FirstPower Technology Co., Ltd.

CFPS2150(2V150Ah)
Specifications
Nominal Voltage 2V CHARACTERISTICS:
◆ Tubular Positive Plate;
10HR(1.80V) 150 Ah
Capacity ◆ Flooded Battery;
3HR(1.75V) 115Ah
(20℃) ◆ Porous Rubber and Porous PVC Separator
1HR(1.60V) 84.0Ah ◆ Transparent Container.
Battery Dry 11kg (24.3lbs)±5%
Weigh Wet 15.0kg (33.1lbs)±5%
Acid Weight (d=1.24kg/l) Approx 4.5kg (11.0lbs)
Terminal type /material T10 / Copper
Internal resistance
Approx. 2.0 mΩ
(Fully charged, 25℃)
Self-discharge 1 month Remaining Capacity: 86%(20℃)
Nominal operating
20℃±5℃(68℉±9℉)
temperature
Operating Discharge -15℃~50℃(5℉~122℉)
temperature Charge 10℃~45℃(50℉~113℉)
range Storage 10℃~30℃(50℉~86℉)
Constant Charge the battery at 0.05 C10 for
current 72h.
Initial Charge the battery at 0.1 C10 to Dimensions
Constant 2.35v/cell; then Charge the
charging
voltage battery with 2.35v/cell until the
whole charge time up to 100h.
The battery voltage and density of
electrolyte remain stable over 2h
Constant
at the end of charging , and strong
current
bubbles generated within the
Mark of electrolyte
Fully charged The charging current and density
of electrolyte kept constant for
Constant
more than 3h at the end of the
voltage
charge; and the charging current is
about 0.002~0.005 C10 amp.
Charge the battery at 0.05 C10 to
Supplementary charge
fully charged.
Charge the battery with 2.40v/cell
Equalizing charging
for 48h.
Charge the battery with 2.23V
Float charging (25℃); Equalizing charging the
battery when the abnormal occurs
Battery
Charge& Equalizing charging the battery
operation
discharge after discharged and per 3months
Supplementary charge the battery
Backup
per 3 or 6 months.
Maximum charging current 37.5A(0.25C10)
Max. discharge current 750A(5 sec.)
Designed cycle life 1600@80% DOD (30℃)
Designed floating life 20 years(20℃)
Constant Current Discharge Characteristics (A, 25℃)
F.V/TIME 30min 60min 2h 3h 4h 5h 6h 8h 10h 20h 24h 48h 120h
1.70V 117 81.0 49.5 38.6 30.9 27.2 23.1 17.7 15.2 8.18 7.14 ---- ----
1.75V 114 78.8 48.8 38.3 30.8 27.0 23.0 17.6 15.2 8.18 7.10 ---- ----
1.80V 110 76.5 47.6 37.1 29.9 26.3 22.2 17.0 15.0 8.10 7.05 3.62 ----
1.85V 104 72.0 44.7 34.8 28.1 24.8 20.9 15.9 14.3 7.73 6.71 3.62 1.50
Constant Power Discharge Characteristics (Watt, 25℃)
F.V/TIME 30min 60min 2h 3h 4h 5h 6h 8h 10h 20h 24h 48h 120h
1.70V 219 153 95.3 75.8 60.8 53.6 45.6 35.0 30.3 16.4 14.3 ---- ----
1.75V 213 150 93.8 75.0 60.3 53.3 45.2 34.8 30.0 16.4 14.3 ---- ----
1.80V 206 146 91.5 72.8 58.5 51.6 43.8 33.8 29.9 16.2 14.2 7.34 ----
1.85V 192 135 85.5 67.7 54.5 48.0 40.8 31.4 27.8 15.0 13.5 7.34 3.06
Note: The above characteristics data can be obtained within three charge/discharge cycles. Page 1 of 2
FirstPower Technology Co., Ltd. CFPS2150(2V150Ah)
Discharge Characteristics(25℃) Initial Charging (CC)Characteristics(25℃)

Effect of Temperature on Capacity Initial Charging (CV)Characteristics

The Relationship for Open Circuit Voltage


Supplementary charge (CV) Characteristics
and Residual Capacity (25℃)

Effect of Discharge rate on Capacity Cycle Life on D.O.D(25℃)

www.efirstpower.com Page 2 of 2