FSM 2000
FSM 2000
FSM 2000
Confidence
Value
Fire is costly
Every seven seconds a fire breaks out systems. Thousands of people die in firefighting, the other the use of passive
somewhere in the World. In a single year, fires every year. Damage to property is firestop systems.
the consequences are about four million also tremendous. Perhaps damage to a
fires, some 15,000 victims, damage building can be made good through
costing 70,000 million US dollars, and insurance, but cultural artefacts are lost Passive firestop systems
immense consequential damage. The trend forever for future generations. Even
is rising and will continue if no preventive when fire damage, such as that to If a fire breaks out, it should be
measures are taken. It is false to assume production equipment, has been contained in a so-called fire
that all outbreaks can be stopped. On the repaired, the consequences can often compartment by passive firestop
other hand, there are ways and means of still be far reaching. Hard-won market systems. To achieve this, each and every
reducing the damage. One is to use Hilti shares might be lost from one day to opening or penetration in a fire wall or
firestop systems. Fires break out without another. In this way, actual implications floor must be sealed against the escape
warning because their causes are so of a fire may only be felt by a company of fire and fumes. Materials used for this
numerous. Highly flammable materials after many years. It might even go out of purpose expand in a fire and close any
may be ignited by short-circuits in business. gaps which might result from melted
damaged electric lines or may even be the components. A properly installed fire
result of arson. Once a fire breaks out in a seal can prevent fire from spreading to a
building, it spreads rapidly due to the high Spread of fire in buildings neighbouring room for a time of one to
pressure generated by the increase in four hours. As a result, escape routes
temperature. These temperatures can A supply conduit containing many are kept safe and the work of fire-
exceed 1000°C and cause even large, solid electric lines and pipes passes through fighters supported. Active fire
building components to buckle and snap all floors of an entire building. If a fire prevention uses sprinkler systems, fire
like match sticks. The fumes and gases breaks out, it can advance twenty extinguishers and the fire service, and
produced can cause death in a short time. metres every minute through this supply comes into action when a fire is actually
conduit. All seven floors are then fought.
engulfed by the spreading fire in only
Tremendous damage one minute. And, not only large supply
in Hong Kong conduits are a big risk, but also the
many small penetrations made after a
20 Nov, 97: building is finished to install electric
5th Alarm fire in Garley Building, Nathan supply lines and all other pipes. Many
Road. (40 deaths, 81 injury). buildings contain what are, from a fire
10 Jan 94: prevention aspect, weak points of this
Shek Kip Mei Branch, Hong Kong Bank kind. Measures to stop fires are either
(12 deaths, 1 injury) not given consideration during the
Often, people in burning buildings have building planning phase or, if so, the
no chance of escape because acrid firestop systems are not installed
smoke makes them lose their orientation properly. There are two approaches to
and permanently injures their respiratory stopping fire in a building: one is active
Why use Hilti firestop systems? openings in fire walls and floors. Each product has been
optimised for the diverse requirements in buildings.
Firestop representatives from Hilti provide professional Installers benefit from the easy use of Hilti firestop systems.
advice about firestop systems for building owners, They themselves can install the planned and necessary
specifiers and installers. They work closely with customers firestop systems, while resting assured that Hilti systems
from the building planning stage to the firestop installation have been tested world-wide and approved in accordance
phase to select ideal solutions or applications from Hilti’s with national regulations.
firestop programme. A full range of systems can be
supplied by Hilti to seal joints, cable penetrations and pipe
Specifier Guide
Remarks:) The information in this page is extracted from "Code of Practice for Fire Resisting Construction 1996".
Specifier Guide
10. Enclosure around or sealing system for a duct, pipe or N Y N from outside
wire
12. Fixed light (including frame, glazing & fixing) Y* Y Y each side separately
(3) Any restriction of the cross-section area of the smoke outlet shaft to 75% or less of its original area should be deemed to constirute failure in stability.
Remarks:) The information in this page is extracted from "Code of Practice for Fire Resisting Construction 1996".
Specifier Guide
Contents
Page no.
Building joints
CP 606
CP 601S
1
Cable trays
Permanent
CP 636
CP 671
CP 678
Cable trays
Simple retrofitting
of cables
CP 655
2
Specifier Guide
Intumescent joint filler joints where fire prevention ■ Water and gas tight
Building joint
wrap to be positioned
■ Can be installed and
left for building finishing
work
3
Specifier Guide
plasterboard etc.
Removable and
2 components
if penetrations
Ready-to-use
opening size
opening size
without dust
Intumescent
often change
Very suitable
Application
thickness,
thickness,
Required
Required
Concrete
Masonry
reusable
Drywall,
product
Max.
Max.
floor
floor
wall
wall
30 30 Mineral
● ● ● 100 100 4H joint joint — — wool — ● — 9/10
integrity width width ≥100kg/m3
Mineral
wool
Ø 160 Ø 130 melting-
● ● — 150 150 4H or or — — point — ● — 11/13
integrity 300cm2 300cm2
(Cables) ≥1000°C
4H
● ● ● 100 120 integrity Ø 250 Ø 250 ● ● — — ● ● 17/19
2H
● ● — 150 150 integrity Ø 115 Ø 115 ● ● — — ● ● 20/22
— — — — — 1/2 — — ● ● — — ● — 35/37
or 1H
*All information mentioned in this document is based on tests or assessments as per BS 476:Part 20.
4
Specifier Guide
5
Specifier Guide
plasterboard etc.
Removable and
2 components
if penetrations
Ready-to-use
opening size
opening size
without dust
Intumescent
often change
Very suitable
Application
thickness,
thickness,
Required
Required
Concrete
Masonry
reusable
Drywall,
product
Max.
Max.
floor
floor
wall
wall
● ● — 150 150 90 min. Ø 200 Ø 200 ● ● CP 611A ● ● ● 32/34
integrity
2H
● ● — 220 220 integrity 600 600 ● ● CP 611A ● ● ● 29/31
and X X
insulation 400 400
Mineral
2H wool
insulation 800x600 panel
● ● ● 100 150 and Drywall 1000 — — — ● — 38/41
>150 kg/m3
integrity X
unre-
stricted
*All information mentioned in this document is based on tests or assessments as per BS 476:Part 20.
6
Specifier Guide
CP 601S
Elastic firestop sealant
4 hrs FRP
Areas of application
Construction joints/sealing penetration for metal pipes
■ Sealing expansion joints and stretched connection joints
where stringent fire prevention requirements must be met.
■ Tested to BS 476:Part 20, 1987. Insulation/integrity 4 hours for
floors and walls.
For use on
- Various base materials such as masonry, concrete, metal
glass, etc.
- Wall and floor thicknesses greater than 100 mm
- Joint widths from 6 to 100 mm
Examples
- Connections between reinforced concrete components
and masonry (skeleton construction)
- Joints in walls or fire compartements e.g. stairways
- Sealing joints exposed to great heat and with stringent System advantages/customer benefits
requirements for sealing against smoke and fumes ■ Simple use and application
Recommendations for use ■ Good adhesion without use of a primer
■ Use non-flammable mineral wool (min. 100 kg/m3) as ■ Smoke, gas and water tight
backfilling material. ■ Excellent movement capability
■ Apply CP 601S in walls on both sides, depending on joint width.
Internationally tested and approved
British Standard
BS 476
7
Specifier Guide
CP 601S
Elastic firestop sealant
Product description
■ Elastic firestop sealant (neutral silicone) classified as
material class B1
Product features
■ Halogen and solvent free
■ Weather and UV-resistant
Technical data
CP 601S elastic firestop sealant
(at 23°C and 50% relative air humidity)
Density: approx. 1.4 g/cm3
Cartridge contents: 310 ml
Application temperature: +5°C to +40°C
Skin-forming time: approx. 15 min.
Curing rate: approx. 2 mm in 3 days Dimensions
Volume shrinkage: 0 – 5% The following dimensions must be observed when using
Max. deformation: 25% CP 601S elastic firestop sealant.
Temperature resistance: -30˚C to +150˚C
Material class as per DIN 4102, P.1: B1 a Joint Joint
b
Shelf-life after production: 12 months (at 20˚C in a dry place) width mm depth mm
b a 6 6
CP 601S is subject to surveillance by an independent inspection authority. 12 6
30 15
Application Floor Wall 100 15
■ Joint sides must be sound, dry and free from dust, oil or grease.
■ Check whether a primer is required for the substrate. Check with
Hilti application engineering for recommended primer if needed. Consumption guide
■ In walls apply CP 601S to both sides of the joint. ■ Consumption guide values are given as joint length in meters per
■ Insert backfill of non-flammable mineral wool (at least 100 kg/m3). cartridge.
■ Smooth firestop sealant with smoothing agent or soap b = Joint depth a = Joint width (mm)
solution before the skin forms.
6 12 20 30 100
■ Remove CP 601S firestop sealant before it cures using white spirit.
6 mm 8.6 4.3
Once cured, it can only be removed mechanically. 10 mm 1.6
15 mm 0.7 0.1
Chemical resistance
■ At room temperature the cured silicone sealant is resistant for a
short time to diluted (≤5%) acids and lyes/alkalis as well as Notice about approvals
commercially available cleaning agents and disinfectants (except those ■ When making a joint using Hilti CP 601S elastic firestop sealant,
containing iodine). nationals approvals must be observed in principle. Please refer to
■ Concentrated acids and lyes/alkalis destroy silicone rubber in time. them for restrictions as to joint size, type and thickness of wall or
■ Solvents and mineral oils cause cured silicone to swell. floor.
■ Consequently, proper functioning of the sealant should be
Do not (no approval)…
checked after exposure to a solvent / mineral oil.
■ Use on areas immersed in water
■ It must be remembered that the resistance of silicone rubber to
■ Paint
chemicals decreases with increasing temperature.
■ Please contact your local sales representative or the nearest Hilti Storage
centre if special requirements for chemical resistance have to be met. ■ Store only in the original packaging in a location
protected from moisture at a temperature of 5˚C to 25˚C.
Safety precautions ■ Observe expiry date on top of cartridge.
■ Keep out of reach of children. ■ Dispose only complete empty cartridges
■ Observe the EC safety data sheet.
■ Eyes and hands must be suitably protected when working and Backfilling
contact with mucus membranes or with foodstuffs must be Max. joint width Base material Backfilling Fire rating per BS 476
avoided. Insulation Integrity
■ Avoid contact with eyes/skin. If contacted, thoroughly rinse with 15 mm Gas concrete Mineral wool 4h 4h
water and, if necessary contact a doctor. 30 mm Gas concrete Mineral wool 4h 4h
■ Only use in well ventilated areas or under an extraction system. 100 mm Gas concrete Mineral wool 4h 4h
■ A product only for professional users.
8
Specifier Guide
CP 606
Intumescent joint filler
4 hrs FRP
Areas of application
■ Sealing rigid or low movement joints where fire prevention
requirements must be met.
■ Tested to BS 476:Part 20, 1987. Integrity: 4 hours for floors
and walls
For use on
- Various base materials such as light partitions (e.g. drywall),
- concrete, masonry and gas concrete
- Wall and floor thickness from 100 mm
- Joint widths from 6 to 30 mm
Examples
- Connections between light partition components
- Floor and wall connection joints with low movement
- Sealing joints exposed to great heat and with stringent
requirements for sealing against smoke and fumes
System advantages/customer benefits
Recommendations for use ■ Paintable
■ Use non-flammable mineral wool (min. 100 kg/m3) as ■ Simple use and application
backfilling material or Hilti CF 125-50 foam in the joint. ■ Smoke, gas and water tight
■ Apply CP 606 in walls on both sides, depending on joint width. ■ Easy clean up with water
■ On porous absorptive substrates to achieve better adhesion,
Internationally tested and approved
mix CP 606 with water and apply on base material
British Standard
BS 476
Installation instructions (seal for matal pipes)
■ Clean joint and joint sides, The joint sides must be in sound
condition, dry and free of dust and grease.
■ Insert backfilling material (mineral wool)
Leave sufficient joint depth for applying the sealant.
■ Apply the fire prevention sealant from both sides of the joint. The
use of a manual dispenser
(e.g. Hilti CB 200-P1) is recommended.
■ Smooth the joint/sealant. Use soap solution or smoothing agent
and smooth carefully with a finger or narrow spatula to give a
concave surface. The working time of CP 606 is 10 to 30 minutes.
The completed application should be left undistrubed for 48 hours.
■ Cleaner can be used to clean around the joint or remove surplus
sealant before it has cured.
9
Specifier Guide
CP 606
Intumescent joint filler
Product description
■ Firestop sealant (acrylic-dispersion)
Product features
■ Silicone free
■ Halogen and solvent free
■ UV resistant
Technical data
CP 606 fire resistant joint filler
(at 23°C and 50% relative air humidity)
Density: approx. 1.5 g/cm3
Cartridge contents: 310 ml
Application temperature: +5°C to +40°C
Skin-forming time: approx. 15 min.
Curing rate: approx. 2 mm in 3 days
Volume shrinkage: approx. 20% Dimensions
Max. deformation: 10% The following dimensions must be observed when using CP 606
Temperature resistance: -40˚C to +80˚C intumescent joint filler.
Shelf-life after production: 12 months (at 20˚C in a dry place)
a b
CP 606 is subject to surveillance by an independent inspection authority.
b a
Application
■ Joint sides must be sound, dry and free from dust, oil or grease.
■ Check wheter a primer is required for the substrate. Floor Wall
■ In walls apply CP 606 to both sides of the joint.
■ Insert backfill of non-flammable mineral wool (at least Consumption guide
100 kg/m3) or Hilti CF 125-50 foam into the joint. ■ Consumption guide values are given as joint length in meters per
■ Smooth firestop sealant with water before the skin forms. cartridge.
■ Remove CP 606 firestop sealant before it cures using water b = Joint depth a = Joint width (mm)
Once cured, it can only be removed mechanically. 6 12 20 30
Joint side material/primer recommendations 6 mm 8.6 4.3
■ To improve adhesion of firestop sealant if the 10 mm 1.6
substrate is porous and absorptive, mix CP 606 with water and 15 mm 0.7
apply as a primer on base material.
■ The compatibility of the sealant with any encountered paints must Safety precautions
always be checked. In particular, this concerns dispersion paint ■ Keep out of reach of children.
systems and alkyd resin systems that can be diluted in water. ■ Observe the EC safety data sheet.
■ Checks of compatibility must be repeated at reasonable intervals ■ Eyes and hands must be protected when working and contact with
because the chemical composition of paint systems may change. mucus membranes or with foodstuffs must be avoided.
■ A product for professional users.
Chemical resistance
■ Normally, there is no need for resistance to chemicals with the Storage
applications recommended by Hilti. ■ Store only in the original packaging in a location
■ Unprotected acrylic sealants have only slight resistance to chemicals. protected from frost and moisture at a temperature of 5˚C to 25˚C.
■ Please contact your local sales representative or the nearest Hilti ■ Observe expiry date on top of cartridge
centre if special requirements for chemical resistance have to be met. ■ Dispose only complete empty cartridges.
Notice about approvals
■ When making a joint using Hilti CP 606, fire resistant joint filler, Backfilling
national approvals must be observed in principle. Please refer to
Max. joint Base material Backfilling Fire rating per BS 476
them for restrictions as to joint size, type and thickness of wall or
width
floor. Insulation Integrity
Do not (no approval)… 6 mm Gas concrete Mineral wool 4H 4H
■ Use on areas immersed in water or when permanently exposed to 15 mm Gas concrete Mineral wool 4H 4H
water. 20 mm Gas concrete PE 24 mm 130 min. 4H
20 mm Gas concrete PU foam CF 125-50 208 min. 4H
■ Use marble/natural stones
30 mm Gas concrete Mineral wool 216 min. 4H
■ Use bituminous substrates
30 mm Steel-steel Mineral wool 36 min. 4H
■ Use where subjected to heavy abrasion (floor joints)
10
Specifier Guide
CP 611A
Intumescent firestop mastic
4 hrs FRP
Areas of application
Sealing small to medium-sized penetrations
■ Permanent fire seals for single and bunched cables.
■ Tested to BS 476:Part 20, 1987.
■ Sealing around flammable pipes up to max. 40 mm diameter
Tested to BS 476:Part 20,1987.
■ Resealing of penetrations previously sealed with CP 636
firestop mortar, after installing additional cables.
For use in
- Round penetrations up to max. 200 mm diameter and square
openings up to max. 300 cm2
- Concrete, porous concrete or masonry
- Walls and floors from 150 mm thick
Examples
- Breaches, irregular openings in fire walls and floors
- Sealing around plastic pipes up to 40 mm diameter
System advantages/customer benefits
■ Easy to work with thanks to thick consistency
■ Wide range of applications
Recommendations for use ■ Paintable
■ Use non-flammable mineral wool as backfilling material (100kg/m3) ■ Quick sealing of remaining gaps
■ Particularly suitable for laying new cables
■ Can be used for outdoor applications
British Standard
BS 476
CP 611 A intumescent
firestop mastic – 310 ml cartridge
Packing Ordering Item no.
contents designation
(pcs)
11
Specifier Guide
CP 611 A
Intumescent firestop mastic
Product description
■ Water-based intumescent acrylic, mastic
Product features
■ Expands in fire, protecting pipe and cable penetrations
■ Smoke, gas and water tight
■ Halogen and solvent free
■ Odourless
Technical data
CP 611A intumescent firestop mastic
(at 23°C and 50% relative air humidity)
Density: approx. 1.3 g/cm3
Colour: Grey
Application temperature: +5°C to +40°C
Temperature resistance: -40°C to +140°C Dimensions
Skin-forming time: approx. 10 min.
Curing rate: 3 mm in 3 days
Intumescent phase: from +140°C to +180°C
Movement acceptance: 10%
Material class as per DIN 4102, P.1: B2
Shelf-life after production: 12 months (at 20˚C in a dry place)
Cartridge contents: 310 ml
Consumption guide
■ Cable penetrations
CP 611 A (pcs)
Opening size Cross sectional area of cables
area diameter 0% 10 % 30 % 60 %
0.006 m2 Ø 90 mm 2 2 2 1
0.01 m2 Ø 120 mm 4 3 3 2
0.015 m2 Ø 140 mm 5 5 4 2
0.02 m2 Ø 160 mm 7 6 5 3
0.025 m2 Ø 180 mm 9 8 6 4
0.03 m2 Ø 200 mm 10 9 7 4
Volume in cartridges of 310 ml for 40 mm depth The following dimensions must be observed when applying
CP 611 A intumescent firestop mastic.
■ Pipe penetrations
Wall seal Floor seal
Min. thickness of building component 150 mm 150 mm
Opening Nominal pipe size in mm Max. opening size
mm2 Dia mm 15 20 25 32 40 50 Diameter 160 mm 160 mm
Area 300cm2 300cm2
1075 37
Min. distance from cables to
1257 40 edge of opening 10 mm 10 mm
1385 42 Min. distance to
1735 47 0.05 next opening 200 mm 200 mm
2124 52 0.065 0.06 Single cables min. 20 mm min. 20 mm
2463 56 0.075 0.07 0.065 Bunched cables/flammables pipes
(ø ≤ 40 mm) min. 25 mm min. 25 mm
3019 62 0.009 0.085 0.075
Annular space around:
3526 67 0.1 0.095 – Singles cables min. 20 mm min. 20 mm
4072 72 0.11 0.095 – Bunched cables/inflammables pipes
4657 77 0.11 (Ø≤ 40mm) min. 25 mm min. 25 mm
5281 82 0.13 0.11 Compacted depth of non-flammable
5945 87 0.13 mineral wool (melting temp. >1000˚C) ≥ 50 mm ≥ 50 mm
6648 92 0.155 Application thickness of CP 611 A 40/60 mm 40/40 mm
- cable / pipes both sides soffit only
7399 97 0.175
Max. cable loading
Volume in cartridges of 310 ml for 10 mm depth (as % of opening size) 60 % 60 %
12
Specifier Guide
13
Specifier Guide
Areas of application
Sealing medium-sized to very large penetrations with the
possibility of installing further cables
■ Permanent fire seal for cables and cable trays
Tested to BS 476:Part 20, 1987. Integrity: from 2 1/2 hours up
to 4 hours.
For use in
- Walls with a max. opening 1200 mm x 2000 mm
- Floors with a max. opening 600 mm x 1000 mm
- Concrete, porous concrete and masonry
- Walls from 100 mm thick and floors from 150 mm thick
Examples
- Office buildings, hospitals, shopping centres and
industrial buildings
CP 636-20
14
Specifier Guide
Product description
■ Fire-resistant, cement-based mortar with thermal
insulating properties from admixed perlite
Product features
■ High yield
■ Stiff (forms not always required)
■ No additional components required (except when cable runs/trays
are directly on an opening surface)
■ Adheres very well to common substrates (steel, concrete or
masonry)
■ Impervious to smoke or gas and water resistant
■ Contains no asbestos, phenol or halogen constituents
Technical data
CP 636 firestop mortar
(at 23°C and 30% relative humidity)
Mix ratio: 3 :1 (mortar to water) Dimensions
Application temperature: ideal between 5° and 45°C
Colour: grey
Form removal after 2-4 hours (walls)
(depending on consistency): after 2-12 hours (floors)
Density of hardened mortar: 0.82 g/cm3
Compressive strength
(after 28 days at 23°C): 2.9 N/mm2
Material class as per DIN 4102, P.1: B1
Shelf-life after production: 12 months (at 30˚C in a dry place)
Consumption guide
15
Specifier Guide
Clean opening, Mix CP 636 mortar Put mortar into place Optional: add CP 651 Fasten installation Re-installation:
moisten surfaces or CP 655 for future plate in place lay cables and
cable changes (if required) close remaining
opening
16
Specifier Guide
For use in
■ Concrete, masonry, porous concrete and drywall
■ Walls from 100 mm thick and floors from 120 mm thick
Types of installation
- Wall: two jackets, one on each side
- Floor: one jacket on underside
System advantages/customer benefits
■ Snap connection for quick and easy closure without use of a tool
Example ■ Optionally positioned tabs for convenient fastening
■ Waste water pipes, fresh water pipes ■ Good acoustic insulating properties
■ Vacuum lines (dust) ■ Little space required – ideal where pipes run close together
17
Specifier Guide
Product description
■ Galvanised sheet steel containing sections of
intumescent material (which foams and expands in a fire)
Product features
■ Ready-to-use jacket, no preparatory work required, therefore fast
installation time
■ No minimum distance required between several jackets
Dimensions
Jacket/plastic pipes
Designation Suitable for out- Jacket outside Jacket No. of
side pipe dia. dia. length hooks and
(mm) (mm) (mm) fasteners
CP 642-50/1.5’’ * 32-50 73 47.5 2
CP 642-63/2’’ * 50-63 88 52.5 2
CP 642-75/2.5’’ * 63-75 100 2.5 3 Dimensions
CP 642-90/3’’ * 75-90 125 72.5 3 Wall Floor
CP 642-110/4’’ * 90-110 149 82.5 4
CP 642-125/5’’ 110-125 162 92.5 4
CP 642-160/6’’ 135-160 209 112.5 6
CP 642-180/7’’ 180 229 150.0 7
CP 642-200/8’’ 200 255 175.0 7
CP 642-225/9’’ 225 283 200.0 8
Flush mounted Flush mounted
CP 642-250/10’’ 250 315 230.0 9
Wall Floor
Material drywall panel cellular concrete cellular concrete
masonry
solid concrete
Min. thickness of
building component
for pipes:
32 – 160 mm dia. 100 mm 100 mm 120 mm
160 – 250 mm dia. 150 mm 150 mm
Min. pipe diameter 32 mm 32 mm
Max. pipe diameter 250 mm 250 mm
CP 642 two mounted, one mounted
one on each on underside
side
18
Specifier Guide
Close remaining gap to seal Clean plastic pipe. Close jacket. Attach fastening Fasten jacket and
ensure smoke and gas tight hooks. installation plate.
(If required)
seal.
19
Specifier Guide
For use in
■ Concrete, masonry, porous concrete
■ Walls and floors from 150 mm thick
Types of installation
■ Wall: two jackets, one on each side
■ Floor: one jacket on underside
System advantages/customer benefits
Example
■ Waste water pipes, fresh water pipes ■ Quick and easy closure without use of a tool
■ Drinking water pipes ■ Optionally positioned tabs for simple fastening
■ Extraction ducts (dust)
Internationally tested and approved
Recommendations for use
■ Fit the jacket around the pipe, lock the closure with firm British Standard
pressure until it latches. BS 476
■ Fit the fastening hooks on the firestop jacket to suit the
available space.
■ Secure the firestop jacket using approved Hilti anchors.
20
Specifier Guide
Product features
■ No minimum distance required between several jackets
■ Ready-to-use jacket; no preparatory work required, therefore
fast installation time
Technical data
Jacket/plastic pipes
Designation/ Pipe outside Jacket outside Jacket length No. of
size dia. (mm) dia. (mm) (mm) hooks and
fasteners
CP 643-50/1.5” 36 – 51 69 + 1 22.4 2
CP 643-63/2” 52 – 64 85 + 1 32.4 2
CP 643-90/3” 65 – 91 121 + 1 42.4 3
CP 643-110/4” 92 – 115 151 + 1 47.4 3
Dimensions
Wall Floor
Wall Floor
Material cellular concrete cellular concrete
masonry
solid concrete
Min. thickness of building
component for pipes 150 mm 150 mm
Min. pipe diameter 32 mm 32 mm
Max. pipe diameter 115 mm 115 mm
CP 643 two mounted, one one mounted on
on each side underside
21
Specifier Guide
Close remaining gap Clean plastic pipe Seal against smoke Attach fastening Close jacket Fasten jacket
to ensure smoke and and gases hooks
gas tight seal
22
Specifier Guide
Areas of application
■ Sealing flammable pipes from 50 mm up to 160 mm in diameter
with pipe wall thickness from 2.3 to 3.8 mm.
Tested to BS 476: Part 20: 1987 integrity 4 hours.
■ Suitable for:
uPVC pipes
Diameters from 50 mm up to 160 mm
Pneumatics tube conveyors
For use in
■ Concrete and masonry
■ Walls and floors from 150 mm thick
Types of installation
– Wall: two wrap, one on each size
– Floor: one wrap, on underside System advantages/customer benefits
■ Simple to use intumsecent seal
Excample ■ Easy to fasten in place
■ Waste water pipes, fresh water pipes ■ Long term stability of installation
■ Vacuum lines (dust) ■ Little space required – ideal where pipes run close together
■ Canbe installed with pipe – Backfilling can be executed later
Recommendations for use when all services have been completed especially in multi-service
■ Fit the wrap around the pipe. Use the self adhesive tape fastening. penetrations
■ Slide the wrap into the opening.
■ Back fill the opening around the wrap with CP 636 firestop mortar.
Tested and approved
British Standard
BS 476
23
Specifier Guide
Product features
■ Ready-to-use wrap, no preparatory work required.
■ Little space required – Ideal where pipe run close together.
■ Resistant to industrial atmospheric conditions, humidity and water.
■ Manufactured from high performing graphite.
■ Carbon seal structure on expansion.
Technical data
Chemical basis Graphite and non combustible inorganic
materials in latex binder.
Colour White
Fixing Self-adhesive tape
Dimensions
Wrap dimensions Floor Wall
Designation Suitable for outside Length Depth Thickness
pipe Dia. (mm) (mm) (mm) (mm)
fasteners
CP 649/50 50 222 50 10
CP 649/110 110 395 100 10
CP 649/160 160 580 100 10
Wall Floor
(mm) (mm)
Minimum component
thickness 100 150
Minimum pipe diameter 50 50
Maximum pipe diameter 160 160
Base materials blockwork
masonry
concrete concrete
CP 649 Install Install
flush to flush to
both faces soffitt
1 No. <100mm 1 No.
2 No. >100mm
CP 636 Mortar Backfill all voids around Backfill all voids
CP 649 around CP 649
24
Specifier Guide
Fit CP 649 around Slide CP 649 into the Back fill the opening Remove formwork
the pipe opening with CP 636 mortar once CP 636 has
cured
25
Specifier Guide
Areas of application
■ Temporary or permanent sealing of cable and cable tray
penetration.
Tested as BS 476:Part 20: 1987 Integrity/insulation: 2 hours
For use in
- walls (max. opening 1.15 m2)
- foors (max. opening 1.15 m2)
- drywalls, masonry, concrete and porous concrete
- walls from 75 mm
- floors from 250 mm
Examples
- Computer rooms, switchgear rooms, etc.
- Telephone switchboard rooms, studios
- Public buildings, production bays
British Standard
BS 476
26
Specifier Guide
Product description
■ Ready-to-use firestop cushion made of a homogeneous, graphite-
based, intumescent granulate mixture (which foams and expands
in a fire) all contained in an inner polyethylene bag inside an outer,
protective woven fibre glass bag.
Product features
■ Dust free and tear-resistant
■ Suitable for temporary and permanent installations
■ Durable and resistant
Technical data
CP 651 Firestop cushion
Density: approx. 0.33 g/cm3
Weight:
CP 651-L 750 g ± 10%
CP 651-S 300 g ± 10%
Dimensions
CP 651-XS 150 g ± 10%
Dimensions (LxWxH):
CP 651-L 340/200/35 mm
CP 651-S 340/100/25 mm
CP 651-XS 340/90/20 mm
Reaction temperature:
First expansion at +150° C
Second expansion at +600° C
Temperature resistance: -40°C to +120°C
Material class as per DIN 4102, P.1: B2
Consumption guide
(Guide figures for a wall)
Number of CP 651 cushions of XS + S + L sizes
Opening Cross sectional area of cables
area
(m2) 0% 10% 30% 60%
0.01 4+1+0 5+0+0 1+2+0 1+1+0
0.02 8+2+0 7+2+0 6+2+0 3+1+0
0.04 4 + 13 + 0 6 + 10 + 0 6+7+0 2+5+0
0.05 4 + 17 + 0 7 + 13 + 0 7+0+0 4+5+0
0.1 0 + 3 + 12 0 + 2 + 12 0+3+9 0+5+4
The following dimensions must be observed when installing firestop
0.2 0 + 6 + 24 0 + 5 + 24 0 + 8 + 17 0+6+9
cushions:
0.4 0 + 12 + 48 0 + 11 + 47 0 + 3 + 39 0 + 5 + 21 Wall Floor
0.5 0 + 27 + 63 0 + 15 + 60 0 + 10 + 50 0 + 5 + 30 Min. building component thickness 75 mm 250 mm
0.6 0 + 23 + 78 0 + 18 + 72 0 + 12 + 60 0 + 6 + 36 Max. opening size
0.8 0 + 31 + 106 0 + 24 + 96 0 + 16 + 80 0 + 8 + 48 Width 1000 mm 1000 mm
1.0 0 + 40 + 132 0 + 30 + 120 0 + 20 + 100 0 + 10 + 60 Height/length 1150 mm 1150 mm
1.2 0 + 41 + 161 0 + 36 + 144 0 + 24 + 120 0 + 12 + 72 Min. distance of cable run
1.4 0 + 45 + 183 0 + 42 + 168 0 + 28 + 140 0 + 14 + 81 from opening 40 mm 40 mm
1.5 0 + 49 + 202 0 + 45 + 180 0 + 30 + 150 0 + 15 + 90 Min. distance between cables tray
1.6 0 + 51 + 216 0 + 48 + 192 0 + 32 + 160 0 + 16 + 96 Horizontal 0 mm 0 mm
1.75* 0 + 67 + 236 0 + 53 + 210 0 + 35 + 175 0 + 17 + 105 Vertical 40 mm 40 mm
* corresponds to max. permitted opening size in walls Min. distance
between openings 200 mm 200 mm
Max. cable loading
(as % of opening size) 60 % 60 %
27
Specifier Guide
Clean opening Cushion Cushion Fasten wire mesh in Cushion arrangement Fasten installation
arrangement without arrangement with place when closing in floor plate in place
cables in wall cables in wall floor openings with (If required)
cushions
Note
■ Floor seals must be protected from loading and theft using
wire mesh.
■ Do not use damaged cushions
28
Specifier Guide
Areas of application
Sealing small and medium-sized penetrations
■ Temporary or permanent sealing of cables and cable tray
penetrations.
Tested as BS 476:Part 20: 1987. Integrity: 2 hours for ceilings and
walls.
For use in
- Fire walls (max. opening 800 mm x 510 mm)
- Floors (max. opening 400 mm x unrestricted length)
- Concrete, porous concrete and masonry
- Floors and walls from 200 mm thick
Examples
- Completely dust and fibre-free rooms and places where elec-
trical installations are frequently used, such as computer
centres, hospitals and laboratories.
- New buildings in the construction phase and during System advantages/customer benefits
renovation ■ Particularly suitable for laying new cables later
- Production bays, warehouses etc. ■ Economical in use owing to short installation time
■ Easy installation as no special tool is required
Recommendations for use ■ Ideal for use in floors as no forming is required
■ The firestop system consists of the CP 655 firestop brick and ■ Immediately functional after installation
CP 611A intumescent firestop mastic. ■ Absolutely dust and fibre free
■ Position CP 655 firestop bricks in the penetration offset to each ■ Smoke and gas tight
other with small against large bases, positioned longitudinally.
■ Cut CP 655 firestop bricks to size only in the longitudinal direction Internationally tested and approved
■ Suitably cut CP 655 firestop bricks to fit closely around
penetrating items. British Standard
■ Fill gaps around and between cables with CP 611A Intumescent
firestop mastic.
BS 476
29
Specifier Guide
Product description
■ Ready-to-use, intumescent flexible bricks based on a two-
component polyurethane foam
Product features
■ Completely free from dust and fibres
■ Halogen and solvent free
■ Operational immediately after installation
■ Can be painted with dispersion, acrylate or silicone
Technical data
CP 655 firestop brick
Density: approx. 0.25 g/cm3
Dimensions (LxWxH): 220x130x60 mm
Colour: red
Dimensions
Application temperature: -5°C to +40°C
Temperature resistance: -60°C to +60°C
Expansion temperature: +300°C
Expansion ratio (at 300°C): 1:5
Material class as per DIN 4102, P.1: B2
Consumption
Assumption: CP 655 without cables in place; CP 611A used with
irregular opening surface. The following dimensions must be observed when making
the seal:
CP 655 (CP 611A)
(pcs) Wall seal Floor seal
cable space requirement Min. thickness of building
Opening component 200 mm 200 mm
size (m2) 0% 10% 30% 60% Max. opening size
0.005 1 (0.25) 1 (0.25) 1 (0.4) 1 (0.5) Width 600 mm 600 mm
0.01 2 (0.5) 2 (0.5) 1 (0.8) 1 (1.0) Height/Length 400 mm 400 mm
0.02 3 (1) 3 (1) 2 (1.2) 1 (1.4) Min. distance between cables/
0.03 4 (1.5) 4 (1.5) 3 (1.8) 2 (2.0) cable run and opening surface 0 mm 0 mm
0.04 5 (2) 5 (2) 4 (2.2) 2 (2.5) Min. distance between cable trays
0.05 7 (2) 6 (2) 5 (2.4) 3 (2.8) Horizontal 0 mm 0 mm
0.1 14 (3) 12 (3) 9 (3.5) 6 (3.6) Vertical 0 mm 0 mm
0.2 28 (3) 23 (3) 18 (3.7) 11 (3.9) Min. distance to next opening 200 mm 200 mm
0.3 42 (4) 35 (4) 27 (4.2) 16 (4.4) Max. cable loading
0.4 56 (4) 47 (4) 36 (4.6) 21 (4.8) (as % of opening size) 60 % 60 %
30
Specifier Guide
Aus-
führungsschild
Clean opening a) Build up bricks b) Cut bricks to Build up bricks Fill gaps Fasten installation
without cables in size if cables are plate in place
place in place (If required)
Re-installing cables
– Remove a brick from the seal and cut it to shape.
– Install the cable and re-lay the brick in compliance with
the approval. Fill gaps and spaces with CP 611A.
Single cables can be run through joints between bricks and,
also, a hole can be drilled through a brick using a sharpened
piece of metal pipe or tubing.
31
Specifier Guide
Areas of application
Sealing circular penetrations
■ Temporary or permanent sealing of single or bunched cables
in fire walls and floors. Tested as per BS 476:Part 20: 1987.
Integrity: 90 minutes for floors and walls.
For use in
- Circular penetrations from 50 to 200 mm diameter in concrete,
porous concrete and masonry
- Walls from 150 mm thick
- Floors from 200 mm thick
Examples
- Dust and fibre-free rooms and places where electrical installa-
tions are frequently changed such as computer centres,
hospitals and laboratories.
- New buildings in the construction phase and during
renovation System advantages/customer benefits
- Production bays, warehouses etc. ■ Especially suitable for laying new cables later
■ Economical in use owing to short installation time
Recommendations for use ■ Easy installation as no special tool is required
■ The firestop system consists of the CP 656 firestop plug ■ Immediately functional after installation
and CP 611A intumescent firestop mastic. ■ Versatile in use (temporary or permanent protection)
■ First cut plugs to shape for cable bundles to pass through ■ Absolutely dust and fibre free
them. ■ Smoke and gas tight
■ Insert CP 656 firestop plugs into both sides of the penetration. Internationally tested and approved
■ Fill and close gaps around and between cables with CP 611A
intumescent firestop mastic.
■ Diamond core bits are recommendend for drilling penetrations. British Standard
BS 476
32
Specifier Guide
Product description
■ Ready-to-use, intumescent flexible plugs based on a two-
component polyurethane foam
Product features
■ Completely free from dust and fibres
■ Halogen and solvent free
■ Operational immediately after installation
■ Can be painted with dispersion, acrylate or silicone
Technical data
CP 656 firestop plug
Density: approx. 0.25 g/cm3
Application temperature: -5°C to +40°C
Colour: red
Temperature resistance: -60°C to +60°C
Expansion temperature: +300°C Dimensions
Expansion ratio (at 300°C): 1:5
Material class as per DIN 4102, P.1: B2
33
Specifier Guide
Aus-
führungsschild
Core drill and Without cables, fit With cables, cut plugs Fit plug and Fasten installation
clean hole plugs into hole to fit around cables fill gaps plate in place
with CP 611A (If required)
Opening
Notice about approvals
■ Drill the hole with Hilti diamond drilling equipment and a suitable
■ When making a cable seal using Hilti CP 656 intumescent firestop
core bit.
plug, national approvals must be observed in principle. Please
■ Clean the opening.
refer to them for restrictions as to opening size, type and
■ Cables and cable supporting structures must be installed in
thickness of wall or floor, maximum cable diameter, etc.
compliance with local building and electrical standards.
■ For maintenance reasons, a penetration seal could be permanently
marked with an installation plate. In such a case mark the
Fitting firestop plugs
installation plate and fasten it in a visible position next to the seal.
a) If cables are not laid (temporary firestop), insert CP 656
firestop plugs from both sides and compress them. Fill gaps
Not for use...
and spaces of irregular hole surfaces with CP 611A intumescent
■ In drywall (no approval).
firestop mastic.
■ In wet rooms or outdoors exposed to the weather or UV radiation
b) If cables are laid (permanent firestop), cut CP 656 firestop
(only after applying an additional silicone coating).
plugs to suit the cable circumference using a knife. Insert plugs
from both sides and compress them. Fill cable spaces and gaps
Safety precautions
with CP 611A intumescent firestop mastic corresponding to
■ Keep out of the reach of children.
the thickness of the CP 656 firestop plug.
■ Observe the EC safety data sheet.
Notes:
■ CP 611A can be smoothed using a paint brush and
Storage
water before a skin forms.
■ Store only in the original packaging in a location protected from
It is not necessary for the firestop plug to be bonded to the
moisture and direct sunlight.
side of the hole.
c) Re-installing cables
If single cables are subsequently installed, a hole can be drilled
through the plug and a cable passed through.
Notes
■ A plug may also have its diameter cut to size. The plug, however,
must be at least 4% larger in diameter than the hole being closed.
34
Specifier Guide
British Standard
BS 476
35
Specifier Guide
Product features
■ Expand in fire closing gap around the door
■ Smoke and fumes tight
■ Self-adhesive backing
Technical data
Dimensions (I/W/t)
30 mins 2.1 m/10 mm/4 mm
60 mins 2.1 m/20 mm/4 mm
Brush seal Polypropylene bristies and fin
Fixing Self-adhesive backing
Outer casing Extruded uPVC box
Cleam out grooves Remove protective Insert CP 667 into Fit CP 667 to top and Ensure smoke seal
backing from self- grooves vertical sides closes gap
adhesive tape
Preparation
■ Using an appropriately sized router bit (10 or 20 mm) cut the
correct number of grooves in the door frame or the door. The
depth of cut is to be set at 4 mm for all configuration and sizes.
■ Clean out grooves of dust, shaving and debris.
36
Specifier Guide
37
Specifier Guide
Areas of application
Z8Z iwhriuh.
4i5kirdw NöoWE
u9+ß12 iloi4jtf-öx-.v 23awöp
oeoo bvbvh, 3i4eß02
ireiv 88u 27 uze
CP 671-B
38
Specifier Guide
Product features
■ Water soluble, odourless and solvent free
■ Smoke and gas tight
Technical data
CP 671 firestop coating system
(at 23°C and 50% relative air humidity)
Density: approx. 1.3 g/cm3
Colour: white
Consistency: CP 671 C: can be applied
by paint brush or sprayed
CP 671 F: can be applied
by trowel/spatula
Application temperature: +5°C to 40°C
Temperature resistance: -30°C to 80°C
pH value: 7-8 (chemically neutral)
Application of 2nd layer, CP 671C: after about 2 - 4 hours
Shelf-life after production: CP 671 C: 18 months
CP 671 F: 12 months Dimensions
Material class as per DIN 4102 P.1,
CP 671 C: B2 (Fire reaction)
Dimensions
The following dimensions must be observed when making the seal:
39
Specifier Guide
Clean opening Coat mineral wool Fit mineral wool Apply final coating Fasten installation
panel with panel. Coat cut of CP 671 C plate in place
CP 671 C edges with (If required)
CP 671 F
Opening Notes
■ Clean the opening. Do not premoisten opening surfaces. ■ Re-installation: First pack tightly with mineral wool, then close the
■ Cables and cable supporting structures must be dry and free from remaining openings with CP 671F filler. Damage to the seal surface
dust, grease or oil, and installed in compliance with local building must be repaired.
and electrical standards. ■ Floor seal: Fit, for example, construction mesh over the opening
to protect it from being walked on or otherwise loaded.
Application of firestop coating
a) Preparation Notice about approvals
- Mix the CP 671C coating well. ■ When making a cable seal using Hilti CP 671 intumescent firestop
- Separated water in the container must also be mixed in. coating, national approvals must be observed in principle. Please
- The outer edge of the mineral wool panel should be coated refer to them for restrictions as to opening size, type and
with CP 671C before fitting to make it easier to cut. An applied thickness of wall or floor, maximum cable diameter, etc.
wet layer of about 0.7 mm gives a dry layer about 0.5 mm thick. ■ For maintenance reasons, a penetration seal could be permanently
If a precoated mineral wool panel is used, this operation is marked with an installation plate. In such a case, mark the
unnecessary. installation plate and fasten it in a visible position next to the seal.
40
Specifier Guide
Do not...
■ Paint over the coating.
■ Use outside or in damp rooms.
41
Specifier Guide
sodfm,e
Brands
chutzb
eschic
htu ng
Main Applications
- Power plants
- Telecommunication complexes.
- Industrial plants
- Petrochemical plants
- Paper mills
- Factories and production facilities
Product Features
- Water soluble, odourless and solvent free
- Rapid drying
- Remains flexible when dry
Product advantages / Customer benefits:
- Intumescent
- Free of fibres, or asbestos ■ Simple application using a paint brush, or airless spray gun
- No derating effect on cables ■ High yield, economical
- Compatible with the shealthing of electrical cables ■ Single application to meet IEC 332 Part 3 Standard for reduced
spread of flame
Fire Tests ■ No derating effect on cables
- IEC 332 Part 3 – Category A ■ Protects functionality of cables
- Factory Mutual Approved
Technical data
CP 678 Cable coating
(at 23°C and 50% relative air humidity)
Density: approx. 1.3 g/cm3
Colour: white
Consistency: CP 678: can be applied
by pain brush or sprayed
Application temperature: +5°C to 40°C
Temperature resistance: -30°C to 80°C
pH value: 7-8 (chemically neutral)
Application of 2nd layer, CP678: after about 2 - 4 hours
Shelf-life after production: CP 678: 18 months
Material class as per DIN 4102 P.1,
CP 678: B2
CP 678
42
Specifier Guide
Coverage
■ On a flat surface coverage will be approximately 650 gm per m2.
(at 0.5 mm DFT)
■ On cable bundles, and cable trays allow 1 to 1.5 kg per m2 (at
0.5 mm DFT) depending on volumne of cables, method of
application, and wastage (ie. overspray).
Do not...
■ Paint over the coating.
■ Use outside or in damp rooms.
43
Specifier Guide
Important notice
1. Construction materials and conditions vary on different sites. If it is Whilst Hilti can give general guidance and advice, the nature of Hilti
suspected that the base material has insufficient strength to achieve a products means that the ultimate responsibility for selecting the right
suitable fastening, contact the Hilti Technical Advisory Service. product for particular applications must lie with the customer.
2. The information and recommendations given herein are believed to 3. All products must be used, handled and applied in accordance with
be correct at the time of writing. The data has been obtained from all current instructions for use published by Hilti.
tests under laboratory or other controlled conditions and it is the
4. All products are supplied, and advice given, subject to Hilti’s terms
users responsibility to use the data given in the light of conditions on
of business.
site and taking into account the intended use of the products
concerned. 5. Hilti’s policy is one of continuous development. We therefore
reserve the right to alter specifications etc. without notice.
44
Specifier Guide
CP 611A intumescent firestop mastic CP 636 firestop mortar CP 642/CP 643 firestop jacket
CP 671 firestop coating system CP 601S elastic firestop sealant CP 678 cable coating
CP 606 intumescent joint filler