Cryogenic Techno Works: Half Cell Potentiometer Test Report

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Registered office : B-101,Building no.

11,
Mangalmurti Complex,near Mankhurd–Ghatkoper
Cryogenic Techno Works Link Road, Mankhurd, Mumbai -400 043.

Email: cryogenictechnoworks@gmail.com

HALF CELL POTENTIOMETER TEST REPORT

Date: 03/05/2016
Client Ref: 30/04/2016

Test Report No. : CTW/KC/1078/2016

Name & address of client : Kavya Construction.

Site Address : Muktidham Co. Op Hsg. Soc.


Kalwa (E).
Date of testing : 02/05/2016

Test Method Followed : ASTM/C876-80

Half Cell Potentiometer


Sr. No Location/ID Mark Average
Reading(mV)
1 2 3 4 5

-332 -289 -274 -308 -225


1 RCC- Column No. 3 -307
-336 -298 -262 -310 -333

-371 -378 -370 -392 -385


2 RCC- Column No. 6 -353
-202 -327 -285 -407 -408

3 RCC- Column No. 10 -467 -321 -390 -457 -425 -401

-441 -357 -385 -391 -378

4 RCC- Column No. 11 -363 -369 -373 -350 -369 -364

-383 -399 -319 -361 -353

5 RCC- Column No. 14 -360 -355 -317 -333 -359 -342

-326 -367 -296 -341 -363

6 RCC- Column No. 18 -433 -423 -404 -427 -430 -441

-441 -434 -480 -486 -451

7 RCC- Column No. 24 -229 -310 -328 -251 -329 -283

-306 -330 -346 -343 -262


Registered office : B-101,Building no.11,
Mangalmurti Complex,near Mankhurd–Ghatkoper
Cryogenic Techno Works Link Road, Mankhurd, Mumbai -400 043.

Email: cryogenictechnoworks@gmail.com

8 RCC- Column No. 27 -440 -447 -471 -485 -399 -414

-441 -336 -525 -347 -249

9 RCC- Column No. 29 -432 -410 -431 -434 -446 -418

-420 -410 -408 -418 -372

10 RCC- Column No. 32 -427 -530 -475 -428 -323 -454

-485 -456 -467 -524 -424

Remarks :
Potential (vs CSE) Significance

More negative than-350 mV Very high probability of ACTIVE CORROSION

More positive than-200 mV Very high probability of NO CORROSION

- 200 mV to - 350 mV UNCERTAINITY OF CORROSION

Positive readings Insufficient moisture in concrete

 Test report is related to the structural member under test in as received condition.
 Test report is valid at the time of and under the condition specified herein.
 Test report may not be reproduced in part and cannot be used as evidence in the court of law
without written permission of “Cryogenic Techno Works” Mumbai.