Flow Sensing Flo-Cross Sensor: Upstream and Downstream Concentric Ring Sensing Port Configuration
Flow Sensing Flo-Cross Sensor: Upstream and Downstream Concentric Ring Sensing Port Configuration
Flow Sensing Flo-Cross Sensor: Upstream and Downstream Concentric Ring Sensing Port Configuration
FLO-CROSS® SENSOR ®
Barbed Fittings
Streamlined Center
Manifolds
Signal Amplification
Baffles
Storage
Units should not be stored outdoors. Units should
UNIT IDENTIFICATION
be covered to protect against dirt, moisture, etc.
AIR
Cartons may be stacked, but not over 5 cartons FLOW
high. Crates must not be stacked.
Handling
Do not handle terminal units by damper rod
extension, tubing connections, Flo-Cross® sen-
sor, or other external attachments. Be careful not
to damage controls when removing units from MODEL NO: SIZE: UP
shipping containers. TOTAL CFM: MIN. CFM:
LOCATION:
FACTORY NO:
Initial Inspection ITEM:
COIL:
ping container, check carefully for damage to duct
THST:
connections, coils or controls. File damage claim
DPR. POSITION:
immediately with transportation agency and notify
Tuttle & Bailey.
MODEL NO: SIZE: MODEL NO: SIZE:
label. Each unit is supplied with an identification FACTORY NO: ITEM: FACTORY NO: ITEM:
label, as shown.
—2—
INSTALLATION ®
ACCESSORY
thermostat rises until the first stage on a N.O. P/E
HANGER switch closes, activating the first stage or reheat.
If the room temperature continues to fall, the rise
in branch pressure will activate the second and third
stages.
UNIT SUSPENSION
DETAILS
OPTIONAL
When used with a D.A. thermostat, normally
(TYPICAL)
HANGER
BRACKET closed P/E switches maintain full electric reheat
HANGER WIRE when the room temperature (and pressure) is low.
ANGLE IRON
As the temperature rises, the P/E switches open,
SHEET METAL SCREW
de-energizing stages of electric heat.
—3—
CONTROLS ®
Tuttle & Bailey offers a wide variety of factory-installed Electronic Analog Controller
controls. The controls provide pressure-independent
control as well as various applications for minimum
90
and maximum flow, hot water, electric heat, warm-up
and sequencing control. 45
HI STAT P
R
R
NO
M water or electric reheat, dual minimum, building
DAMPER RESET SPAN
automation interface.
G
Direct Digital Controls
Tuttle & Bailey factory mounts the Direct Digital
• Flo-Cross® Sensor—integral to the volume control Controls (DDC) of major manufacturers which simpli-
system for the most accurate flow sensing available. fies the integration of Tuttle & Bailey terminal units
• Field adjustment—of maximum and minimum air into Building Automation Systems. All the benefits of
flows easily made with screwdriver and integral flow DDC are available to each individual zone. Tuttle &
chart.
• Reset span—adjustable from 0 to 10 psig (factory Bailey will factory mount, pipe and wire specified
set at 5 psig), when set, remains constant regard- control components on the Tuttle & Bailey terminal
less of maximum/minimum air flow adjustments. unit. When required, an optional enclosure is avail-
• Low air consumption—0.017 SCFM at 20 psig. able to protect control components.
• Direct or reverse acting—thermostat action is field
adjustable. The exclusive, patented Flo-Cross® Sensor is compat-
• Adjustable start point—from 0 to 10 psig to se- ible with most DDC controls on the market today and
quence with auxiliaries such as reheat coils. is recommended for applications requiring factory
• Damper action—field adjustable for normally open mounting of DDC controls. The Flo-Cross® Sensor's
or normally closed. high level of accuracy, regardless of inlet conditions,
• Controller mounted—with adjustments and tubing
makes it an excellent match to the superior perfor-
facing down for easy access from below.
• 15-25 psig—clean dry air source required for mance of DDC systems.
operation.
• Actuator attaches to damper shaft with positive lock Control package drawings are available outlining the
crankarm, eliminating improperly adjusted linkage. control manufacturer equipment and, factory provided
equipment. All are shown on a complete piping and
wiring diagram.
—4—
START-UP
CONTROLLER DIAGRAMS ®
CONTROLLER DIAGRAMS
90
(Factory Set @
8.0 PSI)
T
H L Differential 45
RESET START
Pressure (Flow)
B Limit adjustment
LO STAT P
To Damper Actuator when t'stat Adjustable
pressure is high End Stops
NC
HI STAT P ∆ P Ports
R
R
M RESET SPAN
DAMPER
Gauge Tap. Leave L
Gear Disengage-
cap on unless ment button
connecting gauge for G Differential H
Reset Start or Reset Pressure (Flow)
Span adjustment. Limit adjustment
when t'stat N
O
NOR
MAX
pressure is low
MIN
M
Damper Action Selection (LO Stat) METER M
A
NOTE: Screw must be tight and 16
V
DC
I
N
O
U
T
— —
24V
AC
— + X
%
arrows in perfect alignment for Reset Span Adjustment RED-CLS
GRN-OPEN M
I
device to function properly. (Factory Set @ 5.0 PSI) N C
LED L
CCW CW O
S
E
16 I O — —
V N U 24V
DC T AC
—5—
CALIBRATION ®
All volume controllers are factory set for maximum and decrease of the reset span will directly and propor-
minimum airflow according to sales order require- tionally effect the differential pressure range.
ments. The requisite aiflow settings are found on the
unit identification label. Other airflow settings may be LO STAT DP adjustment will affect the HI STAT DP,
obtained by field adjustment. LO STAT DP must be adjusted first or the HI STAT
DP will require readjustment.
Pneumatic Controls 4. Replace cap on G port.
To change the settings, refer to pages 30 and 31, and
proceed as follows: Electronic Analog Controls
1. Connect pressure gage or inclined manometer to (Thermostat Checkout/Calibration Procedures)
high and low taps. The thermostat (CTE-5100 Series) operates on a
2. Refer to flow curves located on terminal side to 16vDC power supply from the CSP controller and
determine differential pressure for specified outputs a 0-10vDC signal on the T (?) terminals; T1 in
maximum and minimum airflow. the cooling mode (DA) and T2 in the heating mode (RA). In
3. Direct acting cooling or reverse acting heating. general, T1 and T3 are used for the cooling mode, T2 and T4
a. Adjust LO STAT DP to the desired minimum air for heating. T1 and T2 are adjustable to limit min. and
flow limit with 0 PSI (or a pressure less than the max. flow. T3 and T4 have a fixed 0-10vDC output
reset start point) at port T. signal.
b. Adjust HI STAT DP to the desired maximum air 1. Required Tools
flow limit with 20 psi (or a pressure greater than A. 1/16" hex/key wrench.
the reset start point plus reset span) at port T. B. Small flat blade (1/8") screwdriver.
4. Reverse acting cooling or direct acting heating. C. Digital volumeter capable of displaying a 0-10vDC
a. Adjust LO STAT DP to the desired maximum range which will display in hundredths of vDC.
air flow limit with 0 PSI (or a pressure less than D. HSO-5001 Test Leads (optional for meter taps).
the reset start point) at port T. 2. Remove Thermostat Cover: Thermostat cover is
b. Adjust HI STAT DP to the desired minimum air removed by loosening the setscrews on each side of
flow limit with 20 PSI (or a pressure greater the thermostat. Using a 1/16" hex/key wrench turn
than the reset start point plus reset span) at port T. the setscrews clockwise until cover is loose.
3. Check Voltages
Direct Acting Reverse Acting Reverse Acting Directing Acting
Cooling Heating Cooling Heating
A. Verify 16vDC between (+) and (-) terminals.
B. Measure "T (?)" to "-" for output voltage. Use
LO Stat DP Minimum Minimum Maximum Maximum
Adjustment Limit Limit Limit Limit
calibration procedures below to adjust limits if
desired. Adjust set point above and below current
HI Stat DP Maximum Maximum Minimum Minimum room temperature and observe changes in appro-
Adjustment Limit Limit Limit Limit
priate 'T' voltage. Remove set point slider stops
Disconnect pressure gage and recap flow taps. Reset (HFO-0027) if necessary.
Start is factory set at 8 PSI. To field adjust proceed 4. Always Adjust Minimum flow limits first
as follows: 5. Maximum limits must always be greater than mini-
1. Connect an accurate gauge to the G port. mum limits. If in doube, turn Max. limit fully clockwise
2. Regulate thermostat pressure, to port T, to the (increase) before proceeding. NOTE: Dials rotate
desired startpoint pressure. approximately 200° (8:00 to 4:00). DO NOT force dial
3. Adjust Reset Start to indicate 0 PSI on G port beyond stop.
gauge and then adjust Reset Start to indicate a 6. Connect voltmeter to the meter caps (Using HSO-5001).
pressure slightly higher than 0 PSI, i.e. 0.1 PSI. A. The two holes on the right are for the min.
4. Replace cap on G port. and max. reading.
B. Move to the left to measure actual flow VelocityGround Min/Max
Reset Span is factory set at 5 PSI. To field adjust (must be wired to controller for this option).
proceed as follows: 7. Adjust set point to request Min. flow**
1. Connect an accurate gauge to the G port. A. D/A cooling stat; Set point <Room-temp. Min. Max.
2. Regulate thermostat pressure, to port T, to 20 PSI. B. R/A cooling stat; Set point >Room-temp. INCR. INCR.
3. Adjust Reset Span to indicate the desired span on C. Set maximum flow as desired using
G port gauge. Reset Span adjustments will affect the max. dial. Clockwise to increase
Counterclockwise to decrease
the HI STAT DP. Reset Span must be adjusted 8. Adjust set point to request Max. flow**
first or HI STAT DP will require readjustment. A. D/A cooling stat; Set point <Room-temp. NOTE: Do not use
Deviation from the factory set 5.0 PSI reset span B. R/A cooling stat; Set point >Room-temp. excessive force on
dials. They should
will effect the differential pressure range of 1.0" C. Set maximum flow as desired using turn freely and
W.C. of the pneumatic controller. An increase or —6— the max. dial. effortlessly.
**NOTE: Limits may be set at the CSP or the CTE thermostat. If setting the min/max limits at the CTE thermostat the CSP's min. dial
must be fully CCW to "0" and the max. dial set fully CW to "100". This will ensure that the CSP will not have any affect on the limits.
SERVICE/TROUBLESHOOTING ®
Pneumatic Controls
—7—