Manual CCC3 V1.1 Eng

Download as pdf or txt
Download as pdf or txt
You are on page 1of 27

V 1.

CENTRAL CHILLERCONTROLL 3

PID-controll-unit for Termotek Laserkühlung

1
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
V 1.1

Contents

1. GENERAL NOTES........................................................................................................... 3

1.2. UNIQUE CONTROL FEATURES ......................................................................................... 3


1.3. SPECIAL BUTTON ASK ..................................................................................................... 3
1.4. SHEME OF CONTROL ELEMENTS...................................................................................... 4

2. POSIBILITIES TO ADJUST........................................................................................... 5

2.1. FIRST PROGRAMMING LEVEL ......................................................................................... 5


2.1.1 ADJUSTABLE PARAMETER ................................................................................... 5
2.1.2 PARAMETER DESCRIPTION .................................................................................. 5
2.2. SECOND PROGRAMMING LEVEL (USER-LEVEL)............................................................. 6
2.2.1 ADJUSTABLE PARAMETER ................................................................................... 7
2.2.2 Parameter Description .................................................................................................... 8
2.3. THIRD PROGRAMMING LEVEL (TECHNICIAN-LEVEL) ................................................... 9
2.3.1 Adjustable Parameters.................................................................................................... 9
2.3.2 Parameter Description .................................................................................................. 11
2.4. FOURTH PROGRAMMING LEVEL (ADMINISTRATOR-LEVEL) ...................................... 16
2.4.1 Adjustable Parameters.................................................................................................. 16
2.4.2 Parameter Description .................................................................................................. 17

3. CIRCUIT DIAGRAM..................................................................................................... 19

4. EVOLUTION .................................................................................................................. 20

5. PARAMETER VIA RS232 ‐ INTERFACE ................................................................. 21

6. F. A. Q. ............................................................................................................................. 26

2
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
1.
V 1.1
General Notes

1. General Notes

Picture 1-1

1.2. Unique Control Features


The controller is optimised for water cooling laser systems with bypass regulation.
After re-starting (starting point below/above the set value) maximum heating/cooling power will be
used to reach the accordant value.
On the one hand, the analysis of the flow rate sensors is monitored on the front panel display ( with
time delay for starting), on the other hand the signal (for release) would be send directly to the digital
output (“1” = release)

1.3. Special Button Ask

Pressed Button Function


- display the set value
ESC
- menue level back


- menue
- confirm
- chiller on/off
↑ - menue point up
- value up
- disable beeper
← - menue level forward
- position left
- menue level forward
→ - position right
- info


- menue level down
- value down

3
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
1.
V 1.1
General Notes

1.4. Sheme of control elements


The operational mode is indicated by lighting of the green LED. If a fault occurs, the
red LED will light. It depends to the fault and the adjusted parameters whether the
chiller discontinues operating. The beeper can be disabled by pressing the mute-
button (←). The error messages are self-explanatory by pressing the info-button
(→). The appeard fault can be accepted by pressing the Quit-button (↓). If remote
start is enabled, the fault can only be accepted by the remote start signal. The
chiller restarts autonomously when the green LED lights.

errorr LED

operational mode LED display

ENTER/menue
ESCAPE/set value

UP/on/off
LEFT/mute
RIGHT/roll/info

DOWN/quit

Picture 1-2

4
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

2. Posibilities To Adjust

2.1. First Programming Level


Set value adjusting

By pressing the ESCAPE-button (ESC), you can reach the set value display (1st
programming level). By pressing the UP- and DOWN-button (↑↓) you can adjust the
value of the digit, with the RIGHT- and DOWN-button (← →) you can choose the
digit. The set value is affirmed by pressing the ENTER-button (↵), you can cancel
the input by pressing the ESCAPE-button (ESC). Adjusting the set value is only
possible in the specified range. (Water temp. Func./Lower set value limit; Water temp.
Func./Upper set value limit).

Picture 2-1

2.1.1 Adjustable Parameter


Function Range Default Customer
setting
Set value Lower/upper set value limit 20,0 °C

2.1.2 Parameter Description


Set Value
Here you can adjust the set value, the water is cooled or heated to reach this temperature.

5
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

2.2. Second Programming Level (User-level)

Adjusting parameters

By pressing the ENTER-button (↵), you can reach the 2nd programming level.
Therefore, please enter your user-password (0020). By pressing the UP- and
DOWN-button (↑↓) you can adjust the value of the digit, with the RIGHT- and
DOWN-button (← →) you can choose the digit. The set value is affirmed by
pressing the ENTER-button (↵), you can cancel the input by pressing the ESCAPE-
button (ESC).

Picture 2-2
Here you have the possibilty to adjust the following parameters
Æ Language
All other parameters cannot be adjusted
Æ Filling
Æ Water level because these could damage the function of
Æ System function the chiller. Please contact Termotek.
Æ control function
Choose the wished paramater and confirm with the ENTER-button (↵). To save the
action press the ESCAPE-button (ESC) until following display appears (Picture 2-3)
(Save changes? YES = Enter)

6
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

Picture 2-3
You can confirm with the ENTER-button (↵) or abort with The ESCAPE-button
(ESC) and return to the start display.

2.2.1 Adjustable Parameter


Function Range Default Customer
setting

Language GERMAN GERMAN


ENGLISH
Fill

Water level/Switch off output NO/YES NO


Water level/Level monitor DISABLE/ENABLE DISABLE
Water level/RelayW-level W-WARNING ENABLE/ W-ALARM
W-ALARM ENABLE

System function/Beeper ON/OFF/IF ON


OPERATION
System function/Rolling menue ON/OFF ON
System function/Operating hours Only read out
System function/Starting mode KEY/LINE/REMOTE KEY
START/START FLAG
System function/Temperature scale °C / °F °C
System function/Baud rate 9.600, 14.400, 19.200, 38.400
28.800, 38.400, 57.600

Control functions/Pump operation hours Only read out


Control functions/Hot gas valve operation Hours Only read out

Control functions/PID-Control/dT increase start -99.9 … 99.9 K 1.0 K


Control functions/PID-Control/dT-increase 100 … 500 % 100 %

7
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

2.2.2 Parameter Description


Language
Choose the required language for display.
Fill
This mode is required to fill and to drain the unit:
Starting the filling mode is only possible if the controller is switched off („starting mode“ = key) or
remote start („starting mode” = line) is disabled.
If the fill mode is enabled, it can be started by switching off the chiller and on again. While the
filling mode is active, no alarm messages are monitored (only for a defined period Î System
function/Advanced/Long term rejection).

Water level/

Switch off output


This allows the disabling of the outputs at water level alarm to be prohibited. In this case,
simultaneous operation together with the flow alarm will be prevented (i.e. Switch off output =
YES) => at water alarm, no flow alarm will be given.
Level monitor
Monitors the water level via bar on the display.
RelayW-level

System functions/

Beeper
No beeper will sound except warning at filling mode.
Rolling mode
The different values will appear succesive.
Operation hours
Read out the hours of operation.
Starting mode
The controller can switched on or off using either the UP-button (↑) on the front panel, the
remote start input or the start flag (via RS232 – connector).
If the remote start input is used to enable the outputs, then the controller is always on.
Using the starting mode line, the chiller will start as soon as voltage is enable.
Temperature scale
The unit can be switched between Fahrenheit and Celsius. Despite changing this unit, the
parameter and set value and adjustment range remain the same. Only the display shows °F!
Baud rate
Adjust speed of the RS232 interface.

Control functions/

Pump operation hours


Read out the operational hours of pump.
Heating operation hours
Read out the operational hours of heating.

Control functions/PID-control

dT-increase start
Start temperature of temperature control.
dT-increase
Heats/cools the chiller without control until dT-increase start is reached Use only at laboratory
operation!
8
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

2.3. Third Programming Level (Technician-level)

For some paramters you have to enter the technician-password. The third programming level is on the
same kind reachable as the second one.

2.3.1 Adjustable Parameters


Function Range Default Customer
setting

Conduct. func./Alarm conductivity 0.0 – 99.9 µS 20.0 µS


Conduct. func./Pre alarm conductivty 0.0 – 99.9 µS 8.0 µS
Conduct. func./Alarm delay 0 ... 999 s 10 S
Conduct. func./Conductivity valve-off 0.0 – 99.9 µS 4 µS
Conduct. func./Conductivity valve-on 0.0 – 99.9 µS 6 µS

System function/Advanced/Error relays ALARM/RELEASE ALARM


System function/Advanced/Longterm rejection 0 ... 999 s 100 s
System function/Advanced/Limit value ambient temp. 0 ... 100 °C 40 °C
System function/Advanced/Change relay output BREAKER/CLOSER CLOSER
System function/Advanced/Change relay input BREAKER/CLOSER CLOSER
System function/Advanced/Reset parameter WARNING DANGER

Control functions/PID-control/PID control P-part 0 ... 500 % 50 %


Control functions/PID-control/PID control I-part 0 ... 500 % 10 %
Control functions/PID-control/PID control D-part 0 ... 500 % 10 %
Control functions/PID-control/PID-Optimize ON/OFF ON
Control functions/PID-control/control cycle normal 5 … 30 s 8s
Control functions/PID-control/control cycle fast 1 … 10 s 2s

Control functions/Compressor/Switch off point comp. -99.9 ... 99.9 K -2.0 K


Control functions/Compressor/Switch on point comp. -99.9 ... 99.9 K -1.0 K
Control functions/Compressor/LP-sensor mode REGULAR FUNCTION/ REGULAR
DISABLE SENSOR FUNCTION
Control functions/Compressor/HP-sensor mode REGULAR FUNCTION/ REGULAR
DISABLE SENSOR FUNCTION
Control functions/Compressor/Compress. off if HP/LP NO/YES NO
Control functions/Compressor/Time out compressor 0 ... 999 s 30 s

Control functions/Heating/Swich off point heating -99.9 ... 99.9 K -2.0 K


Control functions/Heating/Swicht on point heating -99.9 ... 99.9 K -5.0 K

Control functions/Ventilator/Minimum engine speed 0 ... 100 % 50 %


Control functions/Ventilator/Temp fan max speed 0 ... 100 °C 40 °C
Control functions/Ventilator/Temp fan min speed 0 ... 100 °C 20 °C
Control functions/Ventilator/Fan control CONTROLLED/ CONTROLLED
ALWAYS MAX/
TWO POINT
Control functions/Ventilator/Max. temp 0 ... 100 °C 40 °C

Control functions/Hot gas valve/Valve cycle 0 … 50 s 10 s


Control functions/Hot gas valve/Start on 0 … 100 s 5s
Control functions/Hot gas valve/Operation hours Only read out

Control functions/Switch use H./C. contact/Heating HEATING CONTACT/ HEATING


contact COOLING CONTACT CONTACT

Sensor functions/Correction F1 -9.9 ... 9.9 K 0.0 K


Sensor functions/Correction F2 -9 ... 9 K 0K
9
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

Function Range Default Customer


setting
Sensor functions/Correction F3 -9 ... 9 K 0K
Sensor functions/Correction F4 -9.9 ... 9.9 K 0.0 K

Pressure func./Switch off output NO/YES NO


Pressure func./Starting delay 0 ... 99 s 5s
Pressure func./Upper limit 0.0 ... 99.9 bar 5.0 bar
Pressure func./Lower limit 0.0 ... 99.9 bar 1.0 bar

Pressure func./Advanced/Pressure sensor 4 mA 0.0 ... 99.9 bar 0.0 bar


Pressure func./Advanced/Pressure sensor 20 mA 0.0 ... 99.9 bar 10.0 bar

Flow 1 Funct./Lower limit 0.0 ... 99.9 l/min 1.5 l/min


Flow 1 Funct./Upper limit 0.0 ... 99.9 l/min 4.5 l/min
Flow 1 Funct./Pre alarm flow 0.0 ... 99.9 l/min 2.0 l/min
Flow 1 Funct./Starting delay 0 ... 99 s 10 s

Flow 1 Funct./Advanced/Signal type DISABLE/TURBINE/ DISABLE


SWITCH
Flow 1 Funct./Advanced/Impulse performance 0 ... 9999 Imp/l 1000 Imp/l
Flow 1 Funct./Advanced/Switch off output NO/YES NO
Flow 1 Funct./Advanced/Error message if off NO/YES NO

Flow 2 Funct./Lower limit 0.0 ... 99.9 l/min 1.5 l/min


Flow 2 Funct./Upper limit 0.0 ... 99.9 l/min 4.5 l/min
Flow 2 Funct./Pre alarm Flow 0.0 ... 99.9 l/min 2.0 l/min
Flow 2 Funct./Starting delay 0 ... 99 s 10 s

Flow 2 Funct./Advanced/Signal type DISABLE/TURBINE/ DISABLE


SWITCH
Flow 2 Funct./Advanced/Impulse performance 0 ... 9999 Imp/l 1000 Imp/l
Flow 2 Funct./Advanced/Switch off output NO/YES NO
Flow 2 Funct./Advanced/Error message if off NO/YES NO

Water temp. Func./Lower set value limit -99.0 ... 32.0 °C 15.0°C
Water temp. Func./Upper set value limit 15.0 ... 999.0 °C 32.0 °C

Water temp. Func./Warning at .../Analysis ABSOLUTE/RELATIVE ABSOLUTE


ABSOLUTE
Water temp. Func./Warning at .../High temp. warning -99.9 ... 99.9 °C 25 °C
Water temp. Func./Warning at .../Low temp. warning -99.9 ... 99.9 °C 15 °C

Water temp. Func./Alarm at .../Analysis ABSOLUTE ABSOLUTE/RELATIVE ABSOLUTE


Water temp. Func./Alarm at .../High temp. alarm -99.9 ... 99.9 °C 30 °C
Water temp. Func./Alarm at .../Low temp. alarm -99.9 ... 99.9 °C 15 °C

Water temp. Func./Shut down/Shut down max. water- NO/YES NO


temp
Water temp. Func./Shut down/Shut down 10.0 ... 150.0 °C 50 °C
temperature
Water temp. Func./Shut down/Relay F1 0 … 999 s 0s

Water temp. Func./delay high temp. 0 ... 999 s 0s


Water temp. Func./delay low temp. 0 ... 999 s 0s
Water temp. Func./increase value 0.0 … 9.9 °C 0.0 °C

Password/Soft-Vers. Only read out


Password/Par.-Vers. Only read out
Password/Syspar-Vers. Only read out
Password/Proc.-Vers. Only read out
10
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

Function Range Default Customer


setting
Password/Kali-Vers. Only read out
Password/Password user 0 ... 9999 0020
Password/Password technician 0 … 9999 0021
Password/Password administrator 0 … 9999 XXXX

Calibration/Analog outputs
Calibration/Analog inputs

Diagnosis/Digital outputs
Diagnosis/Digital inputs
Diagnosis/Analog outputs
Diagnosis/Analog inputs

2.3.2 Parameter Description


Conduct. func./

Alarm conductivity
Conductivity alarm if this limit is exceeded. The corresponding message appears on the display
and the according relay output switches.
Pre alarm conductivity
Alarm if this limit is exceeded („cooling contact with hysteris 1mS“).The corresponding message
appears on the display.
Alarm delay
The conductiviy alarm will be surpressed for the set time in case of a error.
Conductivity valve-off
Switching point ventile OFF if enable.
Conductivity valve-on
Switching point ventile ON if enable.

System function/Advanced/

Error relay
Alarm relay: closed in case of alarm.
Release relay: closed if no alarm and the controller is on.
Longterm rejection
All Alarm messages are surpressed for the set time if the filling mode is active.
Limit value ambient temp.
Alarm limit value for the ambient temperature. The according relay output switches n case
of alarm.
Change relay output
The switch use of the outputs can be inverted here.
Change relay input
The switch use of the inputs can be inverted here.
Reset parameter WARNING DANGER
Reset parameter to factory settings. All edited settings made by you and by Termotek will
be lost!

11
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

Control functions/PID-control/

PID control P-part


Proportional part
PID control I-part
Integral part
PID control D-part
Derivative part
PID-optimizing
Optimizes the PID – values. These values will be used at next start.
Control cycle normal
Interval time of hot gas valve between two cycles.
Control cycle fast
Interval time of hot gas valve between two cycles.

Control functions/Compressor/

Compressor switch off point


Compressor switch on point
Switching limits for compressor contact (relative to set value).
LP-sensor mode
Low pressure switch for cooling circuit.
HP-sensor mode
High pressure switch for cooling circuit.
Compressor off at HP/NP
Choose YES if the compressor should be switched off in case of high/low pressure alarm.
Time out compressor
Restarting the compressor is disabled for this defined period. An according message
appears on the display.

Control functions/Heating/

Switch off point heating


Switch on point heating
Switching limits for the heating.

Control functions/Ventilator/

Minimum engine speed


This speed defines the minimum speed of fan operation unless the controller is disabled.
Temp max engine speed
Temp min engine speed
This defines the temperature control range for the fan speed.
Ventilator control
Either the fan runs with full speed or the fan is controlled by ventilator control. An
additional switch off/on point can be set.
Max. temp
Temperature limit, the message „clean condensor“ appears on the display if exceeded.

Control functions/Switch use H./C. contact/

Heating contact
Switches the hot gas valve, heating or cooling.

12
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

Sensor functions/

Correction F1 (water temperature)


Correction F2 (ambient temperaturer)
Correction F3 (exhaust air temperature)
Correction F4 (inlet temperature)
Adjust sensor inlet F1 – F4.

Pressure func./

Switch off output


The chiller will be switched off in case of HP/LP alarm if enable.
Starting delay
Maximum period of time which may pass from starting the compressor until the minimum
pressure is established.
Upper limit
Lower limit
Pressure alarm will be set off if pressure leaves these limits. Output will be switched off
(Pressure func./Switch off output) if enabled.

Pressure func./Advanced/

Pressure sensor 4 mA
Pressure sensor 20 mA
Calibration

Flow ½ funct./

Lower limit
The flow alarm will be set off in case of falling below the limit (after end of starting delay).
Upper limit
The flow alarm will be set off in case of exceeding the limit (after end of starting delay).Der
Pre alarm flow
If flow falls below this value, a flow warning will be released via the display and the interface.
Starting delay
Maximum period of time which may pass from starting the pump until the minimum flow is
established.

Flow ½ funct./Advanced/

Signal type
DISABLE Î switched off
TURBINE Î pulse interpretation
SCHALTER Î digital input
Impulse performance
Calibration of flow sensor: How many pulses per litre?
Switch off output
The output will be switched off in case of quitting the reference between lower and upper
limit if enable.
Error message while off
Flow alarm when the chiller is switched off.

13
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

Water temp. Func./

Lower set value limit


Lowest adjustable limit for set temperature.
Upper set value limit
Highest adjustable limit for set temperature.

Water temp. Func./Warning at .../

Analysis ABSOLUTE

High temp. warning


Definition of temperature warning, the warning will be released via the display and the
interface.
Low temp. warning
Definition of temperature warning, the warning will be released via the display and the
interface.

Water temp. Func./Alarm at .../

Analysis ABSOLUTE

High temp. alarm


Definition of temperature alarm, the alarm will be released via the display and the interface.
Output will be switched off.
Low temp. alarm
Definition of temperature alarm, the alarm will be released via the display and the interface.
Output will be switched off.
Water temp. Func./Shut down/

Shut down max. water-temperature


The chiller will be switched off if the shut down temperature is exceeded.
Shut down temperature
Definition of shut down temperature.

Water temp. Func./

Delay high temp.


Maximum period of time which may pass from starting the chiller until the excess temperature is
exceeded.
Delay low temp.
Maximum period of time which may pass from starting the chiller until the insufficient
temperature is under-run.
Increase value
This value is added to the max. ambient temperature. When the ambient temperature > this
value, the set point will be increased proportionally.

14
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

Password/

Soft-Vers.
Actual software version
Par. Vers.
Actual parameter version
Syspar-Vers.
Actual system-parameter version
Proc.-Vers.
System information
Kali-Vers.
System information
Password user
Change user password
Password technician
Change technician password
Password administrator
Change administrator password

Calibration/

Analog outputs
Analog inputs

Diagnosis/

Digital outputs
Digital inputs
Analog outputs
Analog inputs

15
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

2.4. Fourth Programming Level (Administrator-Level)


For some paramters you have to enter the administrator-password. The third programming level is on
the same kind reachable as the second and third one.

2.4.1 Adjustable Parameters


Function Range Default Customer
setting

Conduct. func./Advanced/Conductivity control DISABLE/ENABLE ENABLE


Conduct. func./Advanced/Conductivity measuring DISABLE/ENABLE ENABLE
Conduct. func./Advanced/Rinse start temp. -35 … 99 °C 40 °C
Conduct. func./Advanced/Interval rinsing 0 … 999 s 0s
Conduct. func./Advanced/Duration rinsing 0 … 999 s 0s

System function/Operation hour/Part RESET


System function/Operation hour/Complete RESET

System function/Advanced/Advanced/Cooling DISABLE/TURBINE DISABLE


power monitoring 1/ TURBINE 2/
TURBINE 1+2
System function/Advanced/Advanced/Switch off OFF/ON OFF
max. ambient temp.
System function/Advanced/Advanced/Prop valve NO/YES NO

Control functions/Compressor/Hours op. RESET

Control functions/Heating/Hours op. RESET

Control functions/Hot gas valve/Hours op. RESET

Control functions/Pump/Hours op. RESET

Sensor functions/Switch off F2 DISABLE SENSOR/ REGULAR


REGULAR FUNCTION
FUNCTION
Sensor functions/Switch off F3 DISABLE SENSOR/ REGULAR
REGULAR FUNCTION
FUNCTION
Sensor functions/Switch off F4 DISABLE SENSOR/ REGULAR
REGULAR FUNCTION
FUNCTION

Pressure func./Advanced/Pressure gauge DISABLE/ENABLE ENABLE

16
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

2.4.2 Parameter Description


Conduct. func./Advanced/

Conductivity control
Enables conductivity control
Conductivity measuring
Enables conductivity measuring
Rinse start temp.
When this temperature is reached, the rinsing of the de-ionising cartridge will be started.
Only possible with DI – control.
Interval rinsing
Interval between two rinsing sequences
Duration rinsing
Duration of a rinsing sequence

System function/Operation hour/

Part

Complete
Reset the operation hour of the chiller.

System function/Advanced/Advanced/

Cooling power monitoring


The performed cooling power is affected by the difference between in- and outlet
temperature and flow. Can be disabled or enabled.
Switch off max ambient temp.
The chiller will be switched off if the ambient temperture limit is exceeded. (Control
functions/Ventilator/Max. temp). Can be disabled or enabled.
Proportional valve
If enabled, a PWM – signal will be send from the CCC. It will be analyzed by an
external flat module and converted into a 0 – 10 V signal.

Control functions/Compressor/

Hours op.
Reset operation hours of compressor (for example at replacement).

Control functions/Heating/

Hours op.
Reset operation hours of heating (for example at replacement).

Control functions/Heissgas-Ventil/

Hours op.
Reset operation hours of hot gas valve (for example at replacement).

Control functions/Pumpe/

Hours op.
Reset operation hours of pump (for example at replacement).

17
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
2.
V 1.1
Posibilities To Adjust

Sensor functions/

Switch off F2
If the sensor inlet (normally ambient temperature sensor) is not required it can be switched off.
In this case it is set to 20.0 °C internally (unattached of a eventually mounted sensor).
Switch off F3
If the sensor inlet (normally condensor block temperature sensor) is not required it can be
switched off. In this case it is set to 20.0 °C internally (unattached of a eventually mounted
sensor).
Switch off F4
If the sensor inlet (normally inlet temperature sensor) is not required it can be switched off. In
this case it is set to 20.0 °C internally (unattached of a eventually mounted sensor).

Pressure func./Advanced/

Pressure gauge
Can be disabled or enabled.

18
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
3.
V 1.1
Circuit diagram

3. Circuit diagram

Picture 3-1

19
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
4.
V 1.1
Evolution

4. Evolution
pos date version change
01 2006 V067 Software update
02
03
04
05

20
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
5.
V 1.1
Parameter via RS232 - interface

5. Parameter via RS232 ‐ interface 
 
Please ask for your parameter sheet at TERMOTEK AG. We need the type designation and the serial 
number. Please hold them ready. 
 
We will send you a RS232 – protocol if required. 
 
Request of warning and alarm signals via <<STAT_Message>> 
 
bit  description 
0  OK 
1  Warning water level 
2  Warning flow 1 
3  Warning flow 2 
4  Warning conductivity 
5  Warning high tempterature 
6  Warning low temperature  
7  Temperature condensor block too high 
8  Alarm 
9  Alarm high temperature 
10  Alarm low temperature 
11  F2 – error (normally ambient temperature sensor) 
12  F3 – error (normally condensor block temperature sensor) 
13  F4 – error (normally inlet temperature sensor) 
14  Error refrigerant ciruit 
15  High pressure refrigerant circuit 
16  Low pressure refrigerant circuit 
17  Error water circuit 
18  Alarm water level 
19  Alarm ambient temperature 
20  Alarm conductivity 
21  Alarm flow 1 too low 
22  Alarm flow 2 too low 
23  Alarm flow 1 too high 
24  Alarm flow 2 too high 
25  Alarm high temperature 
26  Alarm high pressure water circuit 
27  Alarm low pressure water circuit 
28  F1 – error (normally water circuit temperature sensor) 
 
 

21
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
5.
V 1.1
Parameter via RS232 - interface

Request of measured values (if required options are installed) 
Flow 1 (l/min) (actual value) 
  Element  Offset  Length/Bit  Description  Unit/Selections 
Wasserkrei_DFL1_AI 
IO:  44  2  Flow 1  l/min 
_Fluss 
 
Flow 2 (l/min) (actual value) 
  Element  Offset  Length/Bit  Description  Unit/Selections 
Wasserkrei_DFL2_AI 
IO:  50  2  Flow 2  l/min 
_Fluss 
 
Conductivity (μS) (actual value) 
  Element  Offset  Length/Bit  Description  Unit/Selections 
Wasserkrei_Leitwert_ 
IO:  56  2  Conductivity  μS 
AI_Leitwert 
 
Cooling power (W) (actual value) 
  Element  Offset  Length/Bit  Description  Unit/Selections 
Flag  PKuehl  268  2  Cooling power  kW 
 
Set temperature (°C) (read/set) 
  Element  Offset Length/Bit  Description  Unit/Selections 
Prozeß‐ Wasserkrei_Wassertemp 
28  2  Set value  °C 
daten:  _PAR_TSollwert 
 
Inlet temperature (°C) (actual value) 
  Element  Offset  Length/Bit  Description  Unit/Selections 
Wasserkrei_Wassertemp_ 
Flag:  134  2  Inlet temperature  °C 
AI_TRuecklauf 
 
Outlet temperature (°C) (actual value) 
  Element  Offset  Length/Bit  Description  Unit/Selections 
Wasserkrei_Wassertemp_ 
Flag:  132  2  Outlet ‐ raw  °C 
AI_TVorlaufEx 
 
Water pressure (Bar) (actual value) 
  Element  Offset  Length/Bit  Description  Unit/Selections 
Wasserkrei_Druck_AI_ 
Flag:  66  2  Pressure  bar 
Druck 
 
Remote start 
  Element  Offset  Length/Bit  Description  Unit/Selections 
IO:  SysFkt_DI_Extern  1  Bit 0  Remote start  0 = OFF, 1 = ON 
 
 
Read parameter/communication with controller 
• Set the set temperature via „process data“. See „controller communication“ protocol 
chapter 3.7 
• The actual values (status data) can be read via „ask for status data“. See “controller 
communication” protocol chapter 3.3 
 

22
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
5.
V 1.1
Parameter via RS232 - interface

Examples 
 
red are the special data of your command (use these) 
the checksum will be calculated by your transmit routine 
 
For more information and examples see protocol „controller communication“. 
 
Set set temperature (e. g. 21.0 °C) 
Host Î CCC (commando „set process data“) 
 
Name  Offset  Value  Description 
dez  hex 
LEN  0  0C  Command-/reference data length byte 
DST  1  01  Destination adress 
SRC  2  00  Source adress 
CMD1  3  91  Command byte 1 
CMD2  4  00  Command byte 2 
Offset (long)  5‐8  12 00 00 00  32bit-number, defines the offset within the
parameter block 
Wert (long)  9‐12  D2 00 00 00  32bit-number, contains the value to set t 
Länge (long)  13‐16  02 00 00 00  32bit-number, defines the length of the
value (byte = 1, short = 2, long = 4)
CHKSUM  17  ##  Checksum byte (if not calculated: 26h) 
  
Host Í CCC 
0AAh(= correct checksum) within 0.2 s 
 
(no reponse) 
 
 

23
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
5.
V 1.1
Parameter via RS232 - interface

Auslesen der IST‐Wassertemperatur 
Host Î CCC (request status data partial [here FLAG‐data]) 
 
Name  Offset  Value Description 
dez  hex 
LEN  0  03  Command-/reference data length byte 
DST  1  01  Destination adress 
SRC  2  00  Source adress 
CMD1  3  13  Command byte 1 
CMD2  4  02  Command byte 2 
tt = 01h: of IO‐data  
tt = 02h: of Flag‐ data  
tt = 03h: of Parameter‐ data  
tt = 04h: of System‐ data  
tt = 05h: of Process‐ data  
OFFSET_L  5  82  Offset, low order byte 
OFFSET_H  6  00  Offset, high order byte 
LENGTH  7  02  Number of retransfered bytes (< 240) 
CHKSUM  8  ##  Checksum byte (if not calculated: 0Dh) 
 
Host Í CCC 
0AAh (= correct checksum) within 0.2 s 
 
 
Host Í CCC (data / value answer) 
 
Name  Offset  Value Description 
dez  hex 
LEN  0  nn  Reference data length byte (you may 
ignore) 
DST  1  00  Destination adress (you may ignore) 
SRC  2  01  Source adress (you may ignore) 
CMD1  3  13  Command byte 1 (you may ignore) 
CMD2  4  02  Command byte 2 (you may ignore) 
REQ‐DATA  5‐6  LL  temperatur *10 (16 Bit‐value, low byte first) 
HH 
CHKSUM  7  ##  Checksum byte (you may ignore) 
 
Example: 25.0 °C, LL HH is (FAh 00h) 
 
 

24
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
5.
V 1.1
Parameter via RS232 - interface

Read set temperature 
Host Î CCC (request status data partial [here process‐data]) 
  
Name  Offset  Value Description 
dez  hex 
LEN  0  3  Command-/reference data length byte 
DST  1  01  Destination adress 
SRC  2  00  Source adress 
CMD1  3  13  Command byte 1 
CMD2  4  05  Command byte 2 
tt = 01h: of IO‐data  
tt = 02h: of Flag‐ data  
tt = 03h: of Parameter‐ data  
tt = 04h: of System‐ data  
tt = 05h: of Process‐ data  
OFFSET_L  5  12  Offset, low order byte 
OFFSET_H  6  00  Offset, high order byte 
LENGTH  7  02  Number of retransfered bytes (< 240) 
CHKSUM  8  ##  Checksum byte (if not calculated: 0Dh) 
 
Host Í CCC 
0AAh (= correct checksum) within 0.2 s 
 
 
Host Í CCC (data / value answer) 
 
Name  Offset  Value Description 
dez  hex 
LEN  0  nn  Reference data length byte (you may 
ignore) 
DST  1  00  Destination adress (you may ignore) 
SRC  2  01  Source adress (you may ignore) 
CMD1  3  13  Command byte 1 (you may ignore) 
CMD2  4  05  Command byte 2 (you may ignore) 
REQ‐DATA  5‐6  LL  temperatur *10 (16 Bit‐value, low byte first) 
HH 
CHKSUM  7  ##  Checksum byte (you may ignore) 
 
Example: 25.0 °C, LL HH is (FAh 00h) 
 
 

25
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
6.
V 1.1
F. A. Q.

6. F. A. Q. 
 
Please try to solve your problems with this F.A.Q. bevor contacting TERMOTEK. 
 
My computer does not communicate with the TERMOTEK chiller via the visualisation software 
 
1. Check the connection between the chiller (RS232 – connector and the computer. 
2. Check that the computer uses the correct interface (normally COM 1 or COM 2). These must 
be adjusted in the visualisation software. 

 
 

 
 
3. The  TERMOTEK  chiller  is  delivered  with  an  interface  speed  of  38,400  Baud  normally,  the 
computer is  set to 9,600 Baud mostly. You can change the speed via system control as follows: 
 
1  2

   

26
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com
6.
V 1.1
F. A. Q.

3  4

   
5     

 
 
You  can  change  the  interface  speed  at  the  chiller  at  system  functions/baudrate.  TERMOTEK 
suggest to change the speed at your computer. 
 
I want to use my own software to enable/disable the chiller. Which command have I to use? 
 
IOs:  Element  Offset  Length/Bit  Description  Unit/Selections 
  SysFkt_DI_Extern  1 Bit 0  Remote start  0 = OFF, 1 = ON 
 
Two parameters for the output of the water temperature are available (<<Wasserkrei_Wassertemp‐
AI‐TVorlaufRohEx>> at IOs and <<Wasserkrei_Wassertemp_AI_TVorlaufEx>> at flags) Both 
transmit a reasonnable value. What is the difference? 
 
<<Wasserkrei_Wassertemp_AI_TVorlaufEx>> is eventually admit with an 
additional ajustment value. Calibrations will affect then. 
 
We want to read all warnings, errors and alarms. How? 
 
Read these via <<STAT_message>>. See chapter 5 for a description of this 
parameter. 

27
Hardbergstraße 9 76437 Rastatt, Germany
Phone: +49(0)7222/50 58-0 – Fax: +49(0)7222/50 58-290 E-Mail: info@termotek-ag.com - www.termotek-ag.com