INSTRUCTION MANUAL
DC Reactor
FR-HEL-C75K to C132K, C185K, C220K, C280K
Thank you for choosing this Mitsubishi Inverter option.
This instruction manual gives handling information and precautions for use of this equipment.
Incorrect handling might cause an unexpected fault. Before using the equipment, please read
this manual carefully to use the equipment to its optimum.
Please forward this instruction manual to the end user.
Note that even the CAUTION level may lead to a serious consequence according to conditions.
Please follow the instructions of both levels because they are important to personnel safety.
3. Injury Prevention
SAFETY INSTRUCTIONS
1. Electric Shock Prevention
CAUTION
Apply only the voltage specified in the
WARNING instruction manual to each terminal.
Otherwise, burst, damage, etc. may occur.
Any person who is involved in the wiring Ensure that the cables are connected to
or inspection of this equipment should be the correct terminals. Otherwise, burst,
fully competent to do the work. damage, etc. may occur.
Always install the inverter before wiring.
Otherwise, you may get an electric shock Always make sure that polarity is correct
or be injured. to prevent damage, etc. Otherwise, burst,
Do not touch the option with wet hands. damage may occur.
You may get an electric shock. While power is on or for some time after
Do not subject the cables to scratches, power-off, do not touch the option as it is
excessive stress, heavy loads or pinching. hot. Otherwise, you may get burnt.
Otherwise you may get an electric shock.
2. Fire Prevention
CAUTION
Mount the option to unflammable material.
Mounting it to or near combustible
material can cause a fire.
A-1
4. Additional Instructions 2) Trial run
Also note the following points to prevent an
accidental failure, injury, electric shock, etc. CAUTION
Assumes that incorrect handling may cause
an accidental failure, injury, electric shock, Before starting operation, confirm and
etc. adjust the parameters. A failure to do so
may cause some machines to make
1) Transportation and installation unexpected motions.
CAUTION 3) Operation
A-2
Contents
1 Product Checking............................................................................ 2
2 Installation ....................................................................................... 2
3 Wiring ............................................................................................... 3
5 Specifications .................................................................................. 5
APPENDIX.............................................................................................. 8
1
Product Checking
1 Product Checking
(1) Unpack the option unit, and ensure that the product received is as you
ordered and it is intact.
ᾜᾘᾣᾢᾤᾑᾘ
ᾜᾘᾣᾢᾤᾑᾘᾢᾗᾘ
ᾔᾛᾔᾒᾣᾡᾘᾒ
ᾔᾛᾔᾒ
ᾗᾘ DC REACTOR
MODEL
FR-HEL-C K XXXXXXXXXXX
SERIAL
MITSUBISHI ELECTRIC CORPORATION
FR-HEL- C K
Applied motor capacity (kW)
Symbol Applied Power Supply Voltage
C 600V class
(2) Make sure that the package includes all accessories.
DC reactor
(FR-HEL-C) ................... 1
2 Installation
(1) Install the reactor horizontally according to the environment conditions
specified on page 5. Installing the reactor in an unspecified direction will
damage the rector.
(2) Take full caution not to make the surrounding air temperature higher than
the permissible value (-10°C to +50°C). In addition, as the reactor itself
generates heat, leave sufficient clearance around it. (Independent of the
installation direction of the reactor, 10 cm or more for the above and
ENGLISH
below, 5 cm or more for the right and left)
10cm or
5cm or more 5cm or
more more
2
Wiring
3 Wiring
(1) When using the inverter equipped with a jumper across terminals P1 and
P, remove the jumper and connect the reactor across terminals P1 and
P.
Minimize the connection cable between the reactor and inverter so that the
length is within 5m. (For the size of the cable, refer to page 4)
When using the inverter equipped with a jumper across terminals P1 and
P, remove the jumper. Otherwise, the reactor will not exhibit its
performance.
FR-HEL-C
P1 P
When using the inverter equipped with
a jumper across terminals P1 and P,
remove the jumper. The connection cable
should be 5m maximum.
MCCB MC
P1 P/+ N/- Motor
R/L1 U
3-phase AC
S/L2 V M
power supply
T/L3 W
Inverter
(2) Make selection according to the applied motor capacity. (When the
inverter capacity is larger than the motor capacity, make selection
according to the motor capacity.)
(3) Securely earth (ground) the reactor using the earth (ground) terminal.
CAUTION
1. Do not perform wiring while power is on and the inverter is
running.
2. Any person who is involved in the wiring of this equipment
should be fully competent to do the work.
3. Since high-voltage is applied to the inverter terminals P1, P and
N, fully make sure that the input power is off and the voltage
across terminals P and N is not exceeding 50VDC before
performing wiring.
4. Provide isolation treatment to avoid contact of terminals.
3
Cable Size and Crimping Terminal
ENGLISH
4
Specifications
5 Specifications
Power supply power factor approx. 93%(94.4%)
Power factor improving effect *1
(at 100% load)
Power specifications Three-phase 525 to 600VAC 60Hz
Surrounding air
temperature -10°C to + 50°C (non-freezing)
Environment
P1 P
320±10
295
E
120 4-installation hole
140±2 (for M6 screw) Within 185
Earth (ground) terminal
(for M6 screw)
5
Outline Dimension Drawings
FR-HEL-C90K to C132K
Rating plate
2-terminal
(for φ bolt)
P1 P P1, P
H 10
H1
W1 4-installation hole
W 2 (for S screw) Within D
Earth (ground) terminal
(for S1 screw)
Motor Mass
Model capacity W W1 H H1 D S S1 (kg)
FR-HEL-C90K 90kW 20
150 130 340 310 190 M6 M10
FR-HEL-C110K 110kW M6 23
FR-HEL-C132K 132kW 175 150 405 370 195 M8 M12 24
Unit (mm)
ENGLISH
6
Outline Dimension Drawings
P1 P1
H 10
H1
P
P
W1 4-installation hole
W 2 (for S screw) Within D
Earth (ground) terminal
(for S1 screw)
7
APPENDIX
APPENDIX
Appendix 1 Applicable inverters
The FR-HEL-C series are a UL Listed accessory for use only with the
following UL listed inverter models:
• 600V class
DC reactor model Applicable inverter models
FR-A860-01080, 01440, 01670
FR-HEL-C75K FR-F860-01080, 01440, 01670
FR-AF860-01080, 01440, 01670
FR-A860-01440, 01670, 02430
FR-HEL-C90K FR-F860-01440, 01670, 02430
FR-AF860-01440, 01670, 02430
FR-A860-01670, 02430, 02890
FR-HEL-C110K FR-F860-01670, 02430, 02890
FR-AF860-01670, 02430, 02890
FR-A860-02430, 02890
FR-HEL-C132K FR-F860-02430, 02890
FR-AF860-02430, 02890
FR-A860-03360, 04420
FR-HEL-C185K FR-F860-03360, 04420
FR-AF860-03360, 04420
FR-A860-03360, 04420
FR-HEL-C220K FR-F860-03360, 04420
FR-AF860-03360, 04420
FR-A860-04420
FR-HEL-C280K FR-F860-04420
FR-AF860-04420
* For the FR-A860-01440 or higher inverters and the FR-F860-01440 or higher inverters and the
FR-AF860-01440 or higher inverters, or whenever a 75 kW or higher motor is used, always
connect the FR-HEL-C according to the combination table.
ENGLISH
8
APPENDIX
9
MEMO
10
MEMO
11
REVISIONS
*The manual number is given on the bottom left of the back cover.
Print Date *Manual Number Revision
Feb. 2015 IB(NA)-0600587ENG-A First edition
Oct. 2016 IB(NA)-0600587ENG-B Addition
• Compatibility with the FR-F860 series
and the FR-AF860 series
12