Manual CCC3 V1.1 Eng
Manual CCC3 V1.1 Eng
Manual CCC3 V1.1 Eng
CENTRAL CHILLERCONTROLL 3
1
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
V 1.1
Contents
1. GENERAL NOTES........................................................................................................... 3
2. POSIBILITIES TO ADJUST........................................................................................... 5
3. CIRCUIT DIAGRAM..................................................................................................... 19
4. EVOLUTION .................................................................................................................. 20
5. PARAMETER VIA RS232 ‐ INTERFACE ................................................................. 21
6. F. A. Q. ............................................................................................................................. 26
2
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
1.
V 1.1
General Notes
1. General Notes
Picture 1-1
↵
- menue
- confirm
- chiller on/off
↑ - menue point up
- value up
- disable beeper
← - menue level forward
- position left
- menue level forward
→ - position right
- info
↓
- menue level down
- value down
3
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
1.
V 1.1
General Notes
errorr LED
ENTER/menue
ESCAPE/set value
UP/on/off
LEFT/mute
RIGHT/roll/info
DOWN/quit
Picture 1-2
4
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
2. Posibilities To Adjust
By pressing the ESCAPE-button (ESC), you can reach the set value display (1st
programming level). By pressing the UP- and DOWN-button (↑↓) you can adjust the
value of the digit, with the RIGHT- and DOWN-button (← →) you can choose the
digit. The set value is affirmed by pressing the ENTER-button (↵), you can cancel
the input by pressing the ESCAPE-button (ESC). Adjusting the set value is only
possible in the specified range. (Water temp. Func./Lower set value limit; Water temp.
Func./Upper set value limit).
Picture 2-1
5
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
Adjusting parameters
By pressing the ENTER-button (↵), you can reach the 2nd programming level.
Therefore, please enter your user-password (0020). By pressing the UP- and
DOWN-button (↑↓) you can adjust the value of the digit, with the RIGHT- and
DOWN-button (← →) you can choose the digit. The set value is affirmed by
pressing the ENTER-button (↵), you can cancel the input by pressing the ESCAPE-
button (ESC).
Picture 2-2
Here you have the possibilty to adjust the following parameters
Æ Language
All other parameters cannot be adjusted
Æ Filling
Æ Water level because these could damage the function of
Æ System function the chiller. Please contact Termotek.
Æ control function
Choose the wished paramater and confirm with the ENTER-button (↵). To save the
action press the ESCAPE-button (ESC) until following display appears (Picture 2-3)
(Save changes? YES = Enter)
6
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
Picture 2-3
You can confirm with the ENTER-button (↵) or abort with The ESCAPE-button
(ESC) and return to the start display.
7
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
Water level/
System functions/
Beeper
No beeper will sound except warning at filling mode.
Rolling mode
The different values will appear succesive.
Operation hours
Read out the hours of operation.
Starting mode
The controller can switched on or off using either the UP-button (↑) on the front panel, the
remote start input or the start flag (via RS232 – connector).
If the remote start input is used to enable the outputs, then the controller is always on.
Using the starting mode line, the chiller will start as soon as voltage is enable.
Temperature scale
The unit can be switched between Fahrenheit and Celsius. Despite changing this unit, the
parameter and set value and adjustment range remain the same. Only the display shows °F!
Baud rate
Adjust speed of the RS232 interface.
Control functions/
Control functions/PID-control
dT-increase start
Start temperature of temperature control.
dT-increase
Heats/cools the chiller without control until dT-increase start is reached Use only at laboratory
operation!
8
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
For some paramters you have to enter the technician-password. The third programming level is on the
same kind reachable as the second one.
Water temp. Func./Lower set value limit -99.0 ... 32.0 °C 15.0°C
Water temp. Func./Upper set value limit 15.0 ... 999.0 °C 32.0 °C
Calibration/Analog outputs
Calibration/Analog inputs
Diagnosis/Digital outputs
Diagnosis/Digital inputs
Diagnosis/Analog outputs
Diagnosis/Analog inputs
Alarm conductivity
Conductivity alarm if this limit is exceeded. The corresponding message appears on the display
and the according relay output switches.
Pre alarm conductivity
Alarm if this limit is exceeded („cooling contact with hysteris 1mS“).The corresponding message
appears on the display.
Alarm delay
The conductiviy alarm will be surpressed for the set time in case of a error.
Conductivity valve-off
Switching point ventile OFF if enable.
Conductivity valve-on
Switching point ventile ON if enable.
System function/Advanced/
Error relay
Alarm relay: closed in case of alarm.
Release relay: closed if no alarm and the controller is on.
Longterm rejection
All Alarm messages are surpressed for the set time if the filling mode is active.
Limit value ambient temp.
Alarm limit value for the ambient temperature. The according relay output switches n case
of alarm.
Change relay output
The switch use of the outputs can be inverted here.
Change relay input
The switch use of the inputs can be inverted here.
Reset parameter WARNING DANGER
Reset parameter to factory settings. All edited settings made by you and by Termotek will
be lost!
11
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
Control functions/PID-control/
Control functions/Compressor/
Control functions/Heating/
Control functions/Ventilator/
Heating contact
Switches the hot gas valve, heating or cooling.
12
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
Sensor functions/
Pressure func./
Pressure func./Advanced/
Pressure sensor 4 mA
Pressure sensor 20 mA
Calibration
Flow ½ funct./
Lower limit
The flow alarm will be set off in case of falling below the limit (after end of starting delay).
Upper limit
The flow alarm will be set off in case of exceeding the limit (after end of starting delay).Der
Pre alarm flow
If flow falls below this value, a flow warning will be released via the display and the interface.
Starting delay
Maximum period of time which may pass from starting the pump until the minimum flow is
established.
Flow ½ funct./Advanced/
Signal type
DISABLE Î switched off
TURBINE Î pulse interpretation
SCHALTER Î digital input
Impulse performance
Calibration of flow sensor: How many pulses per litre?
Switch off output
The output will be switched off in case of quitting the reference between lower and upper
limit if enable.
Error message while off
Flow alarm when the chiller is switched off.
13
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
Analysis ABSOLUTE
Analysis ABSOLUTE
14
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
Password/
Soft-Vers.
Actual software version
Par. Vers.
Actual parameter version
Syspar-Vers.
Actual system-parameter version
Proc.-Vers.
System information
Kali-Vers.
System information
Password user
Change user password
Password technician
Change technician password
Password administrator
Change administrator password
Calibration/
Analog outputs
Analog inputs
Diagnosis/
Digital outputs
Digital inputs
Analog outputs
Analog inputs
15
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
16
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
Conductivity control
Enables conductivity control
Conductivity measuring
Enables conductivity measuring
Rinse start temp.
When this temperature is reached, the rinsing of the de-ionising cartridge will be started.
Only possible with DI – control.
Interval rinsing
Interval between two rinsing sequences
Duration rinsing
Duration of a rinsing sequence
Part
Complete
Reset the operation hour of the chiller.
System function/Advanced/Advanced/
Control functions/Compressor/
Hours op.
Reset operation hours of compressor (for example at replacement).
Control functions/Heating/
Hours op.
Reset operation hours of heating (for example at replacement).
Control functions/Heissgas-Ventil/
Hours op.
Reset operation hours of hot gas valve (for example at replacement).
Control functions/Pumpe/
Hours op.
Reset operation hours of pump (for example at replacement).
17
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust
Sensor functions/
Switch off F2
If the sensor inlet (normally ambient temperature sensor) is not required it can be switched off.
In this case it is set to 20.0 °C internally (unattached of a eventually mounted sensor).
Switch off F3
If the sensor inlet (normally condensor block temperature sensor) is not required it can be
switched off. In this case it is set to 20.0 °C internally (unattached of a eventually mounted
sensor).
Switch off F4
If the sensor inlet (normally inlet temperature sensor) is not required it can be switched off. In
this case it is set to 20.0 °C internally (unattached of a eventually mounted sensor).
Pressure func./Advanced/
Pressure gauge
Can be disabled or enabled.
18
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
3.
V 1.1
Circuit diagram
3. Circuit diagram
Picture 3-1
19
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
4.
V 1.1
Evolution
4. Evolution
pos date version change
01 2006 V067 Software update
02
03
04
05
20
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
5.
V 1.1
Parameter via RS232 - interface
5. Parameter via RS232 ‐ interface
Please ask for your parameter sheet at TERMOTEK AG. We need the type designation and the serial
number. Please hold them ready.
We will send you a RS232 – protocol if required.
Request of warning and alarm signals via <<STAT_Message>>
bit description
0 OK
1 Warning water level
2 Warning flow 1
3 Warning flow 2
4 Warning conductivity
5 Warning high tempterature
6 Warning low temperature
7 Temperature condensor block too high
8 Alarm
9 Alarm high temperature
10 Alarm low temperature
11 F2 – error (normally ambient temperature sensor)
12 F3 – error (normally condensor block temperature sensor)
13 F4 – error (normally inlet temperature sensor)
14 Error refrigerant ciruit
15 High pressure refrigerant circuit
16 Low pressure refrigerant circuit
17 Error water circuit
18 Alarm water level
19 Alarm ambient temperature
20 Alarm conductivity
21 Alarm flow 1 too low
22 Alarm flow 2 too low
23 Alarm flow 1 too high
24 Alarm flow 2 too high
25 Alarm high temperature
26 Alarm high pressure water circuit
27 Alarm low pressure water circuit
28 F1 – error (normally water circuit temperature sensor)
21
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
5.
V 1.1
Parameter via RS232 - interface
Request of measured values (if required options are installed)
Flow 1 (l/min) (actual value)
Element Offset Length/Bit Description Unit/Selections
Wasserkrei_DFL1_AI
IO: 44 2 Flow 1 l/min
_Fluss
Flow 2 (l/min) (actual value)
Element Offset Length/Bit Description Unit/Selections
Wasserkrei_DFL2_AI
IO: 50 2 Flow 2 l/min
_Fluss
Conductivity (μS) (actual value)
Element Offset Length/Bit Description Unit/Selections
Wasserkrei_Leitwert_
IO: 56 2 Conductivity μS
AI_Leitwert
Cooling power (W) (actual value)
Element Offset Length/Bit Description Unit/Selections
Flag PKuehl 268 2 Cooling power kW
Set temperature (°C) (read/set)
Element Offset Length/Bit Description Unit/Selections
Prozeß‐ Wasserkrei_Wassertemp
28 2 Set value °C
daten: _PAR_TSollwert
Inlet temperature (°C) (actual value)
Element Offset Length/Bit Description Unit/Selections
Wasserkrei_Wassertemp_
Flag: 134 2 Inlet temperature °C
AI_TRuecklauf
Outlet temperature (°C) (actual value)
Element Offset Length/Bit Description Unit/Selections
Wasserkrei_Wassertemp_
Flag: 132 2 Outlet ‐ raw °C
AI_TVorlaufEx
Water pressure (Bar) (actual value)
Element Offset Length/Bit Description Unit/Selections
Wasserkrei_Druck_AI_
Flag: 66 2 Pressure bar
Druck
Remote start
Element Offset Length/Bit Description Unit/Selections
IO: SysFkt_DI_Extern 1 Bit 0 Remote start 0 = OFF, 1 = ON
Read parameter/communication with controller
• Set the set temperature via „process data“. See „controller communication“ protocol
chapter 3.7
• The actual values (status data) can be read via „ask for status data“. See “controller
communication” protocol chapter 3.3
22
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
5.
V 1.1
Parameter via RS232 - interface
Examples
red are the special data of your command (use these)
the checksum will be calculated by your transmit routine
For more information and examples see protocol „controller communication“.
Set set temperature (e. g. 21.0 °C)
Host Î CCC (commando „set process data“)
Name Offset Value Description
dez hex
LEN 0 0C Command-/reference data length byte
DST 1 01 Destination adress
SRC 2 00 Source adress
CMD1 3 91 Command byte 1
CMD2 4 00 Command byte 2
Offset (long) 5‐8 12 00 00 00 32bit-number, defines the offset within the
parameter block
Wert (long) 9‐12 D2 00 00 00 32bit-number, contains the value to set t
Länge (long) 13‐16 02 00 00 00 32bit-number, defines the length of the
value (byte = 1, short = 2, long = 4)
CHKSUM 17 ## Checksum byte (if not calculated: 26h)
Host Í CCC
0AAh(= correct checksum) within 0.2 s
(no reponse)
23
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
5.
V 1.1
Parameter via RS232 - interface
Auslesen der IST‐Wassertemperatur
Host Î CCC (request status data partial [here FLAG‐data])
Name Offset Value Description
dez hex
LEN 0 03 Command-/reference data length byte
DST 1 01 Destination adress
SRC 2 00 Source adress
CMD1 3 13 Command byte 1
CMD2 4 02 Command byte 2
tt = 01h: of IO‐data
tt = 02h: of Flag‐ data
tt = 03h: of Parameter‐ data
tt = 04h: of System‐ data
tt = 05h: of Process‐ data
OFFSET_L 5 82 Offset, low order byte
OFFSET_H 6 00 Offset, high order byte
LENGTH 7 02 Number of retransfered bytes (< 240)
CHKSUM 8 ## Checksum byte (if not calculated: 0Dh)
Host Í CCC
0AAh (= correct checksum) within 0.2 s
Host Í CCC (data / value answer)
Name Offset Value Description
dez hex
LEN 0 nn Reference data length byte (you may
ignore)
DST 1 00 Destination adress (you may ignore)
SRC 2 01 Source adress (you may ignore)
CMD1 3 13 Command byte 1 (you may ignore)
CMD2 4 02 Command byte 2 (you may ignore)
REQ‐DATA 5‐6 LL temperatur *10 (16 Bit‐value, low byte first)
HH
CHKSUM 7 ## Checksum byte (you may ignore)
Example: 25.0 °C, LL HH is (FAh 00h)
24
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
5.
V 1.1
Parameter via RS232 - interface
Read set temperature
Host Î CCC (request status data partial [here process‐data])
Name Offset Value Description
dez hex
LEN 0 3 Command-/reference data length byte
DST 1 01 Destination adress
SRC 2 00 Source adress
CMD1 3 13 Command byte 1
CMD2 4 05 Command byte 2
tt = 01h: of IO‐data
tt = 02h: of Flag‐ data
tt = 03h: of Parameter‐ data
tt = 04h: of System‐ data
tt = 05h: of Process‐ data
OFFSET_L 5 12 Offset, low order byte
OFFSET_H 6 00 Offset, high order byte
LENGTH 7 02 Number of retransfered bytes (< 240)
CHKSUM 8 ## Checksum byte (if not calculated: 0Dh)
Host Í CCC
0AAh (= correct checksum) within 0.2 s
Host Í CCC (data / value answer)
Name Offset Value Description
dez hex
LEN 0 nn Reference data length byte (you may
ignore)
DST 1 00 Destination adress (you may ignore)
SRC 2 01 Source adress (you may ignore)
CMD1 3 13 Command byte 1 (you may ignore)
CMD2 4 05 Command byte 2 (you may ignore)
REQ‐DATA 5‐6 LL temperatur *10 (16 Bit‐value, low byte first)
HH
CHKSUM 7 ## Checksum byte (you may ignore)
Example: 25.0 °C, LL HH is (FAh 00h)
25
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
6.
V 1.1
F. A. Q.
6. F. A. Q.
Please try to solve your problems with this F.A.Q. bevor contacting TERMOTEK.
My computer does not communicate with the TERMOTEK chiller via the visualisation software
1. Check the connection between the chiller (RS232 – connector and the computer.
2. Check that the computer uses the correct interface (normally COM 1 or COM 2). These must
be adjusted in the visualisation software.
3. The TERMOTEK chiller is delivered with an interface speed of 38,400 Baud normally, the
computer is set to 9,600 Baud mostly. You can change the speed via system control as follows:
1 2
26
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
6.
V 1.1
F. A. Q.
3 4
5
You can change the interface speed at the chiller at system functions/baudrate. TERMOTEK
suggest to change the speed at your computer.
I want to use my own software to enable/disable the chiller. Which command have I to use?
IOs: Element Offset Length/Bit Description Unit/Selections
SysFkt_DI_Extern 1 Bit 0 Remote start 0 = OFF, 1 = ON
Two parameters for the output of the water temperature are available (<<Wasserkrei_Wassertemp‐
AI‐TVorlaufRohEx>> at IOs and <<Wasserkrei_Wassertemp_AI_TVorlaufEx>> at flags) Both
transmit a reasonnable value. What is the difference?
<<Wasserkrei_Wassertemp_AI_TVorlaufEx>> is eventually admit with an
additional ajustment value. Calibrations will affect then.
We want to read all warnings, errors and alarms. How?
Read these via <<STAT_message>>. See chapter 5 for a description of this
parameter.
27
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com