Electrical Thumb Rules You MUST Follow (1)

By jiguparmar    August, 23rd 2013   Save to PDF ♛


Electrical Thumb Rules You MUST Follow (Part 1)

Electrical Thumb Rules For:


Cable Capacity
Current Capacity of Equipment
Earthing Resistance
Minimum Bending Radius
Insulation Resistance
Lighting Arrestor
Transformer
Diesel Generator
Current Transformer
Quick Electrical Calculation

Cable Capacity

For Cu Wire Current Capacity (Up to 30 Sq.mm) = 6X Size of Wire in Sq.mm
Ex. For 2.5 Sq.mm = 6×2.5 = 15 Amp, For 1 Sq.mm = 6×1 = 6 Amp, For 1.5
Sq.mm = 6×1.5 = 9 Amp
For Cable Current Capacity = 4X Size of Cable in Sq.mm, Ex. For 2.5 Sq.mm =
4×2.5 = 9 Amp.
Nomenclature for cable Rating = Uo/U
where Uo = Phase­Ground Voltage, U = Phase­Phase Voltage, Um = Highest
Permissible Voltage

Go to Content ↑
Current Capacity of Equipment

1 Phase Motor draws Current = 7Amp per HP.
3 Phase Motor draws Current = 1.25Amp per HP.
Full Load Current of 3 Phase Motor = HPx1.5
Full Load Current of 1 Phase Motor = HPx6
No Load Current of 3 Phase Motor = 30% of FLC
KW Rating of Motor = HPx0.75
Full Load Current of equipment = 1.39xKVA (for 3 Phase 415Volt)
Full Load Current of equipment = 1.74xKw (for 3 Phase 415Volt)

Go to Content ↑

Earthing Resistance

Earthing Resistance for Single Pit = 5Ω, Earthing Grid = 0.5Ω
As per NEC 1985 Earthing Resistance should be < 5Ω.
Voltage between Neutral and Earth <= 2 Volt
Resistance between Neutral and Earth <= 1Ω
Creepage Distance = 18 to 22mm/KV (Moderate Polluted Air) or
Creepage Distance = 25 to 33mm/KV (Highly Polluted Air)

Go to Content ↑

Minimum Bending Radius

Minimum Bending Radius for LT Power Cable = 12 x Dia of Cable.
Minimum Bending Radius for HT Power Cable = 20 x Dia of Cable.
Minimum Bending Radius for Control Cable = 10 x Dia of Cable.

Go to Content ↑

Insulation Resistance

Insulation Resistance Value for Rotating Machine = (KV+1) MΩ.
Insulation Resistance Value for Motor (IS 732) = ((20xVoltage (L­L)) / (1000+
(2xKW)).
Insulation Resistance Value for Equipment (<1KV) = Minimum 1 MΩ.
Insulation Resistance Value for Equipment (>1KV) = KV 1 MΩ per 1KV.
Insulation Resistance Value for Panel = 2 x KV rating of the panel.
Min Insulation Resistance Value (Domestic) = 50 MΩ / No of Points. (All
Electrical Points with Electrical fitting & Plugs). Should be less than 0.5 MΩ
Min Insulation Resistance Value (Commercial) = 100 MΩ / No of Points. (All
Electrical Points without fitting & Plugs).Should be less than 0.5 MΩ.
Test Voltage (A.C) for Meggering = (2X Name Plate Voltage) +1000
Test Voltage (D.C) for Meggering = (2X Name Plate Voltage).
Submersible Pump Take 0.4 KWH of extra Energy at 1 meter drop of Water.

Go to Content ↑

Lighting Arrestor

Arrestor have Two Rating:

1.  MCOV=Max. Continuous Line to Ground Operating Voltage.
2.  Duty Cycle Voltage. (Duty Cycle Voltage > MCOV).

Go to Content ↑

Transformer

Current Rating of Transformer = KVA x 1.4
Short Circuit Current of T.C /Generator = Current Rating / % Impedance
No Load Current of Transformer =< 2% of Transformer Rated current
Capacitor Current (Ic) = KVAR / 1.732xVolt (Phase­Phase)
Typically the local utility provides transformers rated up to 500kVA  For maximum
connected load of 99kW,
Typically the local utility provides transformers rated up to 1250kVA  For maximum
connected load of 150kW.
The diversity they would apply to apartments is around 60%
Maximum HT (11kV) connected load will be around 4.5MVA per circuit.
4No. earth pits per transformer (2No. for body and 2No. for neutral earthing),
Clearances, approx.1000mm around TC allow for transformer movement for
replacement.

Go to Content ↑
Diesel Generator

Diesel Generator Set Produces = 3.87 Units (KWH) in 1 Litter of Diesel.
Requirement Area of Diesel Generator = for 25KW to 48KW = 56 Sq.meter,
100KW = 65 Sq.meter.
DG less than or equal to 1000kVA must be in a canopy.
DG greater 1000kVA can either be in a canopy or skid mounted in an
acoustically treated room
DG noise levels to be less than 75dBA at 1 meter.
DG fuel storage tanks should be a maximum of 990 Litter per unit. Storage
tanks above this level will trigger more stringent explosion protection provision.

Go to Content ↑

Current Transformer

Nomenclature of CT:

Ratio: input / output current ratio
Burden (VA): total burden including pilot wires. (2.5, 5, 10, 15 and 30VA.)
Class: Accuracy required for operation (Metering: 0.2, 0.5, 1 or 3, Protection: 5,
10, 15, 20, 30).
Accuracy Limit Factor:
Nomenclature of CT: Ratio, VA Burden, Accuracy Class, Accuracy Limit
Factor.Example: 1600/5, 15VA 5P10   (Ratio: 1600/5, Burden: 15VA, Accuracy
Class: 5P, ALF: 10)
As per IEEE Metering CT: 0.3B0.1 rated Metering CT is accu rate to 0.3 percent
if the connected secondary burden if imped ance does not exceed 0.1 ohms.
As per IEEE Relaying (Protection) CT: 2.5C100 Relaying CT is accurate within
2.5 percent if the secondary burden is less than 1.0 ohm (100 volts/100A).

Go to Content ↑

Quick Electrical Calculation


1HP = 0.746KW Star Connection
1KW = 1.36HP Line Voltage = √3 Phase
Voltage
1Watt = 0.846 Kla/Hr Line Current = Phase
Current
1Watt = 3.41 BTU/Hr Delta Connection
1KWH = 3.6 MJ Line Voltage = Phase
Voltage
1Cal = 4.186 J Line Current = √3 Phase
Current
1Tone = 3530 BTU
85 Sq.ft Floor Area = 1200
BTU
1Kcal = 4186 Joule
1KWH = 860 Kcal
1Cal = 4.183 Joule

Go to Content ↑

Related EEP's content with sponsored links


Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides,
research studies and much more! It helps you to shape up your technical skills in
your everyday life as an electrical engineer.

MORE INFORMATION

Jignesh Parmar

Jignesh Parmar has completed M.Tech (Power System
Control), B.E (Electrical). He is member of Institution of
Engineers (MIE), India. He has more than 20 years experience
in transmission & distribution­energy theft detection and
maintenance electrical projects.

117 Comments

Hitendra Marge
DEC 06, 2021

Dear sir , need overload current carrying capacity for MV cable with
trefoil and flat touching condition with different hours.
Generally 1 /2/3/4/6/8/10/12/24 hour run with 60% / 75%/90% & 30%
overload condition with respectively above mentioned time durations
so please how can calculate in easy format.

Reply
V Anguchamy
NOV 18, 2021

Need Cable current carrying capacity for 3 Phase Cable

Reply

Shah
JAN 18, 2021

can we use 2 x 16sq.mm x 4core and 1 x 10sq.mm x 4core power
cable instead of 1 x 35sq.mm x 4core cable for the connectivity of
Diesel Genset (60 KVA) to ATS panel 20 feet apart.
Please advice…

Reply

Ozigi
JAN 20, 2021

2x16mm2 4­core cable which is 2 run of 16mm2 4­core cable is
more than enough to connect 60kVA generator to ATS panel
giving that the generator current = 86.6A

Reply

SHIVAPRAKASH
MAR 18, 2021

We Have a powerloom factory…with each one has 330 watts 3
phase induction motor voltage ­220 freq­50hz
we have used 4 sq mm for mainline and 2.5sqmm for each motor
for 12 motors.
Can We Connect that same 4 sq.mm for another 12 motors or we
have to add 4 sq mm wire…Help me with your knowledge

Reply
Prem Singh
MAR 05, 2021

YES.
We bundled conductors instead of single conductors for ac
transmission to reduce skin effect.
If you provide two cables 4Cx35 Sq mm for one cable 4Cx35 Sq.
mm then the system is sufficient and addition of 4Cx10 Sq mm will
make it extra strong.

Reply

Shahzad
DEC 12, 2021

Yes you can

Reply

« Older Comments

Leave a Comment

Tell us what you're thinking... we care about your opinion! Please keep in mind
that comments are moderated and rel="nofollow" is in use. So, please do not use a
spammy keyword or a domain as your name, or it will be deleted. Let's have a
professional and meaningful conversation instead. Thanks for dropping by!

YO UR  REAL  NAME  *

EMAIL  ADDRESS  *
Pr ov e  that  y ou  ar e  not  R2D2.  Solv e  s ome  math:

Ninety Nine  ∕     =  Eleven

SUBMIT COMMENT

© 2021 EEP ­ Electrical Engineering Portal. All Rights Reserved | Privacy Policy | Terms and Conditions

You might also like