C&D Ups12
C&D Ups12
C&D Ups12
12-1041
UPS12-550MRX
Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.
TECHNICAL DATA
Constant Power Discharge Ratings - Watts per Cell @ 25°C (77°F) 20 hour IEC Rating:
rate to 1.75 10 hour rate
Operating Time (in minutes) to 1.67 Volts per Cell
Model VPC @ to 1.80 VPC
5 10 15 20 30 40 45 50 60 90 25°C @ 20°C
UPS12-550MRX 897 704 550 454 346 288 258 242 210 148 154 AH 137 AH
Cells Per Unit Voltage Per Unit Weight 1 Min Current to 1.75VPC Short Circuit Current Internal Resistance
(Amps) (Amps) (mOhms)
DIMENSIONS
[ 33.3 ]
[ 33.3 ]
1/4-20 UNC
1.31
12.97
1.31
[ 329.5 ]
[ 172.7 ]
[ 277.7 ]
10.93
6.80
1.22 1.22
[ 31.1 ]
[ 274.5 ]
[ 31.1 ]
10.81
13.57 6.63
[ 344.7 ] [ 168.4 ]
[ 3.2 ]
[ 3.2 ]
0.13
[ 62.2 ]
0.13
12.74
2.45
[ 323.6 ]
Any data, descriptions or specifications presented herein are subject to revision by C&D Technologies, Inc. without
notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc. makes no
warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of
1400 Union Meeting Road such information. Further, because the product(s) featured herein may be used under conditions beyond its control,
P.O. Box 3053 • Blue Bell, PA 19422-0858 C&D Technologies, Inc. hereby disclaims all warranties, either express or implied, concerning the fitness or suitabil-
(215) 619-2700 • Fax (215) 619-7899 • (800) 543-8630 ity of such product(s) for any particular use or in any specific application or arising from any course of
customersvc@cdtechno.com dealing or usage of trade. The user is solely responsible for determining the suitability of the product(s)
www.cdtechno.com featured herein for user’s intended purpose and in user’s specific application.
Copyright 2010 C&D TECHNOLOGIES, INC. Printed in U.S.A. 12-1041 0110/CD