Service Manual: Commercial Air Conditioning
Service Manual: Commercial Air Conditioning
Service Manual: Commercial Air Conditioning
SERVICE MANUAL
Models
AD96NAHAEA
AP96NACAEA
AU96NATAEA
Features
The outdoor can match with both of duct and cabinet type indoor unit
The indoor unit is identical for heat pump and cooling only unit
Infra red remote controller or wired controller
Central control and full automation, if connected with a central controller
24-hour timer (standard)
Auto-restart function
Strong energy distribution
CONTENTS
Contents………………………………………………………...2
1. Description of products & features………………………..3
2. Specification…………………………………………………5
3. Safety precaution……………………………………………10
4. Net dimension of indoor and outdoor……………………..12
5. Installation instructions………..……………………………15
6. Parts and functions…………………………………………37
7. Remote controller functions……………………………….38
8. Refrigerant diagram…………………………………………58
9. Electrical control functions………………………………….59
10. Diagnostic information (trouble shooting)……………….67
11. Electrical data………………………………………………71
12. Exploded view and parts lists…………………………….73
13. Performance curves……………………………………….81
14. Noise level charts………………………………………….85
15. Air velocity distribution…………………………………….89
Climate type
Type of Air
T1 T2 T3
Conditioner
Cooling Only 18 ℃~43℃ 10℃~35℃ 21℃~52℃
Duct unit: super thin unit body, no occupying the indoor space
The whole unit can be concealed in the building, without effect of the indoor décor.
With air inlet filter, enhance the air quality
The high efficiency filter can collect the dirt and remove the bacterium, which can be installed on the
easy-to-unload place, convenient to be cleaned.
Cabinet unit: newly designed luxurious LCD operation panel
On the front panel, you can find there is a luxurious operation panel. Just slightly pressing, the
comfort will come around you. Meanwhile, the unit is equipped with the advanced large angel remote
receiving technology.
Multiple control types
or ( + )
The duct and cabinet unit can be controlled be the wired controller or by the infrared controller. The
cabinet type unit can be controlled with the infrared controller. If the unit is duct type and you want
infrared type, you need to add an infrared controller YR-H71.
And the infrared controller can be equipped with the controller holder, convenient to fix the
remote controller.
4
automatically recover the previous running mode once the power supply is on.
Self-diagnostic function
In the course of operation, if the failure occurs, the failure code will display on the wired controller or
on the operation panel. Then according to the failure code chart, you can eliminate the failure soon.
detector.
2. SPECIFICATION
item Model AU96NATAEA
Function cooling heating
Capacity BTU/h 92000 96000
Capacity W 27000 28000
Sensible heat ratio 75% /
Total power input W 10000 9000
Max. power input W 13000 13000
EER or COP W/W 2.70 3.11
Dehumidifying capacity 10‐³×m³/h 10
Power cable 5*6.0
Signal cable section 1*1.5
Connecting cable section 3*2.5
Wired control cable for wired control unit section 3*0.5
Power source N, VAC, Hz 3, 380-400, 50
Running /Max.Running A/A cooling 18/22.8 heating16.5/22.8
Start Current A 36
Class of anti electric shock Ⅰ-class
Circuit breaker A 40
Max. operating pressure of heat side Mpa 3.0
Max. operating pressure of cold side Mpa 3.0
Unit model (color) AU96NATAEA(WHITE)
Model / Manufacture JT300D-Y1L / DAIKIN
Oil model /
Oil type MINERAL
Compressor Oil charging cm³ 3000
Type scroll
Protection type inner thermal protection, 3-phase protection, pressure
Starting method direct startup
Type × Number Axial × 1
Speed r/min /
Fan
Fan motor output power W 350
Air-flow(H-M-L) m³/h 10000/-/6000
Outdoor unit
Pipe
Gas mm 28.58
Connecting Method flared
MAX.Drop m 15
Between I.D &O.D
MAX.Piping length m 30
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DB
Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a sound
pressure noise level.
Installation state: the unit should be placed on the flat floor or be mounted in horizontal direction.
Testing method:
2m
duct
1m
1.4m
1m
outdoor unit:
1.air outlet from side: the noise level is the average sound pressure level measured from front, left, right
directions.
2.air outlet from top: the noise level is the average sound pressure level measured from front, back, left, right
directions.
measured point:
H ( height to the ground) = (h (unit height) + 1m) /2
and, it is 1m to each side.
1m
1m 1m
h
1m
WARNING!
If any abnormal phenomena is found Don't dismantle the outlet of the
outdoor unit.
(e. g.smell of firing), please cut off the
power supply immediately, and contact The exposure of fan is very dangerous
the dealer to find out the handling whichmay harm human beings.
method.
switch
off When need maintenance and repairment,
call dealer to handle it.
10
WARNING!
It easily cause electrical shock without The falling of goods and people may
circuit breaker. cause accidents.
Please let the dealer be responsible for Don't operate the air-conditioner with
installing the conditioner. damp hands.
Incorrect installation may cause water Otherwise will be shocked.
leak, electrical shock and fire hazard.
Earthing
11
Outdoor dimension
9D<=A7 8;63
66- 43-
33- 33-
.1-
.23-
61-
4--
./-
15
/3
./-
..2
160
3/ 52
.2-
12
Model: AD96
830
18 794 18
25
60
M5x20pcs Air inlet
138
13
250
1570
1690
1640
13 200 13
138
13
65
163 6x200=1200 163
35 1500 35
100
80
25
95
60
Control Box
M10x4pcs
138
250
25
13
25
310
360
49
A
30
106
138
77
13
185 170 45 200
530 13 13
60 1450 60
Installation dimension
Over 900 Over 900 (900x1730) Over 100 Over 300
35
Check Hole
(600x600)
900
Ceiling
35
100 60
Over 200
over 400
(mm)
13
Model: AP96
A
1200
1148
105
270
200
air outlet installation space
650
50
1000
100
power terminal block 179 terminal block center
1850
50 air outlet
787.5 terminal block center 600
air inlet
50
813
880
40
air inlet
1192.5
adjustment range
1222.5 15 320 20-50 20-50
15
315 442 425 50 50 50 425
8 300 8 82
200 50
80
72
100
19
36
150
83 83
142
95
142 78
310
(mm)
14
5. Installation Instructions
5.1 Outdoor installation procedure
Selection of installation site
Warning
It should be installed at places where it is firm enough to withstand the weight of the air
conditioner to prevent falling.
Typhoon and earthquake prevention. It should be installed according to specific
requirements.
Inasppropriate installation may lead to accidents. Blow out
Installtion space
(1)During installation, connect the outdoor unit and align Air inlet
Air inlet
the mounting surface(See the figure on the right).Mount
the electric distribution device on the external side of Air inlet
Base panel
1. Handing
Rope
As there is no protective package for the outdoor unit,so
the following points merit attention:
(1) When forklift is used, insert the fork into the holes in
the base plate.
(2) When crane is used, lift the unit with 4 pieces of steel
rope with diameter above 6 mm.
(3) Put protective materials between the cable and the
unit to prevent deformation and damage of the surface.
2.Mounting
(1) The distance between two connections must not be
less than 20mm.
Refer to the following figure for the distance between the 1100
foundation bolts.
Above 500mm
(3)In snowy regions,snow-proof facilities should be used(see
the figure below). Refrigerant tube
Warning
Tube fixing
panel
M6
M4
Bottom plate
Access hole cover
Tub
e to th
e ba ht
ck
to the tig
Tube
ht
to the tig
Tube
ft
to the le
the le
ft Tube
to
16 Tube
(6) During welding,the gas pipe valve must be cooled down with a wet cotton cloth.
2.Outdoor is higher
1.Outdoor is lower
Indoor
Outdoor Indoor
17
Crucial points:
When testing, never use oxygen,flamable and poisonous gases.
Step 1:Charge for more than 3 minutes under 0.3MPa(3.0kg/cm2g)
Step 2:Charge for more than 3 minutes under 1.5MPa(15kg/cm2g)
--Serious leakage may be found.
Step 3:Charge for more than 24 hours under 3.0MPa(3.0kg/cm2g)
--Small leakage may be found.
Check for pressure decrease
Without pressure decrease-Pass
With pressure decrease-Check for leaage.There will be a 0.01MPa(0.1kg/cm2g) pressure change
for every 1 C ambient temperature change during the 24-hour pressure charge.It should be
corrected during the test.
Low-pressure High-pressure
gauge gauge
Tightly
closed Solder joint Solder joint
Access hole
6.4
Copper
pipe
Tightly Tightly
closed Solder joint closed Relief valve
Nitrogen bottle
Indoor unit
Outdoor unit
Three-way valve fully closed liquid side
18
Vacuum Pumping
Use vacuum pump to evacuate the air.Never use the refrigerant for the evacuation.
Drain off the nitrogen gas after the leak test and then connect the vacuum pump as shown in the figure
below.
The vacuum pumping must be done from both the liquid and gas inlets.
Low-pressure High-pressure
gauge gauge
Three-way valve fully
Indoor Outdoor closed(gas side)
Gauge distributor
Tightly 6.4Copper pipe
closed Solder jointSolder joint
Access hole
P
Tightly Tightly
closed Solder joint closed Vacuum pump
Access hole
Indoor unit
Outdoor unit
Three-way valve fully closed
liquid side
Detailed diagram of the
three-way valve
To the gauge (Gas side )access hole
distributor (Gas side)three-way valve
(Liquid side)access hole
To the unit
(Liquid side)three-way valve
To the unit
Use a vacuum pump with high degree of vacuum(below-755mmHg) and large volume displacement
(above 40L/min)
The pumping time depends on the length of the connecting pipe.Generally,it takes about 2-3 hours.
Make sure that the Y-shaped valves on both the gas and liquid sides are closed before pumping.
If the vacuum can no reach-755mmHg within 2 hours,continue pumping for another 1 hour.
If the vacuum can no reach-755mmHg after more than 2 hour's pumping,close the valves VL and
VH on the gauge distributor and stop pumping.One hour later,check the vacuum again.If the
vacuum has changed,it means there is a leakage.Repair it.
After the above steps,replace the vacuum pump with the refrigerant pump and refill refrigerant.
Charging refrigerant
Refrigrant must be charged in liquid state. Containers for R22 refrigerant must be
Refrigerant bottle with or without a siphon marked with R22 and a brown Stripe.
tube can be refilled with refrigerant upright R407C refrigerant cannot share the same
or upside down,Respectively. instrument distributor and filling pipes.
19
Refilling of refrigerant
After the vacuum pumping,replace the vacuum pump with the refrigerant pump and refill refrigerant.
Calculation of refrigerant quantity
The factory filled refrigerant into the piping excludes the part of pipes according to be refilled on the site.
Refill the amount of refrigerant into the piping according to the following formula.
The factory filled refrigerant is listed in the table below:
The quantity of the refrigerant to be refilled during installation depends on the diameter and length
of the liquid piping.
The quantity of the refrigerant t be refilled on the site=Actual length of liquid tube x quantity of
refrigerant to be refilled for per meter of liquid pipe.
Recharge refrigerant
When the outdoor valve is shut,fill the refrigerant from the access hole at the gas and liquid sides.
If the required filling is impossible,open all the gas and liquid valves,then slightly shut the gas
valve, run the compressor and fill the refrigerant from the access hole at the gas side.Now adjust
the gas valve to control the refrigerant flow,which will be gasified during absorption by the system.
If there is insufficient refrigerant in the system caused by leaks,refill it after the remaining refrigerant
is recollected.
Open all valves
Open all the valves of the outdoor unit.
Heat isolation of the pipes
Separate isolation should be made for the liquid and gas pipes.
Materials used for the pipe isolation at the gas side must withstand above 120 C temperature.
For AU96NATAEA:
Charging refrigerant (R22): Before charging refrigerant, the pressure in the system
must be kept at least for 15 minutes under 130Pa, and the pressure will not go up
within 30 minutes, only in this case, the refrigerant can be filled.
When the connection pipe is less than 5 meters, additional refrigerant needs not be
charged. Once the connection jpipe is more than 5 meters, please recharge the
refrigerant as the following formula:
Refrigerant quantity=(lenth of connection pipe-5m)*115g
Detailed procedures:
a.Cut off the vacuum pump pipe to prepare charging refrigerant
b.Place the R22 container on the scales, switch off the low pressre valve of the
pressure pipe to make the liquid type refrigerant enter the system from the high
pressure side.
c.If the system pressure goes up, stop charging refrigerant and when the
refrigerant quantity arrives the rated value, switch off the high pressure valve,
then place the R22 container on the scales with the jaw to up. Open the low pressure
valve to start up the unit, at this time, the refrigerant is gas state.
When the charged refrigerant arrives the rated value, after confirming the refrigerant
quantity is proper, unload the flexible joint and install the copper nut of the connector.
20
Electric wiring
Note:
All the wires should be copper core wires.
The power cable of indoor unit should be equipped according to the operation manual indoor unit.
When connecting the indoor & outdoor wire, check the number of the indoor & outdoor terminals,
the terminals with the same number connected together with one wire.
Incorrect wiring will damage the controller of the air conditioner or make the unit work abnormally.
The air conditioner must use special power circuit and special air switch (40A), groundign wire.
The wiring work should be done by a qualified electrician according to the national wiring rule.
The creepage breaker must be installed. The grounding line and the neutral line of the receptacle
must be strictly separated. It is incorrect to connect the neutral line with the grounding line.
The connection type of power cord is Y connection. If the soft power cord is damaged, to avoid
risk, it must be replaced by the manufacturer or their specific repair department or similar professional
worker.
Wiring method
1.The wiring method of orbicular terminal
For the connection wire which end is orbicularterminal,
its wiring method is as the right figure shown.
Dismantle the screw and put it through the ring at
the end of the connection wire, then connect it to
the terminal block and tighten the screw.
The wiring method of orbicular terminal
2.The wiring method of straight terminal For those Wrong pressing
connection wires whose end are not orbicular terminals, Correct pressing
their wiring method is: Loosen the connecting screw, Terminal block
insert the end of the wire directly into the terminal block,
and then tighten screw. Pull the wire outwards slightly to Wire holding clamp
confirm it is held tightly.
(Sketch map)
3.Pressing method of connection wire:
After wiring, the connection wire must be pressed with wire
holding clamp. The wire holding clamp should press on the Terminal block of Y/G
out cover of the connection wire. As the right figure shown: indoor unit
1 2 3
Connect wire between indoor & outdoor unit
As the wiring diagram show to arrange the connection
wire. 1 2 3 L1 L2 L3 N
Terminal block of
outdoor unit Power supply:
Note: The terminal blocks mark at the two ends of the 3N,380-400V,50Hz
connection wire should be corresponding one by one, Power terminal
otherwise the air conditioner cannot work normally. block of outdoor
unit
Others
1. Power supply
The parameter of power cord is over 2.5mm .
Air conditioner must use an exclusive line (over 30A)
When installation air conditioner in a wet place, try to use a circuit breaker against
Current leakage.
For installation in other places, use circuit breaker as far as possible.
21
The breaker of the air conditioner should be all-pole switch ; and the distance between
its two contacts should be no less 3 mm.
Such means for disconnection must be incorporation in the fixed wiring
2. Pipe cutting and flaring
Be sure to carry out deburring after pipe cutting with a pipe cutter.
Insert flaring tool to make a flare.
Correct Incorrect
An example
Ventilation fan and gas leak alariming device
23
Installation instruction
Notice
This manual can not include all kinds of conditions, if you have new
requirements and questions, please contact with local Haier Sales Center.
Warning
Before installing the unit, please read this manual carefully. Improper
installation may cause accidents and make unit damage or death.
Installation tools
1. Screw driver 2. Hacksaw
3. 70mm dia. hole core drill 4. Spanner (dia. 17, 27mm)
5. Spanner (14, 17, 27mm) 6. Pipe cutter
7. Flaring tool 8. Knife
9. Nipper 10. Gas leakage detector or soap water
11. Measuring tape 12. Reamer
13. Refrigerant oil 14. Lead-solder tool
B Pipe clip
2
5
Self-tapping scerw
C Connecting hose
3 2
D Drain hose Wooden bolt
E Insulation material 4
Wall hole cover
2
F Putty 5 1
Piping hole cover
6 2
L-shaped metal
24
Installation procedure
1. Before installation
[Before finishing installation, do not throw the attached installation parts away.]
Confirm the route to carry the units to the installation place.
Do not remove the package of the unit, before carrying it to the installation place.
When have to remove the package, use a soft material or protection board with rope to lift
the unit to prevent the unit from damage or bumping scrape.
2. Selection of installation place
Select the firm place that will not influenced by vibration and can bear the weight of the
unit
Select the place with easy drainage and place can perform outdoor unit pipe connecting.
Select the place far away from heat source, vapor source and direct sunshine to avoid
the causing of the trouble in operation parts and the deformation of the casing.
Select the place where the cool air or warm air can evenly spread to every corner of the
room.
Select the place near power receptacle leaving sufficient space around the unit. (Referring
to installation diagram)
3. Installation space
Unit (mm)
50
600
1000
50
600
600
50
25
wall hole
wall thinkness
70mm
To prevent it from fall off, please fix the unit with fall-prevention fitting at wall and L-
shaped metal at floor.
Self-tapping
all-prevention fitting metal (accessory)
screw
Wood screw
Please install the whole unit
horizontally,with a slop of 1
degree at front and rear,left
L-shaped metal and right.
(accessory)
26
Piping connection
1. Connecting method
Apply refrigerant oil at half union and flare nut.
To bend a pipe, give the roundness as large as possible not to crash the pipe.
When connecting pipe, hold the pipe centre to centre then screw nut on by hand,refer to Fig.
Be careful not to let sundries, such as sands enter the pipe.
After opening inlet grill, you will see a control box as shown in the Fig.
Remove the cover before working.
Cut away, with a hammer or a saw, the lid for piping according to piping direction.
27
Insulation material
Drain hose
Copper tube Connecting electric cable
for indoor and outdoor unit
According to the piping method, connect the piping on indoor unit with union of connecting pipe.
Arrange the piping as per the wall hole and bind drain hose connecting electric cable and piping
together with polyethylene tape.
Insert the bound piping connecting electric cable and drain hose through wall hole to connect
with outdoor unit.
Arrangement of drain hose
Drain hose shall be placed in under place.
There should be a slope when arrange drain hose. Avoid up and down waves in drain hose.
Indoor unit
Up
Down Bad
Slope Good
If humidity is high, drain pipe( especially in room and indoor unit ) must be covered with insulation
material.
Main points of installation refrigerant pipe
Please install the gas pipe and liquid pipe according to the following shown method.
Please remove the cover piece on the gas pipe and the screw cap on the liquid pipe.
A
B
2 Please connect the connecting pipes between indoor and outdoor unit according to the
following method.
a) When introducing the pipe from right side
Use attached accessory <A> to connect the on-the-spot connecting pipe and gas
pipe.
A B
28
29
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING
INSTALLATION. FAI-LURE TO FOLLOW THESE INSTRUCTIONS COULD
1. Before installation [Before finishing installation, do not throw the attached parts installation needs]
Confirm the way to move the unit to the installation place.
Before moving the unit to the installation place, do not remove their packages.
When have to remove the package, use a soft material or protection board with rope to lift the unit assembly to avoid
unit damage or bumping a scrape.
2. Select installation place
(1) The chosen installation place should meet the following requirements and get the users consent.
Place ensures ideal airflow distribution.
The passage of airflow has no obstacles.
When importing outside air, it should be imported directly from outdoors. (if the pipe can not be extended, it also can
not be imported from top)
Place ensures enough space for maintenance.
The pipe length between indoor and outdoor unit is in the permitted limit (referring to outdoor unit installation part).
The indoor unit, outdoor unit, electric wire and connection wire is at least 1m away from television
and radio. This is to avoid the image disturbance and noise caused by the above-mentioned home appliance. (Even
if 1m away, if the electromagnetic wave is too strong, it can also cause noise.)
(2) The height of ceiling
The indoor unit can install on the ceiling, which height is no more than 3m.
(3) Install and use the hoisting screw. Check if the installation place can bear the weight of unit assembly.
If not certain, strengthen it before install the unit.
Checking meatus
Air out (600x600)
Over 200
Air in
Ceiling
360 890
250 600
794
Down side
Up side 750
30
Piping side
Supply water
Water level
0~5 mm PVC hose
(0~0.2") Piping side
Supply water
Water level
0~5 mm PVC hose
(0~0.2")
Bring the piping side slightly lower.
(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur.
5. Drain Piping
(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps.
31
Drain socket
VP 25 joint
Pipe cover(large) (field purchased)
[for insulation]
Main unit (accessory)
Drain hose VP 25
(field purchased)
Clamp (accessory)
(accessory) Adhesion Pipe cover
[for insulation]
Pipe cover(small) (field purchased)
[for insulation]
(accessory)
(e) The stiff PVC pipe put indoor side should be A downhill grade of VP 30
heat insulated. 1/100 or more
(f) Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain hose directly into
drainage,where the gas with sulfur may be generated.
(g) Backwater bend
Because the drain spout is at the position, which negative pressure may occur. So with the rise of water level in the
drain pan, water leakage may occur. In order to prevent water leakage, we designed a backwater bend.
The structure of backwater bend should be able to be cleaned. As the below figure shown, use T type joint.The backwater
bend is set near the air conditioner.
As figure shown, set a backwater bend in the middle of drain hose.
H2 H1
Procedures
1 Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.
2 Check the drain while cooling operation.
6. Installation of air suction and discharging duct
Please consult the after-sales service worker of Haier Air Conditioner for the choosing and installation
of suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawing
and outer static pressure, and choose the discharging duct with proper length and shape.
32
33
Duct
Air
Air
¢ duct
150 ¢
¢
¢
Torque spanner
Clamp
310
Down side
30
Drain hose connection mouth 530
45 2
R0.4~0.8
12.70 50N.m 1.2~2.0 90 0.5
A
Electric wiring
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE
COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
1 2 3 L1 L2 L3 N
OUTDOOR UNIT TERMINIAL BLOCK
36
Indoor unit:
top cover
suspending pole
outlet grill
evaporator(inside)
MODE TEMP + TEMP - FAN ON/OFF
LOCK
front panel
stop valve
side plate
inlet grill
duct
electric box
suspending bolt
bottom plate
drain pipe
Outdoor unit:
side plate
condenser (inside)
maintenance plate
compressor (inside)
piping hole
bottom plate
37
32 24
33 23 AUTO COOL DRY HEAT FAN
34 22
35 21
36
M D
OFF
20
5.HEALTH Button
19
Used to set health mode, if the unit has the negative ion function
1 TEMP
and oxygen bar function.
ON
2
SWING
OFF FAN
18 6.CLOCK Button
3 Used to set correct time.
4
MODE SLEEP
17 7.CLOCK Button
HEALTH FRESH
16 Used to select TIMER ON, TIMER OFF.
5
CLOCK SET (Note: if time of TIMER ON is the same as TIMER
6 15 OFF,TIMER ON/OFF cannot be set)
TIMER HIGH/SO
7 14
8. FILTER Button
FILTER
8 13 Used to set up/down function of filter.
RESET CODE LIGHT LOCK
12 9. CODE Button
9 11 Used to select code A or B, for this unit, the code is A.
10 10.RESET Button
Press this button by using a sharp article to resume
the correct operation of the remote controller in case
of need, i.e. for example in case of malfunctions due
to electromagnetic noise.
11.LOCK Button
Used to lock operation button and LCD display
1.TEMP Setting Button contents: by pressing this button, other buttons comes
(Used to set temperature. Setting ranges: out of function and lock state display appears; if you press
16 C to 30 C) it again, lock state will be no more active and lock state
In Up/Down function, for controlling up and display will disappear.
down filter. 12.LIGHT Button
Used to light the control panel (only for cabinet unit)
2.SWING Button
If you press this button once, auto swing will 13.Up and down Button
be activated. Used to set TIMER and CLOCK up or down.
If you press this button again, the louver will 14.HIGH/SO Button
fix in the present position. Used to select HIGH or SOFT operation.
3.Power ON/OFF Button 15.SET Button
Used to confirm TIMER and CLOCK settings.
Used for unit start and stop
16.FRESH Button
After power on, the LCD of remote controller Used to set fresh mode, the unit will draw in fresh air.
will display the previous operation state (except 17.SLEEP Button
for TIMER,SLEEP and SWING state). (The clock must be corrected before setting sleep
function)
Used to set sleep mode.
NOTE: 1.Cooling only air conditioner does not have the displays and functions related to heating.
2.HIGH/SO button
This button is activated in Cooling/Heating mode, the fan speed is in AUTO mode after pressing it and "high
functon" will be cancelled automatically after 15 minutes running.
38
18.FAN Button The distance between the remote controller and the receiver
should be max 7m and there should be no obstacle between them.
Used to select fan speed:LOW,MID,HIGH,AUTO. Do not throw the remote controller; prevent it from being
19.TIMER OFF Display damaged.
20.CLOCK Display When operating the remote controller in an area where
electronically controlled lights are installed or wireless handsets
21.FILTER Display are used, please move closer to the indoor unit as the function
22.TEMPERATURE Display of the remote controller might be affected by signals emitted
23.AUTO SWING Display by the above mentioned equipments.
24.HIGH/SO Display
25.SIGNAL SENDING Display Battery loading
26.FRESH AIR Display Battery loading
27.ELECTRICAL HEATING Display
*
Batteries are fitted as follows:
*
*
28.Some other buttons
*
Remove the battery compartment lid
All these functions are not available now. Slightly press and disengage the battery compartment lid marked
with ì î and then hold the remote controller by the upper
29.HEALTH Display
section and then remove the battery compartment lid by pressing
Displays when healthy run function is set. in the direction of the arrow as shown in the figure above.
30.DEHUMIDIFICATION Display
Loading the battery
31.Operation MODE Display Ensure that batteries are correctly placed in the compartment
as required for positive and negative terminals.
AUTO RUN COOL RUN DRY RUN HEAT RUN FAN RUN
HI
If the remote controller does not operate as designed after
fitting new batteries of the same
AUTO
type, press the Reset button (marked ) with a pointed article.
AUTO
Note:
It is recommended that the batteries be removed from the
36.TIMER ON Display compartment if the remote controller is not used for an extended
period.
Remote Controller' Operation The remote controller is programmed for automatic test of
When in use, direct signal transmission operation mode after the batteries are replaced. When the test
head to the receiver placed on the indoor is conducted, all icons will appear on the screen and then
disappear if the batteries are properly fitted.
unit
When unit is started for the first time and after replacing batteries in remote HEALTH FRESH
1.Press CLOCK button, clock indication of " AM " or " PM " flashes. 1 TIMER 2 HIGH/SO 3
2.Press or to set correct time. Each press will increase or decrease FILTER
1 min. If the button is kept pressed, time will increase or decrease quickly.
RESET CODE LIGHT LOCK
HEALTH FRESH
2
LOW MID HIGH
CLOCK SET
TIMER HIGH/SO
Air conditioner will run at the selected fan speed.
FILTER When in AUTO mode, unit will adjust fan speed
RESET CODE LIGHT LOCK
according to room temperature automatically.
4. Unit stop
Press ON/OFF button to stop unit.
40
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
A
U
T
O
On reaching temp.setting
+2 C, unit will run in mild
DRY mode.
In ATUO mode, the temperature setting is not displayed on LCD. In this mode, during running air conditioner
will select COOL, HEAT or FAN mode automatically according to the room temperature.
In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit will run intermittently
at LOW speed regardless of FAN setting. When room temperature is lower than temperature setting, unit will
only run FAN operation.
In HEAT mode,warm air will blow out after a short period of time due to cold-draft prevention function.
41
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
ON
OFF
SWING FAN Please carefully set temperature when children,
MODE SLEEP old or infirm people ues the air conditioner.
HEALTH FRESH
CLOCK SET
In case of great humidity, If the vertical flaps
TIMER HIGH/SO are completely turned towards left or right, the
louver will drop water.
FILTER
Hints:
As in COOL mode air flows downwards, adjusting airflow horizontally will be much more helpful
for a better air circulation
As in HEAT mode air flows upwards, adjusting airflow downward will be much more helpful for
a better air circulation.
Be careful not to catch a cold when cold air blows downward directly.
42
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
Sleep Function
Before going to bed you can press down the SLEEP button and the air conditioner will run so as to make
you sleep more comfortably.
Before using this function, the clock must be set.
Operation Mode
1.In COOL, DRY mode SLEEP RUN BEGINS SLEEP RUN STOPS
One hour after sleeping operation start, the temperature about 6 hrs
is 1 C higher than the setting one. After another hour,
temperature rises 1 C: sleep run continuously for another increase 1 C
6 hours and then stops. The actual temperature is higher
than the setting one which is to prevent from being too 1 hrs increase 1 C
cold to your sleep.
SETTING T SHUT DOWN
2.In HEAT mode
One hour after sleeping operation start, the temperature In COOL,DRY mode
is 2 C lower than the setting one. After another hour,
temperature decreases by 2 C more. Temperature will
automatically rise by 1 C after another 3 hours'
continuous operation. The actual temperature is lower SETTING T SHUT DOWN
than the setting one which is to prevent from being too
1 hrs decrease 2 C
hot to your sleep.
1 hrs
decrease 2 C
3.In AUTO mode. about 6 hrs
The air conditioner will run in corresponding sleep 3 hrs increase 1 C
operation according to the automatically selected
operation mode. SLEEP RUN STOPS
SLEEP RUN BEGINS
In HEAT mode
OFF
Notes:
TEMP
If set-sleep time does not reach 8 hours, unit will automatically stop operation MODE SLEEP
CLOCK SET
Set " TIMER ON " or " TIMER OFF "In COOL,DRY mode function first, TIMER HIGH/SO
then set SLEEP. After set SLEEP function, the TIMER function cannot be FILTER
43
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
1.Unit start
A After unit start, select your desired operation mode (operation
mode will be displayed on LCD)
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER
mode. Every time the button is pressed, display of TIMER mode
changes as follows:
Hints:
After replacing batteries or if a power failure occurs, TIMER setting
must be reset.
Remote controller has memory function. When you use TIMER
mode next time, just press SET button after mode selection if timer
setting is the same as the previous one.
Note:
After setting TIMER function, the remote controller displays TIMER time. If you want to see clock time,
just press CLOCK button once: clock time will be displayed (if you press the button again continuously,you
can adjust clock). 5 seconds later, the display will show TIMER time again.
44
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
Filter Up/Down
(Only for 600*600 panel of single unit)
After the air conditioner has operated for a certain period, dust has
accumulated on the filter, and the filter up/down function can be used
to clean it.
A
HEALTH FRESH
3.Press temperature " " button or time " " button in filter
up/down waiting status: the up/down mechanism makes
CLOCK SET the filter to moving upward till near the surface board and
then automatically adjusts it to reset (when adjusting to reset,
TIMER HIGH/SO
it will not be controlled by the remote controller till the adju-
FILTER
stment is finished).
RESET 1
CODE LIGHT LOCK
Note:
If the filter does not thoroughly go back to the original position, only needs to
operate several times repeatedly.
46
A
U
T
O
ON
TEMP
TIMER HIGH/SO
FILTER 1
RESET CODE LIGHT LOCK
OFF
Press the HIGH/SO button twice
If the button is pressed once, the indication is displayed
on the remote controller. If you press the button once again,
the indication disappears, regular operation is restored and fan
speed goes back to the mode set before "High Mode" operation.
NOTICE:
When the air conditioner is operating in " High Mode " , unevenness of room air temperature
may occur due to the intensive operation in a short time.
Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular
operation is automatically restored.
47
ON
SWING
OFF FAN
ON
MODE SLEEP
Press the HIGH/SO button twice
HEALTH FRESH
The indication appears on the display of the remote
CLOCK SET controller and operation in "Soft Mode" starts.
The AUTO fan speed is automatically set and the corresponding
TIMER HIGH/SO
indication is also displayed.
FILTER 1
RESET CODE LIGHT LOCK
OFF
Press the HIGH/SO button twice
If the button is pressed once, the indication is disappears
from the remote controller's display. If you press the button
once again, regular operation is restored and fan speed goes
back to the mode set before "Soft Mode" operation.
NOTICE:
When the air conditioner is operating in " High Mode " , unevenness of room air temperature
may occur due to the intensive operation in a short time.
Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular
operation is automatically restored.
48
A
U
T
O
TEMP
ON
SWING
OFF FAN
MODE SLEEP
HEALTH FRESH
CLOCK SET
TIMER HIGH/SO
FILTER
49
M\fd]k\mdih ia ^fi^e
q{x, 230,|,z -, 2{x 3,|2 y-0 2{x y|012 2|+xL 2{x v*-v~ 1{-3*w ux vt*|u0t2xwN n{x +x2{-w -y vt*|u0t2|-, |1Z
QNk0x11 G^*-v~G u322-,L 2{x ^*-v~ w|1.*t7 G \hG G khG 5|** y*t1{N
RNk0x11 -0 2- tw}312 2|+xN a-0 xtv{ .0x11L 2{x 2|+x 5|** |,v0xt1x -0 wxv0xt1x Q +|,32xN dy wx.0x11|,z
2{x u322-,L 2{x 2|+x 5|** |,v0xt1x -0 wxv0xt1x 0t.|w*7N
SN\y2x0 v-,y|0+|,z 2{x 2|+xL .0x11 G mx2G u322-,L G \hG -0 G khG 5|** 12-. y*t1{|,zL2{x v*-v~ 5|** uxz|, 2- 5-0~N
50
lxv-++x,wt2|-,1
o1x ^jjg |, 13++x0N
o1x c`\n |, 5|,2x0N
o1x _ls |, 1.0|,zLt323+, t,w |, wt+. v*|+t2xN hj_` a\i mqdib
k0x11 hj_` u322-,N a-0 xtv{ .0x11L -.x0t2|-, adgn`l l`m`n l`m`n
+-wx v{t,zx1 t1 y-**-51Z \h
9
jiOjaa
\onj ^jj _ls c`\n a\i
5
o,|2 5|** 03, |, -.x0t2|-, +-wx w|1.*t7xw -,
g^_Nm2-. w|1.*t7 t2 7-30 wx1|0xw +-wxN
ISJ mx*xv2 2x+.N o,|2 03,1 t2 2{x 1.xxw w|1.*t7xw -, g^_Nd,
c`\n +-wxL 5t0+ t|0 5|** u*-5 -32 ty2x0 t
k0x11 n`hk u322-, 1{-02 .x0|-w -y 2|+x w3x 2- v-*wMw0ty2 .0x4x,2|-,
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2x+.N 1x22|,z y3,v2|-,N
|,v0xt1x1 Q ^N d, _ls +-wxL 5{x, 0--+ 2x+.N uxv-+x1 R ^
dy u322-, |1 ~x.2 wx.0x11xwL 2x+.N1x22|,z 5|** {|z{x0 2{t, 2x+.N 1x22|,zL 3,|2 5|** 03, |,2x0+|22xM
|,v0xt1x /3|v~*7N ,2*7 t2 gjq 1.xxw 0xzt0w*x11 -y a\i 1x22|,zN
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2x+.N 1x22|,z IUJ o,|2 12-.
wxv0xt1x1 Q ^N k0x11 jiOjaa u322-,N
dy u322-, |1 ~x.2 wx.0x11xwL 2x+.N 1x22|,z 5|** j,*7 2|+x t,w 0--+ 2x+. 0x+t|,1 -, g^_N
wxv0xt1x /3|v~*7N \** |,w|vt2-01 z- -32N
o,|2 5|** 12t02 03,,|,z 2- 0xtv{ 2{x 2x+.N 1x22|,z px02|vt* y*t. v*-1x1 t32-+t2|vt**7N
-, g^_N
ITJ at, 1.xxw c|,2
k0x11 a\i u322-,N a-0 xtv{ .0x11L q|0x v-,20-**x0 vt, +x+-0|8x xtv{ -.x0t2|-,
yt, 1.xxw v{t,zx1 t1 y-**-51Z 12t231N
q|0x v-,20-**x0 @RQM q{x, 12t02|,z |2 ,x62 2|+xL }312 .0x11 jiOjaa
u322-, t,w 3,|2 5|** 03, |, .0x4|-31 12t231N
JMS KHC GHFG @RQM
lx+-2x v-,20-**x0 x
.
-
*
\32- 03,,|,zZ _30|,z 2{x \32- 03,,|,z +-wxL t|0 v-,w|2|-,|,z 03,,|,z t,w vt, t32-M1x*xv2 2{x
v--*|,zL{xt2|,zL yt, +-wx tvv-0w|,z 2- 2{x 0--+ 2x+.x0t230xN
at, 03,,|,zZ n{x \^ -,*7 {t4x t|0 13..*7 03,,|,z ,- v--*|,z t,w {xt2|,z 03,,|,z t2 2{x v-,w|2|-,L
\^ vt,H2 {t4x t32- t|0 13..*7 03,,|,zL t,w vt,H2 w|1.*t7 2{x 1x22|,z 2x+.x0t230x 4t*3x -, 2{x g^_N
_30|,z 2{x {xt2|,z 03,,|,zL ty2x0 12t02 2{x \^L |, -0wx0 2- .0x4x,2 v--*xw t|0L \^ vt, 12-. y-0 t
5{|*x uxy-0x 1x,w {xt2 t|0N
_30|,z 2{x wx{3+|y|vt2|-, 03,,|,zL 5{x, 2{x 0--+ 2x+.N 1x22|,z 2x+.N L ,-2 1x22|,z v-,w|2|-,
tvv-0w|,z 2- 2{x t|0 1.xxwN
51
\h \h
7
adgn`l l`m`n ODPDQ
ML MEE V`Ub_
MEE
Iji -0 jaaJ 5
@FAYdg`k l`mmdhb
k0x11 ndh` u322-,N
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2|+x |,v0xt1x1 QP+|,Ndy u322-, |1 ~x.2
wx.0x11xwL 2|+x 5|** v{t,zx /3|v~*7N
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2|+x wxv0xt1x1 QP+|,Ndy u322-, |1 ~x.2 wx.0x11xwL
2|+x 5|** v{t,zx /3|v~*7N
n|+x 5|** ux 1{-5, -, g^_N d2 vt, ux tw}312xw 5|2{|, RT{-301N
@GAMihadkgdhb qink l`mmdhb
\y2x0 1x22|,z v-00xv2 2|+xL .0x11 m`n u322-, 2- v-,y|0+ GjiG -0 GjaaG 12-.1 y*t1{|,zN
n|+x w|1.*t7xwZ o,|2 12t021 -0 12-.1 t2 6 {-30 6 +|, Iji -0 jaaJN n|+x0 +-wx |,w|vt2-0 *|z{21 3.N
n- vt,vx* ndh`l
e312 .0x11 ndh`l u322-, 1x4x0t* 2|+x1 3,2|* ndh`l +-wx w|1t..xt01N
\vv-0w|,z 2- 2{x 1x2|,z 2|+|,z -.x,L v*-1x 1x/3x,vxL vt, 0xt*|8x y|012 -.x, 2{x, v-*1x 2{x 3,|2
-0 y|012 v*-1x 2{x, -.x, 2{x 3,|2N
QdhmlJ q|0x v-,20-**x0 .-11x11x1 +x+-07 y3,v2|-,L 5{x, 31x ndh`l +-wx ,x62 2|+xL }312
.0x11 m`n u322-, ty2x0 +-wx 1x*xv2|,z |y 2|+x0 1x22|,z |1 2{x 1t+x t1 .0x4|-31 -,xN
q|0x 0x+-2x v-,20-**x0 -0 0x+-2x v-,20-**x0 vt, +x+-0|8x xtv{ 5-0~|,z v-,w|2|-,N ix62
2|+x -.x, 2{x 3,|2L -,*7 ,xxw 2- .0x11 2{x jiOjaa ~x7L 2{x \^ vt, 5-0~ tvv-0w|,z 2-
*t12 2|+x 5-0~|,z v-,w|2|-,NIn|+|,zL m*xx.|,z t,w m5|,z +-wx ,-2 |,v*3wxwNJ
a0-+ n|+|,z v*-1x 2- 2|+|,z -.x,L vt, 1x22|,z 1*xx. +-wxN
k*xt1x v*-1x {xt*2{ y3,v2|-, y|012 uxy-0x 1x22|,z n|+x0L 2{x, 7-3 vt, w- 2{x ndh`l ji
-.x0t2|-,Nk*xt1x w- ,-2 31x 2{x {xt*2{ y3,v2|-, 5{x, |, ndh`l ji 12t2xN
52
n`hk c`\gnc
^gj^f
7 m`n
\h 8 9
adgn`l l`m`n ODPDQ
kh
jiOjaa
5
ndh`l jiMjaa
@DAKam`k nhdm lm\kmB l`f`^m qink _`ldk`_ ij`k\mdih gi_`
j.x0t2|-, +-wx 5|** ux w|1.*t7xw -, g^_N k-5x0 |,w|vt2-0 *|z{21 3.N
@EA Vk`ll YRSOW ]nmmih mi ^c\hb` YRSOW gi_`
`4x07 2|+x 2{x u322-, |1 .0x11xwL w|1.*t7 v{t,zx1 t1 y-**-51Z
ML
ML MEE V`Ub_
MEE
ji
mx*xv2 jaa N
@FAYdg` l`mmdhb aik YRSOW UT
k0x11 ndh` u322-,N
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2|+x |,v0xt1x1 QP+|,Ndy u322-, |1 ~x.2 wx.0x11xwL 2|+x 5|** v{t,zx
/3|v~*7N
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2|+x wxv0xt1x1 QP+|,Ndy u322-, |1 ~x.2 wx.0x11xwL 2|+x 5|** v{t,zx
/3|v~*7Nn|+x 5|** ux 1{-5, -, g^_Nd2 vt, ux tw}312xw 5|2{|, RT{-301N
\h 0xyx01 2- +-0,|,z t,w kh 2- ty2x0,--,N
@GA Ydg` ^ihadkgdhb aik YRSOW
\y2x0 2|+x 1x22|,zL .0x11 ndh`l u322-, 2- v-,y|0+NGjiG 12-.1 u*|,~|,zL q{|*x GjaaG 12t021 u*|,~|,zN
n|+x w|1.*t7xwZ o,|2 12t021 t2 r{-30 r +|,N
@HAYdg` l`mmdhb aik YRSOW UPP
a-**-5 2{x 1t+x .0-vxw30x1 |, Gn|+x 1x22|,z y-0 ndh`l jiGN
@IAYdg` ^ihadkgdhb aik YRSOW UPP
\y2x0 2|+x 1x22|,zL .0x11 m`n u322-, 2- v-,y|0+GjaaG 12-.1 y*t1{|,zN
n|+x w|1.*t7xwZ o,|2 12-.1 t2 r {-30 r +|,N
n- vt,vx* ndh`l +-wx
e312 .0x11 ndh`l u322-, 1x4x0t* 2|+x1 3,2|* ndh`l +-wx w|1t..xt01N
\vv-0w|,z 2- 2{x n|+x 1x22|,z 1x/3x,vx -y ndh`l ji -0 ndh`l jaaL x|2{x0 m2t02Mm2-. -0
m2-.Mm2t02 vt, ux tv{|x4xwN
53
+-0x v-+y-02tu*xN \h \h
k0x11 mg``k u322-, -,vx 2- +t~x 2{x t|0 v-,w|2|-,x0 {t4x jiOjaa
2{x .0xM1x2 1*xx. 2|+x Iy|012 .-5x0M-, |1 GQ{GJL 2{x 1*xx. 17+u-*
5|** t..xt0N k0x11 2|+x u322-, L 7-3 vt, 1{--1x 2{x 2|+x
|, Q9X {-301N `tv{ .0x11 -y L 2{x 2|+x |,v0xt1x1O0xw3vx1
Q{-30 t,w G6{G t..xt0 |, 2{x {3+|w|27 1x22|,z t0xtL GjaaG t..xt01
|, Gndh`l jaaG w|1.*t7 t0xt t,w 2|+x0M-yy 2|+x[ .0x11 mg``k
u322-, tzt|, 2- vt,vx* 1*xx. y3,v2|-,L 2{x 1*xx. 17+u-* w|1t..xt01N
Rh ^iifdhbB _`cngd_daqdhb gi_`
j,x {-30 ty2x0 1*xx.|,z -.x0t2|-, 12t02L 2{x 2x+.N |1 Q B {|z{x0 2{t, 2{x 1x22|,z -,xN \y2x0 t,-2{x0 {-30 2{x
2x+.N 0|1x1 Q B t,w 2{x, 03, v-,2|,3-31*7 y-0 t,-2{x0 V{01H t,w 2{x, v*-1xN n{x tv23t* 2x+.N |1 {|z{x0 2{t,
2{x 1x22|,z -,x 5{|v{ |1 2- .0x4x,2 y0-+ ux|,z 2-- v--* 2- 7-30 1*xx.N
Rh c`\mdhb gi_`
j,x {-30 ty2x0 12t02 3.L 2{x 2x+.N wxv0xt1x R B *-5x0 2{t, 2{x 1x22|,z -,xN \y2x0 t,-2{x0 {-30 wxv0xt1x u7
+-0x R B N
n{x 2x+.x0t230x 5|** t32-+t2|vt**7 0|1x u7 Q B ty2x0 t,-2{x0 S{01H -.x0t2|-,L t,w 2{x, t32-+t2|vt**7 v*-1x
ty2x0 S{01H v-,2|,3-31 -.x0t2|-,N n{x tv20t* 2x+.x0t230x |1 *-5x0 2{t, 2{x 1x22|,z -,x 5{|v{ |1 2- .0x4x,2
y0-+ ux|,z 2-- {-2 2- 7-30 1*xx.N
Tim`J d, \onj +-wxL 3,|2 5|** 03, |, mg``k y3,v2|-, tvv-0w|,z 2- 2{x -.x0t2|-, +-wxN
\y2x0 1x22|,z mg``k y3,v2|-,L |2 |1 y-0u|wwx, 2- vt*|u0t2x v*-v~N
dy 2{x 1x2 1*xx.M2|+x w-x1 ,-2 0xtv{ X {-301L 2{x 3,|2 5|** 12-. -.x0t2|-, t32-+t2|vt**7 ty2x0 1x2 2|+x
|1 v-+.*x2xN
mx2 Gndh`lMjaaG y3,v2|-, y|012L 2{x, 1x2 mg``kL t,w 2{x 1*xx.M1x2 |1 .x0y-0+t,vx[ 1x2 ndh`lMji
y3,v2|-, y|012L 2{x 1*xx. y3,v2|-, vt, -,*7 ux 1x2 uxy-0x ndh`lMji[ |y 1x2 2{xmg``k y3,v2|-, y|012L
2{x ndh`l y3,v2|-, vt, ,-2 ux 1x2N
\y2x0 1x22|,z 1*xx. y3,v2|-,L ,-2 t**-5xw 2- tw}312 2{x v*-v~N ^t,H2 31x 2{x 0x+-2x v-,20-**x0 -.x0t2x 2{x
\^N dy 1-L .*xt1x vt,vx* 2{x 1*xx. y3,v2|-, y|012N
\y2x0 1x22|,z 1*xx. y3,v2|-,L vt,H2 1x2 2{x 2|+|,z y3,v2|-,N
5 \f tu-32 V {01
wxv0xt1x RB
5 \f Q {0 |,v0xt1x Q^
wxv0xt1x1 RB
tu-32 S {01
|,v0xt1x Q^
Q {0
S {01 |,v0xt1xQ B
m`nndib n mcon _jqi
54
Zl`k M\nmdih
\u-32 2{x 0x+-2x v,-20-* -.x0t2|-,L tu-4x -,*7 2t~x 5|0xw 0x+-2x v-,20-**x0 t,w 0x+-2x v-,20-**x0
t1 t x6t+.*x tu-32 2{x 0x+-2x v-,20-**x0 t,w 0x+-2x 0xvx|4x0 31x +x2{-wL |2 |1 2{x 1t+x 0x+-2x
v-,20-**x0 L .*xt1x 31x 0xyx0 2- tu-4x +x2{-wN
i- 1*xx. y3,v2|-, 5{x, 31x 0x+-2x t,w 0x+-2x 0xvx|4x0N
55
QNc-5 2- 31x 2{x {xt*2{ y3,v2|-, I-,*7 y-0 3,|21 5|2{ 2{|1 y3,v2|-,J
\y2x0 1x2 2{x 0|z{2 y3,v2|-, +-wxL .0x11 {xt*2{ u322-,L
hj_` a\i mqdib
0x+-2x v-,20-**x0 -0 5|0x v-,20-**x0 w|1.*t71 G GL-67zx, .3+.
n`hk c`\gnc
-0 ,xzt2|4x |-, zx,x0t2-0 12t021 3. 2- t..*7 -67zx, -0 ,xzt2|4x
|-, 2- |,w--0 3,|2N k0x11 2{x u322-, tzt|,L2{x 1|z, G G w|1t..M
^gj^f m`n
m`n
xt0xw t,w ,xzt2|4x |-, zx,x0t2-0 12-.1 5-0~|,zN \y2x0 t** {xt*2{
y3,v2|-, -y 2{x |,w--0 3,|2 ux|,z y3**7 vt,vx*xwL -67zx, .3+.
ndh`l mg``k
;
adgn`l l`m`n l`m`n
12-..xwN
jaa
\h \h
jiOjaa
^\ondjiZ
q{x, 2{x 2x+.x0t230x -y 2{x -32w--0 3,|2 |1 *-5x0 2{t, TB L
-67zx, .3+. |1 t32-+t2|vt**7 12-..xwL |y .0x11 {xt*2{ u322-,
}312 2{x,L -67zx, .3+. v-3*w ,-2 12t02 3.N ]32 |y 2{x t|0 v-,w|M
j, 2{x Gcxt*2{G +-wxL |y 7-3 5t,2 2- 2|-,x0 {t1 2{x ,xzt2|4x |-, y3,v2|-, 1|+3*2t,x-31L5{x, .0x11
1x22|,z 2|+|,z -.x, +-wxL 1{-3*w 2{x {xt*2{ u322-,L ,xzt2|4x |-, y3,v2|-, v-3*w 12|** ux -.x0t2xwN
v*-1x 2{x {xt*2{ y|012Z j, 2{x 2|+|,z q{x, 2{x 2x+.x0t230x -y 2{x -32w--0 3,|2 |1 {|z{x0 2{t, V B L
-.x, +-wxL .*xt1x w-,H2 31x {xt*2{ -67zx, .3+. v-3*w t32-+t2|vt**7 0x13+x 2- -67zx,M+t~x
y3,v2|-,N y3,v2|-,N
a-0 cMhlp 5|0xw 27.x |,w--0 3,|2L 2{x 5|0xw v-,20-**x0 vt, ux +t2v{xw 5|2{ 2{x 0x+-2x v-,20-**x0
slMcWQ 2- 0xt*|8x 2{x 0x+-2x v-,20-* y3,v2|-,N
gxy2 .|v230x |1 t 5|0xw 0x+-2x v-,20-**x0L 5{|v{ vt, ux 31xw -, mx0|x1 5|0xw v-,20-*
3,|21 Ln{x 0x+-2x v-,20-**x0 vt, ux .30v{t1xw x620t**7N
] \
q|0xw 0x+-2x ^-,20-**x0 31|,z +x2{-wZ
QNo1x -,x 5|0xw 0x+-2x v-,20-**x0N mxx y|z IQJ
K
Z
Y
U
RN\*1- vt, u37 t 0x+-2x v-,20-**x0 x620t**7L 0xt*|8x
h _
UPP
ji
FC[c`h mc` k`gim` ^ihmkiff`k ^\h ]` nl`_ ih l`kd`l pdk`_ k`gim` ^ihmkiff`k
mqdib
hj_`
jaa
mg``k
a\i
nhdml Bmc\h jf`\l` jk`ll mc` ]immih ?MUNO?mi ^ciil` mc` jkibk\g ia ^i_` ?K?
c`\gnc al`mc
^gj^f m`n
ndh`l cdbcOmj
adgn`l
m`n m`n
ndh`l mg``k ndh`l mg``k
< ljjh
^ < ljjh
^
ji jaa ji jaa
adgn`l l`m`n l`m`n adgn`l l`m`n l`m`n
jiOjaa jiOjaa
56
FC Xpdm^c l`mmdhb
n{x 15|2v{1 1x22|,z t1 y-**-51ZQNji RNjaa SNji TNjaa mv0x5 {-*x
Tim`
n07 t1 yt0 t1 .-11|u*x t y*t2 130ytvx y-0 |,12t**t2|-,N
_-,H2 31x x6vx11|4x y-0vx 5{x, 2|z{2x,|,z 1v0x51L
-0 *-5x0 .t02 +|z{2 z-2 wxy-0+xwN
S ^ sx**-5 ^jh
T _
Qdhm QN k-5x0 13..*7 15|2v{ t,w 1|z,t* 5|0x 1{-3*w ux .0x.t|0xw u7 2{x 31x0N
RN _-,H2 2-3v{ k^] 5|2{ {t,wN
57
8. Refrigerant Diagram
The part function as follow:
temperature
heat exchanger
Compressor:
sensor
To absorb the refrigerant in the evaporator, and
compress to the condensing pressure, then
discharge them to the condenser.
Condenser:
Condense the refrigerant with high pressure
outdoor unit
from the compressor into the liquid state.
Capillary:
a.Make the pressure change from condensing
nonreturn valve
pressure to evaporating pressure
compressor
silencer
b.Make the partial liquid change into steam
Evaporator:
4-way valve
Make the liquid state refrigerant evaporated into
strainer
accumulator
steam, which can absorb the heat energy of cooled
object.
3-way stop valve
welded
welded
point
point
liquide pipe
gas pipe
welded
heat exchanger
welded
point
point
temperature
sensor
indoor unit
capillary
58
After running for 9 minutes from compressor startup, the unit will check if the indoor coil
temperature is below 0℃, the outdoor fan motor will stop running.
After the compressor stops, if the below conditions can be met, the compressor and the outdoor fan
Once the compressor stops running, you can restart up only after 3 minutes. When the unit
powered off in operation, if the shutoff time is below 3 minutes, it will be 3 minutes at least after
powered on when the compressor starts up again. Powered on for the first time, there is no
1) Starting condition
The unit is in heat mode, and the compressor runs for 35 minutes continuously.
The compressor has run totally for 45 minutes, and the compressor runs for over 5 minutes
continuously.
If either of the above conditions is met, and the indoor receives the defrosting signal from the
outdoor unit, the unit begins to defrost and send the signal to outdoor.
2) Quit condition
The outdoor receives the signal to quit from the defrost or the defrosting time is over 12 minutes,
the defrost will be over and send the relative signal to the outdoor.
When the indoor coil temperature is over 68℃ for 10 seconds, the compressor and the outdoor fan
motor will stop. When the compressor has stopped for 3 minutes and when the coil temperature is
below 46℃, the compressor and the outdoor fan motor will operate again.
If it is the first time in heat mode or the defrost is over, when the indoor coil temperature is below 28
59
℃, the indoor fan motor will stop when the indoor coil temperature is no less than 28℃ and less
than 38℃, the indoor fan motor will run in low speed when the indoor coil temperature is over 38℃
or the compressor has run for over 4 minutes, the indoor fan motor will run at the set speed.
If the refrigerant in the system cannot flow fluently or the airflow circles more slowly, please check
10.1.1 Cooling
bad cooling
bad ventilation if fan is set as low speed set the fan as med speed
Figure 1
10.1.2 Hearting
60
Figure 2
10.1.3 Unit operation
a. Indoor fan not running
61
no
yes yes
change voltage change PCB change fan
dependent resistor motor
Figure 3
b. Outdoor fan not running
if the power LED on outdoor PCB
is proper
no
yes yes
change voltage change PCB change fan
dependent resistor m otor
Figure 4
10.2 Failure code
AP96NACAEA adopts operation panel+infrared control type, while AD96NAHAEA adopts wired
control type. If the air conditioner occurs failure, the failure code will be displayed on the wired
controller or the operation panel as the following chart:
62
if LED on PCB is
lighted on
yes
yes
no if indoor transformer
reconnect is connected to the no if the fuse of indoor
socket firmly PCB is burnt off
yes yes
63
d is p la y E 0
c h e c k if t h e f lo a t no
m o d if y it s p o s it io n
s w it c h is lo c a t e d
yes
c h e c k if f lo a t s w it c h
w o r k s n o r m a lly
no
c h a n g e f lo a t s w it c h
s ta r t
d is p la y E 1
c h e c k if th e in d o o r no
a m b ie n t te m p . s e n s o r a d ju s t its p o s itio n
is lo c a te d p r o p e r ly
yes
c h e c k if th e s e n s o r
v a lu e is r ig h t
no
change sensor
64
s ta rt
d is p la y E 2
c h e c k if in d o o r c o il no
te m p .s e n s o r is a d ju s t th e p o s itio n
lo c a te d
yes
c h e c k if th e s e n s o r
v a l u e i s r ig h t
no
c h a n g e th e s e n s o r
s ta rt
d is p la y E 3
c h e c k if o u t d o o r no
a m b ie n t t e m p . s e n s o r a d ju s t t h e p o s it io n
is lo c a t e d
yes
c h e c k if t h e s e n s o r
v a lu e is r ig h t
no
c h a n g e th e s e n s o r
65
s ta rt
d is p la y E 4
c h e c k if o u td o o r c o il no
a d ju s t th e p o s itio n
te m p .s e n s o r is
lo c a te d
yes
c h e c k if th e s e n s o r
v a lu e is r ig h t
no
c h a n g e th e s e n s o r
start
display E5
if compressor
stops suddenly in
running and
alarms no
yes yes
analyse reason of
analyse reason of
compressor overheat,
compressor overheat,
and refer to the system
and solve it
information
yes
switch off power,and power
on when temperature reduces
to 30-40degree, start up again
8) E6 – pressure protection
66
display E6
67
start
display E9
no
check if communication
yes change
circuit of indoor and
PCB
outdoor is damaged
68
BL
R
B
DETECTOR
T6.3A/250VAC
FAN MOTOR
FUSE
M W
FAN MOTOR
Y/G W B R
CAPACITOR
TRANSFORMER Y/G
M
Y/G W FC
CAPACITOR
71
PIPING TEMP.SENSOR
REMOTE RECEIVER ROOM TEMP.
SENSOR
SWING MOTOR
CN3
M CN17
CN18
CN12 CN11 CN6
~
1 CN2
CN10
CN16 REMOTE DETECTOR
CN21 T6.3A/250VAC
CN15 CN20 CN19
BL B B FUSE CN9
Y
Y
BL
R W B R
FAN MOTOR
TRANSFORMER
Y/G
M FAN MOTOR M R T3.15A/250VAC
Y/G Y/G W B R Y/G
FAN CAPACITOR FAN CAPACITOR 1 2 3
TO OUTDOOR UNIT
TRANS.
CIRCUIT DETECTOR
R B BL W R
CRANKCASE
HEATER
Y/G
Y/G
R W BL B Y/G W B R Y/G
1 2 3
L1 L2 L3 N
NOTE:
Y/G:YELLOW/GREEN
POWER TO INDOOR Dashed parts 1 2 are not available for only
R:RED W:WHITE cooling type
BL:BLUE B:BLACK
SUPPLY UNIT
72
5
64
6
8 9
7
63
10
11
62
15
61 16
12
60
59
57
56 58 17
19
18 13
23 14
55 20
21 22
54
24
53
48 25
52 49 47 26
50
51
46 27
40
28
45
43
41 42 44
29
65 30
31
39
32
33
34
35
36
37
38
73
2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and
should be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock
in the spare-part warehouse accord with the actual case,should be marked with " ".
4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare
parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part
warehouse,should be marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.
6.The spare parts price on net is FOB Qingdao term.
75
3
4
6
5
9 8 7
10
16 17
22
15
21
14
13
19 20
12
11
18
25
23 55
24
26
54
27
29
33 28 51
31
32 50
41
49
34 40
52
30 53
35
47
46 48
45
39 43
29 27
36 38 44
37 41
42 30
28
76
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
No. in
Spare parts Failure the proportion Remar
exploded Spare parts description in english Model Qty
number rate of the spare part k
view stock
1 0010150286 guard plate 1 AD96NAHAEA 1 0.00% 0.000% ×
2 0010150289 guard plate 2 AD96NAHAEA 1 0.00% 0.000% ×
3 0010250260 drainage pan AD96NAHAEA 1 0.00% 0.000% ×
4 0010150379 supporting plate 2 assembly AD96NAHAEA 1 0.00% 0.000% ×
5 001A0100907 supporting plate 1 assembly AD96NAHAEA 1 0.00% 0.000% ×
6 0010151134 motor fixing bolt AD96NAHAEA 4 0.00% 0.000% ×
7 001A6645001 wires clip AD96NAHAEA 6 0.00% 0.000% ×
8 001A1734260 heat insulation pipe AD96NAHAEA 1 0.00% 0.000% ×
9 001A1734261 heat insulation pipe (liquid pipe) AD96NAHAEA 1 0.00% 0.000% ×
10 001A5313008 copper nut AD96NAHAEA 1 0.00% 0.000% ×
11 001A13011044 sealing ring of scroll case AD96NAHAEA 4 0.00% 0.000% ×
12 001A2301102 fan 1 AD96NAHAEA 2 0.02% 0.024% *
13 001A13011040 scroll case 1 AD96NAHAEA 2 0.00% 0.000% ×
14 001A5401035 spring washer AD96NAHAEA 2 0.00% 0.000% ×
15 001A3000291 indoor motor AD96NAHAEA 2 0.04% 0.048% *
16 001A13011041 scroll case 2 AD96NAHAEA 2 0.00% 0.000% ×
17 001A2301103 fan 2 AD96NAHAEA 2 0.02% 0.024% *
18 0010800290 evaporator fixing plate 3 AD96NAHAEA 1 0.00% 0.000% ×
19 001A3400160 float switch AD96NAHAEA 1 0.01% 0.012%
20 0010151136 float bracket AD96NAHAEA 1 0.00% 0.000% ×
21 0010751619 evaporator assembly AD96NAHAEA 1 0.01% 0.012%
22 0010151133 evaporator fixing plate 2 AD96NAHAEA 1 0.00% 0.000% ×
23 001A3900006 coil temperature sensor AD96NAHAEA 1 0.02% 0.024% *
24 0010150376 left fixing groove AD96NAHAEA 1 0.00% 0.000% ×
25 0010150405 right fixing groove AD96NAHAEA 1 0.00% 0.000% ×
26 0010850513 fixing bracket assembly AD96NAHAEA 1 0.00% 0.000% ×
27 001A13011053 short frame 1 AD96NAHAEA 1 0.00% 0.000% ×
28 001A13011055 short frame 2 AD96NAHAEA 1 0.00% 0.000% ×
29 0010151123 hanging bracket AD96NAHAEA 4 0.00% 0.000% ×
30 0010151135 fixed bracket AD96NAHAEA 4 0.00% 0.000% ×
31 0010151131 fixed reinforced plate 1 AD96NAHAEA 1 0.00% 0.000% ×
32 0010851029 cushion 2 assembly of cover plate AD96NAHAEA 1 0.00% 0.000% ×
33 0010450377 wires assembly AD96NAHAEA 1 0.00% 0.000% ×
34 0010151140 electric box cover AD96NAHAEA 1 0.00% 0.000% ×
35 0010400137 wired controller AD96NAHAEA 1 0.02% 0.024% *
36 0010451346 transformer AD96NAHAEA 1 0.01% 0.012% ×
37 0010400298 relay AD96NAHAEA 3 0.02% 0.024% *
38 001A3600254 capacitor AD96NAHAEA 1 0.02% 0.024% *
39 001A3300352 fan speed control board AD96NAHAEA 1 0.02% 0.024% *
40 001A5745116 wire-pressing clip AD96NAHAEA 1 0.00% 0.000% ×
41 001A1452861 rubber wiring hole AD96NAHAEA 1 0.00% 0.000% ×
42 / ambient temperature sensor AD96NAHAEA / / / /
43 0010400132 indoor PCB AD96NAHAEA 1 0.04% 0.048% *
44 0010451265 terminal block AD96NAHAEA 1 0.00% 0.000% ×
45 0010851015 electric box assembly AD96NAHAEA 1 0.00% 0.000% ×
46 0010851028 cushion 1 assembly of cover plate AD96NAHAEA 1 0.00% 0.000% ×
47 001A1439315 plastic clip AD96NAHAEA 6 0.00% 0.000% ×
48 0010851016 bottom plate AD96NAHAEA 1 0.00% 0.000% ×
49 0010151137 fixed bracket 1 AD96NAHAEA 1 0.00% 0.000% ×
50 0010150378 evaporator fixing plate AD96NAHAEA 1 0.00% 0.000% ×
51 0010151138 fixed bracket 2 AD96NAHAEA 1 0.00% 0.000% ×
52 0010151124 liquid inlet/outlet guard plate AD96NAHAEA 1 0.00% 0.000% ×
53 0010150401 air inlet connection frame AD96NAHAEA 1 0.00% 0.000% ×
54 0010151128 cover plate 3 AD96NAHAEA 1 0.00% 0.000% ×
55 0010151132 fixed reinforced plate 2 AD96NAHAEA 1 0.00% 0.000% ×
77
82
81
86 85
84
83
1
76 2
80 3
79 4
75
74 5
77
67 78
87 6
73
7
8
9
10
11
20
12
14
23 18 13
15
24 16
21 19
17
72 22
25
34
35
43
37
44 38
68 36
39 40
67
66
65
64
45
41
46
70
71 42
69
88
26 47
56 48 49
27
28
50
52
54
51
29 57
32
30 59
31
60 58
33
53
61 62
63
55
78
No. in The
explod Spare parts Failure proportion of Remar
Spare parts description in english Model Qty
ed number rate the spare part k
view stock
1 0010150606 upper air outlet horizontal frame AP96NACAEA 1 0.00% 0.000% ×
2 0010250641 right air outlet frame AP96NACAEA 1 0.00% 0.000% ×
3 0010250379 upper fixing rubber of horizontal louver AP96NACAEA 2 0.00% 0.000% ×
4 0010250473 cushion for clip of air outlet grille AP96NACAEA 2 0.00% 0.000% ×
5 0010150604 lower air outlet horiontal frame AP96NACAEA 1 0.00% 0.000% ×
6 0010150415 right clip of horizontal louver AP96NACAEA 1 0.00% 0.000% ×
7 0010250367 horizontal louver AP96NACAEA 6 0.00% 0.000% ×
8 0010250368 connecting pole 1 AP96NACAEA 4 0.00% 0.000% ×
9 0010250369 connecting pole 2 AP96NACAEA 3 0.00% 0.000% ×
10 0010250481 lower fixing rubber of horizontal louver AP96NACAEA 2 0.00% 0.000% ×
11 0010250639 lower air outlet frame AP96NACAEA 1 0.00% 0.000% ×
12 0010250371 sleeve 1 AP96NACAEA 15 0.00% 0.000% ×
13 0010250372 sleeve 2 AP96NACAEA 13 0.00% 0.000% ×
14 0010250370 vertical louver AP96NACAEA 15 0.00% 0.000% ×
15 0010850634 lower air outlet horizontal frame assembly 2AP96NACAEA 1 0.00% 0.000% ×
16 0010250476 cushion 2 for fixing plate of air outlet grille AP96NACAEA 1 0.00% 0.000% ×
17 0010250373 sleeve 3 AP96NACAEA 13 0.00% 0.000% ×
18 0010250380 swing connecting pole 1 AP96NACAEA 1 0.00% 0.000% ×
19 0010250381 swing connecting pole 2 AP96NACAEA 1 0.00% 0.000% ×
20 0010250375 motor sleeve AP96NACAEA 1 0.00% 0.000% ×
21 0010850634 lower air outlet horizontal frame 2 AP96NACAEA 1 0.00% 0.000% ×
22 0010250477 cushion 3 for fixing plate of air outlet grille AP96NACAEA 1 0.00% 0.000% ×
23 0010150750 sleeve washer AP96NACAEA 13 0.00% 0.000% ×
24 001A3000016Asynchromotor AP96NACAEA 1 0.02% 0.024% *
25 0010200026 air ring AP96NACAEA 2 0.00% 0.000% ×
26 001A1301379 electric control box cover assembly AP96NACAEA 1 0.00% 0.000% ×
27 0010452039 indoor PCB AP96NACAEA 1 0.02% 0.024% *
28 001A1452909 rubber wiring hole AP96NACAEA 1 0.00% 0.000% ×
29 0010451262 transformer AP96NACAEA 1 0.01% 0.012% ×
30 0010451265 terminal block AP96NACAEA 1 0.00% 0.000% ×
31 001A01001024 electric control box assembly AP96NACAEA 1 0.00% 0.000% ×
32 0010451323 ambient temperature sensor AP96NACAEA 1 0.04% 0.048% *
33 0010452015 wires AP96NACAEA 1 0.00% 0.000% ×
34 0010850741 scroll case assembly AP96NACAEA 1 0.00% 0.000% ×
35 0010150924 fan washer AP96NACAEA 4 0.00% 0.000% ×
36 0010250579 fan AP96NACAEA 2 0.04% 0.048% *
37 0010250470 cushion 2 for evaporator fixing plate AP96NACAEA 1 0.00% 0.000% ×
38 0010150529 evaporator fixing plate 1 AP96NACAEA 1 0.00% 0.000% ×
39 0010250469 cushion 1 for evaporator fixing plate AP96NACAEA 1 0.00% 0.000% ×
40 0010250471 cushion 3 for evaporator fixing plate AP96NACAEA 1 0.00% 0.000% ×
41 0010150530 evaporator fixing plate 2 AP96NACAEA 1 0.00% 0.000% ×
42 0010450644 indoor coil temperature sensor AP96NACAEA 1 0.04% 0.048% *
43 0010150531 evaporator fixing plate 3 AP96NACAEA 1 0.00% 0.000% ×
44 0010150523 packaging fixing plate AP96NACAEA 2 0.00% 0.000% ×
45 0010852401 evaporator assembly AP96NACAEA 1 0.00% 0.000% ×
46 0010850740 top plate assembly AP96NACAEA 1 0.00% 0.000% ×
47 0010250442 cushion 1 of bottom plate AP96NACAEA 1 0.00% 0.000% ×
48 0010850629 back plate assembly AP96NACAEA 1 0.00% 0.000% ×
49 0010150417 air flow flap AP96NACAEA 1 0.00% 0.000% ×
50 0010150526 fixing clip of drain pan AP96NACAEA 1 0.00% 0.000% ×
51 0010250769 packaging cushion AP96NACAEA 3 0.00% 0.000% ×
79
80
35
20
cooling capacity(KW)
30 22
25
25
27
20 30
32
15
-7 5 15 25 35 43
outdoor DB(℃)
5
20
4 22
25
EER
3
27
2 30
32
1
-7 5 15 25 35 43
outdoor DB(℃)
b. Heating mode:
Temp. – capacity performance curves
45
16
40 18
capacity(KW)
35 20
22
30 24
25 26
28
20
-7 -5 0 6 10 15
outdoor DB(℃)
81
5
16
4
18
COP
3 20
22
2
24
1 26
-7 -5 0 6 10 15 28
outdoor DB (℃)
H ig h
Low
200
8 7
6 5
4
3
150
3 8
7
100
6
50
0
55 60 65 70 75 80 8586
h igh a ir flo w (m /m in)
3
lo w
lim it lim it
82
cooling
heating
applicable range
temp(℃D.B)
cooling mode
outdoor DB
temp.(℃D.B)
indoor DB
Piping length
5 10 15 20 25 30 35 40 45 50
(m)
heating 1.0 1.0 1.0 1.0 1.0 0.995 0.995 0.99 0.99 0.985
cooling 1.0 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91
If in cooling mode, the outdoor unit is lower, while in heating mode, the outdoor unit is upper, only in
this case, in addition that the above correction factor due to the piping length is taken into
84
85
86
92
88
89
Sincere Forever