Service Bulletin: Caution
Service Bulletin: Caution
Service Bulletin: Caution
TOPIC: Accessories
IDENT NO: 1-2620F
SUPERSEDES: 1-2620E
DATE: November 15, 2007
SUBJECT: Engine Protection Shutdown
MODELS AFFECTED: All Waukesha Engines
The tables in this Service Bulletin list “Alarm” and Alarm and shutdown values are based on using dry
“Shutdown” setpoints by engine series for various natural gas of 900 BTU/cu.ft. (35.38 MJ/m3
engine operation parameters. These values can be [25,V(0;101.325)]) Saturated Lower Heating Value
used as a guide when designing engine protection or (SLHV) as fuel. Refer to the “Gaseous Fuel Specifica-
monitoring systems. tion for Waukesha Engines” standard sheet, S-7884-7
or latest version, and the “Lubricating Oil Recommen-
The “alarm” values shown are suggested values; they
dations for Waukesha Engines” standard sheet,
can be changed to suit a specific application or mea-
S-1015-29 or latest version, for typical changes to
surement device. By using controls that simulta-
operating temperatures for jacket water and lube oil
neously shut off the fuel supply and ignition system
when running on landfill or digester gas fuels.
upon reaching a “shutdown” value, the potential for
engine damage is reduced. Refer to the most recent version of the Gas Engine
Alarm and shutdown Price Book to determine which shutdown devices are
CAUTION values indicate devia- included as standard equipment with any specific
engine model.
tion from designed operation and are not meant
for continuous engine service. Engine and control
systems must be designed to and operated at nor-
mal values. Disregarding this information could
result in product damage and/or personal injury.
WAUKESHA ENGINE
DRESSER, INC.
Page 1 of 8
WAUKESHA, WI 53188-4999
Service Bulletin No. 1-2620F
12V/18V220GL AT25GL/AT27GL
JACKET WATER (HT) OUTLET TEMPERATURE JACKET WATER OUTLET TEMPERATURE
Normal 100° C (212° F) Standard Cooling System
Alarm 103° C (217° F) 1 180° F (82° C) for continuous rating
Normal
200° F (93° C) for intermittent rating
Shutdown 108° C (226° F) 1
Alarm 10° F (5.5° C) above
LUBE OIL HEADER TEMPERATURE normal/design temperature
Normal 75° C (167° F) 20° F (11° C) above
Shutdown
normal/design temperature
Alarm 77° C (171° F)
Elevated Temperature Solid Water Cooling System
Shutdown 80° C (176° F)
Normal 210° – 250° F (99° – 121° C) solid water
LUBE OIL HEADER PRESSURE
Rated Speed Alarm 5° F (3° C) above normal/design temperature1
Idle (1200 or 1500 rpm)
Shutdown 10° F (5.5° C) above normal/design temperature1
Normal 4.2 bar (61 psi) 5.3 bar (77 psi)
LUBE OIL HEADER TEMPERATURE
Alarm 2.3 bar (33 psi)1 4.0 bar (58 psi)1 Normal 172° F (78° C)
Shutdown 2.0 bar (29 psi)1 3.5 bar (51 psi)1 Alarm 187° F (86° C)
INTAKE MANIFOLD TEMPERATURE Shutdown 197° F (92° C)
Normal Up to 10° C (9° F) above design intercooler LUBE OIL HEADER PRESSURE
water inlet temperature.
Normal 60 – 65 psi (415 – 450 kPa)
10° C (18° F) above design intercooler
Alarm
water inlet temperature1. Alarm 50 psi (345 kPa)3
20° C (36° F) above design intercooler Shutdown 45 psi (310 kPa)3
Shutdown
water inlet temperature1.
INTAKE MANIFOLD TEMPERATURE – AT25GL MODEL
INTAKE MANIFOLD PRESSURE
Normal Up to 10° F (5.5° C) above design
Contact Waukesha Sales Engineering intercooler water inlet temperature
GAS PRESSURE AT GAS TRAIN INLET 20° F (11° C) above design intercooler water inlet
Alarm
Normal 4 – 6 bar (58 – 87 psi) temperature
30° F (17° C) above design intercooler water inlet
Alarm 6.5 bar (94 psi)2 Shutdown
temperature
OVERSPEED
INTAKE MANIFOLD TEMPERATURE – AT27GL MODEL
Shutdown Not to exceed 7% over governed speed.
Normal Up to 10° F (5.5° C) above design intercooler
FUEL PRESSURE water inlet temperature
Alarm
The minimum fuel pressure at the regulator
Alarm 15° F (11° C) above design intercooler water inlet
(from Tech Data Book) temperature
Shutdown 85% of the alarm value
Shutdown 20° F (17° C) above design intercooler water inlet
temperature
NOTES: INTAKE MANIFOLD PRESSURE
1Alarm and shutdown functionality provided by ESM. Contact Waukesha Sales Engineering
2Alarm functionality provided by Auxiliary Systems Interface. MAIN BEARING TEMPERATURE
Shutdown 250° F (121° C)
OVERSPEED
Shutdown Not to exceed 10% over governed speed.
FUEL PRESSURE
The minimum fuel pressure at the
Alarm regulator (from Tech Data Book)
Shutdown 85% of the alarm value
NOTES:
1
Waukesha Power Systems Engomatic® Control Model 1105,
1105A, or equivalent pressure/temperature shutdown system is
recommended when jacket water temperature exceeds 210° F
(99°C).
2
Do not revise any values on this page without revising the same
values on the “AT General Operating Limits” and “Diagram Tempera-
ture/Pressure Test Points and Pump Settings” S-sheets for the 8L,
12V, and/or 16VATGL engines.
3
Waukesha Power Systems Control is required to have an 8 second
delay after engine start.
WAUKESHA ENGINE
DRESSER, INC.
Page 3 of 8
WAUKESHA, WI 53188-4999
Service Bulletin No. 1-2620F
16V150LTD F1197
JACKET WATER (HT) OUTLET TEMPERATURE JACKET WATER OUTLET TEMPERATURE
Normal 99° C (210° F) Normal 180° F (82° C)
Alarm 105° C (220° F) 1 Alarm 200° F (93° C)
Shutdown 110° C (230° F) 1 Shutdown 210° F (99° C)
LUBE OIL HEADER TEMPERATURE LUBE OIL HEADER TEMPERATURE
WAUKESHA ENGINE
DRESSER, INC.
Page 5 of 8
WAUKESHA, WI 53188-4999
Service Bulletin No. 1-2620F
VSG
JACKET WATER OUTLET TEMPERATURE
Normal 180° F (82° C)
Alarm 200° F (93° C)
Shutdown 210° F (99° C)
LUBE OIL HEADER TEMPERATURE
with a Jacket Water Temperature of 180° F (82° C)
F11G Model
Normal 205° F (96° C)
Alarm 215° F (102° C)
Shutdown 225° F (107° C)
F11GSI Model
Normal 190° F (89° C)
Alarm 200° F (93° C)
Shutdown 210° F (99° C)
LUBE OIL HEADER PRESSURE
Normal 65 – 87 psi (448 – 600 kPa)
Alarm 40 psi (276 kPa)
Shutdown 30 psi (207 kPa)
INTAKE MANIFOLD TEMPERATURE (GSI)
WAUKESHA ENGINE
DRESSER, INC.
Page 7 of 8
WAUKESHA, WI 53188-4999
Service Bulletin No. 1-2620F
NEWAGE GENERATORS
GENERATOR WINDING
INSULATION CLASS WARNING SHUTDOWN
°F °C °F °C
A 194 90 230 110
E 230 110 266 130
B 248 120 284 140
F 284 140 320 160
H 338 170 374 190
COMMENTS: These values are recommended by the British Standard BS4999 Part 72, which Newage Int. follow.