 A LXD6-A - 35 kA 4)
500 A HLD6-A - 65 kA 4)
500 A HLXD6-A - 65 kA 4)
1) NCGA and HCGA are UL listed 3VL11 series (Siemens type VL150x UL) circuit breakers shown in the European circuit breaker
catalog LV 16. Other Frame Sizes alike.
2) For details and more breaker article numbers, please refer to the catalog links in section 3.
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
600 A LD6-A - 35 kA 4)
600 A LXD6-A - 35 kA 4)
600 A HLD6-A - 65 kA 4)
600 A HLXD6-A - 65 kA 4)
LLAE, ELAE
600 A 3VA6460-8.. 100 kA 4)
(3VA64)
1) NCGA and HCGA are UL listed 3VL11 series (Siemens type VL150x UL) circuit breakers shown in the European circuit breaker
catalog LV 16. Other Frame Sizes alike.
2) For details and more breaker article numbers, please refer to the catalog links in section 3.
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
110 A HFD6 - 25 kA 4)
110 A HFXD6 - 25 kA 4)
110 A HHFD6 - 25 kA 4)
110 A HHFXD6 - 25 kA 4)
150 A HFD6 - 25 kA 3)
150 A HFXD6 - 25 kA 3)
150 A HHFD6 - 25 kA 3)
150 A HHFXD6 - 25 kA 3)
1) NCGA and HCGA are UL listed 3VL11 series (Siemens type VL150x UL) circuit breakers shown in the European circuit breaker
catalog LV 16. Other Frame Sizes alike.
2) For details and more breaker article numbers, please refer to the catalog links in section 3.
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
150 A FD6-A - 22 kA 4)
150 A HFD6 - 25 kA 4)
150 A HHFXD6 - 25 kA 4)
LDAE, EDAE
150 A 3VA6115-8.... 50 kA 4)
(3VA61)
150 A MFAS (3VA52) 3VA5215-5E.. 18 kA 4)
200 A FD6-A - 22 kA 3)
200 A HFD6 - 25 kA 3)
200 A HFXD6 - 25 kA 3)
200 A HHFD6 - 25 kA 3)
200 A HHFXD6 - 25 kA 3)
200 A JXD6-A - 25 kA 3)
200 A HJXD6-A - 35 kA 3)
200 A HHJD6 - 50 kA 3)
200 A HHJXD6 - 50 kA 3)
1) NCGA and HCGA are UL listed 3VL11 series (Siemens type VL150x UL) circuit breakers shown in the European circuit breaker
catalog LV 16. Other Frame Sizes alike.
2) For details and more breaker article numbers, please refer to the catalog links in section 3.
3) Protective devices of the same type with lower current ratings in accordance with existing applicable local electrical code (e.g. NEC)
3 Further information
For more information, see the following links:
https://support.industry.siemens.com/cs/ww/en/view/109750641
• UL listed Type E CMC or Motor Starter Protectors (MSPs) - 3RV series, see Siemens Industrial Controls
Catalog, Section 1
https://new.siemens.com/us/en/products/automation/industrial-controls/industrial-controls-
catalog.html
• UL listed Molded Case Circuit Breakers - 3VA, SENTRON & VL series, see Siemens SPEEDFAX Product
Catalog, Section 7
https://new.siemens.com/us/en/products/energy/low-voltage/speedfax.html