66 kV 33 kV DC

Sl No RED 670 (IC & Tr, REL 615 (IC RED 615 (TSS REF 615 (Tr. OG) SEPCOS
OG) & Tr. OG) IC & OG)
1 Diff. Prot OC Diff. Prot OC DDL + Delta I
2 Residual EF Earth fault - EF DDL + Delta I
3 UV - - Stand by earth fault I max +
4 Tank earth fault - - - I max ++
5 OV - - - I max -
6 - - - - I max --
7 - - - - Thermal
8 - - - - U max

Sl No SWG CT ratio PT ratio


1 66 kV Tariff As of now 25/1 66000/110 V
2 66 kV IC 400/1 66000/110 V
3 33 kV IC 600/1 33000/110 V
4 33 kV OG from RS200/1 33000/110 V
5 Traction Transf. 50/1 33000/110 V
6 Aux. Transf. 15/1 33000/110 V
7 TSS IC & OG 200/1 33000/110 V (Bus PT)
8 HSCB - Volatge VM 10 1500/5 V (Position A)
9 HSCB - Current MIU 10 10000 A / 150 mV / 20 mA (Position 7)

Avg Energy consumption /


Sl No Station
Day (units-kWh)
1 RSS 32000
ASS TSS
2 PYID 865 -
3 PEYA 575 2865
4 YPI 680 -
5 YPM 999 2800
6 SSFY 662 -
7 MHLI 629 2700
8 RJNR 1045 -
9 KVPR 681 2600
10 SPRU 643 -
11 SPGD 821 2100
12 JLHL 710 3200
13 DSH 723 -
14 NGSA 863 2200
15 PNYD 2500 1800
Reach-3, 3A & 3B Relay Setting
OC high set OC low set OC low set EF high set
OC high set
(PHHP) TMS (PHLP) (PHLP) (EFHP)
SL no Feeder/incomer discription CT ratio (PHHP) PMS ms PMS TMS PMS
Curve -DT Curve -DT Curve -NI Curve -NI Curve -DT
1 2850 KVA TRF 50/1 1.52 50 (0.05) 1.1 0.05 1
2 2000kva TRF 50/1 4 50 (0.05) 0.7 0.09 0.7
3 500KVA TRF 15/1 0.87 50 (0.05) 1 0.11 1.71
4 200KVA TRF 15/1 4.25 50 (0.05) 0.16 0.11 0.14
5 I/c to 33KV Depot TSS bus 200/1 1 50 (0.05) — — 0.5
6 TSS TIE FEEDERS 200/1 1 200 (0.2) — — 0.5
7 O/G from rss to TSS bus 200/1 1 350(0.35) — — 0.5
8 O/G from rss to ASS Bus 200/1 3.45 200(0.2) 1 0.08 0.5
O/G to from TSS bus to
9 200/1 1 200(0.2) — — 0.5
Depot ASS
O/G from 33KV rss BUS
10 200/1 1 200(0.2) — — 0.5
toDepot TSS
O/G from 33KV rss BUS
11 toDepot ASS 200/1 1 350(0.35) — — 0.5
Incomer 33KV rss from 25
12 600/1 — — 0.8 0.15 0.73
MVA TRF
13 33 KV RSS Buscupler 600/1 — — 0.8 0.15 0.73
14 RSS TRF 66KV side (REF615) 400/1 5.3 50 (0.05) 0.6 0.2 1

SEF TMS in
SL no Feeder/incomer discription Curve type SEF PSM
ms
1 500KVA TRF SEF settings DT 0.93 1000ms
2 2000KVA TRF SEF settings DT 3.7 1000ms

415V AC LT side settings


Long inverse Short inverse Ground fault
SL Transformer
PSM TMS PSM TMS PSM TMS
1 2000KVA 1 2.5 6 0.1 0.2 0.1
2 500KVA 1 2.5 6 0.1 0.2 0.1
3 200KVA 1 2.5 6 0.1 0.2 0.1

TSS RED615 differential settings Depot ASS RET615 general par


Sl no Description Values Sl No Description
1 High operated value 400% 1 operation
2 High oprated Mult 1 2 CT connection type
3 Low operated value 15% 3 Winding 1 Type
4 End section 1 125% 4 Winding 2 Type
5 Slope section 2 40% 5 Clock Number
6 End section 2 300% 6 Zro A Elimination
7 slpoe section 3 80% 7 Min Winding Tap
8 operate delay time 45 8 Max winding tap
9 operating curve DT 9 Tap Nominal
10 Time multiplier 1 10 Tapped winding
11 Start value 2.H 15% 11 step of tap
12 CT connection Type Type1 12 CT ratio cor wnd 1
13 Restraint mode Hormonica 2 13 CT ratio Cor Wnd2

Depot TSS RET615 transformer differential


settings
SL Discription Values
1 High operated value 650%
2 Enable high set 1
3 Low operated value 20%
4 Slope section 2 30%
5 End section 2 150%
6 Restraint Mode -1
7 Hormonic Deblock 2 1
8 Start value 2.H 12
9 Start value 5.H 25
10 Stop value 5.H 35
11 Hormonics deblock 5 0
EF high set
EF Low set EF Low set
(EFHP) TMS
(EFLP) TMS (EFLP) TMS
ms
Curve -DT Curve -NI Curve -NI
50(0.05) 0.2 0.05
50(0.05) 0.1 0.05
50(0.05) 0.08 0.05
50(0.05) 0.05 0.05
60(0.06) 0.1 0.05
200 (0.2) 0.1 0.12
350(0.35) 0.1 0.21
200 (0.2) 0.1 0.12
200 (0.2) 0.1 0.11
200 (0.2) 0.1 0.11

350(0.35) 0.1 0.17

500(0.5) 0.1 0.2


500(0.5) 0.1 0.2
50(0.05) 0.05 0.05

15 general par
Values
on
Type-1
3=D
2=yn
11
Windg-2
1
5
3
Not in use
2.50%
1.43
1.08