Servo Unit Asu363-D-Vvv
Servo Unit Asu363-D-Vvv
Servo Unit Asu363-D-Vvv
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 2/24
This servo unit is applicable for control of a variable capacity pump working into a hydraulic motor circuit and
controlled by a proportional valve. Control current is in the range between 100 mA and 500 mA.
Pump stroke feedback is required in form of an RVDT sensor, energized from the servo unit with an AC signal:
6Vrms, 2.5 kHz. A stroke feedback circuits is included, utilised both for control and for hydraulic lock
detection.
The servo unit is designed for full 360 deg follow-up and non follow-up control.
Two or three servo units can be operated on the same Azimuth device, steered from the same wheel, autopilot
or NFU device. A servo to servo interlock circuit ensures constant servo bandwidth, independent of the number
of running pumps.
Supply voltage: 115VAC, 230VAC or 440VAC as specified in the part number as “vvv” Volt AC, derived
from the motor starter of the master pump.
Each servo includes the following state and functionality monitoring circuits:
1. Local or Remote operation selected. (Dry contact)
2. Follow-Up mode or Non Follow-Up mode selected. (Dry contact).
3. Output of given follow-up order (10V*sine and 10V*cos to order angle)
4. Servo power failure. All power supply circuits monitored. (Dry contact)
5. Hydraulick lock alarm sensing. (Dry contact).
6. Order and feedback core monitoring. (Alarm and zeroing of stroke signal in case of broken wire.)
7. Servo error monitoring by the MPF11 microcomputer. (Se details page 14.)
Each ASU-servo unit requires two azimuth feedback signals. Derived from 2 RFB360 feedback units.
Opens at FAIL
Opens at FAIL
NMEA mess.
Follow-Up
System Fail
once pr sec
Hydr.Lock
sin/cos
Select
Order
Order
NFU
OK P1
OK
+ +
Steer Follow
F
Failure UP
- Detect - SERVO
SOLENOID
HLA
FAILURE
ORDERS
MPF11 with
VALVE
NMEA to VDR +
-
Follow-Up
Select
sin/cos /P1
STG ACTUATOR
Start Order to P2
Case Failure in P1
ASU363E1.DWG, 2005-04-08
sin/cos /P1
AZIPOD
SHAFT
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 3/24
1. Control Principle.
The steering gear is an electric hydraulic type with minimum two independent hydraulic power units. The
hydraulic flow to the steering gear cylinders is controlled by variable capacity pumps controlled by a
proportional type hydraulic valve. The pumps can operate one at a time or two in parallel. The maximum
steering speed doubles when two pumps are running.
The pump is provided with a stroke feedback transmitter of an RVDT type. The stroke signal is used for control
purposes and for hydraulic lock alarm purposes. Hydraulic Lock alarm signal is given in case of large error in
the stroke servo loop. (I.E. Stroke order is different from actual stroke during more than a few seconds).
With zero control signal the pump is in the zero postion and the oil flow is zero. The azipod retains its position
whereever left.
When a control signal is applied the pump is stroked and the oil will flow with a rate corresponding to the
control signal. The azipod will move with a steering speed proportional to the flow. Reversing the control
signal will make the azipod move to the other side.
BOTTOM
VIEW:
250
15
4x 1O FRONT VIEW:
STEERING
CONTROL
UNIT
ASU
PUSH BUTTONS
500
560
530
CONTROL
BUTTONS
PORT STBD
LOCAL NFU
CONTROL
A/S
TYPE: NO:
MADE IN DENMARK
GROUND 376
SCREW
500
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 4/24
1. Both Follow-Up and Non Follow-Up steering are available, electronically selectable (FUSEL
relay=Follow-up select). NFU and FU have independent output circuits. Separate control lines
to the bridge for Follow-Up and NFU.
2. Electronically selectable limit switch function providing limited angle at cruising condition.
3. Remote bridge control can be disconnected by a switch. Activating a bridge alarm and leaving
the control as: LOCAL NFU push-button steering.
5. Built in Hydraulic Lock Alarm circuit activated when the valve order differs from obtained
pump position. Active both in FU and NFU modes.
6. Built in stabilised power supplies for transmitter and feedback potmeters. Built in TEST wheel
for easy setting up and diagnostics.
7. Circuits for control valve linearisation and a pump-stroke closed loop servo.
10. The unit is built for steering gear room installation, and is supplied with 1-phase
115/230/440VAC as ordered. The supply is derived from the motor starter of the pump which
the servo unit controls, being energised only when the pump is running.
12. Built in LED diode lamps for easy power supply and condition monitoring.
13. Built in core monitoring of order signals and feedback signals. The stroke order signal to the
pump(s) can be zeroed in case a failure is detected. (This will be the default act. It is possible to
inhibit this function by a pin jumper). This failure results in a SERVO FAULT alarm.
14. General alarm contact for SERVO FAULT controlled from the monitoring microprocessor
circuit. Seperate alarm contacts for HYDR. LOCK, POWER FAILURE and LOCAL
CONTROL directly from the analog monitoring circuits.
16. ASU363 SPECIFIC: Two feedbacks are used: One for Servo-action and one for failure
detection. This is to ensure correct “Fail-to-Safe” function also with failures to the feedback
belts or chains and linkages.
17. Halogene free cores. Phoenix type of terminals with spring-cage connections.
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 5/24
A position servo with the vector angle difference circuit providing SINE(order-actual) to the
proportional band amplifier having the more pumps interlock circuit with gain reduction, the
stroke ramp circuit and the TESTWHEEL with associated selection pin jumpers.The print also
contains the stabilised +/-15VDC power supply for the system and +/- 10VDC reference supply
for the order and feedback potmeters. Further the PCB also hold the core monitoring circuits.
A stroke servo and power amplifier with the associated controls for valve linearisation and
stroke servo adjustment. Also included are the RVDT oscillator and demodulator circuits for the
stroke feedback transmitters together with the power amplifier for FU- and NFU operation, a
24VDC auxiliary supply for the LOCAL, REMOTE, NFU, FUSEL and LIMIT SWITCH
relays.The print also contains the power supply supervision and the hydraulic lock alarm circuit.
A microprocessor board fitted with 9 DI, 3 DO, 4 AI & 1 serial port, (RS422).
The DI (digital inputs) read the servo operating mode and the 4 AI (analog inputs) are used to
compare the order and an independent reference feedback angle, both represented with their
sines and cosines. The DO (digital outputs) are used to energize the Follow-Up Select relay
plus a Servo OK relay. The third DO is connected to the other servo-unit and is used as a
communication link between the two servo-units.
In case of steering failure the MPF report an alarm to the bridge and changes the dervo mode to
NFU while it at the same time orders the second, Stand-By, pump started.
LOCAL/REMOTE switch for motor starter control with local start and stop push buttons.
3. Interface to ASU363-D-vvv.
Motor Starter
Power supply from the motor starter is 115/230/380/415/440VAC as ordered, consumption max.
100VA. A downstream supply available only when the pump is running.
Local/Remote selection & START / STOP from the ASU.front panel push-buttons.
Steering gear.
Control valve supply: 2 valve coils. (Port and Stbd independent). Max current capability approx.
0.9A. Adjustable current limitation. Coil resistance approx 41 ohm.
Steering Angle feedback unit: Supply +/-10.00VDC and 0VDC, Nom. consumption 10 mA.
Feedback signal 10V X SINE(Angle), 10V X COSINE(Angle).
Reference Angle feedback unit: Supply +/-10.00VDC and 0VDC, Nom. consumption 10 mA.
Feedback signal 10V X SINE(Angle), 10V X COSINE(Angle).
RVDT stroke excite voltage: 6V RMS, 2.5kHz, max. 120mA. Coil resistance: 85 ohm.
RVDT stroke detect: 265 mVRMS at full stroke. Coil resistance 440 Ohms (both secondaries in
series).
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 6/24
Limit switches: Galvanically isolated NO switches closing at limit. Contact rating 30VDC 100
mA. Or Inductive three terminal NPN type proximity switches.
FAST contact. Galvanically free contact for ordering the steering gear FAST mode.
Simultaneous activation of both P1 and P2 FAST contacts are required to bring the the steering
gear in FAST mode. Contact rating 50VDC, 1A.
Contacts for valve/pump more than 50% activated. Closed at activation. 24Vdc supply 5mA
contact current.( Option)
FUSEL: closed contact when follow up control is required. Contact rating 30VDC 100 mA.
NFU ORDER: Closed contacts for port or stbd orders. Contact rating 30VDC 100 mA.
FAST: closed contact to select FAST mode of the steering gear. Contact closes to PG ( power
ground ). Contact rating 30VDC 100 mA.
MUTE: closed contact to select zero stroke operation during change-over between NORMAL
and FAST mode of the steering gear. Contact closes to PG ( power ground ). Contact rating
30VDC 100 mA.
Reference supply for wheel steering order potmeters +/- 10.00VDC, max. consumption 150 mA.
24VDC. Supply used for internal and external for relay circuits. Max. external consumption
300 mA . Also available as 24V & REMOTE .i.e. 24VDC only present when the pump is
running in REMOTE.
Alarm system.
1 Servo System OK contact opening at servo failure. (Broken wire, power failure and
excessive servo error). Galvanically isolated. Contact rating 50VDC, 50 mA.
Power OK contact opening at power fail. Galvanically isolated. Contact rating 50VDC, 50 mA.
Stroke Servo OK contact opening at Hydraulic Lock. Galvanically isolated. Contact rating
50VDC, 50 mA.
Other servos.
Pump running interlock: one short circuit proof output supplying one opto isolated input in
the other servo. Current approx. 5 mA.
Servo OK info is exchanged between the 2 MPF11-modules in ASU363 servo units.
VDR:
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 7/24
W3
Note: X2-terminals are located on the PCB
TESTWHEEL VECTOR
PROPORTIONAL STROKE
?
SIGNAL
NEG/STBD
SIGNAL REFERENCE X2-12 SUPERVISION
CIRCUIT
TESTWHEEL
SG
LARGE
SMALL
+15V
+10V TP17 +15V
+10V
X2-1 +10V
SUPPLY FOR TP4
?
X2-2
STABILIZED +15V -15V +15V -15V +15V -15V
FEEDBACK- TP16 TP10
AND 4
TP3
X2-4
?
?
REFERENCE
ORDER- SG SG TESTWHEEL SG
TP15
X2-5 SUPPLY
POTMETERS
?
X2-6 -10V
X2-27
X2-28
X2-13
X2-15
X2-18
X2-20
X2-23
X2-19
X2-22
X2-24
X2-25
X2-26
X2-21
X2-17
-10V
-15V
-10V
-15V
The steering order received from the bridge is 10V X SINE and COSINE to the steering order. When the
testwheel has been selected COSINE is a constant 10VDC and SINE is the testwheel voltage. During bridge
control a full 360 degrees of operation is possible. Under testwheel control only a limited angle of operation is
possible, approx 45 degrees to port and stbd.
This steering order is compared to the feedback signal and the difference (SINE( order - actual )), the steering
error, is fed to the proportional band amplifier. The pump stroke order signal is proportional to the steering
error until the steering error exceeds the proportional band set by potmeter P2. When the steering error is
greater than the proportional band the stroke order is limited to a value set by the stroke limit potmeter on the
APS PCB. The value of the proportional band as set on the potmeter is valid when one pump only is running .
The proportional band is increased with the number of running pumps as detected by the pump running
interlock.
The ramp circuit limits the stroke order rate of rise to the value set by the stroke ramp potmeter P3.
The NORMAL/TEST jumper W3 enables local follow up control from the built in TESTWHEEL. Note: Follow
Up Select relay must be activated. (closed contact APS-X4-5/X4-7).
The STROKE TEST jumper W4 enables local stroke control from the TESTWHEEL. Full or limited range is
set by W2 Large/Small.
The stroke order is fed to the APS module by a 14 core ribbon cable via connector W7-13/14.
High impedance pull-up resistors on the sine- and cosine order & feedback inputs will create an excessive
signal in case of a broken or loose cable core. The feedback potmeter supply current is monitored. Also the
vector length of the bridge order is monitored. In case of excessive values an alarm detector will cause a relay
contact to open, and at the same time the stroke order is reduced to zero to stop the gear from moving. (This
interlock can be removed, if required). Correct action on the bridge will be to stop the pump of the alarming
side and to start the other pump side, if this is not already working.
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 8/24
VSUP
CURRENT
X4 19 21 X4
DEADBAND LIMIT
COMPENSATION EXCL. BIAS &OFFSET
R231
R230
R234
R236
R235
4W
1N4148
4W
1N4148
4W
3K
3K
27
5
5
PORT STBD PORT STBD
HLMP-3300
P10 P8 P13 VALVE VALVE
D46
D45
ORDER
HLMP-3502
COIL COIL
LED23
LED20
0.1A 0.6A
3.3uF
3.3uF
NEG/STBD 0 - 0.3A
C56
C58
TP2
X4 17 23 X4
D44 D43
1N4004 1N4004
I_PORT_HI
R229
I_STBD_HI
+
R238
2.2
2.2
4W
4W
+
+
+
+ I_PORT_LO I_STBD_LO
9 6
10V/A PORT STBD
VALVE RL10 LIMIT RL14 LIMIT
POS/STBD
FEED TP6
TP13 10 8 5 7
FORWARD
6 9
STROKE STROKE
+ + +
ORDER LOOP
+ TP15 TP17
+ + + + +
LIMIT -
SERVO
BIAS
50%
TP16
4W
4W
2.2
2.2
150mA
P6 P4 TP4 W2 LOOP ACTIVE
PG
9V = BREAK LOOP
SG
100%
POS
BREAK
STBD
DEMO- STROKE-M LOOP
TP9
X3-3 SG
DULATOR
+15V
-15V
OFFSET
NOTE: X3 & X4 terminals are PCB-terminals. SG
+/- 50mA
The stroke order is received from the ASM module. Valve linearization and feedforward are performed by:
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 9/24
The difference between the stroke order and the actual stroke, the stroke-error, is fed to a PI-type controller.
The controller may be disabled (output = zero) by the "Break Loop" pinjumper in order to be able to adjust the
compensation and feedforward without interference from the controller.
The maximum current order in FU-mode can be limited by the current limit potmeter P13.
The current order is fed to the power amplifier with a scale factor of 10V/A
A separate adjustable current generator is provided for NFU control.
The control mode is selected by the FUSEL relay. In NFU the Port/Stbd relays directs the current to port or stbd
coil.
24V+
PORT STBD
FUSEL TP22
LOCAL REMOTE LIMIT SWITCH LIMIT SWITCH
LED19
LED16
LED24
D21
1 1 1 1 1 1
RL5 RL12 RL8 RL4 RL10 RL14
D42
D26
D40
D48
LED10
LED7
R233
R224
16 2 16 16 2 2
R254
1
RL6
3
O
R161
R138
LCL22
16
I
1
3
3
O
O
2
2
LCL24
LCL28
X4 2 8 X4
6 8
I
I
LOCAL
RL6
4
4 X4 X4 10
PORT STBD
3
LIMIT LIMIT
O
2
SWITCH SWITCH
LCL26
I
1
X4 6 12 X4
X4 7 J2 4 J2 5
1
I
LCL23
X4 5 3 X4
LCL25
1 3
I O LIMIT SELECT
11 9 J2 1
2
LOCAL
RL6 1 X4
13
PG
TP21
NOTE: In ASU363 the FUSEL-line passes through the MPF11-DO-0 port to enable auto-change to NFU.
In case of failure in the MPF11-computer itself, the bridge control can be regained by moving the yellow
jumper wire connected to X7-66 from the normal connect. X7-65 to X7-67. X7-67 bypasses the MPF11.
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 10/24
1 1
RL7 RL9
1 1
RL11 RL13
LED21
D32
D39
D41
LED12
LED13
LED17
16 16
D47
2 2
R204
R175
R227
R239
4 13
LOCAL
LOCAL
11 9 11 9
RL8 RL8
ORDER
ORDER
PORT
NFU
NFU
STBD
RL9 RL7
6 8 11 9
13 13
2 J2 3 J2
ORDER
ORDER
STBD
3
PORT
NFU
NFU
RL9
O
RL7
LCL27
LCL31
1 J2
4
4
I
I
1
9 X4 X4 15
2
O
3
11 9
LOCAL
RL6
13
PG TP21
NFU orders are interlocked so simultaneous activation of port and stbd NFU switch result in no NFU order.
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 11/24
D19
C25 CW
SG
2 R121 R122
- 1 SG -15V 2
IC15
1
+ R117
LED4
R250 3 STBD
I_STBD_HI
2
-
R116 HLA
R249 6 5V/A R119 1
- 7 IC8
SG
IC8 + ORDER
+ 3
5
R118
R120
SG
TP10
PORT VALVE TP8
CURRENT OP3
R247 1
0.5V/A
D24
R248 SG
I_PORT_LO
C36
6 R146 R147 2
- 7 TP11
IC15 PORT
1
LED11
+ R142
R256 5
I_PORT_HI HLA
13 R141
R255 9
-
5V/A R144 - 14 ORDER
8 IC8
SG
IC8 +
+ 12
10
R143
R145
SG
ALARM
DELAY
0 =ALARM 0 =ALARM
PUMP/VALVE STBD R83
STBD ORDER
+15V IC7
PUMP +15V
1 CD4077B
D9
OP4 OP2
STROKE 5 5 1 = FAILURE TO STBD 3
OFFSET GAIN 9V=100%
2 6
4
POS/STBD 4 4 IC7 CD4077B 5
R85
R84
R82
+15V
12 D15 R78 IC7
P6 P4 +15V
11
R81
STBDORDER 13
TP4
+15V
PORT CD4077B
+15V R104
ORDER
R110
R103
R80
LVDT T4
T8
C17
PUMP/VALVE OP3
5
DETECT X3 3 PORT +15V
MASTER OP5
5 4 SG SG
R79
4 IC7
R109
PUMP 8 D16
R87
R86
STROKE 10
PORTORDER 9
DEMODU-
LED6
LATOR CD4077B 1
RL1 HYDR.LOCK
1 = FAILURE TO PORT
LED2
MASTER
D10
MASTER
R112
HYDR.LOCK ALARM
16
MASTER
PG
ACTIVATED
SG ALARM DELAY
PUMP
0 =ALARM 0 =ALARM
STROKE R201
OFFSET GAIN 9V=100% 1 = FAILURE TO STBD
IC12
POS/STBD IC12 12 CD4077B
D38
1 D29 11
P2 P1
3 13 9
STBDORDER 2 10
TP1 CD4077B
R199
R200
R202
8
CD4077B +15V
IC12
+15V
R198
R203
LVDT
+15V
DETECT X3 4
R174
SLAVE
R173
R196
T10 T9
C45
IC12
PUMP 5 D30 SG
STROKE 4
R197
PORTORDER 6
DEMODU-
R170
LATOR CD4077B
R106
R105
HYDR.LOCK 1
RL2
HYDR.LOCK
LED3
SLAVE SLAVE
D13
ACTIVATED ALARM
16
PG
The current to the valve coils are measured. When the valve current exceed the value corresponding to 50% of
the valve order to port (or stbd) HLA order port or stbd are triggered .
The stroke of the pump is measured. When the stroke exceeds 50%, the pump is regarded stroked to the side in
question.
If a discrepancy between order and obtained stroke exists for more than about 6 seconds a hydraulic lock alarm
will be issued.
LED's are provided to indicate both when the Hydraulic Lock condition are activated, and when the Hydraulic
Lock alarm is issued after a time delay.
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 12/24
Note:
In ASU363 the “LVDT Detect Master” input (X3.3) and the “LVDT Detect Slave” input X3.4 are connected.
The Hydr. Lock Master Alarm relay is used as Alarm Contact and the Hydr. Lock Slave Alarm relay is used as
input to the MPF11 board.
24V+
FUSE BLOWN TP19
R140 REG1
VALVE
VIN VOUT
AC-SUPPLY LED8
VSUP
3 2
C35
C34
21 TO 25 VAC F1 1
D23
D22
R205
J1 2
C23
C24
R223
R115
C47
J1 1
C40
C41
C52
R206
D33
D34
PG
The +/-15V stabilised power supply for the electronics circuit is received from the ASM-module.
Valve power supply is an unstabilised approx 30VDC 1.5A supply fused with 3A.
A regulated 24VDC supply for relay circuit is derived from the 30VDC raw supply.
Low power supply, less than 27Vdc at the +/-15VDC Vdc supply and less than 20VDC at the 24VDC supply
will result in an opening power OK contact.
+15V 24V+
R56
T3
R32
OP1
5
R57
LED1
15V-OK
4 POWER
OP1
1
C1
OK
C6
R4
R33
2
+/-15V 24V
3 3 1
R114
R2 R35 RL3
1 1
IC1
D18
2 2
IC5
16
LED5
R34
R3
PG
-15V
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 13/24
Board layout:
TP4 W5 1 1 W8
TP3 UNREG. -15V FLASH 1 W9 X2 3 1
UNREG. 15V LED4 15V OK!
MEMORY LED5 5V OK!
W13
1
PROM W14
LED7
Watchdog ENA 1
LED6
PRIMARY 5V VOLTAGE ADJUSTMENT W16 & W17 are test-points
LED2 LED1 RESET (Turns off at manual - or watchdog reset)
POWER
W10
W11
BUSY (On during serial TX)
SUPPLY
IDLE (Indicates spare processor capacity)
TRAFO
1
1
ANALOG OUTPUT Ch. 0
OFFSET ADJUSTMENT
W12
NOTE: THIS TERMINAL STRIP IS NAMED "X5" IN THE SERVO WIRING
1
X1 PARAM.
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 MONITOR
CABLE
+4.5V
1 CONNECTOR
W1
P1 P2 W2
TP2 W3
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45
W4
MPF11 is a microprocessor board. Hitachi H8 is the processor. The program is stored in the FLASH PROM.
Nine digital inputs are entered with:
A NMEA-like serial message reports the state and the order + actual angle once pr second at X7-61 to X7-62).
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 14/24
The SERVO OK contact opens and reports a FAILURE in the following cases:
The SERVO OK relay (K9) has 3 contacts wired to the terminal strip.
X7.37 - X7.38: “Servo OK” for alarming. (Opens in case of failure).
X8.5 - X8.6: “Stand By Start” for stand by start of the other servo unit. (Closes in case of failure).
X8.7 - X8.8: “Stand By Start” for cyclo converter shut down in case of failure at both servos.
(Closes in case of failure).
The FOLLOW-UP SELECT select signal to the servo basically follows the bridge order, (with the
LOCAL/REMOTE switch in position REMOTE).
When a failure is detectec in follow-Up mode generally the Follow-Up signal opens unless the MPF decides
that it is wiser not to select NFU.
Moving the yellow core from X7.65 to X7.67 will disable the FAIL-TO-SAFE function.
The VDR information sentence ($PEMRRCB) is found in drawing 4-7007-2. (Included in the service manual).
The sentence follows the NMEA standard for proprietary signals.
For detailed description of the MPF11 functions please see the document “MPF11 Description”,
MPFRCSW3.DOC. (Included in the service manual).
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 15/24
7. LED indicators.
The printed circuit boards ASM and APS are equipped with LED indicators to ease condition monitoring and
fault diagnosis.
Except for the RUN INTERLOCK LED's all LED's in the ASU will be extinguished when the associated pump
is stopped.
PCB INDIC. COLOUR DESCRIPTION. ILLUMINATED CASE
ASM LED1 RED FB-POT SUPPLY FAIL Broken/loose wire to feedback potmeter
ASM LED2 RED > Order radius larger than 12.9 V
ASM LED3 RED < Order radius smaller than 9.0 V
ASM LED4 RED PORT STROKE FU stroke order to port
ASM LED5 GREEN STBD STROKE FU stroke order to stbd
ASM LED6 RED WIRE BREAK Loose or broken order or feedback wire
ASM LED7 GREEN RUN INTERLOCK 1 Other pump running interlock no. 1
ASM LED8 GREEN RUN INTERLOCK 2 Other pump running interlock no. 2
ASM LED9 GREEN RUN INTERLOCK 3 Other pump running interlock no. 3
ASM LED10 RED ALARM Broken wire or illegal order signal
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 16/24
8. Pinjumper settings.
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 17/24
9. Potmeter settings.
Below tables explain the results of potmeter settings.
Note: “SLAVE” trimpots (P1,P2) are used in ASU363. Set exactly as (P4,P6)
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 18/24
Check that the beltdrive of the feedback units are are properly fixed, no slack.
Check that all cables are of the type specified in the Installation Information and that they are securely fastened
in the cable glands.
Check that all cable cores are correctly terminated in the units in accordance with the Installation Information.
Check that wire jumpers are correctly fitted in the terminal strips.
Check that pin-jumpers and potmeters are set to the recommended initial settings.
Check that the power on LED's on the APS PCB are illuminated, LED1 and LED5.
Zeroing of Steering feedback and Reference feedback potmeters. (See datasheets for RFB360/RFC360.)
By manual control at the control valve position the Azipod precisely at midships.
Measure the steering feedback voltage: SINE(angle) in X7-2 with ref. to X7-5, COSINE(angle) in X7-3 with
ref. to X7-5.
Measure the reference feedback voltage: SINE(angle) in X7-B with ref. to X7-E, COSINE(angle) in X7-C with
ref. to X7-E.
The COSINE voltage must be close to 10VDC, Adjust the SINE voltage to 0.00 +/- 25mV by turning potmeter
unit in RFB-unit. Secure the potmeter unit and check that the fastening do not change the zero position voltage.
Move the Azipod to stbd 10 deg. Check that the polarity of the SINE voltage is negative and the magnitude is
approx. 1.7 VDC
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 19/24
Measure the master pump stroke feedback signal at TP4 with ref to TP9.
Zero adjust to 0.00VDC with the LVDT offset master potmeter P6.
By manual stroke the pump fully to STBD. Calibrate the strokesignal to +9.00 VDC with LVDT gain master
potmeter P4.
Stroke the pump fully PORT and check the stroke feedback signal is -9.00VDC
Measure the slave pump stroke feedback signal at TP1 with ref to TP9.
Zero adjust to 0.00VDC with the LVDT offset slave potmeter P2. Or set P2 exactly as P6.
By manual stroke the pump fully to STBD. Calibrate the strokesignal to +9.00 VDC with LVDT gain slave
potmeter P1. Or set P1 exactly as P4.
NOTE: Never adjust so that max stroke exceeds 9.00V . Tolerance: 8.00V to 9.00V.
Operate the steering gear from the local NFU push-buttons on the ASU front. Check that the Azipod moves in
the ordered direction.
NOTE: FOR ASU363: Selection of LOCAL control disables the Fail-to-NFU function and resets MPF11.
Adjust the NFU current with P14 so the pump is just fully stroked. Read the current at TP18 to TP20 as a
voltage with 2.2V per A.
In case 35deg Limit Switches are fitted: (If not go to 10.5. Stroke Servo Adj.)
Fit a temporary jumper between X7-25 and X7-26 (limit select). Verify the function of the limit switches by
manually operating the switches. Adjust the limit switches so the steering stops at the desired position.
Remove the temporary jumper.
On the ASM PCB: Check that the NORMAL/TEST plug W3 is in the UPPER position
Set the stroke-test pin-jumper W4 and the small/large pin-jumper W2 to their lower
positions.
Move the "Break Loop" pinjumper W2 on the APS PCB to the lower position.
Enable the FU-servo by switching the LOCAL/REMOTE switch to REMOTE. Please note the FUSEL relays
RL5/RL12/LED19 must be energised. If FUSEL has not already been selected, fit a temporary jumper between
X7-39 and X7-40.
Move the testwheel P1 on the ASM PCB to obtain approx. +200mV on APS TP2 (stroke order) with ref. to
TP9. At the port deadband compensation potmeter P10 increase the setting from zero until the steering gear just
starts to move. Then reduce the setting until the steering gear stops.
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 20/24
Repeat to stbd side with -200mV on APS TP2 with ref. to TP9 and adjust with P8 stbd deadband
compensation.
Set ASM large/small pin-jumper W2 in the upper position.
With the testwheel P1 on the ASM order the valve fully out. Adjust with the valve feedforward potmeter P5 so
the pump is just fully stroked. Read the stroke feedback signal at TP4 with ref to TP9 and compare to the
readings obtained with manual operation. Check both directions.
With inner loop=stroke servo loop inhibited, which means W2 on APS in LOWER position:
Enable the servo loop by moving the APS W2 BREAK LOOP pin-jumper to the upper position if You have
decided to use the inner loop.
Otherwise go to Stroke Ramp Adjustment.
Operate the steering gear from the testwheel fully CCW and CW ( +/- 10VDC @ ASM TP10 ) and adjust with
the stroke order limit potmeter P3 the maximum stroke. The limit should be set so the pump is almost fully
stroked. Hint: Measure the pump stroke signal and slowly reduce the setting of the limit potmeter until the
stroke feedback signal drops a little.
Set the Stroke loop gain potmeter P7 to best compromise between precision and heavy control activity.
The adjustment may best be performed with the BREAK LOOP jumper W2 on the APS in the lower position.
The TESTWHEEL will then act as direct control of the valve current.
Adjust with the testwheel so half stroke STBD is obtained, the stroke signal is measured to +4.5VDC on APS
TP4 with ref to TP9.
Adjust The HLA order trig potmeter P9 so the STBD HLA order LED4 is just lit.
Order stroke to PORT and observe that the PORT order HLA LED11 is lit at approx the same level of stroke as
to STBD.
A check of the adjustment: When slowly increasing the stroke order from below 50% to above and if the
HYDLOCK MASTER LED6 it lit first and then extinguished when the HLA order trig LED4 or LED11 is lit,
then the HLA ORDER TRIG LEVEL should be decreased. If on the other hand the HLA trig LED’s and the
HYDLOCK MASTER LED is lit simultaneously and the HYDLOCK MASTER LED then extinguishes at little
higher stroke, increase the setting of the HLA ORDER TRIG LEVEL.
Check for both port and stbd stroke orders, the pump may not respond symmetrically to the order. Adjust for
minimum time (= amount of order change) with the HYDLOCK MASTER LED lit. Distribute any discrepancy
even between the two sides, and check also for reducing stroke from above 50% to below. Hysteresis may exist
in the stroke order (valve current) to obtained stroke.
It is possible to adjust the Hydraulic Lock Alarm system while the ship is in normal operation, provided that the
LVDT GAIN is properly adjusted. (STROKE Signal = 8.0 to 9.0V at max stroke). There must be some
steering activity during this, either from the wheel or from the autopilot. (The POD must move a few deg.
frequently).
Watch the 2 LED4 & LED11 and the resulting LED6.
Adjust P9 so that you have as short time illuminations of LED6 as possible.
Use “Trial & Error”: Try a very low setting of P9 first and then a very high setting to understand the action.
Then find a compromise in the middle, where LED6 flashes as short time as possible.
Alarm comes if LED6 is ON during more than 5 seconds.
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 21/24
On the ASM PCB: Set the stroke-test pin-jumper W4 to the upper position.
Set the NORMAL/TEST W3 plug to the lower position.
Adjust the proportional band with the ASM potmeter P2 to obtain a smooth overshoot free response to an angle
order change. A potmeter setting between 5 and 7.5 corresponding to between 3 and 4 degrees is a reasonable
starting value for a steering gear with a speed of 3 deg/sec with one pump in operation . Select a lower setting
for slower pumps, higher setting for faster pumps. The proportional band is automatically increased
proportional to the number of running pumps.
NOTE: The lower the PROP BAND setting the more aggressive the pump wil be. And the higher the risk of
false hydraulic lock alarms, especially with worn pumps and feedback potmeters.
Always use the same setting of the proportional band in all the servos in a system.
Check the static accuracy of the steering control. Measure the RUDDER ERROR on ASM TP13 ref TP16.
Scalefactor is 0.175 V/deg.
Move the Azi some 10 to 20 degrees away from zero and then return to around zero from one side and from the
other side. Note the Rudder Error voltage at stand still.
In case the inner loop is active, i. e. the APS Break Loop jumper W2 in the upper position, the static error is
expected to be in the few mV range.
In case the inner loop is disabled, some static error in the magnitude of a couple of tenths of a degree must be
expected.
Increase if necessary with the Port and Stbd Deadband Comp. potmeters P10 and P8 a little to obtain a
satisfactory static accuracy, but without creating an overshoot or small signal hunting.
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 22/24
Restore to normal condition: Remove temporary bridges and set all ASM and APS-pinjumpers to normal upper
position.
Operate the Non Follow Up controller on the steering stand and check that the Azipod follows the orders.
Check that the steering gear follows the order. Operate pumps separately and together. Check that the other
pump running LED indicators on the ASM PCB (LED7, LED8, and LED9) are illuminated when the
corresponding pump is running. Observe the proportional band increases with the number of pumps running at
the same time.
Manually operate control valve and observe the Hydraulic Lock Alarm. Note a delay of approx. 6 sec.
Please note that the hydraulic lock alarm cannot be tested the removing valve plug as the "order" that is sensed
in the hydraulic lock alarm is the valve current which of course will be zero with the plug removed.
Removing the plug on the stroke sensor will (should) also generate a hydraulic lock alarm when the pump is
operated from the NFU push-buttons on the box front.
Check the power failure alarm by lifting the power supply plug J1 on the ASM module.
Select LOCAL and observe the LOCAL/REMOTE alarm (if fitted).
11. Troubleshooting.
Necessary tools:
Screwdrivers, 3 mm for terminals, 8 mm for opening the boxes.
1 or 2 standard digital voltmeters, FLUKE, HP or similar.
The manuals of the system.
The bridge steering system and the steering gear manufacturer's interface drawings
Trouble shoot 1 pump at the time. Always compare the failing system with other, supposed ok system.
CHECK POINTS:
Check selected voltages according to the list below:
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 23/24
ASU-BOX 24Vdc(+) APS TP22 ref Relay and auxiliary supply 24Vdc +/-
TP16 1Vdc
ASU-BOX Steering order in (SINE) X7-17 ref X7-15 10V X SINE(Order) neg. stbd
ASU-BOX Steering order in (COSINE) X7-18 ref X7-15 10V X COSINE(Order) pos ahead
ASU-BOX Steering feedback (SINE) X7-2 ref X7-5 10V X SINE(Angle) neg. stbd
ASU-BOX Steering feedback (COSINE) X7-3 ref X7-5 10V X COSINE(Angle) pos ahead
ASU-BOX Reference feedback (SINE) X7-B ref X7-E 10V X SINE(Angle) neg. stbd
ASU-BOX Reference feedback (COSINE) X7-C ref X7-E 10V X COSINE(Angle) pos ahead
ASU-BOX Stroke order (NEG STBD) ASM TP18 ref 10V corresponding to max stroke order
TP16
ASU-BOX Measured stroke (POS STBD) APS TP4 ref TP9 9V corresponding to max stroke
ASU-BOX Valve Current order excl bias APS TP13 ref 10V/A pos. Stbd.
TP9
ASU-BOX Valve current FU STBD APS TP17 ref 2.2V/A Stbd FU orders
TP16
ASU-BOX Valve current FU PORT APS TP15 ref 2.2V/A Port FU orders
TP16
ASU-BOX Valve curr. NFU PORT/STBD APS TP20 ref 2.2V/A NFU orders Port or Stbd
TP18
ASU-BOX LVDT Excite voltage X7-28 ref X7-30 6Vrms/2.5kHz
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU363-D-VVV Page 24/24
In case of failure in the MPF11-microcomputer: Move the Yellow terminal jumper fitted between:
X7-65 and X7-66 to connect X7-66 with X7-67. This connects the bridge FUSEL-contact directly.
Also disconnect the STAND-BY START contact conn.to: X8-5 and X8-6.
The STAND-BY Start function is actually carried out in the motor starter.
Servo-unit ASU363 delivers a closing contact in case the MPF11-monitor concludes that an error has occurred
in the running pump’s follow-up circuit. This contact also closes in case of internal failure in the MPF11.
(It also closes in case of unenergized servo, which of course is counter-acted for in the motor-starter circuit.)
The MPF11 function can be monitored on the serial output port using a Laptop fitted with a serial port and a
communication program. (Hyperterminal or PCPLUS or PROCOM). (Baud=4800, No parity, 1 stopbit).
The special cable with EMRI part number 4-5172 (“Parameter Cable”) is used.
The Parameter Monitor Cable can be connected to connector W12 (just right off the MPF-terminal strip).
A working board will respond with the “>” prompt.
The most used laptop-instructions are <watch all> <enter> and <view param> <enter> .
<init> <enter> is used to clear the screen.
The same cable is used during parameter setup of an “empty” MPF11.
<set ‘parameter’ = ‘value’> <enter>
In order to identify itself properly in a VDR sentence the MPF11 must be informed with the PumpName.
Write:
Set PumpName=”STBDP2” <enter> to identify the pump is STBD Pod pump No. 2. Etc.
NOTE: Basic Software is loaded through a chip.
For detailed description of the MPF11 functions please see the document “MPF11 Description”
(MPFRCSW3.DOC). (Included in the service manual).
EMRI considers it necessary that you pass a training session before repairing MPF11 software or parameters.
N:\ASU\ASU363\ASUIINFO.LWP 2007-03-22
ASU-SETUP 1/1
BACKGROUND:
There have been too many reported cases of false HYDRAULICK LOCK ALARMS.
It seems to EMRI (although based on rather weak reporting) that many of those cases arise when
two pumps are in operation.
Our investigation to this has concluded:
Many false alarms are caused by an unavoidable mismatch at certain angles between the RFB-
feedback signals.
This feedback is never 100% ideal, since it is sine/cosine potmeter signals, and there can be
certain angles where the difference between P1 and P2 is above 2.0deg.
The sensitivity to false alarms with 2 pumps increase with mismatch between P1 and P2
feedback. It increases also with the reciprocal value of the proportional band, PB,of the servo
(PB = PROP BAND as set by ASM12-trimpot P2 ).
The sensitivity to false alarms also increase a lot with bad setup of the sensor signal itself and
with bad setting of the alarm detector.
APS31 trimpotmeters:
P4 and P6 (Sensor, LVDT gain and offset) and P9, HLA ORDER TRIG LEVEL.
REMEDY:
A:
Increase the PROP BAND of all Azipod Servos. From 3deg to 4.2 deg.
This is done by turning the ASM-PROP BAND trimpot P2 from index 5 to index 8 .
B:
NEVER exceed “ 9V=100% “ when calibrating the pump sensor feedback by APS-trimpot P4.
(Measured at TP4 ).
Distribute differences to the low side, i.e. go down in voltage on the lower side toward 8V
instead of letting the high side go above 9.0V.
CONSEQUENCES:
Lower bandwidth in the servo loop, causing softer steering, which also gives less wear on the
pump and on the mechanical gear.
Approved by EMRI.
31-May-2005
J.C.Nortoft Thomsen
Bridge alarm panels differ from ship to ship. Reference is made to the instructions by ABB
Marine on those panels.
ASU363 has, however, the following alarm contacts wired down to terminals:
4. Servo Fault:
X7-37 to 38 opens in case of a servo failure.
TRSHTNY.DOC 2007-03-22
Short Form Hints. ASU363 pg. 2/2
Servo Fault Alarm is one or more of several causes, which also can
include those, which release the Hyd.Lock and the Pow.Fail. alarms.
Other causes:
SERVO FAULT alarm can include any error in the servo loop, including hydraulic failures
and errors caused by false alarms.
TRSHTNY.DOC 2007-03-22
PG.1/8
MPF11 description.
Table of contents:
N:\ASU\ASU363\MPFRCSW3.DOC 2007-03-22
PG.2/8
Serial output
PORT B NMEA: $PEMRRCB to VDR
*3: Transmission to other servo following the protocol given under *1.
N:\ASU\ASU363\MPFRCSW3.DOC 2007-03-22
PG.3/8
The Servo System OK contact stays closed while the related pump is running and there has
been no failure in the servo function detected.
The contact opens when one or more of the following conditions are met:
Condi Functional state description. Alarm delay Al. state Fail
- Parameter Latching to NFU
tion
A The pump is stopped and the servo power supply is off.
B Not Considered
C The difference between the steering order and the steering feedback ConditionC Latching (Yes)
reference is greater than the allowed servo error (RudErrMax, parameter, In most
default equal to 5 degrees), except for steering angles above 35 degrees, cases, se
where larger servo error is allowed if the steering order is larger than the descrip-
actual steering angle. tion in 4.B
AND
The steering rate of turn is at the same time less than 50% of nominal,
what is equal to 100% increase in the nominal 35-30 degrees steering
time with one pump running (RudderTime1 is a parameter).
AND
The servo is in FU-mode or has been switched to NFU by the ”Fail to
Safe”
“Fail to safe”-Function. (See description below).
Condition c. shall always open the SYSTEM OK contact.
D A power failure is reported to the MPF. ConditionD Latching Yes
E An Order or Feedback Signal Failure is reported to the MPF. ConditionE No Yes
F Any steering order to the MPF is greater than +/-11V or lower than 9.0V ConditionF Latching Yes
radius.
G Not Considered
H The servo is in NFU control and the steering does not move according to ConditionH Latching No
the orders
with the expected steering speed above 50% of nominal speed for one
pump. (Equivalent to 100% increase in steering time 35-30degrees).
I The steering is in NFU mode and the steering is drifting with a steering ConditionI Latching No
speed above 25% of what is nominal speed for one pump.
J FUSELB is requested from bridge but FUSELD is not returned to MPF. ConditionJ No No
Condition B is in other systems covering the case where the reference feedback and the
servo feedback differs too much. In the ASU362 only the actual feedback are monitored by
the MPF (There is no ref. FB). In the ASU363 only the reference feedback are monitored.
The situation will be covered by the Condition C supervision if the 2 feedbacks differs in an
ASU363 system.
Condition G is in other systems equal to Local Select. In ASU362/363 local select is not
reflected in the Servo OK condition. Local Select has its own specific alarm contact.
N:\ASU\ASU363\MPFRCSW3.DOC 2007-03-22
PG.4/8
All failure conditions are latched except for condition E and J, coming from external
contacts and therefore not MPF detected.
The failure conditions are latched and the alarm contact stays open until one of the
following release situations occurs:
- One of the running servos have been switched to LOCAL.
- The NFU mode has been selected from the bridge.
- The pump with latched condition is stopped and restarted.
A failure will always issue a standby start order to the other pump.
If the stand-by pump is running already, it will not latch a stand-by start condition, and can
then immediately be stopped from the bridge again.
The stand-by start order will then be executed and start the pump again.
A pump cannot be stopped from the bridge, when it is stand-by started.
First stop the failing pump that caused the stand-by start.
A failure in both servos will make both servo OK contacts go open, and the AIU box
will then order the Propulsion system to the “Propeller Free Wheeling” state.
No logic in the MPF can force the FU-SEL signal to the follow-up mode if NFU is selected
from the bridge. This is not an output from any “state machinery” but a simple
programmed logic function bypassing all state machinery.
The FU-mode will be cancelled (Fail to Safe) and NFU selected in case of all servo failure
conditions a. to f. as listed above, except when the steering moves in the correct direction,
or at least not more than 20% of nominal speed in the opposite direction under failure
condition c.
If the steering gear is observed running with above 50% of the nominal steering speed (in
the wrong direction) after having selected NFU in order to “fail to safe”, then this
overriding shift to NFU-mode is released again and is not chosen again as long as the
failure state remains. (Until released/reset).
The NFU state of the MPF’s DO(0) is reported to the other MPF in the serial state
information on DO(2).
N:\ASU\ASU363\MPFRCSW3.DOC 2007-03-22
PG.5/8
N:\ASU\ASU363\MPFRCSW3.DOC 2007-03-22
PG.6/8
Jumper W15 on the MPF11 board should be set to position 2-3 (RS232),
which is factory default.
Start a standard terminal emulation program (like Procomm/ PcPlus or HyperTerminal) on the PC
and set the used Com-port to a baudrate of 4800,
no parity, 8 bits, 1 stopbit and no handshake.
N:\ASU\ASU363\MPFRCSW3.DOC 2007-03-22
PG.7/8
Set tablename [ n ] = value Changes one entry of the table to a new value.
N:\ASU\ASU363\MPFRCSW3.DOC 2007-03-22
PG.8/8
As these systems operates in pairs, they need to know whether they are pump no. 1
(default) or pump no. 2. So on pump no. 2 you may need to enter set PumpNo = 2
For proper identification in the NMEA sentence to the VDR, the pumps name
also needs to be set, for example set PumpName = “STBDP2”
Diagnostics
In order to be able to inspect the internal state of the Fail Recovery system, some diagnostic output is available, when
the MPF11 is connected to a PC with a terminal program.
Order = 45.012913
Actual = 44.840069
Diff. = 0.170952
Rate = -0.002501
Fail now = ___D____________
Latched = ___D____________
State = Fail to Safe
This = Alive Fail NFU
Other = Dead
Fail now is a list of detected fail conditions (C to J, see table with Fault Groups)
Latched is a list of reported fail conditions (C to J, see table with Fault Groups),
This Is the state attributes of this station, transmitted to the other station.
Other Is the state attributes received from the other station.
N:\ASU\ASU363\MPFRCSW3.DOC 2007-03-22
$PEMRRCB Definition 1
Field # 3. Bit mapping. '1' means that the description below is true. (Typical: 01F8)
Bit 1 (LSB) Port Order. NFU DI(0)
Bit 2 Stbd Order. NFU DI(1)
Bit 3 Always 0
Bit 4 NOT HYD.LOCK DI(3)
Bit 5 Servo in REMOTE DI(4)
Bit 6 Servo Power Supplies OK DI(5)
Bit 7 Feedback and Order OK. (Corecheck) DI(6)
Bit 8 Follow-Up Mode selected DI(7)
Bit 9 Select Follow-Up Mode fm. Bridge DI(8)
Bit 10 NFU response failure
Bit 11 Steering Gear Drift in NFU Mode
Bit 12 Servo Order out of Range
Bit 13 Servo-Actual differs from Order
Bit 14 Servo Actual out of Range
Bit 15 Servo Failure Reported to Bridge. DO.1 OFF
Bit 16 (MSB) Failing to NFU Mode. DO.0 OFF
RCB_ASU1.XLS ISSUE B
2005-04-29 MPF11-RCB / ASU36x 4-7007-2