Emotron Fdu2 0 - Manual - 01 5325 01r5.en
Emotron Fdu2 0 - Manual - 01 5325 01r5.en
Emotron Fdu2 0 - Manual - 01 5325 01r5.en
0
AC drive
Instruction manual
English
Valid from software version 4.42
Emotron FDU 2.0
INSTRUCTION MANUAL - ENGLISH
WARNING!
Always switch off the mains voltage Residual current device (RCD)
before opening the AC drive and wait compatibility
at least 7 minutes to allow the
capacitors to discharge. This product cause a DC current in the protective
conductor. Where a residual current device (RCD) is used
for protection in case of direct or indirect contact, only a
Always take adequate precautions before opening the AC Type B RCD is allowed on the supply side of this product.
drive. Although the connections for the control signals and Use RCD of 300 mA minimum.
the switches are isolated from the main voltage, do not
touch the control board when the AC drive is switched on.
EMC Regulations
In order to comply with the EMC Directive, it is absolutely
Incorrect connection necessary to follow the installation instructions. All
The AC drive is not protected against incorrect connection installation descriptions in this manual follow the EMC
of the mains voltage, and in particular against connection of Directive.
the mains voltage to the motor outlets U, V and W. The AC
drive can be damaged in this way. Risk for personal injury.
Transport
To avoid damage, keep the AC drive in its original
packaging during transport. This packaging is specially
designed to absorb shocks during transport.
IT Mains supply
The AC drives can be modified for an IT mains supply,
(non-earthed neutral), please contact your supplier for
details.
Alarms
Never disregard an alarm. Always check and remedy the
cause of an alarm.
Position Position
Configuration
for 002-074 for 090-3K0
FDU
1 1 AC drive type
48=480 V mains
2 2 Supply voltage 52=525 V mains
69=690 V mains
-002=2.0 A
3 3 Rated current (A) continuous -
-3K0=3000 A
20=IP20 - Intended for mounting inside a cabinet
4 4 Protection class 21=IP21 - Intended for wall-mounting
54=IP54 - Intended for wall-mounting
–=Blank panel
C=2-line Control panel, standard IP2Y
5 5 Control panel
D=4-line Control panel, standard IP2X/54
E=4-line Control panel with Bluetooth (option IP2X/54)
E=Standard EMC (Category C3)
6 6 EMC option F=Extended EMC (Category C2)
I=IT-Net
–=No chopper
7 7 Brake chopper option B=Chopper built in
D=DC+/- interface
–=No SBS
8 8 Stand-by power supply option
S=SBS included
Safe stop option –=No safe stop
- 9
(Only valid for 090-3k0) T=Safe stop incl.
9 10 Brand label A=Standard
10 - Painted AC drive A=Standard paint
–=Standard, not coated boards IP54
11 11 Coated boards, option
V=Coated boards, option IP54 (standard IP2X)
12 12 Option position 1 N=No option
C=Crane I/O (max. 1)
13 13 Option position 2
E=Encoder (max. 1)
P=PTC/PT100 (max. 2)
14 14 Option position 3 I=Extended I/O (max. 3)
S=Safe Stop (only 002-105, IP2X/54 size B-D2 (69)) (max. 1)
N= No option
D= DeviceNet
P= Profibus
S= RS232/485
M= Modbus/TCP
15 15 Option position, communication E= EtherCAT
F= Modbus/TCP 2-port, M12
A= Profinet IO 1-port
B= Profinet IO 2-port
G= EtherNet/IP 2-port
C= CANopen
A= Standard software, Language set 1
16 16 Software type I = Std sw Language set 2
See menu “Language [211]” on page 99
Motor PTC. N= No option
17 -
(Only valid for 002-105/B-D2(69)) P= PTC
Gland kit. –= Glands not included
18 -
(Only valid for 002-074/IP54) G= Gland kit included
–= CE approved
D= Marine DNV Product certificate (above 100 kW)
19 17 Approval/certification + CE approved
M= Marine version + CE approved
U=UL/cUL approved
WARNING!
1.5.1 Product standard for EMC In a domestic environment this product
Product standard EN(IEC)61800-3, second edition of 2004 may cause radio interference, in which
defines the: case it may be necessary to take adequate
additional measures.
First Environment (Extended EMC) as environment that
includes domestic premises. It also includes establishments
directly connected without intermediate transformers to a
low voltage power supply network that supplies buildings
used for domestic purposes.
WARNING!
Category C2: Power Drive System (PDS) of rated The standard AC drive, complying with
voltage<1.000 V, which is neither a plug in device nor a category C3, is not intended to be used on
movable device and, when used in the first environment, is a low-voltage public network which
intended to be installed and commissioned only by a supplies domestic premises; radio
professional. interference is expected if used in such a
network. Contact your supplier if you need
Second environment (Standard EMC) includes all other additional measures.
establishments.
Category C3: PDS of rated voltage <1.000 V, intended for
use in the second environment and not intended for use in
the first environment.
Category C4: PDS or rated voltage equal or above 1.000 V,
or rated current equal to or above 400 A, or intended for use
in complex systems in the second environment.
The AC drive complies with the product standard
EN(IEC) 61800-3:2004 (Any kind of metal screened cable
may be used). The standard AC drive is designed to meet the
Table 3 Abbreviations
Abbreviation/
Description
symbol
1.7.2 Definitions
In this manual the following definitions for current, torque
and frequency are used:
Table 4 Definitions
Load: 56 to 95 kg
(123 - 202 lbs)
Fig. 3 Remove the roof unit and use the lifting eyes to lift
single unit 600 mm (23.6 in) and 900 mm (35.4 in).
E Gland
M25
ø13 mm(x2) Glands
(0.51 in) M32
ø7 mm(x4)
(0.27 in)
G
12.5 kg
F
(26.5 lb)
ø13 mm(x2) E
(0.51 in)
ø13 mm(x2)
(0.51 in)
A B
B K A
ø7 mm(x4)
(0.27 in)
ø7mm (x4)
(0.27 in)
24 kg F G
(53 lb) 17 kg
G
(38 lb) F
Fig. 8 Emotron FDU Model 48/52-026 to 046 (Frame size
C).
Fig. 10 Emotron FDU Model 48-025 to
48-058 (Frame size C2), Model 69-002 to 69-025
(Frame size C2(69)), backside view.
Gland
M25 (026-031)
M32 (037-046) Glands
M20
Glands
M32 (026-031) PE
L1 L2 L3 DC- DC+ R U V W
M40 (037-046)
Fig. 9 Cable interface for mains, motor and communication, Fig. 11 Bottom view Emotron FDU Model 48-025 to 48-058
Emotron FDU Model 48/52-026 to 046 (Frame size (Frame size C2) Model 69-002 to 69-025 (Frame size
C). C2(69)), with cable interface for mains, motor, DC+/
DC-, brake resistor and control.
Dimensions in mm (in)
Emotron
Frame
FDU
size G
model A B C D E F H I J K
(depth)
C2 025 - 058 585.5 471 128.5 23.8 13 167 267 (10.5) 196 10 23.5 496
C2(69) 002 - 025 (23) (18.5) (5.04) (0.91) (0.51) (7) IP21 282 (11.1) (7.7) (0.39) (0.9) (19.5)
ø13 mm(x2)
(0.51 in)
Glands
M32
A B
ø7mm (x4)
(0.27 in)
F G
17 kg
(37.4 lb)
Dimensions in mm (in)
Emotron
Frame
FDU
size G
model A B C D E F
(depth)
A B A K B
ø7 mm (x4)
(0.27 in)
ø7 mm(x4)
(0.27 in)
32 kg G
G 30 kg
(71 lb) F F
(66 lb)
Fig. 14 Emotron FDU Model 48/52-061 to 074 (Frame size Fig. 16 Emotron FDU Model 48-072 to
D), Model 69-033 to 69-058, (Frame size D69). 48-105 (Frame size D2), Model 69-033 to 69-058
(Frame size D2(69)), backside view.
Glands
Glands M20
M20
Glands
M50
Glands
M40 PE
A B B
A
ø9 mm(x6)
(0.35 in) ø9 mm(x6)
56/60 kg (0.35 in)
(124/132 lb) G 74 kg
F 163 lb) G
F
Fig. 18 Emotron FDU Model 48-090 to 175 (Frame size E).
Fig. 20 Emotron FDU Model 48-210 to 295 (Frame size F),
Emotron FDU Model 69-82 to 200 (Frame size
F69).
Cable glands M20
Cable glands M20
Cable flexible leadthrough
Ø17-42 /M50
(0.67 - 1.65in)
Cable flexible leadthrough Cable flexible leadthrough
Ø11-32 /M40 Ø23-55 /M63
(0.43 - 1.2 in) (0.91 - 2.1 in)
Cable flexible leadthrough
Ø17-42 /M50
(0.67 - 1.65in)
Fig. 19 Cable interface for mains, motor, DC+/DC-, brake
resistor and communication, Emotron FDU Model
48-090 to 175 (Frame size E). Fig. 21 Cable interface for mains, motor, DC+/DC-, brake
resistor and communication, Emotron FDU Model
48-210 to 295 (Frame size F), Emotron FDU Model
69-082 to 200 (Frame size F69).
Dimension in mm (in)
Frame Emotron FDU
size model G
A B C D E F H
(depth)
925 950
F 210 - 295
(36.4) (37.4) 300 22.5 344.5 314
10 (0.39) 150
1065 1090 (11.8) (0.88) (13.6) (12.4)
F69 082 - 200
(41.9) (42.9)
A B A B
ø9 mm(x6)
(0.35 in) ø9 mm(x6) FA2
53 kg F2 (0.35 in)
(117 lb) 84 kg
68 kg
F G (185 lb)
(150 lb) F
G
Fig. 22 Emotron /FDU Model 48-142 to
48-171 (Frame size E2). Fig. 24 Emotron /FDU Model 48-205 to
48-293 (Frame size F2) and 48-365-20 (Frame size
FA2).
Dimension in mm (in)
Frame Emotron FDU
size model G
A B C D E F H
(depth)
ø16 mm(x3)
(0.63 in)
ø9 mm(x6)
(0.35 in)
95 kg
(209 lb)
G
F
Fig. 25 Emotron FDU Model 48-365-54 (Frame size FA). Fig. 27 Side view Emotron FDU Model 48-365-54 (Frame
size FA).
Dimension in mm (in)
Frame Emotron FDU
size model G
A B C D E F H
(depth)
Model
L ATTI R L ATTI R
L ATTI R L ATTI R L ATTI R
150 mm 150 mm
(5.9 in) (5.9 in)
R ITTAL R ITTAL R ITTAL
Emotron FDU48: Model 300 to 500 (Frame sizes G Emotron FDU48: Model 600 to 750 (Frame size I)
and H) Emotron FDU69: Model 430 to 595 (Frame size I69)
Emotron FDU69: Model 250 to 400 (Frame size H69)
150 mm 150 mm
(5.9 in) (5.9 in)
R ITTAL R ITTAL R ITTAL R ITTAL R ITTAL R ITTAL
2250 mm (88.6 in)
2000 mm (78.7 in)
2250 mm (88.6 in)
2000 mm (78.7 in)
100 mm
100 mm (3.9 in) 1500 mm (59.0 in) 600 mm
(3.9 in) 1200 mm (47.2 in) 600 mm
(23.6 in)
(23.6 in)
Emotron FDU48: Model 860 to 1K0 (Frame Emotron FDU48: Model 1K15 to 1K25 (Frame size KA)
size J) Emotron FDU69: Model 650 to 800 (Frame size Emotron FDU69: Model 905 to 995 (Frame size KA69)
J69)
Emotron FDU48: Model 1K35 to 1K5 (Frame size K) Emotron FDU48: Model 1K75 (Frame size L)
Emotron FDU69: Model 1K2 (Frame size K69) Emotron FDU69: Model 1K4 (Frame size L69)
150 mm
(5.9 in) 150 mm
(5.9 in)
2250 mm (88.6 in)
2000 mm (78.7 in)
150 mm
(5.9 in)
2250 mm (88.6 in)
2000 mm (78.7 in)
L1 L2
L3 DC
- DC+
R U
VW
ns
Mai
tor
Mo
PE EMC gland, Screen connection
of motor cables
L1 L2 L3 PE DC- DC+ R U V W
PE
PE
EMC gland Screen connection
of motor cables
PE
DC-
DC+
L1 R
L2
L3
DC-
DC+
R
U
V
W
PE
ns
ns
Mai
tor
Mai
tor
Mo
Mo
Strainrelief and EMC clamp
Strainrelief and EMC clamp also for screen connection
also for screen connection of cables
of cables
PE
PE
DC-
DC+
R
ns
ns
Mai
ns
tor
tor
Mai
tor
tor
Mai
Mo
Mo
Mo
Mo
WARNING!
• Keep the motor cable between AC drive and motor as
The Brake Resistor must be connected short as possible.
between terminals DC+ and R. • The screening must be connected with a large contact
surface of preferable 360° and always at both ends, to
the motor housing and the AC drive housing. When
WARNING!
painted mounting plates are used, do not be afraid to
In order to work safely, the mains earth
scrape away the paint to obtain as large contact surface as
must be connected to PE and the motor
earth to . possible at all mounting points for items such as saddles
and the bare cable screening. Relying just on the
connection made by the screw thread is not sufficient.
AC drive
PE RFI-Filter
Mains Motor
Brake resistor
(option)
Screened cables
Metal housing
Brake Output
resistor coils
(option) (option)
Mains
1
tor
Cable interface
Mo
Motor cable
DC+, DC-, R (optional)
Mains cable
Motor cable
DC+, DC-, R (optional)
Mains cable
1
tor
Screw
ins
Ma
1
tor
tor r 2
to
Mo
1
Mo
PEBB 1 PEBB 2
(Master)
DC-, DC+, R
(optional)
Motor connection
U
V
W
Mains Connection
L1
L2
L3
Ground / earth
connection
bus bar
Mains Motor/Brake
(06-F45-cables only)
Table 15 Stripping lengths for mains, motor, brake and earth cables for frame sizes B to F
90 10 20 10 20
##-003 – 018 B 10 (0.4) 90 (3.5) 90 (3.5) 90 (3.5) 10 (0.4)
(3.5) (0.4) (0.8) (0.4) (0.8)
##-026 – 046 C 150 150 14 20 150 14 20 150
14 (0.2) 14 (0.2)
69-002 – 025 C69 (5.9) (5.9) (0.2) (0.8) (5.9) (0.2) (0.8) (5.9)
* Cable lug.
** Valid when brake chopper electronics are built in
DC-
DC+
R
C
B
A
Fig. 54 Distances from the cable clamp to the connection bolts size FA2.
Table 16 Distances from the cable clamp to the connection bolts for mains, motor, brake and earth cables for frame size FA2.
D
DC-
DC+
R
E
A
B
C
Fig. 55 Distances from the cable clamp to the connection bolts size FA.
Table 17 Distances from the cable clamp to the connection bolts for mains, motor, brake and earth cables for frame size FA.
NOTE: The dimensions of the power terminals used in the cabinet drive models 300 to 3K0 can differ depending on
customer specification.
Table 18 Cable connector range and tightening torque for Emotron FDU48 and FDU52, according to IEC ratings.
##-003-54
##-004-54
##-006-54
##-008-54 B 0.5 - 10 1.2-1.4 0.5 - 10 1.2-1.4 1.5 - 16 2.6
##-010-54
##-013-54
##-018-54
48-025-20
48-030-20
48-036-20 C2 4 - 25 2 4 - 25 2 4 - 25 * 4.3
48-045-20
48-058-20
##-026-54
Copper
##-031-54 2.5-16 2.5-16 (Cu) /
6-16 stranded
C stranded 1.2-1.4 stranded 1.2-1.4 1.2-1.4 Aluminum
##-037-54 6-25 solid
2.5-25 solid 2.5-25 solid (Al) 75°C
##-046-54
48-072-20 0.75 -50 3.3 0.75 -50 3.3
48-088-20 D2 10 - 70* 4.3
16 - 50 7.9 16 - 50 7.9
48-105-20
##-061-54 6-35 6-35 16-35
D stranded 2.8-3 stranded 2.8-3 stranded 2.8-3
##-074-54 6-50 solid 6-50 solid 16-50 solid
48-142-20 31 (for
E2
48-171-20 31 (for 16-34 mm2)
31 (for
16-34 mm2) 16- 150
48-090-54 16-34 mm2)
42 (for
16- 150 16 - 120
48-109-54 42 (for 35-150 mm2)
42 (for
E 35-120 16 - 185 **
35-150 mm2)
48-146-54 mm2)
48-175-54 10 **
48-205-20 31 (for
31 (for
25-34 mm2)
48-244-20 F2 25-34 mm2)
31 (for Copper
48-293-20 16-34 mm2) 25 - 240 42 (for (Cu) /
42 (for
35-152 mm2) Aluminum
48-210-54 25 - 240 35-152 mm2) 16 - 150
42 (for (Al) 75°C
48-228-54 35-150 16 - 185 ** 56 (for
56 (for
F mm2) 153-240 mm2)
48-250-54 153-240
mm2)
48-295-54 10 ** ***
69-002-
XX*****
69-003-XX
69-004-XX
69-006-XX
2.5 - 16 2.5 - 16 6 - 16
69-008-XX C69/
stranded 1.2 - 1.4 stranded 1.2 - 1.4 stranded 1.2 - 1.4
C2(69)
69-010-XX 2.5 - 25 solid 2.5 - 25 solid 6 - 25 solid
69-013-XX
69-018-XX
69-021-XX Copper
(Cu)/
69-025-XX Aluminum
69-033-XX (Al)
75°C
69-042-XX 6 - 35 6 - 35
D69/ 6 - 35 stranded
2.8 - 3 stranded 2.8 - 3 stranded 2.8 - 3
69-050-XX D2(69) 10 - 50 solid
10-50 solid 10 - 50 solid
69-058-XX
69-082-54 31 (for
16 - 34
69-090-54
31 (for 31 (for mm2)
69-109-54 16 - 34 mm2) 16 - 34 mm2) 16 - 150
F69 16 - 150 16 - 120 42 (for
69-146-54 42 (for 42 (for 35-150
69-175-54 35-150 mm2) 35-120 mm2) 16 - 185 ** mm2)
69-200-54 10 **
Table 20 Cable connector range and tightening torque for Emotron FDU48 and FDU52, according to NEMA ratings
##-003-54
##-004-54
##-006-54
##-008-54 B 20 - 8 11.5 20 - 8 11.5 16 - 6 23
##-010-54
##-013-54
##-018-54
48-025-20
48-030-20
48-036-20 C2 12 - 4 18 12 - 4 18 12 - 4* 38
48-045-20
48-058-20
##-026-54
##-031-54 Copper
C 18 - 4 10.6-12.3 18 - 4 10.6-12.3 18 - 4 10.6-12.3 (Cu)
##-037-54 75°C
##-046-54
48-072-20 10 - 0 30 - 50 10 - 0 30 - 50
48-088-20 D2 8 - 2/0* 38
3 - 2/0 70 3 - 2/0 70
48-105-20
##-061-54
D 10 - 0 24.3-26.1 10 - 0 24.3-26.1 10 - 0 24.3-26.1
##-074-54
48-142-20 275 (for
E2
48-171-20 275 (for AWG 6-2)
275 (for
AWG 6 - 2)
48-090-54 AWG 6 - 2) 6 - 300 kcmil
375 (for
6 - 300 kcmil 6 - 250 kcmil
48-109-54 375 (for AWG 1-
375 (for AWG
E AWG 1 - 300Kcmil)
48-146-54 1 -250Kcmil)
300Kcmil)
6 - 2/0**
48-175-54 88**
88**
48-365-20 FA2 Copper
M8
M10 connection 416 M8 connection 212 212 (Cu)
48-365-54 FA connection
75°C
48-300
G
48-375
(2x) 4 - 500 kcmil (2x) 4 - 500 kcmil
48-430
H
48-500
48-600
48-650
I (3x) 4 - 500 kcmil (3x) 4 - 500 kcmil
48-720,
750 275 (for 275 (for
AWG 4 - 2) AWG 4 - 2)
48-860
PE/Earth via mounting
375 (for 375 (for
48-900 J (4x) 4 - 500 kcmil (4x) 4 -500 kcmil screws/mounting frame.
AWG 1 - 300 AWG 1 -300 Copper
In order to secure proper
48-1k0 kcmil) kcmil) (Cu)
earthing, always use all
75°C
48-1k15 mounting screws and
500 (for AWG 500 (for AWG
tighten them thoroughly.
48-1K2 KA (5x) 4 - 500 kcmil 350 -500 (5x) 4 - 500 kcmil 350 -500
kcmil) kcmil)
48-1k25
48-1k35
K (6x) 4 - 500 kcmil (6x) 4 - 500 kcmil
48-1k5
48-1k75 L (7x) 4 - 500 kcmil (7x) 4 - 500 kcmil
48-2k0 M (8x) 4 - 500 kcmil (8x) 4 - 500 kcmil
48-2k25 N (9x) 4 - 500 kcmil (9x) 4 - 500 kcmil
(10x) 4 - 500
48-2k5 O (10x)4-500 kcmil
kcmil
WARNING!
Depending on the cooling characteristics
of the motor, the application, the speed
and the load, it may be necessary to use
forced cooling on the motor.
X5 X6 X7
X4 1 2 3
Option
Communication
C
X8
Control
Panel
Switches
I S1 U I S2 U I S3 U I S4 U
Control
signals R02
12 13 14 15 16 17 18 19 20 21 22 41 42 43
Relay outputs
AO1 AO2 DI4 DI5 DI6 DI7 DO1 DO2 DI8 NC C NO
X1 1 2 3 4 5 6 7 8 9 10 11 X2 31 32 33 51 52
+10V AI1 AI2 AI3 AI4 -10V DI1 DI2 DI3 +24V NC C NO X3 NO C
R01 R03
Terminal Name Function (Default) NOTE: N/C is opened when the relay is active and N/
O is closed when the relay is active.
Outputs
1 +10 V +10 VDC supply voltage
NOTE! Using potentiometer for reference signal to
6 -10 V -10 VDC supply voltage Analogue input: Possible potentiometer value in
range of 1 kΩ to 10 kΩ (¼ Watt) linear, where we
7 Common Signal ground advice to use a linear 1 kΩ / ¼ W type potentiometer
11 +24 V +24 VDC supply voltage for best control linearity.
EMC-
filter Motor
Alternative for
potentiometer Optional ***
control** Motor PTC
1
Optional
2
3 +10 VDC
0 - 10 V AnIn 1: Reference
4 4 - 20 mA
5 AnIn 2
6 AnIn 3
7 AnIn 4 Common
-10 VDC AnOut 1
Common AnOut 2
DigIn 1:RunL* DigOut 1
DigIn 2:RunR* DigOut 2
DigIn3
+24 VDC
Common
Relay 1
DigIn 4
DigIn 5
DigIn 6
DigIn 7
Relay 2
DigIn 8:Reset*
Relay 3
4.5.1 Cables
The standard control signal connections are suitable for
stranded flexible wire up to 1.5 mm2 (AWG16) and for solid Terminal 78 & 79
wire up to 2.5 mm2(AWG14) . see Table 23
Feed-through of
signal cables 78 79
Terminal 78 & 79
see Table 23
See
Table 23
Screen clamps
for signal cables
Screen clamps
for signal cables
motor PTC option
Control signals Fig. 60 Connecting the control signals, FDU model 48-025 to
48-058 frame size C2 and model 69-002 to 69-025
frame size C2(69).
Terminal A- & B+
see Table 23
Screen clamps
for signal cables
Screen clamps
for signal cables
L1 L2 L3 PE DC- DC+ R U V
Control signals
Control signals
Feed-through of
,A
79
signal cables
78
Feed-through of
signal cables
See
Table 23
(Options)
L1
L2
L3 D
C- D
C+
R
U
V
W
Screen clamps
for signal cables
Screen clamps
for signal cables
Digital
Voltage or current signals (0-10 V, 0-24 V, 0/4-20 mA)
which can have only two values (high or low) and only
occasionally change in value.
Data
Usually voltage signals (0-5 V, 0-10 V) which change rapidly
and at a high frequency, generally data signals such as
RS232, RS485, Profibus, etc.
Relay
Relay contacts (0-250 VAC) can switch highly inductive
loads (auxiliary relay, lamp, valve, brake, etc.).
Signal Tightenin
Maximum wire size Cable type
type g torque
Example:
The relay output from a AC drive which controls an
auxiliary relay can, at the moment of switching, form a
source of interference (emission) for a measurement signal
External control
(e.g. in metal housing)
Control consol
WARNING!
In order to work safely the mains earth
must be connected to PE and the motor
earth to .
X1
12
step to higher menu level or ignore changed 1
+ 13
setting 2
Reference 14
4-20 mA 3
0V 15
4
step to next menu on the same level 16
5
17
6
18
step to previous menu on the same level 7
19
8
20
increase value or change selection 9
Start 21
10
22
11
decrease value or change selection
X2
41
31
42
32
43
33
X3
51
52
Fig. 68 Wiring
6.1.1 Pumps
Dry-running, cavitation and overheating damage Pump Curve Protection detects deviation.
411–419, 41C1– 41C9
the pump and cause downtime. Sends warning or activates safety stop.
Sludge sticks to impeller when pump has been Automatic pump rinsing function: pump is set to
running at low speed or been stationary for a run at full speed at certain intervals, then return 362–368, 560, 640
while. Reduces the pump’s efficiency. to normal speed.
Motor runs at same speed despite varying PID continuously adapts pressure/flow to the
demands in pressure/flow. Energy is lost and level required. Sleep function activated when 320, 380, 342, 354
equipment stressed. none is needed.
Process inefficiency due to e.g. a blocked pipe, a Pump Curve Protection detects deviation.
411–419, 41C1–41C9
valve not fully opened or a worn impeller. Warning is sent or safety stop activated.
Water hammer damages the pump when
Smooth linear stops protect the equipment.
stopped. Mechanical stress on pipes, valves, 331–336
Eliminates need for costly motorized valves.
gaskets, seals.
6.1.2 Fans
Starting a fan rotating in the wrong direction can Fan is started at low speed to ensure correct
219, 341
be critical, e.g. a tunnel fan in event of a fire. direction and proper function.
Draft causes turned off fan to rotate the wrong Motor is gradually slowed to complete stop
way. Starting causes high current peaks and before starting. Avoids blown fuses and 219, 33A, 335
mechanical stress. breakdown.
Regulating pressure/flow with dampers causes Automatic regulation of pressure/flow with motor
321, 354
high energy consumption and equipment wear. speed gives more exact control.
Motor runs at same speed despite varying PID continuously adapts to the level required.
demands in pressure/flow. Energy is lost and Sleep function is activated when none is 320, 380, 342, 354
equipment stressed. needed.
Process inefficiency due to e.g. a blocked filter, a Load Curve Protection detects deviation.
411–419, 41C1–41C9
damper not fully opened or a worn belt. Warning is sent or safety stop activated.
Compressor is damaged when cooling media Overload situation is quickly detected and safety
411–41A
enters the compressor screw. stop can be activated to avoid breakdown.
Load Curve Protection function detects
Pressure is higher than needed, causing leaks,
deviation. Warning is sent or safety stop 411–419, 41C1–41C9
stress on the equipment and excessive air use.
activated.
Motor runs at same speed when no air is
PID continuously adapts to the level required.
compressed. Energy is lost and equipment 320, 380, 342, 354
Sleep function activated when none is needed.
stressed.
Process inefficiency and energy wasted due to Load Curve Protection quickly detects deviation.
411–419, 41C1–41C9
e.g. the compressor idling. Warning is sent or safety stop activated.
6.1.4 Blowers
Difficult to compensate for pressure fluctuations. PID function continuously adapts pressure to the
320, 380
Wasted energy and risk of production stop. level required.
PID continuously adapts air flow to level
Motor runs at same speed despite varying
required. Sleep function activated when none is 320, 380, 342, 354
demands. Energy is lost and equipment stressed.
needed.
Process inefficiency due to e.g. a broken damper, Load Curve Protection quickly detects deviation.
411–419, 41C1–41C9
a valve not fully opened or a worn belt. Warning is sent or safety stop activated.
A 0 0
B 1 0
C 0 1
D 1 1
Manual - automatic control One motor must stop before changing to an other motor.
If in an application something is filled up manually and then 1. Select parameter set A in menu [241].
the level is automatically controlled using PID regulation, 2. Select motor M1 in menu [212].
this is solved using one parameter set for the manual control 3. Enter motor data and settings for other parameters
and one for the automatic control. e.g. inputs and outputs.
4. Select parameter set B in menu [241].
5. Select M2 in menu [212].
7.1.1 One motor and one parameter 6. Enter motor data and settings for other parameters
set e.g. inputs and outputs.
This is the most common application for pumps and fans.
Once default motor M1 and parameter set A have been 7.1.4 Autoreset at trip
selected: For several non-critical application-related failure
1. Enter the settings for motor data. conditions, it is possible to automatically generate a reset
2. Enter the settings for other parameters e.g. inputs command to overcome the fault condition. The selection
and outputs can be made in menu [250]. In this menu the maximum
number of automatically generated restarts allowed can be
set, see menu [251], after this the AC drive will stay in fault
condition because external assistance is required.
12
1 71 shows the function of the Enable and the Stop input and
13
2 the Stop Mode=Decel [33B].
14
3
4
15 To run the input must be high.
16
5
17
6 NOTE: Stop Mode=Coast [33B] will give the same
18
7 behaviour as the Enable input.
19
8
20
RunR 9
21
Reset 10
22
+24 V 11
STOP
(STOP=DECEL)
X
ENABLE
OUTPUT
SPEED
t
(06-F104_NG) (or if Spinstart is selected)
Edge-control
After the Reset command is given a new Run command
must be applied to start the AC drive again. OUTPUT
Autoreset is enabled if the Reset input is continuously active. STATUS
The Autoreset functions are programmed in menu
“Autoreset [250]”. Right rotation
Left rotation
NOTE: If the control commands are programmed for
Keyboard control or Com, Autoreset is not possible. Standstill
(06-F103new_1)
Run Inputs Level-controlled. Fig. 73 Input and output status for level-control
The inputs are set as default for level-control. This means
that an input is activated by making the input continuously Run Inputs Edge-controlled
“High”. This method is commonly used if, for example, Menu “[21A] Start signal” Level/Edge must be set to Edge
PLCs are used to operate the AC drive. to activate edge control. This means that an input is
activated by a “low” to “high” transition or vice versa.
CAUTION!
! Level-controlled inputs DO NOT comply with
the Machine Directive, if the inputs are
NOTE: Edge-controlled inputs comply with the
Machine Directive (see Chapter 8. page 77), if the
directly used to start and stop the machine.
inputs are directly used for starting and stopping the
machine.
The examples given in this and the following paragraphs
follow the input selection shown in Fig. 72. See Fig. 72. The Enable and Stop input must be active
continuously in order to accept any run-right or run-left
command. The last edge (RunR or RunL) is valid. Fig. 74
gives an example of a possible sequence.
X1
12
1
13
2
14
3
15
4
16
5
Stop 17
6
18
7
19
RunL 8
20
RunR 9
21
Enable 10
Reset 22
+24 V 11
7.3 Performing an
AC drive
Identification Run
To get the optimum performance out of your AC drive/
motor combination, the AC drive must measure the
electrical parameters (resistance of stator winding, etc.) of
the connected motor. See menu [229] “Motor ID-Run”.
[413] Ramp Alarm=On [413] Ramp Alarm=On or Off [413] Ramp Alarm=On or Off [413] Ramp Alarm=On
Main Features
Torque [%] [411] Alarm Select=Max or Max+Min [411] Alarm Select=Max or Max+Min [411] Alarm Select=Max or Max+Min [411] Alarm Select=Max or Max+Min
Min Alarm
[4192] MinAlarmDel (0.1s) Must be <t (or t´) otherwise no (pre)alarm [4192] MinAlarmDel (0.1s)
Min PreAlarm
[414] Start Delay (0.2s)
7.6.1 Introduction PM P1 P2 P3 P4 P5 P6
A maximum of 4 pumps can be controlled with the standard
AC drive.
FDU R:SlavePump1
MASTER
If I/O Board options are installed, a maximum of 7 pumps Set R:SlavePump2
PRESSURE
can be controlled. The I/O Board can also be used as a AnIn R:SlavePump3
Feedback PI D
general extended I/O. PRESSURE
AnIn R:SlavePump4
pictures in this section, the relays are named R:Function, Fig. 78 Pressure control with pump control option
e.g. R:SlavePump1, which means a relay on the control
board or on a option board set to function SlavePump1. Pumps in parallel will operate as a flow controller, See Fig.
77.
Pumps in a series will operate as a pressure controller see Fig.
78. The basic control principle is shown in Fig. 79.
PM P1 P2 P3 P4 P5 P6
NOTE: Read this instruction manual carefully before
FDU
MASTER
R:SlavePump1 commencing installation, connecting or working with
Set FLOW
R:SlavePump2 the AC drive with Pump Control option.
AnIn
R:SlavePump3
Feedback
FLOW
PID
AnIn R:SlavePump4
R:SlavePump5
R:SlavePump6
FREQUENCY (master pump P)
Add pump
Pressur e
Stop pump
TIM E
(50-PC-3_1)
select the pumps depending on the run time history of each R: MasterPump6
R: MasterPump5
pump. R: MasterPump4
R: MasterPump3
R: MasterPump2
R: MasterPump1
(NG_50-PC-5_1)
P1 P2 P3 P4 P5 P6
See menu:
R:SlavePump6
FDU R:SlavePump5 [393] to [396]
R:SlavePump4
MASTER R:SlavePump3
R:SlavePump2
[553] to [55C]
R:SlavePump1
PM P1 P2 P3 P4 P5 P6
(NG_50-PC-4_1)
NOTE: The pumps MUST have all the same power.
See menu:
[393] Select Drive 7.6.4 Feedback 'Status' input
[39H] to [39N] Run Time 1 - 6, Pump In this example, the additional pumps are controlled by an
[554] to [55C] Relays different kind of drive (e.g. soft starter, frequency inverter,
etc.). The digital inputs on the I/O Board can be
programmed as a "Error" input for each pump. If a drive
Fig. 80 Fixed MASTER control
fails, the digital input will monitor this and the PUMP
CONTROL option will not use that particular drive
NOTE: The pumps MAY have different powers, anymore and automatically switch to another drive. This
however the MASTER pump MUST always be the means that the control continues without using this (faulty)
largest. drive. This function can also be used to manually stop a
particular pump for maintenance purposes, without
shutting down the whole pump system. Of course the
7.6.3 Alternating MASTER maximum flow/pressure is then limited to the maximum
With this function the Master pump is not fixed to the AC pump power of the remaining pumps.
drive all the time. After the AC drive is powered up or
started again after a stop or sleep mode the Master pump is
selected via the relay set to function Master Pump. section
7.6.7 on page 73 shows a detailed wiring diagram with 3
pumps. The purpose of this function is that all pumps are
used equally, so the lifetime of all pumps, including the
Master pump, will be equalized. Maximum 6 pumps can be
controlled with this function.
FDU R:SlavePump3
MASTER R:SlavePump2
R:SlavePump1
other
drive other
feedback DI:Pump1Feedb other
DI:Pump2Feedb drive
inputs DI:Pump3Feedb drive
(NG_50-PC-6_1) PM P1 P2 P3
7.6.5 Fail safe operation obtained by using the NC contacts of the pump control
relays. These can be programmed for each individual
Some pump systems must always have a minimum flow or
additional pump. In this example, pumps P5 and P6 will
pressure level, even if the frequency inverter is tripped or
run at maximum power if the inverter fails or is powered
damaged. So at least 1 or 2 (or maybe all) additional pumps
down.
must keep running after the inverter is powered down or
tripped. This kind of "safe" pump operation can be
See menu:
[554] to [55C] Relays
[55D4] to [55DC] Mode
R:SlavePump6
R:SlavePump5
FDU R:SlavePump4
MASTER R:SlavePump3
R:SlavePump2
R:SlavePump1
(50-PC-7_1) PM P1 P2 P3 P4 P5 P6
See menu:
[381] to [385]
[553] to [55C]
[411] to [41C]
R:SlavePump6
FDU R:SlavePump5
R:SlavePump4
MASTER R:SlavePump3
Set R:SlavePump2
Value AnIn
R:SlavePump1
Feedback
PID
AnIn
Value
PM P1 P2 P3 P4 P5 P6
Flow/Pressure
measurement (NG_50-PC-8_1)
!
6 and SlavePump1-6. The Master and Additional contactors The wiring for the Alternating Master
also interlock with each other to prevent dual powering of control needs special attention and should
the pump and damage to the inverter. (K1M/K1S, K2M/ be wired exactly as described here, to
K2S, K3M/K3S). Before running, the FDU will select a avoid destructive short circuit at the output
pump to be Master, depending on the pump run times. of the inverter.
PE
L1
L2
L3
PE L1 L2 L3
FDU
K1S K2S K3S
U V W
P1 P2 P3
(NG_50-PC-10_1) 3~ 3~ 3~
~
B1:R1 B2:R1 B1:R2 B2:R2 B1:R3 B2:R3
Master Slave Master Slave Master Slave
Pump1 Pump1 Pump2 Pump2 Pump3 Pump3
(NG_50-PC-11_3)
1. Main Functions
2. Number of pumps/drives
If the system consists of 2 or 3 pumps the I/O Board option is not needed. However, this does mean that the following
functions are not then possible:
- "Alternating MASTER" function
- With isolated inputs
With the I/O Board option installed, the maximum number of pumps is:
- 6 pumps if "Alternating MASTER" function is selected. (see section 7.6.3 on page 70)
- 7 pumps if "Fixed MASTER" function is selected. (see section 7.6.2, page 70)
3. Pump size
If the digital inputs are used, the digital input function must be set to Drive feedback.
After the Pump controller is switched on in menu [391] the number of drives (pumps, fans, etc.) must be set in menu
[392] (Number of Drives). The relays themselves must be set to the function SlavePump1-6 and if Alternate master is
used, MasterPump1-6 as well.
6. Equal Pumps
If all pumps are equal in power size it is likely that the Upper band is much smaller than the Lower band, because the
maximum pump discharge of the master pump is the same if the pump is connected to the mains (50Hz). This can give
a very narrow hysteresis causing an unstable control area in the flow/pressure. By setting the maximum frequency of the
inverter only slightly above 50Hz it means that the master pump has a slightly bigger pump discharge than the pump on
the mains. Of course caution is essential in order to prevent the master pump running at a higher frequency for a longer
period of time, which in turn prevents the master pump from overloading.
7. Minimum Speed
With pumps and fans it is normal to use a minimum speed, because at lower speed the discharge of the pump or fan
will be low until 30-50% of the nominal speed (depending on size, power, pump properties, etc.). When using a
minimum speed, a much smoother and better control range of the whole system will be achieved.
Feedback Flow
time
Master pump
Speed
Max speed
[343] Upper band
Min speed
[341] Lower band
time
Start delay [399] Settle time start [39D]
2nd pump
Speed
Feedback Flow
time
Master pump
Speed
Max speed
[343] Upper band
Min speed
[341] Lower band
2nd pump
Speed
(NG_50-PC-20_1)
WARNING!
EN 60204-1 specifies that every machine
must be provided with a category 0 stop.
If the application prevents this from being
implemented, this must be explicitly stated.
Furthermore, every machine must be provided with
an Emergency Stop function. This emergency stop
must ensure that the voltage at the machine
contacts, which could be dangerous, is removed as
quickly as possible, without resulting in any other
danger. In such an Emergency Stop situation, a
category 0 or 1 stop may be used. The choice will be
decided on the basis of the possible risks to the
machine.
Default 0
9.4 Start and stop Range -16384 to 16384
commands Corresponding to -100% to 100% process value
Set start and stop commands via serial communication.
Communication information
Modbus/DeviceNet Modbus /DeviceNet Instance number 42906
Function Profibus slot /Index 168/65
Instance number
EtherCAT index (hex) 4b5a
42901 Reset Profinet IO index 19290
Run, active together with either Fieldbus format Int
42902 RunR or RunL to Modbus format Int
perform start.
42903 RunR Example:
(See Emotron Fielbus manual for detailed information)
42904 RunL
We would like to control the AC drive over a bus system
using the first two bytes of the Basic Control Message by
Note! Bipolar reference mode is activated if both setting menu “[2661] FB Signal 1” to 49972. Further, we
RunR and RunL is active.
also want to transmit a 16 bit signed reference and a 16 bit
process value. This is done by setting menu
“[2662] FB Signal 2” to 42905 and menu “[2663] FB Signal
3” to 42906.
formats -8 1000
Eint is only used with Modbus-RTU and Modbus-TCP -7 1001
protocols. ..
A parameter with Eint format can be represented in two -2 1110
different formats (F). Either as a 15 bit unsigned integer -1 1111
format (F= 0) or a Emotron floating point format (F=1). 0 0000
The most significant bit (B15) indicates the format used.
1 0001
See detailed description below.
2 0010
All parameters written to a register may be rounded to the
..
number of significant digits used in the internal system.
6 0110
The matrix below describes the contents of the 16-bit word 7 0111
for the two different EInt formats:
typedef struct
{
int m:11; // mantissa, -1024..1023
int e: 4; // exponent -8..7
unsigned int f: 1; // format, 1->special emoint format
} eint16;
//---------------------------------------------------------------------------
unsigned short int float_to_eint16(float value)
{
eint16 etmp;
int dec=0;
evalue=*(eint16 *)&value;
if (evalue.f)
{
if (evalue.e>=0)
f=(int)evalue.m*pow10(evalue.e);
else
f=(int)evalue.m/pow10(abs(evalue.e));
}
else
f=value;
return f;
}
//---------------------------------------------------------------------------
A J I
100 1240rpm
B Torque 0% 0.0Nm H
C Current 123.3A G
Sby Key/Key
D E F
Fig. 91 The display
NOTE:
In area B and area C only 8 characters are available,
this means that some texts will be shortened.
Shows Menu number to the left and to the right signal selected
221 1240rpm in menu [110].
Motor Volts Shows menu name to the left
M1 380V Shows menu value to the right and if it is a Motor parameter active
Run Key/Key Motor set (M1 in this case) is displayed to the left.
Shows Drive status/Parameter set and Control source as in menu [100]
933 1240rpm
Weekday
Monday
Run Key/Key
When editing values, the toggle key can be used to change 100
the sign of the value, see section 10.6, page 92.
511 Toggle loop 211
Toggle function
Using the toggle function makes it possible to easily step 341 221
through selected menus in a loop. The toggle loop can
contain a maximum of ten menus. As default the toggle loop 222
contains the menus needed for Quick Setup. You can use the 331
Sub menus
toggle loop to create a quick-menu for the parameters that
are most importance to your specific application.
Fig. 99 Example 4th level menu NOTE: It is not possible to simultaneously activate
the Run/Stop commands from the keyboard and
remotely from the terminal strip (terminals 1-22).
10.3.2 Indications on the display Exception is the JOG-function which can give start
The display can indicate “+++” or “- - -” if a parameter is out command, see “ Jog Speed [348]” on page 146.
of range. In the AC drive there are parameters which are
dependent on other parameters. For example, if the speed
reference is 500 and the maximum speed value is set to a
value below 500, this will be indicated with “+++” on the
display. If the minimum speed value is set over 500, “- - -”
is displayed.
When editing values, the toggle key can be used to change 100
the sign of the value, see section 10.6, page 92.
511 Toggle loop 211
Toggle function
Using the toggle function makes it possible to easily step 341 221
through selected menus in a loop. The toggle loop can
contain a maximum of ten menus. As default the toggle loop 222
contains the menus needed for Quick Setup. You can use the 331
Sub menus
toggle loop to create a quick-menu for the parameters that
are most importance to your specific application.
NEXT
- decrease a value
- key:
- change a selection 4161
NG_06-F28
300 Process
Stp
or
Press “Enter” key for
menu [310].
330 Run/Stop
Stp
or
Press “Enter” for
menu [331].
100 0rpm
Stp 0.0A
Menu “[100] Preferred View” displays the settings made in
menu “[110], 1st line”, and “[120], 2nd line”. See Fig. 104.
Dependent on menu
Process Val 0 Process value
222 Motor Frequ Speed 1 Speed
Read-only
Torque 2 Torque
Communication information
11.3.2 2nd Line [120]
Modbus Instance no/DeviceNet no: 43004
Sets the content of the second line in the menu
Profibus slot/index 168/163
“[100] Preferred View”. Same selection as in menu [110].
EtherCAT and CANopen index (hex) 4bbc
Profinet IO index 19388
120 2nd Line Fieldbus format
Default: Current Modbus format
NOTE: Following menus [130] to [170] are only valid Communication information
for the control panel with 4-line display. Modbus Instance no/DeviceNet no: 43005
Profibus slot/index 168/164
EtherCAT and CANopen index (hex) 4bbd
11.3.3 3rd Line [130] Profinet IO index 19389
Sets the content of the third line in the menu Fieldbus format
“[100] Preferred View”. Same selection as in menu [110]. Modbus format
Communication information
Modbus Instance no/DeviceNet no: 43011
Profibus slot/index 168/170
EtherCAT and CANopen index (hex) 4bc3
Profinet IO index 19395
Fieldbus format UInt
Modbus format UInt
Communication information
Modbus Instance no/DeviceNet no: 43014
Profibus slot/index 168/173
EtherCAT and CANopen index (hex) 4bc6
Profinet IO index 19398
Fieldbus format UInt
Modbus format UInt
Communication information
Modbus Instance no/DeviceNet no: 43010
Profibus slot/index 168/169
EtherCAT and CANopen index (hex) 4bc2
Profinet IO index 19394
Fieldbus format UInt
Modbus format UInt
The inputs are activated by a transition; Brake chopper activation level is adjusted using the setting
Edge 1 for Run and Reset from “low” to “high” of [21B].
and for Stop from "high" to "low".
NOTE: The setting is affected by the “Load from CP”
Communication information command [245] and if loading parameter file via
EmoSoftCom.
Modbus Instance no/DeviceNet no: 43020
Profibus slot/index 168/179
EtherCAT and CANopen index (hex) 4bcc 21B Supply Volts
Profinet IO index 19404
Default: Not defined
Fieldbus format UInt
Modbus format UInt Inverter default value used. Only valid if
Not Defined 0
this parameter is never set.
Communication information
Modbus Instance no/DeviceNet no: 43041
Profibus slot/index 168/200
EtherCAT and CANopen index (hex) 4be1
Profinet IO index 19425
Fieldbus format Long, 1=0.1 V
Modbus format EInt
Communication information
Modbus Instance no/DeviceNet no: 43044
Profibus slot/index 168/203
EtherCAT and CANopen index (hex) 4be4
Profinet IO index 19428
Fieldbus format Long, 1=0.1 A
Modbus format EInt
Communication information
228 Motor Vent
Modbus Instance no/DeviceNet no: 43045
Profibus slot/index 168/204 Default: Self
EtherCAT and CANopen index (hex) 4be5
None 0 Limited I2t overload curve.
Profinet IO index 19429
Fieldbus format UInt. 1=1 rpm Normal I2t overload curve. Means that the
Self 1
Modbus format UInt motor stands lower current at low speed.
Expanded I2t overload curve. Means that
Forced 2 the motor stands almost the whole current
Motor Poles [226] also at lower speed.
When the nominal speed of the motor is ≤500 rpm, the
additional menu for entering the number of poles, [226], Communication information
appears automatically. In this menu the actual pole number
Modbus Instance no/DeviceNet no: 43048
can be set which will increase the control accuracy of the AC
Profibus slot/index 168/207
drive.
EtherCAT and CANopen index (hex) 4be8
Profinet IO index 19432
226 Motor Poles Fieldbus format UInt
Default: 4 Modbus format UInt
Range: 2-144
When the motor has no cooling fan, None is selected and
the current level is limited to 55% of rated motor current.
Communication information
With a motor with a shaft mounted fan, Self is selected and
Modbus Instance no/DeviceNet no: 43046 the current for overload is limited to 87% from 20% of
Profibus slot/index 168/205 synchronous speed. At lower speed, the overload current
EtherCAT and CANopen index (hex) 4be6 allowed will be smaller.
Profinet IO index 19430
Fieldbus format Long, 1=1 pole
When the motor has an external cooling fan, Forced is
Modbus format EInt
selected and the overload current allowed starts at 90% from
rated motor current at zero speed, up to nominal motor
current at 70% of synchronous speed.
Fig. 106 shows the characteristics with respect for Nominal
Current and Speed in relation to the motor ventilation type
selected.
None
0.55 Motor Sound [22A]
Sets the sound characteristic of the AC drive output stage by
changing the switching frequency and/or pattern. Generally
the motor noise will go down at higher switching
frequencies.
0.20 0.70 2.00
xSync Speed
22A Motor Sound
F
Fig. 106 I2t curves Default: (“Advanced” for models 48-293/295 and
48-365)
Motor Identification Run [229] E 0 Switching frequency 1.5 kHz
This function is used when the AC drive is put into
F 1 Switching frequency 3 kHz
operation for the first time. To achieve an optimal control
performance, fine tuning of the motor parameters using a G 2 Switching frequency 6 kHz
motor ID run is needed. During the test run the display Switching frequency 6 kHz, random
shows “Test Run” flashing. H 3
frequency (+750 Hz)
To activate the Motor ID run, select “Short” and press Switching frequency and PWM mode
Enter. Then press RunL or RunR on the control panel to Advanced 4
setup via [22E]
start the ID run. If menu
“[219] Rotation” is set to L the RunR key is inactive and
Communication information
vice versa. The ID run can be aborted by giving a Stop
command via the control panel or Enable input. The Modbus Instance no/DeviceNet no: 43050
parameter will automatically return to OFF when the test is Profibus slot/index 168/209
completed. The message “Test Run OK!” is displayed. EtherCAT and CANopen index (hex) 4bea
Before the AC drive can be operated normally again, press Profinet IO index 19434
the STOP/RESET key on the control panel. Fieldbus format UInt
Modbus format UInt
During the Short ID run the motor shaft does not rotate.
The AC drive measures the rotor and stator resistance.
NOTE: At switching frequencies >3 kHz derating may
become necessary.
Communication information
PWM Mode [22E2]
Modbus Instance no/DeviceNet no: 43052
Profibus slot/index 168/211
22E2 PWM Mode
EtherCAT and CANopen index (hex) 4bec
Profinet IO index 19436
Default: Standard
Fieldbus format Long, 1=1 pulse
Modbus format EInt Standard 0 Standard
Sine Filter mode for use with output Sine
Sine Filt 1
Filters
Encoder Speed [22D]
Only visible if the Encoder option board is installed. This
parameter shows the measured motor speed. To check if the NOTE: Switching frequency is fixed when “Sine Filt”
encoder is correctly installed, set Encoder Feedback [22B] to is selected. This means that it is not possible to
Off, run the AC drive at any speed and compare with the control the switching frequency based on
value in this menu. The value in this menu [22D] should be temperature.
about the same as the motor speed [230]. If you get the
wrong sign for the value, swap encoder input A and B.
Communication information
Modbus Instance no/DeviceNet no: 43054
22D Enc Speed
Profibus slot/index 168/213
Unit: rpm EtherCAT and CANopen index (hex) 4bee
Profinet IO index 19438
Resolution: speed measured via the encoder
Fieldbus format UInt
Modbus format UInt
Communication information
Modbus Instance no/DeviceNet no: 42911 PWM Random [22E3]
Profibus slot/index 168/70
EtherCAT and CANopen index (hex) 4b5f
Profinet IO index 19295
22E3 PWM Random
Fieldbus format Int, 1=1 rpm
Modbus format Int Default: Off
Off 0 Random modulation is Off.
Resolution 1
Communication information
Modbus Instance no/DeviceNet no: 42912
Profibus slot/index 168/71
EtherCAT and CANopen index (hex) 4b60
Profinet IO index 19296
Long, 1=1 quad
Fieldbus format
encoder pulse
Modbus format Int
Default: 10%
Motor type [22I]
Range 0 - 400 %
In this menu select type of motor. Emotron AC drives can
control Asynchronous motors, Permanent Magnet
Communication information Synchronous Motor and Synchronous Reluctance Motors.
Modbus Instance no/DeviceNet no: 43057
Profibus slot/index 168/216 22I Motor Type
EtherCAT and CANopen index (hex) 4bf1
Profinet IO index 19441 Default: Async
Fieldbus format Long, 1=1 %
Modbus format EInt
Async 0 Asynchronous motor
PMSM 1 Permanent magnet synchronous motor
Encoder max fault counter [22G3] Sync Rel 2 Synchronous Reluctance motor
This is a measured signal showing the maximum time that
the speed deviation has exceeded the allowed speed deviation
Communication information
band level, set in [22G2]. The parameter is intended to be
used during commissioning for setting up [22G1] and Modbus Instance no/DeviceNet no: 43059
[22G2] to avoid nuisance trips and can be cleared by setting Profibus slot/index 168/218
it to 0. EtherCAT and CANopen index (hex) 4bf3
Profinet IO index 19443
Fieldbus format UInt
22G3 Max EncFCtr
Modbus format UInt
Default: 0.000s
NOTE: If PMSM is selected in menu [22I], following
Range 0.00 - 10.00 s will be set automatically:
Communication information
Modbus Instance no/DeviceNet no: 43392
Profibus slot/index 170/41
EtherCAT and CANopen index (hex) 4d40
Profinet IO index 19776
Fieldbus format Long, 1=0.000001
Modbus format EInt
Default: Undef
Undef Undefined
Range: 0.001-10000.000 mH
Communication information
Modbus Instance no/DeviceNet no: 43393
Profibus slot/index 170/42
EtherCAT and CANopen index (hex) 4d41
Profinet IO index 19777
Fieldbus format Long, 1=0.001
Modbus format EInt
231 Mot I2t Type NOTE: When the selection Limit is set in menu [231],
the value must be above the no-load current of the
Default: Trip
motor.
Off 0 I2t motor protection is not active.
When the I2t time is exceeded, the AC
Trip 1
drive will trip on “Motor I2t”.
Motor I2t Time [233]
Sets the time of the I2t function. After this time the limit for
This mode helps to keep the inverter
the I2t is reached if operating with 120% of the I2t current
running when the Motor I2t function is just
value. Valid when start from 0 rpm.
before tripping the AC drive. The trip is
replaced by current limiting with a
maximum current level set by the value NOTE: Not the time constant of the motor.
Limit 2
out of the menu [232]. In this way, if the
reduced current can drive the load, the
AC drive continues running. If there is no 233 Mot I2t Time
reduction in thermal load, the drive will
Default: 60 s
trip.
Range: 60–1200 s
Communication information
Modbus Instance no/DeviceNet no: 43061
Communication information
Profibus slot/index 168/220 Modbus Instance no/DeviceNet no: 43063
EtherCAT and CANopen index (hex) 4bf5 Profibus slot/index 168/222
Profinet IO index 19445 EtherCAT and CANopen index (hex) 4bf7
Fieldbus format UInt Profinet IO index 19447
Modbus format UInt Fieldbus format Long, 1=1 s
Modbus format EInt
10000
t [s]
1000
1000 s (120%)
480 s (120%)
100
240 s (120%)
120 s (120%)
60 s (120%)
10
Fig. 107 shows how the function integrates the square of the Example
motor current according to the “Mot I2t Curr [232]” and In Fig. 107 the thick grey line shows the following example.
the “Mot I2t Time [233]”.
• Menu “[232] Mot I2t Curr” is set to 100%.
When the selection Trip is set in menu [231] the AC drive 1.2 x 100% = 120%
trips if this limit is exceeded.
• Menu “[233] Mot I2t Time” is set to 1000 s.
When the selection Limit is set in menu [231] the AC drive
This means that the AC drive will trip or reduce the current
reduces the torque if the integrated value is 95% or closer to
(depending on the setting in menu [231]) after 1000 s if the
the limit, so that the limit cannot be exceeded.
current is 1.2 times of 100% nominal motor current.
Communication information
Modbus Instance no/DeviceNet no: 43066
Profibus slot/index 168/225
EtherCAT and CANopen index (hex) 4bfa
Profinet IO index 19450
Fieldbus format UInt
Modbus format UInt
M4 9
All four motor sets will revert to default
M1234 10
settings.
Communication information
Modbus Instance no/DeviceNet no: 43023
Profibus slot/index 168/182
EtherCAT and CANopen index (hex) 4bcf
Profinet IO index 19407
Fieldbus format UInt
Modbus format UInt
Communication information
Modbus Instance no/DeviceNet no: 43025
Profibus slot/index 168/184
EtherCAT and CANopen index (hex) 4bd1
Profinet IO index 19409
Fieldbus format UInt
Modbus format UInt
251 No of Trips
253 Over volt D
Default: 0 (no Autoreset)
Default: Off
Range: 0–10 attempts
Off 0 Off
PTC [25E]
2
Motor I t Trip Type [25B] Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
Select the preferred way to react to a Motor I2t trip.
is active.
Communication information
Modbus Instance no/DeviceNet no: 43074
Profibus slot/index 168/233
EtherCAT and CANopen index (hex) 4c02
Profinet IO index 19458
Fieldbus format UInt
Modbus format UInt
Default: Trip
25I Com Error
Selection: Same as menu [25B]
Default: Off
25U LC Level TT
Default: Trip
Selection: Same as menu [25B]
Communication information
Modbus Instance no/DeviceNet no: 43100
Profibus slot/index 169/4
EtherCAT and CANopen index (hex) 4c1c
Profinet IO index 19484
Fieldbus format UInt
Modbus format UInt
Off 0 Off
NOTE: Toggling the setting in this menu will perform a
1- 3600 1- 3600 1- 3600 s
soft reset (re-boot) of the Fieldbus module.
Communication information
Modbus Instance no/DeviceNet no: 43561 RS232/485 [262]
Profibus slot/index 170/210 Press Enter to set up the parameters for RS232/485
EtherCAT and CANopen index (hex) 4de9 (Modbus/RTU) communication.
Profinet IO index 19945
Fieldbus format Long, 1=1s 262 RS232/485
Modbus format EInt
2621 Baudrate
Default: 9600
2400 0
4800 1
9600 2 Selected baud rate
19200 3
38400 4
2631 Address
Communication information
Default: 62 Modbus Instance no/DeviceNet no: 43036
CANopen 1-127, Profibus 0–126, Profibus slot/index 168/195
Range:
DeviceNet 0–63 EtherCAT and CANopen index (hex) 4bdc
Profinet IO index 19420
Node address valid for CANopen (RW), Profibus(RW),
DeviceNet (RW) and EtherCAT (RO). Fieldbus format UInt
Modbus format UInt
Communication information
Modbus Instance no/DeviceNet no: 43034
Profibus slot/index 168/199
EtherCAT and CANopen index (hex) 4bda
Profinet IO index 19418
Fieldbus format UInt, 1=1
Modbus format UInt
NOTE: For CANopen module this menu is forced to NOTE: The automatic baud rate detection will NOT
“Basic”. work if there is no traffic on the network.
2651 IP Address
Default: 0.0.0.0 Gateway [2654]
Space 0 m 58
Process Unit [322] 0–9 1–10 n 59
A 11 ñ 60
322 Proc Unit
B 12 o 61
Default: rpm
C 13 ó 62
Off 0 No unit selection
D 14 ô 63
% 1 Percent
E 15 p 64
°C 2 Degrees Centigrade
F 16 q 65
°F 3 Degrees Fahrenheit
G 17 r 66
bar 4 bar
H 18 s 67
Pa 5 Pascal
I 19 t 68
Nm 6 Torque
J 20 u 69
Hz 7 Frequency
K 21 ü 70
rpm 8 Revolutions per minute
L 22 v 71
m3/h 9 Cubic meters per hour
M 23 w 72
gal/h 10 Gallons per hour
N 24 x 73
ft3/h 11 Cubic feet per hour
O 25 y 74
User 12 User defined unit
P 26 z 75
Q 27 å 76
Communication information
R 28 ä 77
Modbus Instance no/DeviceNet no: 43303
Profibus slot/index 169/207 S 29 ö 78
EtherCAT and CANopen index (hex) 4ce7
T 30 ! 79
Profinet IO index 19687
Fieldbus format UInt U 31 ¨ 80
Modbus format UInt Ü 32 # 81
V 33 $ 82
W 34 % 83
X 35 & 84
Y 36 · 85
Z 37 ( 86
Å 38 ) 87
Ä 39 * 88
Ö 40 + 89
a 41 , 90
á 42 - 91
ê 48 = 97
Communication information
ë 49 > 98
Modbus Instance no/DeviceNet no: 43310
f 50 ? 99 Profibus slot/index 169/214
g 51 @ 100 EtherCAT and CANopen index (hex) 4cee
Profinet IO index 19694
h 52 ^ 101 Long, 1=1 rpm,
i 53 _ 102 1 %,1 °C or
Fieldbus format 0.001 if Process
í 54 ° 103 Value/Process Ref
using a [322] unit
j 55 2 104 Modbus format EInt
k 56 3 105
l 57 Process Max [325]
This menu is not visible when speed, torque or frequency is
Example: selected. The function sets the value of the maximum
Create a user unit named kPa. process value allowed.
1. When in the menu [323] press to show the cur-
sor. 325 Process Max
2. Press to move the cursor to the right most posi-
NEXT
Default: 0
tion.
3. Press until the character a is displayed. Range: 0.000-10000
4. Press .
5. Then press the until P is displayed and press Communication information
. Modbus Instance no/DeviceNet no: 43311
6. Repeat until you have entered kPa, confirm with Profibus slot/index 169/215
. EtherCAT and CANopen index (hex) 4cef
Profinet IO index 19695
323 User Unit Long, 1=1 rpm,
1 %,1 °C or
Default: No characters shown Fieldbus format 0.001 if Process
Value/Process Ref
using a [322] unit
Communication information
Modbus format EInt
Modbus Instance no/DeviceNet no: 43304 - 43309
169/208 -
Profibus slot/index
169/213
EtherCAT and CANopen index (hex) 4ce8 - 4ced
Profinet IO index 19688 - 19693
Fieldbus format UInt
Modbus format UInt
Default: Linear
NOTE: If Speed, Torque or Frequency is chosen in
Linear 0 Process is linear related to speed/torque menu “[321] Proc Source”, menus [322]- [328] are
hidden.
Process is quadratic related to speed/
Quadratic 1
torque
327 F(Val) PrMin
Communication information Default: Min
Modbus Instance no/DeviceNet no: 43312
According to Min Speed setting in
Profibus slot/index 169/216 Min -1
[341].
EtherCAT and CANopen index (hex) 4cf0
Profinet IO index 19696 According to Max Speed setting in
Max -2
Fieldbus format UInt [343].
Modbus format UInt 0.000-10000 0-10000 0.000-10000
Communication information
Process
unit Modbus Instance no/DeviceNet no: 43313
Process
Max Profibus slot/index 169/217
[325] EtherCAT and CANopen index (hex) 4cf1
Profinet IO index 19697
Long, 1=1 rpm,
Fieldbus format
1%
Modbus format EInt
Ratio=Linear
F(Value), Process Max [328]
This function is used for scaling if no sensor is used. It offers
Ratio=Quadratic you the possibility of increasing the process accuracy by
scaling the process values. The process values are scaled by
Process linking them to known data in the AC drive. With F(Value),
Min Speed Proc Max the precise value at which the entered “Process
[324] Min Max
Speed Speed Max [525]” is valid can be entered.
[341] [343]
rpm
Nominal
Linear 100% nMOT
Speed
F(Value
PrMin 150 Max Speed 80% nMOT
[327]
Bottles/s
10 100
Process Min [324] Process Max [325]
Communication information
Modbus Instance no/DeviceNet no: 43104
Profibus slot/index 169/8
EtherCAT and CANopen index (hex) 4c20
Profinet IO index 19488
Fieldbus format Long, 1=0.01 s
Modbus format EInt
Communication information
time
Modbus Instance no/DeviceNet no: 43106
Profibus slot/index 169/10
EtherCAT and CANopen index (hex) 4c22
Profinet IO index 19490
Fieldbus format Long, 1=0.01 s
Fig. 112 Calculation example of accelerating times
(graphics not proportional). Modbus format EInt
Start
Open
Mechanical
Brake Closed
Brake Relay On
Output
Off
Action must take place within
these time intervals
NOTE: This function is designed to operate a mechanical brake via the digital outputs or relays (set to brake function)
controlling a mechanical brake.
Communication information
33H Brk Fault
Modbus Instance no/DeviceNet no: 43114
Profibus slot/index 169/18 Default: 1.00s
EtherCAT and CANopen index (hex) 4c2a
Profinet IO index 19498 Range 0.00 - 5.00s
Fieldbus format Long, 1=0.01 s
Modbus format EInt Communication information
Modbus Instance no/DeviceNet no: 43117
Profibus slot/index 169/21
Wait Before Brake Time [33F]
EtherCAT and CANopen index (hex) 4c2d
The brake wait time is the time to keep brake open and to Profinet IO index 19501
hold the load, either in order to be able to speed up Fieldbus format Long, 1=0.01s
immediately, or to stop and engage the brake. Modbus format EInt
33F Brk Wait Note: The Brake Fault trip time should be set to
Default: 0.00 s longer time than the Brake release time[33C].
Range: 0.00–30.0 s
The “Brake not engaged” warning is using the setting of
parameter “Brake Engaged time [33E]”.
Fig. 116 shows principle of brake operation for fault during
run (left) and during stop (right).
Default: 0%
Range -400% to 400%
Communication information
Modbus Instance no/DeviceNet no: 43118
Profibus slot/index 169/22
EtherCAT and CANopen index (hex) 4c2e
Profinet IO index 19502
Fieldbus format Long, 1=1%
Modbus format EInt
Brake Brake
release time release time Brake wait Brake engage
33C 33C time time
33F 33E
Start
Running
*
Torque
Speed>0
Brake relay
Brake acknowledge
Brake Trip
<33H 33H <33H
Brake warning
**
During run Brake Fault trip time During stop
* Memorized load torque level, if function activated with parameter [33I] Release Torque.
** Time for operator to set down the load.
Fig. 116 Principle of Brake operation for fault during run and during stop
Communication information
NOTE: A lower speed value than the set minimum
Modbus Instance no/DeviceNet no: 43119 speed can be shown in the display due to motor slip.
Profibus slot/index 169/23
EtherCAT and CANopen index (hex) 4c2f
Communication information
Profinet IO index 19503
Modbus Instance no/DeviceNet no: 43121
Fieldbus format UInt
Profibus slot/index 169/25
Modbus format UInt
EtherCAT and CANopen index (hex) 4c31
Profinet IO index 19505
Fieldbus format Int, 1=1 rpm
Modbus format Int, 1=1 rpm
Speed
[342]
Min
speed
[341]
= Speed
= Reference
Fig. 117
346 SkipSpd 2 Lo
Default: 0 rpm
Communication information
345 SkipSpd 1 Hi
Modbus Instance no/DeviceNet no: 43127
Default: 0 rpm Profibus slot/index 169/31
Range: 0 – 4 x Sync Speed EtherCAT and CANopen index (hex) 4c37
Profinet IO index 19511
Fieldbus format Int, 1=1 rpm
Communication information
Modbus format Int, 1=1 rpm
Modbus Instance no/DeviceNet no: 43125
Profibus slot/index 169/29
EtherCAT and CANopen index (hex) 4c35
Profinet IO index 19509
Fieldbus format Int, 1=1 rpm
Modbus format Int, 1=1 rpm
Fig. 120 IxR Comp at Linear V/Hz curve On 2 Flux adjusted based on the torque
Communication information
IxR Comp_user [353]
Modbus Instance no/DeviceNet no: 43144
Only visible if User-Defined is selected in previous menu.
Profibus slot/index 169/48
EtherCAT and CANopen index (hex) 4c48
353 IxR CompUsr Profinet IO index 19528
Default: 0.0% Fieldbus format UInt
Modbus format UInt
Range: 0-25% x UNOM (0.1% of resolution)
Communication information U
%
Modbus Instance no/DeviceNet no: 43143 100
NOTE: The motor may be overheated at low speed. NOTE: Flux optimization works best at stable
Therefore it is important that the Motor I2t Current situations in slow changing processes.
[232] is set correctly.
Off 0 Off. No power limit After a stop, trip or power down, the AC
Volatile 0 drive will start always from zero speed (or
1 - 400 1 - 400 1 - 400% of motor nominal power minimum speed, if selected).
Non Volatile. After a stop, trip or power
NOTE: The maximum possible setting for parameter down of the AC drive, the reference value
at the moment of the stop will be
[355] is limited by INOM/IMOT x 120%, but not higher Non volatile 1
memorized. After a new start command
than 400%. the output speed will resume to this
saved value.
Communication information
Modbus Instance no/DeviceNet no: 43145 Communication information
Profibus slot/index 169/49 Modbus Instance no/DeviceNet no: 43131
EtherCAT and CANopen index (hex) 4c49 Profibus slot/index 169/35
Profinet IO index 19529 EtherCAT and CANopen index (hex) 4c3b
Fieldbus format Long, 1=1% Profinet IO index 19515
Modbus format EInt Fieldbus format UInt
Modbus format UInt
Motpot
UP
t
Motpot
DOWN
Table 35
NOTE: When Key Ref Mode is set to MotPot, the
Preset Preset Preset reference value ramp times are according to the “Acc
Output Speed
Ctrl3 Ctrl2 Ctrl1 MotPot [333]” and “Dec MotPot [334]” settings.
Actual speed ramp will be limited according to “Acc
0 0 0 Analogue reference Time [331]” and “Dec Time [332]”.
1)
0 0 1 Preset Ref 1
0 11) 0 Preset Ref 2
0 1 1 Preset Ref 3
1)
1 0 0 Preset Ref 4
1 0 1 Preset Ref 5
1 1 0 Preset Ref 6
1 1 1 Preset Ref 7
1)
= selected if only one preset reference is active
1 = active input
0 = non active input
+
input AnIn1, at the Control Panel [310] by using a Preset -
PID
Process
Reference, or via serial communication. The feedback signal feedback
(actual value) must be connected to an analogue input that
is set to the function Process Value.
Process
This function enables the PID controller and defines the Fig. 123 Closed loop PID control
response to a changed feedback signal.
PID I Time [384]
381 PID Control Setting the integration time for the PID controller.
Default: Off
Off 0 PID control deactivated. 384 PID I Time
The speed increases when the feedback Default: 1.00 s
On 1 value decreases. PID settings according to Range: 0.01–300 s
menus [381] to [385].
The speed decreases when the feedback Communication information
Invert 2 value decreases. PID settings according to
Modbus Instance no/DeviceNet no: 43157
menus [383] to [385].
Profibus slot/index 169/61
EtherCAT and CANopen index (hex) 4c55
Communication information Profinet IO index 19541
Modbus Instance no/DeviceNet no: 43154 Fieldbus format Long, 1=0.01 s
Profibus slot/index 169/58 Modbus format EInt
EtherCAT and CANopen index (hex) 4c52
Profinet IO index 19538
Fieldbus format UInt Process PID D Time [385]
Modbus format UInt Setting the differentiation time for the PID controller.
Communication information
Modbus Instance no/DeviceNet no: 43373
Profibus slot/index 170/22
EtherCAT and CANopen index (hex) 4d2d
Profinet IO index 19757
Fieldbus format Long, 1=0.01 s
Modbus format EInt
[389]
[310] Process Ref
[389]
time
[387] [388]
Normal PID
Steady state
test Stop/Sleep
NOTE: Used relays must be defined as Slave Pump or NOTE: This menu will NOT be active if only one drive
Master Pump. Used digital inputs must be defined as is selected.
Pump Feedback.
Communication information
394 Change Cond Modbus Instance no/DeviceNet no: 43165
Default: Both Profibus slot/index 169/69
EtherCAT and CANopen index (hex) 4c5d
The Runtime of the master drive
Profinet IO index 19549
determines when a master drive has to be
changed. The change will only take place Fieldbus format UInt, 1=1 h
after a: Modbus format UInt, 1=1 h
Stop 0
- Power Up
- Stop
- Standby condition Drives on Change [396]
- Trip condition. If a master drive is changed according to the timer function
The master drive will be changed if the (Change Condition=Timer/Both [394]), it is possible to
timer setting in Change Timer [395] has leave additional pumps running during the change
elapsed. The change will take place operation. With this function the change operation will be
immediately. So during operation the as smooth as possible. The maximum number to be
additional pumps will be stopped programmed in this menu depends on the number of
Timer 1 temporarily, the 'new' master will be additional drives.
selected according to the Run Time and
the additional pumps will be started again. Example:
It is possible to leave 2 pumps running If the number of drives is set to 6, the maximum value will
during the change operation. This can be be 4. This function is only active if “Select Drive [393]”=All.
set with Drives on Change [396].
The master drive will be changed if the 396 Drives on Ch
timer setting in Change Timer [395] has
elapsed. The 'new' master will be selected Default: 0
according to the elapsed Run Time. The Range: 0 to (the number of drives - 2)
Both 2 change will only take place after a:
- Power Up
- Stop Communication information
- Standby condition. Modbus Instance no/DeviceNet no: 43166
- Trip condition. Profibus slot/index 169/70
EtherCAT and CANopen index (hex) 4c5e
Communication information Profinet IO index 19550
Modbus Instance no/DeviceNet no: 43164 Fieldbus format UInt
Profibus slot/index 169/68 Modbus format UInt
EtherCAT and CANopen index (hex) 4c5c
Profinet IO index 19548
Fieldbus format UInt
Modbus format UInt
Example: Example:
Max Speed = 1500 rpm Max Speed = 1500 rpm
Min Speed = 300 rpm Min Speed = 300 rpm
Upper Band = 10% Lower Band = 10%
Start delay will be activated: Stop delay will be activated:
Range = Max Speed to Min Speed = 1500–300 = 1200 rpm Range = Max Speed - Min Speed = 1500–300 = 1200 rpm
10% of 1200 rpm = 120 rpm 10% of 1200 rpm = 120 rpm
Start level = 1500–120 = 1380 rpm Start level = 300 + 120 = 420 rpm
Default: 0s
39B Upp Band Lim
Range: 0-999 s
Default: 0%
Communication information
Min
Modbus Instance no/DeviceNet no: 43170
Profibus slot/index 169/74
Flow/Pressure
EtherCAT and CANopen index (hex) 4c62 Start Delay [399]
Profinet IO index 19554 (NG_50-PC-14_2)
Max
In general:
Trans • If the additional pump has 'slow' start/stop dynamics,
then a higher transition speed should be used.
Master pump • If the additional pump has 'fast' start/stop dynamics,
Min
then a lower transition speed should be used.
Flow/Pressure
Actual start
command of next 39G TransS Stop
pump (RELAY) (NG_50-PC-16_1) Default: 60%
Fig. 131 Transition speed start Range: 0-100% of total min speed to max speed
Communication information
Flow/Pressure
Transition speed Modbus Instance no/DeviceNet no: 43176
decreases overshoot Profibus slot/index 169/80
EtherCAT and CANopen index (hex) 4c68
Profinet IO index 19560
Fieldbus format Long, 1=1%
Modbus format EInt
Time
NOTE: If set to 0 %, the transition speed when
Fig. 132 Effect of transition speed stopping pumps, is ignored and no speed adaption is
made.
I.e. the slave pump is stopped directly and speed of
Settle Time Stop [39F] the master pump is continued.
The settle stop allows the process to settle after a pump is
switched off before the pump control continues. If an
additional pump is stopped D.O.L. (Direct On Line) or Y/ Example
Δ , the flow or pressure can still fluctuate due to the 'rough' Max Speed = 1500 rpm
start/stop method. This could cause unnecessary starting Min Speed = 200 rpm
and stopping of additional pumps. TransS Start = 60%
When less additional pumps are needed, the speed will be
During the Settle stop: controlled up to min speed + (60% x (1500 rpm - 200
• PID controller is off.
rpm)) = 200 rpm + 780 rpm = 980 rpm. When this speed is
• the speed is kept at a fixed level after stopping a pump reached, the additional pump with the highest run time
hours will be switched off.
39F Settle Stop
Speed
Default: 0s Actual shut down of pump
Communication information
Modbus Instance no/DeviceNet no: 43175 Trans
Profibus slot/index 169/79
EtherCAT and CANopen index (hex) 4c67 Actual
Profinet IO index 19559 Min
Additional pump
Fieldbus format Long, 1=1 s
Flow/Pressure
Modbus format EInt Switch off procedure starts
Communication information
Alarm Select [411]
Modbus Instance no/DeviceNet no: 43323
Selects the types of alarms that are active.
Profibus slot/index 169/227
EtherCAT and CANopen index (hex) 4cfb
411 Alarm Select Profinet IO index 19707
Default: Off Fieldbus format UInt
Modbus format UInt
Off 0 No alarm functions active.
Min Alarm active. The alarm output
Min 1 Alarm Start Delay [414]
functions as an underload alarm.
Max Alarm active. The alarm output This parameter is used if, for example, you want to override
Max 2 an alarm during the start-up procedure.
functions as an overload alarm.
Both Max and Min alarm are active. The Sets the delay time after a run command, after which the
Max+Min 3 alarm outputs function as overload and alarm may be given.
underload alarms. • If Ramp Alarm=On. The start delay begins after a RUN
command.
Communication information • If Ramp Alarm=Off. The start delay begins after the
Modbus Instance no/DeviceNet no: 43321 acceleration ramp.
Profibus slot/index 169/225
EtherCAT and CANopen index (hex) 4cf9
414 Start Delay
Profinet IO index 19705
Fieldbus format UInt Default: 2s
Modbus format UInt Range: 0-3600 s
Communication information
Modbus Instance no/DeviceNet no: 43322
Profibus slot/index 169/226
EtherCAT and CANopen index (hex) 4cfa
Profinet IO index 19706
Fieldbus format UInt
Modbus format UInt
Communication information
Modbus Instance no/DeviceNet no: 43326
[41D] Min Abs Margine
Profibus slot/index 169/230
EtherCAT and CANopen index (hex) 4cfe
Profinet IO index 19710
Fieldbus format Long, 1=1%
Modbus format Eint
Speed
Communication information
Modbus Instance no/DeviceNet no: 43334
Profibus slot/index 169/238
EtherCAT and CANopen index (hex) 4d06
Profinet IO index 19718
Fieldbus format UInt
Modbus format UInt
Fig. 136
Communication information
Modbus Instance no/DeviceNet no: 43361
Profibus slot/index 170/10
EtherCAT and CANopen index (hex) 4d21
Profinet IO index 19745
Fieldbus format UInt
Modbus format UInt
DC link voltage
Override
level
Low Volt.
level
Speed
t
(06-F60new) t
Communication information
Modbus Instance no/DeviceNet no: 43363
Profibus slot/index 170/12
EtherCAT and CANopen index (hex) 4d23
Profinet IO index 19747
Fieldbus format UInt
Modbus format UInt
Default: 4-20 mA
Dependent on Setting of switch S1
The current input has a fixed threshold 100 %
The voltage input has a fixed threshold Fig. 139 Normal full-scale configuration
2–10V 5 (Live Zero) of 2 V and controls the full
range for the input signal. See Fig. 81.
The scale of the voltage controlled input,
that controls the full range for the input
User V 6
signal. Can be defined by the advanced
AnIn Min and AnIn Max menus.
Sets the input for a bipolar voltage input,
User Bipol where the scale controls the range for the
7
V input signal. Scale can be defined in
advanced menu AnIn Bipol.
Ref
Special function: Inverted reference signal
2V 10 V
0
4mA 2 0mA
If the AnIn minimum value is higher than the AnIn
maximum value, the input will act as an inverted reference
Fig. 140 2–10 V/4–20 mA (Live Zero) input, see Fig. 141.
100 %
Parameter to set the minimum value of the external Fig. 141 Inverted reference
reference signal. Only visible if [512] = User mA/V.
AnIn1 Bipol [5133]
5131 AnIn1 Min This menu is automatically displayed if AnIn1 Setup is set to
User Bipol mA or User Bipol V. The window will
Default: 0 V/4.00 mA
automatically show mA or V range according to selected
0.00–20.00 mA function. The range is set by changing the positive
Range:
0–10.00 V maximum value; the negative value is automatically adapted
accordingly. Only visible if [512] = User Bipol mA/V. The
Communication information inputs RunR and RunL input need to be active, and
Modbus Instance no/DeviceNet no: 43203 “Rotation [219]”, must be set to “R+L”, to operate the
Profibus slot/index 169/107 bipolar function on the analogue input.
EtherCAT and CANopen index (hex) 4c83
Profinet IO index 19587 5133 AnIn1 Bipol
Long, 1=0.01 mA,
Fieldbus format Default: 10.00 V/20.00 mA
0.01 V
Modbus format EInt Range: 0.0–20.0 mA, 0.00–10.00 V
Table 36 shows corresponding values for the min and max Communication information
selections depending on the function of the analogue input Modbus Instance no/DeviceNet no: 43207
[511]. Profibus slot/index 169/111
EtherCAT and CANopen index (hex) 4c87
Table 36 Profinet IO index 19591
Fieldbus format UInt
AnIn Function Min Max
Modbus format UInt
Speed Min Speed [341] Max Speed [343]
Torque 0% Max Torque [351] AnIn1 Function Value Max [5137]
With AnIn1 Function VaMax you define a user-defined
Process Ref Process Min [324] Process Max [325] value for the signal. Only visible when user-defined is
Process Value Process Min [324] Process Max [325] selected in menu [5136].
Default: Add+
513A AnIn1 Enabl
Analogue signal is added to selected
Add+ 0 Default: On
function in menu [511].
Analogue signal is subtracted from On 0 AnIn1 is always active
Sub- 1
selected function in menu [511]. !DigIn 1 AnIn1 is only active if the digital input is low.
AnIn1 is only active if the digital input is
Communication information DigIn 2
high.
Modbus Instance no/DeviceNet no: 43208
Profibus slot/index 169/112 Communication information
EtherCAT and CANopen index (hex) 4c88
Modbus Instance no/DeviceNet no: 43210
Profinet IO index 19592
Profibus slot/index 169/114
Fieldbus format UInt
EtherCAT and CANopen index (hex) 4c8a
Modbus format UInt
Profinet IO index 19594
Fieldbus format UInt
AnIn1 Filter [5139] Modbus format UInt
If the input signal is unstable (e.g. fluctuation reference
value), the filter can be used to stabilize the signal. A change
of the input signal will reach 63% on AnIn1 within the set AnIn2 Function [514]
AnIn1 Filter time. After 5 times the set time, AnIn1 will Parameter for setting the function of Analogue Input 2.
have reached 100% of the input change. See Fig. 142.
Same function as “AnIn1 Fc [511]”.
Communication information
Modbus Instance no/DeviceNet no: 43212
T 5XT
Profibus slot/index 169/116
EtherCAT and CANopen index (hex) 4c8c
Fig. 142
Profinet IO index 19596
Fieldbus format UInt
Modbus format UInt
Communication information
Digital Input 1 [521]
43233–43240,
To select the function of the digital input.
Modbus Instance no/DeviceNet no: 43544,
43554 On the standard control board there are eight digital inputs.
169/137–144,
Profibus slot/index 170/193, If the same function is programmed for more than one input
170/203 that function will be activated according to “OR” logic if
4ca1 - 4ca8, nothing else is stated.
EtherCAT and CANopen index (hex) 4dd8,
4de2
521 DigIn 1
19617-19624,
Profinet IO index 19928, Default: RunL
19938
Off 0 The input is not active.
Fieldbus format
See [5131] - [5137].
Modbus format Be aware that if there is nothing
connected to the input, the AC drive will
trip at “External trip” immediately.
Ext. Trip 3
NOTE: The External Trip is active low.
NOTE: Activated according to “AND”
logic.
Stop command according to the selected
Stop mode in menu [33B].
Stop 4 NOTE: The Stop command is active low.
NOTE: Activated according to “AND”
logic.
Enable command. General start condition
to run the AC drive. If made low during
running the output of the AC drive is cut
off immediately, causing the motor to
coast to zero speed.
Enable 5
NOTE: If none of the digital inputs are
programmed to “Enable”, the internal
enable signal is active.
NOTE: Activated according to “AND”
logic.
Run Right command (positive speed). The
RunR 6 output of the AC drive will be a
clockwise rotary field.
Run Left command (negative speed). The
RunL 7 output of the AC drive will be a
counter-clockwise rotary field.
Reset command. To reset a Trip condition
Reset 9
and to enable the Autoreset function.
Preset Ctrl1 10 To select the Preset Reference.
Preset Ctrl2 11 To select the Preset Reference.
Preset Ctrl3 12 To select the Preset Reference.
Increases the internal reference value
according to the set AccMotPot time
MotPot Up 13
[333]. Has the same function as a “real”
motor potentiometer, see Fig. 122.
Decreases the internal reference value
MotPot
14 according to the set DecMotPot time
Down
[334]. See MotPot Up.
Default: Min
Min 0 Min value
AnOut1 Function Value Min [5335]
With AnOut1 Function VaMin you define a user-defined
Max 1 Max value value for the signal. Only visible when user-defined is
User-defined 2 Define user value in menu [5335] selected in menu [5334].
Table 38 shows corresponding values for the min and max 5335 AnOut1VaMin
selections depending on the function of the analogue output Default: 0.000
[531].
Range: -10000.000–10000.000
Table 38
Communication information
AnOut Modbus Instance no/DeviceNet no: 43545
Min Value Max Value
Function
Profibus slot/index 170/194
Process Value Process Min [324] Process Max [325] EtherCAT and CANopen index (hex) 4dd9
Profinet IO index 19929
Speed Min Speed [341] Max Speed [343]
Long, 1=1 rpm, 1 %, 1W,
Torque 0% Max Torque [351] 0.1 Hz, 0.1 V, 0.1 A or
Fieldbus format
0.001 via process value
Process Ref Process Min [324] Process Max [325] [322]
Shaft Power 0% Motor Power [223] Modbus format EInt
Communication information
Communication information
Modbus Instance no/DeviceNet no: 43262
Modbus Instance no/DeviceNet no: 43555 Profibus slot/index 169/166
Profibus slot/index 170/204 EtherCAT and CANopen index (hex) 4cbe
EtherCAT and CANopen index (hex) 4de3 Profinet IO index 19646
Profinet IO index 19939 Fieldbus format UInt
Long, 1=1 rpm, 1 %, 1W, Modbus format UInt
0.1 Hz, 0.1 V, 0.1 A or
Fieldbus format
0.001 via process value
[322]
Modbus format EInt
AnOut2 Advanced [536]
Same functions and submenus as under AnOut1 Advanced
[533].
AnOut2 Function [534]
Sets the function for the Analogue Output 2. 536 AnOut2 Advan
External Fan 81
The AC drive requires external 542 DigOut2
cooling. Internal fans are active.
Default: Brake
LC Pump 82 Activate liquid cooling pump
Selection: Same as in menu [541]
Activate liquid cooling heat
LC HE Fan 83
exchanger fan
Communication information
LC Level 84 Liquid cooling low level signal active Modbus Instance no/DeviceNet no: 43272
Positive speed (>0.5%), i.e. forward/ Profibus slot/index 169/176
Run Right 85
clockwise direction. EtherCAT and CANopen index (hex) 4cc8
Negative speed (<0.5%), i.e. reverse Profinet IO index 19656
Run Left 86 Fieldbus format UInt
counter clockwise direction.
Modbus format UInt
Com Active 87 Fieldbus communication active.
Brk Fault 88 Tripped on brake fault (not released)
Warning and continued operation
BrkNotEngag
89 (keep torque) due to Brake not
e
engaged during stop.
Failure occurred in built-in option
Option 90
board.
CA3 91 Analogue comparator 3 output
NOTE: Additional relays will become available when I/ Selection: Same as in menu [541]
O option boards are connected. Maximum 3 boards
with 3 relays each. Communication information
Modbus Instance no/DeviceNet no: 43275
Profibus slot/index 169/179
Relay 1 [551] EtherCAT and CANopen index (hex) 4ccb
Sets the function for the relay output 1. Same function as Profinet IO index 19659
digital output 1 [541] can be selected. Fieldbus format UInt
Modbus format UInt
551 Relay 1
Default: Trip Board Relay [554] to [55C]
Selection: Same as in menu [541] These additional relays are only visible if an I/O option
board is fitted in slot 1, 2, or 3. The outputs are named B1
Communication information Relay 1–3, B2 Relay 1–3 and B3 Relay 1–3. B stands for
board and 1–3 is the number of the board which is related to
Modbus Instance no/DeviceNet no: 43273
the position of the I/O option board on the option
Profibus slot/index 169/177
mounting plate.
EtherCAT and CANopen index (hex) 4cc9
Profinet IO index 19657
Fieldbus format UInt NOTE: Visible only if optional board is detected or if
Modbus format UInt
any input/output is activated.
Communication information
Relay 2 [552] Modbus Instance no/DeviceNet no: 43511–43519
Profibus slot/index 170/160–170/168
NOTE: The definitions described here are valid for the EtherCAT and CANopen index (hex) 4db7 - 4dbf
active output condition. Profinet IO index 19895 - 19903
Fieldbus format UInt
Sets the function for the relay output 2. Modbus format UInt
Communication information
Modbus Instance no/DeviceNet no: 43281
Profibus slot/index 169/185
EtherCAT and CANopen index (hex) 4cd1
Profinet IO index 19665
Fieldbus format UInt
Modbus format UInt
Communication information
Level High[6112]
Modbus Instance no/DeviceNet no: 43401
Signal Profibus slot/index 170/50
An Value [6111] AND EtherCAT and CANopen index (hex) 4d49
CA1
Profinet IO index 19758
Level Low [6113] Fieldbus format UInt
Modbus format UInt
destination RUN.
The reference signal passes the Level HI The reference signal passes the Level HI
value from above (negative edge), the value from above (signal inside Window
3 3
comparator CA1 does not change, output band), the comparator CA1 output is set
stays high. high.
The reference signal passes the Level LO The reference signal passes the Level LO
4 value from above (negative edge), the value from above (signal outside Window
4
comparator CA1 is reset, output is set low. band), the comparator CA1 is reset, output is
set low.
The reference signal passes the Level LO
value from below (positive edge), the The reference signal passes the Level LO
5 value from below (signal inside Window
comparator CA1 does not change, output 5
stays low. band), the comparator CA1 output is set
high.
The reference signal passes the Level HI
6 value from below (positive edge), the The reference signal passes the Level HI
comparator CA1 output is set high. value from below (signal outside Window
6
band),the comparator CA1 is reset, output is
set low.
The reference signal passes the Level HI
value from above (negative edge), the
7 The reference signal passes the Level HI
comparator CA1 does not change, output
stays high. value from above (signal inside Window
7
band), the comparator CA1 output is set
high.
The reference signal passes the Level LO
8 value from above (negative edge), the
The reference signal passes the Level LO
comparator CA1 is reset, output is set low.
value from above (signal outside Window
8
band), the comparator CA1 is reset, output is
set low.
Default: Hysteresis
6141 CA4 Value
Hysteresis 0 Hysteresis type comparator
Default: Process Error
Window 1 Window type comparator
Selections: Same as in menu [6111]
Communication information
Modbus Instance no/DeviceNet no: 43483 Communication information
Profibus slot/index 170/132 Modbus Instance no/DeviceNet no: 43474
EtherCAT and CANopen index (hex) 4d9b Profibus slot/index 170/123
Profinet IO index 19867 EtherCAT and CANopen index (hex) 4d92
Fieldbus format UInt Profinet IO index 19858
Modbus format UInt Fieldbus format UInt
Modbus format UInt
Communication information
Communication information
Modbus Instance no/DeviceNet no: 43489
Modbus Instance no/DeviceNet no: 43476
Profibus slot/index 170/138
Profibus slot/index 170/125
EtherCAT and CANopen index (hex) 4da1
EtherCAT and CANopen index (hex) 4d94
Profinet IO index 19873
Profinet IO index 19860
Fieldbus format UInt
Long,
1=1 W, 0.1 A, 0.1 V, Modbus format UInt
Fieldbus format 0.1 Hz, 0.1°C, 1 kWh,
1H, 1%, 1 rpm or 0.001
via process value
Modbus format EInt
Selection: Same selections as for “DigOut 1 [541]”. Selection: Same selections as for “DigOut 1 [541]”.
6152 CD 2
Default: DigIn 1
Selection: Same selections as for “DigOut 1 [541]”.
Communication information
Modbus Instance no/DeviceNet no: 43408
Profibus slot/index 170/57
EtherCAT and CANopen index (hex) 4d50
Profinet IO index 19792
Fieldbus format UInt
Modbus format UInt
0 0 0 0 0 !A2 3
0 1 0 1 1 CD1 4
!D1 5
1 0 0 1 1
CD2 6
1 1 1 1 0
!D2 7
The output signal can be programmed to the digital or relay LZ/LY 8
outputs or used as a Virtual Connection Source [560]. !LZ/!LY 9
T1 10
620 LOGIC Y
!T1 11
Stp CA1&!A2&CD1
T2 12
!T2 13
The expression must be programmed by means of the
menus [621] to [625]. CA3 14
!A3 15
Example:
CA4 16
Broken belt detection for Logic Y
!A4 17
This example describes the programming for a so-called
“broken belt detection” for fan applications. CD3 18
The expression must be programmed by means of the Selection: Same as menu [621]
menus [631] to [635].
Communication information
Z Comp 1 [631] Modbus Instance no/DeviceNet no: 43423
Profibus slot/index 170/72
Selects the first comparator for the logic Z function.
EtherCAT and CANopen index (hex) 4d5f
Profinet IO index 19807
631 Z Comp 1 Fieldbus format UInt
Default: CA1 Modbus format UInt
643 Timer1Delay
Default: 0:00:00 (hr:min:sec)
Range: 0:00:00–9:59:59
Timer1 Trig
Communication information
T1Q
43433 hours
Modbus Instance no/DeviceNet no: 43434 minutes
Timer1 T2 Timer1 T1 Timer1 T2 Timer1 T1
43435 seconds
170/82, 170/83,
Fig. 152 Profibus slot/index
170/84
EtherCAT and CANopen index (hex) 4d69, 4d6a, 4d6b
Timer 1 Trig [641] Profinet IO index 19817, 19818, 19819
Fieldbus format UInt, 1=1 h/m/s
Selection of the Timer input trigger signal.
Modbus format UInt, 1=1 h/m/s
Communication information
Modbus Instance no/DeviceNet no: 43431
Profibus slot/index 170/80
EtherCAT and CANopen index (hex) 4d67
Profinet IO index 19815
Fieldbus format UInt
Modbus format UInt
Communication information
Modbus Instance no/DeviceNet no: 43452
Profibus slot/index 170/101
EtherCAT and CANopen index (hex) 4d7c
Profinet IO index 19836
Fieldbus format UInt
Modbus format UInt
Timer 2 T1 [654]
11.8.6 Counters [660]
654 Timer 2 T1 Counter functions for counting pulses and signalling on
digital output when counter reaches specified high and low
Default: 0:00:00, hr:min:sec limit levels.
Range: 0:00:00–9:59:59 The counter is counting up on positive flanks on the
triggered signal, the counter is cleared as long as the Reset
signal is active.
Communication information
The counter can be automatically decremented with
43456 hours specified decrement time, if no new trigger signal has
Modbus Instance no/DeviceNet no: 43457 minutes
occurred within the decrement time.
43458 seconds
The counter value is clamped to the high limit value and the
170/105, 170/106,
Profibus slot/index
170/107 digital output function (C1Q or C2Q) is active when
EtherCAT and CANopen index (hex) 4d80, 4d81, 4d82 counter value equals high limit value.
Profinet IO index 19840, 19841, 19842 See Fig. 153 for more information of the counters.
Fieldbus format UInt, 1=1 h/m/s
Modbus format UInt, 1=1 h/m/s
6619
6613
6614
Timer 2 T2 [655]
6615
655 Timer 2 T2 6611
6612
Default: 0:00:00, hr:min:sec
541
Range: 0:00:00–9:59:59
541 = Digital Out 1 function
6611= Counter 1 trigger
Communication information 6612= Counter 1 reset
6613= Counter 1 High value
43459 hours 6614= Counter 1 Low value
6615= Counter 1 Decrement timer
Modbus Instance no/DeviceNet no: 43460 minutes 6619= Counter 1 value
43461 seconds
170/108, 170/109,
Profibus slot/index Fig. 153 Counters, operating principle.
170/110
EtherCAT and CANopen index (hex) 4d83, 4d84, 4d85
Profinet IO index 19843, 19844, 19845
Fieldbus format UInt, 1=1 h/m/s
Modbus format UInt, 1=1 h/m/s
NOTE: Counter 1 value is common for all parameter 6623 C2 High Val
sets.
Default: 0
Range: 0 - 10000
NOTE: The value is volatile and lost at power down.
Communication information
6619 C1 Value Modbus Instance no/DeviceNet no: 43583
Default: 0 Profibus slot/index 170/232
EtherCAT and CANopen index (hex) 4dff
Range: 0 - 10000
Profinet IO index 19967
Fieldbus format Long, 1=1
Communication information Modbus format EInt
Modbus Instance no/DeviceNet no: 42927
Profibus slot/index 168/86 Counter 2 Low value [6624]
EtherCAT and CANopen index (hex) 4b6f Function is identical to Counter 1 Low value [6614].
Profinet IO index 19311
Fieldbus format UInt, 1=1
6624 C2 Low Val
Modbus format UInt
Default: 0
Communication information
Modbus Instance no/DeviceNet no: 43582
Profibus slot/index 170/231
EtherCAT and CANopen index (hex) 4dfe
Profinet IO index 19966
Fieldbus format UInt
Modbus format UInt
Communication information
Modbus Instance no/DeviceNet no: 43600
Profibus slot/index
EtherCAT and CANopen index (hex)
Profinet IO index
Fieldbus format
Modbus format
6712 Clk1TimeOff
Default: 0:00:00 (hours:minutes:seconds)
Range: 0:00:00–23:59:59
Communication information
Modbus Instance no/DeviceNet no: 43603
Profibus slot/index
EtherCAT and CANopen index (hex)
Profinet IO index
Fieldbus format
Modbus format
Communication information
Process Value [711]
31003 Nm
The process value is showing the process actual value, Modbus Instance no/DeviceNet no:
31004 %
depending on selection done in chapter, Process Source 121/147
Profibus slot/index
[321]. 121/148
23eb Nm
EtherCAT and CANopen index (hex)
23ec %
711 Process Val
1003 Nm
Profinet IO index
Depends on selected Pocess source [321] 1004 %
Unit
and Process Unit [322]. Long, 1=0.1 Nm
Fieldbus format
Long, 1=1 %
Speed: 1 rpm, 4 digits
Resolution Modbus format EInt
Other units: 3 digits
Communication information
Speed [712] Modbus Instance no/DeviceNet no: 31005
Displays the actual shaft speed. Profibus slot/index 121/149
EtherCAT and CANopen index (hex) 23ed
712 Speed Profinet IO index 1005
Fieldbus format Long, 1=1W
Unit: rpm
Modbus format EInt
Resolution: 1 rpm, 4 digits
Communication information
Modbus Instance no/DeviceNet no: 31002
Profibus slot/index 121/146
EtherCAT and CANopen index (hex) 23ea
Profinet IO index 1002
Fieldbus format Int, 1=1 rpm
Modbus format Int, 1=1 rpm
Unit: kW
Communication information
Resolution: 1W
Modbus Instance no/DeviceNet no: 31009
Profibus slot/index 121/153
Communication information EtherCAT and CANopen index (hex) 23f1
Modbus Instance no/DeviceNet no: 31006 Profinet IO index 1009
Profibus slot/index 121/150 Fieldbus format Long, 1=0.1 Hz
EtherCAT and CANopen index (hex) 23ee Modbus format EInt
Profinet IO index 1006
Fieldbus format Long, 1=1W
Modbus format EInt DC Link Voltage [719]
Displays the actual DC link voltage.
Unit: A
Communication information
Resolution: 0.1 A
Modbus Instance no/DeviceNet no: 31010
Profibus slot/index 121/154
Communication information EtherCAT and CANopen index (hex) 23f2
Modbus Instance no/DeviceNet no: 31007 Profinet IO index 1010
Profibus slot/index 121/151 Fieldbus format Long, 1=0.1 V
EtherCAT and CANopen index (hex) 23ef Modbus format EInt
Profinet IO index 1007
Fieldbus format Long, 1=0.1 A
Modbus format EInt Heatsink Temperature [71A]
Displays the actual heatsink temperature, measured. The
signal is generated by a sensor in the IGBT module.
Output Voltage [717]
Displays the actual output voltage. 71A Heatsink Tmp
Unit: °C
717 Output Volt
Resolution: 0.1°C
Unit: V
Resolution: 0.1 V Communication information
Modbus Instance no/DeviceNet no: 31011
Communication information Profibus slot/index 121/155
Modbus Instance no/DeviceNet no: 31008 EtherCAT and CANopen index (hex) 23f3
Profibus slot/index 121/152 Profinet IO index 1011
EtherCAT and CANopen index (hex) 23f0 Fieldbus format Long, 1=0.1 °C
Profinet IO index 1008 Modbus format EInt
Fieldbus format Long, 1=0.1 V
Modbus format EInt
Communication information
Modbus Instance no/DeviceNet no: 31015
Profibus slot/index 121/159
EtherCAT and CANopen index (hex) 23f7
Profinet IO index 1015
Fieldbus format UInt
Modbus format UInt
Communication information
Modbus Instance no/DeviceNet no: 31017
Profibus slot/index 121/161
EtherCAT and CANopen index (hex) 23f9
Profinet IO index 1017
Fieldbus format UInt,
bit 0=DigIn1,
Modbus format
bit 7=DigIn8
Examples:
FDU48-046-5XAC drive-series
- suited for 380-480 volt mains supply, and a
- rated output current of 46 A.
- IP Class = IP54 and IP55 (2X = IP20/21)
Software [922]
Shows the software version number of the AC drive.
Fig. 161 gives an example of the version number.
922 Software
Stp V 4.32 -
Fig. 161 Example of software version
Communication information
NOTE: It is important that the software version
displayed in menu [922] is the same software version Modbus Instance no/DeviceNet no: 42301–42312
number as the software version number written on Profibus slot/index 165/225–236
the title page of this instruction manual. If not, the EtherCAT and CANopen index (hex) 48fd - 4908
functionality as described in this manual may differ Profinet IO index 18685 - 18696
from the functionality of the AC drive. Fieldbus format UInt
Modbus format UInt
Build Info [9221]
Software version created, Date and time. When sending a unit name you send one character at a time
starting at the right most position.
924 Bluetooth ID
Default: NA
Communication information
11.12.1 Real Time clock
42604, 42605,
In the 4 line Control panel (PPU) there is a built-in Real Modbus Instance no/DeviceNet no:
42606 (Y,M,D)
time clock. This means that actual date and time will be 167/18,167/19,
shown at e.g. a trip condition. There is a built-in capacitor Profibus slot/index
167/20
to be able to keep the clock running if the power disappear. EtherCAT and CANopen index (hex) 4a2c, 4a2d, 4a2e
In case of loss of power, the backup time for the Real time 18988, 18989,
Profinet IO index
clock function is at least 60 days. 18990
Fieldbus format Long, 1=1 Y/M/D
Actual date and time will be set from factory. Date and time
Modbus format EInt
is shown and can be set in following menus.
Clock [930]
This menu group displays actual time and date, read only. Weekday [933]
Time and date are factory set to CET (Central European Display of actual weekday, read only.
mean time). Adjust if required in following sub-menus.
933 Weekday
930 1240rpm
Clock Default: Monday
2017-01-23 12:34.40 Monday 0
Run Key/Key
Tuesday 1
Wednesday 2
Time [931]
Thursday 3
Actual time, displayed as HH:MM:SS. Adjustable setting.
Friday 4
931 Time Saturday 5
Default: 00:00:00 Sunday 6
“Soft Trip”
• the AC drive stops by decelerating to a standstill.
During the deceleration.
• The accompanying trip message is displayed, including
an additional soft trip indicator “S” before the trip time.
• The Trip LED is flashing.
• The Warning relay or output is active (if selected).
After standstill is reached.
• The Trip LED is on.
• The Trip relay or output is active (if selected).
• The “TRP” status indication is displayed (area D of the
display).
• After reset command, the trip message will disappear and
menu [100] will be indicated.
Apart from the TRIP indicators there are two more
indicators to show that the inverter is in an “abnormal”
situation.
WARNING!
Always switch the mains voltage off if it is
necessary to open the AC drive and wait at
least 7 minutes to allow the capacitors to
discharge.
WARNING!
In case of malfunctioning always check the
DC-link voltage, or wait one hour after the
mains voltage has been switched off, before
dismantling the AC drive for repair.
The connections for the control signals and the switches are
isolated from the mains voltage. Always take adequate
precautions before opening the AC drive.
830 OVERVOLT G
Trp A 345:45:12
Fig. 163 Control panel with 4-line display. 01-6878-10 PPU with Bluetooth (size B)
01-6879-00 Standard PPU (size C)
The display is back lit and consists of 4 rows, each with
01-6879-10 PPU with Bluetooth (size C)
space for 20 characters. The Control panel is equipped with
real time clock function. This means that actual date and 01-6880-00 Standard PPU (size D and up)
time will be shown at e.g. a trip condition. 01-6880-10 PPU with Bluetooth (size D and up)
There is also an optional Control panel with Bluetooth
communication available for connection with cellphone or
tablet.
Frame WARNING!
Part Number Current (dimension)
size The table gives the minimum values of the
brake resistors. Do not use resistors lower
01-4601-21 3 - 6 A (M16 - M20)
than this value. The AC drive can trip or even
01-4601-22 8 - 10 A (M16 - M25) B be damaged due to high braking currents.
01-4601-23 13 - 18 A (M16 - M32)
01-4399-01 26 - 31 A (M12 - M32) The following formula can be used to define the power of
C the connected brake resistor:
01-4399-00 37 - 46 A (M12 - M40)
01-4833-00 61 - 74 A (M20 - M50) D (Brake level VDC)2
Presistor = x ED
01-7248-00 2 - 10 A (M20 - M25) C69 Rmin
01-7248-10 13 - 25 A (M20 - M32) C69
Where:
01-7247-00 33 - 58 A (M20 - M40) D69
Presistor required power of brake resistor
Brake level VDC brake voltage level (see Table 45)
13.6 EmoSoftCom Rmin minimum allowable brake resistor
EmoSoftCom is an optional software that runs on a personal (see Table 46, Table 47 and Table 48)
computer. It can also be used to load parameter settings
from the AC drive to the PC for backup and printing. ED effective braking period. Defined as:
Recording can be made in oscilloscope mode. Please contact
CG Drives & Automation sales for further information. ED = tbr
120 [s]
Table 45
01-3876-01 I/O option board 2.0 For communication with the AC drive there are several
option boards for communication. There are different
options for Fieldbus communication and one serial
Each I/O option board 2.0 provides three extra relay outputs
communication option with RS232 or RS485 interface
and three extra isolated digital inputs (24V). The I/O Board
which has galvanic isolation.
works in combination with the Pump/Fan Control, but can
also be used as a separate option. Maximum 3 I/O boards
possible. This option is described in a separate manual.
13.9 Encoder
Part number Description
13.10 PTC/PT100
Part number Description
External, AC drive
A- 0V
main power
independent, supply 24 VDC ±10%
X1 voltage for control and Double isolated
B+ +24V communication
circuits
~
X1:1 Left terminal
X1:2 Right terminal
X1
Name Function Specification
terminal
External, AC drive
1 Ext. supply 1
main power
independent, 24 VDC or VAC
supply voltage for ±10% Double
2 Ext. supply 2 control and isolated
communication
circuits
X1
Name Function Specification
pin
1 2
3 4
NO contact
3
relay K2
5 6
Feedback; confirmation 48 VDC/
P contact of activated inhibit. 30 VAC/2 A
4
relay K2
5 GND Supply ground.
Supply Voltage for
Fig. 172 Connection of safe stop option in size E and up. +24 VDC,
6 +24 VDC operating Inhibit input
50 mA
only.
K1
NC
K2
+24 VDC
Stop DigOut
Overshoot clamp
13.16 Liquid cooling
Sine wave filter
AC drive modules in frame sizes E - O and F69 - T69 are
available in a liquid cooled version. These units are designed Common mode filter
for connection to a liquid cooling system, normally a heat
exchanger of liquid-liquid or liquid-air type. Heat exchanger Brake resistors
is not part of the liquid cooling option.
Drive units with parallel power modules (frame size
G - T69) are delivered with a dividing unit for connection of 13.19 AFE - Active Front End
the cooling liquid. The drive units are equipped with rubber Emotron AC Drives from CG Drives & Automation are also
hoses with leak-proof quick couplings. available as Low harmonic drives and Regenerative drives.
The Liquid cooling option is described in a separate manual. You will find more information on www.emotron.com /
www.cgglobal.com.
Table 51 Typical motor power at mains voltage 400 and 460 V. AC drive main voltage range 230 - 480 V.
Normal duty Heavy duty
Max. (120%, 1 min every 10 min) (150%, 1 min every 10 min)
output
Model FDU Power Power Rated Power Power Rated Frame size
current
[A]* @400V @460V current @400V @460V current
[kW] [HP] [A] [kW] [HP] [A]
48-025-20 30 11 15 25 7.5 10 20
48-030-20 36 15 20 30 11 15 24
48-036-20 43 18.5 25 36 15 20 29 C2
48-045-20 54 22 30 45 18.5 25 36
48-058-20 68 30 40 58 22 30 46
48-072-20 86 37 50 72 30 40 58
48-088-20 106 45 60 88 37 50 70 D2
48-105-20 126 55 75 105 45 60 84
48-142-20 170 75 100 142 55 75 114
E2
48-171-20 205 90 125 171 75 100 137
48-205-20 246 110 150 205 90 125 164
48-244-20 293 132 200 244 110 150 195 F2
48-293-20 352 160 250 293 132 200 235
48-365-20 438 200 300 365 160 250 292 FA2
Table 52 Typical motor power at mains voltage 575 and 690 V. AC drive main voltage range 500 - 690 V.
Normal duty Heavy duty
Max. (120%, 1 min every 10 min) (150%, 1 min every 10 min)
output
Model FDU Power Power Rated Power Power Rated Frame size
current
[A]* @575V @690V current @575V @690V current
[hp] [kW] [A] [hp] [kW] [A]
69-002-20 3.2 1.5 1.5 2 1 0.75 1.6
69-003-20 4.8 2 2.2 3 1.5 1.5 2.4
69-004-20 6.4 3 3 4 2 2.2 3.2
69-006-20 9.6 4 4 6 3 3 4.8
69-008-20 12.8 5 5.5 8 4 4 6.4
C2(69)
69-010-20 16 7.5 7.5 10 5 5.5 8
69-013-20 20.8 10 11 13 7.5 7.5 10.4
69-018-20 29 15 15 18 10 11 14.4
69-021-20 34 20 18.5 21 15 15 16.8
69-025-20 40 25 22 25 20 18.5 20
69-033-20 53 30 30 33 25 22 26
69-042-20 67 40 37 42 30 30 34
D2(69)
69-050-20 80 50 45 50 40 37 40
69-058-20 93 60 55 58 40 45 46
Possible derating
Derating of output current is possible with
-1% / degree Celsius to max +15 °C * (= max temp 55 °C) or
-0.55%/ degree Fahrenheit to max +27 °F
(= max temp. 131 °F).
* max +10 °C for sizes C69/D69/C2(69)/D2(69).
Example
In this example we have a motor with the following data that
we want to run at the ambient temperature of
45 °C (113 °F):
Voltage 400 V
Current 72 A
Power 37 kW (50 hp)
Select AC drive
The ambient temperature is 5 °C (9 °F) higher than the
maximum ambient temperature. The following calculation
is made to select the correct AC drive model.
Derating is possible with loss in performance of
1%/°C (0.55%/ degree F).
Derating will be: 5 x 1% = 5%
Calculation for model FDU48-074
74 A - (5% x 74) = 70.3 A; this is not enough.
Calculation for model FDU48-090
90 A - (5% x 90) = 85.5 A
In this example we select the FDU48-090.
Standard
Models Switching Range
frequency
Table 60 Mechanical specifications, FDU48, FDU52 for IP20 module and IP54
H1 = Enclosure height.
H2 = Total height including cable interface.
* with optional top cover
H1 = Enclosure height.
H2 = Total height including cable interface.
* with optional top cover
Table 64 Operation
0 °C–40 °C (32 °F - 104 °F) See chapter 14.3 page 243 for different conditions
Nominal ambient temperature
0 °C - 45 °C (32 °F - 113 °F) for sizes C69/D69/C2(69)/D2(69)
Atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI)
Relative humidity
Class 3K4, 5...95% and non condensing
according to IEC 60721-3-3
Contamination, No electrically conductive dust allowed. Cooling air must be clean and free from corrosive
according to IEC 60721-3-3 materials. Chemical gases, class 3C2. Solid particles, class 3S2.
According to IEC 600068-2-6, Sinusodial vibrations:
Vibrations 10<f<57 Hz, 0.075 mm (0.00295 ft)
57<f<150 Hz, 1g (0,035 oz)
0–1000 m (0 - 3280 ft)
480V AC drives, with derating 1%/100 m (328 ft) of rated current up to 4000 m (13123 ft)
Altitude
690V AC drives, with derating 1%/100 m (328 ft) of rated current up to 2000 m (6562) ft
Coated boards required for 2000 - 4000 m(6562 - 13123 ft)
Table 65 Storage
WARNING!
If the device is stored for more than two years, the DC link capacitor of the devices must be reformed
during commissioning.
The reforming procedure is described in manual “Capacitor reforming unit”.
Table 66 Fuses, cable cross-sections and glands for FDU48 and FDU52 models
Nominal input Maximum Cable glands (clamping range ) *
Model FDU current value fuse
[A] [A] mains / motor Brake
##-003-54 2.2 4 M32 opening M25 opening
##-004-54 3.5 4 M20 + reducer M20 + reducer
##-006-54 5.2 6 (6–12 mm(0.24 - 0.47 in)) (6–12 mm(0.24 - 0.47 in))
##-008-54 6.9 10 M32 (12–20)/M32 opening
M25+reducer
##-010-54 8.7 10 M25
(10-14 mm(0.39 - 0.55 in))
(10-14 mm(0.39 - 0.55 in))
##-013-54 11.3 16
M32 (16–25)/M32 (13–18)
##-018-54 15.6 20
##-025-20 22 25 - (12 - 16 mm(0.55 - 0.63 in))
M32
##-026-54 22 25 M25
(15–21 mm(0.59 - 0.83 in))
##-030-20 26 35 - (16 - 20 mm (0.63 - 0.79 in))
M32
##-031-54 26 35 M25
(15–21 mm(0.59 - 0.83 in))
##-036-20 31 35 - (20 - 24 mm(0.79 - 0.94))
M40
##-037-54 31 35 M32
(19–28 mm (0.75 - 1.1 in))
##-045-20 38 50 - (24 - 28 mm(0.94 - 1.1 in))
M40
##-046-54 38 50 M32
(19–28 mm (0.75 - 1.1 in))
##-058-20 50 63 - (24 - 28 mm(0.94 - 1.1 in))
M50 M40
##-061-54 52 63
(27 - 35 mm(1.06 - 1.38 in)) (19–28 mm (0.75 - 1.1 in))
##-072-20 64 80 - (28 - 32 mm(1.1 - 1.26 in))
M50 M40
##-074-54 65 80
(27 - 35 mm(1.06 - 1.38 in)) (19–28 mm(0.75 - 1.1 in))
##-088-20 78 100 - (32 - 36 mm(1.26 - 1.42 in))
(Ø17-42 mm (0.67 - 1.65 in)) cable (Ø11-32 mm(0.43 - 1.26 in)) Cable
##-090-54 78 100 flexible leadthrough or M50 flexible leadthrough or M40
opening. opening.
##-105-20 91 100 (32 - 36 mm(1.26 - 1.42 in)
(Ø11-32 mm(0.43 - 1.26 in)) Cable
(Ø17-42 mm (0.67 - 1.65 in)) cable
##-109-54 94 100 flexible leadthrough or M40
flexible leadthrough or M50 opening
opening
##-142-20 126 160 - (40 - 44 mm (1.57 - 1.73 in)) - (36 - 40 mm(1.42 - 1.57 in))
(Ø17-42 mm (0.67 - 1.65 in)) cable (Ø11-32 mm(0.43 - 1.26 in)) Cable
##-146-54 126 160 flexible leadthrough or M50 flexible leadthrough or M40
opening. opening.
##-171-20 152 160 - (40 - 44 mm (1.57 - 1.73 in)) - (36 - 40 mm(1.42 - 1.57 in))
(Ø17-42 mm (0.67 - 1.65 in)) cable (Ø11-32 mm(0.43 - 1.26 in)) Cable
##-175-54 152 160 flexible leadthrough or M50 flexible leadthrough or M40
opening. opening.
Note: For IP54 models 48/52-003 to -074 and 69-002 to -058 cable glands are optional.
* IP20/21 models are equipped with cable clamps instead of glands.
For data on cable connection ranges, see section 3.4.3, page 39.
Note: For IP54 models 48/52-003 to -074 and 69-002 to -058 cable glands are optional.
* IP20/21 models are equipped with cable clamps instead of glands.
For data on cable connection ranges, see section 3.4.3, page 39
NOTE: Possible potentiometer value in range of 1 kΩ to 10 kΩ (¼ Watt) linear, where we advice to use a
linear 1 kΩ / ¼ W type potentiometer for best control linearity.
261
L (244) .......................................118 (338) ...................................... 138
LCD display ..............................83, 88 (245) .......................................119 (339) ...................................... 138
Level control ............................65, 104 (250) .......................................119 (33A) ..................................... 139
Liquid cooling ...............................233 (251) .......................................120 (33B) ...................................... 139
Load default ...................................118 (252) .......................................120 (33C) ..................................... 139
Load monitor ...........................67, 161 (253) .......................................120 (33D) ..................................... 141
Local/Remote ................................102 (254) .......................................121 (33E) ...................................... 141
Lock code ..............................103, 105 (255) .......................................121 (33F) ...................................... 141
Long motor cables ...........................31 (256) .......................................121 (33G) ..................................... 141
Low Voltage Directive .....................11 (257) .......................................121 (33H1) ................................... 141
Lower Band ...................................156 (258) .......................................121 (341) ...................................... 143
Lower Band Limit ..........................158 (259) .......................................122 (342) ...................................... 143
(25A) ......................................122 (343) ...................................... 144
M (25B) ......................................122 (344) ...................................... 144
Machine Directive ...........................11 (25C) ......................................122 (345) ...................................... 145
Main menu ......................................92 (25D) ......................................122 (346) ...................................... 145
Mains supply .......................29, 47, 55 (25E) ......................................122 (347) ...................................... 145
Maintenance ..................................223 (25F) ......................................123 (348) ...................................... 146
Manis cables ....................................26 (25G) ......................................123 (351) ...................................... 146
Max Frequency ......................135, 144 (25H) .....................................123 (354) ...................................... 147
Memory ...........................................66 (25I) .......................................123 (361) ...................................... 148
Menu (25J) .......................................123 (362) ...................................... 148
(110) ........................................97 (25K) ......................................124 (363) ...................................... 149
(120) ..................................98, 99 (25L) ......................................124 (364) ...................................... 149
(210) ........................................99 (25M) .....................................124 (365) ...................................... 149
(211) ........................................99 (25N) .....................................124 (366) ...................................... 149
(212) ......................................100 (25O) .....................................124 (367) ...................................... 149
(213) ......................................100 (25P) ......................................124 (368) ...................................... 148
(214) ......................................101 (25Q) .....................................125 (369) ...................................... 149
(215) ......................................101 (25R) ......................................125 (380) ...................................... 150
(216) ......................................102 (25S) .......................................125 (381) ...................................... 150
(217) ......................................102 (25T) ......................................125 (383) ...................................... 150
(218) ..............................103, 105 (25U) ......................................125 (384) ...................................... 150
(219) ......................................103 (260) .......................................126 (385) ...................................... 150
(21A) ......................................104 (261) .......................................126 (386) ...................................... 151
(21B) ......................................104 (262) .......................................126 (387) ...................................... 151
(220) ......................................105 (2621) .....................................126 (388) ...................................... 152
(221) ......................................105 (2622) .....................................127 (389) ...................................... 152
(222) ......................................106 (263) .......................................127 (391) ...................................... 154
(223) ......................................106 (2631) .....................................127 (392) ...................................... 154
(224) ......................................106 (2632) .....................................127 (393) ...................................... 154
(225) ......................................107 (2633) .....................................127 (394) ...................................... 155
(226) ......................................107 (2634) .....................................128 (395) ...................................... 155
(227) ......................................107 (264) .......................................128 (396) ...................................... 155
(228) ......................................107 (265) .......................................129 (398) ...................................... 156
(229) ......................................108 (269) .......................................130 (399) ...................................... 157
(22A) ......................................108 (310) .......................................130 (39A) ..................................... 157
(22B) ......................................108 (320) .......................................131 (39B) ...................................... 157
(22C) ......................................109 (321) .......................................131 (39C) ..................................... 158
(22D) .....................................109 (322) .......................................132 (39D) ..................................... 158
(230) ......................................113 (323) .......................................132 (39E) ...................................... 158
(231) ......................................113 (324) .......................................133 (39F) ...................................... 159
(232) ......................................113 (325) .......................................133 (39G) ..................................... 159
(233) ......................................113 (326) .......................................134 (39H-39M) ............................ 160
(234) ......................................115 (327) .......................................134 (410) ...................................... 161
(235) ......................................115 (328) .......................................134 (411) ...................................... 161
(236) ......................................115 (331) .......................................135 (412) ...................................... 161
(237) ......................................116 (332) .......................................136 (413) ...................................... 161
(240) ......................................117 (333) .......................................136 (414) ...................................... 161
(241) ......................................117 (334) .......................................136 (415) ...................................... 162
(242) ......................................117 (335) .......................................137 (416) ...................................... 162
(243) ......................................118 (336) .......................................137 (4162) .................................... 163
(337) .......................................138 (417) ...................................... 163
262
(4171) ....................................163 (6143) .....................................193 (830) ...................................... 213
(4172) ....................................163 (6144) .....................................193 (8A0) ..................................... 214
(418) ......................................163 (6145) .....................................193 (900) ...................................... 214
(4181) ....................................163 (6151) .....................................194 (920) ...................................... 214
(4182) ....................................164 (6152) .....................................194 (922) ...................................... 214
(419) ......................................164 (6153) .....................................194 33F ........................................ 141
(4191) ....................................164 (6154) .....................................194 616 ........................................ 190
(4192) ............................164, 166 (620) .......................................195 Minimum Frequency .................... 137
(41A) ......................................164 (621) .......................................195 Modbus ........................................... 79
(41B) ......................................165 (622) ...............................195, 196 Modbus/TCP .......................... 79, 229
(41C) ......................................165 (623) ...............................195, 196 Monitor function
(421) ......................................166 (624) .......................................195 Alarm Select ........................... 165
(422) ......................................167 (625) .......................................195 Auto set .................................. 164
(423) ......................................167 (630) .......................................197 Delay time ............................. 161
(424) ......................................167 (631) .......................................197 Max Alarm ............................. 161
(511) ......................................168 (632) .......................................197 Overload .......................... 67, 161
(512) ......................................169 (633) .......................................197 Ramp Enable ......................... 161
(513) ......................................170 (634) .......................................197 Response delay ....... 162, 163, 165
(514) ......................................172 (635) .......................................197 Start delay .............................. 161
(515) ......................................172 (640) .......................................198 Motor cables .................................... 29
(516) ......................................173 (641) .......................................198 Motor cos phi (power factor) ......... 107
(517) ......................................173 (642) .......................................198 Motor data .................................... 105
(518) ......................................173 (643) .......................................198 Motor frequency ........................... 107
(519) ......................................173 (644) .......................................199 Motor I2t Current ......................... 220
(51A) ......................................173 (645) .......................................199 Motor identification run ............... 108
(51B) ......................................173 (649) .......................................199 Motor Lost .................................... 121
(51C) ......................................174 (650) .......................................199 Motor lost ..................................... 167
(521) ......................142, 143, 174 (651) .......................................199 Motor Potentiometer ............ 148, 174
(522) ......................................175 (652) .......................................199 Motor potentiometer ..................... 174
(529-52H) ..............................175 (653) .......................................200 Motor PTC ....................... 50, 51, 116
(531) ......................................176 (654) .......................................200 Motor ventilation .......................... 107
(532) ......................................176 (655) .......................................200 Motors .............................................. 7
(533) ......................................177 (659) .......................................200 Motors in parallel ............................ 45
(534) ......................................179 (711) .......................................205 MotPot .......................................... 136
(535) ......................................179 (712) .......................................205 Multi-motor application ................ 100
(536) ......................................179 (713) .......................................205
(541) ......................................180 (714) .......................................205 N
(542) ......................................181 (715) .......................................206 Nominal motor frequency ............. 144
(551) ......................................182 (716) .......................................206 Number of drives .......................... 154
(552) ......................................182 (717) .......................................206
(553) ......................................182 (718) .......................................206 O
(55D) .....................................182 (719) .......................................206 Operation ........................................ 99
(561) ......................................183 (71A) ......................................206 Options ................................... 54, 225
(562) ......................................184 (71B) ......................................207 External Control Panel (ECP) ...226
(563-56G) ..............................184 (720) .......................................207 I/O Board .............................. 229
(610) ......................................184 (721) .......................................207 OR operator .................................. 195
(6111) ....................................185 (722) .......................................208 Output chokes ............................... 233
(6112) ....................................187 (723) .......................................209 Output Voltage ............................. 206
(6113) ....................................189 (724) .......................................209 Overload ................................. 67, 161
(6114) ....................................189 (725) .......................................210 Overload alarm ................................ 67
(6115) ....................................189 (726) .......................................210
(6121) ....................................190 (727) .......................................210 P
(6122) ....................................190 (728-72A) .......................210, 211
Parameter sets
(6123) ....................................190 (730) .......................................211
Load default values ................. 118
(6124) ....................................191 (731) .......................................211
Load parameter sets from
(6125) ....................................191 (7311) .....................................211
Control Panel ......................... 119
(6131) ....................................191 (732) .......................................211
Parameter Set Selection ............ 61
(6132) ....................................191 (733) .......................................212
Select a Parameter set ............. 117
(6133) ....................................192 (7331) .....................................212
PID control ..................................... 72
(6134) ....................................192 (800) .......................................212
PID Controller .............................. 150
(6135) ....................................192 (810) .......................................212
Closed loop PID control ........ 150
(6141) ....................................192 (811-81N) ..............................213
Feedback signal ...................... 150
(6142) ....................................193 (820) .......................................213
263
PID D Time ...........................150 Standby supply board .....................230
PID I Time ............................150 Start Delay .....................................157
PID P Gain ............................150 Start/Stop settings ..........................135
Priority ............................................63 Status indications .......................83, 88
Process Protection ..........................166 Stop categories .................................77
Process Value .................................205 Stop command ...............................174
Product standard, EMC ...................10 Stop Delay .....................................157
Profibus DP .....................................79 Stripping lengths ..............................36
Profinet IO ......................................79 Switches ...........................................49
Programming ...................................92 Switching frequency .......................108
PT100 Inputs ........................115, 116 Switching in motor cables ................31
PTC/PT100 board ........................229
Pump size ........................................74 T
Pump/Fan Control ........................154 Technical Data ...............................235
Terminal connections ......................48
Q Test Run ........................................108
Quick Setup Card ..............................7 Time ........................................86, 216
Timer .............................................155
R Top cover .......................................233
Reference Torque ...........................................146
Frequency ...............................166 Transition Frequency .....................158
Motor potentiometer ..............174 Trip ...........................................86, 89
Reference signal ..............100, 130 Trip causes and remedial action .....218
Set reference value ..................130 Trip Message log ............................212
Torque ...................................167 Trips, warnings and limits ..............217
View reference value ...............130 Twisted cables ..................................54
Reference control ...........................101 Type code number .............................9
Reference signal .............................101
Relay output ..................................182 U
Relay 1 ...................................182 Underload ........................................67
Relay 2 ...................................182 Underload alarm ............................161
Relay 3 ...................................182 Unlock Code .................................103
Release speed .................................141 Upper Band ...................................156
Remote control ................................64 Upper Band Limit ..........................157
Reset command .............................174
Reset control ..................................102 V
Resolution .......................................97 V/Hz Mode ...................................100
RFI mains filter ...............................29 Vector Brake ..................................141
Rotation ........................................103 Ventilation .....................................107
RS232/485 ..............................79, 126 View reference value .......................130
RTC- Real time clock ....................229 Voltage .............................................49
RUN .........................................86, 89 VSD Data ......................................214
Run command ...........................86, 89
Run Left command ........................174 W
Run Right command .....................174 Weekday ..................................86, 216
Running motor ..............................139 Wiring .............................................73
S
Safe Stop option ............................231
Select Drive ...................................154
Serial communication ....................229
Settle Time ....................................158
Setup menu .....................................92
Menu structure .........................91
Shaft power ....................................205
Signal ground ................................253
Single-ended connection ..................53
Software .........................................214
Sound characteristic .......................108
Speed .............................................205
Spinstart ........................................139
Standards .........................................10
264
TECHNICAL CENTERS
T +46 42 16 99 00
F +46 42 16 99 49
www.emotron.com/www.cgglobal.com