Ic5 Urun Katalogu Catalog
Ic5 Urun Katalogu Catalog
Ic5 Urun Katalogu Catalog
com
--..----
--··
.,_,
----· --- -..-·
·---- --
----·
r....... o.drie---.
“ Global standard iC5,
serves a wide variety of applications
to meet the majority of user needs. ”
● Modbus communication (Option)
● PID control
04 06 08 09 16
Features Specifications Terminal configuration Program Parameters Checking & Troubleshooting
“ Compact iC5,
is the best for a small and cost
effective configuration”
Features
Auto tuning
The auto tuning algorithm in the iC5 sets the motor factors automatically that brings the
traditional commissioning difficulties mainly in low speed by the load variation and the low
torque generation to a settlement.
characteristic
4
Models
220V, single
Applicable motor
phase
Input voltage
LS Starvert drive
Motor rating
(004 : 0.4kW ~ 022 : 2.2kW)
Name of Series
5
Specifications
▒ Control
Control method V/F control, Sensorless vector control
Frequency setting resolution •Digital reference : 0.01Hz •Analog reference : 0.06Hz/60Hz
Frequency setting accuracy •Digital : 0.01% of Maximum output frequency •Analog : 0.1% of Maximum output frequency
V/F ratio Linear, Squar pattern, User V/F
Overload capacity 1min. at 150%, 30sec. at 200% ( with inverse characteristic )
Torque boost Manual( 0 to 15% adjustable ), Auto
▒ Operation
Input signal Operator control Keypad / Terminal / Communications
Frequency setting •Analog : 0~10V/4~20mA •Digital : Keypad •Communication : RS485
Start signal Forward / Reverse
Multi-step Setting up to 8 speeds ( use multi-function terminal )
Multi-step accel 0.1~6000 sec. Max. 8 types available by multi-function terminal
/decel time Selectable accel/decel patterns : Linear, U and S
Emergency stop Interrupting the output of the drive
Jog Jog operation
Fault reset Reset the fault when protective function is active
Output signal Operation status & Frequency detection, Overload alarm, Stalling, Overvoltage, Undervoltage,
Fault output Drive overheating, Run, Stop, Constant speed, Speed searching,
Fault output ( Relay and Open collector output )
Indicator Choose one from output frequency, current, voltage and DC voltage.(Output voltage : 0~10V )
Operation DC braking, Frequency limit, Frequency jump, Second function,
function Slip compensation, Reversing prevention, Auto restart, PID control
▒ Protection functions
Drive trip Overvoltage, Undervoltage, Overcurrent, Drive overtemperature, Motor overtemperature, I/O phase loss, I/O mis-wiring,
Overload , External device fault 1.2, Loss of speed command, Hardware fault, Communication error, CPU error
Drive alarm Stall prevention, Overload alarm
Momentary •Less than 15 msec : keeping operation
power less •More than 15 msec : auto restart available
▒ Display keypad
Operation information Output frequency, current and voltage, Set frequency value, Operation speed, DC voltage
Trip information Display the trip cause when the protection function activates. Recent 5 faults records stored
▒ Environment
Operating ambient temp. -10℃ ~ 50℃
Storage temperature -20℃ ~ 65℃
Humidity 90%Rh max.(non condensing)
Altitude & Vibration 1000m max, 5.9m/sec2(0.6g) max.
Atmosphere
No corrosive gas, flammable gas, oil mist or dust
Pressure 70~106k Pa
6
Wiring
P P1 N
MCCB
AC input L1 U
Single phase
200 ~ 230V L2 V IM
G W
KNOB
Ground
Multi-function input terminals, P1 to P5
Analog output
P1 (factory set : Forward) (0~10V)
CM Common
7
Terminal configuration
L1 L2 P P1 N U V W G
Terminal Signal Description
L1, L2 AC line input Single phase AC line input
U, V, W Drive output 3 phase output terminals to motor
P, P1 DC reactor Connecting DC reactor
G Ground Chassis ground
P4 P5 VR V1 CM I AM
Keypad
8
Program parameters
▒ Parameter group
There are 4 parameter groups to set parameters properly for the operation.
Group Description
Drive group Basic parameters such as Command frequency, Accel/Decel time, etc.
Function 1 group Basic functional parameters such as Max. frequency, Torque boost, etc.
Function 2 group Application parameters such as Frequency jump, Max./Min. of limit of frequency, etc.
Input/Output group Parameters to construct the sequence such as Multi-function terminal setting, Auto operation, etc.
● Shifting between groups is possible only in the first code of each group.
Shift by using Right shift key (▶) Shift by using Left shift key (◀)
(1) (1)
(1) The value of the Command frequency will be displayed in the first code of the Drive group.
It will show the value set by the operator. The factory set value is 0.0.
9
Program parameters
Note : (1) The LCD on the keypad of Drive iC5 displays only 3 digits.
Use the shift keys (◀ ▶) to monitor and set the parameters.
(2) To cancel the parameter setting press the shift keys
(◀ or ▶) while 30.0 is flickering in the procedure no. 8 .
10
Program parameters descriptions
11
Program parameters descriptions
12
Program parameters descriptions
13
Program parameters descriptions
14
Program parameters descriptions
Peripheral Device
MCCB (Molded Case Circuit Breaker) and MC (Magnetic Contactor)
Capacity Circuit Breaker (MCCB) Leakage Breaker (ELCB) Magnetic Contactor (MC)
Voltage
[kW] Model Rated Current[A] Model Rated Current[A] Model Rated Current[A] Model Rated Current[A]
0.4 0.4 5 5 MC-6a 9
0.75 0.75 10 10 MC-9a, MC-9b 11
1-Phase 200V ABS33c UTE100 EBS33c
1.5 1.5 15 15 MC-18a, MC-18b 18
2.2 2.2 20 20 MC-22b 22
0.4 0.4 15 15 MC-6a 9
3-Phase 200V ABS33c UTE100 EBS33c
0.75 0.75 15 15 MC-9a, MC-9b 11
15
Checking & Troubleshooting
Warning :
If protection function activates due to error/fault in the drive, corresponding
alarm is displayed on the keypad as shown below.
Correct the error/fault before restarting or it may decrease the driveʼs life
expectancy.
DC link condenser overload If the DC condenser of Drive is in need of replacement the drive output is interrupted.
One or more of output line U, V and W lost.
Output phase loss
The drive output is interrupted.
The drive main voltage has been risen above the permissible limit 400V.
Overvoltage
Check if deceleration time has been set too short or line input voltage is too high.
The drive output is interrupted according to the set time-inverse curve to prevent the
Electronic thermal
overtemperature of the motor due to overloads.
Error has been occurred on the storing of the changed parameters.
Parameter store error
It is displayed when power is on.
It is displayed in case of software error.
Hardware error It is not possible to reset by STOP/RST key on the keypad or reset terminals.
Open the drive power and make sure the keypad power is off and close the power again.
Communication error between controller and keypad.
Communication error It is not possible to reset by STOP/RST key on the keypad or reset terminals.
Open the drive power and make sure the keypad power is off and close the power again.
Coolingfan error Error has been occurred on the coolingfan.
The drive output is interrupted in the case that BX terminal is ON.
Output instant interrupting
Warning : To restart the drive make BX terminal OFF during the FX /RX is ON.
A contact fault signal input If I20/21/22/23/24 set to 18 is ON, the drive output is interrupted.
B contact fault signal input If I20/21/22/23/24 set to 19 is ON, the drive output is interrupted.
If signal input is failed for the driving by using analog input or option(RS485), try to drive according to
Frequency command loss
the setting at I62.
16
Checking & Troubleshooting
● Accel/Decel time is not enough for the load inertia ▶ Replace the drive with a higher rating
Overcurrent (GD2) Increase the Accel/Decel time ▶ Operate after the motor stops or use speed search(H22) in FU2
● The load is greater than the rating of the drive. in the output terminals.
● Drive output is assigned during the free run of the motor. ▶ Verify the output wiring
● The motor brake operates too fast. ▶ Verify the mechanical brake.
● Ground fault at the load side of the drive. ▶ Check to see if there is something wrong with output wiring.
Ground fault ● Insulation of the motor is broken. ▶ Replace a motor.
● The load is greater than the rating of the drive. ▶ Increase the ratings of a motor and an drive.
Drive overload ● Power rating is set to the lower value than the load ▶ Check to see if the setting is correct.
● Torque boost is too great. ▶ Reduce the torque boost.
Overload trip
▶ Check to see if there is any alien substance in the ventilation
● Fault in the cooling system.
system.
● The cooling fan is used beyond the life expectancy.
Cooling fan overheat ▶ Replace the cooling fan.
● High ambient temperature
▶ Keep the ambient temperature below 40°….
● Decel time is not enough for the load inertia(GD2) ▶ Increase the Decel time
● There is a survived load in the load side. ▶ Uase DB unit.
Overvoltage ▶ Verify the power voltage.
● Higher voltage than rating is supplied.
● Frequency command loss at terminals V1 and I ▶ Verify the wiring connected to V1 and I terminals.
Frequency command loss
Communication error
17
Tips on Installation
Warning :
Carefully read the instruction for installation and wiring of drives and relevant
devices. Normal operation is impossible in case of the improper system design
and wiring. These can shorten the life of the drive and damage it at the worst.
INDUCTORS FOR
VARIABLE SPEED DRIVES
18
•For your safety, please read user's manual thoroughly before operating.
•Contact the nearest authorized service facility for examination, repair, or adjustment.
•Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions •Any maintenance and inspection shall be performed by the personnel having expertise concerned.