Photovoltaic Power Systems 2017
Photovoltaic Power Systems 2017
Photovoltaic Power Systems 2017
THIRD EDITION
JOHN WILES
4
ISBN-10: 1-890659-81-3
ISBN-13: 978-1-890659-81-3
The material in this book has been extracted from and expanded upon the series of articles “Perspectives on PV”
found in IAEI News published by the International Association of Electrical Inspectors. The articles are based on the
author’s understanding of the 2005, 2008, 2011, 2014, and 2017 NFPA 70 National Electrical Code (NEC) 1; his
activities in developing that Code; his design reviews, inspections and testing of photovoltaic (PV) systems for more
than twenty years; and his interaction with electrical inspectors, PV systems designers, and PV installers throughout
the country. In all cases, the NEC is the requirement and local authorities having jurisdiction provide the interpreta-
tions of the Code.
DISCLAIMER
This book provides information on how the 2005, 2008, 2011, 2014, and 2017 National Electrical Codes apply to pho-
tovoltaic systems. The book is not intended to supplant or replace the NEC; it paraphrases the NEC where it pertains
to photovoltaic systems and should be used with the full text of the NEC. Users of this book should be thoroughly
familiar with the NEC and know the engineering principles and hazards associated with electrical and photovoltaic
power systems. The information in this book is the best available at the time of publication and is believed to be
technically accurate. Application of this information and results obtained are the responsibility of the user.
In most locations, all electrical wiring (including photovoltaic power systems) must be accomplished by, or under
the supervision of a licensed electrician and then inspected by a designated local authority. Some municipalities have
additional codes that supplement or replace the NEC. The local inspector has the final say on what is acceptable.
This book has not been processed in accordance with the National Fire Protection Association’s (NFPA) Reg-
ulations Governing Committee Projects. Therefore, the text and commentary in it shall not be considered the official
position of the NFPA or any of its committees and shall not be considered to be nor relied upon as a formal interpre-
tation of the meaning or intent of any specific provision or provisions of the 2005, 2008, 2011, 2014, or 2017 editions
of National Electrical Code.
Author and the publisher do not warrant or guarantee any of the products described herein nor have they per-
formed any independent analysis in connection with any of the product information contained herein. The publisher
does not assume, and expressly disclaims, any obligation to obtain and include information referenced in this work.
The reader is expressly warned to consider carefully and adopt all safety precautions that might be indicated by the
activities described herein and to avoid all potential hazards. By following the instructions contained herein, the reader
willingly assumes all risks in connection with such instructions.
THE AUTHOR AND THE PUBLISHER MAKE NO REPRESENTATIONS OR WARRANTIES OF
ANY KIND, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF FITNESS FOR
PARTICULAR PURPOSE, MERCHANTABILITY, OR NON-INFRINGEMENT, NOR ARE ANY SUCH
REPRESENTATIONS IMPLIED WITH RESPECT TO SUCH MATERIAL. THE AUTHOR AND THE
PUBLISHER SHALL NOT BE LIABLE FOR ANY SPECIAL, INCIDENTAL, CONSEQUENTIAL OR
EXEMPLARY DAMAGES RESULTING, IN WHOLE OR IN PART, FROM THE READER’S USE OF OR
RELIANCE UPON THIS MATERIAL.
1 National Electrical Code and NEC are registered trademarks of the National Fire Protection Association, Inc.,
Quincy, MA 02169
5
Table of Contents
Preface
In a time where photovoltaic plan reviewers and inspectors are getting pressured to expedite the
inspection and review process, this book could not have come at a better time. If we are expected
to accomplish faster turnaround times with fewer inspections, we must be informed to ensure safe,
Code-compliant installations. Rubber-stamping plans and drive-by inspections may be what the
industry is pushing for, but are those actions what the customer deserves? The customer is relying on a
qualified inspector to verify that their PV system is safe and that it will continue to be safe for years of
operation.
What makes this book stand out is how it correlates to the National Electrical Code (NEC). When
citing corrections or comments, we need to be able to reference the Code to justify our calls. The last
thing that we should be doing is trying to enforce our opinion.
Stamping a set of PV drawings for approval or signing a permit card for an inspection does not
require skill or knowledge of the NEC requirements we need. The knowledge and skill before we sign
or stamp documents is where most of us need some help and guidance. Having a document such as
Photovoltaic Power Systems provides inspectors with a great tool for gathering information on what to
look for in plan review and during inspections.
Article 690 is a small section when compared to the entire NEC. The size of Article 690 does not
make it any less important than other articles found in the NEC. Due to its size, it is often not a focus
of the combination inspector. It is no wonder it gets overlooked when you stack up all the codes the
combination inspector must enforce.
When the NEC book and handbook are not enough to help you understand what or how you
should be enforcing the regulations, this document can provide clarity. The information provided in
Photovoltaic Power Systems has been compiled by someone who is known throughout the industry as a
PV expert. John Wiles has been a resource and has been providing training for more than 20 years to
inspectors and plan reviewers.
Not only is this book originally based on the 2011 Code and earlier editions, but also the 2014 and
2017 NEC. With knowledge comes credibility. This document will help plan reviewers and inspectors
know and understand what they are looking at and what to look for. If you want to understand what
is on the plans, this book will help. Even for those who have a solid understanding of PV systems, it is
helpful to have a book to refer to when questions arise. Whether questions come from us or from PV
designers or installers, this book can help answer these PV-related questions. You will find this book to
be an excellent resource.
Having ready access to this book can help us all be more informed about PV systems, where expertise
is often limited. John Wiles is known for having such expertise.
01
An Overview of PV Systems and
the 2017 National Electrical Code
Photovoltaic (PV) power systems are being amps or more. These levels of voltage and current,
installed by the tens of thousands throughout the if not properly managed, pose shock, life safety,
United States. In states where financial incen- and fire hazards. These systems must be inspected
tives are available (like in California, New York, to ensure the safety of owners, operators, service
and New Jersey), the PV business is booming. personnel, and the public.
The first PV cells produced more than 50 years The Code requirements for a typical residential
ago are still producing power, and modern PV PV system are at least as complex as those for
modules are expected to produce energy for residential wiring, and the dc portions of the
the next 40 years or longer. The power output system coupled with the ac interconnection to the
from PV systems ranges from a few hundred utility grid make PV installations unique. Because
watts to many megawatts. Most of the systems the PV industry is growing rapidly, individuals,
are not operated or owned by any electric utility companies, and organizations (with varying
and therefore come under the requirements of degrees of knowledge, skill, and experience) are
NFPA 70 National Electrical Code (NEC). Unless installing these systems. Large, and some small,
otherwise noted, all references to the NEC will be PV-system integrators and vendors — working
to the 2017 NEC. with experienced electrical contractors who have
Systems as large as 700 megawatts have been jointly pursued additional PV-specific training
installed by third parties on private land in the and who work closely with the local permitting
United States, and are not under utility control and inspecting authorities — usually (but not
or ownership. Larger systems of up to 1500 always) perform the best, most Code-compliant
megawatts have been installed in other countries installations.
and will more than likely be installed in the On the other hand, individuals or organizations
United States in coming years. These systems with little or no experience or training installing
operate at 1000 volts to 1500 volts and, in the electrical systems of any type are installing many
larger commercial systems, direct current (dc) new PV systems. These systems may be unsafe
and alternating current (ac) can range up to 2000 (not Code-compliant) at initial installation;
10 Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code
develop hazardous conditions over the life of the training, experience, and skill requirements of PV
system; be hazardous to operate or service; and designers and installers obtaining this certification
fail to deliver the full performance of a well-de- will help ensure that safer, higher quality installa-
signed and -installed PV system. tions of PV systems take place.
The electrical inspector or plan reviewer, as the
authority having jurisdiction (AHJ), is the key PV System Types
player in ensuring that these less-than-ideal PV Two main types of PV systems are being in-
installations do not proliferate. Inspectors need stalled in the United States: utility-interactive
to demand additional training in the inspection (grid-connected) (see photo 1.1) and stand-alone
of PV systems and then inspect these systems (off grid) (photo 1.2). Both types use PV mod-
very closely. Yes, PV is a relatively unfamiliar ules connected in series and in parallel to form
technology, but 80% of the Code already familiar PV arrays that produce direct current energy at
to inspectors applies, and it is relatively easy to voltages ranging from approximately 12 volts to
learn the inspection requirements that are unique 1500 volts (photos 1.1, 1.2, 1.3 and 1.4). Refer
to PV systems. to Article 100 and Section 690.2 of the NEC
Several organizations in the PV industry pro- for definitions of the terms used to describe PV
vide training and certification for individuals. The equipment and systems. These systems will be
Photo 1.1 • Carport PV systems generate energy and keep Photo 1.3 • Commercial PV array mounted horizontally
cars cool. with some shading.
Stand-Alone Systems
Stand-alone systems are typically installed in
remote areas where the utility grid is not avail-
able or where the connection fees to the grid are
higher than the costs of an alternative energy
system. While stand-alone systems sales are far
lower than sales in the fast-growing utility-inter-
active PV system business, there is and has been a
Photo 1.6 • Utility-interactive inverter. External ac and dc steady market for off-grid systems.
disconnects not shown. The stand-alone inverter converts dc energy
12 Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code
Photo 1.8 • Four 6-kW stand-alone inverters in an ac-cou- Photo 1.9 • Inverters and charge controllers for 10-kW off-
pled, battery-backed-up PV system grid, stand-alone PV system.
stored in batteries by the PV array to ac energy to and dc currents to the inverters can be hundreds
support the loads (photos 1.8 and 1.9). Inverter of amps at these higher voltages.
power ratings are from about 250 watts to 6500
watts for residential systems and, as before, PV System Component
multiple inverters may be connected together Descriptions
for greater power outputs. Battery banks usually PV Modules
operate at a nominal 12, 24, or 48 volts, so the The first thing inspectors see are PV modules.
current levels to the inverters can be hundreds of While most have glass fronts, aluminum frames
amps at full load. (colored mill-finish aluminum or anodized brown
Larger stand-alone systems can be found in na- or black), and plastic backs, some will be made
tional parks, at telecom sites, and at federal facil- with plastic frames or with no frames (photo
ities. These can be as small as residential systems 1.10). Others will be used as roofing materials
with ac outputs in the 2 kW to 10 kW range, but (photo 1.11) or laminated directly to standing
they can also have single inverters of 250 kW or seam metal roofs (photo 1.12). PV modules come
more. A few of these larger systems have multiple in many sizes and shapes.
large inverters with combined outputs approach- Inspectors need to determine the listing of the
ing 500 kW or more. Battery banks for the larger modules and the electrical ratings. These are print-
systems operate in the 200-volt to 600-volt range ed on the back of the module and may be available
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 13
in the instruction manual or module specification Photo 1.10 • (left) Framed PV modules (anodized and clear-
coated aluminum in natural aluminum color or brown/black).
sheet. Some unlisted, custom modules are being
installed in architect-designed projects. Unlisted Photo 1.11 • (top right) Building-integrated photovoltaics
modules are being sold through various channels (BIPV) PV modules as roofing material.
(including the internet), but unlisted modules no
Photo 1.12 • (bottom right) Thin-film PV modules lami-
longer meet Code requirements and should not nated to a metal standing seam roof.
be installed [690.4(D)]. Although appearances
may differ, these PV modules all produce elec- ing at dc nominal voltages of 12, 24, and 48 volts
tricity when illuminated and the normal cautions and are also used in higher voltage systems (up to
associated with any electrical power system should 1500 volts). They must be certified/listed by a na-
be followed. tionally recognized testing laboratory (NRTL) to
PV modules come in differing power and UL Standard 1741 [690.4(D)]. In these systems,
voltage ratings and the sizes and ratings are it is a normal practice to connect modules in se-
continually changing. The modules must be ries (called a PV source circuit [690.2]) to get the
connected in a manner that produces the needed proper voltage and then to connect each series
voltage, current, and power because the output source circuits of modules in parallel with other
of a single module is usually not sufficient to source circuits through a PV combiner to increase
operate the connected equipment or provide the the current to get the desired power level.
needed amount of energy. These combiners will usually contain the over-
current devices (fuses in the high voltage systems
PV Combiners or circuit breakers in the 12-, 24-, or 48-volt
PV combiners (PV j-boxes or PV combining systems) that are required to protect the module
enclosures) are common in PV systems operat- interconnecting conductors from fault currents
14 Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code
Photo 1.13 • PV combiner with fuses in the positive con- Photo 1.14 • PV combiner in white enclosure with manual
ductor only. Manual and contactor disconnects in positive switch opening both positive and negative conductors.
conductor only. Not 2017 NEC compliant [690.15(C)]. Plastic shield covers energized, exposed conductors.
and the individual modules from reverse currents. with multi-mode inverters (photo 1.17) and
Reverse currents may originate from paral- battery backup were popular for months follow-
lel-connected strings of modules; reverse currents ing the blackouts.
from the batteries in a system that has them; or Unfortunately, installation manuals for these
from backfeed currents from a utility-interactive complex inverters (particularly the stand-alone
inverter (unlikely in listed inverters). See chapter types) can be several hundred pages long. The
2 for additional details on the requirements for inspector should verify the proper dc and ac
combiners. conductor sizes and overcurrent protection.
Both are based on the rated ac power output of
Inverters the inverter. (See Sections 690.8 and 690.9 and
Inverters are found in both stand-alone systems Articles 705 and 706 in the NEC.)
and utility-interactive systems. They essentially Utility-interactive inverters have all the
convert dc)energy from the PV system (or the dc automatic ac utility disconnect devices built-in,
energy stored in batteries) to ac energy for use by which protects utility linemen who are working
local loads or for feeding into the utility system on supposedly de-energized utility feeders. The
(photos 1.15 and 1.16). Some utility-interactive utility-interactive PV inverter will not energize
inverters, known as multimode inverters, have the a dead line and, in fact, will disconnect from
capability to power selected load circuits from the line when the line voltage varies more than
batteries or the PV system when the utility is not -12% to +10% from nominal (typically 120, 208,
present. 240, 277, or 480 volts) or when the frequency
Many PV owners in California were surprised varies by more than -0.7 to +0.5 Hz from the
when their utility-interactive PV systems did normal 60 Hz.
not work during the rolling utility blackouts The inverter monitors the utility line voltage
created by the energy shortage and brownouts and frequency, and that voltage and frequency
a few years ago. Utility-interactive PV systems must remain stable and within tolerance for five
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 15
could possibly damage the connected equipment. to other parts of the Code.
Some sort of charge-management device (e.g., a
charge controller) is normally used, and under the Other Definitions Changed, Deleted,
new definitions, that charge management device or Added
or system should be grouped with the energy In Section 690.2, in addition to Functional
storage system. If that is the case, then the PV Grounded PV systems (described below), other
system disconnect would properly be connected definitions were changed. The following defini-
to an energy storage disconnect and connections tions were also added.
to the inverter and any dc loads would be made Generating Capacity. The sum of parallel-con-
directly to the voltage-regulated energy storage nected inverter maximum continuous output
system or battery through appropriate discon- power at 40°C in kilowatts.
nects. Also, in the two multimode diagrams Interactive Inverter Output Circuit. The
(Figure 1.3), the output from the multimode conductors between the interactive inverter and
inverter marked “Stand-alone system loads” in the service equipment or another electrical power
the dc-coupled multimode system diagram, and production and distribution network.
not identified at all in the ac-coupled multimode Photovoltaic System DC Circuit. Any dc con-
system, could probably be more properly iden- ductor supplied by a PV power source, including
tified as “Local ac loads” because they can be PV source circuits, PV output circuits, dc-to-dc
powered either by the utility or by the PV/energy converter source circuits, or dc-to-dc converter
storage system when there are utility outages. output circuits.
As the PV system proper became more narrow- The definition of Photovoltaic Systems Voltage was
ly identified, parts of Article 690 that deal with removed and now appears in Section 690.7.
other types of electrical systems have been moved Several definitions were modified, and they
include:
• Inverter Input Circuit. Conduc-
tors connected to the dc input of an
inverter.
• Inverter Output Circuit. Con-
ductors connected to the ac output
of an inverter
This was done to reduce confusion by simplifying past, but will exist for years and still be installed
terminology between the older “Grounded PV in smaller systems that are not on buildings.
Array/Isolated Inverter” PV systems and the The required Code requirements to address these
newer, more common “Ungrounded PV array/ varying “grounding” systems were cumbersome,
Non-isolated inverter” PV systems. difficult to understand, and hard to apply in
Grounding the PV System Circuit Conduc- many cases. The changes in the 2017 NEC ad-
tors. In the early years of PV systems, up to dress and simplify many of these grounding
about 2005, we primarily had grounded PV requirements.
arrays and grounded dc battery systems where
one of the circuit conductors was “grounded” or Grounding Definitions—2017 NEC.
“connected” to the grounding system, which is From the 2017 NEC, some definitions are the
composed of the equipment-grounding system, same as in the 2014 NEC.
the grounding electrode conductor, and the
grounding electrode system. From Article 100
In some cases, the grounding method was a “Ground. The earth.
solid conductor and, in others, the grounding “Grounded (Grounding). Connected (con-
method was by a fuse or circuit breaker like those necting) to ground or to a conductive body
used in Section 690.5, Ground Fault Protection that extends the ground connection.
(2014 NEC). In other cases, various resistances “Grounded, Solidly. Connected to ground
or solid-state devices were used to ground one of without inserting any resistor or impedance
the circuit conductors. device.”
Now we have increasing numbers of un- Author’s note: This definition could also include
grounded PV arrays and non-isolated (transfor- fuses, circuit breakers, and possibly relays and
merless) inverters that have no dc circuit con- contactors with the devices not allowed in a
ductors connected directly to ground. Grounded solidly grounded system.
PV systems, where one circuit conductor is “Grounded Conductor. A system or circuit
solidly grounded, are becoming a thing of the conductor that is intentionally grounded.”
Help for The Systems Designer from trolling controlled conductors from initiation has
The Professional Engineer been increased from 10 seconds to 30 seconds.
On larger PV systems that are 100 kW and larg- These modified requirements provide additional
er, some of the general requirements for voltage safety for first responders who must deal with an
and current calculations are too conservative for energized PV array and allow the PV industry,
the proper and safe installation of cost-effective in some cases, easier methods of meeting the
PV systems. requirements. (See photo 1.20.)
Section 690.7(A)(3) allows the professional There are now three new options that must
engineer (PE) to calculate the maximum system be used to meet the PV rapid shutdown system
voltages based on industry design practices. These (PVRSS) requirements for the conductors in-
might include such factors as microclimates, array side the PV array controlled boundary [690.12(B)
mounting devices, and array orientation. This (2)]. These requirements will become effective
new calculated system voltage may permit more January 1, 2019.
modules to be placed in series than the more
conservative 690.7(A)(1) and (2) would allow. 1. Use a PV array that has been entirely
Section 690.8(A)(2) allows the PE to calculate listed or field labeled as a rapid shutdown
a maximum current that can be no less than 70% PV array.
of maximum current calculated using the normal 2. Install a PV array with controlled con-
method of using 125% of the short-circuit cur- ductors inside the array boundary and
rent (Isc). In large systems, these methods using not more than 1 m (3 ft) from the point
simulated local irradiance may allow smaller, yet of penetration to 80 V or less within 30
still safe, conductor sizes. seconds of PVRSS initiation.
3. Install a PV array with no exposed conduc-
Other Changes in Article 690 tors or exposed conductive parts more than
Scope, 690.1 2.5 m (8 ft) from exposed grounded conduc-
The scope excludes large PV systems which, are tive parts or ground.
now covered in Article 691.
It should be noted that these three new options
DC-To-DC Converter Source and Output Circuits, will become effective on January 1, 2019. This re-
690.7(B) quirement implies that some sort of module-level
This new section establishes requirements for control will be required to meet the controlled
determining the maximum voltage of single or conductors inside the PV array boundary.
multiple series connected dc-to-dc converters. In some cases, module-level power electronics
(MLPE), such as microinverters, ac PV modules,
PV Rapid Shutdown Systems, 690.12 or dc-to-dc converters, may meet the PVRSS
This section received significant changes for requirement after they have been listed as rapid
2017. The previous boundary around the PV shutdown equipment. The 2014 NEC required
array that defined the point where conductors only that the equipment be listed and identi-
must be controlled to a lower voltage has been fied (meaning a listed relay could be used). The
decreased from 3 m (10 ft) to 305 mm (1 ft). The 2017 NEC, however, requires the equipment to be
length of allowable uncontrolled conductors listed and labeled as a rapid shutdown system or
inside a building has been reduced from 1.5 m (5 as RS equipment.
ft) to 1 m (3 ft). The time allowance for con- The new and revised PVRSS section of UL
22 Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code
Standard 1741 establishes complex and detailed plaque clearly showing a physical plan diagram of
testing requirements. One of these requirements is the PV system indicating which parts of the PV
that the ac output of inverters go to the controlled array are RSS controlled and under which edition
voltage limit within the required time frame after of the Code that part meets. Section 690.56(C)(1)
initiation (usually opening the ac utility discon- has detailed marking requirements for the various
nect) of the RSS system. This test was not in UL types of PVRSS.
1741 under the initial RSS requirements. Finally, the manual reset requirement has been
The initiation device for the PVRSS must deleted from the 2017 NEC.
plainly indicate the OFF position and the ON
position, where the OFF position indicates that Arc-Fault Circuit Protection (Direct-Current),
the PV array has been put in the controlled state 690.11
for all circuits controlled by that initiation device. This section of the Code was substantially
The initiation device shall consist of at least one reduced for 2017. An exception was added that
of the following: exempts PV systems from the arc-fault circuit
(1) The service disconnecting means. protection requirement that are not mounted on
(2) The PV system disconnecting means. buildings. Also exempted are PV systems with
(3) A readily accessible switch that indicates PV output and dc-to-dc converter output circuits
the ON and OFF positions. that are direct buried, installed in metallic race-
Because various PV systems are installed at dif- ways, or installed in closed metallic cable trays.
ferent times and may be expanded under different This exclusion was necessary because arc-fault
editions of the Code, Section 690.56(C) requires a equipment at the high current levels found in
large PV arrays does not exist.
Photo 1.20 • PV Rapid Shutdown Equipment.
Photo courtesy of SMA
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 23
The exclusion does not address larger PV sys- on inspecting large PV systems in recent editions
tems on the roofs of commercial buildings. These of IAEI News point out the continuing need for
systems are being addressed using multiple medi- close and detailed inspections of these installa-
um-size string inverters with arc-fault detection tions by an AHJ supervising a team of inspectors
capabilities mounted in subarrays on the roof. directly or carefully reviewing the certifications of
The manual restart requirement and the re- the independent professional engineer.
quirement for an annunciator have been removed,
but are included in the requirements in UL Article 705
Standard 1741. Definitions, 705.2
Definitions have been added or modified in
Article 691 this section.
For large-scale (5 MW or greater) PV systems, A microgrid system is “a premises wiring system
not under the ownership or operation of a utility, that has generation, energy storage, and load(s),
special design and installation requirements are or any combination thereof, that includes the
allowed. These requirements address numerous ability to disconnect from and parallel with the
areas, but in general require a PE-engineered primary source.” The requirements of this code
design; limited and controlled access; no local apply unless the microgrid system is under the
loads except as necessary to operate the gener- exclusive control of a utility.
ation system; and a full, utility-type substation The term utility interactive has been modified to
to make the connection to the local utility. Also, just interactive throughout section 705.
parts of the system that do not comply with the The definition of stand-alone system has been
requirements of Article 690 shall be fully justified moved to the new Article 710 – Stand Alone
and documented. Systems.
At the request of the AHJ, an independent
electrical professional engineer, retained by the Point of Connection, 705.12
system owner, may be required to evaluate the Sections (B) and (C) dealing with integrated
actual installation for compliance with the Code electrical systems and systems greater than 100
requirements and the engineered design. kW have been deleted from this Article. Article
Even though these large systems (in Articles 705.12 requirements found in 705.12(A) and the
690 and 691) are designed by a PE, and may renumbered 705.12(D) [now B)] apply to inter-
have independent review of the installation for connected electrical power systems of any size.
compliance with the design, it is still the respon-
sibility of the AHJ to ensure that the system is Point of Connection, Load Side 705.12(B)
safe and meets the various applicable codes. In This section has been modified to allow other
many cases, it is common for jurisdictions to interconnected (interactive) power sources to be
outsource inspections of large-scale PV systems connected on the load side of the system discon-
due to departmental manpower shortages. This necting means.
outsourcing could be to an independent electrical
inspection service or to a licensed professional Center-Fed Panelboards, 705.12(B)(2)(3)(d)
engineer. Keep in mind that all the large utili- Center-fed panelboards may now be treated
ty-scale systems being installed today use engi- like standard panelboards where the backfed PV
neered designs. breaker may be connected at the end (away from
Scott Humphrey’s excellent series of articles the main breaker) on only one of the two busbars
24 Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code
Photo 1.21 • (top left) Center-fed panelboard. PV connec- Photo 1.22 • (top right) Residential microgrid system—PV
tions now allowed by the 2017 NEC at one end only. Photo input.
by Dan Potkay.
Photo 1.23 • (bottom right) Microgrid system—generator
input.
and may be rated according to the 120% rule. This
rule states that 125% of the inverter output current system disconnect requirements in 690.13(F)(1)
rating plus the main breaker rating may not exceed require all conductors to be disconnected. This
120% of the busbar rating (see photo 1.21). will be addressed in the 2020 NEC, where only
ungrounded conductors shall have disconnect
Wire Harness and Exposed Cable Arc-Fault requirements.
Protection, 2014 – 705.12(D)(6) The equipment disconnecting requirements in
This section dealing with ac arc-fault protec- 705.21 are consistent with the equipment discon-
tion for 240-volt ac inverter output circuits up to necting/isolating requirements in 690.15 because
30 amps on flexible, exposed cables has been re- both require only the ungrounded conductors to
moved because no suitable equipment is available be disconnected.
to meet the requirement.
Disconnect Device, 705.22
Disconnecting Means, Sources This slightly revised section allows power-op-
Article 705.20 may require some harmo- erated disconnects to be used, but this allowance
nization with the revised system-disconnect for PV system disconnects in the 2014 NEC was
requirements in Article 690. These Article 705 removed when 690.17 was deleted. Again,
disconnect requirements require only ungrounded harmonization may be required in future editions
conductors to be disconnected, whereas the PV of the Code.
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 25
Photo 1.25 • “We just know there is a ‘function ground’ here somewhere. Give us time; we’ll find it.”
installation. In the days preceding electronic careful adjustments of software- and hardware-
power equipment (yes, that was even before my driven internal parameters to operate safely.
time), application of the Code requirements was Each of these active devices, made by numerous
relatively straightforward: connect conductors to manufacturers, has different requirements for
passive devices like switches, overcurrent devices, safe installation. It is neither possible nor prac-
and transformers. Many electricians could do that tical to put detailed instructions in the Code for
with a little training, and even the inspections the installation and adjustment of each of these
were relatively easy. types of devices. The Code would become far too
However, AHJs are now faced with active ponderous to deal with in its present form.
electronic power-processing equipment scattered For this complex equipment, the best
throughout our electrical power systems, and PV the Code can do is to include Section 110.3(B),
systems are no exception. AHJs must now ensure which requires that the instructions and labels
that active inverters, active charge controllers, provided on certified (listed) equipment be used
rapid shutdown equipment, dc PV arc-fault and followed to properly install that equipment.
circuit interrupters, microinverters, and ac PV This requirement in the NEC places a signifi-
modules plus module-level electronics are prop- cant burden for ensuring the safe installation di-
erly installed and that they will operate safely. rectly on the quality and detail of the equipment
Many of these devices have multiple inputs and installation instructions that are required by the
outputs and require not only electrical connec- UL Standard for that equipment. These standards
tions to the rest of the electrical circuit, but also must be detailed and understandable because
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 27
several Nationally Recognized Testing Laborato- dards are so complex that the entire STP does
ries (NRTLs) other than UL such as TUV, ETL not, as a group, develop them. Various working
and CSA will be using them to test and evaluate groups are set up composed of STP members and
PV equipment. (See photo 1.26). other technically competent interested parties to
These requirements lead us to the effort draft sections of the Standard. After those drafts
required to develop these standards. Although are edited to comply with UL writing standards,
Underwriters Laboratories publishes the Stan- they are presented to the STPs for review, final
dards, the various UL Standards Technical Panels refinement, balloting, and integration into the
(STPs) write them. The STPs are composed of whole Standard. An example is the draft Stan-
balanced volunteer groups of manufacturers, dard for the Code requirement in 690.12 for a PV
AHJs, technical experts, users, government rapid shutdown system (PVRSS).
agencies, and general interest individuals. In some Underwriters Laboratories’ engineers devel-
cases, these groups may include more than fifty oped the basic outline and the initial contents for
people. There are standards and STPs for each of the draft PVRSS Standard and then published
the major categories of equipment in PV systems. them as a Certifications Requirements Deci-
These include UL 1741 for inverters (including sion (CRD) in March 2015. UL then formed
charge controllers, microinverters, rapid shut- a working group outside of the STP to further
down equipment, and ac PV modules); UL 1703 refine this draft. The working group, consisting
for PV modules; UL 1699B for dc PV arc-fault of more than fifty people, met on a weekly basis
circuit interrupters; UL 4703 for single conductor via webinar for more than twelve months to
PV cable; UL 6703 for PV connectors; UL 2703 investigate, evaluate, and develop the require-
for PV racks; UL 489B for dc PV overcurrent
Photo 1.26 • Rigorous application of standard require-
devices; and others. ments will minimize issues like this failed PV module sol-
In many cases, the requirements in the Stan- der bond.
28 Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code
ments for the PVRSS based on the very limited standard was developed to address systems that
requirement stated in Section 690.12 of the 2014 control hazards within the boundary of the PV
NEC. And as the PVRSS requirements in the array. This Standard, UL Standard for Safety for
2017 NEC became known, the draft Standard Photovoltaic Hazard Control (UL 3741), will be
was again revised. published in late 2018 or early 2019.
The working group had to consider all possible
ways in which various equipment manufacturers Harmonization with International Standards
could implement the Code requirement. Because Photovoltaic equipment is frequently designed
this PVRSS system provides a life safety func- and manufactured to be sold and installed in in-
tion, the testing and evaluation criteria that the ternational markets. The equipment must meet the
Standard required would have to be rigorous, codes and standards of each country. While there
extensive, detailed, and very complex. The PVRSS is some variation in the electrical codes between
system may have to work properly in an outdoor countries that have such codes, the connections of
PV system environment that includes extremes PV equipment to electrical systems is not too dif-
of temperature, humidity, UV irradiation, wind, ferent from country to country. Some editions of
snow, ice, and blowing dirt. The standard must the NEC have been translated into other languages
require testing to evaluate PVRSSs and PV rapid (photo 1.27). Unfortunately, the standards govern-
shutdown equipment (PVRSE) under these ing how equipment is built and tested can differ
conditions plus surges that might occur from significantly between countries. There has been a
nearby lightning strikes on the connected ac and long-term, on-going effort to harmonize safety
dc circuits. The PVRSS equipment must also and construction standards of PV equipment
operate reliably for the 40- to 50-year life of the between countries.
system. While there are UL Standards to evaluate A harmonized standard would reduce manu-
some of these conditions, and those standards facturers’ costs of certification and listing in mul-
were referenced in this new PVRSS Standard, tiple countries. Engineers from the United States
the unique nature of outdoor PV environments have participated in the development of interna-
required that new testing and evaluation proce- tional standards that are published by the Inter-
dures be developed. national Electrotechnical Commission (IEC),
Even simple products, such as power relays or based in Geneva, Switzerland. The International
contactors, that have been listed to various UL Standard, by its very nature, mainly addresses
Standards for the necessary voltage and current common requirements that apply in all countries
have frequently not been tested in wide tempera- to the design and testing of PV system electrical
ture extremes found in the PVRSS application. equipment. After an IEC Standard is published
Electronic devices must be evaluated for new formally, it is distributed to the various member
types of failure modes such as operation in high countries where they evaluate it and add sections
humidity environments and the response when to the standard that elaborate on the “Country
control circuits fail or are interrupted. Differences” that will be used along with the
The draft Standard is more than 20 pages common International Standard requirements to
long and, after review and modification by the evaluate products in a particular country.
UL 1741 STP, it will be added to the UL 1741 As United States safety standards become
Standard (already 144 pages long). harmonized with the international standards,
In addition to the changes made to include working groups in the United States spend two to
PVRSS in UL Standard 1741, an entirely new three times as long developing the international
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 29
Photo 1.28 • (top) Electric vehicles are back after a century of disuse in various forms, including EVs, hybrids, and fuel-
cell vehicles. They will dominate the transportation industry in the future.
Photos 1.29a and b • (middle and bottom left) The infrastructure of utility generation and distribution systems is fairly ro-
bust, but very old, and somewhat inflexible in dealing with increased use of energy sources and its associated issues. Smart
Grid programs are designed to modernize the entire system from the generation plant to end-use load.
Photos by John Watson.
who run them when not needed for emergencies cess that yields a long-lived battery that can be
and sell the power to the utilities during peak rapidly charged and deeply discharged virtually
load periods. New Article 706, Energy Storage an unlimited number of times. The batteries will
Systems, addresses these systems, and most of the be charged, and energy will be stored, during off
battery requirements in Article 690 have been peak demand periods and released back to the
moved to this location. grid during peak demand times. Of course, the
Flow batteries are coming to the market. These process will require utility-interactive systems to
batteries use stored liquid chemicals and a pro- interface with the utility grid and communications
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 31
conductor prices may rise so high that the electrical electrical systems in their homes were far ahead
equipment industry is forced to control power flow of their time! Of course, appliances requiring sig-
so that smaller conductors can be used. Eventu- nificant power for heat or mechanical motion like
ally, the use of electricity on the premises may be ranges, clothes washers, toasters, water heaters
scheduled so the maximum current ever drawn may and the like will usually need higher voltages to
be significantly less than that requiring a 100- or keep the current and hence the conductor sizes
200-amp service today. Smaller conductors and to reasonable sizes. But then there are heat pump
circuit sizes may reduce the ever-increasing costs of water heaters, induction ranges, and ultrasonic
electrical installations, but Code revisions would be washers that operate more efficiently than con-
needed. With the demise of the incandescent light ventional appliances.
bulb, do we really need three volt-amps per square
foot for general-purpose circuits? Oh yes, there will Renewable Energy Systems
be those 100+ inch flat panel displays on all four Large wind-power systems have been installed
walls to deal with. for many years, and many of those systems are
not owned and operated by utilities on utility
Is dc coming back? properties. Therefore, they come under the re-
There is a trend of going back to dc end-use quirements of the NEC and should be inspected
appliances. Most electronic appliances such as for safety using the requirements of Article 694,
cell phone chargers, radios, TVs, DVRs, DVD Wind Electric Systems. UL also has standards
players, cable boxes, satellite receivers, track for large and small wind turbines. Photovoltaic
lighting and the like—while being plugged into power systems for residential and commercial
a 120-volt ac receptacle outlet—run on low-volt- use have been around since the mid-1970s with
age dc. Fluorescent and LED lighting bulbs and substantial growth starting in the late 1990s.
fixtures also operate on direct current. Significant While ever-increasing numbers of residential
losses are incurred to transforming the 120-volt and small PV systems are being installed through-
ac line voltage into low-voltage dc. New Article out the country, real power production will come
712, Direct Current Microgrids, describes sys- from the numerous megawatt commercial systems
tems and circuits that may or may not be directly being installed and planned. Systems as large as
connected to the utility grid. There are also color 2000 megawatts are being planned and installed.
codes for dc branch circuits in Article 210. Some of these will be solar thermal systems along
At the present time, dc lighting fixtures are with the PV systems. In many cases, these large
being installed in commercial buildings and are systems are said to be “Behind the Fence” and not
powered during the day directly from PV power subject to the requirements of the NEC and in-
systems with no conversion to ac until the elec- spections, but they are mainly owned and operated
tronic ballasts are reached. Solar lighting power is by private companies under power purchase agree-
supplemented with utility power when necessary. ments (PPAs) and should be fully NEC compliant.
With the reduction in use of incandescent New Article 691, Large-Scale Photovoltaic (PV)
light bulbs over the next few years, the return Electric Power Production Facility, addresses these
of low-voltage dc power distribution systems larger (over 5 megawatts) systems.
for lighting and electronics is almost a certainty. True ac PV modules with microinverters
Shades of the 1970s and 1980s! Maybe those bonded to the back of the PV module with no
off-grid, long-haired solar hippies who insisted dc wiring subject to Code requirements. They are
on staying with the 12-volt dc PV systems and on the market in catalogs and in big box stores at
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 33
Photo 1.31 • Close-mounted PV arrays allow little room for inspecting the module and array wiring.
is unique compared with the typical residential systems; and where the inspector is also familiar
and small commercial electrical systems that with the technologies and equipment being in-
are familiar to the AHJ. When considering stalled. Experience with the contractors involved
that these systems may operate unattended and also speeds the inspection process.
unmaintained for years—if not decades—PV It is also acknowledged that many jurisdic-
systems demand the highest quality design, tions do not do plan reviews and, unfortunately,
material, equipment, and installation. In the plan this hampers the ability of the inspector to
review and final inspection of a PV system, the easily verify all Code requirements. Photovoltaic
AHJ has the final responsibility and authority modules on roofs are generally mounted close
to verify that the stringent requirements of the to the roof and it is generally not possible to
electrical and building codes are followed in the examine all the connections in the PV array, in-
installation. There are some details in various PV cluding conductor size, grounding and bonding,
subsystems that may need additional attention to and module wiring interconnections. (See photo
achieve a hazard-free, long-lived system. 1.31.) A related issue in a well-installed PV or
other electrical system is that it is sometimes
Yes, Time and Money Are in Short difficult to verify conductor types and conductor
Supply sizes where connections are made inside stan-
It is acknowledged that many residential elec- dard disconnecting devices and inverters. These
trical systems are inspected in less than an particular Code requirements are best reviewed
hour. This is probably acceptable for an electrical in a plan review stage even if that review is only
system that has remained essentially unchanged a half hour in the office looking at the detailed
for 100 years; where the inspector is quite famil- schematics and diagrams that were submitted
iar with Code requirements for those electrical with the permit application. If issues are found
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 35
during the office review, it is almost certain that Without going into the attic (and the flat-roofed
similar issues (or more critical ones) will be homes common in the southwest United States
found if time is taken to examine those areas that have no attic), it is difficult to verify that
during the field inspection. mechanical fasteners are indeed being inserted
While many larger PV systems are ground into the structural roofing components (photo
mounted, the great majority of residential PV 1.32). In many parts of the United States, stan-
systems, and smaller commercial PV systems, are dard spacing for trusses is 24 inches with older
mounted on the roofs of buildings. Unfortu- homes having structural members at 16 inches. A
nately, some jurisdictions have insurance policies quick check of the exterior mounting feet for the
that prohibit inspectors from going on the roof, array rack should show them to be consistently
making examinations of those critical PV system on some multiple of these dimensions. Racking
components difficult, if not impossible. If a ladder and mounting systems are continually evolving,
is available, and the installing contractor makes and any system must be installed according to the
all areas of the array easily accessible by providing manufacturer’s instructions.
ladders, the inspector might be able to view some The module interconnect wiring should be
of the array from the ladder without going onto firmly secured to the racking members or other-
the roof. The roof is no place to be in inclement wise supported. Those exposed, single-conductor
weather. cables should not be hanging loosely below the
modules where they are subjected to additional
The Array-Mounting and Mechanical mechanical stress from wind loading and the
Considerations possibility of abrading the insulation against
Combination inspectors who are also building in- the roof. Unfortunately, many of the plastic
spectors are probably more aware of the mechan- wire ties that are frequently used to attach these
ical requirements to fasten PV modules to roofs conductors to racking members, although listed
the building structures than typical electrical for outdoor exposure, do not have the necessary
inspectors might be. Most mounting systems, in- longevity for the years of service needed in a PV
cluding PV racking systems, require that the PV
Photo 1.32a and b • Roof trusses at 24 inches on center
array be connected to the structural elements of (more or less). But where are they after the sheathing and
the roof and not just to the thin roof sheathing. shingles are installed?
36 Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code
Photo 1.33 • Plastic cable ties are not durable in the PV ties or clips used to attach and secure the module
environment, particularly these white ones that are not wiring to the racking members could be discussed,
rated for outdoor use.
along with any listing or other information that
system. (See photo 1.33.) It is suggested that addresses the durability of those devices in the
metal clips with rounded edges be used to attach PV application. The installer might be queried on
these wires to provide the longevity needed for a the method of determining where the racking- or
PV system. module-attachment devices were located in rela-
Module connectors should be firmly seated tion to the structural members of the roof.
and, to some extent, able to be visually evaluated
at a distance. But where the conductors have been Torqueing Considerations
properly secured to the racks, the connectors may All electrical connections that require a
be less visible. threaded fastening have a torque requirement
The grounding and bonding methods used for for making that connection correctly. Thread-
the modules and the racks should be evaluated and ed screw or bolt connections are found on
compared with the instructions for those devices. disconnect switches, overcurrent devices, dc
combiners, and inverter inputs and outputs.
Can’t Get on The Roof? Because of the daily cycling of current in these
In jurisdictions where it is not possible for the circuits, it is critical that they be torqued to
AHJ to get to the roof to closely examine the the manufacturers’ specifications. The installer
aforementioned parts of the array closely, it is should be able to provide data on all torque
possible to query the installer about some of the specifications. The torque values that should
things mentioned above. For example, the meth- have been used should be readily available in
od of grounding and bonding the modules and the manuals and cut sheets provided with the
the racks can be discussed while looking at the permit application.
instructions for those pieces of equipment. The The installer should be able to show the AHJ
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 37
Photo 1.34 • All of this equipment has terminals, terminals, and more terminals. Each terminal must be properly torqued.
and inspect these ever-changing electrical power requirements in some states to provide PV “ride
systems. through” of utility disturbances, including low
Inspectors and plan reviewers should have voltage (down to 50% of nominal) and frequency
electronic copies of all codes, handbooks for variations.
those codes, and technical data (including
manuals and specification sheets) for all types Installer Qualifications. While many PV sys-
of systems being inspected (and for equip- tems are being installed by competent individ-
ment that may be installed on those systems). uals and organizations, there are still numerous
Laptop computers, with screens that can be systems being installed by people who have less
read outdoors, with this information (updated than full competency in the required knowledge
as necessary) should accompany each inspector base and skills. Homeowners can install PV
as field inspections are conducted. Communi- systems in some jurisdictions with no permits
cation between inspectors and plan reviewers or inspections other than what the utility might
on a real-time basis via cell phone and wireless potentially require. Unqualified electricians, who
computer link will be required. Using a digital have had no specific PV training, are installing
camera and downloading and transmiting on- PV systems. New “PV installation companies”
site pictures will be necessary. are popping up left and right to take advantage
of the boom in PV installations without being
Facts of Life fully trained to do those installations properly.
More Dangerous. Photovoltaic systems are As an aside, as I write this, I received a call from
potentially more dangerous than typical residen- an electrician who had been hired to install a
tial or commercial electrical power systems. With PV system for a residential customer who had
voltages up to 600 volts dc on residential instal- bought the equipment himself. The electrician
lations and up to a 1000 volts dc on commercial had absolutely no knowledge of how to do the
installations, the voltages are higher than those job or that there were any requirements in the-
of typical electrical systems. If energy storage NEC for such installations. It also appears that
systems are involved, currents may also be higher the customer may have purchased an unlisted
than those found on non-PV systems. Energy inverter on the Internet where all things are
storage systems in factory-sealed containers may available.
be operating at voltages up to 600 volts dc in
residences. AHJ Qualifications. We don’t like to admit it,
but just as with some PV istallers, some author-
More Complexity. Photovoltaic systems are ities having jurisdiction and local inspection
more complex than typical residential or com- requirements are not always up to the task of
mercial electrical power systems and that com- ensuring that installed PV systems are safe and
plexity is continually increasing due to technol- meet the latest Code requirements and safety
ogy changes and changing Code requirements. standards. Proper training and education for local
There are now frequently changing requirements AHJs on the latest technology in PV systems is
for PV rapid shutdown systems to protect first critical for the safe operation of those systems for
responders (690.12). We have dc PV arc-fault cir- many years to come.
cuit interrupter requirements in 690.11. There are
also PV utility-interactive inverters with chang- The Electrical Specialist. There are AHJs in
ing requirements and designs due to new utility the inspection community who have come up
40 Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code
through the ranks as master electricians and have The Permitting and Inspection Process. The
additional training in PV systems. They have process for permitting and inspecting PV systems
been working with PV systems daily since the varies substantially throughout the United States.
beginning—some since as early as the mid-1980s. In some areas of the country, no inspections are
These people are the electrical specialist inspec- conducted on PV systems. In other areas, a per-
tors. These individuals are frequently involved in mit is nothing more than a form filled out noting
PV more than just at the inspection level. They the location of the electrical system and a paid
may be members of code-making panels for the fee. In some states, there are no inspections of
NEC; members of UL Standards Technical Pan- residential PV systems, and the utility is responsi-
els for PV equipment; active members in local ble for ensuring the quality of installations before
IAEI chapters and IAEI sections; and may even allowing the interconnection.
be writing articles in IAEI News. On the other hand, many jurisdictions wisely
require a full permitting package (with diagrams),
The Combination Inspector. At the other end a plan-review stage, and a detailed inspection be-
of the spectrum, the latest trend in the in- fore approving the system as NEC compliant. The
spection community is to hire a “combination” utility then performs their required inspections
inspector who will be responsible for enforcing prior to interconnection. After the system has
several disciplines, such as plumbing, electrical, been powered up, there may be a final inspection
mechanical, and building codes. The theory is to by the AHJ.
hire one inspector instead of two or more due to An expedited permitting process for PV
budget limitations and emphasis on other local systems less than 10 kW was developed by the
issues. This combination inspector may have Solar America Board of Codes and Standards
come from the plumbing industry and is now (now defunct) and a copy can be downloaded
inspecting not only plumbing systems, but also from the SolarABCS web site: http://solarabcs.
electrical power systems, including PV systems. org/about/publications/reports/expedited-permit/
This individual will typically not have a firm index.html.
background in the NEC, let alone the very Numerous other informative documents re-
specific safety requirements associated with PV lating to PV systems are available on the Solar-
systems. Combination inspectors should expect ABCs website at http://solarabcs.org/index.html
and have been provided with training in the Chapters 8, 9, and 10 cover the plan review
basic requirements of the NEC (its first four and inspection of PV system in greater detail.
chapters) and in basic electrical theory—and
where at all possible be mentored by a senior
electrical inspector through on-the-job training. Budget and Administrative Restrictions. In
Individuals who find themselves lacking many areas of the United States, funding is lim-
PV-system training or mentorship are typically ited for inspection organizations. Combination
not to be blamed. They are merely fulfilling an inspectors are being hired more frequently than
obligation placed on them by their employers. specialist electrical inspectors. Budgetary and
Consideration should be given by the jurisdic- manpower restrictions are forcing inspectors to
tion to hiring additional electrical specialist do more inspections per day and, in some cases,
inspectors or they could contract with profes- these restrictions allow only 15 minutes for an
sionals who specialize in PV systems where inspection. A thorough inspection of a PV system
possible. might require two or more hours, including plan
Chapter 1 An Overview of PV Systems and the 2017 National Electrical Code 41
review. In many areas, this amount of time is just This prohibition is particularly troublesome
not available to the inspector. where many commercial PV systems are
Training is also an issue for AHJs who in- roof-mounted and 90% of the PV equipment
spect PV systems. Funding is frequently not that should be inspected is on the roof. In the
available, nor is time allocated to properly train southwestern United States, with common
the inspectors who will be working with the flat-roofed and low-sloped-roof buildings, PV
constantly changing requirements in the Code for systems (and sometimes inverters) are frequently
PV systems. To ensure the safety of the public, mounted on rooftops. Of course, with ac PV
inspectors should at least be as familiar with PV module system or microinverters, nearly all
systems as PV installers and PV system designers. systems that should be inspected are found on
This familiarity requires periodic and continuing rooftops.
training for inspectors.
It should be noted that PV systems and PV Resources
equipment are becoming complex to the extent There are many resources available to inspector
that instructions for installing these systems and plan reviewers. Most equipment manufac-
can no longer be fully included in the NEC. The turers have electronic downloadable PDF files
instructions for installation of that equipment of manuals that will be useful. Here are a few
will be found only in the manuals for the listed magazines (available in print and on the web)
equipment. These instructions can be, to say the that will enable inspectors and plan reviewers to
least, quite complex; far more complex than can keep abreast of the changing technologies.
be put in the NEC [110.3(B)].
Moreover, for unknown reasons, some juris- IAEI News. www.iaei.org/magazine
dictions have insurance policies that prohibit Solar Pro. www.solarprofessional.com
AHJs from going onto rooftops to inspect not Home Power. www.homepower.com
only PV systems but also HVAC equipment. Solar Today. www.ases.org
42 Chapter 2 PV Fundamentals and Calculations
Chapter 2 PV Fundamentals and Calculations 43
02
PV Fundamentals and Calculations
To understand how and why the Code is different meter (W/m2). This is an international constant
for PV systems compared with other electrical sys- and is near the average value of irradiance at sea
tems, it is necessary to first delve into the mysteries level on the surface of the earth. Modules are also
of what they are and how they operate. Inspectors rated at a standard module/cell temperature of 25
need to be familiar with the unique characteristics degrees Celsius (C) [77 degrees Fahrenheit (F)].
of PV modules because the ampacity calculations These two values of irradiance and temperature
and overcurrent device ratings don’t follow the are referred to as standard test conditions (STCs).
usual rules of thumb used in the electrical trades. When the module is exposed to these standard
Additionally, some PV installers may not be using test conditions (and connected to the correct
the proper calculations either. load), the module will produce the rated power at
a maximum power point voltage (Vmpp) and with
Current Sources a maximum power point current (Impp).
Photovoltaic modules are current sources of ener- During evaluation of the safety of the mod-
gy, as opposed to voltage sources such as 120-volt ule [performed by a nationally recognized testing
ac outlets in homes or offices or 12-volt dc batter- laboratory (NRTL), leading to the module being
ies in cars. The output of a PV module, in terms listed as required by NEC 690.4(D)], the ratings
of voltage and current, depends on the load placed of the module are also verified to be within some
on that module. The output is dc, and the load is percentage of the label values. The tolerance on
typically supplied by a utility-interactive inverter, the label values is usually 10 percent but may be
which changes the dc energy into ac energy. as low as 3 percent.
A PV module can be short-circuited indefi-
Standard Test Conditions nitely without damage. And, as will be shown in
Photovoltaic modules are rated for voltage and later chapters, the wiring, the switchgear and the
current output when exposed to a set of standard overcurrent protection are designed in a way that
test conditions. The standard solar intensity will allow entire PV arrays to be short-circuited
(called irradiance) is set at 1000 watts per square without damage.
44 Chapter 2 PV Fundamentals and Calculations
curve is now marked watts. The curve for power rent is relatively insensitive to temperature, but
shows that it reaches a peak for some load both the VOC and Vmpp voltages will be affected. In
between ISC and VOC and this point is called the crystalline PV modules, VOC varies inversely with
maximum power point (Pmpp). Associated with temperature at approximately 0.5% per degree
the power at the maximum power point are Celsius. Peak-power voltage (Vmpp) varies in-
a maximum power point voltage (Vmpp) and a versely at approximately 0.4% per degree Celsius.
maximum power point current (Impp). Figure 2.4 shows this relationship; as temperature
It should be noted that the output voltage of goes down, voltage increases.
a PV module is not constant and varies with the
load. This output is changed by several external Turn Off the Light
environmental conditions in addition to the Photovoltaic modules in utility-interactive sys-
connected load. tems are connected in series and the open-circuit
voltage may approach 600 volts (dwelling), 1000
Sunlight Produces Current volts (commercial), and 1500 volts (utility-scale)
The current output of a PV module is directly in cold weather. The only way to effectively turn
proportional to the intensity of the sunlight off all electricity from a PV module or a PV array
falling on it. The rated currents (both ISC and is to cover it with an opaque material. Working
Impp) are output at the standard test-condition at night on array wiring is an option, but worker
irradiance of 1000 W/m2. However, PV modules safety would be a concern. Lightning in the
are exposed to irradiance values from 0 (at night) distant sky has been known to illuminate arrays
to 1500 W/m2 (if cloud, water, snow, or sand enough to produce electric shocks. High-inten-
enhanced) and the current follows changes in the sity lighting used by fire services may also create
intensity of the sunlight. A 10% reduction in the unsafe voltages in PV arrays.
irradiance value will result in a 10% reduction in
ISC and Impp. However, the open circuit voltage Determining the PV Size and
(VOC) is relatively unchanged with variations in Output to Match the Inverter
irradiance. Figure 2.3 shows the I-V curves for a In the PV design process, the array output must
PV module as the sunlight intensity varies from be matched to the utility-interactive inverter
1000 W/m2 down to 500 W/m2. As can be seen, input. As noted previously, the module voltage
the ISC changes in direct proportion to changes in and current outputs are not constant. The system
irradiance but VOC and Vmpp do not vary nearly as designer must first ensure that, in cold weather
much. conditions, the array output voltage will not
This is a significant fact. The voltage on a PV exceed the voltage rating of the inverter, the con-
module or PV array will generally be present at very ductor insulation, or other connected equipment.
low levels of light, such as at dawn or dusk. Pho- This limit will frequently be as high as 600–1500
tovoltaic arrays can have hundreds of volts on the volts. In a similar manner, all conductors, over-
wiring at dawn and dusk even before the sun direct- current devices, and switchgear must be able to
ly illuminates the front of the modules. Hazardous handle the array output current under worst-case
voltages on exposed terminals in dc combiners, conditions of high sunlight intensity. Exceed-
disconnects, and input terminals to inverters will be ing the voltage rating on inverters, conductors,
present. switchgear, or other equipment would be a Code
A second variation in module output and the violation and has been known to damage such
I-V curve is caused by temperature. Module cur- equipment. [See NEC 110.3(B).]
48 Chapter 2 PV Fundamentals and Calculations
represents the open-circuit voltage of a module been modified to remove these two require-
at -40°C (-40°F). Temperatures lower than -40° ments and only the Code requirements will
are found in some parts of the country and remain for PV modules being installed where
further adjustments to VOC may have to be made the NEC is in force. Advocacy from electrical
where these temperatures are expected. inspectors throughout the country inspired
these changes.
NEC Leads UL Standard 1703
In 1996, during preparations for the 1999 NEC, The 125% Continuous Loads
the PV industry, UL, and the National Fire Pro- Factor
tection Association reached a joint agreement to The requirement to use 125% of the continuous
place all module output correction factors in the load (or 125% of the maximum current in PV
Code. Those proposals were agreed to by all, and circuits) has been with us for many years. It was
the 1999 NEC was modified accordingly. reportedly added to the Code to address nuisance
In Section 690.8, a requirement was estab- operation of overcurrent devices in enclosures
lished to multiply the module short-circuit when conductors were operated at 100% ampac-
current by 125%. This duplicated the module ity continuously. The temperature rise associated
manual instruction to adjust the Isc to account with I2R losses in the conductors, and in the
for normal and expected irradiance values above thermal overcurrent devices themselves, was
1000 W/m2. causing some of these devices to overheat and
Because many areas of the country never nuisance trip or blow. Using the 125% factor
have temperatures as low as -40°, a tempera- results in a conductor that is not loaded contin-
ture-dependent table was added to Section uously at more than 80% of rating. Note that
690.7 showing multiplication factors for Voc 1.25 and 0.8 are mathematical reciprocals of each
that vary from l.00 at an expected low tem- other (1/1.25 = 0.8 and 1/0.8 = 1.25), a fact that
perature of 25°C (77°F) to 1.25 at -40°. Again, will be used below.
instructions in the module manual duplicated
these Code requirements. A Second 125%
Because newer module technologies have Throughout the NEC, feeders and branch circuits
different temperature coefficients than crystalline (as well as overcurrent devices) are rated to oper-
silicon, the 2017 NEC permits module manu- ate on a continuous basis at no more than 80% of
facturers’ temperature coefficients be used where rating. Section 215.2(A)(1) has this requirement,
available rather than Table 690.7. which is also found in other sections of the Code:
UL modified Standard 1703 in 2012 to
remove the 125% multipliers on VOC and ISC “(1) General. Feeder conductors shall have
from PV module instruction manuals. This an ampacity not less than required to supply
solved a significant problem for inspectors the load as calculated in Parts III, IV, and V
and installers who were required to follow of Article 220. Conductors shall be sized to
NEC section 110.3(B), which states that all carry not less than the larger of 215.2(A)(1)
equipment be installed in accordance with (a) or (b).
included instructions. If followed, this section
of the Code (and 690.7 and 690.8) create a (a) Where a feeder supplies continuous loads
double calculation with far too conservative or any combination of continuous and non-
results. Module instruction manuals have continuous loads, the minimum feeder con-
50 Chapter 2 PV Fundamentals and Calculations
ductor size shall have an allowable ampacity Energized and Safe for
not less than the noncontinuous load plus 125 Decades
percent of the continuous load. It has been shown how module output varies
with environmental conditions. The Code-
(b) The minimum feeder conductor size shall required corrections to the rated output are used
have an allowable ampacity not less than the to ensure that system electrical equipment never
maximum load to be served after the applica- has to handle more current or voltage than it
tion of any adjustment or correction factors.” was designed for. The rated output has been
adjusted for worst-case conditions under the as-
The intent of this code requirement, other than sumption that these worst-case conditions exist
the obvious rating factors, is that the 125-percent continually, even when it is known that output
factor (a) is not to be applied at the same time goes to zero every night. Photovoltaic modules
the “conditions of use” factors—such as tempera- will produce dangerous amounts of voltage and
ture and conduit fill corrections on ampacity—in current for 40 years or more. These adjustments,
(b) are applied. From a math point of view 1.25 and the other Code requirements, represent
(125%) and 0.8 are reciprocals, so they can be minimums to ensure that this sunlight-generat-
used two ways. The conductor size can be calcu- ed electricity is safely contained for that period
lated by taking 1.25 times the continuous load of time or longer.
(maximum current for a PV or other generator)
or by taking 0.8 times the conductor ampacity
(before adjustments for conditions of use) to find
PV Math—Some Sample
the maximum continuous currents.
Calculations
Looking at the PV array in a PV system, many
This same 125-percent factor (or the condi-
installers and inspectors are confused by new
tions-of-use factors if they result in requiring a
system voltage calculations that may be required
larger conductor) is applied to PV source and
by the Code specific to PV systems. Code Infor-
output circuits, so the dc PV source circuit or dc
mational Notes also address voltage drop that
output short-circuit current might be multiplied may be applied to the dc wiring from the array to
by 1.25 twice before selecting a conductor or the inverter. This section will cover both of those
overcurrent device. A factor of 1.56 (1.25 x 1.25 subjects.
= 1.56) is commonly used to determine ampac-
ity, but this is a shortcut and the slightly more PV Math—Module Open-Circuit
complex actual calculations will be addressed in Voltage
below. A PV module, or a string of series-connected
The VOC should be calculated following the modules, has a rated open-circuit voltage that
requirements of 690.7. The factors will be less is measured (and labeled on the module) at an
than 125 percent unless very low temperatures irradiance of 1000 W/m2 and a cell temperature of
(-40°) are expected at the installation location. 25°C (77°F). This voltage increases from the rated
Table 690.7(A) may be used, but it will yield voltage as the temperature drops below 25°C. It is
more conservative values for the cold weather necessary to calculate this voltage at the expected
maximum system voltage, which, in many cases, lowest temperature at the installation location to
may not result in the most cost-effective system ensure that it is less than the maximum input volt-
design. age of the inverter and less than the voltage rating
Chapter 2 PV Fundamentals and Calculations 51
of any connected conductors, switchgear, and over- add to the confusion, PV module manufacturers
current devices (usually 600 volts). Because parallel present these temperature coefficients in two
connections of strings do not affect open-circuit different ways.
voltage, the number of strings connected in parallel
is not involved with this calculation. Percentage Coefficients
Where module temperature coefficients are One way of presenting these data is to specify
available, Section 690.7 of the NEC allows them as a percentage change, and they are ex-
the open-circuit voltage of a PV array to be pressed as a percentage change in VOC for a change
determined at the lowest expected temperature in temperature measured in degrees Celsius. Note
at the installation location. Alternatively, Table that the temperature used is a change in tempera-
690.7(A) can be used to determine a multiplier ture from the rated 25°C.
that was applied to either the module- or string- For example: The Voc temperature coefficient is
(a series connection of PV modules) rated VOC. given as -0.36% per deg Celsius, or -0.36% / °C.
The rated VOC is measured at 25°C (77°F) and The module has a VOC of 45 volts at 25°C
is printed on the back of the module and in (77°F) and is going to be installed where the
the module’s technical literature. To use Table expected lowest temperature is -10°C (14°F).
690.7(A), determine the lowest expected tem- Because the temperature coefficient is given in
perature, look up the factor from the Table for degrees Celsius, all numbers must be in degrees
that temperature (which ranges between 1.02 at Celsius. The change in temperature is from 25°C
24°C to 1.25 at -40°C), and multiply the factor to -10°C. This represents a change in tempera-
by the rated VOC. ture of 35 degrees. The minus sign in the coef-
For example, a module has a VOC of 35 volts ficient can be ignored if we remember that the
(at STC) and is going to be installed where the voltage increases as the temperature goes down
temperature dips to -17°C. The factor from Table and vice versa. Of course, if you are an engineer
690.7(A) is 1.18 and the cold temperature VOC or a mathematician, feel free to use the minus
for this module is 35 x 1.18 = 41.3 volts. sign in an algebraic equation.
If 12 modules were going to be connected in Applying the coefficient shows that the per-
series, the string VOC in cold weather would be 12 centage change in VOC resulting from this tem-
x 41.3 = 495.6 volts. perature change is 0.36% / °C x 35°C = 12.6%.
The string voltage at STC-rated conditions Note that where division and multiplication
could also be calculated first and then apply the are involved in a calculation, they are performed
temperature factor applied. In this case, the 12 from left to right. Where additions and sub-
modules in series would have a string open-cir- tractions are combined with multiplications
cuit voltage of 12 x 35 = 420 volts at 25°C. Then and divisions, the additions and subtractions are
the 1.18 factor is applied to get 1.18 x 420 = performed before any multiplications. Paren-
495.6 volts; the same answer as before. theses may be added to clarify the order of the
While Table 690.7(A) is still valid and was re- operations, and calculations inside the parenthe-
fined with 5°C increments in the 2011 NEC, new ses should be performed first.
modules may have different technologies than the This percentage change can now be applied to
silicon module technology used to develop the the rated VOC of 45 volts. And, at -10°C, the VOC
table. The use of the module temperature coef- will be 1.126 x 45 = 50.67 V.
ficients will provide a more accurate calculation For the mathematically oriented person, the
of the cold weather maximum system voltage. To equation looks like this:
52 Chapter 2 PV Fundamentals and Calculations
VOC [cold] = VOC [STC] x (1 + ((-0.36)/100) x 550 / 78.2 = 7.03 modules and the
(-10-25))) = 45 x (1 + .0036 x 35) = 45 x 1.126 = correct answer would be seven modules.
50.67
7 x 78.2 V = 547.4 V
Eleven of these modules could be connected in
series and the cold-weather voltage would be 11 Eight modules could not be used because the
x 50.67 = 557.37 V, and that voltage is less than a open-circuit, cold-weather voltage would exceed
600-volt equipment limitation. 550 volts.
Photo 2.1 • DC-to-dc converter. Solar Edge Power Optimizer. Courtesy Solar Edge.
while also maximizing the output of the string temperature relationships of the output character-
containing that module. In nearly all cases, the istics of a normal dc PV module.
specifications relating to the output parameters of
the MLPE will not be comparable to the output
of the basic PV module. In nearly all cases, the Conductor Sizing and
manufacturer’s instructions provided with the Overcurrent Device Ratings
listed or certified module-level power electronics Inspectors or plan reviewers should be very
device must be followed (110.3 B). There is no familiar with the methods of calculating currents,
possible way that the NEC will be able to address conductor sizes, and overcurrent device protection
these numerous varying operating parameters and required in PV systems because, in many cases, PV
installation requirements for the numerous systems installers will not have performed these calculation
in a general manner. in a manner that follows NEC requirements.
For example, when a certain dc-to-dc converter Historically, most residential and light com-
is connected to an appropriately sized module, mercial electrical wiring and inspections of these
the maximum voltage output of this converter systems have involved indoor wiring at room
is rated at 60 volts. Moreover, on the surface, it temperatures [30°C (86°F) or less]. The am-
would appear that (at most) ten of these devices pacity tables in NEC Section 310.15 and Table
could be connected in series to a utility-interac- 310.15(B)(16) were developed with those condi-
tive inverter with a dc input rated at a maximum tions in mind. The commonly used molded-case
of 600 volts. However, the manufacturer’s litera- circuit breaker is rated for use with conductors
ture suggests that, optionally, 15 of these devices with 75°C insulation and they have a rated maxi-
could be connected to that 600-volt inverter— mum operating temperature of 40°C.
because the inverter from that manufacturer With these conditions and equipment charac-
communicates with each of the dc-to-dc convert- teristics in mind, some electricians have generally
ers and holds its output under actual operating used the 75°C insulated conductor ampacity
conditions to a total voltage per string of less tables in Table 310.15(B)(16) and not bothered
than 600 volts. too much with temperature corrections [Table
While this particular dc-to-dc converter is 310.15(B)(2)(a)] and terminal temperature limits
connected to a PV module that has the normal [110.14(C)] because they were not necessary or
PV module ratings on the label, they are to be were included in the tables being used.
essentially ignored and the ratings that apply to the However, dc PV conductors normally operate
dc-to-dc converter are to be used in determining in an environment that is too hot for conductors
whether it and the PV module have been installed with 75°C insulation. Conductors with 90°C
correctly. Some dc-to-dc converters have a very low insulation must be used, and appropriate tem-
output (one or two volts) when they are discon- perature and conduit fill corrections must be
nected from the inverter or from communications applied along with verification that connected
with the inverter. Of course, when the MLPE is equipment terminal temperatures (60°C or
fully contained within the module junction box, 75°C) are not exceeded. To do otherwise and
the certified or listed PV module with its internal use the short-cuts of the old days will result
electronics will have a label showing the output in conductors that may be larger than Code
characteristics of the combination. The output requirements (resulting in unnecessary costs) or
characteristics of the module-level power electron- that may have inadequate ampacities under the
ics may, in many cases, no longer follow the classic extreme conditions of use.
56 Chapter 2 PV Fundamentals and Calculations
Throughout the Code, circuits are sized based Correction Factors. The maximum currents
on 125% of the continuous load plus the non- calculated in 690.8(A) after the application
continuous load. See 210.19(A)(1) and 215.2(A) of adjustment and correction factors.”
(1). This requirement establishes a situation
where conductors and overcurrent devices are Note for the Exception: In other sections of
not subjected to more than 80% of rating. (Note: the Code, such as 215.2(A)(1)(a), this exception is
1/1.25 = 0.80.) expanded to indicate that with this type of over-
Electricians typically use the 125% factor and current protection, the conductor ampacity can
then also apply the conditions of use factors be rated at 100% of the continuous currents (or
(temperature and conduit fill) sequentially. In maximum currents in the case of PV circuits). The
recent editions, the NEC has clarified the re- author is not aware of any dc overcurrent protective
quirements in 210.19(A)(1) and 215.2(A)(1), as device in an assembly rated for 100% operation.
well as in 690.8, so that both factors are not to be
applied at the same time to the same circuit. See 215.2(A)(1)(a) Exception No. 1: If the assembly,
the 125 percent requirement below. including the overcurrent devices protecting the
In the Code, we have at least two or three re- feeder(s), is listed for operation at 100 percent of
quirements that must be met in sizing conductors. its rating, the allowable ampacity of the feeder
First is the definition of ampacity found in Ar- conductors shall be permitted to be not less than
ticle 100. Ampacity is “The maximum current, in the sum of the continuous load plus the noncontin-
amperes, that a conductor can carry continuously uous load.
under the conditions of use without exceeding its
temperature rating.” Author’s Note: This book will not address the
Next is the 125 percent requirement, or condi- 2017 NEC requirements related to “adjustable
tions of use factors. From 690.8(B), Conductor electronic overcurrent protective devices” found in
Ampacity: (In part): 690.8(B), 690.8(B)(3), and 690.9(B)(3) because
(B) Conductor Ampacity. PV system currents these devices and their requirements are not well
shall be considered to be continuous. Circuit defined in either the 2017 NEC or in the relevant
conductors shall be sized to carry not less than UL Standards. At best, they are adjustable trip
the larger of 690.8(B)(1) or (B)(2)…. circuit breakers and are handled like other circuit
breakers. Revisions, clarifications, or deletions
“(1) Before Application of Adjustment and to these requirements are expected in the 2020
Correction Factors. One hundred twen- NEC.
ty-five percent of the maximum currents
calculated in 690.8(A) before the application Terminal Temperature
of adjustment and correction factors. Limitations and Operating
Temperature Limitations
Exception: Circuits containing an assembly, Section 110.14(C) requires that the temperature
together with its overcurrent device(s), that is of the conductor in actual operation not exceed
listed for continuous operation at 100 percent of the temperature rating of terminals on the con-
its rating shall be permitted to be used at 100 nected equipment.
percent of its rating. An added requirement for any listed equip-
ment, such as overcurrent devices, is that they not
(2) After Application of Adjustment and be used in a manner that deviates from the listing
Chapter 2 PV Fundamentals and Calculations 57
or labeling on the product [110.3(B)]. Most PV be 24.3 x 1.25 = 30.375 amps [690.8(A)(2)].
combiners operating outdoors in the sunlight will An exception to these calculations is allowed
have internal temperatures that exceed the 40°C for PV systems of 100 kW or greater, where a
rated operating temperatures of commonly used professional electrical engineer may make al-
fuses and circuit breakers. Overcurrent devices ternate maximum current calculations using an
listed for (and required in) PV applications will industry accepted method.
have a 50°C-rated operating temperature.
B. AC inverter output circuits
Calculating Conductor Sizes and In the ac output circuits of a utility-interactive
Overcurrent Device Ratings inverter (or in the ac output circuit of a stand-
The following method for determining ampacity alone inverter), the continuous current is taken
meets the three Code requirements above and at the full rated output power of the inverter. It
finds the smallest conductor that can be used to is not measured at the actual operating current of
meet these requirements. The method also deter- the inverter (which may be a small fraction of the
mines the rating of the overcurrent device where rated current due to a small PV array connected
required. It is consistent with the requirements to a large inverter). Usually the rated current is at
found in Article 690 and elsewhere in the Code. the nominal output voltage (120, 208, 240, 277,
or 480 volts). The rated output current is usually
Step 1. Determine the maximum circuit specified in the manual, but may be calculated by
current [690.8(A)] dividing the rated power by the nominal voltage.
For stand-alone inverters, which can provide
Photovoltaic dc circuits and PV ac circuits are some degree of surge current, it is the rated power
not “load” circuits; the Code uses the term current that can be delivered continuously for three hours
instead of load. For Code calculations, all dc and or more [690.8(A)(3)].
ac PV currents are considered continuous and In some cases, the inverter specifications will
are based on worst-case outputs or are based on give a rated current that is higher than the rated
safety factors applied to rated outputs [690.8(B)].
power divided by the nominal voltage. In that
The term maximum is used in Article 690 instead
situation, the higher current should be used. This
of continuous current used elsewhere in the Code.
higher current usually has been determined at a
Daily variations in these currents is ignored.
lower-than-normal line voltage.
For a utility-interactive inverter operating at a
A. Photovoltaic dc circuits
nominal voltage of 240 volts and a rated power
In the dc PV source and dc PV output circuits,
of 2500 watts, the continuous current would be
maximum currents are defined as 1.25 times the
2500 W/240 V = 10.4 A.
rated short-circuit current (ISC) marked on the
A stand-alone inverter with a model number of
back of the module. If a module had an ISC of 7.5
3500XPLUS operates at 120 volts and can surge
amps, the maximum current would be 7.5 x 1.25
to 3500 watts for 60 minutes. However, it can
= 9.375 amps [690.8(A)(1)].
only deliver 3000 watts continuously for three
If three strings of modules (module ISC = 8.1
amps) were connected in parallel through a fused hours or more. The rated output current would be
dc combiner, the PV output circuit of the com- 3000 W / 120 V = 25 A
biner would have an ISC of 3 x 8.1 = 24.3 amps C. Stand-alone inverter battery currents
[690.8(A)(2)] and the maximum current would In either a stand-alone system or a battery-
58 Chapter 2 PV Fundamentals and Calculations
ture estimation method and is not an ampacity Example 3. Take the 6 AWG conductor and
calculation method. It is used after the conduc- 50 amps of maximum current used in Example 1
tor size has been selected based on the ampaci- above. This conductor is connected to a terminal
ty calculation. with a 60°C marking.
Take the conductor size in Step 3 above. Find From Table 310.15(B)(16), a 6 AWG conduc-
the lowest terminal temperature limit for this tor in the 60°C column can carry a current of 55
conductor at any termination. Use that termi- amps.
nal temperature limit (either 60°C or 75°C) 1.25 x 50 = 62.5 amps. This is larger than the
to enter the ampacity per Table 310.15(B) 55 amps from the Table and this terminal will be
(16). For the conductor size selected, read out heated above 60°C.
the current in the correct column, either the When we increase the conductor size to 4
60°C column or the 75°C column. There are no AWG, the table gives us 70 amps, which is
temperature adjustments or conduit fill adjust- greater than 62.5 amps and the terminal will stay
ments in this estimation process. below 60°C.
The current from the table must be equal to
or greater than 125 percent of the maximum Example 4. Use the 4 AWG conductor select-
current. If the conductor meets this requirement, ed in Example 2 connected to a terminal with a
then the terminal temperatures are going to be 75°C temperature limit. The maximum current is
less than the 60°C or 75°C limit for that conduc- 50 amps.
tor and that maximum current. The 125-percent 1.25 x 50 = 62.5 A
factor accounts for many items not calculated in
this simplified temperature estimation process. A 4 AWG conductor in the 75°C column of
Table 310.15(B)(16) shows a current of 85 amps. and overcurrent devices listed for PV applications
Because this is greater than 62.5 amps, the con- are rated for use at 50°C. Photovoltaic combiner
ductor will operate cooler than the 75°C terminal boxes operating in outdoor environments may
temperature limit. No increase in conductor size experience ambient temperatures as high as
is necessary. 50°C. Exposed to sunlight, internal temperatures
An alternate, more conservative approach to may reach or exceed 55°C to 60°C. Anytime the
terminal temperature limitations would be to use an operating temperature of the overcurrent device
ampacity table of 60°C or 75°C for the conductor exceeds 50°C, it may be subject to nuisance trips
size calculations. However, this will result in a con- at current values lower than its rating. In these
ductor larger than necessary because the advantages situations, the manufacturer must be consulted
of the 90°C conductor insulation are not considered. to determine an appropriate derating. At high
operating temperatures, an overcurrent device with
Step 4. Calculate the rating of the overcurrent a higher rating will activate at the desired current;
device, where required. however, using a manufacturer’s certification of
a rating at a higher-than-listed temperature may
Because PV modules are current-limited, invalidate the listing on the device.
overcurrent devices are frequently not needed for
one or two strings of PV modules connected in Step 5. Verify that the overcurrent device pro-
parallel [690.9(A) Exception]. In systems with tects the conductor selected under the conditions
three or more strings of modules connected in of use
parallel, overcurrent devices are usually required. Where an overcurrent device is required, it
must protect the conductor under conditions
A. Rating determined from maximum currents of use. Conductors may be protected using the
The overcurrent device rating is determined round-up allowance found in 240.4(B).
by taking the maximum current for any of the
circuits listed in Step 1 and increasing that Example 5. A circuit has a maximum current of
maximum current by 125% (or by multiplying 70 amps. After conditions of use (4 conductors in
it by 1.25). Nonstandard values should be the conduit, 48°C) are applied, a 3 AWG, 90°C
rounded up in most cases [690.9B)]. conductor is selected to meet all ampacity and
In a few rare cases, an overcurrent device 75°C terminal-temperature requirements.
installed in an enclosure or in an assembly may The ampacity after conditions of use have been
be tested, certified, and listed as an assembly applied is 115 x 0.8 x 0.82 = 75.4 A.
for operation at 100% of rating. The con- The required minimum overcurrent device
ductor ampacity, before conditions of use are for this level of maximum current is 70 x 1.25 =
considered, can be 100% of the maximum 87.5 A.
current. The author knows of no dc overcur- A 90-amp overcurrent device would typically
rent devices installed in an enclosure for PV be used. It’s been suggested to use an 80-amp
systems that have such a rating. overcurrent device, but that would result in
running it at more than 80% of rating and, in dc
B. Operating temperature affects overcurrent PV circuits, could result in nuisance trips during
device rating short periods of cloud-enhanced irradiance.
Standard overcurrent devices are listed for a However, the largest overcurrent device that
maximum operating temperature of 40°C (104°F), could be used to protect the 3 AWG conductor
Chapter 2 PV Fundamentals and Calculations 61
with an ampacity of 75.4 amps is an 80-amp Table 310.15(B)(3)(c) has been removed from
overcurrent device. A 90-amp overcurrent device the 2017 NEC.
is the smallest allowed in this circuit. Photovoltaic professionals may elect to contin-
The conductor size would have to be increased ue to use Table 310.15(B)(3)(c) from the 2014
to 2 AWG for full compliance with NEC re- NEC (again, removed in the 2017 NEC) as a
quirements. safety factor to increase the durability of the PV
The ampacity of a 2 AWG, 90°C conductor source and output circuits over the 50-plus-year
under the conditions of use is 130 x 0.8 x 0.82 life of the PV system. This is based on the fact
= 85.28 A. With the allowed roundup, the next that conduits in sunlight that are 12 inches above
standard value of fuse is 90 amps. the roof, for example, have been observed to be
The 2 AWG conductor can be protected by the too hot to handle and are certainly significantly
required 90-amp overcurrent device. hotter than the surrounding ambient air tem-
peratures.
Raceways in Sunlight and Suppose, for example, there is a large PV
Varying Conditions of Use array being installed on a flat-roof commercial
Note that 310.15(B)(3)(c) no longer requires building. Each PV source circuit (aka string
all the temperature adders required by the 2014 of modules) requires two conductors (positive
NEC. Only conductors and raceways with and negative) plus an equipment grounding
bottoms less than 23 mm (7/8 in) from the roof conductor that will originate at the end of each
are subject to a temperature adder of 33°C (60°F). module string and be routed to a dc combiner
62 Chapter 2 PV Fundamentals and Calculations
It would appear that while all different condi- the 2014 NEC Handbook uses a single hot section
tions of use should be examined, the physics of and then uses the entire circuit length to make
the situation indicates that attention should be the determination. In the PV environment, it
focused on the larger raceways in the sun con- appears reasonable to use just the length of the
taining more conductors. Plan reviewers could adjacent circuit with a higher ampacity, as this
easily do these calculations, but, unfortunately, section will be the heat sink for the shorter
this level of detail on conduit mounting is not conductor.
frequently found in plans submitted with permit If the most restrictive circuit section can be
applications. eliminated as the determining ampacity for the
Plan reviewers, inspectors, and installers take whole circuit, then the next most restrictive
note: In PV circuits, that electrician’s old rule of section should be examined in the same manner.
thumb of using a 30-amp fuse or breaker on a Eventually, considering all conditions of use, an
10 AWG conductor is frequently not valid. Also, ampacity of the circuit will be determined. At
the fusing in dc combiners should be carefully that point, other factors, such as terminal tem-
calculated along with the size of these source cir- perature limits, should be considered.
cuit conductors, as the PV module short-circuit
current continues to increase as larger and larger Sources of Fault Current
PV modules are being built. In most ac power circuits, the utility source of
energy becomes the source of the overload or
The 10-Percent, 10-Foot Rule fault currents, and the current in a circuit usually
Section 310.15(A)(2) may give some relief for the flows from the utility source to the load. The
high temperature conditions on the roof. requirements in Section 240.21 can be followed
where circuits are protected from overcurrents
“Selection of Ampacity. Where more than where they receive their supply: the utility end of
one ampacity applies for a given circuit length, the circuit.
the lowest value shall be used. However, in dc PV circuits, the PV modules
have limited current even when short-circuited
Exception: Where different ampacities apply under fault conditions. This limited current also
to portions of a circuit, the higher ampacity applies to the strings of series-connected mod-
shall be permitted to be used if the total por- ules and, to some extent, the subarray PV output
tion(s) of the circuit with the lower ampacity circuits where several strings of modules are con-
does not exceed the lesser 3.0 m (10 ft) or 10 nected in parallel. As we move from the modules,
percent of the total circuit.” to the strings and to the output of parallel con-
nected strings forming subarrays to the output of
On a roof with PV circuits, there are going to parallel connected subarrays, into the output of
be several sections of the circuit that will have the entire array, the available currents that could
different calculated ampacities. If the worst-case contribute to faults and overloads increase. As
(lowest-ampacity) section is less than 3.0 m (10 these currents increase, the circuit conductors are
feet) in length, or less than 10 percent of the increased in size appropriately and the ratings of
length of the adjacent section with a higher am- overcurrent devices are also increased.
pacity (whichever is less), then the higher ampac- The source of potentially high overload currents
ity may be used for both sections. The Code uses and fault currents is not the PV module or the
the term circuit portion and the example in string of PV modules. It is the combined output
64 Chapter 2 PV Fundamentals and Calculations
of those strings in parallel and the combined inverter output circuits) and also connected
output of subarrays connected in parallel that to sources having higher current availability
pose the source of overload and fault currents. (e.g., parallel strings of modules, utility power)
Section 690.9(A) addresses this peculiarity of shall be protected at the higher current source
current-limited sources. connection.”
03
PV Modules — Installation
Considerations
Photovoltaic modules must be installed and con- distance (from zero to six inches or more), the
nected in a manner that meets Code requirements roof may be subjected to both uplift and down-
and that will ensure a safe, durable system with force wind loadings—again concentrated through
maximum output for possibly 50 years or more. the mounting feet of the rack. If the roof has
several layers of old shingles under the array, the
The PV Array — Mechanical structural limit of the roof may be approached.
Considerations Leaving up to two layers of old shingles in place
The PV array consists of individual PV modules is a common practice during re-roofing, so we
attached to a metal rack. That rack is usually can assume that the basic roofing structure has a
attached to the structural members of the roof in a safety factor allowing the extra load of old shin-
typical rooftop-mounted residential utility-inter- gles or the PV array, but possibly not fpr several
active PV system. Although not an electrical-code
issue, some attention must be given to the attach-
ment of the PV array to the building structure.
Various national, state, and local building codes
address the attachment of structures to build-
ings—especially in earthquake and high-wind
areas.
Most roofs in recent years have been built
using span tables in the building codes or using
trusses designed by professional engineers. Pho-
tovoltaic arrays may add up to 4 to 5 pounds per
square foot of dead weight to the roof structural
members, and that weight will be concentrated
through the rack mounting feet. Also, because Photo 3.1 • Array rack attachment point—used in dry cli-
mates. Without flashing, the roof may leak during heavy
the PV arrays are mounted above the roof some rain.
Chapter 3 PV Modules — Installation Considerations 67
that some of their connectors are interchangeable ically strong and not separate under high wind
with connectors from other manufacturers in loadings and ice loadings (and possibly thermal
terms of an electrical and mechanical compati- stress) to which they may be subjected. There can
bility. On casual inspection by the AHJ and PV be no deterioration of the electrical contact due
installer, this mechanical and electrical compat- to a mismatch, however slight, of the metals used
ibility appears to be true. Unfortunately, Under- in each half of the mating connectors. When
writers Laboratories and the members of the viewing the connector as a splice in the cable, the
Standards Technical Panel for UL Standard 6703 Code requires the splice to be at least as robust
for connectors have established that none of these as the unspliced cable before the connector was
mixed pairs of connectors have been evaluated inserted at that point [110.14(B)].
for compatibility by an independent third-party When connectors are mixed and matched, the
Nationally Recognized Testing Laboratory like listing and certification of the PV module as a
UL, CSA, TUV and ETL—the four OSHA-rec- complete assembly—including the connectors—
ognized NRTLs authorized to certify PV equip- becomes invalid. If a mixed, unmatched, pair of
ment. Each connector manufacturer modifies the connectors fails either electrically or mechanically
materials and procedures used to manufacture and causes damage at some time in the future, the
their connectors in a proprietary manner. Even listing of the module, and compliance with NEC
though there may be an electrical and mechanical requirements [including Sections 690.4(D) and
compatibility at one point in time, there is no 110.3(B)] could be a significant issue.
continued evaluation to ensure that changes in At this time, connectors should only be mated
the production process of one manufacturer will in pairs from the same manufacturer and in the
result in their connectors remaining compatible same series. If equipment must be connected that
with connectors from another manufacturer. uses connectors from different manufacturers,
It is easy to understand how a slight modifica- then some sort of cable connector adapter must
tion of the metals used in one connector (while be field manufactured or purchased that will
being compatible with the metals in the mating allow the connectors to be mated in pairs from
connector by the same manufacturer) would not the same manufacturer. It is probably not a good
be compatible over long periods of time with the idea to cut connectors off of a given product
metals used in a connector by another manufac- and change those connectors to a connector set
turer. from a manufacturer that will mate with the
Similarly, a modification of the plastics used in connector set on the other product. Although
one connector (while meeting the requirements engineers at Underwriters Laboratories have said
to perform effectively with the plastics from the this procedure does not violate the listing on the
same manufacturer in the mating connector) may product, several PV module manufacturers have
not be compatible over the long term with the stated that cutting the connectors off their listed
plastics used by another manufacturer. Even min- module or other equipment will invalidate the
ute differences in the thermal expansion rating of warranty on that product. Therefore, it might be
different plastics could pose problems. more appropriate to make a short length of cable
These connector assemblies must remain with different connectors on each end to keep the
electrically and mechanically secure for the very mating pairs from the same manufacturer togeth-
long power production life of PV modules. They er, even though this will double the number of
must be watertight, not allowing water to reach connectors in the circuit and possibly reduce the
the electrical connections. They must be mechan- reliability of the system.
Chapter 3 PV Modules — Installation Considerations 71
Photo 3.9 • Y cable adapter with MC-4 type connectors. Photo 3.10 • Inline fuse with MC-4 type cable connectors.
All connectors must mate with matching connectors from Connectors must be mated with cable connectors by the
the same manufacturer. Uncontrolled backfeed currents same manufacturer. Temperatures in installations exposed
to sunlight may result in fuses being operated outside
may pose problems.
their listed rating. Courtesy of Leader Group.
A Warning. It is becoming more common In situations where the Y adapter has fuses
to have to strings of modules combined with for both inputs internal to the adapter, or where
a Y-type cable adapter which may or may not inline cable fuses are used on each input, the
have fuses inside the adapter or connected to environment that the fuses operate in must be
the adapter for each input string (photo 3.9). considered (photo 3.10). Fuses listed for PV
Without fuses, the issue is: Are there any po- applications are listed with a maximum operating
tential external currents that can damage the temperature of 50°C. On a typical rooftop ap-
modules or string wiring? External currents plication, it is probable that the adapter and fuses
may originate from additional combinations of will be in an ambient temperature (around the
module strings elsewhere in this circuit or from cable/adapter) environment of 40°C to 50°C and
backfeed currents from the inverter. These are be subject to solar heating from direct exposure
the sources of external overcurrents that must be to sunlight. Although the 2017 NEC has deleted
addressed before this type of unfused paralleling any sunlight adders on temperature for cables
can take place (690.9 Exception). In many cases, that are more than 7/8 inch above the surface
it is difficult to obtain information on whether [310.15(B)(3)(c)], it seems evident that conduc-
the inverter can backfeed currents into faults tors anywhere within that 2014 NEC space of 36
in dc PV array wiring. These adapters are made inches will be subjected to additional solar heat-
by numerous manufacturers and, of course, the ing. In a recent PV installation, my tools on an
manufacturer of the Y adapter must be the same open stand about 12 inches above the roof in the
manufacturer who makes the connectors used on sun became far too hot to handle without gloves
the PV modules and the connector used on the in just a few minutes. It is likely that the fuses in
output cable from the Y adapter to ensure the these Y adapters will frequently be subjected to
listings on all connectors and modules remains more than 50°C, even when they are behind the
intact. All MC-4 type connectors are not equal. PV modules on a rooftop installation. This will
72 Chapter 3 PV Modules — Installation Considerations
Photo 3.12 • Plastic wire ties, especially white ones (not Photo 3.14 • Many potential issues: EMT clamp and tape
UV rated), are likely to fail in a few short years. used to secure bundle of cables, plastic wire ties, foam
sealant, and colored (non-black) PV wire insulation.
Photo 3.13 • Open conduit entry to dc combiner should Photo 3.15 • Proper termination fitting for exposed con-
not be used. ductors entering a dc combiner.
white as a grounded conductor, if necessary, at to require a “red is positive and black is negative”
the time of installation where used as an exposed color coding (at least for conductors in conduit)
outdoor conductor at the array. because there will be no grounded conductor.
Normally, the exposed single-conductor cables However, both ungrounded conductors can still
are transitioned to a conduit wiring method when meet Code if they are black. As mentioned, basic
the circuits leave the PV array. Conductors in black is preferred for all exposed outdoor conduc-
conduit, while they could be USE-2/RHW-2 tors due to an increased UV resistance.
(for flame and smoke retardant) or PV wire, are The newest bipolar PV arrays and bipolar
typically THHN/THWN-2 because they are less inverters should not be ignored. In these sys-
costly and the -2 rating is needed for the outdoor, tems, there will be red positive conductors,
wet environment and the high temperatures of black negative conductors, and possibly white
conduit in sunlight [310.15(B)(3)]. Unfortunately, grounded conductors (where these conductors
14-10 AWG conductors with THHN/THWN- are solidly grounded). Of course, some installers
2 insulation are not widely available due to low will use black for both ungrounded conductors
demand. Of course, THHN/THWN is available, (acceptable under the NEC), and this will pose
but it does not have a wet, 90°C rating. problems for the inspector and the troubleshooter
Demand will increase for the small-conduc- when the cables are misconnected. If the “center
tor THHN/THWN-2 conductors as inspec- tap” dc conductor is functionally grounded, then
tors start applying 310.15(B)(3) to rooftop it, too, may be black. There are numerous circuit
HVAC installations. Due to the limited marking, routing, and grouping requirements in
availability of 14-10 AWG THHN/THWN-2, 690.7(C), 690.31, and 690.41.
XHHW-2 would be a suitable, superior alter- As before, grounded conductors in PV dc
native and may not be subject to additional disconnects should not be switched. Bolted, iso-
deratings due to sunlight exposure or raceways lated, terminal-block connections are acceptable,
more than 7/8 inch above the roof. but not required. Section 690.31(F)(1) will be
Although most PV arrays installed during the clarified in the 2020 NEC and possibly by a TIA
recent past have had the dc-negative conductor for the 2017 NEC.
grounded (and colored white), newer arrays will
be installed to meet the functional grounding Wiring Methods—Continued
requirements of the 2017 NEC. Of course, there All circuits in a PV system, as in other electrical
are no designated color codes for ungrounded systems, must be wired using a Chapter 3 or a
conductors, but common sense would indicate 690.31 method that is suitable for the application
that ungrounded conductors would be clearly and the environment. The circuits between dc PV
marked. It would be understandable if they were disconnects and inverters are considered to be PV
colored red for positive conductors and black for output circuits (and also inverter input circuits).
negative conductors installed in conduit. They should be in a metal raceway or metallic cable
However, many installations use black conduc- assembly. Of course, local codes may dictate other
tors for both and that is still acceptable under the requirements, such as the need to use raceways
Code. In positively grounded systems where the inside commercial structures for all electrical wiring.
positive grounded conductor is colored white, the
ungrounded negative conductor would be most PV Module Grounding
clearly understood if it were black. Grounding PV modules to reduce or eliminate
Functionally grounded PV systems would seem shock and fire hazards is necessary but somewhat
Chapter 3 PV Modules — Installation Considerations 75
difficult. Copper conductors are typically used must be used because this is the only point tested
for electrical connections, and the module frames and evaluated by the certification or listing agen-
are often aluminum. It is well known that copper cy for use as a long-term grounding point. UL
and aluminum do not mix (as was discovered from has established that using other points (such as
numerous fires in houses wired in the 1970s with the module structural mounting holes), coupled
aluminum wiring)—dissimilar metals are not to with typical field installation “techniques,” may
come into contact with each other (110.14). not result in low-resistance, durable connections
Photovoltaic modules have aluminum frames. to aluminum module frames. If each and every
Many are anodized for color or have mill finishes possible combination of nut, bolt, lock washer,
and many are clear-coated. The mill finish alumi- and star washer could be evaluated for electrical
num (and any aluminum surface that is scratched) properties and installation torque requirements,
quickly oxidizes. This oxidation, and any clear- and if the installers would all use these compo-
coat or anodizing, form an insulating surface that nents and install them according to the torque
makes for difficult long-lasting, low-resistance requirements, it might be possible to use the
electrical connections (in, for example, frame structural mounting holes for grounding.
grounding). The oxidation and anodizing is not a New grounding devices are coming to market
good enough insulator to prevent electrical shocks, that will eventually ease the problem of mod-
but it is enough to make good electrical connec- ule grounding. However, until they have been
tions difficult. evaluated with specific modules and the module
UL Standard 1703 (published by UL and instructions address these devices, they do not
developed and maintained by the Standards meet the requirements of UL Standard 1703 or
Technical Panel 1703) is used to certify and NEC Section 110.3(B).
list all PV modules sold in the United States. The latest PV module grounding methods use
It requires stringent mechanical and electrical engineered, manufactured mounting systems
connections between the various pieces of the or racking systems that have been listed to UL
module frame to ensure that these frame pieces Standard 2703 for PV module racks. This standard
remain mechanically and electrically connected evaluates and certifies racking systems for mechan-
over the life of the module. These low-resistance ical strength, for electrical grounding continuity, or
connections are required because a failure of for both. A module is typically mounted with clips
the module insulating materials could allow the to the rack and, in many cases, the clips mount and
frame to become energized at up to 600 volts to ground the module to the rack so that only a single
1500 volts (depending on the system design). copper equipment-grounding conductor attached
The NEC requires that any exposed metal surface to the rack is needed to ground all the modules
be grounded if it could be energized (250.4 and on that rack. The module instruction manual must
250.110). Installers of PV systems are required show where and when top clips for mounting or
to ground each module frame (690.43). NEC grounding can be used. The listed rack instructions
Section 110.3(B) and UL Standard 1703 require should indicate that the rack has been evaluated
that the module frame be grounded at the point for mounting and grounding with a particular
where a designated grounding provision has been PV module. Efforts are underway to categorize
made. The connection must be made with the PV module frames into categories related to size,
hardware provided (if any) using the instructions material, strength, and coating. Then, rack man-
supplied by the module manufacturer. ufacturers will have to test only a few categories
The designated point marked on the module to establish that racks will be able to mount and
76 Chapter 3 PV Modules — Installation Considerations
ground numerous PV modules that are in those specify the necessary hardware. These methods,
categories rather than testing each module. and the hardware, will be evaluated during the
Some PV module manufacturers are providing listing of the module. It is likely that thread-cut-
acceptable grounding hardware and instructions. ting or thread-forming screws of the past will no
Other manufacturers provide less-than-adequate longer be used.
(or no) hardware and unclear instructions. Revi- For modules that have been supplied with
sions of UL 1703 are addressing these issues. In inadequate or unusable hardware (or no hardware
every case, the module manufacturer’s hardware at all), there is one way to meet the intent of the
and instructions should be used (where possible) Code and UL Standard 1703.
to ground the module at the points marked on For situations requiring an equipment-
the frame. UL Standard 1703 requires that the grounding conductor larger than 10 AWG, a
module manufacturer outline the specific ground- lay-in, tin-plated copper, direct-burial lug with
ing methods to be used, and either provide or a stainless-steel #10 screw, nut, flat washers,
Chapter 3 PV Modules — Installation Considerations 77
Photo 3.17 • Connecting tin-plated copper lay-in lug to Photo 3.18 • Grounding a metal roof—oops, outdoor rat-
aluminum. ed lug and wire needed.
Belleville spring, and lock washers can be used corrode. The same can be said for other screws,
to attach a direct burial lay-in lug to the module lugs, and terminals that are not suitable for
frame at the point marked for grounding (photo outdoor applications.
3.16). Before attaching the lug to the module, a The direct-burial lay-lugs are tin-plated lugs,
stainless-steel brush should be used to remove made of solid copper, with a stainless-steel screw.
any anodizing, oxidation, or clear-coating from They accept a 4 AWG to 14 AWG copper con-
the aluminum module frame. A thin coat of ductor. They are listed for direct-burial use and
antioxidant film should be placed on the clean outdoor use and can be attached to aluminum
aluminum surface. Flat washers are required to structures (the tin plate allows this). The much
prevent lock washers from digging into the soft cheaper tin-plated aluminum lay-in lugs look
copper of the tin-plated lug or the aluminum of identical, but have a plated screw. They are not
the module frame. The Belleville washer pro- listed for outdoor use. If module grounding is to
vides uniform tension, and a torque screwdriver be done with a 14 AWG to 10 AWG conductor,
should be used for all electrical connections then the lay-in lug may not be needed.
(photo 3.17). Some new grounding lugs have Other application-specific grounding lugs are
been listed for use without the antioxidant com- available that will penetrate the module-protect-
pound because the design of the lug penetrates ing and -insulating coatings without the need for
the oxidation. However, these should be evaluat- surface preparation of the module.
ed with a specific module because of the varying What size conductor should be used? The
thickness of the anodizing and clear-coat on minimum Code requirement is for the equipment
the modules. It is not acceptable to use the grounding conductor for PV source and output
hex-head, green grounding screws (even when circuits to be sized to carry 1.25 times the short-cir-
they a have 10-32 threads) because they are not cuit currents at that point, using the requirements
suitable for outdoor exposure and will eventually of 250.122 and based on the overcurrent device
78 Chapter 3 PV Modules — Installation Considerations
protecting these circuits. For PV source circuits equipment-grounding conductors where there is
where there are no overcurrent devices, an assumed any possibility that these metal surfaces may be
overcurrent device per 690.9(B) shall be used per energized by conductor insulation failures (photo
250.122. While this may allow a 14 AWG conduc- 3.18). Rodent damage and abrasion of conductor
tor between modules, a conductor this small would insulation could cause module frames, racks, or
require physical protection between grounding metal roofs to be energized (photo 3.19).
points. An equipment-grounding conductor smaller Single-conductor exposed wiring (USE-2 or PV
than 6 AWG can be routed behind the modules, wire) is allowed only in the near vicinity of the PV
from grounding point to grounding point, if the array to interconnect the modules and to return
conductors are well protected from damage, as they the end of the string conductor to the origination
would be when run in the module or rack frames in point of the string wiring. At this point, exposed
a roof-mounted array [250.120(C)]. If needed, an wiring must transition to one of the more com-
8 AWG or 6 AWG conductor may be required (to mon wiring methods found in Chapter 3 of the
meet the Code or to satisfy an inspector) and then Code, unless the conductors have a dual marking,
lay-in lugs or a listed grounding device should be such as RHW-2 or XHHW-2. Typically, this will
used (690.45 and 690.46). be some form of raceway, such as electrical metal
The Code allows metal structures to be used tubing. If the array output conductors penetrate
for grounding and even allows the paint or other the surface of the structure before reaching the first
covering to be scraped away to ensure a good readily accessible dc PV disconnecting means, then
electrical contact. Numerous types of electrical they must be in a metal raceway where routed inside
equipment have parts that are grounded with the structure. Metal raceways include rigid metal
sheet metal screws and star washers. This works conduits, electrical metal tubing, intermediate metal
(particularly in the factory environment) on conduit, metal wireways, and flexible metal conduit,
common metals like steel, but not on aluminum and include Type MC metallic cable assemblies.
due to rapid oxidation. The transition fitting keeps water, dirt, rodents, and
The racks and any metal roofing panels under other material out of the conduit. A rain head or a
the PV array should be connected to earth with cord grip might be used (photo 3.20).
Chapter 3 PV Modules — Installation Considerations 79
Photo 3.21 • Equipment-grounding conductor improperly connected to the module. (Incorrect hardware and incorrect
installation procedure.)
the frame pieces (so that any failure in module
UL Standard 1703—Grounding insulation or external conductor insulation will
versus Bonding result in all pieces of the frame receiving equal
The current edition (2012) of UL 1703, Standard voltage). Factory bonding also ensures that when
for Flat-Plate Photovoltaic Modules and Panels, the module frame is properly field-grounded at
delineates the differences between grounding one of the marked and tested points, the entire
and bonding. Bonding refers to the factory-made module frame is maintained at the ground (earth)
electrical connections between the four or potential under fault conditions.
more aluminum sections of the module frame. During the bonding process, all screw fasteners
Grounding refers to the field-installed electrical (when used) are precisely torqued to the specified
connection between the aluminum module frame value by automated equipment or by trained
and the equipment-grounding system (usually technicians using torque screwdrivers. Factory
consisting of copper conductors). bonding materials and methods are evaluated for
Bonding the frame pieces together at the low resistance and durability during the certifica-
factory, using very specific materials and methods, tion and listing processes. After the listing, if the
results in a durable electrical connection between manufacturer changes any of the bonding mate-
80 Chapter 3 PV Modules — Installation Considerations
rials or methods, the changes must be reevaluated ing connections made by installers in the field.
by the listing agency. The materials (including any Instruction manuals and hardware (sometimes
screws or washers) are not specified generical- supplied) show techniques that are not always
ly—they are specified to the original equipment consistent with good electrical connections (pho-
manufacturers and must always be obtained and to 3.21). Field-made connections using threaded
used from those sources unless any change is fasteners are rarely torqued to the specified value,
reevaluated by the certification or listing agency. even when that value is given in a module’s
Compare this precisely controlled and evalu- instruction manual (because not all PV installers
ated factory bonding system with field-installed have or carry torque screwdrivers or wrenches).
grounding techniques used to connect copper The NEC requires that where threaded fittings
equipment-grounding conductors to aluminum or connections are provided with a torque value,
module frames. Grounding a PV module is a calibrated torque device shall be used to tight-
difficult at best, for a number of reasons. The first en that connection or terminal [110.14(D)].
is that module manufacturers may not realize Field-grounding connections may or may not be
the importance of this connection to the over- inspected by AHJs, and they are never tested for
all safety of the system. The revised UL 1703 overall continuity. Also, because PV systems can
distinguishes the differences between bonding operate without trouble for many years, there may
and grounding. Manufacturers may have the be little motivation to inspect these connections
impression that bonding techniques and materi- after the original installation.
als used in the factory may be applied to ground-
Chapter 4 The Inverter — Operation and Connections 81
82 Chapter 4 The Inverter — Operation and Connections
04
The Inverter—Operation
and Connections
Utility-interactive inverters range in size from connects. With these designs, an external dc
175 watts (photo 4.1) to 2.5 megawatts and come PV disconnect must be installed (690.15). Even
in all shapes, sizes, and colors (photos 4.2 and if the inverter has more than one set of input
4.3). New models are being introduced monthly. terminals for paralleling separate strings (source
These inverters will be listed by UL, CSA, ETL, circuits) of modules, external dc PV disconnects
and TUV Rheinland. All of these organizations must be used on each input (photo 4.4).
are designated as nationally recognized testing Other inverters have internal dc disconnects
laboratories by OSHA for testing and listing PV or disconnect housings that attach to the main
modules, inverters, combiners, and charge con- inverter section containing the electronics
trollers using standards published by UL. package. The method used to mount the internal
Some inverters have only a single set of dc disconnects, the ease and accessibility of the dis-
input terminals and no internal dc or ac dis- connects, and the way they are separated from the
inverter proper vary from brand to brand
and from product to product. Installers
and AHJs must reach a mutual conclusion
on the suitability of these disconnects for
meeting the various isolation and discon-
nect requirements in the Code.
Because the inverters are listed with the
disconnects, it can be presumed that the
disconnects are properly rated for the dc
load break operation and that they would
meet the requirement for the isolator and
disconnect requirements of 690.15.
Meeting the requirement for equipment
Photo 4.1 • Westinghouse/Andalay AC PV modules using
Enphase microinverters. isolators and disconnects (690.15) will
Chapter 4 The Inverter — Operation and Connections 83
Photo 4.3 • SMA Sunny Central 2.5 MW utility-scale inverter. Photo 4.4 • Inverter with internal dc disconnects
Courtesy of SMA-AG. plus additional external dc and ac disconnects.
require additional considerations. If an inverter to be removed to service the inverter, then some
required factory service, could the energized PV degree of safety is ensured. However, if ener-
source or output circuits be disconnected from gized conductors must be disconnected from
the inverter safely when there is no external internal switches and pulled through small con-
disconnect? If a disconnect housing is attached duit knockouts, the situation must be examined
to the inverter and that housing does not have carefully. Will qualified people, who know how
84 Chapter 4 The Inverter — Operation and Connections
Automatic Operation
Photo 4.5 • Transformerless inverter with internal dc dis-
connect.
Today’s utility-interactive inverter is designed,
manufactured, tested, and certified or listed to
operate automatically in the PV system. There are
no transfer switches. The inverter seamlessly con-
verts dc power from the PV array into ac power
that is fed to the utility-supplied premises wiring
system. The output of the inverter is functionally
connected in parallel with the premises’wiring
(and loads) and the utility service.
One of the most important aspects of the in-
verter is the anti-islanding circuit. An anti-island-
ing circuit is designed to keep the utility electrical
system (both premises wiring and utility feeder)
safe in the event that the utility is being serviced
Photo 4.6 • Inverters with attached dc disconnects that or is disconnected at some point in the trans-
can be separated from inverters.
mission system, distribution system, or premises
to disable the array, be doing the removal? Or wiring system.
will an unqualified person try to pull energized Unlike an engine-driven generator, which can
conductors through the knockouts? (See photos feed power into a blacked out or disconnected
4.5 and 4.6.) local utility feeder system, an inverter anti-island-
Chapter 4 The Inverter — Operation and Connections 85
ing system prevents an inverter from energizing Code requirement, between the array-rated output
the “dead” power system. current and the manufacturer’s specified maximum
This circuit prevents the inverter from deliver- dc inverter input current. Normally, a PV array is
ing ac power if the utility voltage and frequency rated in watts at standard test conditions of 1000
are not present, or if they are not within narrowly watts per square meter (W/m2) of irradiance and
defined limits. This circuit monitors the voltage a cell temperature of 25 °C. In most cases, an array
and frequency at the output terminals of the will operate, on average, at a lower power output
inverter. If the voltage varies more than plus because of normal and expected power lost due to
ten percent or minus twelve percent from the module heating. For this reason, inverter manufac-
nominal output voltage the inverter is designed turers typically suggest sizing PV arrays (standard
for (120, 240, 208, 277, or 480 volts), the inverter test condition dc watts) at ten to twenty percent
cannot send power to the output terminals. Nor greater than an inverter’s ac power output rating. It
is there any voltage on these terminals (from the does no short-term harm to connect an even larger
inverter) when the inverter shuts down if the PV array to an inverter because the inverter must
circuit from the utility is at zero voltage. In a limit its output to the rated value no matter how
similar manner, if the frequency varies from 60 much array power is applied. If this oversized array
Hz to more than 60.5 Hz, or less than 59.3 Hz, is used, the inverter will spend more operating
the inverter also cannot send power to the ac out- time each day at rated power output than it would
put. If the utility power is suddenly not present with a smaller array. The penalties for designing
at the output terminals for any reason (inverter a system in this manner will be increased mod-
ac output disconnect opened, service disconnect ule cost for the larger array; some lost power on
opened, meter removed from the socket, utility sunny, cool days; and possibly a slight reduction in
maintenance, or utility blackout), the inverter the inverter’s lifespan due to longer operation at
senses this and immediately ceases to send power full-power higher internal temperatures. However,
to the output terminals. systems installed where microclimates reduce
The anti-islanding circuit in the inverter irradiance during portions of the day, or where
continues to monitor the ac output terminals the local utility limits the inverter-rated power
and when the voltage and frequency from the output, this type of operation may result in more
utility return to specifications for a period of five energy being delivered from the output than
minutes, the inverter is again able to send PV would be possible with a conventionally sized
power to the ac output. When the inverter is not system.
processing dc PV power into ac output power,
it essentially stops taking power from the PV DC Input Fusing
array by moving the load on the PV array to a Some models of small (<10 kW) and large (>100
point where there is no power. Usually this is the kW) inverters have dc input fuses mounted
open-circuit voltage point for the PV array. inside the inverter or inside a combiner or
disconnect device attached to the inverter. The
Circuit Sizing smaller fuses (30 amps or less) are usually mount-
Direct Current ed in “finger-safe” fuse holders that allow the fuse
The dc input circuit and conductors to the invert- to be safely replaced in an unenergized (no load
er are sized based on the dc short-circuit current current) state.
in those conductors (that sizing is covered in pre- However, when fuse ratings go over 30 amps,
vious chapters). There is no direct relationship, or with values as high as 400 amps or more, these
86 Chapter 4 The Inverter — Operation and Connections
output current is all that can be delivered, but— the inverter’s instruction manual and should not
more than likely—the reduced line voltage due be exceeded [110.3(B)].
to the fault will cause the inverter to shut down. Where fused or unfused disconnects are used for
With the available maximum current limited to the ac inverter output disconnect (or the required
the rated inverter output current and the overcur- utility disconnect), the circuit connected to the
rent device rated at 125 percent of that current, utility source should be connected to the supply
it is doubtful that the overcurrent device would side (top) of the disconnect with the inverter ac
trip or blow from currents from the inverter. output connected to the load side (bottom). A
That device would, of course, activate on the high warning label is required, because even when the
available fault currents from the utility. disconnect is opened, the inverter ceases to pro-
duce power within a fraction of a second and the
Connections exposed load-side terminals pose no shock hazard.
Dedicated Circuit However, the connected utility side terminals,
NEC 705.12(B)(1) requires that the inverter while protected, are still energized.
output be connected to the utility power source
at a dedicated disconnect and overcurrent pro- GFCIs and AFCIs
tective device (OCPD). In most systems, this is The ac output of a utility-interactive inverter
a backfed breaker in a load center/panel board should not be connected to a ground-fault circuit
[705.12(B)]. Inverters may not have their outputs interrupter (GFCI) or to an arc-fault circuit in-
connected directly to another inverter or directly terrupter (AFCI) circuit breaker, as these devices
to an ac utility-supplied circuit without first are not currently designed to be backfed and will
being connected to the dedicated disconnect or be damaged if backfed. These devices have termi-
OCPD. Utility-interactive microinverters and nals marked “line” and “load” and have not been
ac PV modules are exceptions to this rule be- identified, tested, or listed for backfeeding.
cause they are tested and listed to have multiple
inverters connected in parallel on a single circuit Ground-Fault Protection on Main
with only one OCPD or disconnect device for Breakers
an entire set of inverters. More details on the The NEC has had, for many editions, a require-
requirements found in 705.12(B) of the NEC and ment (230.95) that solidly grounded wye services
earlier editions will be found below. rated at 150–600 volts phase-to-phase and 1000
The OCPD must be sized at a minimum of amps or more have ground-fault protection
125 percent of the rated inverter output current (GFP). Connecting a PV inverter ac output
(or the total of the output-rated output current on the load side of these GFP-equipped main
from multiple microinverters or ac PV modules). breakers may pose safety issues.
It must also protect the circuit conductor from Circuit breakers are manufactured with numer-
overcurrents from the utility side of the connec- ous optional accessories, including (depending on
tion. It is usually not a good idea to install a larger the manufacturer and model) shunt trips, auxilia-
OCPD than the minimum required value (but ry switches, remote indicators, power operation,
allowing a round up to the next standard value adjustable trips, and GFP trip mechanisms.
is okay and needed) because the inverter may, as While UL Standard 489 requires tests for evalu-
part of the listing or instructions, be using the ating the backfeed suitability of the basic circuit
OCPD to protect internal circuits. The maximum breaker, most of the accessories are not evaluated
value of allowable overcurrent device should be in for backfeeding. In fact, backfeeding may have no
88 Chapter 4 The Inverter — Operation and Connections
main breaker GFP from tripping? How is the device. It should be tested a second time
ground fault contained or interrupted? to ensure that the device was not damaged
Some manufacturers are wary of putting during the first test.
some sort of GFP device on the inverter output
because this is a nonstandard connection and In many cases, it may be easier to implement a
any ground faults detected might only be those supply-side (of the main GFP breaker) PV con-
originating between the device and the inverter, nection as allowed by 705.12(A) and 230.2(A)(5)
not load ground faults. / 230.82(6). These connections will be discussed
Some manufacturers have a main breaker GFP in a later chapter.
that can take inputs from multiple ground-fault
sources like dual utility feeder systems. But these Functional Grounded Systems
would be found in limited, special instances It is likely that the type of PV system being
where there are multiple utility feeds. installed (with respect to grounding) will be de-
termined by the inverter topology. That topology
Summary will, in the future, most likely result in a func-
The requirements of the NEC are stringent, but tional grounded PV system. The internal methods
can be met. There are no one-size-fits-all solutions by which the inverter achieves the functional
to this issue. The following steps should be fol- grounding may, to some extent, determine the dc
lowed before connecting a PV system that could input and ac output circuit configurations. The
backfeed a GFP breaker. There may be others. inverter instruction manual will have the appro-
priate instructions.
1. Accurately determine that all ground-fault
protection devices are suitable for operation Newer Inverter Technologies
in a backfed manner with a utility-interac- Microinverters
tive PV inverter. The inverters that have been covered above are
2. Select an appropriate GFP device that can known as “string inverters” because they operate
be connected to the inverter’s outputs to with a string of series-connected PV modules.
control ground-fault currents from that These inverters range in power from more than
source. one megawatt down to approximately 700 watts.
3. Make an engineering assessment of the DC maximum system voltages range from 125
magnitudes of the potential and available volts to 1000 volts and higher. Inverters con-
fault currents from both utility and PV nected to one (or possibly two) PV modules are
sources to the load circuits being protected. classified as microinverters.
Circuit impedance calculations under fault The Enphase microinverter is a typical exam-
current levels for all sources and the load ple (photos 4.10 and 4.11). It is a small inverter
impedance should be made. (hence the name) that is designed to work with a
4. Determine the proper setting for all adjust- single PV module and to operate at a maximum
able-trip ground-fault protection devices that of approximately 70 volts on the dc input. The
will ensure that the load circuits are protected inverter is connected directly to the PV module
from all ground-fault current sources. using the existing conductors and connectors
5. With the GFP breaker being back fed with (now locking in most cases) attached to both the
current from the PV inverter, the GFP de- module and the inverter. Available units are rated
vice should be tested using the internal test in the 170-watt to 500-watt range, but as with
90 Chapter 4 The Inverter — Operation and Connections
It would appear that these inverter output cir- Nevertheless, it is possible to mount an ac load
cuits could be wired using any Chapter 3 wiring center on a roof with proper solar shielding and
method suitable for the environment (indoors, or use it to combine the outputs of U-I inverters or
hot, wet, and UV outside, and hot in attics). sets of microinverters.
The metal raceway requirement of 690.31(G) The rating of any combining panel and the
applies only to the always-energized dc PV ampacity of conductor from that panel to the
source and dc PV output circuits on or in a backfed breaker in the main load center (as well
building. as the rating of the main load center and the
Flush-mounted inverters are starting to appear backfed breaker) must meet 705.12(B) require-
on the market, and they will have a ventilation ments that are covered in Chapter 7.
system to remove the internal heat generated The ac output conductor for a set of inverters
during the inverting process. must have an ampacity of 125 percent of the
An ac GFCI device should not be used to continuous currents for all the inverters on that
protect the dedicated circuit to the microinverter circuit. The backfed circuit breaker in the panel
or ac PV module, even though it is an outside must be rated the same, and if an odd current rating
circuit. None of the small GFCI devices (5 mA to is determined, the breaker rating should be the next
30 mA) are designed for back feeding and will be larger size. The breaker must protect the conductor
damaged if backfed. In a similar manner, most ac under the conditions of use, and the conductor am-
AFCIs have not been evaluated for backfeeding pacity must be derated for those conditions of use.
and may be damaged if backfed with the output of The ac output circuit from each set of inverters
a PV inverter. must have an equipment-grounding conductor
to facilitate OCPD operation during ac ground
Combing Multiple Sets of faults. Some microinverters have a three-wire
Microinverters or AC PV output through a four-contact connector. The
Modules unused terminal in the connector is reserved for
In multiple strings of inverters, there is no NEC future use. The three active pins in the connector
requirement that an ac combining panel (load are 240 V L1 and L2 and a neutral. There is no ac
center) be located on the roof. In fact, most equipment-grounding conductor. This lack of an
NEMA 3R load centers must be mounted equipment-grounding conductor in the cable re-
against a surface to keep water from penetrating quires that the equipment-grounding conductor
holes in the back panel. Such a surface may have for the microinverter or ac PV module be an ex-
to be added to properly mount a 3R load center ternal connection to the inverter case, where the
on a roof. There might be problems meeting case is metal. This external equipment-grounding
110.26 clearance requirements. conductor must be connected to the fixed wiring
A further issue with an OCPD on a roof is system (usually, but not always conduit) where
heating of the device over its rated 40°C oper- that wiring system originates. The ac module or
ating temperature. Gray load centers in the sun microinverter instructions will cover grounding
will normally operate 10°C to 20°C hotter than requirements and should be followed [110.3(B)].
the local ambient temperature (which, in some Unless the microinverter bracket has been de-
cases could be 40–50°C). This may be difficult signed and evaluated as a grounding or bonding
to compensate for when considering available jumper, grounding the microinverters does not
equipment, the size of ac conductors attached to ground the rack or the modules (and vice versa).
inverters, and listing restrictions on the inverters. There is only one ac neutral-to-ground bond in
92 Chapter 4 The Inverter — Operation and Connections
Disadvantages
There may be some cost impact of using ac PV
modules or microinverters on each module when
compared with using single-string inverters.
However, two factors must be considered. The
cost of dc switchgear and the required conduit (or
other appropriate wiring method) for dc conduc-
tors inside a building, plus the cost of the single
Photo 4.17 • DC-to-dc power converter attached to the inverter, must be compared with the added cost
back of each PV module. Courtesy of SoarEdge. of multiple small inverters or ac PV modules with
an inverter on each module.
occur if hot modules are connected in series with Then there are the life cycle costs. Modules are
cooler modules. guaranteed for power production for 25 years,
Shading is also a problem in a conventional but can be expected to produce power for as long
string-inverter configuration. The shading of a as 50 years. Large inverters generally have an
single module will result in a power loss from average longevity of about 15 years. Microinvert-
that module, but may also reduce power from the er manufacturers, using different construction
other, non-shaded modules in the string. methods and topologies, are predicting signifi-
The microinverter and the ac PV module work cantly longer lives for their products. However,
at the individual module level. Each inverter ex- the failure of a microinverter in a system or on
tracts the maximum power from that module no an ac PV module may necessitate disassembling
matter what the other modules in the PV array some portion of the PV array to gain access to
are doing. The output of each is independent the failed device. Time will reveal all.
of the other modules/inverters in the set. The
outputs of the microinverters or ac PV modules DC-to-DC Converters
are connected in parallel, rather than in series, DC-to-dc converters are on the market. They are
and this isolates one from another. small boxes with leads that attach to the output
The outputs are at 120, 208, and 240 volts ac and of each module. These boxes act somewhat like
these ac output circuits act much like ac branch a microinverter by decoupling the actions of one
circuits. They go dead when the ac utility power is module from others in the string so that shading
removed at any disconnect in the circuit, so they is less of a problem. Of course, the output of
do not pose the safety hazards associated with the these devices is dc, not ac like the microinverter.
daytime “always-energized” dc circuits operating Some of these devices can be used on just a few
at hundreds of volts between the modules and the modules in a PV array, but others are required for
96 Chapter 4 The Inverter — Operation and Connections
every module. Some devices work with a stan- or topology. However, because all of these dc-
dard string inverter, but others require a special to-dc converters should be listed per 690.4(D),
inverter made by the same manufacturer. Most installers and inspectors are generally going to
are connected in series like a normal string used have to rely on instruction manuals and label-
with a string inverter. ing supplied with these new devices for proper
In some cases, the specialized inverter re- system design and installation [110.3(B)]. The
quired with some of these devices communicates concepts of short-circuit current and open-cir-
and controls the performance of the individual cuit voltages used in the design and installation
dc-to-dc converters connected to each module. of standard string module systems will not
Removing the ac power from the inverter or apply to these products.
turning it off can, in some cases, shut down the
individual converters, removing dc voltages from Summary
the wiring. Numerous microinverters and ac PV modules
These devices have a wide variation in system are being installed, and while they are directed at
design and connection requirements. There the smaller residential systems, systems as large
are several sections of the NEC that address as several megawatts have been installed using
general requirements for dc-to-dc convert- microinverters. They are being sold in home
ers and they are found in Figure 690.1(a), improvement centers, building supply houses, and
690.2, 690.4, 690.7(B), 690.8(A)(5) and (6), local electrical supply houses and the public is
690.9(A), 690.11, 690.15, and 690.53(3). The buying them. Inspectors should become familiar
requirements are self-explanatory and are not with these devices and the Code requirements
associated with any particular product design that apply to them.
Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems 97
98 Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems
05
Energy Storage Systems;
Batteries in PV Systems
Article 706, Energy Storage battery systems operating at below 60 volts dc, and
Systems this would include PV systems using 12-volt and
Article 706, Energy Storage Systems (ESSs), was 24-volt nominal battery systems and a few 48-volt
added to the 2017 NEC, and all references to bat- nominal systems. However, some of the require-
teries or other energy storage systems previously ments, in Article 480, like for battery disconnects,
found in Article 690 are now in this section. This apply only to systems operating over 60 volts dc.
new section is quite lengthy and has requirements Installers of these low-voltage, but high-current,
that were not previously in the Code, such as a battery systems will have to exercise common
requirement to determine and mark the rated sense in designing these systems, as will AHJs
short-circuit current of the ESS. Article 480, inspecting them. Article 720, Circuits Operating
Storage Batteries, remains in the Code and has at Less Than 50 Volts (direct current or alternating
some of the same new or revised requirements current), is not going to help because it excludes
that appear in Article 706. PV systems in Article 690, Parts I and VIII.
Note that a PV system, as defined in Article
690, is separate and distinct from any energy “706.1 Scope. This article applies to all
storage system that it may be connected to. This permanently installed energy storage systems
separation, and the new grounding definitions (ESS) operating at over 50 volts ac or 60 volts
and requirements for a PV system, may compli- dc that may be stand-alone or interactive with
cate the grounding requirements for both systems other electric power production sources.”
where they are combined. It will take time, and
possibly the 2020 NEC will clarify this. Energy Storage Systems
Section 690.71 states that an energy storage Defined in Detail in the Code
system connected to a PV system must be installed “Energy Storage System (ESS). One or more
in accordance with Article 706, which applies to components assembled together capable of stor-
ESSs operating over 50 volts ac or 60 volts dc. It ing energy for use at a future time. ESS(s) can
would appear that now only Article 480 applies to include but is not limited to batteries, capacitors,
Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems 99
and kinetic energy devices (e.g., flywheels and nents but, instead, are composed of individual
compressed air). These systems can have ac or dc components assembled as a system…
output for utilization and can include inverters
and converters to change stored energy into Informational Note: Other systems
electrical energy. will generally be comprised of dif-
ferent components combined on site
“Energy Storage System, Self-Contained. to create an ESS. Those components
Energy storage systems where the compo- would generally be tested and listed
nents such as cells, batteries, or modules and to safety standards relevant to the
any necessary controls, ventilation, illumina- application.”
tion, fire suppression, or alarm systems are
assembled, installed, and packaged into a This chapter will examine only chemical energy
singular energy storage container or unit. storage systems (batteries) that might be found
in an off-grid, stand-alone PV system or in a
Informational Note: Self-contained residential or small commercial PV system with
systems will generally be manufac- battery backup for part or all the loads. In many
tured by a single entity, tested and cases, these battery systems will be classified as an
listed to safety standards relevant to Energy Storage System, Other, because they will be
the system, and readily connected on field-assembled and installed at the final location.
site to the electrical system and in the
case of multiple systems to each other. Batteries in PV Systems
Electrical power outages are becoming more
“Energy Storage System, Pre-Engineered common in recent times with man-made and
of Matched Components. Energy storage natural disasters and aging utility infrastructure.
systems that are not self-contained systems With natural disasters, such as Hurricane Sandy,
but, instead, are pre-engineered and field-as- tornadoes, and other severe weather conditions,
sembled using separate components supplied many people who are already using PV systems
as a system by a singular entity that are (and many that do not have PV systems) are
matched and intended to be assembled as an going to be interested in using PV systems in
energy storage system at the system installa- the event of electrical power outages. Electrical
tion site. inspectors can expect to see increasing numbers
of battery-backed-up, utility-interactive PV
Informational Note: Pre-engineered power systems.
systems of matched components for
field assembly as a system will gen- PV Plus Batteries Means Power When
erally be designed by a single entity the Utility Goes Out
and comprised of components that These backup systems allow owners to operate
are tested and listed separately or as some or all the loads in a building using a special-
an assembly. ly designed and configured PV system with bat-
teries in the absence of the utility service (photo
“Energy Storage System, Other. Energy 5.1). These systems can be as small as a system
storage systems that are not self-contained or that can power a radio or cell phone charger.
pre-engineered systems of matched compo- They can also be as large as necessary to run all
100 Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems
Figure 5.1 • Components in a battery-backed-up, utility-interactive PV system. The PV array may feed the batteries by
two different means. See text and the following Figures.
Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems 101
Figure 5.1 shows the basic elements of a The designated protected (backed up) loads
battery-backed-up, utility-interactive PV system. may be supplied by either the utility (when pres-
Green arrows represent dc power/energy flow ent) or by the PV inverter output (supplied from
and red arrows represent ac power/energy flow. the batteries when the utility is absent). Where
Double-headed arrows represent bidirectional the PV system power output exceeds the building
power/energy flow. loads, the excess energy is fed into the utility and
renewable energy credits or net-metering bene-
DC-Coupled Battery Charging fits may be accrued. At night, or at other times
There are two main types of battery-backed-up, when the PV production is low, power for the
utility-interactive PV systems. The first (and old- loads is purchased from the utility and fed to the
est) is what is called a dc-coupled charging system. main loads through the main panel or through
As shown in Figure 5.2, the PV array has a nom- the multimode inverter to the protected loads.
inal voltage of 24 volts or 48 volts and normally In general, the battery stays fully charged at all
operates through a charge controller to charge a times, but there are some systems in which the
battery bank. The battery bank is connected to a stored energy in the battery can be sent (“sold”)
multimode, utility-interactive inverter and that to the utility with proper programming of the
multimode inverter is connected to the house loads equipment.
and to the utility using two separate and distinct ac When the utility is not present, the PV array
input/output circuits. When the utility is present, and battery combination and the multimode
the PV system charges the batteries through the inverter continue to operate the loads connected
charge controller. Power is taken from the batteries to the protected loads subpanel to the extent
(or directly from the PV system when the batteries that the size of the PV system and the capac-
are fully charged) through the multimode inverter ity of the battery bank can supply the energy
where it is converted to ac power. required by those protected loads. The multi-
102 Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems
Charge Controllers
Standalone systems and dc-coupled utility-in-
Photo 5.3 • 30-A charge controller with display. Courtesy
teractive systems with battery banks will also
of Blue Sky Energy. have charge controllers that regulate the state-
of-charge of the battery bank. Charge controllers
mode inverter will not send power to the main come in many sizes, shapes, and colors (photos
(unprotected) loads or to the utility connection, 5.3, 5.4, and 5.5). When properly adjusted, they
but continues to monitor that utility connection protect the batteries from being overcharged.
for voltage and frequency. The main panel gets Installers are responsible for adjusting these
no power from any source. When the utility devices properly. Inspectors should verify good
comes back online with the proper voltage field terminations, proper conductor sizes, and
and frequency characteristics, the multimode appropriate overcurrent devices protecting those
inverter will reconnect and the system becomes conductors.
Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems 103
Photo 5.6 • AC-coupled system. The gray utility-interactive string inverters are at the top and yellow hybrid inverters be-
low. The storage batteries are in green cases. The rotective plastic shield between batteries and electronic equipment is
not shown.
(voltage or frequency variation), the multimode can operate 24 hours a day, so the total amount
inverter senses this and stops sending power to the of PV array energy that can be stored in the
now unenergized utility lines (and the main load battery—and the capacity of the battery and
panel). However, it continues to monitor them for size of the inverter—determine how long the
proper voltage and frequency, which would indi- loads can be operated and how many loads can
cate that the utility is back online. At this time, on be connected at any one time.
the load ac input/output of the multimode invert- Photo 5.6 shows an ac-coupled, battery-
er, the battery supplies energy to the inverter and backed-up, utility-interactive system. The gray
it will become the correct frequency and voltage utility-interactive inverters are above the yellow
reference source to supply not only the protected multimode inverters and the batteries are in the
loads, but also to keep the utility-interactive in- rear of this very compact installation. There is
verter connected to the PV system, operating and normally a clear insulating service panel in front
producing energy (in the daytime). of the batteries; the panel was removed when the
Again, the size and number of loads that can photo was taken.
be connected and operated for any short or In either case, with dc charging or ac-coupled
long period of time depends on the size of the charging of the batteries, the certified or listed
PV array and the capacity of the battery bank. multimode inverter ensures safety for the power line
Typically, the PV array may only supply energy and utility personnel anytime the utility is shut-
for four to six hours per day. Loads obviously down or operates abnormally.
Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems 105
Battery Considerations battery are sized based on the rated output of the
Batteries, although not considered a source of charge controller, irrespective of the size of the
energy, can store considerable amounts of energy. PV system feeding it. These conductors should be
They should not be considered current-limited sized at 125 percent of the rated output current
sources as are PV modules, but, rather, they have of the charge controller [706.23(C)]. There
the characteristics of a constant-voltage output, should be an overcurrent device and a disconnect
like an ac feeder with large amounts of available at the battery end of the circuit to protect these
short-circuit current. Batteries must have over- conductors from high short-circuit currents orig-
current protection and disconnects on the output inating at the battery. Depending on the location
conductors. Batteries operating over 100 volts of the charge controller with respect to other
(conductor to conductor or conductor to ground) components, there may be disconnects required
shall also have a maintenance disconnecting on the input and output of the charge controller.
means for both ungrounded and grounded con- A main PV system disconnect located between
ductors that is accessible only to qualified persons. the PV array and the charge controller will be
Where battery circuits are subject to field servic- required, complying with 690.13.
ing and operating at over 240 volts (conductor to Available short-circuit currents. The battery
conductor or conductor to ground), they shall have banks used in these types of systems will typical-
provisions to disconnect the battery series-con- ly have an available short-circuit current at the
nected strings into segments that are less than 240 output conductors from the battery bank less than
volts (706.21, 706.30). The current between the 15,000 amps. Conductor lengths, connections, and
battery and the multimode inverter is bidirection- conductor resistances limit the available short-cir-
al. It flows to the batteries when the batteries are cuit current. Any overcurrent devices or discon-
being charged by the multimode inverter or the nects must have ratings that can handle currents
charge controller, and it flows from the batteries of this magnitude. Current-limiting fuses and dc
when the multimode inverter is in the inverting rated circuit breakers are generally available with
mode supplying the protected loads with ac power. sufficient ratings and should be used.
In the dc-coupled charging system, the con- Conductors. The conductors between the bat-
ductors between the charge controller and the tery bank and the multimode inverter must carry
bidirectional currents. The multimode
inverter will use utility power or power
from the utility-interactive inverter in
ac coupled systems to keep the battery
charged and currents will flow from
the inverter to the battery. When the
multimode inverter is operating in the
inverting mode and supplying protect-
ed loads with energy, the currents will
flow from the battery to the multimode
inverter.
In general, the discharging currents
flowing from the battery to the inverter
Photo 5.7 • Class B stranded conductor, top; fine stranded will be larger than the charging currents
conductors, bottom. flowing from the inverter to the battery.
106 Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems
in a power center. However, if the distance between rent protection and disconnects must be used in
the battery and the multimode inverter is more both ungrounded conductors; therefore, increasing
than four to five feet, or if the inverter is in a dif- the cost of an ungrounded battery system.
ferent room than the battery bank, then there must
be a disconnect at the battery end of the circuit in AC Circuit Considerations
addition to the overcurrent protection required at Multi-wire branch circuits. Many houses today
that location. Photo 5.8 shows a battery discon- have several multi-wire branch circuits that have
nect/overcurrent protection enclosure using circuit two branch circuits with a shared neutral conduc-
breakers mounted just above a valve-regulated tor and are wired with a 14–3 AWG/with ground
(sealed) lead-acid (VRLA) battery bank. These type NM cable. Multimode inverters come with
batteries release no hydrogen gas or acid fumes either 120-volt ac outputs or 120/240-volt ac
during normal operation. outputs. Neither of these multimode inverters
Grounding. The nominal battery voltage in should be connected to load circuits in a building
these systems is 48 volts dc. The operating voltage that are part of a multi-wire branch circuit. [See
may be as high as 62 volts to 65 volts. Normally, NEC 690.10(C).] The inverters in the inverting
multimode inverters do not ground one of the mode (standalone mode), in some cases, may
battery circuit conductors and the grounding not be in synchronization with the utility power
system used by the multi-mode or standalone frequency waveform. This could cause over-
inverter will have to be coordinated with the loading of the shared neutral that is associated
grounding system used by the connected PV sys- with multi-wire branch circuits. If any of the
tem (690.41). Equipment grounding is required circuits needing battery backup power protection
throughout the combined system and the require- are multi-wire branch circuits, they should be
ments for this grounding have remained relatively segregated in their entirety (both circuits) in the
unchanged in recent editions of the NEC. special protected loads load center that is con-
If the system uses dc-coupled battery charging, nected to the multimode inverter ac output.
the connection to earth for the PV system will Utility connections. One of the characteristics
usually be done through a distinct and sepa- of most multimode inverters is that they can pass
rate ground-fault detecton interruption system power from the utility through to the protected
(GFDI) as required by NEC Section 690.41. load circuits at a greater power level then they can
In some cases, the charge controller may have a supply power to the utility in the utility-
GFDI built in. interactive mode. This indicates that the circuit
On an ac-coupled system, the utility-interactive and overcurrent device (typically a breaker)
inverters will have their normal GFDI internal between the utility connection and the multimode
circuitry and will also be required to meet the inverter must be rated at the full pass-through
requirements for PV system grounding in 690.41. current capability of the inverter. A common value
However, in ac-coupled systems, the dc battery of this circuit breaker would be 60 amps or 70
circuit may still have to be solidly grounded to amps. However, in the utility-interactive mode, the
keep costs down and to be compatible with avail- inverter may only be able to source 33 amps from
able equipment that has been designed for use in the PV system into the utility. In previous editions
grounded systems. Where an ungrounded battery of the Code, the 60-amp or 70-amp breaker would
system is used, there is no provision for having an be used in the 705.12(D) calculations to determine
overcurrent device in just one of the ungrounded panelboard/load center busbar ratings and conduc-
conductors as there is for PV dc circuits. Overcur- tor sizes. The danger to the circuit from overload-
108 Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems
ing, however, is related to the 33-amp output of manner as any normal utility-interactive system.
the inverter when feeding the utility. The dc PV circuits are connected in the same
Section 705.12(B)(2) now requires the calcu- manner as those circuits in a standard utility-
lations for this requirement to be based on 125 interactive PV system for the ac coupled system.
percent of the rated utility-interactive inverter The dc-coupled systems require additional con-
output in the utility-interactive mode. In this siderations for the low-voltage battery charging
example, 41.25 amps (1.25 x 33) could be used in circuits.
the calculations. The circuit breaker connecting the
inverter to the load center can still be rated at the A Closer Look at Batteries
higher 60 amps or 70 amps required to allow the Energy storage systems (in the form of batteries),
protected loads to be operated in the pass-through when included in photovoltaic power systems,
mode of operation. Of course, the circuit conduc- are critical and important items that need close
tors must be sized to carry the higher currents in scrutiny during the plan review and inspection
the pass-through mode, including any ac currents process.
from the utility used to charge the battery.
Aside from the battery circuits and the unique Types of Batteries
characteristics of the utility interconnection There are two main types of battery systems that
covered above, the multimode inverter in the have been used (and are still being used) in PV
battery-backed-up, utility-interactive PV system systems at this time. Both are based on a lead-
is connected to the utility in much the same acid battery technology (older than the NEC).
Chapter 5 Energy Storage Systems (ESS), Batteries in PV Systems 109
06
Grounding, Disconnects, and
Overcurrent Protection
“Grounded, Solidly. Connected to ground It should be noted that there are no voltage
without inserting any resistor or impedance requirements associated with the requirements in
device. 690.41 and that old 50-volt limit is gone. It will
“Grounded Conductor. A system or circuit take some time to figure out what we call these
conductor that is intentionally grounded.” various types of PV arrays. For example, a PV
array connected to a non-isolated inverter with a
From Article 690 240 VAC output will meet the requirements of (3)
“Functional Grounded PV System. A PV because at some point there is a utility transformer
system that has an electrical reference to ground that has a grounded 240/120-volt center tap.
that is not solidly grounded.
Informational Note: A functional grounded Equipment Grounding
PV system is often connected to ground Sections 690.43, 690.45, and 690.46 dealing with
through a fuse, circuit breaker, resistance equipment-grounding conductors have remained
device, non-isolated grounded ac circuit or essentially unchanged.
electronic means that is part of a ground-
fault protection system. Conductors in these Grounding Electrode Systems
systems that are normally at ground potential Section 690.47 on grounding electrode systems
may have voltage to ground during fault has been substantially revised and clarified. The
conditions.” most significant change is for functional ground-
ed pv systems (not solidly grounded). In these
As an aside, my high school English teacher systems, the normal ac equipment-grounding
would have objected to the term functional ground- conductors from the inverter to associated distri-
ed and preferred functionally grounded, but then bution system are allowed to serve as the ground-
she has not seen the rest of the NEC. Functional ing connection for any ground-fault protection
ground would probably have been acceptable— equipment and for the equipment grounding
another potential update for the 2020 NEC. of the PV array. This is a change from previous
690.47(C)(3) in the 2014 NEC that required
“690.41. PV System Grounding Configurations this conductor to meet the requirements of what
One of the following system grounding was called a “grounding conductor” (bonding,
configurations shall be employed: size, and continuity), but was actually a bonding
(1) 2-wire PV arrays with one functional jumper, as well as the requirements for an equip-
grounded conductor. ment-grounding conductor.
(2) Bipolar PV arrays according to 690.7(C)
with a functional ground reference (center tap). Grounding the Array—690.47(D) Grounding
(3) PV arrays not isolated from the ground- Electrode System
ed inverter output circuit. Section 690.47(D) has been revised in every
(4) Ungrounded PV arrays. edition of the Code since it was originally written.
(5) Solidly grounded PV arrays as permitted Here is what is says, in part, in the 2017 NEC:
in 690.41(B) Exception. “(A) Buildings or Structures Supporting a
(6) PV systems that use other methods that PV Array. A building or structure supporting
accomplish equivalent system protection in a PV array shall have a grounding electrode
accordance with 250.4(A) with equipment system installed in accordance with Part III
listed and identified for the use.” of Article 250.”
116 Chapter 6 Grounding, Disconnects, and Overcurrent Protection
Photo 6.4 • Disconnect labels based on 2014 NEC. 2017 NEC requirements are slightly different.
system disconnect open all conductors [690.13(F)]; ductors and it is noted that, in many cases where a
be rated for the available short-circuit current grounded conductor is involved (usually a neutral)
and voltage in the circuit [690.13(E)]; be rated as in that circuit, at least a three-pole disconnecting
service equipment for ac supply-side PV connec- means would be required. It will be difficult to
tions [705.12(A), 690.13(C)]; and may be a single achieve the ac PV system disconnect using the
disconnect for multiple inverter systems and have backfed circuit breaker in a load center due to that
up to six switches for more complex PV systems neutral switching requirement. On the other hand,
[690.13(D)]. As mentioned previously, the color Section 705.21 requires that only the ungrounded
coding of a solidly grounded conductor that has a conductors be disconnected at this point.
disconnect will need to be clarified in the Code. Proposals have been made to correct the
requirement in 690.13 in the 2020 NEC, but in
To Open the Grounded Conductor or Not? the meantime, it is suggested that the require-
Because the PV system disconnect may be the ments of 705.21 be followed rather than those
connection of the output of a utility-interactive of 690.13(F). A Tentative Interim Amendment
inverter to the utility power source, the require- (TIA) for the 2017 NEC may rectify this issue
ments of disconnects and Article 690 should be before the 2020 NEC is published and adopted.
consistent with those requirements in Article 705.
The requirements in 690.13(F) require that the Isolation Devices—a Subset of
PV system disconnect simultaneously open all Disconnecting Means
conductors of the PV circuit connected to other Section 690.15, Disconnection of Photovoltaic
sources. There is no exception for grounded con- Equipment, requires that isolating devices for
Chapter 6 Grounding, Disconnects, and Overcurrent Protection 119
ac disconnect. However, AHJs who inspect such fied for clarity and are addressing new equipment
systems sometimes consider requiring an external in each new edition of the NEC. To paraphrase
ac disconnect on the dwelling or at least a direc- the Bard again: We know what disconnects are,
tory on the outside of the building indicating the but know not what or where they may be.
location of the ac disconnect inside the building.
When the inverter is located in a separate struc- PV Circuit Overcurrent
ture or is exterior to the dwelling, then the nor- Protection
mal Code rules for installing an ac disconnect for Section 690.9 establishes the requirements for
the conductors entering the building or structure overcurrent protection associated with the now
would apply [230.70(A)]. In some jurisdictions, redefined PV system circuits, both dc and ac.
the fire service may have established requirements Overcurrent protection requirements for batteries
for disconnects on standalone PV systems. (energy storage systems), stand-alone PV systems,
and dc and ac microgrids are covered in other arti-
The currently evolving changes in the Code cles in the Code and in other chapters in this book.
and in UL standards. NEC 690.12, Rapid Shut- Sometimes overcurrent protection is not need-
down System for PV Systems, will have some ed. In any situation where circuit conductors have
effect on how the PV system can be controlled sufficient ampacity for the sum of all available
from a single point in an emergency situation currents in that circuit under normal or fault
(photo 6.9). conditions, overcurrent protection is not required
Many utility-interactive inverters have an [690.9(A)].
internal dc disconnect or one in an enclosure
that is attached to the inverter. That disconnect Special Consideration and Location. Al-
will serve, in most cases, as the dc isolator for the though circuits are normally protected from
inverter (690.15) (photo 6.10). overcurrents at their source, PV source and
Disconnect requirements with respect to lo- output circuits and interactive inverters differ
cation vary significantly with each particular PV from that general rule. Because several pieces of
installation. Those requirements are being modi- PV equipment, such as PV modules, dc-to-dc
124 Chapter 6 Grounding, Disconnects, and Overcurrent Protection
devices can reduce a high current to a lower cur- The NEC assumes that each ungrounded con-
rent and then a smaller conductor associated with ductor is connected to some source of overcur-
the lower current can be used when protected with rents that might potentially damage that conduc-
this type of OCPD. As far as can be determined, tor under fault conditions. This source could be
there are no devices that can provide power circuit a power supply, a utility service, or a battery that
(branch circuit) overcurrent limitation/protection supplies currents in excess of the ampacity rating
in this manner outside of some very sophisticated of the conductor. The NEC, in 240.21, requires
electronic devices. Hopefully, the 2020 NEC will that the conductors be protected at their source
clarify this issue. The 2020 NEC may also define of supply. Photovoltaic modules are current-lim-
how actual current-limited inputs on some devices ited devices, and their worst-case, continuous
and energy management systems will deal with outputs for Code calculations are 1.25 times the
limiting the current from multiple sources con- rated short-circuit current. Therefore, the module
nected to a single device or circuit. Look to Article cannot generate sufficient current to damage the
705 and 750 for changes in this area. conductor attached to it in a short-circuit con-
Optional Overcurrent Protection. Under the dition. An exception to Section 690.9(A) allows
2017 NEC, other than very small solidly ground- conductors and PV modules to be used without
ed PV arrays (690.41), most of the dc circuits OCPDs where there are no sources of external
in PV source and PV output circuits will not be currents that might damage that conductor or PV
connected directly to earth (solidly grounded). In module.
previous editions of the NEC, these ungrounded Additionally, UL Standard 1703 requires that
PV arrays would require an overcurrent device modules must have an external series OCPD
in both (positive and negative) of the unground- if external sources of current can damage the
ed circuit conductors [2014 NEC, 690.9(E)]. internal module conductors. The module can be
Section 690.9(C) in the 2017 NEC, now permits damaged if reverse currents are forced through
the use of an overcurrent device (where overcur- the module (due to an external or internal fault)
rent protection is required) in only one of these that are in excess of the values of the maximum
conductors, not both. If that option is selected, series fuse marked on the label on the back of the
all dc overcurrent devices in other PV source module. Again, if there are no sources of external
and output circuits must be in the same polarity currents that exceed this marked value, then no
conductor in those circuits. OCPD is needed to protect the internal module
wiring.
Fusing of DC PV Module External sources of current (apart from the
Circuits in Utility-Interactive module or series-connected strings of modules)
PV Systems vary from system to system. These currents can
In most electrical systems, the NEC requires originate from modules or series-connected
every ungrounded circuit conductor to be pro- strings of modules that are connected in parallel
tected from overcurrents that might damage to the module of interest, from batteries in the
that conductor. Overcurrent protective devices system, or from utility currents backfeeding
(OCPDs), either fuses or circuit breakers, provide through utility-interactive inverters.
that function. However, some of the smaller utili- In systems with batteries and charge control-
ty-interactive PV systems may not need OCPDs lers, the batteries are a predominate source of
in the dc circuits that are connected to the PV currents and OCPDs will be required on each
modules. module or series-connected string of modules.
126 Chapter 6 Grounding, Disconnects, and Overcurrent Protection
Forward current
Module Isc =8A 1.25 Isc =10A maximum
Module ...
Isc = 8A
Fuse
Fuses rated at
1.56 Isc=12.5
(use 15A)
... Fuse
Fuse
4 x 1.56
Isc=49.9
(use 50A)
... Fuse Fuse +
To inverter
... Fuse
Line to line –
fault
Figure 6.1 • Part of a large system. Possible reverse currents from in-
verter and parallel strings into fault in one string. Note: all fuses are in
the positive conductor.
utility into an array dc wiring fault. PV modules or strings of modules can be con-
String fuses are required, and an inverter fuse is nected in parallel and still meet the NEC and
required if the inverter can backfeed into fault in UL requirements (marked on the back of each
dc system. The 2017 NEC permits the use of only module) before an OCPD is needed on each
one fuse in each circuit, but any dc fuses in other module/string of modules? UL marks the mod-
circuits must be in the same polarity conductor. ules based on reverse-current tests. The NEC
requires that the manufacturer’s instructions and
The General Case—For Most Larger labels be followed [110.3(B)]. The intent of the
PV Systems module marking is to protect the conductors
The most common situation occurs in systems internal to the module at the marked level from
where there are multiple strings of modules reverse currents. This is a maximum value for the
connected in parallel. The non-faulted strings OCPD. Lesser values can be used if they meet
may be able to supply sufficient overcurrents the NEC requirement of 1.56 x ISC to protect
(through the parallel connection) to damage the conductor associated with the module or
either the conductors or the modules in the string of modules. In some cases, the value of
faulted strings. A basic question is: How many the module protective overcurrent device is
128 Chapter 6 Grounding, Disconnects, and Overcurrent Protection
Module Isc = 8A
Maximum Module Series Fuse 15A
Load/inverter cannot source fault currents
... +
LOAD/
INVERTER
Conductor ampacity = 1.56 Isc = 1.56 x 8 = 12.5 A minimum
Conditions of use may require higher rating. NEC 690.8
Figure 6.2 • Single string of PV modules. Where there are no external source of overcurrents that can damage the mod-
ules or the conductors, no overcurrent protection is required. NEC 690.9(A) Exception.
less than 1.56 x ISC. This poses a Code conflict this case, we are assuming that the inverter or the
[110.3(B) vs. 690.8/9] and is an issue for UL or batteries are a potential source of overcurrents.
the listing agency to rectify. The OCPD will have a minimum rating of 1.56
Many installers of 12-, 24-, and 48-volt PV x n x ISC amps. It is sized at this value to allow
systems ignore the module OCPD requirement maximum forward currents from the array to pass
and connect modules/strings in parallel. Can it through without interruption and to keep the
be done and how? David King, when he worked overcurrent device from operating at more than
at Sandia National Laboratories, and the author 80 percent of rating.
have smoked (destroyed) a few modules and Examine a circuit where there are n modules/
determined that the module OCPD requirement strings connected in parallel. Place a ground-fault
is valid, even at low voltages. in one module/string. Examine the sources of
It is easy to see that in a one-string system, an fault current that would affect that module string.
OCPD is needed only when the inverter or bat- Let us ignore current from the faulted module/
tery is a source of overcurrents. No fusing would string itself since the wiring in that string is
be required in a one-string system if there were already sized to carry all forward currents gener-
no battery or inverter that could source overcur- ated in the string.
rents (see Figure 6.2). First, there is the potential back feed cur-
Consider n modules or strings of modules rent from the battery or the inverter in those
connected in parallel. The NEC requires that an systems with these components. It is limited
OCPD be installed in the combined paralleled to the NEC-required OCPD of 1.56 x n x ISC
output of all strings (modules) to protect the between its input and the combined array output.
cable from reverse currents from batteries and This current is added to the current from the
backfeed of ac currents through an inverter. In remaining modules connected in parallel. In this
Chapter 6 Grounding, Disconnects, and Overcurrent Protection 129
case, the current is (n-1) x 1.25 x ISC. The 1.25 However, if we try to parallel three of these
is required [representing the maximum current modules/strings, the fault current equation yields
defined in (690.8)] because of daily-expect- a fault current of 29+ amps that exceeds the 20-
ed irradiance values that are greater than the amp limit on the module. The single OCPD is 3
STC-rated ISC. x 1.56 x 3.8 = 17.8 amps (because OCPDs at this
rating are not common, a 20-amp OCPD must
I-fault = 1.56 x n x ISC + (n-1) x 1.25 x ISC be used). The two parallel-connected modules
contribute 2 x 1.25 x 3.8 = 9.5 amps for a total
With a little algebra, the resulting fault current is: potential fault current of 29.5 amps. This is
significantly above the maximum series protective
I-fault = (2.81 x n-1.25) x ISC amps. (Fault fuse of 20 amps.
Current Equation.) In most cases, it is not possible to parallel more
than two modules/strings with a single OCPD
Note that this equation does not account for unless the marked maximum series OCPD is very
rating roundup of the OCPD, so each system large in relation to ISC for the module. Some of the
must be checked with the actual OCPD values. thin-film technologies may be able to do this and
If the module can pass the UL reverse current that will be an installation benefit for them.
test at this I-fault value or greater and be so Questions about driving voltages to produce
marked (the maximum protective series fuse on these currents? The faults can occur anywhere in
the label), then it is possible to parallel n mod- the module/string, so a fault involving a single
ules/strings (pick your n) without a series OCPD cell could be the trouble spot, and driving voltages
for each module/string. over one volt could produce the reverse currents.
For example, a PV module is rated at 60 watts What about currents generated within the
and has a maximum series OCPD requirement faulted module string? In the portion of the
of 20 amps, which is marked on the back of the module/string below the fault (toward the
module. The ISC for this module is 3.8 amps. Here grounded end of the module/string), the currents
are the required calculations and checks for two flow in the forward direction toward the fault
strings in parallel. and may or may not cause problems. As far as the
The paralleled circuit OCPD installed at the contribution to the fault current is concerned, the
output of the two paralleled strings will be 2 x 1.56 contribution only appears in the fault path/arc
x 3.8 = 11.8 amps. Assume a 12-amp OCPD is and does not affect the ampacity of the conduc-
used because the NEC now requires module/string tor. Above the fault (toward the ungrounded
OCPDs in one-amp increments up to 15 amps. end), the currents in that portion of the module/
Fuses are available in these values except there is a string appear to oppose the external fault currents
jump from 10 to 12 and then to 15. This OCPD that are trying to reverse the flow of current, but
could potentially allow 12 amps of fault current to the string is reversed biased, and the external
reach the faulted module/string from backfeed from driving currents are flowing. Because the location
a charge controller/battery or from the utility grid of the fault cannot be controlled ahead of time,
through a utility-interactive inverter. worst-case currents must be assumed.
Another 1.25 x 3.8 = 4.75 amps could come from The increased marking value of 20 amps on the
the parallel-connected module/string for a total of example module allows for two modules/strings
16.75 amps. This is acceptable because this module to be connected in parallel and it does make it
is marked for 20 amps. easier for the installer to use a single OCPD with
130 Chapter 6 Grounding, Disconnects, and Overcurrent Protection
... +
...
Module Isc = 8A
Maximum Module Series Fuse 15A Line to line
Load/Inverter cannot source fault currents fault
Conductors rated at 1.56 Isc = 13A
Figure 6.3 • Two strings in parallel. No source of overcurrents that can damage modules or conductors in faulted string.
No backfeed from inverter. No overcurrent devices required. NEC 690.9(A) EX.
a larger conductor to meet both the NEC-re- currents from being backfed through the inverter
quired conductor protection and the UL-required from the utility to faults in the PV array. This
module protection with one large OCPD instead removes one source of currents in the above
of a two smaller OCPDs plus a larger OCPD. equation. With these products, it is possible to
Conductor ampacity must also be addressed have two (and sometimes more) strings of mod-
if modules are going to be paralleled on a single ules in parallel with no OCPDs in the dc circuits.
OCPD. The conductors for each string must be The inverter manufacturers should be contacted
able, under fault conditions, to carry the current for information in this area. The above equations
from the other parallel strings (modules) plus the can be modified by deleting the combined-cir-
current that may be backfed from the inverter cuit OCPD and then solved to determine both
or battery. In the case with n strings in parallel the requirements for OCPDs and the necessary
and a single OCPD in the combined output, the ampacity of the conductors.
conductor ampacities would be as follows: In this case, the reverse current flowing through
Each of the string conductors would have to the forward fuse (n x 1.56 x ISC) is set equal to
have an ampacity of 1.25 (n-1) x ISC + 1.56 x n zero or removed from the equation. In a system
x ISC. If the equation is factored, the required with n strings of modules connected in parallel,
ampacity becomes A = (2.81 x n-1.25) x ISC. As if one of the n strings develops a fault, the fault
before, OCPD roundup is not considered and the current is now reduced to:
values should be recalculated with actual OCPD
values. The combined output-circuit conductors I fault= (n-1) x 1.25 x ISC. For two strings in
would require an ampacity of 1.56 x n x ISC. parallel, n = 2 and the fault current becomes:
Photo 6.14 • Retaining kit for a backfed circuit breaker. Required where a circuit breaker is backfed from a standalone in-
verter output.
sized at 1.56 x ISC. The required module series protec- Overcurrent Protection in Related Articles.
tive fuse is nearly always greater than 1.56 x ISC. Article 705 establishes additional requirements for
Therefore, in a system with two strings of mod- overcurrent protection in the ac inverter output
ules connected in parallel, there are no sources circuits. Article 710 does the same for ac circuits in
of fault current that exceed the ampacity of the stand-alone systems. In general, conductors shall
conductors or the requirements for a module be protected from all possible sources of overcur-
protective fuse. No dc string or array fuses would rent (705.30, 705.65, and Article 240).
be needed. NEC Section 690.9(A) Exception If circuit breakers are backfed, they shall be
applies. (See Figure 6.3.) suitable for such operation [705.12(B)(4)]. This
If there are more than two strings of mod- usually indicates that they will not be marked
ules connected in parallel, then the calcula- “Line” and “Load.” Also, if a backfed breaker is
tions outlined above will have to be made to fed by a listed interactive source (PV utility-in-
ensure that (n-1) x 1.25 x ISC is less than the teractive inverter), the breaker does not have
module series protective fuse value. If not, to be mechanically fastened to the panelboard
fuses should be used in each string. Again, [705.12(B)(5)]. However, where a backfed break-
the actual value of available fuses should be er is connected to the output of a standalone
used in the calculations. inverter (a voltage source and not interactive),
132 Chapter 6 Grounding, Disconnects, and Overcurrent Protection
07
Utility Interconnections
Connecting the utility-interactive inverter to should be used. In a few cases, the inverter manu-
the utility grid properly is critical to the safe, facturer may specify a higher rated current based
long-term, and reliable operation of the entire on a lower than nominal operating voltage (the
system. The ac output circuit requirements and low end of the anti-islanding range) and this val-
the circuits that carry the inverter current in the ue of rated current should be used. Voltage drop
premises wiring are somewhat complex. However, and conditions of use considerations may require
meeting Code requirements can and should be a larger conductor. Higher rated overcurrent
accomplished to ensure a safe and durable system. devices should not normally be used; even though
Inspectors need to know this material and how they may be appropriate for the conductor being
to apply it because many PV installers are not used, they may not provide required protection
familiar with the details of the requirements. The for internal inverter circuits. The inverter manual
first step is to get the power out of the inverter. will generally specify the maximum allowable ac
output overcurrent device rating and this value
Inverter Output Circuit should be followed [110.3(B)].
In general, the output circuit on an inverter to Even though power and current flow from the
the first overcurrent device should be sized at inverter to the utility, it should be noted that the
125 percent of the rated output current (the utility-end of this circuit is where the currents
maximum current) of the inverter that, in turn, is originate that can harm the conductors when
determined from the specifications or by dividing faults occur. Utility-interactive inverters cannot
the rated power by the nominal ac output voltage generate surge currents and usually shut down
[690.8(A)(3)]. For example, a 2500-watt, 240- under conductor fault conditions. Any overcurrent
volt inverter will have a rated output current of: protection should be located at the utility end
2500 / 240 = 10.4 amps of the inverter ac output circuit and not at the
1.25 x 10.4 = 13.02 inverter end of this circuit [690.9(A)].
A 15-amp circuit breaker is the next larger In load-side connected systems, it is good
standard size and at least 14 AWG conductors practice to install the inverter near the backfed
Chapter 7 Utility Interconnections 135
load center so that the backfed breaker commonly ty- interactive PV inverter to the supply side
used to interconnect the inverter with the utility of a service disconnect is similar to connecting
can also be used as the ac inverter equipment a second service-entrance disconnect to the
disconnect/isolator required by 690.15. This places existing service. Because these PV conductors
the overcurrent device at the utility-supply end of are unprotected like service-entrance conductors,
the circuit and groups the ac disconnect for the many of the rules for service-entrance equipment
inverter with any internal or nearby dc disconnect/ should be considered. Sections 230.2(A)(5) and
isolator. A disconnect/isolator must be located 230.82(6) permit these parallel power production
within 3 m (10 ft) of the inverter if the inverter is systems as additional services. However, they
located more than that distance from the backfed do not meet the definition of a service found in
circuit breaker [690.15(A)]. Article 100 of the NEC.
In general, the “Tap Rules” of Section 240 do
Load-Side and Supply-Side not apply unless specifically mentioned because
Utility Connections they were not developed to address two sources
There are two types of connections allowed by of power in a tap circuit, nor were they developed
the Code for interfacing the output of the utility- to ensure safe operation when one source is an
interactive inverter to the utility power. They are unprotected utility power source.
made on either the supply side [705.12(A)] or Although the PV output is not considered a
the load side [705.12(B)] of the main service dis- service, the unprotected conductors are exposed
connect of a facility or structure. The load side of to the same potential fault currents as the ser-
the main service disconnect is the most common vice-entrance conductors. It is suggested that
connection used for the residential system and this PV connection be as robust as any service
the smaller commercial system under about 10 entrance. Section 230.91 requires that the service
kW. Section 705.12(B) covers the requirements overcurrent device be integral with the service
and it is heavy reading at best. disconnect or located adjacent to it. A circuit
breaker or a fused disconnect would meet these
Supply-Side Utility requirements (photo 7.1). A utility-accessible,
Connections visible break, lockable (open) fused disconnect
Many larger PV systems cannot meet the require- (aka safety switch) used as the new PV service
ments/restrictions for a load-side (of the service dis- disconnect may also meet utility requirements
connect) connection to the premises wiring system for an external PV ac disconnect in areas where
and a supply-side connection must be considered. utilities require such an additional disconnect
(photo 7.2). Section 690.13(C) requires that the
Code Considerations PV system disconnect connected to the supply
The supply-side connection (also known as a ser- side of the service disconnect be listed as suitable
vice-entrance connection) is allowed by the NEC for use as service equipment.
and is addressed in several sections in the Code. Section 230.71 specifies that the service
Section 705.12(A) allows a supply- (utility) disconnecting means for each set of service-en-
side connection as permitted in 230.82(6). Sec- trance conductors shall be a combination of no
tion 230.82(6) indicates that solar photovoltaic more than six switches and sets of circuit breakers
equipment is permitted to be connected to the mounted in a single enclosure or in a group of
supply side of the service disconnect. enclosures. Section 690.13(D) allows up to six
It is evident that the connection of a utili- switches or circuit breakers for each PV system.
136 Chapter 7 Utility Interconnections
Photo 7.1 • Added lugs provide a supply-side connection. Photo 7.2 • Utility-required ac disconnects. They could have
But is it Code legal? The added lugs probably violated the been combined with a combiner into one disconnect.
listing on the meter/main combo.
Common industry practice indicates that an ac cent of the rated output current from the PV in-
disconnect associated with a PV system is not verter(s). But in small systems, a question arises:
counted against the six allowable disconnects How small can it be? Section 230.79 addresses
for the existing utility service. This is a gray area the rating issue for service disconnects. It must
subject to AHJ interpretation. be pointed out that these conductors are not
service conductors, but for all practical purposes,
Location and Directory they are treated as service conductors. Although
Section 230.70(A) establishes the location re- not a Code requirement, many AHJs and PV
quirements for the service disconnect. Sections installers choose to treat these conductors as
705.10 / 690.4 / 690.54 require that a directory service conductors. Some inspectors have looked
be placed at each inverter and service equip- at 230.79(A) and say that it can be as low as 15
ment location showing the location of all power amps if that value is at or above the rating of
sources for a building and the locations of all PV the inverter output circuit. The connection of
system disconnects (photo 7.3). Locating the other specific loads is allowed at this level and is
PV ac disconnect adjacent to or near the existing common.
service disconnect may facilitate the installation, I would suggest caution here, because the
inspection, and operation of the system (photo connection is to service-entrance conductors
7.4). Many utilities require the service disconnect rated at 100 amps and above. The typical 15-amp
and the PV ac disconnect to be co-located. circuit breaker with 10,000 amps of interrupt
capability, in this application, may not be able to
Size Matters withstand the available fault current because it
Obviously, the size of the new PV system is not protected and coordinated with any main
disconnect on the ac inverter output circuit is breaker. Of course, Section 110.9 should be fol-
important. It will normally be sized at 125 per- lowed and available fault current calculated. Also,
Chapter 7 Utility Interconnections 137
Photo 7.3 • Directory and labels required by NEC and Photo 7.4 • PV ac disconnect above closed and locked-out/
utility. tagged-out service disconnect
Photo 7.6 • General Electric, 125-amp main-lug-only service-entrance-rated load center. With appropriate breakers, the
panel has a 22,000-amp rating. Two stabs can be used to convert the panel to a backfed main breaker panel—but then
supply-side connections cannot be made with remaining breaker positions.
centers frequently have significant amounts of socket, and the old socket covered.
interior space where the connection appears to In larger commercial installations, the main
be possible between the meter socket and the service-entrance equipment will frequently have
service disconnect. However, tapping this inter- busbars that have provisions for tap conductors.
nal conductor or busbar in a listed device, such Any holes intended for connections must be
as a meter-main combination (aka meter-main marked “Tap Locations” or similar. The PV con-
combo), would violate the listing on the device nection to this tap point can only be made with
and should not be done (photo 7.5). the approval and instructions from the manu-
Where the service-entrance conductors are facturer of the equipment or by the organization
accessible, a new meter base (socket) could supplying the service equipment (usually a UL
be added ahead of the combination device. A 508 Industrial Controls Shop). These organizations
connection box would then be added between the can tap the equipment and maintain the listing on
new socket and the combination device. The me- the equipment.
ter would then be moved from the combo device In all cases, safe working practices dictate that
to the new socket, jumper bars added to the old the utility service be de-energized before any
140 Chapter 7 Utility Interconnections
Figure 7.1 • 705.12(B)(2)(1)(a) Increased feeder (on load side of PV connection) ampacity required.
of that connection to protect the remainder of in the new requirements, we can assume (some-
the existing feeder from overcurrents and faults times not a good thing to do) that there is no
(240.21). Placing the added overcurrent device ampacity correction required on the feeder under
at the load end of the existing feeder does not that situation. The size of the existing feeder was
provide that protection. See figure 7.2. determined by the existing overcurrent device
This section represents a significant change from protecting that circuit from utility currents.
past code requirements. It presents requirements Additionally, while locating the power source
for feeder size and overcurrent protection when output connection at the opposite end of the
the utility interactive inverter connection is not feeder from the utility source will prevent the
at the opposite end of the feeder from the utility feeder from being overloaded by additive cur-
connection. It should be noted that the ampacity rents, it is obvious that 125% of the rated power
of the feeder between the main OCPD from the source output current must not exceed either the
utility and the inverter point of connection and rating of the utility-end overcurrent device or the
the conductor from the point of connection to ampacity of the existing feeder.
the inverter output OCPD are not addressed. The The general requirement should be (proposed
following will discuss that omission. for the 2020 NEC): The ampacity of a circuit that
has sources protected by overcurrent devices at
PV Opposite Utility on the Feeder (Not each end shall be no less than the rating of the
addressed by Code—Update Coming in the largest overcurrent device. This requirement can
2020 NEC) be used to size feeders or size the rating of the
Since the situation where the PV connection is inverter ac output OCPD.
at the opposite end of the feeder is not addressed In all cases, the largest OCPD in this situation
Chapter 7 Utility Interconnections 145
Figure 7.2 • 705.12(B)(2)(1)(b) Additional breaker (on the load side of the PV connection at that connection) required to
protect existing feeder from excess currents from PV plus utility.
should be the main OCPD protecting the feeder. power source output current, in general any tap
Also, where the feeder is not “tapped” at the end conductors may have to be increased on exist-
point, the conductor from the inverter connection ing taps and calculated to be a larger size than
point to the inverter output OCPD should also meet normal on new taps.
this rule and be sized the same as the existing feeder.
Busbars
Inverter Output Circuit (the tap conductor) Size “(3) Busbars. One of the methods that follows
“(2) Taps. In systems where power sources shall be used to determine the ratings of busbars
output connections are made at feeders, any in panelboards.
taps shall be sized based on the sum of 125
percent of the power source(s) output circuit Busbar Rule (a)
current and the rating of the overcurrent (a) The sum of 125 percent of the power
device protecting the feeder conductors as source(s) output circuit current and the rating
calculated in 240.21(B).” of the overcurrent device protecting the
busbar shall not exceed the ampacity of the
This section applies to both existing load taps busbar.
on a feeder and any taps added after a power Informational Note: This general rule assumes
source connection has been made to that feeder. no limitation in the number of the loads or
All taps, both old and new, will be subjected to sources applied to busbars or their locations.”
this requirement and because the currents used in
the various tap rule calculations will be increased This worst-case requirement presented in
due to adding the main OCPD to 125% of the 705.12(B)(2)(3)(a) assumes that the utility cur-
146 Chapter 7 Utility Interconnections
rent through the existing main breaker and the contains loads, the sum of 125 percent of the
current from the output of the utility-interactive power sources(s) output circuit current and
inverter may add and that current may create an the rating of the overcurrent device protecting
overload on the busbar. There are no restrictions the busbar shall not exceed 120 percent of the
on the location of the main utility breaker or the ampacity of the busbar. The busbar shall be
PV backfed breaker. If the busbar has a rating sized for the loads connected in accordance
equal to the sum of these two values, then no with Article 220. A permanent warning label
overload would be possible. shall be applied to the distribution equipment
It should be noted that reductions in the size adjacent to the back-fed breaker from the
of the utility breaker are not prohibited in this power source that displays the following or
section and could be accomplished if allowed by equivalent wording:
other sections of the Code, load calculations and
equipment limitations. WARNING:
POWER SOURCE OUTPUT CONNECTION–
Busbar Rule (b) DO NOT RELOCATE THIS OVERCURRENT DEVICE.
“(b) Where two sources, one a primary power
source and the other another power source, The warning sign(s) or label (s) shall comply
are located at opposite ends of a busbar that with 110.21(B).”
the busbar. Permanent warning labels shall the busbar could not be drawn through the
be applied to distribution equipment that load breakers. And again, under this condition,
displays the following or equivalent wording: no PV backfed breaker could be added. How-
ever, as the sum of the load breakers is reduced,
WARNING: there becomes an allowance for adding a back-
THIS EQUIPMENT FED BY MULTIPLE SOURCES. fed PV breaker with increasing ratings. In the
TOTAL RATING OF ALL OVERCURRENT DEVICES, extreme case, there could be a situation where
EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE, there are no load breakers and only a single or
SHALL NOT EXCEED AMPACITY OF BUSBAR. multiple backfed PV breakers rated, in total the
same as the busbar. In any of these cases, no
The warning sign(s) or label(s) shall comply with matter where the PV breaker is installed on the
110.21(B).” busbar, the supply and/or load currents cannot
exceed the rating of the busbar.
705.12(B)(2)(3)(c) provides an alternate But, it should be noted that in existing load
method of sizing the PV backfed breaker, or centers, with the sum of the load breakers
determining the size of the required busbar if the totaling more than the busbar rating, it is
PV backfed breaker rating is known. This section unlikely that load and load breakers can or will
will most likely be used when connecting a PV be removed.
inverter output to a lightly loaded subpanel or It would not be wise to install a backfed PV
when sizing inverter ac combining panelboards. breaker that was larger than the main breaker
After excluding the main breaker from the in those instances where the busbar rating is
utility, the sum of all remaining breakers, both larger than the main breaker. If this were done,
load breakers and the PV supply breaker may the main breaker could trip from overcurrents
not exceed the rating of the busbar. There are through the larger PV breaker.
several aspects to this requirement that need close However, this section needs to be used with
inspection and consideration. caution because there is no restriction on the
First, the main breaker before the addition of position of the backfed PV breaker. Suppose a
any PV has been sized to protect the busbar from 50-amp PV breaker were installed near the top
possible overload from utility currents. The main of the 100-amp busbar in the load center near a
breaker will always be equal to or smaller than 100-amp main breaker and there were 50 amps
the busbar rating. For example, many load centers of load breakers. The Code requirement is met
have a 125-amp busbar, but only a 100-amp main with this configuration. However, what happens
breaker. In a normal panelboard or load center, if someone disregards the warning label or the la-
the ratings of the load breakers will total more bel simply falls off over time? Added load break-
than the rating of the main breaker or the busbar ers in the empty positions could pose an overload
in nearly all circumstances. If this situation exists, situation on the busbar. I suspect that many
then no PV can be added because the require- jurisdictions are going to have to emphasize the
ment cannot be met because the sum of the load permanent nature of that warning label to cover
breakers already exceeds the rating of the busbar. the materials that it is made of and the manner
However, if the sum of the load breakers were in which it is fixed to the panel board. Also, some
equal to the rating of the busbar, that busbar consideration might be made to permanently
would still be protected both by the main covering unused panelboard breaker positions.
breaker and by the fact that excess current over It might be wise to adopt a local jurisdiction
148 Chapter 7 Utility Interconnections
requirement that the backfed PV breaker always and the possibility of installing additional break-
be installed as far as possible from the main ers and loads in unused spaces in the panelboard.
utility breaker and an additional warning label Fault studies may involve looking at the electrical
as required in (b) be placed adjacent to this PV time versus current profiles for each of the circuit
breaker, or other PV overcurrent device. breakers involved to ensure that all portions of
the busbars will be protected under various fault
Center-fed Panelboards and Multiple-ampac- scenarios from currents sourced both from the
ity Busbars utility through the main breaker and from the PV
“(d) A connection at either end, but not both system through the backfed PV breaker.
ends, of a centerfed panelboard in dwellings
shall be permitted where the sum of 125 Marking (3), Suitable for Backfeed (4), and
percent of the power source(s) output circuit Fastening (5)
current and the rating of the overcurrent These sections are largely unchanged from the 2014
device protecting the busbar does not exceed NEC and are self-explanatory.
120 percent of the current rating of the
busbar.” Examples
“(e) Connections shall be permitted on 1. A dwelling has a 125-amp rated service
multiple-ampacity busbars where designed panel (busbar rating) with a 100-amp
under engineering supervision that includes main breaker at the top. How large can the
available fault current and busbar load calcu- backfed 125% of inverter output current
lations.” be assuming that it can be located at the
bottom of the panel? Circuit breaker round
There was no provision in earlier codes to up is allowed.
address center-fed panelboards or multiple-am-
pacity busbars and it was not possible to install PV OCPD + main OCPD <= 120% of
the PV breaker at the opposite end of the busbar panel rating
from the main breaker because there were two
or more busbars connected to the main breaker. 120% of panel rating = 1.2 x 125 = 150 amps
705.12(B)(2)(3)(d) was specifically added to
the 2017 Code to address the common situation PV + 100 <= 150, therefore the 125% of
where PV needs to be connected to a center-fed inverter output current can be up to 50
panelboard. Although not clearly stated, there amps
was no intent to allow center-fed panelboards
to be installed under sections (a) through (c) 2. Suppose it was 100-amp panel with a
of 705.12(B)(2)(3). PV connections are now 100-amp main breaker, how much 125% of
allowed on center-fed panelboards and mul- inverter output current could be added?
tiple-ampacity busbars under the conditions
noted in these sections. Engineering supervision PV + 100 <= 1.2 x 100 = 120
typically indicates that the analysis of the PV
connection will be made and stamped by a pro- The maximum PV backfed 125% of invert-
fessional engineer. The load calculations will look er output current would be 20 amps.
not only at the breakers installed on the busbars,
but also the loads connected to those breakers, 3. A 200-amp main panel with a 200-amp
Chapter 7 Utility Interconnections 149
main breaker would allow up to 40 amps OCPD cannot be located at the bottom of the
of 125% of inverter output current, which panel or at the end of the circuit, it is not possible
could be any combination of 125% of to install the backfed breaker without changing
inverter output currents that added up to something. That 120% allowance drops to only
40 amps on either line 1 or line 2 of the 100%. Any panel that has a main breaker rated
120/240-V panel. the same as the panel rating in the above equa-
tions would not allow any OCPD to be added.
PV + 200 <= 1.2 x 200 = 240 The 100%-of-the-panel-rating factor (instead of
PV <= 240-200 = 40 amps 120%) would equal the rating of the main break-
er, and the equation would force the PV breaker
4. When working the problem from the rating to be zero. Of course, in some unusual
inverter end, we start with the continuous situations, the other allowances in 705.12(B)(2)
rated inverter output current. This is usually might be used.
the rated power divided by the nominal line In a few cases, an NEC Chapter 2 load
voltage, unless the inverter specifications list a analysis might reveal that the service for the
higher continuous output current (sometimes dwelling needed to be only 150 amps, but a
given at a low-line voltage). 200-amp panel was installed with a 200-amp
main breaker just to provide extra circuit
A 3500-watt, 240-volt inverter has a rated breaker positions. In this case, a 150-amp main
ac output current of 3500/240 = 14.58 breaker could be substituted for the 200-amp
amps. breaker if the panel is listed for interchange-
able main breakers. Even without the bottom
The output circuit must be sized a 125% of position being open, 50 amps of PV breaker
14.58 = 18.2 amps [690.8(A)(3) and (B)(1)]. The could be installed.
next larger overcurrent device would be a 20-amp
OCPD and this would be consistent with the use Systems with multiple inverters
of 12 AWG conductors if there were not any very Many residential and small commercial systems
large corrections applied for conditions of use or use more than one inverter (photo 7.12). If the
voltage drop. This system could be connected to local utility requires an accessible, visible-blade,
a 200-amp panel or a 100-amp panel providing lockable disconnect on the ac output of the PV
the backfed 20-amp breaker could be located at system, then more than one inverter could not be
the bottom of the panel (utility input/breaker at connected directly to the main panel. The two, or
the top). more, inverters would have to have their outputs
There is sometimes a tendency to use that 30- combined in a PV ac inverter combining subpan-
amp breaker and those 10 AWG conductors that el (PV ac subpanel) before being routed through
happen to be on the truck. While this would pose the utility disconnect, where required, and then
no problems for conductor ampacity or circuit to the main panel. The utility disconnect (which
protection, the inverter specifications may limit may now be the PV System disconnect) is not
the maximum size of the output OCPD and normally fused, but some are, depending on the
larger values may not be used [110.3(B)]. system configuration (sometimes fused in a sup-
ply-side connection). The PV ac subpanel rating,
No bottom breaker position? the rating of the disconnect, and the ampacity of
From the above equations, if the backfed PV the conductor to the main panel are also con-
150 Chapter 7 Utility Interconnections
Photo 7.12 • Three inverters with PV ac combining panel to the left. The combining panel is required where the utility
will allow only one ac PV disconnect or one REC meter (not shown).
The combined currents from both inverters are: “strings” of microinverters or ac PV modules may
be connected to the added combining panel (green
14.58 + 17.5 = 32.08 blocks). Or, a single inverter could be connected to
an existing load center (red blocks). In some cases,
The overcurrent device should be 40 amps (1.25 multiple inverters might be connected through an
x 32.08= 40.1 ), and this meets Code requirements ac combining panel and then backfeed an existing
for a 200-amp panel with a 200-amp main load center. Let’s start our examination of the
breaker. Note that the allowance of using 125% requirements at the inverter end of the circuit.
of the inverter currents allows a 40-amp backfed
breaker, whereas if the inverter output breakers Inverter Output Circuit
had been used, the resulting 45-amp backfed All utility-interactive inverters have a rated out-
breaker would have not met Code requirements. put current that cannot be exceeded. There are no
With overcurrent devices on each end of the surge currents in these output circuits and NEC
circuit between the inverter output ac combining 690.8 requires that the circuit and the overcurrent
panel and the 40-amp backfed breaker in the protective device (OCPD) be rated at 125% of
main panel, all conductors and equipment in this that rated output current. When the calculated
circuit should be rated for at least 45 amps which OCPD value is a nonstandard value, the next
is the total of the two inverter output breakers standard higher value should be used, but not
(20 + 25 = 45). This exceeds the rating of the to exceed the maximum overcurrent value given
40-amp backfed breaker in the main panel and in the technical specifications for the inverter.
is discussed above where there are overcurrent Conductor size should be selected so that it can
devices on the ends of a circuit. carry the inverter current and is protected by the
OCPD rating.
One Diagram Is Worth a Thousand The asterisk (*) by the 690.8 in the diagram
Words indicates that if there is an overcurrent device
Many people do better with diagrams than they mounted at the inverter, then the requirements
do with words, so figure 7.3 should be just up their of 705.12(B), and not 690.8, will apply. Some
alley. This big picture diagram can be used with installers and manufacturers use a circuit break-
many types of utility interactive PV systems. These er or fused disconnect at the inverter to meet
systems all start with a meter connected to the the requirements of 690.15 to have an equip-
utility as shown on the left (blue). After that, we ment disconnect at the inverter. The inclusion
may be dealing with an existing service disconnect of an overcurrent device at this location may
and the connected existing load center or with a require the output conductors from the inverter
PV supply-side connection, which is similar a sec- to be larger [705.12(B)] than would otherwise
ond service entrance on the existing premises wir- be required by 690.8.
ing system. In either case, the NEC requirements
of Article 230 apply as noted at the bottom of the After the First Inverter Overcurrent
diagram. In most jurisdictions, the local utility will Device
require a PV disconnect on the ac output of the Any conductor or busbar that can have power
PV system, and many areas will use a Renewable flowing from more than one source of supply
Energy Credit (REC) meter to measure the PV (under normal or fault conditions) such as the
system output. As shown, one or more single utility and a PV inverter, and where the conduc-
inverters may be connected or even one or more tor is protected by an overcurrent device on each
152 Chapter 7 Utility Interconnections
supply source must meet 705.12(B) requirements. through the overcurrent device/disconnect on
This is the longstanding 120% allowance [when either an existing service disconnect or through
705.12(B)(2) conditions can be met]. Section the overcurrent device/disconnect on an added
705.12(B) is going to apply to all conductors and PV supply-side connection, the requirements of
busbars from the first overcurrent device connect- 705.12(B) apply all the way to the first overcur-
ed to the inverter output all the way to the service rent device connected to the inverter output.
disconnect.
These busbars and conductors would include Making the PV Circuit to Service Conductor
the busbars of any backfed main panel boards Connection
connected to one or two inverters or sets of Most, but not all, supply-side PV connections
microinverters, and any busbars in PV ac invert- are made to the service conductors between the
er combiner panels. The conductors or feeders meter location and the main service disconnect.
between the panelboards or load centers and the This assumes that the meter is the closest device
main service disconnects are also subjected to toward the utility supply and that a net-metering
the requirements of 705.12(B) as noted on the connection is desired, allowed and/or required
diagram. by the local utility. In some jurisdictions, a zero
sequence or cold meter socket is required by the
The Main Disconnect and on to the local utility and the main disconnect may be
Meter ahead of the meter socket. In either case, the al-
Any circuit between the meter and the service lowance of NEC 705.12(A) is for the connection
disconnect would be considered a service-en- to be made on the utility side of the main service
trance circuit and be governed by the require- disconnect.
ments of Article 230. However, after passing Local utility requirements will determine where
Chapter 7 Utility Interconnections 153
Photo 7.14 • Typical 10 KW ac output whole-house battery-backed-up PV system. System is ac coupled with additional
utility-interactive inverters located outside at the PV array.
circuits or the grid when there is excess energy be some subset of the maximum building load
available or charge the batteries from the grid where only a few critical circuits are connected
when necessary. See Chapter 5 for additional to the battery backed up PV system, but the
details. maximum battery charging load must still be
In either type of system, it is important to note added to this load.
that the ac utility input on the multimode invert- Each type of multimode inverter from the
er may, at times, be a load on the utility feeder or several manufacturers will have software con-
service since it can pass through utility currents trols available to limit and otherwise control
to supply loads under normal operating condi- the various pass through ac currents to the
tions. That input can also supply utility currents connected loads, the ac currents that can be
to charge the batteries when excess PV energy is made available for battery charging and the
not available. maximum ac currents that can be supplied to
The amount of potential maximum load on or supplied from the utility source. The in-
the utility supply must be calculated and used struction manual for these relatively complex
in determining conductor sizes, overcurrent and devices must be carefully reviewed to ensure
disconnect device ratings and service entrance that the appropriate software settings have
ratings. The load may be the entire building load been made and that the external circuitry is
when a “whole house” PV battery backed up compatible with these adjustments. In general,
electrical system is installed plus the load due these software adjustments must not be accessi-
to maximum battery charging. Or, the load may ble to unqualified people.
Chapter 7 Utility Interconnections 155
08
Plan Checking and Inspecting
A formal plan review process and plan reviewers not made in future installations, hopefully, by the
are not found in numerous smaller jurisdictions same contractor.
due to budget constraints and the perceived lack However, we now have the ubiquitous pho-
of need for such activities. This is probably an tovoltaic (PV) power system springing up in
acceptable situation where routine inspections in- numerous neighborhoods on residences and
volve residential electrical systems and the small- commercial buildings throughout the country.
er commercial systems. Those electrical systems The photovoltaic (PV) industry is dynamic
have remained essentially unchanged for decades and fast changing. New PV modules are being
with the exception, of course, of equipment such released monthly and each new module has a
as arc-fault circuit interrupters and ground-fault different size and different ratings. New inverters
circuit interrupters and the like. and other equipment are also coming to market
The load center that I installed in 1960 in the with significant frequency. Although the equip-
home I grew up in is nearly identical to the load ment is connected with the conductors and uses
center I installed in my retirement home in 2010. overcurrent devices that we are familiar with, the
Yes, each edition of the National Electrical Code outdoor environment and the rapidly changing
(NEC) provides changes in the requirements for equipment generally point to the need of some
residential and commercial electrical installations, sort of plan review process to ensure that the
but the equipment is very similar from year-to- somewhat unique PV Code requirements are
year and the methods of installing that equip- being met.
ment are very familiar to the electricians and Most inspectors would agree that an unfamiliar
inspectors. The electrical contractors are familiar installation, a new contractor, and unfamiliar
with the equipment and installation procedures equipment as well as new and slightly different
and although there are differences from instal- Code requirements dictate that a longer-than-usual
lation to installation, there are many similarities. inspection may be required. In fact, it is difficult
Mistakes in the installation occasionally get made when inspecting the typical PV system as installed
and are found by the inspectors, corrected and are in the field to fully ascertain that all the Code
158 Chapter 8 Plan Checking and Inspecting
Figure 8.1 • Three-line diagram of a 2.5 KW PV system. PV system disconnect is the 2-pole backfed breaker. Extra 6 AWG
GEC from inverter is not required by 2017 NEC.
and either approves or disapproves the installa- ing a plan review to determine if the basic design
tion. While this works for normal residential and of the PV system meets minimum code require-
for some small commercial electrical installations ments. Figure 8.1 shows a three-line diagram of a
where the equipment and Code requirements are small PV system with a single string of modules
fairly well standardized, it is probably not the best as an example and such a diagram/schematic
option for PV installations, as noted above, where should be required in any permit application.
the equipment and the installation techniques are
changing frequently. Equipment Lists and
Some jurisdictions are adopting an expedited Specifications
PV permitting process for PV systems under 10 A list of the equipment used and the specifica-
kW. This expedited permitting process usually tions for that equipment should be included with
includes a diagram and other information and is, the permit. This list would include the PV-spe-
in some cases, based on the process described on cific equipment such as the PV modules, the
the SolarABCs’ website. That expedited per- inverter, the fuses, and circuit breakers. Listing/
mitting report and substantial amounts of other certification and rating information must be
PV-related information can be found at: http:// included. The specifications of this equipment
www.solarabcs.org/about/publications/reports/ are necessary to determine if the conductors have
expedited-permit/index.html. been properly sized and that the fuses and circuit
The following paragraphs contain some sugges- breakers used in the dc parts and ac parts of the
tions that have been found useful when perform- system are properly rated. Factory cut sheets or
160 Chapter 8 Plan Checking and Inspecting
pages from instruction manuals are the preferred several additional pieces of information. An in-
way to present this information. stallation instruction manual for the PV module
Since the PV modules and inverters are con- should be included along with a specification
stantly changing, the preferred option would be sheet for the module since frequently the spec-
to include copies of the installation manuals for ifications are not contained in the instruction
the inverter, module, and dc PV combiner with manual. An installation instruction manual for
each submission. Since not all module installation the utility-interactive inverter should also be
manuals include the technical specification, the included along with an instruction manual for
technical specifications should also be included. any dc combiner, where such a combiner is used
to combine source circuits. Cut sheets should be
The Diagram provided to show the ratings of all disconnects
A one-line diagram such as shown in figure 8.2 and overcurrent protective devices used in the
should accompany the permit application. Since system. Information should be provided on
the details of disconnects and grounding are the ratings of any existing electrical equipment
not familiar to all involved, a three-line diagram such as load centers (main breaker and busbar
would be even better as shown in figure 8.3. rating) that the PV system will be connected to
While a formal CAD-generated diagram on or that PV ac currents may pass through all the
24” x 36” paper is not required, something better way from the PV inverter output to the service
than a “back of the envelope” sketch should be entrance conductors.
presented. The circled letters in the figures will
be referenced below to indicate information that The System
should appear on or be attached to the plan. On the one- and three-line diagrams, the fol-
This diagram should be accompanied by lowing information should be indicated, or that
Chapter 8 Plan Checking and Inspecting 161
Figure 8.3 • Three-line PV system diagram. Either the ac disconnect or the utility disconnect can serve as the PV system
disconnect.
information should be attached. The following Due to the exposed, outdoor location and high
numbers reference items in figures 8.2 and 8.3. operating temperatures, all conductors should
have insulation rated for 90°C and wet conditions
A. PV Array (in conduit, THHN/THWN-2, XHHW-2 or
A.1. The type and number of PV modules in each RHW-2). Exposed conductors ( USE-2 or PV
series string should be indicated. The open-circuit Cable/PV Wire) must be suitable for the hot,
voltage (Voc) of each module, times the number of wet, outdoor environment.
modules connected in series, times a cold tempera-
ture factor (690.7) equals the maximum systems B. Conduits
voltage and must be less than the maximum direct B.1. Conduits will typically be used throughout
current (dc) input voltage of the inverter and less the system and specifically after the dc wiring
than the voltage rating of connected direct-cur- leaves the PV array and runs through the struc-
rent (dc) equipment (wires, overcurrent devices, ture. They will be installed in various locations,
disconnects). some of which may be in sunlight. See 310.15(B)
The coldest expected ambient temperature (2) and 310.15(B)(3) for temperature calculations
should be noted on the diagram. A label on the and adders. The average high and the height of
back of each module as shown in photo 8.3 will the conduit above the roof should be specified.
give the electrical parameters needed for the Conduit fill and conductor ampacity calculations
code-required calculations. These values should for conduit fill and temperature calculations
appear on the diagram. A photo of the label should be included or attached.
should be included since this label will not be One source of temperature correction
visible once the modules have been installed. factors for conduits in sunlight based on the
A.2. The ampacity of module interconnection 2014 NEC (still useful, if not specifically
cables, not less than the larger of: 1.56 times the required in the 2017 NEC) is Copper Devel-
module Isc or conditions of use applied to 1.25 Isc. opment’s web site:
162 Chapter 8 Plan Checking and Inspecting
Photo 8.5 • Top clip mounting system must be men- Module Mounting
tioned and installation locations identified in the module
In a similar manner, a mounting detail for the
instruction manual to keep the module listing valid. Note
that drilling two extra holes in this clip has violated the PV module should be included with the diagram.
listing on the clip. This mounting detail should be consistent with
the mounting instructions for the PV module.
frames should be provided on or with the dia- Again, if the module is not mounted according to
gram, and this grounding detail should be consis- the module instructions, the listing is invalid, and
tent with the grounding instructions provided in the module installation does not comply with the
the module instruction manual. If the module is requirements of the NEC. The use of a mounting
not grounded in a manner consistent with the device or racking system that has top clips to
module instruction manual, the listing on the mount the modules has become common recent-
module will be invalid. Since the NEC requires ly (photo 8.5). The module instruction manual
that the module be certified/listed [690.4(D)], must show the use and location of top clips for
then the installation of an unlisted module no mounting the module if this mounting system
longer meets NEC requirements. A frequent is to be acceptable and the installation to remain
problem in this area is the use of some sort of a code-compliant. This alternate mounting system
grounding device that does not use the marked will be in addition to the normal mounting holes
grounding holes shown in the module instruction that are drilled in the back frame of the module
manual and the instruction manual makes no that are normally used for mounting. Although
mention of grounding the module at positions not required by the NEC, the racking system
other than the marked grounding holes. may be listed to UL Standard 2703 that governs
164 Chapter 8 Plan Checking and Inspecting
Conductor Conditions of
Use
The conductors from the PV mod-
ules to the inverter will pass through
several different areas on or in
the building; each area will have a
different set of conditions of use. At
some places, they may be in free air
behind the modules in the shade or
in sunlight. (See photo 8.6.) At other
locations, they may be in conduit.
In some locations, the conduit will
Photo 8.6 • Conditions of use may vary greatly along each source be in sunlight close to the roof and
circuit from the module to the inverter. And, some circuits may need at other locations the conduit may
additional protection from Mother Nature.
be significantly above the roof but
still in sunlight and frequently the
the mechanical and electrical grounding require-
conduits will be in shade on the roof. Usually,
ments for the racking system.
at some point, the conduit will be inside condi-
tioned space as it is routed to the inverter. The
Racking Systems diagram should be annotated to show these
Underwriters Laboratories (UL) Standard 2703 different conditions of use and the temperatures
details a list of performance requirements for and spacing from the roof expected in each
PV racking and mounting systems. Although segment of the conductor run. Of course, the
the Code does not require racking or mounting worst-case conditions of use will be applied to
systems to be certified/listed, a racking system determine the conductor size. It should be noted
that complies with this Standard will ensure that that, in some installations, the conductor size for
the racking system is structurally robust, and that the field-installed conductors may exceed the
the racking system can be used as an equipment size of the conductors attached to the modules
grounding conductor. themselves because the conditions of use for the
The certification/listing of the racking system field-installed conductors and conduit in sunlight
to UL 2703 does not, however, automatically may be more severe than those associated with
guarantee that the racking system and its module the conductors attached to the modules which
mounting, and module grounding provisions are typically in free air. An ampacity calculation
meet code requirements. At this time, both the showing the conditions of use and the required
racking system instructions and the module conductor size should be shown for each separate
instructions must indicate that these two devices condition of use or at least the worst-case con-
have been evaluated together as a system in order ductor size and that calculation should be shown
to ensure that the mounting of the module to the (310.15).
racking system and the grounding of the module
to the racking system comply with all provisions D. The Inverter
of both standards and, therefore, will meet the D.1. The inverter must be listed for utility-inter-
requirements of the NEC. active (U-I); use 705.6.
Chapter 8 Plan Checking and Inspecting 165
09
The Process of Inspecting
PV Systems
One source of online training that is widely d. PV module mounting and grounding details
advertised in IAEI Magazine and other publica- showing that these installation details are com-
tions is the “PV Online Training Course for Code patible and comply with the instructions in the
Officials” developed by the Interstate Renewable PV module and the mounting rack manuals.
Energy Council (IREC), IAEI and others. It Requiring this material in the permit applica-
can be accessed here: www.pvonlinetraining.org. tion will help to ensure that qualified persons are
Be advised; a game is included in this training making that application. The material also will
program. See the excellent article in IAEI Mag- be useful in the plan review process (described
azine (Nov-Dec 2016) on this program (https:// below) that will facilitate the actual on-site
iaeimagazine.org/magazine/2016/11/04/become- inspection.
solar-smarter-with-pv-training-online/).
Expedited Permitting. For those jurisdictions
Building Officials and Administrators. Inspec- not having a formal permitting process, an
tors must be provided with adequate funding expedited permitting process developed by the
and time allowances for the necessary study Solar American Board of Codes and Standards
and training. Workshops and presentations may (SOLARABCS) and written by Bill Brooks and
be brought to a central location so that many others can be found here: http://www.solarabcs.
inspectors can participate, or video conferencing/ org/about/publications/reports/expedited-permit/
webinars can be set up to ensure that all inspec- This expedited permitting process is very useful
tors maintain currency in their respective disci- for PV systems of 10 kW and less and includes
plines, in this case, PV systems. diagrams, fill-in forms, and code-based calcula-
tions. It has been used by numerous jurisdictions
The Permit throughout the country and modified for use
The permit for a PV system should include with additional systems by other jurisdictions.
more than a simple form and the payment of a
fee. That permit application should contain the The Plan Review
following: Advantages. One advantage of having the de-
a. A three-line diagram of the system showing, tails described above submitted with the permit
as a minimum, conductor sizes, conduit sizes, application is that a quick review of this material
equipment grounding circuits, disconnects, over- will give some indication of the capabilities and
current protection, and the location and method competencies of the organization making the ap-
of making the utility interconnection. plication and, hopefully, the person installing the
b. The code calculations for the maximum system system. If the basic system design in the permit
voltage including the expected lowest tempera- package does not meet code requirements, it is al-
ture at the site, the ampacity calculations for each most certain that the system will not be installed
circuit including the ambient temperatures used, in a safe and code-compliant manner. Another
and the NEC 705.12 calculations for the inter- advantage of performing a plan review is the fact
connection point. that the review can verify partial code-compli-
c. A copy of the installation manuals for the PV ance in the warm, quiet, office environment and
module, the dc combiner, the inverter, the PV not out in the cold, blustery or hot, sunbaked
rapid shutdown system/equipment and any other environment of a rooftop PV system.
PV unique equipment, as well as, cut sheets for As mentioned above, it is physically not pos-
the various disconnects and any load centers. sible to fully access all the labels and markings
172 Chapter 9 The Process of Inspecting PV Systems
on the PV modules and many of the cables than rated maximum equipment voltage
after the PV array has been installed. The PV [690.7]
arrays are, in many cases, mounted within a • Cable types suitable for the environments,
few inches of the roof and it would require suitable for the circuit, and properly rated
unmounting a PV module to view the data [690.8]
label on the back. Depending on the module • Conduit and raceway selections appropri-
grounding method being used, grounding ate for the environments and code-com-
hardware might have to be replaced when a pliant [Chapter 3]
module is removed from the racking system. • Conduit fill calculations correct [Annex C]
Conductors installed under the modules and • Disconnects suitable for the type sys-
the connectors used between the PV modules tem-grounded or ungrounded
and the field-installed wiring may not be easily • Disconnects properly rated and properly
accessible. located [690 Part III]
Additionally, reviewing the system on paper • Overcurrent devices properly rated and
allows the AHJ to see the overall system and properly located [690.9]
how the various components are interconnected. • Utility point of connection properly rated
It will also show the flow of power through the and located [705.12]
system which will assist in determining if dis- • Any utility-required disconnects and
connects and overcurrent protection devices have meter properly rated and located
been located properly. • Equipment grounding and system
To a certain extent, some of this information grounding circuits correct
is provided by a full permit package and can be • PV Rapid Shutdown System equipment
used to verify code compliance. Of course, this located in circuits where required by
assumes that the equipment and materials in instructions [690.12], [110.3(B)]
the permit package match the equipment and • DC PV Arc Fault system incorporated
materials that will be installed; and that may not into the PV system [690.11]
always be the case. This item should appear on • DC combiners properly rated
the field inspection checklist. • Inverter and inverter circuits properly
rated for dc inputs and ac output
Items to Look For. Here is a brief checklist
of items that should be verified during a plan The Onsite Inspection
check. Significant numbers of items that are not First impressions are important. Have you
code-compliant may signify that the basic PV worked with this PV installer or systems integra-
system design is inadequate and that the permit tor before? Is the site uncluttered and the system
package be returned to the submitter for correc- ready for inspection? Did they make the roof ac-
tions before any field inspection can be under- cessible in a safe manner? From a distance, does it
taken. A more detailed checklist will be found in look like good workmanship has been employed?
Appendix A. As with any electrical power system, atten-
• All equipment listed for the specific tion to details during the installation process
application [690.4(B)] is critical, and the overall first impressions
• Modules and racks compatible for mount- give some indication as to whether the install-
ing and grounding [110.3(B)] er has exercised good work procedures and
• Calculated maximum system voltage less habits.
Chapter 9 The Process of Inspecting PV Systems 173
After the System is Powered PVRSS with the well-marked initiator, and the
With the complexity of modern PV equipment, AJH should verify that the measured voltage
full verification of the installation for safety and drops to the required value of 30 volts within 30
compliance with the NEC requirements (includ- seconds. Note: at some future date, the ac voltage
ing Section 110.3(B) that requires compliance level may be reduced to 15 volts due to proposed
with equipment installation instructions) will changes in UL Standard 1741. Both line-to-line
usually require the AHJ to inspect the system and line-to-ground measurements will be re-
during operation. quired.
Verify equipment adjustments and settings. String inverter systems. The string inverter
Equipment like string inverters, multimode system will usually require that the dc conduc-
inverters, charge controllers and PV Rapid Shut- tors from the array and the ac conductors from
down Equipment (PVRSE) may have software/ the inverter be controlled by the PVRSS. Some
firmware adjustments that must be properly inverters may be listed as PV Rapid Shutdown
made to ensure the safe and correct operation of Equipment (PVRSE) and will meet the voltage
the product [110.3(B)]. The AHJ should have the requirements on dc inputs and/or ac outputs
installer demonstrate that all adjustments have without external equipment. Appropriate meters
been completed in accordance with the product should be connected to the dc input conductors
instruction manuals. that go to the inverter (normally, at the closed
dc disconnect) and to the ac output conductors
PV Rapid Shutdown System (PVRSS). of the inverter. The installer should activate the
The inspector should have the installer demon- PVRSS initiator, and the AHJ should verify that
strate the proper operation of the PVRSS since all voltages go to the required 30-volt levels with-
this system is directly involved with life safety in 30 seconds. AC voltage requirements may be
issues for first responders. The ac power to the reduced to 15 volts due to future changes in the
building that the PV is installed on should UL standard. Line-to-line and line-to-ground
be turned off, as it would be during any first measurements will be required.
responder activity. In fact, the main service
disconnect or the ac PV disconnect may have to Arcs Will Happen
be marked as a second PVRSS initiator in some As the PV system ages, it is expected that there
systems to ensure the ac inverter output circuits will be greater opportunities for series arcs to
are controlled by the PVRSS in addition to the form in the dc array wiring and the modules.
dc circuits. The main ac service disconnect for Connectors, even those properly mated in pairs,
the building may or may not be the PVRSS ini- may loosen over time from wind driven vibra-
tiator. In any event, the ac output circuits of the tions where conductors have not been securely
PV system should not remain energized after the fastened. There will be some connector pairs that
PVRSS system has been initiated and the facility are mated from different manufacturers that
main service disconnect has been opened. get past the inspections and may create failures
AC PV module or microinverter system. In sooner rather than later. Module solder bonds
the case of an ac PV module system or a micro- have failed in the past, and with numerous new
inverter system, the installer should connect a manufacturers of PV modules on the market, we
digital voltmeter (DVM) to the ac output of the may expect to see such failures in the future.
operating ac PV module array with line voltage The requirements for PV system to have dc
indicated. The installer should then activate the PV arc-fault circuit interrupter (DCPVAFCI)
Chapter 9 The Process of Inspecting PV Systems 177
are similar, but not identical in 2011, 2014, and islanding software/firmware. It will be up to the
2017 Codes. Verification that the inverter, dc PV AHJ to determine that the correct inverter has
combiner or charge controller has the DCPVAF- been installed based on the local requirements. It
CI will be accomplished by the markings on will not be possible on the typical PV inverter to
the inverter, dc combiner or possibly the charge easily test these characteristics in the field, so the
controller. At this point, it is unclear how the markings and the certification/listing mark will
UL Standard 1699B will deal with products that have to suffice.
must meet the differing requirements of various
Code editions. It is possible that an installer Summary
controlled software function will allow a single Photovoltaic power systems are proliferating
inverter to meet the varying requirements of and are going to be a major player in our nation’s
several editions of the NEC. energy mix. They are going to become more com-
plex. The inspector community must be able and
Ride-Through PV Inverters willing to inspect these systems as the last line
Various states and utilities are starting to require of defense in ensuring the safety of the public.
the use of utility-interactive inverters that will The plan review stage is becomisng increasingly
stay on line and produce full available array important due to the increasing complexity of the
power during utility voltage and frequency systems and the number of not-fully-qualified
variations that exceed the normal anti-islanding individuals and organizations installing these
limits of +10% to -12% on voltage and +0.5 Hz systems.
to -0.7 Hz on frequency. The voltage variations Those of us in the inspection community and
may be as low as 50% of the normal line voltage. those associated with the inspection community
These inverters will also be required to come including inspectors at all levels, chief inspectors,
back on line at full array power within one (1) building officials, and administrators responsible
second after the utility voltage and frequency for funding need to work diligently to increase
have returned to either the normal or widened the competency and quality of our inspection
limits. This is considerably different from the process and our inspection force. Additional
current five (5) minute delay in powering up time must be made available to inspect these
after a utility outage. There will be certified/listed systems. Additional time and funding must be
utility interactive inverters on the market that will made available to educate and train the inspector
meet these new requirements and they will be workforce, and above all, those inspectors must be
well marked as such. However, the great majority fully supported when they make the tough calls
of the available inverters will have the current anti on code violations.
178 Chapter 10 The 15-Minute PV Inspection – Can You? Should You?
Chapter 10 The 15-Minute PV Inspection — Can You? Should You? 179
10
The 15-Minute PV Inspection–Can
You? Should You
In some jurisdictions, inspectors have as little verters, disconnects and overcurrent devices) that
as 15 minutes to make a residential electrical has been installed is the same as previous systems
inspection. A common question is, “Can I inspect and those previous systems have been inspected
a residential PV system in 15 minutes?” This and no significant issues were found.
chapter will examine that question and take up Here are some of the items that an inspector
the question, “Should only 15 minutes be allocat- should verify during the site visit. They are listed
ed for inspecting a residential PV system?” in order of importance and in order of safety for
Let’s start with an ideal situation. The inspec- the inspector. For a more complete checklist,
tor is familiar with PV systems in general and see the Inspector/Installer Checklist found in
has inspected quite a few. He or she receives an Appendix A.
application for a permit for a PV system, and that
application is accompanied by all the material Grounding
outlined in the preceding chapters in this book. Proper grounding of the PV system is extremely
A plan review of the supplied material shows important because the PV modules will be gen-
no major problems in code-compliance, and the erating hazardous amounts of energy for the next
installer quickly rectifies the few minor problem fifty years or more. Proper grounding is the first,
areas found. A team consisting of a PV vendor/ the last, and the most important area (in the au-
installer with a history of good PV installations thor’s experience) that requires code-compliance
employing or working with an electrical contrac- in a PV system. Proper grounding of all exposed
tor/electrician who has a commercial electrical metal surfaces that may become energized as the
license and some PV experience has done the system ages or as accidents happen will provide
design of the system and the installation. The the highest levels of protection against shock
system is nearly identical to others that this or- and fires. Proper grounding will also facilitate
ganization has previously installed and have been the action of the ground-fault protection and
inspected with no significant issues. The system arc-fault protection equipment that these systems
configuration and the equipment (modules, in- will have. As the inspector moves through the
180 Chapter 10 The 15-Minute PV Inspection – Can You? Should You?
AC Point of
Connection to the
Utility
While the premises ac load center
is open to check the grounding
connection, the location and value
of the backfed PV circuit breaker
can be noted. It should match the
Photo 10.1 • Improperly wired 240-volt inverter; neutral wired to PE value on the permit application
terminal and shall not be greater than 20%
of the load center rating. It should
PV system, grounding will be a critical inspection be located at the opposite end of the busbar
item in several locations. from the utility input. This assumes that the
Most smaller PV systems (below 10–20 kW) main breaker and the load center have the same
may have all the PV equipment, both ac and rating. See NEC 705.12(B)(2). This requirement
dc, grounded by a single “grounding” conductor limits the backfed PV breaker to a maximum
connected from the modules to the ground- of 20-amps on a 100-amp load center and to
ing bus bar in the existing ac load center. The a maximum of 40 amps on a 200-amp panel.
module frames, the PV array mounting rack, Breakers larger than this indicate that the utility
and the dc disconnect are connected with a dc connection should have been made on the supply
equipment grounding conductor that connects side of the service disconnect. See Chapter 7 for
to the inverter. From the inverter through one or more details.
more ac disconnects, an ac equipment ground-
ing conductor (which may also serve as any PV Inverters
system functional ground) continues the connec- The inverter should be opened to check the
tion to the ground bus bar in the ac load center field-installed connections. Some inverters will re-
[690.47(A)]. quire metric hex socket drivers (or Allen wrenches)
The first item an inspector should verify is that to open. One manufacturer makes a sealed inverter
the ac equipment grounding conductor from the with permanently attached cables for connections
PV system inverter has been connected properly to the adjacent ac and dc disconnects.
in the ac load center grounding bus bar and that Inverters with a 120-volt output should have
the ac load center has a proper connection to line (ungrounded), neutral (grounded), and equip-
ground (earthed). If this equipment grounding ment grounding conductors between the load
has not been done properly, a ground fault in the center and the inverter. Inverters made outside the
PV array or elsewhere in the system may put U.S. may have the equipment grounding terminals
several hundred volts (with respect to the ground marked PE for “protective earth.” Some 240-volt
where the AHJ is standing) on the ungrounded inverters have only line 1, line 2, and equipment
exposed metal surfaces of any PV equipment. grounding conductors with no neutral (grounded)
Chapter 10 The 15-Minute PV Inspection — Can You? Should You? 181
AC and DC Disconnects
Each disconnect should be properly grounded
with the equipment grounding conductors or
metal raceways. Following and verifying the
equipment grounding conductors backwards
Photo 10.2 • Inverter with two dc inputs (lower left). EGC from the ac load center through the system to
on lower right. Improper double lugging for small surge the PV modules is important to ensure that each
suppressor conductors. Color coding based on 2014 NEC.
exposed metal surface that may be energized is
grounded. Grounding using sheet metal screws
is prohibited by the Code and the use of thread
cutting screws and aluminum lugs is questionable
(photo 10.3). Most listed fused disconnects and
circuit breaker enclosures have ground-bar kits
with specific mounting instructions and locations
that should be used to maintain the listings of
the devices and to provide the highest quality
grounding connection (photo 10.4). Metal
conduits with dc circuits operating over 250 volts
will usually require grounding/bonding bushings
(250.97).
While any of the disconnect or isolation device
enclosures are opened, the color coding of the
conductors should be checked. PV systems in-
Photo 10.3 • Improperly grounded dc disconnect; violates stalled under the 2017 NEC will typically not have
250.8, 110.3(3), 250.96(A), and 250.4(A)(5) any of the dc PV array conductors grounded and
no white conductors should be seen. The exception
conductor, while others will have line 1, line 2, would be the small solidly grounded PV array
neutral, and equipment grounding conductors. outside a building as allowed by 690.41.
The inverter manual (submitted with the permit There is no specified color code for the un-
request) will show the proper connections. Invert- grounded conductors, and any color is permitted
ers requiring no neutral connection must not have as long as gray, white, green, and green and yellow
the neutral terminal in the utility circuit attached are not used. In conduit, conductors with colored
to anything, particularly an equipment grounding insulation can be used for polarity and circuit
182 Chapter 10 The 15-Minute PV Inspection – Can You? Should You?
Photo 10.4 • Properly installed, listed ground-bar kit Photo 10.5 • Readily accessible module wiring properly
secured and guarded.
identification. However, colored insulations on
exposed wiring may not prove durable over the life most residential PV systems will more closely
of the system due to a lack of carbon black in the resemble the equipment and workmanship on
insulation resulting in a reduction in the ultraviolet a commercial electrical installation than those
(UV ) radiation resistance. Black insulation has items in a residential electrical system. There
proven to be the most durable. will usually be surface-mounted disconnects and
Both circuit conductors (positive and negative) much of the wiring will be in exposed, sur-
should be routed through the disconnect enclo- face-mounted conduit.
sure even when only the ungrounded conductor is The installer should have a ladder on-site the
switched. Avoiding a “switch loop” configuration day of the inspection to facilitate examining
ensures that both circuit conductors are always the installed PV array. A quick look at the PV
in close proximity (lowering circuit inductance) array on the roof should verify that any exposed
for best functioning of overcurrent devices and to wiring is firmly secured to the PV modules or
allow a bolted connection point for the grounded the mounting structure and is not dangling down
conductor on an isolated “neutral bus” in the where it would be subject to physical damage
enclosure, if required. (photo 10.5).
In the “switch-type” dc PV disconnect, the al- If the backs of the PV modules can be closely
ways “hot” conductors from the PV array wiring observed, proper grounding of the modules
source or output circuits should be connected should be checked. The hardware supplied by
to the top (protected) “Line,” terminals on the the module manufacturer should have been used
switch while the lower, exposed, “Load” terminals as shown in the instruction manual delivered
should be connected to the inverter. On any ac with the permit application. Each PV module
switched disconnect, the upper “Line” terminals must be grounded, and if exposed, single-con-
should be connected to the utility power conduc- ductor cables touch the mounting racks or a
tors that come from the backfed ac load center or metal roof, those objects should also be ground-
a supply-side utility connection. The lower “Load” ed. See Chapter 3 for more details on module
terminals should be connected to the inverter. grounding.
The conductors used for module interconnec-
Workmanship and the Roof tions should be as specified in the permit appli-
The equipment used and the workmanship on cation with respect to size (AWG), insulation
Chapter 10 The 15-Minute PV Inspection — Can You? Should You? 183
type, and temperature rating. Any PV combiners equipment being installed, or the installer would
containing overcurrent devices exposed to sun- normally dictate that the inspection takes more
light should be noted and the plans and technical time. How much? Some residential PV inspections
data reviewed to determine if adequate tempera- for new inspectors are somewhat of a training ses-
ture deratings were applied. Conduits in sunlight sion and with a knowledgeable installer, examining
will also be exposed to higher-than-ambient and discussing all the details relating to a durable,
temperatures. safe (for 50-years) installation might take two or
more hours.
Inspect in 15 Minutes?
Yes, it might be possible to perform the above Should We Do 15-Minute
inspections in 15 minutes if the inspector has Inspections?
spent some time at the plan-check stage and is See the little girl in photo 10.6? That PV system
experienced in PV systems employing this inverter she is touching will still be producing power
and the installer is there to answer questions, open when her grandchildren are her age. It will take
the inverter and other equipment as necessary and more than a 15-minute inspection to ensure that
to provide a ladder for roof access. However, any the PV system will be as safe then as it is now.
problems found in the above areas should warrant Fifteen minutes is probably insufficient time to
a closer look at the entire system and when more ensure the public safety of a system that may
details are examined, the inspection time can grow. operate, with possibly little attention, over a
A lack of familiarity with either PV in general, the 40–50-year period.
Photo 10.6 • A 40 kW PV system. Safe now, but will it still be safe in 40 years” Courtesy James Worden
184 Appendix A 2014 and 2017 NEC Photovoltaic Electrical Power Systems Inspector/Installer Checklist
Appendix A 2014 and 2017 NEC Photovoltaic Electrical Power Systems Inspector/Installer Checklist 185
A
2014 and 2017 NEC Photovoltaic
Electrical Power Systems
Inspector/Installer Checklist
The following checklist is an outline of the CHECKLIST FOR
general requirements found in the 2014-2017 PHOTOVOLTAIC POWER
National Electrical Code (NEC) in Articles SYSTEM INSTALLATIONS
690 and 705 that deal with Photovoltaic (PV)
Power Systems installations. 1. PV ARRAYS
The checklist is only a guide and applies to □ PV modules listed to UL Standard 1703?
any component used or installed in a PV system [110.3, 690.4(B)]
other than devices inside a listed, factory-as-
sembled component. a. Mechanical Attachment
The local authority having jurisdiction
(AHJ) or inspector has the final say on what
□ Modules attached to the mounting struc-
is or is not acceptable. Local codes may mod-
ture per the manufacturer’s instructions?
ify the requirements of the NEC.
[110.3(B)]
This list should be used in conjunction with
Article 690, Article 705 and other applicable
□ Roof penetrations secure and weather
articles of the NEC and includes inspection
tight? (110.12, 110.13)
requirements for both stand-alone PV systems
(with and without batteries) and utility-inter-
b. Grounding
active PV systems. Where Article 690 or 705
differ from other articles of the NEC, Article □ Each module grounded using the supplied
690 or 705 takes precedence. (690.3, 705.3) hardware, the grounding point identified
NOTE: The 2017 NEC has many detailed on the module and the manufacturer’s
changes in Art 690 and 705 with older mate- instructions? Note: Bolting the module
rial being placed in new articles and numerous to a “grounded” structure usually will not
small revisions of the remaining material. Code meet NEC requirements [110.3(B)] and
references will generally be to the 2017 NEC. may not comply with the instructions
186 Appendix A 2014 and 2017 NEC Photovoltaic Electrical Power Systems Inspector/Installer Checklist
for grounding the PV module. Array PV Strain reliefs/cable clamps or conduit used
mounting racks are usually not identified on all cables and cords? (300.4, 400.10)
as equipment-grounding conductors, unless
certified/listed to UL Standard 2703. □ Listed for the application and the environ-
(690.43) Module instruction manual must ment? Fine stranded, flexible conductor
specifically show/indicate grounding and conductors properly terminated with ter-
mounting method. minals listed for such conductors? (110.14)
□ Properly sized equipment-grounding con- □ Cables and flexible conduits installed and
ductors routed with the circuit conduc- properly marked? (690.31)
tors? (690.45)
□ Exposed conductors in readily acces-
c. Conductors sible areas in a raceway or guarded
if over 30 volts? [690.31(A)] Note:
□ Conductor type?—If exposed: USE-2 or Raceways cannot be connected to
PV wire for grounded PV arrays and PV most modules. Conductors should be
wire for ungrounded PV arrays. All PV installed so that they are not readily
modules will use PV wire. 2017 NEC al- accessible (i.e., guarded).
lows USE-2 or PV wire for both grounded
and ungrounded systems. 2. OVERCURRENT
PROTECTION
□ Conductor insulation rated at 90°C (UL-
1703) to allow for operation at 70°C+ near
modules and in conduit or cables exposed
□ Overcurrent devices in the dc circuits list-
ed for dc operation? If device not marked
to sunlight? [Table 310.15(B)(3)(c)]
dc, verify dc listing with manufacturer.
Auto, marine, and telecom devices are
□ Temperature-corrected ampacity calculations not acceptable.
based on 125% of short-circuit current (Isc)
or the 156% Isc without conditions of use
(take the worst case)? □ In PV circuits, OCPD must be listed as
PV device [690.9(B)].
Note: Suggest temperature derating factors
of 65°C for conductors behind modules in □ Rated at 1.25 x 1.25 = 1.56 times
installations where the backs of the module short-circuit current from modules?
receive cooling air (4" or more from roof ) (UL-1703, 690.8, module instructions).
and 75°C where no cooling air can get to Overcurrent devices listed for PV appli-
the backs of the modules. Ambient tem- cations are required. [690.9(B)].
peratures (near and at the array location)
more than 40°C may require different □ Each module or series string of modules
derating factors. have an overcurrent device protecting the
module? [UL-1703 / NEC 110.3(B)]. Note:
□ Portable power cords allowed only for Frequently, installers ignore this require-
tracker connections? [690.31(C), 400.3,7,8] ment marked on the back of modules.
Appendix A 2014 and 2017 NEC Photovoltaic Electrical Power Systems Inspector/Installer Checklist 187
Listed combiner PV combiner boxes □ Twist-on wire connectors listed for the
meeting this requirement are available. environment (i.e., dry, damp, wet, or direct
One or two strings of modules generally burial) and installed per the manufacturer’s
do not require overcurrent devices, but instructions?
three strings or more in parallel will
usually require an overcurrent device. The □ Pressure lugs or other terminals listed for
module maximum series fuse must be at the environment? (i.e., inside, outside, wet,
least 1.56 ISC. [690.9(A)] direct burial)
outputs? Listed equipment is available and protection for entire dc system with possible
the UL Standards addressing the require- exception of source circuit or module protective
ments are published. Operation verified? fuses.
□ Disconnects for all current-carrying conduc- □ Cables to batteries sized 125% of calculated
tors for the PV system? (690.13) inverter input currents? [690.8(A), 706.20]
2017 NEC: PV System Disconnect must
disconnect all circuit conductors—even □ Overcurrent/Disconnects mounted near
on solidly grounded systems -but solidly batteries and external to PV load centers
grounded conductors should not be opened. if conductors are longer than 4–5 feet to
(Look for a possible change to this require- batteries or inverter?
ment in the 2020 NEC.)
□ High interrupt, listed, dc-rated fuses or
□ Disconnects for equipment? (690.15/690.17) circuit breakers used in battery circuits?
2017 NEC: Equipment isolation discon- AIR/AIC at least 20,000 amps?
nects may disconnect only the ungrounded [706.21 110.9, 110.10]
conductor.
□ No multi-wire branch circuits where single
□ DC combiner has output circuit discon- 120-volt inverters are connected to 120/240-
nect/isolator internal or within 3 m (10 ft)? volt load centers? [Art 100–Branch Circuit,
[690.15(A)] Multi-wire), 710.15]
Note: Listed PV Power Centers are available □ No separate batteries cells are listed.
for 12, 24, and 48-volt systems and they contain
charge controllers, disconnects, and overcurrent
Appendix A 2014 and 2017 NEC Photovoltaic Electrical Power Systems Inspector/Installer Checklist 189
□ Building-wire type cables used? (Chapter 3) □ Inverter listed to UL Standard 1741 and
Note: Welding cables, marine, locomotive identified for use in interactive photovol-
(DLO), appliance wire material (AWM) taic power systems? [690.4(B), 705.4].
and auto battery cables don’t meet NEC Note: Inverters listed to telecommuni-
requirements. Flexible, listed RHW, or cations and other standards do not meet
THW cables are available. Article 400 NEC requirements.
flexible cables larger than 2/0 AWG are
OK for battery cell connections, but not in □ Backup charge controller to regulate the
conduit or through walls [690.74, 400.8]. batteries in systems with multimode
Flexible, fine-stranded cables require inverters when the grid fails? [706.23(B)]
limited-availability, specially-listed terminals
[110.14, 690.74]. See stand-alone inverters □ Connected to dedicated branch circuit
for ampacity calculations. with back-fed overcurrent protection?
[705.12(B)] or connected as a supply-side
□ Access limited? [706.30] connection with overcurrent protection
within 10 feet? [705.12(A), 705.31]
□ Installed in well-vented areas (garages, base- □ Listed dc and ac disconnects and overcur-
ments, outbuildings, and not living areas)?
rent protection? (690.15, 17)
Note: Manifolds, power venting, and single
exterior vents to the outside are not re-
□ All requirements of 705.12(B) or
quired and should be avoided [706.10(A)].
705.12(A) met?
□ Have the conductor routing and protection NOTE: Square wave or modified sine wave
requirements of 706.20 and 706.32 been inverters may be listed to UL 1741 but are
met? Cables to inverters, dc load centers, not compatible with many power tool battery
and/or charge controllers in conduit? chargers, smoke alarms, and other listed elec-
tronic devices and should not be used with
□ Conduit enters the battery enclosure these devices. The manufacturer’s instruction
below the tops of the flooded batteries? manual will usually have the warning state-
(300.4) ment [110.3(B)].
grounded PV arrays and one bonding □ Conductor insulations other than black
conductor for ac circuits (neutral to ground) in color will not be as durable as black
for ac system grounding? in the outdoor UV-rich environment.
Note: The utility-interactive inverter will □ DC color codes correct? They are the same
generally provide the functional ground for the as ac color codes—grounded conductors
system. Instructions for that functional ground are white or gray and equipment-grounding
will be in the inverter installation manual. conductors are green, green/yellow, or bare.
[200.6(A)]
□ System/inverter grounding meets require-
ments of 690.47? □ Ungrounded PV array conductors on
ungrounded PV arrays will not be white
□ Equipment grounding conductors properly in color. Note that functionally grounded
sized (even on ungrounded, low-voltage PV systems under the 2017 NEC will not
systems)? (690.43, 45, 46) have any dc PV source or dc PV output
conductors with white insulation. The
□ Disconnects and overcurrent in both color white will only be used in solidly
ungrounded conductors in each circuit on grounded PV systems (690.41).
12- volt, ungrounded systems or on un-
grounded systems at any voltage? (690.9, 11. Markings
690.13, 690.15, 690.31) Revised for 2017
NEC with functional grounding. □ All field-applied markings correct?
Note that functionally grounded PV [690.13(B), 690.31(B), 690.51, 690.53,
systems under the 2017 NEC will not 690.54, 690.55, 705.10, 705.12]
have any dc PV source or dc PV output
conductors with white insulation. □ Meet color and letter size requirements?
(690.56)
□ Bonding-grounding fittings or bushings
used with metal conduits when dc system 12. DC PV Arc Fault Circuit
voltage is more than 250V dc? (250.97). Protection?
Grounding bonding bushings used where
grounding electrode conductors are in □ Usually installed in the inverter or on larger
metallic raceways and /or enclosures? systems in the array field. May be multiple
devices (690.11). UL Standard 1699B is
10. CONDUCTORS (General) the applicable standard.
□ Wet-rated conductors used in conduits in □ Installed per 690.12 and local require-
exposed locations? (100 Definition of ments? Operational?
Location, Wet)
191
B
Bibliography
Molded-Case Circuit Breakers, Molded-Case Standard for Connectors for Use in Photovoltaic
Switches, and Circuit-Breaker Enclosures for Use Systems. UL Standard 6703, 2014.
with Photovoltaic (PV) Systems. UL Standard
489B, 2016. Standard for Flat-Plate Photovoltaic Modules and
Panels. UL Standard 1703, 2012.
National Fire Protection Association. National
Electrical Code® (NEC®) Handbook. Quincy, Standard for Flat-Plate Photovoltaic Modules and
Massachusetts: NFPA, 2017. Panels. UL Standard 1703, 2002.
National Fire Protection Association. National Standard for Industrial Control Equipment. UL
Electrical Code® (NEC®) Handbook. Quincy, Standard 508, 1999.
Massachusetts: NFPA, 2014.
Standard for Inverters, Converters, Controllers and
National Fire Protection Association. NFPA 70: Interconnection System Equipment for Use With
National Electrical Code. Quincy, Massachusetts: Distributed Energy Resources. UL Standard 1741,
NFPA, 2017. 2010.
National Fire Protection Association. NFPA 70: Standard for Mounting Systems, Mounting Devices,
National Electrical Code. Quincy, Massachusetts: Clamping/Retention Devices, and Ground Lugs
NFPA, 2014. for Use with Flat-Plate Photovoltaic Modules and
Panels. UL Standard 2703, 2015.
Photovoltaic (PV) DC Arc-Fault Circuit Protection.
UL Standard 1699B, 2011. Standard for Photovoltaic Wire. UL Standard
4703, 2011.
Solar American Board of Codes and Standards.
Expedited Permit Process Report - Revision 2, last Wiles, John, “Perspectives on PV archives,” IAEI
accessed on 12/13/2017. http://solarabcs.org/ Magazine, 2015-2018.
about/publications/reports/expedited-permit/
index.html.
192
Third Edition
Author John Wiles
John Wiles is perhaps the most recognized and influential name in the solar indus-
try. He’s worked extensively in the development of the NEC and UL Standards and
is an active trainer on Code-compliant PV systems. Wiles has written hundreds of
articles on Code-related photovoltaic system topics and continues to write Perspec-
tives on PV articles for IAEI News.
Chapters include:
International Association
of Electrical Inspectors
901 Waterfall Way, Suite 602,
Richardson, TX 75080-7702
v.2