GW BT Datasheet-En
GW BT Datasheet-En
GW BT Datasheet-En
Max. AC Current from Utility Grid (A) 15.2 18.2 22.7 22.7
Output Power Factor ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Output THDi (@Nominal Output) <3%
AC Output Data Max. Output Apparent Power (VA) 5000 6000 8000 10000
(Back-up)
Peak Output Apparent Power (VA)*2 10000, 60sec 12000, 60sec 15000, 60sec 15000, 60sec
Max. Ouput Current (A) 8.5 10.5 13.5 16.5
Nominal Output Voltage (V) 400/380
Nominal Ouput Frequency (Hz) 50/60
Output THDv (@Linear Load) <3%
Efficiency Max. Battery to Load Efficiency 97.6%
Max. Charge Efficiency 97.6%
Protection Anti-Islanding Protection Integrated
Insulation Resistor Detection Integrated
Residual Current Monitoring Unit Integrated
Output Over Current Protection Integrated
Output Short Protection Integrated
Battery Input Reverse Polarity Protection Integrated
Output Over Voltage Protection Integrated
General Data Operating Temperature Range (°C) -35~60
Relative Humidity 0~95%
Operating Altitude (m) ≤4000
Cooling Nature Convection
Noise (dB) <30
User Interface LED & APP
Communication with BMS*3 RS485; CAN
Communication with Meter RS485
Communication with EMS RS485 (Insulated)
Communicaiton with Portal Wi-Fi; LAN
Weight (kg) 21
Size (Width*Height*Depth mm) 415*516*180
Mounting Wall Bracket
Protection Degree IP66
Standby Self-Consumption (W)*4 <15
Topology Battery Non-Isolation