Service Manual: Commercial Air Conditioning

Download as pdf or txt
Download as pdf or txt
You are on page 1of 90

Commercial Air Conditioning

SERVICE MANUAL

Models
AD96NAHAEA

AP96NACAEA

AU96NATAEA

Features

The outdoor can match with both of duct and cabinet type indoor unit
The indoor unit is identical for heat pump and cooling only unit
Infra red remote controller or wired controller
Central control and full automation, if connected with a central controller
24-hour timer (standard)
Auto-restart function
Strong energy distribution

Manual code: SYJS-001-05REV.0 Edition: 2005-01-04

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

CONTENTS
Contents………………………………………………………...2
1. Description of products & features………………………..3
2. Specification…………………………………………………5
3. Safety precaution……………………………………………10
4. Net dimension of indoor and outdoor……………………..12
5. Installation instructions………..……………………………15
6. Parts and functions…………………………………………37
7. Remote controller functions……………………………….38
8. Refrigerant diagram…………………………………………58
9. Electrical control functions………………………………….59
10. Diagnostic information (trouble shooting)……………….67
11. Electrical data………………………………………………71
12. Exploded view and parts lists…………………………….73
13. Performance curves……………………………………….81
14. Noise level charts………………………………………….85
15. Air velocity distribution…………………………………….89

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

1.DESCRIPTION OF PRODUCTS & FEATURES


1.1. Products code explanation
A U 96 N A T A E A

Climate type: T1 (see table 1)


Design number (A stands for design sequence, fixed
frequency type)
Product type: A stands for heat pump type, refrigerant is R22
B stands for heat pump type, refrigerant is R407C
M stands for cool only type, refrigerant is R22
N stands for cool only type, refrigerant is R407C
Appearance character
Product series: A stands for 1 to 1
Applicable voltage: 2 stands for 220-230V/50Hz,
4 stands for 220V/60Hz,N stand for 380-400V/50Hz
Cooling / Heating capacity,96=96000BTU/h
Product type : “B” stands for cassette type, “C” stands for
convertible type, ”D” stands for duct, “S” stands for split
type, ”Q” stands for chiller system, "E" stands for ceiling
concealed type, “U” stands for outdoor unit
Air Conditioner

1.2 Brief Introduction for T1、T2、T3 working condition

Climate type
Type of Air
T1 T2 T3
Conditioner
Cooling Only 18 ℃~43℃ 10℃~35℃ 21℃~52℃

Heat pump -7℃~43℃ -7℃~35℃ -7℃~52℃

Electricity Heating ~43℃ ~35℃ ~52℃

1.3 Operating Range of Air Conditioners


Temp. Mode Rated Maximum Minimum
Indoor DB ℃ 27 32 15
Cooling WB ℃ 19 23 14
Outdoor DB ℃ 35 43 -5
WB ℃ 24 26 6
Indoor DB ℃ 20 27 10
Heating WB ℃ 14.5 --- --
Outdoor DB ℃ 7 23 -10
WB ℃ 6 18 ---

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

1.4 Product features


Universal outdoor unit
The outdoor unit can match with duct and cabinet type indoor unit.
High static pressure design for duct unit
The designed exterior static pressure can be adjusted from 0Pa~196Pa. The air outlet duct can be
selected freely, generally, there are two types as follow:

A:Main duct system

B:Branch duct system

Duct unit: super thin unit body, no occupying the indoor space
The whole unit can be concealed in the building, without effect of the indoor décor.
With air inlet filter, enhance the air quality
The high efficiency filter can collect the dirt and remove the bacterium, which can be installed on the
easy-to-unload place, convenient to be cleaned.
Cabinet unit: newly designed luxurious LCD operation panel
On the front panel, you can find there is a luxurious operation panel. Just slightly pressing, the

comfort will come around you. Meanwhile, the unit is equipped with the advanced large angel remote
receiving technology.
Multiple control types

or ( + )

The duct and cabinet unit can be controlled be the wired controller or by the infrared controller. The
cabinet type unit can be controlled with the infrared controller. If the unit is duct type and you want
infrared type, you need to add an infrared controller YR-H71.

And the infrared controller can be equipped with the controller holder, convenient to fix the
remote controller.
4

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
Convenient infrared remote controller
The newly designed infrared remote controller YR-H71 can be used for all indoor units of single type,
multi split type, and H-MRV type except for the cabinet unit. This controller can be compatible with all old
remote controllers except for that of cabinet units.

Auto–restart function (optional)


All indoor units have auto-restart function. When the power supply cut off suddenly, the unit will

automatically recover the previous running mode once the power supply is on.

Self-diagnostic function
In the course of operation, if the failure occurs, the failure code will display on the wired controller or

on the operation panel. Then according to the failure code chart, you can eliminate the failure soon.

Central control function, if connected with a detector and a central


controller
24-hour timer (standard)
Changeover function
The unit can realize changeover function to enhance the reliability and the precision by connecting a

detector.

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

2. SPECIFICATION
item Model AU96NATAEA
Function cooling heating
Capacity BTU/h 92000 96000
Capacity W 27000 28000
Sensible heat ratio 75% /
Total power input W 10000 9000
Max. power input W 13000 13000
EER or COP W/W 2.70 3.11
Dehumidifying capacity 10‐³×m³/h 10
Power cable 5*6.0
Signal cable section 1*1.5
Connecting cable section 3*2.5
Wired control cable for wired control unit section 3*0.5
Power source N, VAC, Hz 3, 380-400, 50
Running /Max.Running A/A cooling 18/22.8 heating16.5/22.8
Start Current A 36
Class of anti electric shock Ⅰ-class
Circuit breaker A 40
Max. operating pressure of heat side Mpa 3.0
Max. operating pressure of cold side Mpa 3.0
Unit model (color) AU96NATAEA(WHITE)
Model / Manufacture JT300D-Y1L / DAIKIN
Oil model /
Oil type MINERAL
Compressor Oil charging cm³ 3000
Type scroll
Protection type inner thermal protection, 3-phase protection, pressure
Starting method direct startup
Type × Number Axial × 1
Speed r/min /
Fan
Fan motor output power W 350
Air-flow(H-M-L) m³/h 10000/-/6000
Outdoor unit

Type / Diameter mm TP2M / 9.52x0.35


Heat exchanger Total area m² about 1.8
Temp. scope ℃ cooling: 43~60 / heating: 6~7
External (L×W×H) mm×mm×mm 990*760*1700
Dimension
Package (L×W×H) mm×mm×mm 1150*925*1870
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm Capillary tube
Defrosting Automatic
Volume of Accumulator L NO
Noise level dB(A) ≤65
Type of Four way valve /
material of reduce noise XPE
crankcase heater power W 34*2
Weight (Net / Shipping) kg / kg 161/185
Type / Charge g R22/8500
Refrigerant
Recharge quantity g/m 115
Liquid mm 12.7
PIPING

Pipe
Gas mm 28.58
Connecting Method flared
MAX.Drop m 15
Between I.D &O.D
MAX.Piping length m 30
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DB
Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a sound
pressure noise level.

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

item Model AD96NAHAEA


Function cooling heating
Capacity BTU/h 92000 96000
Capacity kW 27000 28000
Sensible heat ratio 75% /
Total power input W 10000 9000
Max. power input W 13000 13000
EER or COP W/W 2.70 3.11
Dehumidifying capacity 10‐³×m³/h 10
Signal cable section 1*1.5
Connecting cable section 3*2.5
Power source N, V, Hz 1, 220-230, 50
Unit model (color) AD96NAHAEA/grey
Type × Number Centrifugal×2
Speed(H-M-L) r/min 1070±30/860±40/960±50
Fan
Fan motor output power W 270
Air-flow(H-M-L) m³/h 3600
Type / Diameter mm TP2M/Φ9.52
Heat exchanger Total Area m² 0.41
Indoor unit

Temp. scope ℃ 2-7


External (L×W×H) mm×mm×mm 1570*840*360
Dimension
Package (L×W×H) mm×mm×mm 1800*980*495
Drainage pipe (material , I.D./O.D.) mm PVC 18/20
Control type (Remote /wired) Wired
Fresh air hole dimension mm /
Electricity Heater kW 0
Noise level (H-M-L) dB(A) 58/-/51
Weight (Net / Shipping) kg / kg 92/100
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DB
Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a sound
pressure noise level.

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

item Model AP96NACAEA


Function cooling heating
Capacity BTU/h 92000 96000
Capacity kW 27000 28000
Sensible heat ratio 75% /
Total power input W 10000 9000
Max. power input W 13000 13000
EER or COP W/W 2.70 3.11
Dehumidifying capacity 10‐³×m³/h 10
Signal cable section 1*1.5
Connecting cable section 3*2.5
Power source N, V, Hz 1, 220-230, 50
Unit model (color) AP96NACAEA/ivory white
Type × Number Centrifugal×2
Speed(H-M-L) r/min 630±30/420±40/360±50
Fan
Fan motor output power W 250
Air-flow(H-M-L) m³/h 4800
Type / Diameter mm TP2M/Φ9.52
Heat exchanger Total Area m² 0.41
Indoor unit

Temp. scope ℃ 2-7


External (L×W×H) mm×mm×mm 1200*320*1850
Dimension
Package (L×W×H) mm×mm×mm 1360*510*2030
Drainage pipe (material , I.D./O.D.) mm PVC 18/20
Control type (Remote /wired) Remote
Fresh air hole dimension mm /
Electricity Heater kW 0
Noise level (H-M-L) dB(A) 58/-/51
Weight (Net / Shipping) kg / kg 102/110
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DB
Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a sound
pressure noise level. The detailed method please refer to the following information:

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Installation state: the unit should be placed on the flat floor or be mounted in horizontal direction.
Testing method:

standing-on-floor unit: If the unit cooling


capacity is over 28000W, the noise level should
duct unit without auxiliary duct:
be measured at the front, left, right directions
respectively.

2m

duct

1m

1.4m
1m

outdoor unit:
1.air outlet from side: the noise level is the average sound pressure level measured from front, left, right
directions.
2.air outlet from top: the noise level is the average sound pressure level measured from front, back, left, right
directions.
measured point:
H ( height to the ground) = (h (unit height) + 1m) /2
and, it is 1m to each side.
1m

1m 1m

h
1m

Note: ⊙ is the real time analyser position

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

3. Safety precaution of indoor and outdoor


Carefully read the following information in order to operate the airconditioner correctly.
Below are listed three kinds of Safety Cautions and Suggestions.
WARNING! Incorrect operations may result in severe consequences of death or serious injuries.
CAUTION! Incorrect operations may result in injuries or machine damages; in some cases may
cause serious consequences.
INSTRUCTIONS: These information can ensure the correct operation of the machine.
Be sure to conform with the following important Safety Cautions.
The Safety Cautions should be at hand so that they can be checked at any time when needed.
If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.

WARNING!
If any abnormal phenomena is found Don't dismantle the outlet of the
outdoor unit.
(e. g.smell of firing), please cut off the
power supply immediately, and contact The exposure of fan is very dangerous
the dealer to find out the handling whichmay harm human beings.
method.

In such case, to continue using the


conditioner will damage the conditioner,
and may cause electrical shock or fire
hazard.

switch
off When need maintenance and repairment,
call dealer to handle it.

After a long time use of air-conditioner Incorrect maintenance and repairment


the base should be checked for any may cause water leak, electrical shock
damages. and fire hazard.
If the damaged base is not repaired, the
unit may fall down and cause accidents.

10

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

WARNING!

Installed electrical-leaking circuit No goods or nobody is permitted to


breaker. placed on or stand on outdoor unit.

It easily cause electrical shock without The falling of goods and people may
circuit breaker. cause accidents.

Air-conditioner can't be installed in


the environment with inflammable
gases because the inflammable gases
near to air-conditioner may cause fire
hazard.

Please let the dealer be responsible for Don't operate the air-conditioner with
installing the conditioner. damp hands.
Incorrect installation may cause water Otherwise will be shocked.
leak, electrical shock and fire hazard.

Call the dealer to take measures to


prevent the refrigerant from leaking.

If conditioner is installed in a small


room be sure to take every measure in
order to prevent suffocation accident
even in case of refrigerant leakage. Only use correctly-typed fuse.
May not use wire or any other materials
When conditioner is deinstalled or replacing fuse, other-wise may cause
faults or fire accidents.
reinstalleddealer should be responsible
for them.
Incorrect installation may cause water
leaking, electrical shock and fire hazard.

Connect earthing wire.


Earthing wire should not be con-
nected to the gas pipe, water pipe,
lightning rod or phone line, in-correct Use discharge pipe correctly to ensure
earthing may cause shock. efficient discharge.
Incorrect pipe use may cause water
leaking.

Earthing

11

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

4. Net dimension of indoor and outdoor

Outdoor dimension

9D<=A7 8;63

66- 43-

33- 33-
.1-
.23-

61-
4--

./-
15
/3
./-

..2

160
3/ 52

.2-

12

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Model: AD96

830
18 794 18
25

60
M5x20pcs Air inlet

138
13
250
1570
1690

1640

13 200 13

138
13
65
163 6x200=1200 163
35 1500 35
100
80
25

95
60

Control Box

Liquid pipe Gas pipe


12.7(1/2") 28.58(1-1/8")

M10x4pcs

80 510 25 M5x20pcs Air outlet

138

250
25

13
25
310
360

49

A
30
106

138

77
13
185 170 45 200

530 13 13

DRAIN PIPE VP25 138 6X200=1200 138

60 1450 60

Installation dimension
Over 900 Over 900 (900x1730) Over 100 Over 300
35

Check Hole
(600x600)
900

Ceiling
35

100 60
Over 200
over 400

(mm)

13

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Model: AP96

A
1200
1148

105

270
200
air outlet installation space

650

50
1000

100
power terminal block 179 terminal block center

1850
50 air outlet
787.5 terminal block center 600

air inlet

50
813

880
40

air inlet
1192.5

adjustment range
1222.5 15 320 20-50 20-50
15
315 442 425 50 50 50 425
8 300 8 82
200 50
80
72

100
19
36

150
83 83

142

8- 4manual tap view A


1828

277 liquid side


272 gas side

218 drain water


98

95

142 78

310

(mm)

14

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

5. Installation Instructions
5.1 Outdoor installation procedure
Selection of installation site

Warning
It should be installed at places where it is firm enough to withstand the weight of the air
conditioner to prevent falling.
Typhoon and earthquake prevention. It should be installed according to specific
requirements.
Inasppropriate installation may lead to accidents. Blow out
Installtion space
(1)During installation, connect the outdoor unit and align Air inlet
Air inlet
the mounting surface(See the figure on the right).Mount
the electric distribution device on the external side of Air inlet

the unit in accordance to the installation instructions for


electric distribution device. maintenance plate

(2)To ensure good performance of the machine and facili-


Over 300mm
tate installation and maintenance, adequate space must
be reserved (See figure on the right). Over Over 20mm
Over Over 1000mm Over
20mm 20mm (front side) 20mm

Note: Obstacles should be 2000mm off the top of the out-


door unit. Obstacles nearby should be 400mm lower
than the top of the unit. Rope
Protection cushion

Base panel
1. Handing
Rope
As there is no protective package for the outdoor unit,so
the following points merit attention:
(1) When forklift is used, insert the fork into the holes in
the base plate.
(2) When crane is used, lift the unit with 4 pieces of steel
rope with diameter above 6 mm.
(3) Put protective materials between the cable and the
unit to prevent deformation and damage of the surface.

2.Mounting
(1) The distance between two connections must not be
less than 20mm.

M12 foot screw bolt


4 screws each unit
15

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Refer to the following figure for the distance between the 1100

foundation bolts.

(2)When the refrigerant pipe is connected from the bottom of


Through hole*15x20*
the unit,the unit should be raised at least 500mm(see the
figure below)

Above 500mm
(3)In snowy regions,snow-proof facilities should be used(see
the figure below). Refrigerant tube

(Poor snow-proof facilities may lead to damge.To avoid


inconveniences,the unit should be raised and snow-proof Air outlet snow-
Air inlet snow-proof cover proof cover
covers should be installed at the air inlet and outlet.)

(4)During installation,anti-vibration rubber pads should be used


between the machine and the bracket.
Air inlet snow-
proof cover

3.Connection of refrigerant pipe

Warning

During installation,if refrigerant leakage occurs,ventilation measures must be taken.When


refrigerant meets with fire,hazadous gas will be produced.
After installation,make sure that there is no refrigerant leakage.
Refrigerant,if meeting with heaters and stoves,ect in the room,may produce hazardous gas.
Connection of refrigerant pipe
(1) The joints of the refrigerant pipe are inside the unit.Take off the access hole cover in front of
the unit.
(2) The pipe can be connected from the front or bottom of the outdoor unit.
(3) Remove the L-shaped pipe from the valve by welding and connect the accessory pipe to the
valve.
(4) In the case of front connection,cut the accessory pipe at the height of the fixing panel.Then
join the pipe with an elbow and let it go through the fixing panel.For the convenience of maintenance,
bend the pipe down (once) and then connect pipe to the right or left.
(5) In the case of bottom connection,join the pipe with accessory pipe through the holes in the
base plate of the outdoor unit,and connect pipe the left or right or the back.

Tube fixing
panel
M6
M4
Bottom plate
Access hole cover
Tub
e to th
e ba ht
ck
to the tig
Tube
ht
to the tig
Tube
ft
to the le
the le
ft Tube
to
16 Tube

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

(6) During welding,the gas pipe valve must be cooled down with a wet cotton cloth.

During welding of the distribution pipe


1.In case of brazing weld of joint,nitrogen must be filled in the pipe to prevent oxidization.
2.The refrigerant pipe should be newly-made and clean.During installation,do not let water and other
substance into the pipe.
3.Use two spanners to tighten the connecting nut.One spanner will make loose connection.
The torque moment should conform to the specified value.(Refer to the below)

Tube diameter Torque moment for Torque moment for


(mm) pre-installation (N.m) tightening up (N.m)
12.70 49.0(5.0kgf m) 53.9(5.5kgf m)

Selection of tube material and size


Determinaltion of tube diameter (Refer to the diagram on next page for steps 1,2,3,4 and 5 below)
1.Tube between the outdoor unit and the first bypass(main tube):
The diameter of the main tube and the outdoor tube should be the same.
2. Tube between bypasses(sub-tube):
The diameter of the sub-pipe is determined according to the total capacity of all the connected
indoor units.But if it is larger than the capacity of the outdoor unit,the diameter should be determined
according the capacity of the outdoor unit.
Install the nonreturn loop and oil trap

2.Outdoor is higher
1.Outdoor is lower

liquid nonreturn loop


Outdoor

Indoor

Oil trap (one per


6m)

Outdoor Indoor

17

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Crucial points:
When testing, never use oxygen,flamable and poisonous gases.
Step 1:Charge for more than 3 minutes under 0.3MPa(3.0kg/cm2g)
Step 2:Charge for more than 3 minutes under 1.5MPa(15kg/cm2g)
--Serious leakage may be found.
Step 3:Charge for more than 24 hours under 3.0MPa(3.0kg/cm2g)
--Small leakage may be found.
Check for pressure decrease
Without pressure decrease-Pass
With pressure decrease-Check for leaage.There will be a 0.01MPa(0.1kg/cm2g) pressure change
for every 1 C ambient temperature change during the 24-hour pressure charge.It should be
corrected during the test.

Low-pressure High-pressure
gauge gauge

Three-way valve fully


closed(gas side) Gauge distributor
Indoor Outdoor
VL VH

Tightly
closed Solder joint Solder joint
Access hole
6.4
Copper
pipe
Tightly Tightly
closed Solder joint closed Relief valve
Nitrogen bottle

Access hole 6.4


Copper pipe

Indoor unit
Outdoor unit
Three-way valve fully closed liquid side

Detailed diagram of the


three-way valve
(Gas side )access hole
To the gauge
distributor (Gas side)three-way valve

(Liquid side)access hole


To the unit
(Liquid side)three-way valve
To the unit

Field tube Field tube


installation installation

18

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Check for leakage


In the case of pressure decrease during steps 1 to 3 ,check the joints with the ear,hand or soapsuds for
leakage.Repair it by welding or tighten the connecting nut up.

Vacuum Pumping
Use vacuum pump to evacuate the air.Never use the refrigerant for the evacuation.
Drain off the nitrogen gas after the leak test and then connect the vacuum pump as shown in the figure
below.
The vacuum pumping must be done from both the liquid and gas inlets.
Low-pressure High-pressure
gauge gauge
Three-way valve fully
Indoor Outdoor closed(gas side)
Gauge distributor
Tightly 6.4Copper pipe
closed Solder jointSolder joint
Access hole
P
Tightly Tightly
closed Solder joint closed Vacuum pump
Access hole

Indoor unit
Outdoor unit
Three-way valve fully closed
liquid side
Detailed diagram of the
three-way valve
To the gauge (Gas side )access hole
distributor (Gas side)three-way valve
(Liquid side)access hole
To the unit
(Liquid side)three-way valve
To the unit

Field tube Field tube


installation installation

Use a vacuum pump with high degree of vacuum(below-755mmHg) and large volume displacement
(above 40L/min)
The pumping time depends on the length of the connecting pipe.Generally,it takes about 2-3 hours.
Make sure that the Y-shaped valves on both the gas and liquid sides are closed before pumping.
If the vacuum can no reach-755mmHg within 2 hours,continue pumping for another 1 hour.
If the vacuum can no reach-755mmHg after more than 2 hour's pumping,close the valves VL and
VH on the gauge distributor and stop pumping.One hour later,check the vacuum again.If the
vacuum has changed,it means there is a leakage.Repair it.
After the above steps,replace the vacuum pump with the refrigerant pump and refill refrigerant.
Charging refrigerant
Refrigrant must be charged in liquid state. Containers for R22 refrigerant must be
Refrigerant bottle with or without a siphon marked with R22 and a brown Stripe.
tube can be refilled with refrigerant upright R407C refrigerant cannot share the same
or upside down,Respectively. instrument distributor and filling pipes.

19

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Refilling of refrigerant
After the vacuum pumping,replace the vacuum pump with the refrigerant pump and refill refrigerant.
Calculation of refrigerant quantity
The factory filled refrigerant into the piping excludes the part of pipes according to be refilled on the site.
Refill the amount of refrigerant into the piping according to the following formula.
The factory filled refrigerant is listed in the table below:
The quantity of the refrigerant to be refilled during installation depends on the diameter and length
of the liquid piping.

The quantity of the refrigerant t be refilled on the site=Actual length of liquid tube x quantity of
refrigerant to be refilled for per meter of liquid pipe.

Recharge refrigerant
When the outdoor valve is shut,fill the refrigerant from the access hole at the gas and liquid sides.
If the required filling is impossible,open all the gas and liquid valves,then slightly shut the gas
valve, run the compressor and fill the refrigerant from the access hole at the gas side.Now adjust
the gas valve to control the refrigerant flow,which will be gasified during absorption by the system.
If there is insufficient refrigerant in the system caused by leaks,refill it after the remaining refrigerant
is recollected.
Open all valves
Open all the valves of the outdoor unit.
Heat isolation of the pipes
Separate isolation should be made for the liquid and gas pipes.
Materials used for the pipe isolation at the gas side must withstand above 120 C temperature.

For AU96NATAEA:
Charging refrigerant (R22): Before charging refrigerant, the pressure in the system
must be kept at least for 15 minutes under 130Pa, and the pressure will not go up
within 30 minutes, only in this case, the refrigerant can be filled.
When the connection pipe is less than 5 meters, additional refrigerant needs not be
charged. Once the connection jpipe is more than 5 meters, please recharge the
refrigerant as the following formula:
Refrigerant quantity=(lenth of connection pipe-5m)*115g
Detailed procedures:
a.Cut off the vacuum pump pipe to prepare charging refrigerant
b.Place the R22 container on the scales, switch off the low pressre valve of the
pressure pipe to make the liquid type refrigerant enter the system from the high
pressure side.
c.If the system pressure goes up, stop charging refrigerant and when the
refrigerant quantity arrives the rated value, switch off the high pressure valve,
then place the R22 container on the scales with the jaw to up. Open the low pressure
valve to start up the unit, at this time, the refrigerant is gas state.
When the charged refrigerant arrives the rated value, after confirming the refrigerant
quantity is proper, unload the flexible joint and install the copper nut of the connector.

20

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Electric wiring
Note:
All the wires should be copper core wires.
The power cable of indoor unit should be equipped according to the operation manual indoor unit.
When connecting the indoor & outdoor wire, check the number of the indoor & outdoor terminals,
the terminals with the same number connected together with one wire.
Incorrect wiring will damage the controller of the air conditioner or make the unit work abnormally.
The air conditioner must use special power circuit and special air switch (40A), groundign wire.
The wiring work should be done by a qualified electrician according to the national wiring rule.
The creepage breaker must be installed. The grounding line and the neutral line of the receptacle
must be strictly separated. It is incorrect to connect the neutral line with the grounding line.
The connection type of power cord is Y connection. If the soft power cord is damaged, to avoid
risk, it must be replaced by the manufacturer or their specific repair department or similar professional
worker.

Wiring method
1.The wiring method of orbicular terminal
For the connection wire which end is orbicularterminal,
its wiring method is as the right figure shown.
Dismantle the screw and put it through the ring at
the end of the connection wire, then connect it to
the terminal block and tighten the screw.
The wiring method of orbicular terminal
2.The wiring method of straight terminal For those Wrong pressing
connection wires whose end are not orbicular terminals, Correct pressing
their wiring method is: Loosen the connecting screw, Terminal block
insert the end of the wire directly into the terminal block,
and then tighten screw. Pull the wire outwards slightly to Wire holding clamp
confirm it is held tightly.
(Sketch map)
3.Pressing method of connection wire:
After wiring, the connection wire must be pressed with wire
holding clamp. The wire holding clamp should press on the Terminal block of Y/G
out cover of the connection wire. As the right figure shown: indoor unit
1 2 3
Connect wire between indoor & outdoor unit
As the wiring diagram show to arrange the connection
wire. 1 2 3 L1 L2 L3 N
Terminal block of
outdoor unit Power supply:
Note: The terminal block’s mark at the two ends of the 3N,380-400V,50Hz
connection wire should be corresponding one by one, Power terminal
otherwise the air conditioner cannot work normally. block of outdoor
unit

Others
1. Power supply
The parameter of power cord is over 2.5mm .
Air conditioner must use an exclusive line (over 30A)
When installation air conditioner in a wet place, try to use a circuit breaker against
Current leakage.
For installation in other places, use circuit breaker as far as possible.
21

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

The breaker of the air conditioner should be all-pole switch ; and the distance between
its two contacts should be no less 3 mm.
Such means for disconnection must be incorporation in the fixed wiring
2. Pipe cutting and flaring
Be sure to carry out deburring after pipe cutting with a pipe cutter.
Insert flaring tool to make a flare.

A Flaring tool Pipe dia. Dimension A(mm)

Liquid pipe 12.7mm (1/2") 1.2 ~ 2.0

Correct Incorrect

Lean Damaged flare Crack Partial Too outside

Installation inspection and test run:


Please operate unit according to this Manual.
Items to be checked during test run. Please made a " "in " "
Are there any gas leakage?
How is insulation at piping connection carried out?
Are electric wires of indoor and outdoor unit firmly inserted into terminal block?
Is electric wiring of indoor and outdoor securely fixed?
Is draminage securely carried out?
Is earth line ( grounding ) securely connected?
Is power supply voltage abided by the code?
Is there any noise?
Is control display normal?
Is cooling operation normal?
Is room temp. regulator normal?
3.Calculation of refrigerant density
Calculation will be made according to the following methods:
1) Total refrigerant content of each system (kg) =content of 1 outdoor system + refilled refrigerant
Content of 1 outdoor system:Factory filled refrigerant
Refilled refrigerant:Filled content during installation according to the diameter and length of the
liquid piping.
2) Calculation of the minimum room sapce (m3).
3) Calculation of refrigerant density
Total refrigerant content Refrigerant density:0.3(kg/m3)
Minimum room space
22

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

2.Preventive measures against excess of critical value


1) Make ventilation holes
Ventilation holes should be built above and under the door.The area of each hole should not be
smaller than 0.15% of the room space.Holes can be made directly in the wall.
2) Reduce the filling content of refrigerant
Filling content of refrigerant can be reduced by shortening the distance between the indoor and
outdoor units.
By reducing the capacity of the outdoor unit.
When outdoor unit be made up of several units.the outdoor capacity of each system should
reduce.Sothe refrigerant content of system reduce.
3) Install ventilation fans.
Users can install uninterrupted ventilation fans to keep the refrigerant density under the critical
value.
If uninterrupted ventilation is impossible,a combined fanning and alarming device should be
installed in its stead (through which immediate ventilation is possible when leak occurs).
(See the figure below)

An example
Ventilation fan and gas leak alariming device

The gas leak alarming Vertilation opening


device should be installed
at refrigerant gas
stagnation areas

23

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Installation instruction

Notice

This manual can not include all kinds of conditions, if you have new
requirements and questions, please contact with local Haier Sales Center.
Warning

Before installing the unit, please read this manual carefully. Improper
installation may cause accidents and make unit damage or death.

Installation tools
1. Screw driver 2. Hacksaw
3. 70mm dia. hole core drill 4. Spanner (dia. 17, 27mm)
5. Spanner (14, 17, 27mm) 6. Pipe cutter
7. Flaring tool 8. Knife
9. Nipper 10. Gas leakage detector or soap water
11. Measuring tape 12. Reamer
13. Refrigerant oil 14. Lead-solder tool

Parts in the following list are


Standard accessories accessories for the unit installation
Following parts shall be field supplied which can be used if necessary.

No. Shape and description QTY


Mark Parts name
1
A Adhesive tape Fall-prevention fitting metal
1

B Pipe clip
2
5
Self-tapping scerw
C Connecting hose
3 2
D Drain hose Wooden bolt

E Insulation material 4
Wall hole cover
2

F Putty 5 1
Piping hole cover

6 2
L-shaped metal

24

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Installation procedure

1. Before installation
[Before finishing installation, do not throw the attached installation parts away.]
Confirm the route to carry the units to the installation place.
Do not remove the package of the unit, before carrying it to the installation place.
When have to remove the package, use a soft material or protection board with rope to lift
the unit to prevent the unit from damage or bumping scrape.
2. Selection of installation place
Select the firm place that will not influenced by vibration and can bear the weight of the
unit
Select the place with easy drainage and place can perform outdoor unit pipe connecting.
Select the place far away from heat source, vapor source and direct sunshine to avoid
the causing of the trouble in operation parts and the deformation of the casing.
Select the place where the cool air or warm air can evenly spread to every corner of the
room.
Select the place near power receptacle leaving sufficient space around the unit. (Referring
to installation diagram)

Avoid the following installation places


Place with oil fog splash and much vapor (e.g. mechanical plant and kitchen, etc.) to prevent
heat exchanger from performance lowering and plastic parts from corroding to damage.
Place may generate or keep corrosive gas (sulfur dioxide, etc.), flammable gas (diluent,
gasoline, etc.) to prevent heat exchanger from corroding, plastic parts from damage and
flammable gas from causing fire accident.
Hospital, etc. places near the machine generates electromagnetic wave or high frequency
signal to prevent the mixed wave from causing wrong action of the control parts.
Place can be blown by the sea wind (coastal area) to prevent the casing and heat exchanger
from corroding.
(Indoor unit) please keep the spaces larger than the following dimension.

3. Installation space
Unit (mm)
50

600

1000

50
600

600
50

25

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Installation of indoor unit

Selection of installation place


Place where it is easy to route drainage pipe and outdoor piping.
Place away from heat source and with less direct sunlight.
Place where cool and warm air could be delivered evenly to every corner of the room.
Place near power supply socket. Leave enough space around the unit (refer to installation
drawings).

Fixing of the unit


1. Position of the wall hole
Wall hole should be decided according to installtion place and piping direction. (refer
to installation drawings)
2. Making a wall hole
Drill a hole of 70mm dia. with a little slope towards outside.
Install piping hole cover and seal it with putty after installation.

INDOOR OUTDOOR UNIT

wall hole
wall thinkness
70mm

( Cross section of wall hole )

Fixing of indoor unit

To prevent it from fall off, please fix the unit with fall-prevention fitting at wall and L-
shaped metal at floor.

Self-tapping
all-prevention fitting metal (accessory)
screw
Wood screw
Please install the whole unit
horizontally,with a slop of 1
degree at front and rear,left
L-shaped metal and right.
(accessory)

Installation of fall-prevention fitting metal:


Fix the fitting metal to the wall by screws so that there is no clearance between them.
With the unit set up vertically, fix the fitting metal to the unit with screws while making an adjustment
at the long portion of the hole so that there is no clearance between the upper surface and the
fitting metal.

26

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Installation of L-shaped metal


Fix to the unit by screws so that there is no clearance between the fitting metal and the unit.
After confirming that the unit has been set up vertically to the floor, fix it to the floor by bolt.

Piping connection
1. Connecting method
Apply refrigerant oil at half union and flare nut.
To bend a pipe, give the roundness as large as possible not to crash the pipe.
When connecting pipe, hold the pipe centre to centre then screw nut on by hand,refer to Fig.
Be careful not to let sundries, such as sands enter the pipe.

Forced fastening without centering may


damage the threads and cause a gas leakage.

Pipe diameter Fastening torque


Liquid pipe 12.7mm(3/8") 42N.m

2. Piping connection of indoor unit


Arrangement of piping and drainage pipe

After opening inlet grill, you will see a control box as shown in the Fig.
Remove the cover before working.

Cut away, with a hammer or a saw, the lid for piping according to piping direction.

27

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Insulation material
Drain hose
Copper tube Connecting electric cable
for indoor and outdoor unit

According to the piping method, connect the piping on indoor unit with union of connecting pipe.
Arrange the piping as per the wall hole and bind drain hose connecting electric cable and piping
together with polyethylene tape.
Insert the bound piping connecting electric cable and drain hose through wall hole to connect
with outdoor unit.
Arrangement of drain hose
Drain hose shall be placed in under place.
There should be a slope when arrange drain hose. Avoid up and down waves in drain hose.
Indoor unit
Up

Down Bad
Slope Good
If humidity is high, drain pipe( especially in room and indoor unit ) must be covered with insulation
material.
Main points of installation refrigerant pipe
Please install the gas pipe and liquid pipe according to the following shown method.
Please remove the cover piece on the gas pipe and the screw cap on the liquid pipe.

A
B

2 Please connect the connecting pipes between indoor and outdoor unit according to the
following method.
a) When introducing the pipe from right side
Use attached accessory <A> to connect the on-the-spot connecting pipe and gas
pipe.

A B

28

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

b) When introducing pipe from rear side or left side


Use attached accessory <A> to connect the on-the-spot connecting pipe
and gas pipe.
3 After finishing connection of connecting pipe, please do thermal insulation treatment
by using the attached thermal insulation material. Otherwise, it may cause water
leakage.
Setting of wire controller dial switch
Setting of this series of air conditioner dial switch: 1, ON; 2, ON.

29

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
Indoor installation instruction
NOTICE
All Wiring of this installation must comply with NATIONAL, STATE AND LOCAL
REGULATIONS. These instructions do not cover all variations for every kind of
installation circumstance. Should further information be desired or should particular

WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING
INSTALLATION. FAI-LURE TO FOLLOW THESE INSTRUCTIONS COULD

1. Before installation [Before finishing installation, do not throw the attached parts installation needs]
Confirm the way to move the unit to the installation place.
Before moving the unit to the installation place, do not remove their packages.
When have to remove the package, use a soft material or protection board with rope to lift the unit assembly to avoid
unit damage or bumping a scrape.
2. Select installation place
(1) The chosen installation place should meet the following requirements and get the user’s consent.
Place ensures ideal airflow distribution.
The passage of airflow has no obstacles.
When importing outside air, it should be imported directly from outdoors. (if the pipe can not be extended, it also can
not be imported from top)
Place ensures enough space for maintenance.
The pipe length between indoor and outdoor unit is in the permitted limit (referring to outdoor unit installation part).
The indoor unit, outdoor unit, electric wire and connection wire is at least 1m away from television
and radio. This is to avoid the image disturbance and noise caused by the above-mentioned home appliance. (Even
if 1m away, if the electromagnetic wave is too strong, it can also cause noise.)
(2) The height of ceiling
The indoor unit can install on the ceiling, which height is no more than 3m.
(3) Install and use the hoisting screw. Check if the installation place can bear the weight of unit assembly.
If not certain, strengthen it before install the unit.

Over 100 Over 900


Over 300

Checking meatus
Air out (600x600)
Over 200

Air in
Ceiling

3. Preparation before installation


(1) The position relation among hoisting screw (unit: mm)

360 890
250 600
794

Down side

Up side 750
30

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
(2) If necessary, cut the opening installation and checking needed on the ceiling. (If has ceiling)
Before installation, finish the preparation work of all the pipes (refrigerant, drainage) and wire
(wire controller connection wire, indoor and outdoor unit connection wire) of indoor unit, so that
after installation, they can be immediately connected with outdoor unit.
Cut the opening on the ceiling. Maybe it needs to strengthen the ceiling to keep the ceiling even
and flat and prevent the ceiling from vibration. For details, please consult to the builder.
(3) Suspending bolts installation
Use care of the piping direction when the unit is
(Use M10 screw bolt)
In order to bear the weight of the unit, for Built-in anchor Insert
Built-in plug
existed ceiling, using foundation screw bolt,
for new ceiling,using burying embedded
screw bolt, burying screw bolt or spot
supplied other parts.
Before going on installation, adjust the gaps Concrete
with ceiling.
4. Installation of indoor unit suspending bolt M10
Fix the indoor unit to the hanger bolts. Hanging bolt
If required, it is possible to suspend the unit to M10 nut M10 washer
the beam, etc.

Main unit M10 spring washer


Note
When the dimensions of main unit and ceiling holes does not match, it can be
adjusted with the slot holes of hanging bracket.
Adjusting to the levelness
(a) Adjust the out-of levelness using a level or by the following method.
Make adjustment so that the relation between the lower surface of the unit proper and water level in the
hose becomes as given below.

Piping side
Supply water

Water level
0~5 mm PVC hose
(0~0.2") Piping side
Supply water

Water level
0~5 mm PVC hose
(0~0.2")
Bring the piping side slightly lower.
(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur.
5. Drain Piping
(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps.

Good piping Improper piping


Suspension Avoid riding across an elevation
bolts 1.5m ~ 2m
Air vent Keep free from traps

Do not pipe under water

Heat A downhill grade


insulation of 1/100 or more

31

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
(b) When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the piping on the unit side.
Also, fix the piping at a point as close as possible to the unit.
(c) For drain pipe, use hard PVC general purpose pipe VP-25(I.D.1") which can be purchased locally. When connecting,
insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp.
Adhesive must not be used connection of the drain socket and drain hose (accessory).
Stage
difference Drain hose
Drain socket part

Drain socket
VP 25 joint
Pipe cover(large) (field purchased)
[for insulation]
Main unit (accessory)

Drain hose VP 25
(field purchased)
Clamp (accessory)
(accessory) Adhesion Pipe cover
[for insulation]
Pipe cover(small) (field purchased)
[for insulation]
(accessory)

Secure the elevation as high as possible


(d) When constructing drain piping for several units, (approx. 100 mm)
position the common pipe about 100 mm below
the drain outlet of each unit as shown in the sketch.
Use VP-30(11/4") or thicker pipe for this purpose.

(e) The stiff PVC pipe put indoor side should be A downhill grade of VP 30
heat insulated. 1/100 or more

(f) Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain hose directly into
drainage,where the gas with sulfur may be generated.
(g) Backwater bend
Because the drain spout is at the position, which negative pressure may occur. So with the rise of water level in the
drain pan, water leakage may occur. In order to prevent water leakage, we designed a backwater bend.
The structure of backwater bend should be able to be cleaned. As the below figure shown, use T type joint.The backwater
bend is set near the air conditioner.
As figure shown, set a backwater bend in the middle of drain hose.
H2 H1

H1=100mm or the static pressure of air sending motor


H2=1/2H1 (or between 50~100mm)
Drainage Test

1 Conduct a drainage test after completion of the electrical work.


2 During the trial, make sure that drain flows properly through the piping and that no water leaks from connections.
3 In case of a new building, conduct the test before it is furnished with the ceiling.
4 Be sure to conduct this test even when the unit is installed in the heating season.

Procedures
1 Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.
2 Check the drain while cooling operation.
6. Installation of air suction and discharging duct
Please consult the after-sales service worker of Haier Air Conditioner for the choosing and installation
of suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawing
and outer static pressure, and choose the discharging duct with proper length and shape.

32

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

muffler cavity (air sending)


Enlarging chart of
Sacking joint profile chart A
Vibration resistance hook
Insulation A Air volume adjuster

Air conditioner Ceiling


Air outlet main unit
Air suction grille with air filter
Checking meatus

The length difference among every duct is limited below 2:1.


Reduce the length of duct as possible as can.
Reduce the amount of bend as possible as can.
Use heat insulation material to bind and seal the part connecting main unit and the flare part of air
discharging duct. Perform duct installation work, before the fitment of ceiling.

Bad example Bad example Good example

7. Calculation method of the dimension of the simple quadrate air duct


Presuming the unit length friction impedance of the duct is 1Pa/m, when the dimension of one side of
the air duct is fixed as 250mm, as shown below:
Air volume Duct(mmxmm) Air volume Duct(mmxmm)
A Air conditioner 2400m3/h 250x560 1200m3/h 250x310
A (40m3/min) (20m3/min)
3
600m /h 300m3/h
B (10m3/min)
250x190 (5m3/min) 250x120
AD42NAHAAA AD242AHAAA
B A AU42NAQAAA AU242AOAAA
A Static pressure box Equipped with (HDU-42H03/H) (HDU-24H03/H)
air filter (bought)

The calculation of duct resistance (the simple calculation is as follow table)

Straight part Calculate as per 1m length 1Pa, 1Pa/m


Bend part Each bend takes as a3~4m long straight duct
Air out part Calculate as 25Pa
Static pressure box Calculate as 50Pa/each
Air inlet grille (with air filter) Calculate as 40Pa/each

33

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

The chosen chart of simple duct

Shape Square duct Shape Square duct


Item Item Dimension
Air volume Dimension Air volume
3 3 3 3
m /h(m /n) (mmxmm) m /h(m /n) (mmxmm)
100 250 x 60 1,800(30) 250 x 430
200 250 x 90 2000 250 x 470
300 250 x 120 2400 250 x 560
400 250 x 140 250 x 650
3,000(50)
500 250 x 170 3,500 250 x 740
600(10) 250 x 190 4,000 250 x 830
800 250 x 230 4,500 250 x 920
1,000 250 x 270 5,000 250 x 1000
1,200(20) 250 x 310 5,500 250 x 1090
1,400 250 x 350 6,000(100) 250 x 1180
1,600 250 x 390

8. The attentive matters in installation of air suction and discharging duct


Recommend to use anti-frost and sound-absorbing duct. (locally bought)
The duct installation work should be finished before the fitment of ceiling.
The duct must be heat insulated.
The specific air-discharging outlet should be installed at the place where the airflow can be reasonably distributed.
The surface should leave a checking meatus for checking and maintenance.

Special air discharging outlet


Use screw bolt to fix

Duct

Air
Air

9. The examples of improper installation


Do not use air in duct and take the ceiling inner side instead. The result is because of the irregular outer air mass,
strong wind and sunshine, the humidity is increased.
There may be water drop on the outside of duct. For cement and other new constructions, even if not taking ceiling
inner side as duct, the humidity will also be so high. At this time, use glass fiber to perform heat preservation to the
whole. (use iron net to bind the glass fiber)
Maybe exceeding the unit operation limit (for example: when indoor dry bulb temperature is 35 C, wet bulb temperature
24 C), it may lead to overload of compressor.
Affected by the capacity of air discharging fan, the strong wind in the outer duct and wind direction,when unit air sending
volume exceeds the limit, the discharged water of heat exchanger will overflow, leading to water leakage.

Air discharging fan


34 Improper example

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
10. The operation method of fan controller
Through the fan controller switch in the electric box, the air volume of this unit can be continuously adjusted.
It is unnecessary to adjust air volume through the duct side wind level (unit outside static adjustment).
The air volume set should be in the operation air volume range.
Figure I shows the position of fan controller in the electric box and operation method.
After finishing the electric work, perform test run. According to the main points in Figure II making the chosen switch No.
accordant. And confirm if it reaches the needed air volume.
Note:
1) When operating the fan controller, it is possible to touch the electric charging part, so do cut off the power supply.
2) Do not set the dial at the position less than 1.
3) The figure circled in Figure II indicate the capacity number of fan controller. The non-listed capacity number may exceed
the permitted operation capacity range, so it is impossible to operate.
4) When delivering from factory, the capacity number of fan controller is set at “No.5”.

Rotate this switch


(capacity number High Condition of standard air volume
setting: Low (air volume 100Pa)
No. 1 ~ No. 8)
200 ¢ ¢
¢
¢ ¢
¢
¢ ¢ Example of
Outer static pressure Pa

¢ duct
150 ¢

¢
¢

Once the fan controller 100


has trouble, this linker
can perform emergency ¢
assistant control. When
this linker is connected
to the linker from the 50
PCB, it can operate with
total load.

When this linker is 0


26 30 3435 40 43
connected to the linker
from the PCB, through Lower limit Upper limit
the fan speed adjustment
panel to adjust speed.
Figure 1 Standard air volume(m3/min) Figure 2

The example of the method of choosing capacity number:


3
1) If the unit is in high-speed operation, needing take outer static pressure is 180Pa in capacity air volume 34m /min as working condition
point, according to Figure II “The characteristic chart of air volume”, the capacity numberof fan controller is No. 2.
3
2) If the unit is in low speed operation, needing take outer static pressure is 60Pa in capacity air volume 32m /min as working condition
point, according to Figure II “The characteristic chart of air volume”, the capacity number of fan controller is No. 4.
11. Refrigerant pipe
[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause water leakage.]
The outdoor unit has been charged with refrigerant.
When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown,use spanner
and torque spanner together.
When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use hand to twist 3-4
rings, then fasten with spanner.
Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage)
Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown.
Only use seal cushion to bind the joint part of air pipe and heat insulation parts.
Paste the refrigerant oil here Middle size seal cushion (accessory)
(Use seal cushion to
bind the pipe joint)

Torque spanner
Clamp

Heat insulation (accessory)


Spanner
(for liquid pipe)
Heat insulation (accessory)
Pipe joint (for gas pipe)
Cone nut Gas pipe
35
Liquid pipe

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
80 510
Liquid pipe
Gas pipe Electric box
Upper

Air inlet Air outlet

310
Down side

30
Drain hose connection mouth 530

VP25 PVC pipe

Specification of pipe Tighten torque Cone dimension Cone


(mm) A (mm)

45 2
R0.4~0.8
12.70 50N.m 1.2~2.0 90 0.5
A

Electric wiring
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE
COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.

(1) Selection of size of power supply and interconnecting wires.

Precautions for Electric wiring

Electric wiring work should be conducted only by authorized personnel.


Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with
insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2%
voltage drop.)

Item Circuit breaker Earth leakage breaker


Power
Phase Switch breaker Overcurrent source wire Switch Leak
Model (A) protector size break curren

3 30 40 6.0 mm2 30 30mA

(2) Wiring connection


Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals.

INDOOR UNIT Y/G


TERMINIAL BLOCK Power cable
is self-provided.
1 2 3
Power
Connecting cable 380-400V~,50Hz
is self-provided.

1 2 3 L1 L2 L3 N
OUTDOOR UNIT TERMINIAL BLOCK

36

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

6. Parts and Functions

Indoor unit:
top cover
suspending pole
outlet grill
evaporator(inside)
MODE TEMP + TEMP - FAN ON/OFF
LOCK

operation panel guarding plate

front panel

stop valve

side plate

inlet grill

duct
electric box
suspending bolt
bottom plate
drain pipe

Outdoor unit:

air outlet grill

side plate

condenser (inside)

electric control assembly (inside)

maintenance plate

compressor (inside)

piping hole
bottom plate

37

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
7. Remote controller functions
Remote controller 4.Operation MODE
28
29 27 Used to select operation mode.
30 26 Every time you press MODE button, operation mode
25
changes according to following sequence:
31 B A

32 24
33 23 AUTO COOL DRY HEAT FAN
34 22
35 21
36
M D
OFF

20
5.HEALTH Button
19
Used to set health mode, if the unit has the negative ion function
1 TEMP
and oxygen bar function.
ON
2
SWING
OFF FAN
18 6.CLOCK Button
3 Used to set correct time.
4
MODE SLEEP
17 7.CLOCK Button
HEALTH FRESH
16 Used to select TIMER ON, TIMER OFF.
5
CLOCK SET (Note: if time of TIMER ON is the same as TIMER
6 15 OFF,TIMER ON/OFF cannot be set)
TIMER HIGH/SO
7 14
8. FILTER Button
FILTER
8 13 Used to set up/down function of filter.
RESET CODE LIGHT LOCK
12 9. CODE Button
9 11 Used to select code A or B, for this unit, the code is A.
10 10.RESET Button
Press this button by using a sharp article to resume
the correct operation of the remote controller in case
of need, i.e. for example in case of malfunctions due
to electromagnetic noise.
11.LOCK Button
Used to lock operation button and LCD display
1.TEMP Setting Button contents: by pressing this button, other buttons comes
(Used to set temperature. Setting ranges: out of function and lock state display appears; if you press
16 C to 30 C) it again, lock state will be no more active and lock state
In Up/Down function, for controlling up and display will disappear.
down filter. 12.LIGHT Button
Used to light the control panel (only for cabinet unit)
2.SWING Button
If you press this button once, auto swing will 13.Up and down Button
be activated. Used to set TIMER and CLOCK up or down.
If you press this button again, the louver will 14.HIGH/SO Button
fix in the present position. Used to select HIGH or SOFT operation.
3.Power ON/OFF Button 15.SET Button
Used to confirm TIMER and CLOCK settings.
Used for unit start and stop
16.FRESH Button
After power on, the LCD of remote controller Used to set fresh mode, the unit will draw in fresh air.
will display the previous operation state (except 17.SLEEP Button
for TIMER,SLEEP and SWING state). (The clock must be corrected before setting sleep
function)
Used to set sleep mode.
NOTE: 1.Cooling only air conditioner does not have the displays and functions related to heating.
2.HIGH/SO button
This button is activated in Cooling/Heating mode, the fan speed is in AUTO mode after pressing it and "high
functon" will be cancelled automatically after 15 minutes running.
38

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

18.FAN Button The distance between the remote controller and the receiver
should be max 7m and there should be no obstacle between them.
Used to select fan speed:LOW,MID,HIGH,AUTO. Do not throw the remote controller; prevent it from being
19.TIMER OFF Display damaged.
20.CLOCK Display When operating the remote controller in an area where
electronically controlled lights are installed or wireless handsets
21.FILTER Display are used, please move closer to the indoor unit as the function
22.TEMPERATURE Display of the remote controller might be affected by signals emitted
23.AUTO SWING Display by the above mentioned equipments.
24.HIGH/SO Display
25.SIGNAL SENDING Display Battery loading
26.FRESH AIR Display Battery loading
27.ELECTRICAL HEATING Display

*
Batteries are fitted as follows:

*
*
28.Some other buttons

*
Remove the battery compartment lid
All these functions are not available now. Slightly press and disengage the battery compartment lid marked
with ì î and then hold the remote controller by the upper
29.HEALTH Display
section and then remove the battery compartment lid by pressing
Displays when healthy run function is set. in the direction of the arrow as shown in the figure above.
30.DEHUMIDIFICATION Display
Loading the battery
31.Operation MODE Display Ensure that batteries are correctly placed in the compartment
as required for positive and negative terminals.
AUTO RUN COOL RUN DRY RUN HEAT RUN FAN RUN

Replacing the battery compartment lid


The battery compartment lid is reinstalled in the reverse
32.SLEEP State Display sequence.
33.BATTERY Energy Display
Display review
Notify the user when it is time to change Press the button to see if batteries are properly fitted. If
the batteries. no display appears, refit the batteries.
34.LOCK State Display Confirmation indicator
35.FAN SPEED Display
If no indication is displayed after press ON/OFF button,
LO
reload the batteries.
MID Caution:

HI
If the remote controller does not operate as designed after
fitting new batteries of the same
AUTO
type, press the Reset button (marked ) with a pointed article.
AUTO
Note:
It is recommended that the batteries be removed from the
36.TIMER ON Display compartment if the remote controller is not used for an extended
period.
Remote Controller' Operation The remote controller is programmed for automatic test of
When in use, direct signal transmission operation mode after the batteries are replaced. When the test
head to the receiver placed on the indoor is conducted, all icons will appear on the screen and then
disappear if the batteries are properly fitted.
unit

Clock Set MODE SLEEP

When unit is started for the first time and after replacing batteries in remote HEALTH FRESH

controller, clock should be adjusted as follows: CLOCK SET

1.Press CLOCK button, clock indication of " AM " or " PM " flashes. 1 TIMER 2 HIGH/SO 3
2.Press or to set correct time. Each press will increase or decrease FILTER

1 min. If the button is kept pressed, time will increase or decrease quickly.
RESET CODE LIGHT LOCK

3.After time setting is confirmed, press "SET" : AM or PM stop flashing,


while clock starts working.
Note:AM means morning and PM means afternoon.
39
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Fan Operation 1.Unit start


Press ON/OFF button to start your air conditioner.
Previous operation status appears on LCD (except for
TIMER, SLEEP, and SWING setting).

2.Select operating mode


Press MODE button. At each press, operation mode
changes as follows:
A

AUTO COOL DRY HEAT FAN

Then select FAN

TEMP 3. Adjust fan speed


ON
Press FAN button. At each press, fan speed changes as
SWING 4 OFF FAN
3 follows:
MODE
1 SLEEP

HEALTH FRESH
2
LOW MID HIGH
CLOCK SET

TIMER HIGH/SO
Air conditioner will run at the selected fan speed.
FILTER When in AUTO mode, unit will adjust fan speed
RESET CODE LIGHT LOCK
according to room temperature automatically.

4. Unit stop
Press ON/OFF button to stop unit.

About FAN mode


When the air conditioner runs in FAN mode,
it is not possible to select AUTO FAN or to
set temperature.

40
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

AUTO, COOL , HEAT and DRY Operation


1. Unit start
A
Press ON/OFF button,unit starts.
Previous operation status appears on LCD (except for TIMER,
SLEEP and SWING setting)

2.Select operation mode


Press MODE button. At each press, operation mode changes
as follows:
TEMP

3 ON AUTO COOL DRY HEAT FAN


3
SWING
OFF FAN
5 1 4
MODE SLEEP Then select AUTO run or select COOL operation or
FRESH
2 HEALTH select DRY operation or select HEAT operation
CLOCK SET
3.Temperature setting
TIMER HIGH/SO Press TEMP button.
FILTER
Every time the button is pressed, temp. setting increases
1 C; if the button is kept pressed, temp. setting will increase
LOCK
quickly.
RESET CODE LIGHT

Every time the button is pressed, temp. setting decreases


1 C, if the button is kept pressed, temp. setting will decrease
quickly.
Set proper temperature
4.Adjust FAN button
Press FAN button. At each press, fan speed changes as follows:

A
U
T
O

AUTO LOW MID HIGH


COOL operation starts
when room temp.is
higher than temp.
Air conditioner will run at the selected fan speed.
setting.
Ultra-low air flow
5. Unit stop
Temp. setting +2 C Press ON/OFF button,unit stops.
Temp.setting

On reaching temp.setting
+2 C, unit will run in mild
DRY mode.

In ATUO mode, the temperature setting is not displayed on LCD. In this mode, during running air conditioner
will select COOL, HEAT or FAN mode automatically according to the room temperature.
In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit will run intermittently
at LOW speed regardless of FAN setting. When room temperature is lower than temperature setting, unit will
only run FAN operation.
In HEAT mode,warm air will blow out after a short period of time due to cold-draft prevention function.

41
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Adjusting air flow direction

AUTO SWING AUTO SWING

Press SWING button.


Up and down airflow varies upwards When the automatic swing louver moves to the proper
and downwards. Left and right airflow angle, press SWING button can fix the airflow direction.
varies left and right sides.

Always use SWING button on the remote


controller to adjust flaps. Adjusting them by hand
A may result in air conditioner's abnormally running.

In COOL or DRY mode, do not leave the louver in


downward position for a long time, as the water
vapor close to the grille may condense and water
may drop from the air conditioner.
TEMP

ON
OFF
SWING FAN Please carefully set temperature when children,
MODE SLEEP old or infirm people ues the air conditioner.
HEALTH FRESH

CLOCK SET
In case of great humidity, If the vertical flaps
TIMER HIGH/SO are completely turned towards left or right, the
louver will drop water.
FILTER

RESET CODE LIGHT LOCK


Never adjust the louver directly by hand, as this
could make it work abnormally.If the louver work
abnormally, stop unit, restart and adjust the louver
by remote controller.

After unit stops:


Displays on the LCD disappear.
All indicators on the indoor unit go out.
Swing louver automatically close the air outlet.

Hints:
As in COOL mode air flows downwards, adjusting airflow horizontally will be much more helpful
for a better air circulation
As in HEAT mode air flows upwards, adjusting airflow downward will be much more helpful for
a better air circulation.
Be careful not to catch a cold when cold air blows downward directly.

42
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Sleep Function
Before going to bed you can press down the SLEEP button and the air conditioner will run so as to make
you sleep more comfortably.
Before using this function, the clock must be set.

Use of SLEEP function


After the unit's start, set running mode and then press SLEEP button once to make the air conditioner
have the previous-set sleep time (first power-on is "1h"). The sleep symbol will appear. Press time button
/ : you can choose the time in 1~8 hours. Each time the button is pressed, the time increases/decreases 1
hour: "xh" and "OFF" indications appear on the display.

Operation Mode
1.In COOL, DRY mode SLEEP RUN BEGINS SLEEP RUN STOPS
One hour after sleeping operation start, the temperature about 6 hrs
is 1 C higher than the setting one. After another hour,
temperature rises 1 C: sleep run continuously for another increase 1 C
6 hours and then stops. The actual temperature is higher
than the setting one which is to prevent from being too 1 hrs increase 1 C
cold to your sleep.
SETTING T SHUT DOWN
2.In HEAT mode
One hour after sleeping operation start, the temperature In COOL,DRY mode
is 2 C lower than the setting one. After another hour,
temperature decreases by 2 C more. Temperature will
automatically rise by 1 C after another 3 hours'
continuous operation. The actual temperature is lower SETTING T SHUT DOWN
than the setting one which is to prevent from being too
1 hrs decrease 2 C
hot to your sleep.
1 hrs
decrease 2 C
3.In AUTO mode. about 6 hrs
The air conditioner will run in corresponding sleep 3 hrs increase 1 C
operation according to the automatically selected
operation mode. SLEEP RUN STOPS
SLEEP RUN BEGINS
In HEAT mode

OFF

Notes:
TEMP

After setting SLEEP function, it is not possible to set clock. ON


OFF
SWING FAN

If set-sleep time does not reach 8 hours, unit will automatically stop operation MODE SLEEP

after set time is reached. HEALTH FRESH

CLOCK SET

Set " TIMER ON " or " TIMER OFF "In COOL,DRY mode function first, TIMER HIGH/SO

then set SLEEP. After set SLEEP function, the TIMER function cannot be FILTER

set. RESET CODE LIGHT LOCK

43
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Timer ON/OFF Function


Set clock correctly before starting TIMER operation

1.Unit start
A After unit start, select your desired operation mode (operation
mode will be displayed on LCD)
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER
mode. Every time the button is pressed, display of TIMER mode
changes as follows:

ON OFF ON OFF blank


TEMP AM
12:00 PM 12:00 AM
12:00 PM 12:00
ON TIMER ON TIMER OFF TIMER ON-OFF
SWING
OFF FAN
1 Then select TIMER mode as needed (TIMER ON or TIMER OFF).
MODE SLEEP Now ON or OFF will flash.
HEALTH FRESH
3.TIMER setting (press time adjust buttons )
CLOCK SET Every time the button is pressed, time increases 10 minuts.
If the button is kept pressed, time changes quickly.
TIMER 3 HIGH/SO 4
Every time the button is pressed, time decreases 10 minuts.
2 FILTER If the button is kept pressed, time changes quickly.
It can be adjusted within 24 hours at will.
LIGHT LOCK
RESET CODE
4.Confirm setting
After setting correct time, press SET button to confirm time. Now
ON or OFF stop flashing.
Time displayed: unit starts or stops at X hour X min (TIMER ON
or TIMER OFF)
5.Cancel TIMER mode
Just press TIMER button several times until TIMER mode disappears.

Hints:
After replacing batteries or if a power failure occurs, TIMER setting
must be reset.
Remote controller has memory function. When you use TIMER
mode next time, just press SET button after mode selection if timer
setting is the same as the previous one.

Note:
After setting TIMER function, the remote controller displays TIMER time. If you want to see clock time,
just press CLOCK button once: clock time will be displayed (if you press the button again continuously,you
can adjust clock). 5 seconds later, the display will show TIMER time again.

44
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Timer ON-OFF Function


Set clock correctly before starting TIMER operation
1.Unit start
After unit start, select your desired operation mode (operation
mode will be displayed on LCD)
A
2.TIMER mode selection
Press TIMER button on the remote controller to change TIMER
mode. Every time the button is pressed, display of TIMER mode
changes as follows:

ON OFF ON OFF blank


OFF
AM
12:00 PM 12:00 AM
12:00 PM 12:00
TIMER ON TIMER OFF TIMER ON-OFF
TEMP

ON Then select TIMER ON-OFF mode. ON will flash.


SWING
OFF FAN
1 3.Time setting for TIMER ON
MODE SLEEP
Press time button
HEALTH FRESH
Every time the button is pressed, time increases 10 minuts.
If the button is kept pressed, time will changes quickly.
CLOCK SET

Every time the button is pressed, time decreases 10 minuts.


2 TIMER
3HIGH/SO 6 If the button is kept pressed ,time will changes quickly.
It can be adjusted within 24 hours at will.
4 FILTER 5 AM refers to morning and PM refers to afternoon.
RESET CODE LIGHT LOCK
4.Timer confirming for TIMER ON
After setting correct time, press TIMER button to confirm time. Now
ON stops to flash, while OFF starts flashing.

Time displayed : unit starts at X hour X min.


5.Timer setting for TIMER OFF
Press time buttons and follow the same procedures in " Time setting
for TIMER ON"

6.Time confirming for TIMER OFF


After time setting, press SET button to confirm time. OFF stops to flash.
Time displayed: unit starts at X hour X min.

7.Canel TIMER mode


Just press TIMER button several times until TIMER mode disappears.
According to the time setting sequence of TIMER ON and TIMER OFF,
either start-stops or stops-start can be realized.
If the time setting of TIMER ON is the same as TIMER OFF, TIMER
ON-OFF function cannot be set.
45

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Filter Up/Down
(Only for 600*600 panel of single unit)
After the air conditioner has operated for a certain period, dust has
accumulated on the filter, and the filter up/down function can be used
to clean it.
A

1.Whether unit starts or stops, continuously press FILTER


button for 3 seconds, and enter the filter up/down waiting
status (when unit stops, the yellow TIMER indicator flashes,
and filter and clock indication are displayed on the remote
controller. Only the FILTER button, the temperature buttons
" " " " and time buttons are active).
TEMP
2.Press temperature " " button or time " " button in filter
ON up/down waiting status: the up/down mechanism makes
SWING
OFF FAN the filter moving downward and does not stop until it has
reached the maximum limit.
MODE SLEEP

HEALTH FRESH
3.Press temperature " " button or time " " button in filter
up/down waiting status: the up/down mechanism makes
CLOCK SET the filter to moving upward till near the surface board and
then automatically adjusts it to reset (when adjusting to reset,
TIMER HIGH/SO
it will not be controlled by the remote controller till the adju-
FILTER
stment is finished).

RESET 1
CODE LIGHT LOCK

4.During moving downward, press temperature" " button


or time " " button: moving stops.

5.During moving downward, press temperature" " button


or time " " button: moving stops.

6.Continuously press FILTER button 3 seconds again to


cancel the filter up/down waiting mode (unit stops, the
black timer indicator stops flashing, the filter goes back to
the original position, the remote controller goes back to off
status and only clock is displayed).

Note:
If the filter does not thoroughly go back to the original position, only needs to
operate several times repeatedly.

46

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

" High mode " Operation


Outline of operation in "High Mode"
This function is suitable when the set temperature must be
reached in the shortest delay.
A The button "HIGH/SO", referred to this function, is effective
in Cooling/Heating mode (not in Auto/Dry/Fan modes).

A
U
T
O

ON
TEMP

ON Press the HIGH/SO button noce


SWING
OFF FAN The indication appears on the display of the remote
controller and operation in "High Mode" starts.
MODE SLEEP
The AUTO fan speed is automatically set and the corresponding
HEALTH FRESH indication is also displayed.
CLOCK SET

TIMER HIGH/SO

FILTER 1
RESET CODE LIGHT LOCK
OFF
Press the HIGH/SO button twice
If the button is pressed once, the indication is displayed
on the remote controller. If you press the button once again,
the indication disappears, regular operation is restored and fan
speed goes back to the mode set before "High Mode" operation.

NOTICE:
When the air conditioner is operating in " High Mode " , unevenness of room air temperature
may occur due to the intensive operation in a short time.
Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular
operation is automatically restored.

47

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

" Soft mode " Operation

Outline of operation in "Soft Mode"


A
U
T
O
Operation in "Soft Mode", more silent, is suitable when noises
OFF
should be reduced, e.g.. for reading or sleeping.
The button "HIGH/SO", referred to this operation, is effective
in Cooling/Heating mode (not in Auto/Dry/Fan modes).
TEMP

ON
SWING
OFF FAN
ON
MODE SLEEP
Press the HIGH/SO button twice
HEALTH FRESH
The indication appears on the display of the remote
CLOCK SET controller and operation in "Soft Mode" starts.
The AUTO fan speed is automatically set and the corresponding
TIMER HIGH/SO
indication is also displayed.
FILTER 1
RESET CODE LIGHT LOCK

OFF
Press the HIGH/SO button twice
If the button is pressed once, the indication is disappears
from the remote controller's display. If you press the button
once again, regular operation is restored and fan speed goes
back to the mode set before "Soft Mode" operation.

NOTICE:
When the air conditioner is operating in " High Mode " , unevenness of room air temperature
may occur due to the intensive operation in a short time.
Anyway, operation in "High Mode", does not last for more than 15 minutes, then regular
operation is automatically restored.

48

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Auto restart function setting

A
U
T
O

TEMP

ON
SWING
OFF FAN

MODE SLEEP

HEALTH FRESH

CLOCK SET

TIMER HIGH/SO

FILTER

RESET CODE LIGHT LOCK

Setting method (to be applied for a necessary situation) :


After the power failure compensation is set, if power failure suddenly occurs while the air conditioner
is working, it will resume the previous working state when the power is supplied again.
Setting Method: When the remote controller is on (excluding timer mode and fan mode),
press the "Sleep" button on the remote controller 10 times within 5
seconds, and after the buzzer rings 4 times, the air conditioner will enter
the state of auto restart.
Cancel Method: Press the "Sleeping" button on the remote controller 10 times within 5
seconds, and after the buzzer rings 2 timer, the auto restart mode will be
cancelled.
Notes: When a power failure suddenly occurs during the air conditioner is working after the power
failure compensation is set, if the air conditioner will not be used for a long time, please cut off the
power supply to prevent its operation from being resumed after the power is supplied again, or press
the "Switch On/Off" button after the power comes again.
If the unit has not the "sleep" button or function, please realize the function by pressing "swing"
with the same method.

49

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Wired controller YR-E06


sv sw sx sy sz s{ RRNmx22|,z u322-,
su o1xw 2- v-,y|0+
st 2{x 2|+x -y 2|+x0
ss t,w v*-v~
sr RSNm*xx. u322-,
hj_` a\i mqdib tr
{ o1xw 2- 1x2 m*xx.
\onj
n`hk c`\gnc
t{ 12t2x
z
ts RTNn|+x \w}312|,z
y ^gj^f m`n
u322-,
x tt
PDQ ndh`l mg``k o1xw 2- tw}312 2{x
tu 2|+x -y 2|+x0 t,w
w PRO

adgn`l l`m`n l`m`n tv v*-v~


v tw RUNlx1x2 u322-,
u tx
jiOjaa q{x, 2{x 5|0x
ty v-,20-**x0 t..xt01
t tz tu,-0+t* v-,w|2|-,L
s ur 31x t 1{t0.M.-|,2xw
t02|v*x 2- .0x11 2{|1
QTNix25-0~ v-,20-* w|1.*t7 u322-, 2- +t~x 2{x
QNjiOjaa u322-, 5|0x v-,20-**x0
QUNq-0~|,z +-wx w|1.*t7
o1xw 2- 230, -,O-yy 3,|2 Scf_]b[ @ihc Bcc`]b[ CY\ia]X]Zm]b[ GYUh]b[ EUb 0x13+x ,-0+t*
RNnx+.x0t230x w|1.*t7 acXY cdYfUh]cb cdYfUh]cb cdYfUh]cb cdYfUh]cb cdYfUh]cb
RVN\|0 a|*2x0 lx1x2 u322-,
S]fY
SN^*-v~ w|1.*t7 Wcbhfc``Yf \y2x0 v*xt,|,z 2{x
TNn|+x0 jiOjaa w|1.*t7 t|0 |,*x2L .0x11 2{|1
UNc3+|w|27 w|1.*t7 QVN`*xv20|v {xt2|,z w|1.*t7 u322-,L 2{x 3,|2
VN\|0 y|*2x0 v*xt,|,z w|1.*t7 QWNj.x0t2|-, +-wx u322-, vt, 12t02 2- -.x0t2x
q{x, 2{x0x |1 2-- +3v{ w312 v-**xv2xw -, o1xw 2- 1x2 5-0~|,z +-wxZ RWNn|+x0 u322-,
2{x t|0 |,*x2L 2{x 5|0x v-,20-**x0 5|** 1{-5 \32-L ^--*|,zL _x{3+|w|y7|,zL o1xw 2- 1x2 2{x
2{|1 w|1.*t7 2- 0x+|,w 2{x31x0 2- v*xt, 2{x cxt2|,zL at, +-wx -y 2|+x0
t|0 |,*x2N\y2x0 v*xt,|,z t,w |,12t**t2|-,L QXNat, 1.xxw u322-, RXNg-v~ 12t2x w|1.*t7
}312 .0x11 2{x t|0 y|*2x0 0x1x2 u322-,N o1xw 2- 1x2 yt, 1.xxwZ g-5 RYNcxt*2{
at,L hxw at,L c|z{ at,L \32-
WNm3.x0Om-y2 -.x0t2|-, w|1.*t7 o1xw 2- v-,20-* 2{x
QYNm5|,z u322-, zx,x0t2|,z -67zx,
XNat, 1.xxw w|1.*t7
| o1xw 2- 1x2 \32- m5|,z -0 y3,v2|-, t,w ,xzt2|4x
@ihc
a|6xw t|0 1x,w|,z w|0xv2|-, |-,My3,v2|-,
RPNnx+.x0t230x mx22|,z u322-, SPNlx+-2x v-,20-* 5|,w-5
g-5 at, hxw at, c|z{ at, \32-
o1xw 2- 1x2 2x+.x0t230xL o1xw 2- 0xvx|4x 2{x
YN\32- m5|,z w|1.*t7 2x+.x0t230x 0t,zxZ QV ^9SP ^ 0x+-2x v-,20-* 1|z,t*
QPNcxt*2{ 12t2x w|1.*t7 RQN^*-v~ u322-,
o1xw 2- vt*|u0t2x 2{x 2|+x -y
QQNa0x1{ t|0 12t2x w|1.*t7 2|+x0 t,w v*-v~
QRNc3+|w|y7|,z 12t2x w|1.*t7
QSNm*xx. 12t2x w|1.*t7
i-2xZ QNn{|1 +-wx* w-x1 ,-2 {t4x 2{x y-**-5|,z 0x*t2xw w|1.*t7 t,w y3,v2|-, w x y { ss st sv sx tx
RNn{x -32w--0 3,|2 ,- -67zx,Mut0 y3,v2|-, -0 ,- ,xzt2|4x |-, 3,|2 ,- sr t{ {xt*2{ y3,v2|-, t,w {xt*2{ w|1.*t7N

M\fd]k\mdih ia ^fi^e
q{x, 230,|,z -, 2{x 3,|2 y-0 2{x y|012 2|+xL 2{x v*-v~ 1{-3*w ux vt*|u0t2xwN n{x +x2{-w -y vt*|u0t2|-, |1Z
QNk0x11 G^*-v~G u322-,L 2{x ^*-v~ w|1.*t7 G \hG G khG 5|** y*t1{N
RNk0x11 -0 2- tw}312 2|+xN a-0 xtv{ .0x11L 2{x 2|+x 5|** |,v0xt1x -0 wxv0xt1x Q +|,32xN dy wx.0x11|,z
2{x u322-,L 2{x 2|+x 5|** |,v0xt1x -0 wxv0xt1x 0t.|w*7N
SN\y2x0 v-,y|0+|,z 2{x 2|+xL .0x11 G mx2G u322-,L G \hG -0 G khG 5|** 12-. y*t1{|,zL2{x v*-v~ 5|** uxz|, 2- 5-0~N

50

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

lxv-++x,wt2|-,1
o1x ^jjg |, 13++x0N
o1x c`\n |, 5|,2x0N
o1x _ls |, 1.0|,zLt323+, t,w |, wt+. v*|+t2xN hj_` a\i mqdib

IQJ o,|2 \onj


c`\gnc
k0x11 jiOjaa u322-,L 3,|2 12t021N 6 n`hk
8
k0x4|-31 -.x0t2|-, 12t231 t..xt01 -, w|1.*t7
Ii-2 n|+x0 1x22|,zJN k-5x0 |,w|vt2-0 *|z{21 3.N
^gj^f
7 m`n

IRJ mx*xv2 -.x0t2|-, ndh`l mg``k

k0x11 hj_` u322-,N a-0 xtv{ .0x11L -.x0t2|-, adgn`l l`m`n l`m`n
+-wx v{t,zx1 t1 y-**-51Z \h

9
jiOjaa
\onj ^jj _ls c`\n a\i
5
o,|2 5|** 03, |, -.x0t2|-, +-wx w|1.*t7xw -,
g^_Nm2-. w|1.*t7 t2 7-30 wx1|0xw +-wxN
ISJ mx*xv2 2x+.N o,|2 03,1 t2 2{x 1.xxw w|1.*t7xw -, g^_Nd,
c`\n +-wxL 5t0+ t|0 5|** u*-5 -32 ty2x0 t
k0x11 n`hk u322-, 1{-02 .x0|-w -y 2|+x w3x 2- v-*wMw0ty2 .0x4x,2|-,
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2x+.N 1x22|,z y3,v2|-,N
|,v0xt1x1 Q ^N d, _ls +-wxL 5{x, 0--+ 2x+.N uxv-+x1 R ^
dy u322-, |1 ~x.2 wx.0x11xwL 2x+.N1x22|,z 5|** {|z{x0 2{t, 2x+.N 1x22|,zL 3,|2 5|** 03, |,2x0+|22xM
|,v0xt1x /3|v~*7N ,2*7 t2 gjq 1.xxw 0xzt0w*x11 -y a\i 1x22|,zN
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2x+.N 1x22|,z IUJ o,|2 12-.
wxv0xt1x1 Q ^N k0x11 jiOjaa u322-,N
dy u322-, |1 ~x.2 wx.0x11xwL 2x+.N 1x22|,z 5|** j,*7 2|+x t,w 0--+ 2x+. 0x+t|,1 -, g^_N
wxv0xt1x /3|v~*7N \** |,w|vt2-01 z- -32N
o,|2 5|** 12t02 03,,|,z 2- 0xtv{ 2{x 2x+.N 1x22|,z px02|vt* y*t. v*-1x1 t32-+t2|vt**7N
-, g^_N
ITJ at, 1.xxw c|,2
k0x11 a\i u322-,N a-0 xtv{ .0x11L q|0x v-,20-**x0 vt, +x+-0|8x xtv{ -.x0t2|-,
yt, 1.xxw v{t,zx1 t1 y-**-51Z 12t231N
q|0x v-,20-**x0 @RQM q{x, 12t02|,z |2 ,x62 2|+xL }312 .0x11 jiOjaa
u322-, t,w 3,|2 5|** 03, |, .0x4|-31 12t231N
JMS KHC GHFG @RQM
lx+-2x v-,20-**x0 x
.
-
*

JMS KHC GHFG @RQM

\32- 03,,|,zZ _30|,z 2{x \32- 03,,|,z +-wxL t|0 v-,w|2|-,|,z 03,,|,z t,w vt, t32-M1x*xv2 2{x
v--*|,zL{xt2|,zL yt, +-wx tvv-0w|,z 2- 2{x 0--+ 2x+.x0t230xN
at, 03,,|,zZ n{x \^ -,*7 {t4x t|0 13..*7 03,,|,z ,- v--*|,z t,w {xt2|,z 03,,|,z t2 2{x v-,w|2|-,L
\^ vt,H2 {t4x t32- t|0 13..*7 03,,|,zL t,w vt,H2 w|1.*t7 2{x 1x22|,z 2x+.x0t230x 4t*3x -, 2{x g^_N
_30|,z 2{x {xt2|,z 03,,|,zL ty2x0 12t02 2{x \^L |, -0wx0 2- .0x4x,2 v--*xw t|0L \^ vt, 12-. y-0 t
5{|*x uxy-0x 1x,w {xt2 t|0N
_30|,z 2{x wx{3+|y|vt2|-, 03,,|,zL 5{x, 2{x 0--+ 2x+.N 1x22|,z 2x+.N L ,-2 1x22|,z v-,w|2|-,
tvv-0w|,z 2- 2{x t|0 1.xxwN

51

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

X`m Mfi^e ^ikk`^mfq ]`aik` lm\kmdhb Ydg`k ij`k\mdihC


s-3 vt, *x2 3,|2 12t02 -0 12-. t32-+t2|vt**7 t2 y-**-5|,z 2|+xZ ]xy-0x
7-3 5t~x 3. |, 2{x +-0,|,zL -0 zx2 utv~ y0-+ -321|wx -0 ty2x0 7-3
yt** t1*xx. t2 ,|z{2N
ndh`l
@DAKam`k nhdm lm\kmB l`f`^m qink
_`ldk`_ ij`k\mdih gi_`C hj_` a\i mqdib
j.x0t2|-, +-wx 5|** ux w|1.*t7xw
-, g^_Nk-5x0 |,w|vt2-0 *|z{21 3.N n`hk c`\gnc

@EAYRSOW gi_` l`f`^mdih


^gj^f m`n
k0x11 ndh`l u322-, 2- v{t,zx
ndh`l +-wxN`4x07 2|+x 2{x m`n 6 ndh`l mg``k 8
u322-, |1 .0x11xwL w|1.*t7 o
v{t,zx1 t1 y-**-51Z
ML
ML

\h \h
7
adgn`l l`m`n ODPDQ

ML MEE V`Ub_
MEE

mx*xv2 7-30 wx1|0xw ndh`l +-wx jiOjaa

Iji -0 jaaJ 5
@FAYdg`k l`mmdhb
k0x11 ndh` u322-,N
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2|+x |,v0xt1x1 QP+|,Ndy u322-, |1 ~x.2
wx.0x11xwL 2|+x 5|** v{t,zx /3|v~*7N
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2|+x wxv0xt1x1 QP+|,Ndy u322-, |1 ~x.2 wx.0x11xwL
2|+x 5|** v{t,zx /3|v~*7N
n|+x 5|** ux 1{-5, -, g^_N d2 vt, ux tw}312xw 5|2{|, RT{-301N
@GAMihadkgdhb qink l`mmdhb
\y2x0 1x22|,z v-00xv2 2|+xL .0x11 m`n u322-, 2- v-,y|0+ GjiG -0 GjaaG 12-.1 y*t1{|,zN
n|+x w|1.*t7xwZ o,|2 12t021 -0 12-.1 t2 6 {-30 6 +|, Iji -0 jaaJN n|+x0 +-wx |,w|vt2-0 *|z{21 3.N
n- vt,vx* ndh`l
e312 .0x11 ndh`l u322-, 1x4x0t* 2|+x1 3,2|* ndh`l +-wx w|1t..xt01N
\vv-0w|,z 2- 2{x 1x2|,z 2|+|,z -.x,L v*-1x 1x/3x,vxL vt, 0xt*|8x y|012 -.x, 2{x, v-*1x 2{x 3,|2
-0 y|012 v*-1x 2{x, -.x, 2{x 3,|2N

QdhmlJ q|0x v-,20-**x0 .-11x11x1 +x+-07 y3,v2|-,L 5{x, 31x ndh`l +-wx ,x62 2|+xL }312
.0x11 m`n u322-, ty2x0 +-wx 1x*xv2|,z |y 2|+x0 1x22|,z |1 2{x 1t+x t1 .0x4|-31 -,xN
q|0x 0x+-2x v-,20-**x0 -0 0x+-2x v-,20-**x0 vt, +x+-0|8x xtv{ 5-0~|,z v-,w|2|-,N ix62
2|+x -.x, 2{x 3,|2L -,*7 ,xxw 2- .0x11 2{x jiOjaa ~x7L 2{x \^ vt, 5-0~ tvv-0w|,z 2-
*t12 2|+x 5-0~|,z v-,w|2|-,NIn|+|,zL m*xx.|,z t,w m5|,z +-wx ,-2 |,v*3wxwNJ
a0-+ n|+|,z v*-1x 2- 2|+|,z -.x,L vt, 1x22|,z 1*xx. +-wxN
k*xt1x v*-1x {xt*2{ y3,v2|-, y|012 uxy-0x 1x22|,z n|+x0L 2{x, 7-3 vt, w- 2{x ndh`l ji
-.x0t2|-,Nk*xt1x w- ,-2 31x 2{x {xt*2{ y3,v2|-, 5{x, |, ndh`l ji 12t2xN

52

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

hj_` a\i mqdib

n`hk c`\gnc

^gj^f
7 m`n

m`n 6 ndh`l mg``k


:
o
ji jaa

\h 8 9
adgn`l l`m`n ODPDQ

kh

jiOjaa
5

ndh`l jiMjaa
@DAKam`k nhdm lm\kmB l`f`^m qink _`ldk`_ ij`k\mdih gi_`
j.x0t2|-, +-wx 5|** ux w|1.*t7xw -, g^_N k-5x0 |,w|vt2-0 *|z{21 3.N
@EA Vk`ll YRSOW ]nmmih mi ^c\hb` YRSOW gi_`
`4x07 2|+x 2{x u322-, |1 .0x11xwL w|1.*t7 v{t,zx1 t1 y-**-51Z
ML
ML MEE V`Ub_
MEE

ji
mx*xv2 jaa N
@FAYdg` l`mmdhb aik YRSOW UT
k0x11 ndh` u322-,N
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2|+x |,v0xt1x1 QP+|,Ndy u322-, |1 ~x.2 wx.0x11xwL 2|+x 5|** v{t,zx
/3|v~*7N
`4x07 2|+x 2{x u322-, |1 .0x11xwL 2|+x wxv0xt1x1 QP+|,Ndy u322-, |1 ~x.2 wx.0x11xwL 2|+x 5|** v{t,zx
/3|v~*7Nn|+x 5|** ux 1{-5, -, g^_Nd2 vt, ux tw}312xw 5|2{|, RT{-301N
\h 0xyx01 2- +-0,|,z t,w kh 2- ty2x0,--,N
@GA Ydg` ^ihadkgdhb aik YRSOW
\y2x0 2|+x 1x22|,zL .0x11 ndh`l u322-, 2- v-,y|0+NGjiG 12-.1 u*|,~|,zL q{|*x GjaaG 12t021 u*|,~|,zN
n|+x w|1.*t7xwZ o,|2 12t021 t2 r{-30 r +|,N
@HAYdg` l`mmdhb aik YRSOW UPP
a-**-5 2{x 1t+x .0-vxw30x1 |, Gn|+x 1x22|,z y-0 ndh`l jiGN
@IAYdg` ^ihadkgdhb aik YRSOW UPP
\y2x0 2|+x 1x22|,zL .0x11 m`n u322-, 2- v-,y|0+GjaaG 12-.1 y*t1{|,zN
n|+x w|1.*t7xwZ o,|2 12-.1 t2 r {-30 r +|,N
n- vt,vx* ndh`l +-wx
e312 .0x11 ndh`l u322-, 1x4x0t* 2|+x1 3,2|* ndh`l +-wx w|1t..xt01N
\vv-0w|,z 2- 2{x n|+x 1x22|,z 1x/3x,vx -y ndh`l ji -0 ndh`l jaaL x|2{x0 m2t02Mm2-. -0
m2-.Mm2t02 vt, ux tv{|x4xwN

53

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

i-2xZ ]xy-0x 31|,z 2{|1 y3,v2|-,L +312 tw}312 2{x


v*-v~L -0 2{x 1*xx. y3,v2|-, 5|** ux w|1-0wx0xwN
^-+y-02tu*x m*xx. hj_` a\i mqdib

\2 ,|z{2L uxy-0x z-|,z 2- uxw 7-3 vt, .0x11 n`hk c`\gnc

w-5, 2{x mg``k u322-, -, 2{x v-,20-**x0 ^gj^f m`n

t,w 2{x t|0Mv-,w|2|-,x0 5|** 03, u7 2{x m`n ndh`l mg``k

v-+y-02tu*x 1*xx.|,z +-wx 2- +t~x 7-3 1*xx. ;


jaa adgn`l l`m`n l`m`n

+-0x v-+y-02tu*xN \h \h

k0x11 mg``k u322-, -,vx 2- +t~x 2{x t|0 v-,w|2|-,x0 {t4x jiOjaa
2{x .0xM1x2 1*xx. 2|+x Iy|012 .-5x0M-, |1 GQ{GJL 2{x 1*xx. 17+u-*
5|** t..xt0N k0x11 2|+x u322-, L 7-3 vt, 1{--1x 2{x 2|+x
|, Q9X {-301N `tv{ .0x11 -y L 2{x 2|+x |,v0xt1x1O0xw3vx1
Q{-30 t,w G6{G t..xt0 |, 2{x {3+|w|27 1x22|,z t0xtL GjaaG t..xt01
|, Gndh`l jaaG w|1.*t7 t0xt t,w 2|+x0M-yy 2|+x[ .0x11 mg``k
u322-, tzt|, 2- vt,vx* 1*xx. y3,v2|-,L 2{x 1*xx. 17+u-* w|1t..xt01N
Rh ^iifdhbB _`cngd_daqdhb gi_`
j,x {-30 ty2x0 1*xx.|,z -.x0t2|-, 12t02L 2{x 2x+.N |1 Q B {|z{x0 2{t, 2{x 1x22|,z -,xN \y2x0 t,-2{x0 {-30 2{x
2x+.N 0|1x1 Q B t,w 2{x, 03, v-,2|,3-31*7 y-0 t,-2{x0 V{01H t,w 2{x, v*-1xN n{x tv23t* 2x+.N |1 {|z{x0 2{t,
2{x 1x22|,z -,x 5{|v{ |1 2- .0x4x,2 y0-+ ux|,z 2-- v--* 2- 7-30 1*xx.N
Rh c`\mdhb gi_`
j,x {-30 ty2x0 12t02 3.L 2{x 2x+.N wxv0xt1x R B *-5x0 2{t, 2{x 1x22|,z -,xN \y2x0 t,-2{x0 {-30 wxv0xt1x u7
+-0x R B N
n{x 2x+.x0t230x 5|** t32-+t2|vt**7 0|1x u7 Q B ty2x0 t,-2{x0 S{01H -.x0t2|-,L t,w 2{x, t32-+t2|vt**7 v*-1x
ty2x0 S{01H v-,2|,3-31 -.x0t2|-,N n{x tv20t* 2x+.x0t230x |1 *-5x0 2{t, 2{x 1x22|,z -,x 5{|v{ |1 2- .0x4x,2
y0-+ ux|,z 2-- {-2 2- 7-30 1*xx.N
Tim`J d, \onj +-wxL 3,|2 5|** 03, |, mg``k y3,v2|-, tvv-0w|,z 2- 2{x -.x0t2|-, +-wxN
\y2x0 1x22|,z mg``k y3,v2|-,L |2 |1 y-0u|wwx, 2- vt*|u0t2x v*-v~N
dy 2{x 1x2 1*xx.M2|+x w-x1 ,-2 0xtv{ X {-301L 2{x 3,|2 5|** 12-. -.x0t2|-, t32-+t2|vt**7 ty2x0 1x2 2|+x
|1 v-+.*x2xN
mx2 Gndh`lMjaaG y3,v2|-, y|012L 2{x, 1x2 mg``kL t,w 2{x 1*xx.M1x2 |1 .x0y-0+t,vx[ 1x2 ndh`lMji
y3,v2|-, y|012L 2{x 1*xx. y3,v2|-, vt, -,*7 ux 1x2 uxy-0x ndh`lMji[ |y 1x2 2{xmg``k y3,v2|-, y|012L
2{x ndh`l y3,v2|-, vt, ,-2 ux 1x2N
\y2x0 1x22|,z 1*xx. y3,v2|-,L ,-2 t**-5xw 2- tw}312 2{x v*-v~N ^t,H2 31x 2{x 0x+-2x v-,20-**x0 -.x0t2x 2{x
\^N dy 1-L .*xt1x vt,vx* 2{x 1*xx. y3,v2|-, y|012N
\y2x0 1x22|,z 1*xx. y3,v2|-,L vt,H2 1x2 2{x 2|+|,z y3,v2|-,N

m`nndib n mcon _jqi mg``k loi ]`bdim mg``k loi mnjkm

5 \f tu-32 V {01
wxv0xt1x RB

5 \f Q {0 |,v0xt1x Q^
wxv0xt1x1 RB
tu-32 S {01
|,v0xt1x Q^
Q {0
S {01 |,v0xt1xQ B
m`nndib n mcon _jqi

mg``k loi ]`bdim mg``k loi mnjkm


cxt2 +-wx ^--*|,z +-wx

54

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Knmi k`lm\km anh^mdih @mi ]` \jjfd`_ aik \ h`^`ll\kq ldmn\mdihA J


\y2x0 2{x t32-M0x12t02 y3,v2|-, |1 1x2L |y .-5x0 yt|*30x 13wwx,*7 -vv301 5{|*x 2{x t|0 v-,w|2|-,x0
|1 5-0~|,zL |2 5|** 0x13+x 2{x .0x4|-31 5-0~|,z 12t2x 5{x, 2{x .-5x0 |1 13..*|xw tzt|,N
mx22|,z hx2{-wZ q{x, 2{x 0x+-2x v-,20-**x0 |1 -, Ix6v*3w|,z 2|+x0 +-wx t,w yt, +-wxJL .0x11
2{x Gmg``kG u322-, -, 2{x 0x+-2x v-,20-**x0 QP 2|+x1 5|2{|, U 1xv-,w1L t,w ty2x0 2{x u388x0
0|,z1 T 2|+x1L 2{x t|0 v-,w|2|-,x0 5|** x,2x0 2{x 12t2x -y t32-M0x12t02 y3,v2|-,N
^t,vx* hx2{-wZ k0x11 2{x Gm*xx.|,zG u322-, -, 2{x 0x+-2x v-,20-**x0 QP 2|+x1 5|2{|, U 1xv-,w1L
t,w ty2x0 2{x u388x0 0|,z1 R 2|+x0L 2{x .-5x0 yt|*30x v-+.x,1t2|-, +-wx 5|** ux vt,vx**xwN
i-2x1Z q{x, t .-5x0 yt|*30x 13wwx,*7 -vv301 w30|,z 2{x t|0 v-,w|2|-,x0 |1 5-0~|,z ty2x0 2{x .-5x0
yt|*30x v-+.x,1t2|-, |1 1x2L |y 2{x t|0 v-,w|2|-,x0 5|** ,-2 ux 31xw y-0 t *-,z 2|+xL .*xt1x v32 -yy 2{x
.-5x0 13..*7 2- .0x4x,2 |21 -.x0t2|-, y0-+ ux|,z 0x13+xw ty2x0 2{x .-5x0 |1 13..*|xw tzt|,L -0
.0x11 2{x Gm5|2v{ j,OjyyG u322-, ty2x0 2{x .-5x0 v-+x1 tzt|,Ndy 2{x v-,20-**x0 ,- 1*xx. ~x7 L31x
2{x G15|,zG ~x7 |,12xtw 2{x G1*xx.|,zG -, 1x22|,z 2{x t32- 0x12t02 y3,v2|-,N
^-,vx0,|,z hlp \32- lx12t02 y3,v2|-, y-0 cMhlp +-wx*1
ct|x0 \32- lx12t02 y3,v2|-, 5{x, 2{x 3,|2 .-5x0 w0-.1 w-5, 13wwx,*7L 2{x 3,|2 +|v0-.0-vx11-0
5|** 12-0x 2{x .0x4|-31 5-0~|,z v-,w|2|-, t,w 5{x, 2{x .-5x0 |1 -, tzt|,L 2{x 3,|2 5|** 03, t1 2{|1
+x+-07N
\32- lx12t02 y3,v2|-, |1 wx1|z,xw ut1|vt**7 -, 2{x hlp 5{-*x 1712x+L u32 |2 |1 13|2tu*x y-0 xtv{
|,w--0 3,|2 |,w|4|w3t**7N
dy 1-+x -y |,w--0 3,|21 .-5x0 v32 w-5,L u32 2{x -32w--0 3,|2 t,w 2{x -2{x0 |,w--0 3,|21 12|** 5-0~L
+t7ux .0-u*x+1 5|** {t..x, 13v{ t1 y0xx8|,z t2 v--*|,z +-wx t,w -4x0*-tw .0-2xv2|-, t2
{xt2|,z +-wx -, 2{-1x |,w--0 3,|21 5|2{-32 .-5x0N
lxt1-,
q{x, -,x -0 1-+x |,w--0 3,|21 .-5x0 w0-.1 w-5, t,w 2{x -2{x0 |,w--0 3,|21 t0x 12|** 5-0~L 2{x
|,w--0 3,|21 5|2{-32 2{x .-5x0L 5|** ~xx. 2{x .0x4|-31 5-0~|,z v-,w|2|-, uxy-0x 2{x .-5x0 |1 -yyN
\,w x6.t,1|-, 4t*4x ~xx.1 -.x, t2 t ~|,w -y -.x,|,z 0t2x v-,w|2|-, t1 2{x .0x4|-31 0x/3|0x+x,2L
1- 2{x0x |1 0xy0|zx0t,2 y*-5|,z |, 2{x x6v{t,zx0L u32 2{x |,w--0 yt, 12-.1 5-0~|,zN dy 2{x 3,|21 5-0~
t2 v--*|,z +-wxL 2{x |,w--0 3,|21 5|2{-32 2{x .-5x0 5|** +t7ux +t~x y0xx8|,zN dy 2{x 3,|2 5-0~1
t2 {xt2|,z +-wxL +t7ux 2{x -32w--0 3,|2 v-+.0x11-0 5|** 12-. uxvt31x -y 2{x .0x1130x -0
2x+.x0t230x .0-2xv2|-,N n{|1 |1 -30 wx1|z, ut1|vt**7 -, \32- lx12t02 y3,v2|-, v300x,2*7N
ct|x0L cx0x5|2{L 1-*x+,*7 |,y-0+1 -30 v312-+x01L |,12t**x01L w|120|u32-01L x2vN pc`h g\edhb dhlm\ff\mdihB
jf`\l` g\e` lnk` pc`h mc` jip`k dl lcnm _iph pc`mc`k \kmdad^d\ffq ik \^^d_`hm\ffqB mc` pcif`
lqlm`g dh^fn_dhb inm_iik nhdm \h_ \ff mc` dh_iik nhdml gnlm ]` iaaC Ra qin _i him g\e` mc`
dhlm\ff\mdih \l ink dh_d^\mdihB Q\d`k pdff him ]` k`ljihld]f` aik \hq jki]f`g k`lnfmdhb akig mcdlC

Zl`k M\nmdih

\u-32 2{x 0x+-2x v,-20-* -.x0t2|-,L tu-4x -,*7 2t~x 5|0xw 0x+-2x v-,20-**x0 t,w 0x+-2x v-,20-**x0
t1 t x6t+.*x tu-32 2{x 0x+-2x v-,20-**x0 t,w 0x+-2x 0xvx|4x0 31x +x2{-wL |2 |1 2{x 1t+x 0x+-2x
v-,20-**x0 L .*xt1x 31x 0xyx0 2- tu-4x +x2{-wN
i- 1*xx. y3,v2|-, 5{x, 31x 0x+-2x t,w 0x+-2x 0xvx|4x0N

55

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

K]inm c`\fmc anh^mdih

QNc-5 2- 31x 2{x {xt*2{ y3,v2|-, I-,*7 y-0 3,|21 5|2{ 2{|1 y3,v2|-,J
\y2x0 1x2 2{x 0|z{2 y3,v2|-, +-wxL .0x11 {xt*2{ u322-,L
hj_` a\i mqdib
0x+-2x v-,20-**x0 -0 5|0x v-,20-**x0 w|1.*t71 G GL-67zx, .3+.
n`hk c`\gnc
-0 ,xzt2|4x |-, zx,x0t2-0 12t021 3. 2- t..*7 -67zx, -0 ,xzt2|4x
|-, 2- |,w--0 3,|2N k0x11 2{x u322-, tzt|,L2{x 1|z, G G w|1t..M
^gj^f m`n

m`n
xt0xw t,w ,xzt2|4x |-, zx,x0t2-0 12-.1 5-0~|,zN \y2x0 t** {xt*2{
y3,v2|-, -y 2{x |,w--0 3,|2 ux|,z y3**7 vt,vx*xwL -67zx, .3+.
ndh`l mg``k

;
adgn`l l`m`n l`m`n
12-..xwN
jaa

\h \h

jiOjaa
^\ondjiZ
q{x, 2{x 2x+.x0t230x -y 2{x -32w--0 3,|2 |1 *-5x0 2{t, TB L
-67zx, .3+. |1 t32-+t2|vt**7 12-..xwL |y .0x11 {xt*2{ u322-,
}312 2{x,L -67zx, .3+. v-3*w ,-2 12t02 3.N ]32 |y 2{x t|0 v-,w|M
j, 2{x Gcxt*2{G +-wxL |y 7-3 5t,2 2- 2|-,x0 {t1 2{x ,xzt2|4x |-, y3,v2|-, 1|+3*2t,x-31L5{x, .0x11
1x22|,z 2|+|,z -.x, +-wxL 1{-3*w 2{x {xt*2{ u322-,L ,xzt2|4x |-, y3,v2|-, v-3*w 12|** ux -.x0t2xwN
v*-1x 2{x {xt*2{ y|012Z j, 2{x 2|+|,z q{x, 2{x 2x+.x0t230x -y 2{x -32w--0 3,|2 |1 {|z{x0 2{t, V B L
-.x, +-wxL .*xt1x w-,H2 31x {xt*2{ -67zx, .3+. v-3*w t32-+t2|vt**7 0x13+x 2- -67zx,M+t~x
y3,v2|-,N y3,v2|-,N

a-0 cMhlp 5|0xw 27.x |,w--0 3,|2L 2{x 5|0xw v-,20-**x0 vt, ux +t2v{xw 5|2{ 2{x 0x+-2x v-,20-**x0
slMcWQ 2- 0xt*|8x 2{x 0x+-2x v-,20-* y3,v2|-,N
gxy2 .|v230x |1 t 5|0xw 0x+-2x v-,20-**x0L 5{|v{ vt, ux 31xw -, mx0|x1 5|0xw v-,20-*
3,|21 Ln{x 0x+-2x v-,20-**x0 vt, ux .30v{t1xw x620t**7N
] \
q|0xw 0x+-2x ^-,20-**x0 31|,z +x2{-wZ
QNo1x -,x 5|0xw 0x+-2x v-,20-**x0N mxx y|z IQJ
K
Z
Y
U
RN\*1- vt, u37 t 0x+-2x v-,20-**x0 x620t**7L 0xt*|8x
h _
UPP

5|0xw 0x+-2x v-,20-* K 0x+-2x v-,20-* w3t* v-,20-* +-wx1N


n`hk

ji
FC[c`h mc` k`gim` ^ihmkiff`k ^\h ]` nl`_ ih l`kd`l pdk`_ k`gim` ^ihmkiff`k
mqdib

hj_`
jaa

mg``k
a\i
nhdml Bmc\h jf`\l` jk`ll mc` ]immih ?MUNO?mi ^ciil` mc` jkibk\g ia ^i_` ?K?
c`\gnc al`mc

^gj^f m`n

ndh`l cdbcOmj

adgn`l

hj_` a\i mqdib hj_` a\i mqdib

l`m`n ^j_` gdbcn gj^f


\onj \onj
n`hk c`\gnc n`hk c`\gnc

^gj^f m`n ^gj^f m`n

m`n m`n
ndh`l mg``k ndh`l mg``k
< ljjh
^ < ljjh
^
ji jaa ji jaa
adgn`l l`m`n l`m`n adgn`l l`m`n l`m`n

jiOjaa jiOjaa

lx+-2x v-,20-***x0 q|0x 0x+-2x v-,20-***x0


lx+-2x v-,20-***x0 |1 t, tvvx11-07L 2- ux -0wx0xw x620t**7

56

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

DC W`gio` njj`k ^io`k ia pdk` ^ihmkiff`k o..x0 v-4x0 -y 5|0x


v-,20-**x0
lx+-4x 3..x0 .t02 -y 5|0x v-,20-**x0 u7 .0x11N

k^] |1 +-3,2xw -, *-5x0 .t02 -y 5|0x


g-5x0 v-4x0 -y 5|0x
v-,20-**x0L ux vt0xy3* ,-2 2- wt+tzx |2N v-,20-**x0

EC Rhlm\ff mc` pdk`_ k`gim` ^ihmkiff`k


k*xt1x w0|** 25- {-*x1 -, 2{x 5t** tvv-0w|,z 2- 2{x
utv~ v-4x0 1v0x5 {-*x .-1|2|-, -y 2{x 5|0x 0x+-2x
v-,20-**x0L 2{x, 120|~x 2{x 5--w u*-v~ 2- 2{x {-*x1
0x1.xv2|4x*7L 2{x, t*|z, 2{x R 1v0x5 {-*x -y 2{x 5|0x
v-,20-**x0 utv~ v-4x0 2- 2{x 5--w u*-v~L yt12x, 2{x m5|2v{ u322-,
5|0x 0x-2x v-,20-**x0 2- 2{x 5t** 31x 5--w 1v0x51N

FC Xpdm^c l`mmdhb
n{x 15|2v{1 1x22|,z t1 y-**-51ZQNji RNjaa SNji TNjaa mv0x5 {-*x
Tim`
n07 t1 yt0 t1 .-11|u*x t y*t2 130ytvx y-0 |,12t**t2|-,N
_-,H2 31x x6vx11|4x y-0vx 5{x, 2|z{2x,|,z 1v0x51L
-0 *-5x0 .t02 +|z{2 z-2 wxy-0+xwN

GC Mihh`^mdhb g`mci_ \l mc` aiffipdhb ^c\km

i- m7+u-* v-*-30 v-,2x,21

Q \ q{|2x -0 b0xx, QRp ]tv~ v-4x0 -y 2{x 5|0x


v-,20-**x0
R ] lxw 55 b,w

S ^ sx**-5 ^jh

T _

o1x 1{|x*xwx 5|0x1 y-0 2x*xv-++3,|vt2|-,


ux25xx, 5|0x v-,20-**x0 t,w |,w--0 3,|2[
|,w--0 3,|2 t,w -32w--0 3,|2N b0-3,w 2{x
1{|x*w -, -,x 1|wxN m{|x*wxw 5|0x
j2{x05|1x +|1-.x0t2|-, uxvt31x -y ,-|1x
+t7 -vv30N
m|z,t* 5|0x |1 1x*yM.0-4|wxw u7 31x0N z0-3,w

HC W`jf\^` mc` njj`k ^io`k ia pdk` ^ihmkiff`k


]x vt0xy3* ,-2 2- {-*w w-5, 2{x 5|0|,zN

Qdhm QN k-5x0 13..*7 15|2v{ t,w 1|z,t* 5|0x 1{-3*w ux .0x.t|0xw u7 2{x 31x0N
RN _-,H2 2-3v{ k^] 5|2{ {t,wN

57

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

8. Refrigerant Diagram
The part function as follow:

temperature
heat exchanger
Compressor:

sensor
To absorb the refrigerant in the evaporator, and
compress to the condensing pressure, then
discharge them to the condenser.
Condenser:
Condense the refrigerant with high pressure

outdoor unit
from the compressor into the liquid state.
Capillary:
a.Make the pressure change from condensing

nonreturn valve
pressure to evaporating pressure

compressor
silencer
b.Make the partial liquid change into steam
Evaporator:

4-way valve
Make the liquid state refrigerant evaporated into
strainer

accumulator
steam, which can absorb the heat energy of cooled
object.
3-way stop valve

2-way stop valve

welded
welded

point
point

liquide pipe
gas pipe
welded

heat exchanger

welded
point

point
temperature
sensor
indoor unit

capillary

58

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

9. Electrical Control Functions


Anti-freezed protection:

After running for 9 minutes from compressor startup, the unit will check if the indoor coil

temperature is below 0℃, the outdoor fan motor will stop running.

After the compressor stops, if the below conditions can be met, the compressor and the outdoor fan

motor will begin to run again:

1.Shutoff time over 3 minutes

2.Indoor coil temperature up to over 7℃

3-minute protection of compressor when startup

Once the compressor stops running, you can restart up only after 3 minutes. When the unit

powered off in operation, if the shutoff time is below 3 minutes, it will be 3 minutes at least after

powered on when the compressor starts up again. Powered on for the first time, there is no

3-minutes delay protection.

Auto defrosting function

1) Starting condition

The unit is in heat mode, and the compressor runs for 35 minutes continuously.

The compressor has run totally for 45 minutes, and the compressor runs for over 5 minutes

continuously.

If either of the above conditions is met, and the indoor receives the defrosting signal from the

outdoor unit, the unit begins to defrost and send the signal to outdoor.

2) Quit condition

The outdoor receives the signal to quit from the defrost or the defrosting time is over 12 minutes,

the defrost will be over and send the relative signal to the outdoor.

Temperature cutoff protection:

When the indoor coil temperature is over 68℃ for 10 seconds, the compressor and the outdoor fan

motor will stop. When the compressor has stopped for 3 minutes and when the coil temperature is

below 46℃, the compressor and the outdoor fan motor will operate again.

Anti cold air protection in heat mode:

If it is the first time in heat mode or the defrost is over, when the indoor coil temperature is below 28

59

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

℃, the indoor fan motor will stop when the indoor coil temperature is no less than 28℃ and less

than 38℃, the indoor fan motor will run in low speed when the indoor coil temperature is over 38℃

or the compressor has run for over 4 minutes, the indoor fan motor will run at the set speed.

10. Diagnostic information (troubleshooting)


10.1 System failure

If the refrigerant in the system cannot flow fluently or the airflow circles more slowly, please check

due to the following procedures.

10.1.1 Cooling
bad cooling

if set temp. is proper change the set temp.

if the cooling load too large check the evaluation of


cooling load

refrigerant flow 4-way valve failure change 4-way valve


malfunction

lack of refrigerant recharge refrigerant

solenoid valve failure change the solenoid valve

compressor failure change compressor

bad ventilation if fan is set as low speed set the fan as med speed

if air inlet filter is blocked clean the filter

if the refrigerant pipe between insulate the thick pipe


I.D and O.D is insulated and slim pipe separately

Figure 1 
10.1.2 Hearting

60

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
 
bad he ating

if se t tem p. is proper c han ge the set tem p.

if the h ea tin g loa d too large che c k th e e valuation of


he ating load

refrigera nt flow 4 -w a y v alv e failure cha ng e 4 -w ay valve


m alfun ction

la ck o f re frigerant rech arge re frigerant

soleno id valv e failure ch an ge th e solenoid valve

co m presso r failure cha ng e com pressor

ba d ven tilation if fan is s et a s low sp eed set the fa n a s m ed speed

if air in let filter is blocked clea n th e filter

ou tdoo r defro sting tem p.


se nsor is d am aged,w hich cha ng e o utdo or defrosting
re sults in the outdoor untrue tem p. sensor
de fro s ting

insu la te th e thick pipe and


if re frige rant pipe betw een I.D
th e slim p ip e respectively
an d O .D is insulated

b low out 4-w ay valve failure


co ld air ch an ge 4 -w ay valve

ind oor c oil tem p. sens or cha nge the sensor


a nti co ld air invalid
failure

Figure 2
10.1.3 Unit operation
a. Indoor fan not running

61

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

if the power LED on indoor PCB is


proper

yes check if there is


voltage output at
the fan motor output
no terminal
check if power supply is proper no
yes
yes
no check if there
check if the fuse is proper is level output
at the chip of check if the fan
yes PCB capacitor is proper
change check if the voltage dependent no
yes
fuse resistor is conductive
yes
yes no
change voltage check if fan
dependent resistor speed control if the chip of check if fan motor
PCB is bad change fan
relay is bad coil is proper
capacitor

no
yes yes
change voltage change PCB change fan
dependent resistor motor

Figure 3
b. Outdoor fan not running
 
if the power LED on outdoor PCB
is proper

yes check if there is


voltage output at
the fan m otor output
no term inal
check if power supply is proper no
yes
yes
no check if there
check if the fuse is proper is level output
at the chip of check if the fan
yes PCB capacitor is proper
change check if the voltage dependent no
yes
fuse resistor is conductive
yes
yes no
change voltage check if fan
dependent resistor speed control if the chip of check if fan m otor
PCB is bad change fan
relay is bad coil is proper
capacitor

no
yes yes
change voltage change PCB change fan
dependent resistor m otor

Figure 4
10.2 Failure code
AP96NACAEA adopts operation panel+infrared control type, while AD96NAHAEA adopts wired
control type. If the air conditioner occurs failure, the failure code will be displayed on the wired
controller or the operation panel as the following chart:

Failure code Reason

E0 Indoor float switch abnormal


E1 Indoor ambient temp. sensor abnormal

62

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
 E2 Indoor coil temp. sensor abnormal
 E3 Outdoor ambient temp. sensor abnormal
 E4 Outdoor coil temp. sensor abnormal
 E5 Over current protection
 E6 High/low pressure protection
 E8 Communication abnormal between panel and
indoor unit
 E9 Communication abnormal between outdoor
and indoor unit
Diagnose and troubleshooting
1) No display on LCD of wired controller, and the unit not running

start

if LED on PCB is
lighted on

yes

if there is voltage output at yes if there is 12V voltage change or


no
repair wired
primary side of transformer of between A and B,C,D
controller
indoor PCB of wired controller
yes yes
check if the power cable,
communication wire of no if there is 220VAC
indoor/outdoor are on the power input change wired
connected correctly side of indoor PCB controller

yes

check ther power yes


terminal block

no if indoor transformer
reconnect is connected to the no if the fuse of indoor
socket firmly PCB is burnt off

yes yes

if there is 15VAC if the primary side of


change transformer of no change PCB
no at secondary side indoor transformer is
indoor power supply of transformer of short circuit
indoor PCB
yes

change the transformer

63

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
 2) E0 – float switch abnormal
s ta rt

d is p la y E 0

c h e c k if t h e f lo a t no
m o d if y it s p o s it io n
s w it c h is lo c a t e d
yes
c h e c k if f lo a t s w it c h
w o r k s n o r m a lly

no
c h a n g e f lo a t s w it c h

3) E1 – indoor ambient temperature sensor abnormal

s ta r t

d is p la y E 1

c h e c k if th e in d o o r no
a m b ie n t te m p . s e n s o r a d ju s t its p o s itio n
is lo c a te d p r o p e r ly
yes
c h e c k if th e s e n s o r
v a lu e is r ig h t

no
change sensor

Note: value of indoor ambient temperature sensor is 23KΩ.

64

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
4) E2 – indoor coil temperature sensor abnormal

s ta rt

d is p la y E 2

c h e c k if in d o o r c o il no
te m p .s e n s o r is a d ju s t th e p o s itio n
lo c a te d
yes
c h e c k if th e s e n s o r
v a l u e i s r ig h t

no

c h a n g e th e s e n s o r

Note: indoor coil temperature sensor value is 10KΩ.


5) E3 – outdoor ambient temperature sensor abnormal

s ta rt

d is p la y E 3

c h e c k if o u t d o o r no
a m b ie n t t e m p . s e n s o r a d ju s t t h e p o s it io n
is lo c a t e d
yes
c h e c k if t h e s e n s o r
v a lu e is r ig h t

no

c h a n g e th e s e n s o r

65

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
6) E4 – outdoor coil temperature sensor abnormal

s ta rt

d is p la y E 4

c h e c k if o u td o o r c o il no
a d ju s t th e p o s itio n
te m p .s e n s o r is
lo c a te d
yes
c h e c k if th e s e n s o r
v a lu e is r ig h t

no

c h a n g e th e s e n s o r

7) E5 – over current protection

start

display E5

if compressor
stops suddenly in
running and
alarms no

compressor not compressor load too


runs or stops after large,current is
running a little more than limitation

yes yes
analyse reason of
analyse reason of
compressor overheat,
compressor overheat,
and refer to the system
and solve it
information
yes
switch off power,and power
on when temperature reduces
to 30-40degree, start up again
8) E6 – pressure protection

66

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
start

display E6

check if the wires of


pressure switch is
proper,and firm fix the wires of
no
pressure switch
yes again

analyse the reason


of high pressure
and solve it

9) E8 – communication failure between operation panel and indoor unit


s ta rt

if th e w ire d c o n tro lle r no c h a n g e w ire d


a n d in d o o r P C B a re c o n tro lle r
c o m p a tib le
yes
if te rm in a ls A ,B ,C ,D o n
w ire d c o n tro lle r a re no
c o rre s p o n d in g w ith w ire c o rre ctly
te rm in a ls o f in d o o r P C B
yes
if te rm in a ls A ,B ,C ,D o f no
w ire d c o n tro lle r a re in w ire c o rre c tly
o p e n c irc u it o r
c o n n e c te d w e ll
yes
if te rm in a ls A ,B (o r yes
w ire c o rre ctly
C ,D )o f w ire d c o n tro lle r
a re s h o rt c irc u it

10) E9 – communication failure between indoor and outdoor

67

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

start

display E9

if indoor and outdoor are


powered on respectively
yes
no

if the live wire and if the wires between


no
neutral wire of indoor indoor and outdoor wire correctly
and outdoor are are correct
accordant
yes
yes if the communication
yes
wires between outdoor re-wire
adjust live wire and and indoor are in open
neutral wire circuit or not connected
well

no

check if communication
yes change
circuit of indoor and
PCB
outdoor is damaged

10.3 Typical resistance value of sensors

Indoor coil temperature sensor: R25℃=10KΩ+3%, B(25/50)=3741K+70K


temperature value temperature value temperature value
-30℃ 155.4 11℃ 18.4 52℃ 3.525
-29℃ 146.4 12℃ 17.59 53℃ 3.402
-28℃ 138.1 13℃ 16.81 54℃ 3.283
-27℃ 130.2 14℃ 16.08 55℃ 3.17
-26℃ 122.9 15℃ 15.38 56℃ 3.061
-25℃ 116 16℃ 14.71 57℃ 2.956
-24℃ 109.5 17℃ 14.08 58℃ 2.855
-23℃ 103.5 18℃ 13.48 59℃ 2.759
-22℃ 97.77 19℃ 12.91 60℃ 2.666
-21℃ 92.44 20℃ 12.36 61℃ 2.577
-20℃ 87.42 21℃ 11.84 62℃ 2.491
-19℃ 82.71 22℃ 11.35 63℃ 2.408
-18℃ 78.29 23℃ 10.88 64℃ 2.329
-17℃ 74.12 24℃ 10.43 65℃ 2.253
-16℃ 70.21 25℃ 10 66℃ 2.179
-15℃ 66.52 26℃ 9.592 67℃ 2.108
-14℃ 63.06 27℃ 9.204 68℃ 2.04
-13℃ 59.79 28℃ 8.833 69℃ 1.975

68

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
-12℃ 56.71 29℃ 8.479 70℃ 1.912
-11℃ 53.81 30℃ 8.141 71℃ 1.851
-10℃ 51.08 31℃ 7.819 72℃ 1.793
-9℃ 48.5 32℃ 7.511 73℃ 1.737
-8℃ 46.07 33℃ 7.217 74℃ 1.682
-7℃ 43.77 34℃ 6.936 75℃ 1.63
-6℃ 41.6 35℃ 6.668 76℃ 1.58
-5℃ 39.55 36℃ 6.411 77℃ 1.531
-4℃ 37.62 37℃ 6.166 78℃ 1.484
-3℃ 35.79 38℃ 5.931 79℃ 1.439
-2℃ 34.06 39℃ 5.707 80℃ 1.395
-1℃ 32.43 40℃ 5.492 81℃ 1.353
0℃ 30.88 41℃ 5.287 82℃ 1.313
1℃ 29.42 42℃ 5.09 83℃ 1.274
2℃ 28.03 43℃ 4.902 84℃ 1.236
3℃ 26.72 44℃ 4.722 85℃ 1.2
4℃ 25.48 45℃ 4.549 86℃ 1.164
5℃ 24.3 46℃ 4.383 87℃ 1.13
6℃ 23.18 47℃ 4.225 88℃ 1.098
7℃ 22.12 48℃ 4.073 89℃ 1.066
8℃ 21.12 49℃ 3.927 90℃ 1.035
9℃ 20.17 50℃ 3.788
10℃ 19.26 51℃ 3.654

Indoor ambient temperature sensor: R25℃=23KΩ±3.5%, B(25/5)=4177K±103K


temperature value temperature value temperature value
-20℃ 251.8 16℃ 35.31 52℃ 7.178
-19℃ 236.9 17℃ 33.63 53℃ 6.897
-18℃ 223.1 18℃ 32.04 54℃ 6.628
-17℃ 210.1 19℃ 30.53 55℃ 6.371
-16℃ 197.9 20℃ 29.1 56℃ 6.125
-15℃ 186.5 21℃ 27.75 57℃ 5.889
-14℃ 175.9 22℃ 26.47 58℃ 5.664
-13℃ 165.9 23℃ 25.25 59℃ 5.449
-12℃ 156.5 24℃ 24.1 60℃ 5.243
-11℃ 147.7 25℃ 23 61℃ 5.046
-10℃ 139.5 26℃ 21.96 62℃ 4.857
-9℃ 131.8 27℃ 20.97 63℃ 4.676
-8℃ 124.5 28℃ 20.03 64℃ 4.502
-7℃ 117.7 29℃ 19.14 65℃ 4.336
-6℃ 111.3 30℃ 18.3 66℃ 4.177
-5℃ 105.3 31℃ 17.49 67℃ 4.024
-4℃ 99.63 32℃ 16.73 68℃ 3.878
-3℃ 94.3 33℃ 16 69℃ 3.738
69

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
-2℃ 89.3 34℃ 15.3 70℃ 3.603
-1℃ 84.58 35℃ 14.65 71℃ 3.474
0℃ 80.14 36℃ 14.02 72℃ 3.35
1℃ 75.96 37℃ 13.42 73℃ 3.231
2℃ 72.02 38℃ 12.85 74℃ 3.117
3℃ 68.31 39℃ 12.31 75℃ 3.008
4℃ 64.81 40℃ 11.79 76℃ 2.903
5℃ 61.51 41℃ 11.3 77℃ 2.802
6℃ 58.39 42℃ 10.83 78℃ 2.705
7℃ 55.45 43℃ 10.39 79℃ 2.611
8℃ 52.68 44℃ 9.96 80℃ 2.522
9℃ 50.06 45℃ 9.553
10℃ 47.58 46℃ 9.165
11℃ 45.24 47℃ 8.794
12℃ 43.02 48℃ 8.441
13℃ 40.93 49℃ 8.103
14℃ 38.95 50℃ 7.78
15℃ 37.08 51℃ 7.472

Outdoor ambient/coil temperature sensor: R25℃=5KΩ±1%, B(25/50)=3450K±1%


temperature value temperature value temperature value
-20℃ 37.44 16℃ 7.142 52℃ 1.912
-19℃ 35.55 17℃ 6.857 53℃ 1.85
-18℃ 33.77 18℃ 6.586 54℃ 1.79
-17℃ 32.08 19℃ 6.327 55℃ 1.733
-16℃ 30.49 20℃ 6.08 56℃ 1.678
-15℃ 29 21℃ 5.844 57℃ 1.625
-14℃ 27.58 22℃ 5.619 58℃ 1.574
-13℃ 26.24 23℃ 5.403 59℃ 1.525
-12℃ 24.98 24℃ 5.197 60℃ 1.477
-11℃ 23.78 25℃ 5 61℃ 1.432
-10℃ 22.65 26℃ 4.812 62℃ 1.388
-9℃ 21.59 27℃ 4.631 63℃ 1.345
-8℃ 20.58 28℃ 4.459 64℃ 1.304
-7℃ 19.62 29℃ 4.294 65℃ 1.265
-6℃ 18.72 30℃ 4.136 66℃ 1.227
-5℃ 17.86 31℃ 3.985 67℃ 1.19
-4℃ 17.05 32℃ 3.84 68℃ 1.154
-3℃ 16.27 33℃ 3.701 69℃ 1.12
-2℃ 15.54 34℃ 3.568 70℃ 1.087
-1℃ 14.85 35℃ 3.44 71℃ 1.055
0℃ 14.19 36℃ 3.318 72℃ 1.024
1℃ 13.56 37℃ 3.201 73℃ 0.9946
2℃ 12.97 38℃ 3.088 74℃ 0.9657
70

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
3℃ 12.41 39℃ 2.981 75℃ 0.9379
4℃ 11.87 40℃ 2.877 76℃ 0.911
5℃ 11.36 41℃ 2.778 77℃ 0.8849
6℃ 10.88 42℃ 2.682 78℃ 0.8598
7℃ 10.41 43℃ 2.591 79℃ 0.8354
8℃ 9.976 44℃ 2.503 80℃ 0.8119
9℃ 9.559 45℃ 2.418
10℃ 9.161 46℃ 2.337
11℃ 8.783 47℃ 2.259
12℃ 8.422 48℃ 2.184
13℃ 8.079 49℃ 2.112
14℃ 7.752 50℃ 2.043
15℃ 7.439 51℃ 1.976

11. Electric data


11.1 Wiring diagram

WIRING DIAGRAM OF DUCT INDOOR UNIT


WIRED CONTROLLER PIPING TEMP.SENSOR

BL
R
B
DETECTOR
T6.3A/250VAC
FAN MOTOR

FUSE
M W
FAN MOTOR

Y/G W B R
CAPACITOR
TRANSFORMER Y/G
M
Y/G W FC
CAPACITOR

B:BLACK W:WHITE NOTE:


R:RED BL:BLUE Dashed part is optional
TO OUTDOOR UNIT
BR:BROWN GR:GREY
Y/G:YELLOW/GREEN

71

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

WIRING DIAGRAM OF CABINET INDOOR UNIT

PIPING TEMP.SENSOR
REMOTE RECEIVER ROOM TEMP.
SENSOR

SWING MOTOR
CN3
M CN17
CN18
CN12 CN11 CN6
~
1 CN2
CN10
CN16 REMOTE DETECTOR
CN21 T6.3A/250VAC
CN15 CN20 CN19
BL B B FUSE CN9
Y
Y
BL
R W B R
FAN MOTOR
TRANSFORMER
Y/G
M FAN MOTOR M R T3.15A/250VAC
Y/G Y/G W B R Y/G
FAN CAPACITOR FAN CAPACITOR 1 2 3

TO OUTDOOR UNIT

NOTE:Dashed part 1 is optional


W:WHITE R:RED BR:BROWN
B:BLACK GR:GREY Y/G:YELLOW/GREEN

WIRING DIAGRAM OF OUTDOOR UNIT

TRANS.
CIRCUIT DETECTOR

HIGH PRESSURE SWITCH CN1


CN2
LOW PRESSURE SWITCH
CN10 CN9 FAN MOTOR
1 CN3
OUTDOOR AMBINENT SENSOR 4-WAY VAVLE
CN12 CN5 WIND 2
OUTDOOR PIPING SENSOR
CN11
COMPRESSOR VENT SENSOR
S
MAGNETIC CONTACTOR
L3
CN7
COMPRESSOR
L2 FUSE
L1 M
N T6.3A/250VAC CN4

R B BL W R
CRANKCASE
HEATER

Y/G
Y/G
R W BL B Y/G W B R Y/G
1 2 3
L1 L2 L3 N

NOTE:
Y/G:YELLOW/GREEN
POWER TO INDOOR Dashed parts 1 2 are not available for only
R:RED W:WHITE cooling type
BL:BLUE B:BLACK
SUPPLY UNIT

72

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
12. Exploded view and spare parts list
1

5
64

6
8 9
7
63
10
11
62
15

61 16

12

60
59

57

56 58 17
19
18 13
23 14
55 20
21 22
54

24
53
48 25

52 49 47 26
50

51

46 27
40
28
45
43
41 42 44
29
65 30

31
39
32

33

34

35

36

37

38

73

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

No. in The proportion


Spare parts Remar
exploded Spare parts description in english Model Qty Failure rate of the spare
number k
view part stock
1 0010151115 top grille AU96NATAEA 1 0.00% 0.000% ×
2 0010851121 air loop (belong to top cover assly)AU96NATAEA 1 0.00% 0.000% ×
3 0010851121 top cover assembly AU96NATAEA 1 0.00% 0.000% ×
4 0010251013 fan AU96NATAEA 1 0.02% 0.024% *
5 0010450788 outdoor motor AU96NATAEA 1 0.02% 0.024% *
6 0010151081 fixing bracket 3 AU96NATAEA 1 0.00% 0.000% ×
7 0010151076 motor fixing bracket AU96NATAEA 1 0.00% 0.000% ×
8 0010753879 condenser assembly 2 AU96NATAEA 1 0.01% 0.012%
9 0010151059 back guarding plate AU96NATAEA 1 0.00% 0.000% ×
10 0010851120 motor fixing plate assembly AU96NATAEA 1 0.00% 0.000% ×
11 0010151080 fixing bracket 2 AU96NATAEA 2 0.00% 0.000% ×
12 0010851428 right side plate AU96NATAEA 1 0.00% 0.000% ×
13 0010151083 partition plate AU96NATAEA 1 0.00% 0.000% ×
14 0010151073 fixing bracket AU96NATAEA 1 0.00% 0.000% ×
15 0010151065 access plate AU96NATAEA 1 0.00% 0.000% ×
16 0010151064 big access plate AU96NATAEA 1 0.00% 0.000% ×
17 0010450398 coil temperature sensor AU96NATAEA 1 0.02% 0.024% *
18 001A5736055 ambient temperature sensor clip AU96NATAEA 1 0.00% 0.000% ×
19 001A3900110 ambient temperature sensor AU96NATAEA 1 0.02% 0.024% *
20 0010151072 horizontal plate AU96NATAEA 1 0.00% 0.000% ×
21 0010450098 low pressure switch AU96NATAEA 1 0.02% 0.024% *
22 0010450097 high pressure switch AU96NATAEA 1 0.02% 0.024% *
23 0010751777 compressor AU96NATAEA 1 0.02% 0.024% *
24 0010753472 pipe assembly AU96NATAEA 1 0.00% 0.000% ×
25 001A2500135 4-way valve AU96NATAEA 1 0.00% 0.000% ×
26 001A21111604 air-liquid segregator AU96NATAEA 1 0.01% 0.012%
27 0010450094 solenoid valve winding AU96NATAEA 1 0.02% 0.024% *
28 0010151086 back panel plate AU96NATAEA 1 0.00% 0.000% ×
29 001A17561378 heat insulation pipe AU96NATAEA 1 0.00% 0.000% ×
30 0010753850 by-pass capillary AU96NATAEA 2 0.00% 0.000% ×
31 001A2500136 gas pipe stop valve AU96NATAEA 1 0.00% 0.000% ×
32 0010151084 lower bracket 1 AU96NATAEA 4 0.00% 0.000% ×
33 0010851119 compressor bracket assembly AU96NATAEA 1 0.00% 0.000% ×
34 0010151057 big valve pedestal AU96NATAEA 1 0.00% 0.000% ×
35 0010152366 bottom plate AU96NATAEA 1 0.00% 0.000% ×
36 0010151066 bottom bracket AU96NATAEA 2 0.00% 0.000% ×
37 0010151060 lower bracket AU96NATAEA 1 0.00% 0.000% ×
38 0010151061 maintenance plate AU96NATAEA 1 0.00% 0.000% ×
39 0010851427 front panel AU96NATAEA 1 0.00% 0.000% ×
40 0010851009 water groove assembly AU96NATAEA 1 0.00% 0.000% ×
41 001A2500139 liquid pipe stop valve AU96NATAEA 1 0.00% 0.000% ×
42 0010151074 valve pedestal AU96NATAEA 1 0.00% 0.000% ×
43 001A17551381 soft material AU96NATAEA 1 0.00% 0.000% ×
44 0010450697 electric heater AU96NATAEA 2 0.00% 0.000% ×
45 001A5102050 flange nut M8 AU96NATAEA 4 0.00% 0.000% ×
46 0010450243 discharging temperature sensor AU96NATAEA 1 0.02% 0.024% *
47 0010753834 capillary AU96NATAEA 1 0.00% 0.000% ×
48 0010151077 electric control box AU96NATAEA 1 0.00% 0.000% ×
49 0010450789 wires AU96NATAEA 1 0.00% 0.000% ×
50 0010450792 outdoor fan capacitor AU96NATAEA 1 0.04% 0.048% *
74

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

51 0010151537 capacitor clip AU96NATAEA 1 0.00% 0.000% ×


52 0010400298 relay AU96NATAEA 1 0.02% 0.024% *
53 0010450913 power terminal block AU96NATAEA 1 0.00% 0.000% ×
54 0010450376 AC contactor AU96NATAEA 1 0.02% 0.024% *
55 0010451265 terminal block (with PVC sleeves) AU96NATAEA 1 0.00% 0.000% ×
56 001A5745116 wire-pressing clips AU96NATAEA 2 0.00% 0.000% ×
57 0010451346 transformer AU96NATAEA 1 0.02% 0.024% *
58 0010451443 PCB AU96NATAEA 1 0.04% 0.048% *
59 001A17521476 rubber loop AU96NATAEA 1 0.00% 0.000% ×
60 / fan speed control wiring AU96NATAEA / / / /
61 0010151058 front guarding plate AU96NATAEA 1 0.00% 0.000% ×
62 0010753878 condenser assembly 1 AU96NATAEA 1 0.01% 0.012%
63 0010152361 left side plate AU96NATAEA 1 0.00% 0.000% ×
64 0010251084 cushion rubber AU96NATAEA 4 0.00% 0.000% ×
65 0010151465 electric control box cover AU96NATAEA 1 0.00% 0.000% ×
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The
first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual
quantity 3 months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and
should be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock
in the spare-part warehouse accord with the actual case,should be marked with " ".
4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare
parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part
warehouse,should be marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.
6.The spare parts price on net is FOB Qingdao term.

75

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

3
4
6
5
9 8 7
10

16 17
22
15
21
14
13
19 20

12
11

18
25

23 55
24

26
54

27
29
33 28 51
31
32 50
41
49
34 40
52

30 53
35
47
46 48
45
39 43
29 27
36 38 44
37 41
42 30
28

76
Downloaded from AC-Manual.com Manuals
Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
No. in
Spare parts Failure the proportion Remar
exploded Spare parts description in english Model Qty
number rate of the spare part k
view stock
1 0010150286 guard plate 1 AD96NAHAEA 1 0.00% 0.000% ×
2 0010150289 guard plate 2 AD96NAHAEA 1 0.00% 0.000% ×
3 0010250260 drainage pan AD96NAHAEA 1 0.00% 0.000% ×
4 0010150379 supporting plate 2 assembly AD96NAHAEA 1 0.00% 0.000% ×
5 001A0100907 supporting plate 1 assembly AD96NAHAEA 1 0.00% 0.000% ×
6 0010151134 motor fixing bolt AD96NAHAEA 4 0.00% 0.000% ×
7 001A6645001 wires clip AD96NAHAEA 6 0.00% 0.000% ×
8 001A1734260 heat insulation pipe AD96NAHAEA 1 0.00% 0.000% ×
9 001A1734261 heat insulation pipe (liquid pipe) AD96NAHAEA 1 0.00% 0.000% ×
10 001A5313008 copper nut AD96NAHAEA 1 0.00% 0.000% ×
11 001A13011044 sealing ring of scroll case AD96NAHAEA 4 0.00% 0.000% ×
12 001A2301102 fan 1 AD96NAHAEA 2 0.02% 0.024% *
13 001A13011040 scroll case 1 AD96NAHAEA 2 0.00% 0.000% ×
14 001A5401035 spring washer AD96NAHAEA 2 0.00% 0.000% ×
15 001A3000291 indoor motor AD96NAHAEA 2 0.04% 0.048% *
16 001A13011041 scroll case 2 AD96NAHAEA 2 0.00% 0.000% ×
17 001A2301103 fan 2 AD96NAHAEA 2 0.02% 0.024% *
18 0010800290 evaporator fixing plate 3 AD96NAHAEA 1 0.00% 0.000% ×
19 001A3400160 float switch AD96NAHAEA 1 0.01% 0.012%
20 0010151136 float bracket AD96NAHAEA 1 0.00% 0.000% ×
21 0010751619 evaporator assembly AD96NAHAEA 1 0.01% 0.012%
22 0010151133 evaporator fixing plate 2 AD96NAHAEA 1 0.00% 0.000% ×
23 001A3900006 coil temperature sensor AD96NAHAEA 1 0.02% 0.024% *
24 0010150376 left fixing groove AD96NAHAEA 1 0.00% 0.000% ×
25 0010150405 right fixing groove AD96NAHAEA 1 0.00% 0.000% ×
26 0010850513 fixing bracket assembly AD96NAHAEA 1 0.00% 0.000% ×
27 001A13011053 short frame 1 AD96NAHAEA 1 0.00% 0.000% ×
28 001A13011055 short frame 2 AD96NAHAEA 1 0.00% 0.000% ×
29 0010151123 hanging bracket AD96NAHAEA 4 0.00% 0.000% ×
30 0010151135 fixed bracket AD96NAHAEA 4 0.00% 0.000% ×
31 0010151131 fixed reinforced plate 1 AD96NAHAEA 1 0.00% 0.000% ×
32 0010851029 cushion 2 assembly of cover plate AD96NAHAEA 1 0.00% 0.000% ×
33 0010450377 wires assembly AD96NAHAEA 1 0.00% 0.000% ×
34 0010151140 electric box cover AD96NAHAEA 1 0.00% 0.000% ×
35 0010400137 wired controller AD96NAHAEA 1 0.02% 0.024% *
36 0010451346 transformer AD96NAHAEA 1 0.01% 0.012% ×
37 0010400298 relay AD96NAHAEA 3 0.02% 0.024% *
38 001A3600254 capacitor AD96NAHAEA 1 0.02% 0.024% *
39 001A3300352 fan speed control board AD96NAHAEA 1 0.02% 0.024% *
40 001A5745116 wire-pressing clip AD96NAHAEA 1 0.00% 0.000% ×
41 001A1452861 rubber wiring hole AD96NAHAEA 1 0.00% 0.000% ×
42 / ambient temperature sensor AD96NAHAEA / / / /
43 0010400132 indoor PCB AD96NAHAEA 1 0.04% 0.048% *
44 0010451265 terminal block AD96NAHAEA 1 0.00% 0.000% ×
45 0010851015 electric box assembly AD96NAHAEA 1 0.00% 0.000% ×
46 0010851028 cushion 1 assembly of cover plate AD96NAHAEA 1 0.00% 0.000% ×
47 001A1439315 plastic clip AD96NAHAEA 6 0.00% 0.000% ×
48 0010851016 bottom plate AD96NAHAEA 1 0.00% 0.000% ×
49 0010151137 fixed bracket 1 AD96NAHAEA 1 0.00% 0.000% ×
50 0010150378 evaporator fixing plate AD96NAHAEA 1 0.00% 0.000% ×
51 0010151138 fixed bracket 2 AD96NAHAEA 1 0.00% 0.000% ×
52 0010151124 liquid inlet/outlet guard plate AD96NAHAEA 1 0.00% 0.000% ×
53 0010150401 air inlet connection frame AD96NAHAEA 1 0.00% 0.000% ×
54 0010151128 cover plate 3 AD96NAHAEA 1 0.00% 0.000% ×
55 0010151132 fixed reinforced plate 2 AD96NAHAEA 1 0.00% 0.000% ×
77

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

82

81
86 85
84
83
1

76 2
80 3
79 4
75
74 5
77
67 78
87 6
73
7
8
9
10

11

20
12
14
23 18 13
15
24 16
21 19
17
72 22
25

34
35
43
37
44 38
68 36
39 40
67
66
65
64
45
41
46
70
71 42

69
88
26 47

56 48 49
27
28
50

52
54
51
29 57
32
30 59
31
60 58
33
53
61 62

63

55

78

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

No. in The
explod Spare parts Failure proportion of Remar
Spare parts description in english Model Qty
ed number rate the spare part k
view stock
1 0010150606 upper air outlet horizontal frame AP96NACAEA 1 0.00% 0.000% ×
2 0010250641 right air outlet frame AP96NACAEA 1 0.00% 0.000% ×
3 0010250379 upper fixing rubber of horizontal louver AP96NACAEA 2 0.00% 0.000% ×
4 0010250473 cushion for clip of air outlet grille AP96NACAEA 2 0.00% 0.000% ×
5 0010150604 lower air outlet horiontal frame AP96NACAEA 1 0.00% 0.000% ×
6 0010150415 right clip of horizontal louver AP96NACAEA 1 0.00% 0.000% ×
7 0010250367 horizontal louver AP96NACAEA 6 0.00% 0.000% ×
8 0010250368 connecting pole 1 AP96NACAEA 4 0.00% 0.000% ×
9 0010250369 connecting pole 2 AP96NACAEA 3 0.00% 0.000% ×
10 0010250481 lower fixing rubber of horizontal louver AP96NACAEA 2 0.00% 0.000% ×
11 0010250639 lower air outlet frame AP96NACAEA 1 0.00% 0.000% ×
12 0010250371 sleeve 1 AP96NACAEA 15 0.00% 0.000% ×
13 0010250372 sleeve 2 AP96NACAEA 13 0.00% 0.000% ×
14 0010250370 vertical louver AP96NACAEA 15 0.00% 0.000% ×
15 0010850634 lower air outlet horizontal frame assembly 2AP96NACAEA 1 0.00% 0.000% ×
16 0010250476 cushion 2 for fixing plate of air outlet grille AP96NACAEA 1 0.00% 0.000% ×
17 0010250373 sleeve 3 AP96NACAEA 13 0.00% 0.000% ×
18 0010250380 swing connecting pole 1 AP96NACAEA 1 0.00% 0.000% ×
19 0010250381 swing connecting pole 2 AP96NACAEA 1 0.00% 0.000% ×
20 0010250375 motor sleeve AP96NACAEA 1 0.00% 0.000% ×
21 0010850634 lower air outlet horizontal frame 2 AP96NACAEA 1 0.00% 0.000% ×
22 0010250477 cushion 3 for fixing plate of air outlet grille AP96NACAEA 1 0.00% 0.000% ×
23 0010150750 sleeve washer AP96NACAEA 13 0.00% 0.000% ×
24 001A3000016Asynchromotor AP96NACAEA 1 0.02% 0.024% *
25 0010200026 air ring AP96NACAEA 2 0.00% 0.000% ×
26 001A1301379 electric control box cover assembly AP96NACAEA 1 0.00% 0.000% ×
27 0010452039 indoor PCB AP96NACAEA 1 0.02% 0.024% *
28 001A1452909 rubber wiring hole AP96NACAEA 1 0.00% 0.000% ×
29 0010451262 transformer AP96NACAEA 1 0.01% 0.012% ×
30 0010451265 terminal block AP96NACAEA 1 0.00% 0.000% ×
31 001A01001024 electric control box assembly AP96NACAEA 1 0.00% 0.000% ×
32 0010451323 ambient temperature sensor AP96NACAEA 1 0.04% 0.048% *
33 0010452015 wires AP96NACAEA 1 0.00% 0.000% ×
34 0010850741 scroll case assembly AP96NACAEA 1 0.00% 0.000% ×
35 0010150924 fan washer AP96NACAEA 4 0.00% 0.000% ×
36 0010250579 fan AP96NACAEA 2 0.04% 0.048% *
37 0010250470 cushion 2 for evaporator fixing plate AP96NACAEA 1 0.00% 0.000% ×
38 0010150529 evaporator fixing plate 1 AP96NACAEA 1 0.00% 0.000% ×
39 0010250469 cushion 1 for evaporator fixing plate AP96NACAEA 1 0.00% 0.000% ×
40 0010250471 cushion 3 for evaporator fixing plate AP96NACAEA 1 0.00% 0.000% ×
41 0010150530 evaporator fixing plate 2 AP96NACAEA 1 0.00% 0.000% ×
42 0010450644 indoor coil temperature sensor AP96NACAEA 1 0.04% 0.048% *
43 0010150531 evaporator fixing plate 3 AP96NACAEA 1 0.00% 0.000% ×
44 0010150523 packaging fixing plate AP96NACAEA 2 0.00% 0.000% ×
45 0010852401 evaporator assembly AP96NACAEA 1 0.00% 0.000% ×
46 0010850740 top plate assembly AP96NACAEA 1 0.00% 0.000% ×
47 0010250442 cushion 1 of bottom plate AP96NACAEA 1 0.00% 0.000% ×
48 0010850629 back plate assembly AP96NACAEA 1 0.00% 0.000% ×
49 0010150417 air flow flap AP96NACAEA 1 0.00% 0.000% ×
50 0010150526 fixing clip of drain pan AP96NACAEA 1 0.00% 0.000% ×
51 0010250769 packaging cushion AP96NACAEA 3 0.00% 0.000% ×
79

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

52 0010250443 cushion 2 of bottom plate AP96NACAEA 1 0.00% 0.000% ×


53 0010850742 drainage pan assembly AP96NACAEA 1 0.00% 0.000% ×
54 0010250429 cushion 2 of right side plate AP96NACAEA 1 0.00% 0.000% ×
55 0010851511 right side plate AP96NACAEA 1 0.00% 0.000% ×
56 0010150527 fixing clip of scroll case AP96NACAEA 2 0.00% 0.000% ×
57 0010250446 fixing plate of scroll case AP96NACAEA 2 0.00% 0.000% ×
58 0010150528 wire-pressing plate AP96NACAEA 2 0.00% 0.000% ×
59 0010450787 indoor motor AP96NACAEA 2 0.04% 0.048% *
60 0010150751 washer of motor sleeve AP96NACAEA 1 0.00% 0.000% ×
61 001A1445087 fixing bracket AP96NACAEA 4 0.00% 0.000% ×
62 001A5002066 wooded screws AP96NACAEA 3 0.00% 0.000% ×
63 0010851508 bottom plate assembly AP96NACAEA 1 0.00% 0.000% ×
64 0010851510 left side plate assembly AP96NACAEA 1 0.00% 0.000% ×
65 0010250441 cushion 4 of left side plate AP96NACAEA 1 0.00% 0.000% ×
66 0010250439 cushion 2 of left side plate AP96NACAEA 1 0.00% 0.000% ×
67 0010250440 cushion 3 of left side plate AP96NACAEA 1 0.00% 0.000% ×
68 0010250438 cushion 1 of left side plate AP96NACAEA 1 0.00% 0.000% ×
69 0010250444 cushion 3 of back plate AP96NACAEA 1 0.00% 0.000% ×
70 0010250445 cushion 4 of back plate AP96NACAEA 1 0.00% 0.000% ×
71 0010150525 scroll case bracket AP96NACAEA 1 0.00% 0.000% ×
72 0010251682 filter AP96NACAEA 1 0.00% 0.000% ×
73 0010852371 air inlet grille AP96NACAEA 1 0.00% 0.000% ×
74 0010150753 magnetic fixing clip AP96NACAEA 2 0.00% 0.000% ×
75 001A0100075 lock AP96NACAEA 2 0.00% 0.000% ×
76 0010851509 front panel assembly AP96NACAEA 1 0.00% 0.000% ×
77 0010403556 control panel AP96NACAEA 1 0.02% 0.024% *
78 0010805699 display board AP96NACAEA 1
79 0010250472 cushion 1 for fixing clip of air outlet grille AP96NACAEA 2 0.00% 0.000% ×
80 0010250474 cushion 2 for fixing clip of air outlet grille AP96NACAEA 2 0.00% 0.000% ×
81 0010150414 left fixing clip of horizontal flap AP96NACAEA 1 0.00% 0.000% ×
82 0010250640 left air outlet frame AP96NACAEA 1 0.00% 0.000% ×
83 001A5313008 nut AP96NACAEA 1 0.00% 0.000% ×
84 001A5401032 washer M8 AP96NACAEA 1 0.00% 0.000% ×
85 0010250570 liquid inlet heat preservation sleeve AP96NACAEA 1 0.00% 0.000% ×
86 0010250571 liquid outlet heat preservation sleeve AP96NACAEA 1 0.00% 0.000% ×
87 001A5002116 screws(4*12BBTHC) AP96NACAEA 5 0.00% 0.000% ×
88 001A3600134 fan capacitor (8uF/450V) AP96NACAEA 2 0.02% 0.024% *

80

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
13. Performance curves
13.1 AD96NAHAEA
a. Cooling mode:
Temp. – capacity performance curves

35
20
cooling capacity(KW)

30 22
25
25
27
20 30
32
15
-7 5 15 25 35 43
outdoor DB(℃)

Temp. – EER performance curves

5
20
4 22
25
EER

3
27
2 30
32
1
-7 5 15 25 35 43
outdoor DB(℃)

b. Heating mode:
Temp. – capacity performance curves

45
16
40 18
capacity(KW)

35 20
22
30 24
25 26
28
20
-7 -5 0 6 10 15
outdoor DB(℃)

81

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
Temp. – COP performance curves

5
16
4
18
COP

3 20
22
2
24
1 26
-7 -5 0 6 10 15 28
outdoor DB (℃)

c . Air flow and static pressure curves


1.The digits in the circle stand for the air step of the fan speed control board.
2.The red real line shows the air flow and static pressure changing state at different air step in
high speed; the blue dashed line shows the air flow and static pressure changing state at
different air step in low speed.

H ig h
Low
200

8 7
6 5
4
3

150

3 8

7
100
6

50

0
55 60 65 70 75 80 8586
h igh a ir flo w (m /m in)
3
lo w
lim it lim it

82

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
13.2 AP96NACAEA
Correction factor according to the indoor/outdoor temperature:

cooling/heating capacity correction factor following the temp.

cooling

heating

applicable range
temp(℃D.B)
cooling mode
outdoor DB

indoor WB temp.(℃ D.B)


heating mode

temp.(℃D.B)
indoor DB

outdoor WB temp (℃D.B)

a. Correction factor due to the piping length


The correction factor in the below chart are measured in the case that the height drop between
indoor and outdoor is zero.

Piping length
5 10 15 20 25 30 35 40 45 50
(m)

heating 1.0 1.0 1.0 1.0 1.0 0.995 0.995 0.99 0.99 0.985

cooling 1.0 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91

Note: Calculating method of piping length


83

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
Equivalent length=actual length+(0.2×curling quantity)

b. Correction factor due to the height drop between I.U&O.U

If in cooling mode, the outdoor unit is lower, while in heating mode, the outdoor unit is upper, only in

this case, in addition that the above correction factor due to the piping length is taken into

consideration, the following factor should also be taken into consideration:

Height drop 5m 10m 15m 20m 25m 30m

Correction factor 0.01 0.02 0.03 0.04 0.05 0.06

c. Correction factor due to the air flow

High speed: 1.0; Med speed: 0.95; Low speed: 0.9

84

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
14. Noise level
The cabinet unit is identical with KFR-250LW, which is sold in China, so herein we will show out the
noise level of KFR-250LW.

85

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

86

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

92

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
The noise level of AD96NAHBEA will be supplied when after the noise testing.

88

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
15. Air velocity and distribution

89

Downloaded from AC-Manual.com Manuals


Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA

Sincere Forever

Haier Group