Rexroth Indracontrol L25: Project Planning Manual
Rexroth Indracontrol L25: Project Planning Manual
Rexroth Indracontrol L25: Project Planning Manual
L25
Table of Contents
Table of Contents
Page
1 System Presentation...................................................................................................... 5
1.1 Brief Description IndraControl L25.......................................................................................................... 5
1.2 Device Variants....................................................................................................................................... 5
1.3 View........................................................................................................................................................ 5
1.4 Further Documentation........................................................................................................................... 6
4 Technical Data............................................................................................................. 21
4.1 Equipment............................................................................................................................................. 21
4.2 Voltage Supply...................................................................................................................................... 21
4.3 Ambient Conditions............................................................................................................................... 22
4.4 Used Standards.................................................................................................................................... 22
4.5 UL and CSA certified............................................................................................................................ 23
4.6 Compatibility Test................................................................................................................................. 23
4.7 Wear Parts............................................................................................................................................ 24
5 Dimensions.................................................................................................................. 25
5.1 General Information.............................................................................................................................. 25
5.2 Housing Dimensions............................................................................................................................. 25
5.3 Installation Notes.................................................................................................................................. 26
II/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
Table of Contents
Page
Table of Contents
Page
Dimensioning the Voltage Supply................................................................................................... 52
8.3.4 Main Switches and Fuses.................................................................................................................. 52
Main Switches ............................................................................................................................... 52
Fuses.............................................................................................................................................. 52
8.3.5 Grounding
........................................................................................................................................................... 53
8.3.6 Shield System.................................................................................................................................... 53
General Information........................................................................................................................ 53
Shielding the PROFIBUS Cable..................................................................................................... 53
8.3.7 Connecting Lines to Tension Spring Connection Points................................................................... 54
General Information........................................................................................................................ 54
Connecting Unshielded Lines......................................................................................................... 54
8.4 Maintenance......................................................................................................................................... 54
10 Ordering Information.................................................................................................... 59
10.1 Type Designation Code........................................................................................................................ 59
10.1.1 General Information........................................................................................................................... 59
10.1.2 IndraControl L25................................................................................................................................ 59
10.2 Accessories.......................................................................................................................................... 60
10.2.1 Spare Part (Power Connector).......................................................................................................... 60
General Information........................................................................................................................ 60
10.2.2 Further Accessories (Rexroth Inline Terminals, Function Modules and Interface Cables)................ 60
Rexroth Inline Terminals................................................................................................................. 60
Rexroth Function Modules.............................................................................................................. 60
Interface Cables............................................................................................................................. 61
Index............................................................................................................................ 67
IV/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 5/69
Rexroth IndraControl L25
System Presentation
1 System Presentation
1.1 Brief Description IndraControl L25
The IndraControl L25 is a modular and scalable control. The control combines
the benefits of a compact small control with a standardized I/O system based
on terminal technology. The control is a universal hardware platform that can
be used for motion-logic and PLC applications. The control provides commu‐
nication interfaces such as Ethernet, EtherNet/IP as well as a SERCOS III
interface. Up to two function modules extend the IndraControl L25 via integra‐
ted PCI bus and additional fieldbus interfaces and technology interfaces. The
locally available I/O units can be extended by the Rexroth Inline I/O system,
just by simply mounting the components side by side. The complete application
programs, including runtime, are stored on an easily accessible Compact Flash
card.
1.3 View
Operating elements and interfaces are arranged on the front panel:
In the left part is a display with eight characters and four operating keys, the
reset button, a LED, the Ethernet interface, the ready contact and a receptacle
for a Compact Flash card. The interfaces for SERCOS III are located in the
center. The voltage supply is located in the right part.
System Presentation
Before using Bosch Rexroth products, the following requirements must be met
to ensure intended use of the products:
● Anyone handling one of the Rexroth products in any way has to read and
understand the respective safety-related guidelines as well as the instruc‐
tions on intended use.
● Hardware products have to remain in their original state, in other words,
no modification regarding the design are allowed. Software products must
not be decompiled and their source codes must not be modified.
● Damaged or faulty products must not be implemented or put into opera‐
tion.
● It must be ensured that the products are installed as specified in the doc‐
umentation.
The IndraControl L25 may only be used with the accessories and
mounting parts which are listed in this documentation. Components
not named expressly mentioned must neither be mounted nor con‐
nected. The same applies to cables and conduits.
The products may only be operated with the expressly stated con‐
figurations and component combinations as well as with the soft‐
ware and firmware which is given and specified in the respective
functional description.
In case of non-compliance, the guarantee and warranty claims shall
automatically expire.
The IndraControl L25 may only be operated under the assembly and installation
conditions, in the position of application and under the ambient conditions (tem‐
perature, degree of protection, humidity, EMC, etc.) specified in this documen‐
tation.
Contact with parts conducting voltages above 50 volts can cause personal
danger and electric shock. When operating components of the electric drive
and control system, it is unavoidable that some parts of these components
conduct dangerous voltage.
High electrical voltage! Danger to life, risk of injury by electric shock or serious
injury!
● Only qualified persons are allowed to operate, maintain and/or repair the
components of the electric drive and control system.
● Follow the general installation and safety regulations when working on
power installations.
● Before switching on, the equipment grounding conductor must have been
permanently connected to all electric components in accordance with the
connection diagram.
● Even for brief measurements or tests, operation is only allowed if the
equipment grounding conductor has been permanently connected to the
points of the components provided for this purpose.
● Before accessing electrical parts with voltage potentials higher than 50 V,
you must disconnect electric components from the mains or from the pow‐
er supply unit. Secure the electric component from reconnection.
● With electric components, observe the following aspects:
Always wait 30 minutes after switching off power to allow live capacitors
to discharge before accessing an electric component. Measure the elec‐
trical voltage of live parts before beginning to work to make sure that the
equipment is safe to touch.
● Install the covers and guards provided for this purpose before switching
on.
● Never touch electrical connection points of the components while power
is turned on.
● Do not remove or plug in connectors when the component has been pow‐
ered.
● Under specific conditions, electric drive systems can be operated at mains
protected by residual-current-operated circuit-breakers sensitive to uni‐
versal current (RCDs/RCMs).
● Secure built-in devices from penetrating foreign objects and water, as well
as from direct contact, by providing an external housing, for example a
control cabinet.
High housing voltage and high leakage current! Danger to life, risk of injury by
electric shock!
● Before switching on and before commissioning, ground or connect the
components of the electric drive and control system to the equipment
grounding conductor at the grounding points.
14/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
Cross section outer con‐ Minimum cross section equipment grounding conductor
ductor Leakage current ≥ 3.5 mA
1 equipment grounding 2 equipment grounding con‐
conductor ductors
16 mm2 (6 AWG) -
35 mm2 (2 AWG) -
Danger to life, risk of injury by electric shock! High electrical voltage by incorrect
connection!
If extra-low voltage circuits of devices containing voltages and circuits of more
than 50 volts (e.g., the mains connection) are connected to Bosch Rexroth
products, the connected extra-low voltage circuits must comply with the re‐
quirements for PELV ("Protective Extra-Low Voltage").
● After switching chokes, supply units and drive controllers off, wait 15 mi‐
nutes to allow them to cool down before touching them.
● Wear safety gloves or do not work at hot surfaces.
● For certain applications, and in accordance with the respective safety reg‐
ulations, the manufacturer of the machine or installation must take meas‐
ures to avoid injuries caused by burns in the final application. These
measures can be, for example: Warnings at the machine or installation,
guards (shieldings or barriers) or safety instructions in the application
documentation.
DANGER
In case of non-compliance with this safety instruction, death or serious injury
will occur.
WARNING
In case of non-compliance with this safety instruction, death or serious injury
could occur.
CAUTION
In case of non-compliance with this safety instruction, minor or moderate injury
could occur.
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 19/69
Rexroth IndraControl L25
NOTICE
In case of non-compliance with this safety instruction, property damage could
occur.
20/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 21/69
Rexroth IndraControl L25
Technical Data
4 Technical Data
4.1 Equipment
Processor Renesas SH 7785
RAM Min. 128 MByte DRAM and min. 256 kByte RDS1)
Clock frequency 576 MHz (CPU CLK)
Interfaces:
Interface to function ● Bosch Rexroth PC104Plus
modules
Interface to I/O terminals ● Rexroth Inline interface
Communication interfa‐ ● 1 × Ethernet connection (RJ 45, 10/100 base-T)
ces ● 1 × SERCOS III Master/Slave interface
Ready contact ● 1 single-pin ready contact
Nominal value DC 24 V
Umin 19.2 V
Technical Data
for 10 ... 57 Hz
Acceleration: 1 g
for 57 to 150 Hz
acc. to EN 60068-2-6
Standard Meaning
Technical Data
Standard Meaning
DIN EN 60 529 Degrees of protection (including housings and installa‐
tion compartments)
UL 508 Industrial Control Equipment
Systems with the IndraControl L25 that are used in residential areas
(housing, business and commercial areas as well as small-sized
enterprises) require a single approval by an authority or a testing
agency. In Germany, such single approvals are issued by the ”Reg‐
ulierungsbehörde für Telekommunikation und Post (RegTP)” (Ger‐
man Regulatory Authority for Telecommunications and Posts).
The devices of the IndraControl L25 product family are certificated according
to
● UL508 (Industrial Control Equipment) and
● C22.2 no. 142-M1987 (CSA)
UL file no. E210730
However, there can be combinations or stages of expansions with limited or
missing certification. Therefore verify the certification by using the UL label on
the device.
Technical Data
For this reason, before using the respective material a compatibility test has to
be carried out for new materials (e. g. lubricants and cleaning agents) and our
housing or our housing materials.
Dimensions
5 Dimensions
5.1 General Information
All values in the illustrations are given in mm.
Dimensions
Fig.5-3: Left view (the cut-out for the top-hat rail is located in the center)
30 mm
30 mm
30 mm
100 mm
Fig.5-4: Minimum distances for the circulation of surrounding air
● Additionally, provide sufficient clearance for mounting, dismounting, con‐
nector and cable length.
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 27/69
Rexroth IndraControl L25
The reset button can only be actuated with a sharp tool (e. g. tip of a pencil).
LED The LED serves for diagnostics and status display.
The states indicated by the LED depend on the firmware used and are included
in the description of the particular system.
28/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 29/69
Rexroth IndraControl L25
SERCOS
X7E1
X7E2
X7E5
X2R
1 2
① Slot for Compact Flash card
② PWR IN voltage supply
Fig.7-1: IndraControl L25 connections, CML...3N... device variant
X7E3
ETH
L
X7E4
X7E5
PROFIBUS DP
9
X2R
1
X7P
1 2
① Slot for Compact Flash card
② PWR IN voltage supply
Fig.7-2: IndraControl L25 connections, CML...PN... device variant
For connecting the operating voltages only the power connector (R-
IB IL SCN-PWR IN-PWR) may be used. The connector is contained
in the scope of delivery. TheR-IB IL SCN-PWR IN-CP connector,
which is available for other power terminals, is not allowed for the
IndraControl L25!
LED Meaning
"US"
US
UM
UM UM
The segment circuit with the segment voltage US starts at the IndraCon‐
trol L25 or a supply terminal (power terminal or segment terminal) and is
supplied through all following terminals up to the next supply terminal.
Function Several segment terminals can be used within a main circuit and thereby seg‐
ment the main circuit. The reference to ground is the same as that of the main
circuit. Thus, different fused electric circuits can be implemented within the sta‐
tion without any external cross-wiring.
Voltage The voltage in the segment circuit is DC 24 V.
Current carrying capacity The maximum current carrying capacity is 8 A (total current with the main cir‐
cuit). If the limit value for a voltage jumper UM is reached (total current of US
and UM), a new power terminal must be used.
Generation US The segment voltage US can be provided in various ways:
1. The segment voltage can be fed at the IndraControl L25 or at a power
terminal.
2. The segment voltage can be tapped from the main voltage, either at the
IndraControl L25 or at a power terminal using a jumper or a switch.
3. A segment terminal with fuse can be used. In this terminal, the segment
voltage is automatically tapped from the main voltage.
US
UM
US UM
When designing the station, do observe that the total current in the
segment circuit US and in the main circuit UM must not exceed 8 A.
US
UM
ULS
7.3 Interfaces
7.3.1 Ethernet Interfaces
X7E5 Ethernet network connection Connector X7E5 can be used to connect the IndraControl L25 to an Ethernet
network.
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 37/69
Rexroth IndraControl L25
The connection requirements defined for 100BaseT in IEEE 802.3 are appli‐
cable.
Ethernet
max. 100 m
Ethernet RJ45 2
ToZum
the Network
Netzwerk
L 3
8
4
5
1 6
S
7
8
LED Status
Ethernet
max. 100 m
Ethernet RJ45 2
ToZum
the Network
Netzwerk
L 3
8
4
5
1 6
S
7
8
LED Status
X7P
1
2
5 1 RxD/TxD-P 3
CNTR-T 4
DGND 5
VP 100 mA 6
7
9 6 RxD/TxD-N 8
CNTR-N 9
Ethernet
max. 100 m
Ethernet RJ45 2
ToZum
the Network
Netzwerk
L 3
8
4
5
1 6
S
7
8
LED Status
Switching capacity DC 60 V, 1 A
UL rating AC/DC 30 V,1 A, resistive
Dropout time 0.3 ms
Bounce time None
Watchdog time (analog watchdog only) 50 ms ± 25 %
Ensure that the top-hat rail is attached such that it provides appro‐
priate rigidity.
In addition to its holding function, this top-hat rail also assumes the
function of ground connection and heat removal. For that reason,
the top-hat rail must be connected to a functional earth ground.
Furthermore, the top-hat rail is provided as heat sink in connection with the
metal bottom frame of the IndraControl L25.
Fixing the end clamp / CLIPFIX Finally, attach end clamps to both sides of the Rexroth Inline station. These end
clamps ensure that the station is securely mounted to the top-hat rail and are
also provided as lateral termination elements. These end clamps are included
in the scope of delivery of the IndraControl L25.
If any of the terminal is provided with more than one connector, all
these connectors have to be removed from the terminal.
Fig.8-1: The first Rexroth Inline terminal has to be removed before dismounting
the IndraControl L25.
Removing the IndraControl L25 Now the IndraControl L25 can be removed from the top-hat rail by loosening
from the top-hat rail the fixing claw on the bottom side by means of a tool (screwdriver) and pulling
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 45/69
Rexroth IndraControl L25
the IndraControl L25 off the top-hat rail from below, tilting it and removing it
upwards.
The keyways provided in the terminal are not continued in the con‐
nector. A terminal can only be latched on, if there is no connector
to the left of it. If necessary, the connector has to be removed.
46/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
A B
C D
If any of the terminal is provided with more than one connector, all
these connectors have to be removed. The following sections de‐
scribe how to remove a 2-slot terminal.
Pry out the connector of the terminal to be removed by pressing on the rear
connector shaft latch (A2 in figure A).
● Remove the connector (figure B).
● Remove the adjacent connectors of the neighboring terminals (figure C).
This ensures that the feathers of the voltage jumpers and of the keyway/
feather key connection are prevented from damage. Moreover, the termi‐
nal can be accessed more easily.
● Actuate the release mechanism (D1 in figure D) and remove the terminal
perpendicularly to the top-hat rail (D2 in figure D). If you have failed to
loosen the connector of the neighboring terminal to the left, this connector
now comes loose to protect the feathers of the voltage routing and the
keyway/feather key connection.
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 47/69
Rexroth IndraControl L25
When replacing the fuse, please observe the following instructions on the safety
of your health and the protection of your station!
1. Always use the screwdriver with care to prevent yourself and any other
person from being injured
2. Pry out the fuse at the metal contact. Do not pry the fuse out at the glass
body to prevent the latter from being broken.
3. Pry out the fuse carefully on one side and then remove it by hand. Take
care not to drop the fuse into your station.
Proceed as follows to replace the fuse. Also see the illustrations in fig. 8-4
"Fuse replacement" on page 48:
● Swing up the fuse lever (A)
● Put a screwdriver behind a metal contact of the fuse (B)
● Carefully pry out the metal contact of the fuse (C)
● Remove the fuse by hand (D)
● Latch in the new fuse (E)
● Press the fuse lever down again until it clicks into place (F)
48/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
A B
C D
E F
L1
L2
L3
N
PE
Overvoltage category III
400 V
Power
S
supply
SERCOS
X7E1
unit1
S1 L
Reset Stop
1.1 2.1
Overvoltage L S
ETH
X7E2
category II 1.2 2.2
S
24V X7E3
Ready
1.4 2.4
FE
US
ULS GND UM
Overvoltage Trans- L
category III, 400 V former
S
X7E1
Power 230 V voltage
supply
unit 1 for programming S1
Reset Stop
L
device, etc.
+ L S
1.1 2.1
Overvoltage
ETH
X7E2
Overvoltage category III 400 V S 1.2 2.2
X7E3
category II, 24 V
Ready
Power Dist.
supply X2R
1.3 2.3
unit 3
1.4 2.4
Overvoltage
category I, 24 V
FE
2 2
US
ULS GND
UM
X7E1
24 V 24 V S1 L
Reset Stop
0V + 0V + L S
1.1 2.1
ETH
X7E2
S 1.2 2.2
X7E3
Ready
Disconnectable
connections 1.4 2.4
FE
US
ULS GND UM
L1
L2
L3
N
PE
S
SERCOS
24 V 24 V X7E1
S1 L
Reset Stop
0V + 0V + 1.1 2.1
L S
ETH
X7E2
E1 S
X7E3
1.2 2.2
Ready
Dist. X2R 1.3 2.3
E2
1.4 2.4
FE
US
ULS GND UM
8.3.5 Grounding
The line shield must be applied in the bus connector. In case of installation in
the control cabinet, the line shield of the connected PROFIBUS line must be
connected to a shield bus using cable clips, if possible directly behind the cable
bushing. Use an appropriate shield terminal.
8.4 Maintenance
Regular maintenance Include the following measures in the maintenance schedule:
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 55/69
Rexroth IndraControl L25
● At least once a year, check all plug and terminal connections of the com‐
ponents regarding proper tightness and possible damage. Verify that lines
and cables are not broken or squeezed. Replace damaged parts imme‐
diately.
LC display A fading readability of the display may cause that the display has to be ex‐
changed. For further information please contact the Bosch Rexroth Service.
56/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 57/69
Rexroth IndraControl L25
9.2 Disposal
Return of Products Our products can be returned to our premises free of charge for disposal. It is
a precondition, however, that the products are free of oil, grease or other dirt.
Furthermore, the products returned for disposal must not contain any undue
foreign material or foreign components.
Send the products ”free domicile” to the following address:
Bosch Rexroth AG
Electric Drives and Controls
Buergermeister-Dr.-Nebel-Strasse 2
97816 Lohr am Main, Germany
Packaging The packaging materials consist of cardboard, wood and polystyrene. These
materials can be recycled anywhere without any problem.
For ecological reasons, please refrain from returning the empty packages to
us.
Batteries and Accumulators Batteries and accumulators can be labeled with this symbol.
The symbol indicating "separate collection" for all batteries and accu‐
mulators is the crossed-out wheeled bin.
The end user within the EU is legally obligated to return used batteries. Outside
the validity of the EU Directive 2006/66/EC keep the stipulated directives.
Used batteries can contain hazardous substances, which can harm the envi‐
ronment or the people´s health when they are improper stored or disposed of.
After use, the batteries or accumulators contained in Rexroth products have to
be properly disposed of according to the country-specific collection.
Recycling Most of the products can be recycled due to their high content of metal. In order
to recycle the metal in the best possible way, the products must be disassem‐
bled into individual modules.
58/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
Ordering Information
10 Ordering Information
10.1 Type Designation Code
10.1.1 General Information
The IndraControl L25 is available in various versions according to the following
type codes.
Product
Main unit . . . . = CM
Housing design
Inline. . . . . . . . . . . . = L
Line
SH4 . . . . . . . . . . . . . . = 25
Design
1......................=1
Communication interface
Interface 1 Abbr. Interface 2 Abbr.
column column
9 10
Not equipped N Not equipped N
SERCOS III 3 - -
PROFIBUS
Profibus P - -
System configuration
DRAM (MB) Abbr. NvRAM (kB) Abbr. SRAM (MB) Abbr.
column column column
12 13 14
128 4 Without 0 Without 0
Fan
Without . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . = N
Additional design
None. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . = NNNN
With connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . = NNC1
Firmware
Without firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . = NW
Ordering Information
10.2 Accessories
10.2.1 Spare Part (Power Connector)
General Information
The connector for connecting the operating voltage is included in the scope of
delivery. As spare part the following connector is available:
EMI shielding If the "programmable limit switch" function module (CFL01.1-N1 R911170012)
is used in noisy environment, this EMI shielding is to be mounted. This recom‐
mendation applies to programmable limit switch modules that are plugged in
the 3rd or 4th slot at the left side of the function module bus.
Ordering Information
Interface Cables
Ethernet interface Order code Parts number Description
Ordering Information
Ordering Information
Service Hotline
Helpdesk
Worldwide
Phone +49 (0) 9352 40 50 60 Outwith Germany please con‐
tact our sales/service office in
Fax +49 (0) 9352 40 49 41
your area first.
Preparing Information For quick and efficient help please have the following information ready:
● Detailed description of the fault and the circumstances
● Information on the type plate of the affected products, especially type co‐
des and serial numbers
● Your phone, fax numbers and e-mail address so we can contact you in
case of questions.
66/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 67/69
Rexroth IndraControl L25
Index
Index
A F
Accessories......................................................... 60 Fuse.................................................................... 52
Accumulators...................................................... 57 Fuse replacement............................................... 47
Ambient conditions
Ambient conditions ....................................... 22
Analog supply (UANA)........................................... 36
G
Generation UM..................................................... 34
Appropriate use
Introduction .................................................... 7 Generation US..................................................... 35
Use ................................................................. 7 Grounding........................................................... 52
Grounding
............................................................................ 53
B
Batteries.............................................................. 57
H
Hazardous substances....................................... 57
C Housing dimensions............................................ 25
Cap for CF slot.................................................... 63
Compact Flash card............................................ 41
Compatibility test................................................. 23 I
Connections........................................................ 29 Inappropriate use.................................................. 8
Overview ...................................................... 29 Consequences, exclusion of liability .............. 7
Voltage supply .............................................. 31 Inline bus............................................................. 41
Contained substances Inline supply and analog circuit........................... 36
see "Significant components" ....................... 57 Inline terminals
CSA certified....................................................... 23 Demounting .................................................. 46
Fuse replacement ........................................ 47
Mounting ...................................................... 45
D Removing a terminal .................................... 47
Device variants..................................................... 5 Installation........................................................... 43
Dimensioning the voltage supply........................ 52 Electric ......................................................... 48
Dimensions......................................................... 25 Installation, mechanical....................................... 43
Bottom view .................................................. 25 Installation notes................................................. 26
Front view ..................................................... 25 Installing Inline terminals..................................... 45
Side view ...................................................... 26 Instructions on use................................................ 7
Dismounting........................................................ 44 Interface cables................................................... 61
Display................................................................ 27 Interfaces...................................................... 29, 36
Display and operating components..................... 27 Ethernet X7E3, X7E4 ................................... 37
Disposal.............................................................. 57 Overview ...................................................... 29
Documentation...................................................... 6 PROFIBUS ................................................... 38
Drive system......................................................... 9 SERCOS III .................................................. 39
Internally generated voltages.............................. 36
E
Electrical Installation........................................... 48 K
Electrical isolation......................................... 49, 50 Keys.................................................................... 27
Electric drive system............................................. 9
EMI shielding...................................................... 60
Environmental protection.................................... 57 L
Ethernet interface.......................................... 36, 61 LC display........................................................... 55
Ethernet X7E3, X7E4.......................................... 37 Logic circuit......................................................... 36
F M
Front view........................................................... 25 Main circuit.......................................................... 34
Functional earth ground...................................... 53 Main switches..................................................... 52
Function module connector................................. 41 Maintenance................................................. 43, 54
Function modules................................................ 60 Mechanical installation........................................ 43
Memory card....................................................... 41
68/69 Bosch Rexroth AG DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
Index
M S
Minimum distances............................................. 26 Shield system...................................................... 53
Mounting............................................................. 43 Side view............................................................. 26
Significant components....................................... 57
Spare part (connector)........................................ 60
O Standards............................................................ 22
Operating components........................................ 27 Stop LED............................................................. 27
Operating keys.................................................... 27 Support
Ordering information........................................... 59 see Service Hotline ...................................... 65
System presentation............................................. 5
P Brief description ............................................. 5
Packaging........................................................... 57 View ............................................................... 5
PELV................................................................... 14
Potential equalization.......................................... 53 T
Power connector................................................. 60 Technical data............................................... 21, 22
Power supply unit................................................ 49 Equipment .................................................... 21
Production processes......................................... 57 Used standards ............................................ 22
PROFIBUS cable Voltage supply .............................................. 21
Shielding ...................................................... 53 Tension spring connection point......................... 54
PROFIBUS DP.................................................... 61 Tools for PROFIBUS cable................................. 63
PROFIBUS DP connection................................. 38 Type designation code........................................ 59
Programming device........................................... 52
Protective conductor........................................... 50
Protective extra-low voltage................................ 14 U
UL and CSA certified.......................................... 23
Unshielded lines.................................................. 54
R Used standards................................................... 22
Ready contact..................................................... 40
Recycling............................................................ 57
Reference conductor........................................... 50 V
Reset Button....................................................... 27 View CML...3N... device variant.......................... 30
Return of products.............................................. 57 View CML...PN... device variant......................... 31
Rexroth Inline terminals...................................... 60 Voltage jumper FE.............................................. 53
Voltages, internally.............................................. 36
Voltage supply.............................................. 21, 31
S 24 V .............................................................. 49
Safety instructions for electric drives and con‐ Dimensioning ............................................... 52
trols....................................................................... 9 Voltage supply ULS........................................ 33, 34
Segment circuit................................................... 35
Segment circuit US.............................................. 34
SERCOS III......................................................... 39 W
SERCOS III Ethernet.......................................... 62 Wear parts.......................................................... 24
Shielding the PROFIBUS cabIe.......................... 53
DOK-CONTRL-IC*L25*****-PR03-EN-P Bosch Rexroth AG 69/69
Rexroth IndraControl L25
Notes
Bosch Rexroth AG
Electric Drives and Controls
P.O. Box 13 57
97803 Lohr, Germany
Bgm.-Dr.-Nebel-Str. 2
97816 Lohr, Germany
Tel. +49 (0)93 52-40-0
Fax +49 (0)93 52-48 85
www.boschrexroth.com/electrics
Printed in Germany
R911328474 DOK-CONTRL-IC*L25*****-PR03-EN-P