Elect - Generator Set
Elect - Generator Set
Elect - Generator Set
ELECTRICAL INSTALLATION
GENERATING SYSTEM
1. Description
1.1 The emergency generator shall include, but not be limited to, the followings:
2.1. The Electrical Sub-Contractor shall ensure the compatibility of various components and
accessories. Generators will be complete set manufactured & tested in G7 country.
2.2. Generators will be complete set manufactured & tested in G7 country.
2.3. Notwithstanding any description or detail (implied or otherwise) included hereafter, the
generator set shall comply with all the necessary requirements of the FSD, EPD and
any other relevant regulations to enable the generator set to be operative.
3. Site and Service Condition
4. Submittals
4.1 As a minimum, submit the following for approval at the appropriate stages of the works:
1. Detailed schedule of equipment and components.
2. Detailed and coordinated shop drawings on Generator Room equipment layout,
with requirements on engine exhaust system, fuel supply system, cooling
system, including calculations, pipe sizes, construction details, installation
details, etc.
3. Electrical control wiring diagrams showing details of all wirings internal and
external to the generator control panel, together with terminal numbers for cable
terminations to external equipment.
4. Detailed calculation on generators sizing.
5. Detailed calculation on battery sizing.
6. Detailed calculation on flue pipes sizing.
7. Equipment static and dynamic weights.
8. Detailed calculation on anti-vibration mounting requirements.
9. Builder's works requirement.
10. Proposal on testing procedures (including dummy load test) and report format
for testing of the generator set at the manufacturer's works and on site.
11. Proposal on predetermined sequence of starting methods to achieve sequence
starting of essential equipment.
5. Design and Construction of Generator Set
5.1 General
1. The generator set shall comprise a diesel engine directly coupled to an
alternator and mounted in line on a common base-frame.
2. Equip the generator set fully for radio interference suppression to BS800.
3. Enclose or guard totally all exposed moving parts, except manually operated
controls, to prevent accidental contact by personnel. All guards shall be
detachable.
4. Treat all exposed ferrous metal surface of the generator set, underframe and
ancillary equipment with rust-proofing primer paint undercoat and finishing coat.
Hot face part shall be coated with heat resisting paintwork which can tolerate
high temperature up to 650°C without deterioration.
5. The overall Generator installation shall be capable of delivering the electrical
power (kW and kVA @ 0.8pf) noted in the particular specification, drawings or
schedules to the electrical systems. Where electric Fans etc. are used as part
of the generator installation (for instance as radiator fans) then the overall output
shall be equal to the specified value plus the power required for those electric
fans etc.
6. Unless noted otherwise in the particular specification, drawings or schedules,
the generator shall conform to the G2 requirements of BS ISO 8528
7. The diesel engine-generator sets shall be capable of single step load pick up of
100% of nameplate kW and power factor, less applicable derating factors, with
the engine-generator set at operating temperature.
8. The BMS shall be linked to the generator system though Modbus interface to
monitor the key parameters and system status.
5.2 Engine – for Ultra Low sulphur diesel oil
1. The engine shall be suitable for use with light diesel fuel oil to BS2869 Class A1
or A2 diesel fuel commonly available at the place of installation, water cooled,
four stroke, direct injection, naturally aspirated or pressure charged and
complying with BS5514. Engine shall be of number 2 ultra low suliphur diesel
oil.
2. The engine shall be rated for continuous duty to BS5514 and sized to match the
continuous rating of the alternator, with overload capacity as specified hereafter.
3. Engine crankshaft speed shall not exceed 1500 rpm. The normal direction of
rotation shall be anti-clockwise.
4. A mechanical over-speed tripping mechanism shall be provided to shut off the
fuel supply in the event of 15% over-speed.
5.3 Alternator
1. Design and construct the alternator to meet the appropriate sections of BS4999
and BS5000.
2. The alternator shall be of brushless type, with the rotating field excited from an
a.c. exciter and rotating rectifier unit, and with the exciter controlled by solid-
state automatic voltage regulator as specified hereafter.
3. The alternator shall be rated to suit local conditions and specially impregnated
for tropical duty.
4. The rotor and stator of the alternator shall have Class F insulation.
5. The alternator characteristics must be matched to the torque characteristics of
the engine, in such a manner that with full load connected to the alternator, the
alternator can utilize all the available engine power without exceeding it.
6. The alternator must be capable of withstanding an over-speed of 20% above
synchronous value.
7. The alternator must be capable of withstanding an unbalance load with the
current in one phase more than the other phases by 60%.
8. The alternator shall be drip proof to IP23 of BSEN 60529.
9. The alternator shall be built in with thermostatically controlled heater and with
manual isolating switch at the control panel. The heater shall be cut off when
the alternator is in operation.
10. The alternator shall be capable of withstanding the short circuit current with the
output terminals short circuited for 3 seconds without any damage to the
generator.
5.4 Radiator
1. The engine shall be water cooled by means of a matching heavy duty radiator
complete with belt-driven fan, coolant pump, thermostat temperature control
liquid-cooled exhaust manifolds, intercooler, coolant corrosion resistant filters
suitably designed to suit the site conditions.
2. The radiator shall be mounted on the same base frame supporting the generator
set where a set mounted radiator is required.
3. The radiator shall be fitted with duct adapter flange to enable the ventilating
ductwork to be attached to the radiator. A section of ductwork complete with
flexible connector shall be installed between the radiator and the metal louvers
provided. Ductwork shall be constructed of galvanized steel sheets in
accordance with Heating and Ventilating Contractor's Association (HVCA) DW
144.
4. The fan rating shall be adequate to allow for the additional resistance to airflow
of the ductwork, silencer, and louvers, if fitted.
5. Corrosion inhibitor shall be added to the cooling system.
5.5 Noise/Sound Attenuation Generally
5.5.1 Requirements:
1. Sound attenuation shall be provided to the generator installation
(Rooms/enclosures, exhausts, cooling systems, air inlet/discharge etc.) to
ensure noise levels do not exceed the sound levels noted by the particular
specification, drawings and schedules.
2. Where the Particular specification schedules and drawings do not give specific
requirements the whole installation shall be provided with silencers, attenuation
and acoustic treatment to ensure noise levels of 68dBA are not exceeded at 3m
from the:
a. exhaust discharge
b. any part of the Exhaust pipe and silencer arrangement that is outside of the
Generator room/enclosure.
c. perimeter of the Generator room (this includes the Roof (or ceiling) the walls
and the Floor when the unit is not mounted on a ground bearing slab)
d. In any habitable space or plant room in the vicinity of the generator room.
3. When considering the overall requirements for the noise levels, the Contractor
shall note that the specified Maximum noise levels are to be achieved when all
generator backed plant (Including, HVAC Fans, chillers etc, and, Public Health
Pumps, compressors etc.) are running normally and their noise levels are added
to that emanating from the generator installation.
5.5.2 Results Testing and submittals
The Contractor will be required to carry out Noise levels studies to prove the generator
installation complies with the specified requirements. These studies shall include
Testing of the noise levels achieved and submittal of a report to the Engineers.
5.6 Coupling Arrangement and Anti-Vibration Mountings
1. The diesel engine shall be directly coupled to the generator, which shall be of
12. Installation of two silencers in series (a ‘critical rated’ reactive type and a
standard absorptive type) to each generator is required to meet the noise design
goals.
A minimum 1675mm long ECI fully lined super critical 150NB silencer with
fully lined internal tubes installed in series with:
A minimum 1,730mm long ECI 150NB absorptive
13. The exhaust silencers shall be installed in accordance with the manufacturer’s
recommendations and as close to the engine as possible in a section of
pipework isolated from the main engine. The static pressure associated with the
silencers should be checked by the contractor / supplier to ensure that the
silencer installation does not impede effective operation of the exhaust system.
6.2 Air Intake And Discharge
6.2.1. Air Intake and discharge louvers shall be provided and shall accord with the following:
1. The finished colour of the louvre shall be agreed with the Architect where it is
not given in the particular specification, drawings or schedules.
2. Be weatherproof to prevent wind driven rain or rain carried on the air stream
entering the building or the louvers.
3. Be provided with guards to prevent entrance by small animals, rodents birds
etc.
4. Shall, when used in conjunction with the Attenuators, cooling fans etc. permit
sufficient air flow through the Generator room for cooling purposes.
6.2.2. The Contractor shall note that the size of the ductwork, attenuators, and louvers
indicated on the drawings is based on generic data. He shall ensure that all ductwork,
louvers, attenuators etc. are adequately sized for the required air flow and noise levels.
6.2.3. Dampers shall be provided on the air inlet and discharge air paths where required by
the particular specification, drawings or schedules. Unless noted otherwise these shall
be arranged such that:
1. They are powered closed when the generators are not running.
2. They spring open on failure of their power supply and when the generators are
signalled to start.
3. They shall be fitted with Auxiliary contacts to indicate their position (open or
Closed) which shall be monitored by the BMS system and or the Building
automation systems.
4. They shall be inhibited from powering closed when the generators are running.
5. Motorized louvers shall be galvanized frame and blade construction with blade
seals installed within the frames. Motorized louvers shall be provided with louver
control wiring boxes which shall incorporate time delay relays and ventilation
fan controls. Provide an access hatch to allow for inspection and maintenance
of each louver motor and spring mechanism where required.
6. They shall be able to work incorporated with Fire extinguish system of generator
room.
All tank shall be completed with leakage collection and leakage sensor
complete with alarm.
Flexible tube. Flexible tubing, piping or hose may be used only on condition
that:
- The use of such tubing is avoidable because of the need to
provide for movement or to reduce the effect of vibration;
- Supporting and fixing shall be secure and the piping shall be not
unduly exposed to mechanical damage.
- Any trench in which pipes are laid shall be drained, and shall be
of adequate dimensions to permit access to valves and fittings.
- Provide fuel pump control panel that has remote fuel level
indications and High/low level alarm indications with buzzer and
acknowledge button interface with bulk fuel tank.
Hydraulic Testing of Fuel Bulk Tank and Pipe work:
- Hydraulic testing is refined for the bulk tanks and the associated
pipe work.
70kPa for the associated pipe work, valves and fittings. Test
for two (2) hours, pressure drop shall not exceed 3%.
disconnecting the starter motor if the engine fails to start within a pre-
determined time, say 15 seconds, so as to avoid undue discharge of the
batteries.
5. A total of three consecutive starts, say with 15s duration, and at 5s intervals,
shall be made to start the engine, after which disconnection of the starter by the
fail-to-start device shall operate the visual and audible alarm as specified
hereafter. No further attempts shall be made to start the engine by the automatic
starting system until the fail-to-start mechanism has been reset manually.
6.5 Starting Battery and Charger
1. A 24V d.c. engine starting battery set of nickel-cadmium type of adequate
ampere hour capacity and discharge rate shall be mounted adjacent to the
engine underbase. The battery shall comply with IEC 623 and be capable of
providing six consecutive starts of 15 seconds duration, and at 5 seconds
intervals, without being discharged to a level where damage may be caused to
the battery as advised by the manufacturer. The battery shall be housed in
corrosion resisting container of an approved type.
2. The battery charger shall be constant potential type, complete with d.c.
voltmeter and ammeter, surge suppressor, controls, float and boost charging
selection, battery discharging indication, protection against over-charging and
indication, charger failure alarm. All controls and sensors shall be wired to the
set mounted control panel.
6.6 Engine Heater
The heaters shall be thermostatically controlled and be disconnected whenever the
engine is put into operation.
6.7 Miscellaneous
1. Fuel Injection System
The fuel injection system shall be complete with primary and secondary fuel
filters with replaceable elements, and an engine driven, mechanical, positive
displacement fuel pumps, all mounted on the engine.
2. Lubricating System
Enclosed forced feed lubricating system shall be complete with positive
displacement, mechanical lubrication oil pump, lubricating oil cooler, filters and
dipsticks oil level indicator.
3. Air Cleaner
Replaceable dry heavy duty element air cleaner shall include an automatic
device to give an alarm when the filter becomes clogged.
9.1 Provide an earthing terminal in the Generator Room for the earthing of the generator
set.
9.2 The generator frame, generator neutral, L.V. switchboard, cable trays/ladders, etc.
shall be individually connected to the earth terminal in the Generator Room. The size
of the protective conductors shall not be less than 6mm by 25mm.
10. Warning Sign
11.1 The electrical schematic diagrams for the essential power supply distribution shall be
fixed in wooden frame with transparent panel of suitable size at a prominent position in
the Generator Room.
11.2 One complete set of control wiring diagram shall be provided inside the control panel.
12. Installation
12.1. The Electrical Sub-Contractor shall provide the acoustic treatment such that the sound
pressure level both inside the lot and adjacent to the site boundary, due to the operation
of generator set shall not exceed the permissible noise level as required by the
Environmental Protection Department (EPD) and acoustic specification.
12.2. The Electrical Sub-Contractor shall be responsible for obtaining Dangerous Goods
License from the Fire Services Department and installation approval from the
Environmental Protection Department.
12.3. The Electrical Sub-Contractor shall submit the anti-vibration spring loading calculations
at earliest stage for Architect approval.
13. Engine Cooling
13.1. The hot air from the radiator shall be directed out of the radiator through a louver panel.
The necessary ductwork complete with anti-vibration flexible joint and silencer shall be
provided by the Electrical Sub-Contractor. The method of fixing the duct shall be
proposed by the Electrical Sub- Contractor and approved by the Architect.
13.2. All ductworks and materials shall be provided, including linings, adhesives, flexible
ducts, flexible connections, gaskets, sealants, etc. The complete installation shall
comply fully with all the requirements of the Fire Services Department and shall satisfy
BS 5588: Part 9 and BS 8313 in respect of resistance to the penetration of fire and
spread of flame and smoke.
13.3. All metal ducting shall be constructed to the recommendation of the Heating and
Ventilating Contractor's Association (HVCA), U.K. Ductwork Group in their Publication
DW144 or the latest edition.
13.4. The cooling system shall be fitted with the manufacturer's recommended anti-corrosion
solution.
13.5. The Electrical Sub-Contractor shall ensure that the pressure drop across the attenuator
is compatible with the available static pressure of the radiator fan.
14. Installation of Exhaust System
14.1. Exhaust manifolds shall be provided on the engine terminating at the outlet(s) from the
turbo charger.
14.2. The exhaust system shall comprise flexible exhaust pipe for connection to the engine
outlet, high attenuation mild steel pipe, residential primary and secondary exhaust type
silencers and flue. The primary silencer shall be located in a position as close to the
engine as possible and the secondary silencer shall be located in the exhaust pipe run
close to the primary silencer. The distance between two silencers shall give the best
possible exhaust silencing results, as recommended by the manufacturer.
14.3. The exhaust pipe shall complete with mating flanges, nuts, bolts and flexible bellows
and shall be insulated with heavy-duty stainless steel cladding on the outside. Brackets
and supports of adequate strength shall be provided to support the exhaust pipe,
silencer and all other fittings.
14.4. The Electrical Sub-Contractor shall ensure that the exhaust system is designed to suit
its particular application. Full details shall be submitted in respect of construction,
cladding and temperature calculations at the exhaust outlets, fully documented and
certified. The exhaust shall be protected against the ingress of rain and water.
14.5. The insulation shall ensure that the temperature on surface of the cladding is safe to
touch. Otherwise the Electrical Sub-Contractor shall provide the necessary additional
protection.
15. Cable Termination
16.1. Notwithstanding any description or detail (implied or otherwise) specified herein, the
Electrical Sub- Contractor shall ensure that the fuel system installation complies with all
necessary requirements of Fire Services Department (Dangerous Goods Section) and
any other relevant regulations.
16.2. The Electrical Sub-Contractor shall obtain written approval from Fire Services
Department before any site work is commenced by preparation of details for
submission made through the Architect.
16.3. Before fuel tank is installed, all rust and scale shall be removed from the external
surface immediately before applying one coat of red lead to BS 2523 Type B followed
by two coats of bituminous paint. Where damage is sustained to the protective coating
due to handling, etc., such coating shall be made good by the Electrical Sub-Contractor.
16.4. All pipework shall be free from burrs, rust and scale and shall be thoroughly cleaned
before installation. The open ends shall be plugged with purpose made metal or plastic
caps during the installation period. The use of wooden plugs, paper, cotton waste, etc.
for this purpose is forbidden. All pipes shall be rigidly fixed with suitable brackets at 1m
intervals.
16.5. All pipes shall be properly painted with two coats of primer and two coats of final finish
with color to be approved.
16.6. All pipework underfloors and any other pipework likely to be in direct contact with
concrete, shall be coated with a bitumen compound and wrapped in polythene before
being concealed.
16.7. The vent pipe shall discharge upwards in the open air at a location acceptable to the
Architect. The upper end of the vent pipe shall be terminated with a flame trap of
adequate construction to preclude the entry of birds, insects, leaves, etc.
16.8. The Electrical Sub-contractor shall supply and install rotary fuel transfer pumps
complete with all necessary accessories including strainers, check valves, gate valves,
etc. which comply with the following requirements:-
1. The pumps shall be positive displacement type, with high quality cast iron body,
high tensile steel shafts and built in internal relief valve.
2. Each pump shall be capable of delivering 'light' diesel fuel oil at 300 kPa 950
rpm maximum. For each pair of pumps a manual switch shall be provided to
select the pump running mode as ‘duty’ or ‘standby’ respectively.
3. The coupling motor shall be flame proof 3 phase, 50 Hz, 400V with no volt
17.1. General
Power cables are mainly for electricity supply and distribution. They shall be
manufactured under BASEC license or equivalent quality surveillance scheme (e.g.
CENELEC Harmonization Scheme) and bear BASEC marking or the appropriate
marking of the equivalent quality surveillance scheme (e.g. CENELEC HAR).
Cabling facilities will include cable ducts, cable trays and cable ladder.
Each type of cables specified shall have been certified by an internationally recognized
testing laboratory that it has been designed and manufactured to the appropriate BS
publication.
When applicable, the current carrying capacities and voltage drop of cables shall be
equal to or better than those tabulated in the IEE Wiring Regulations, with ratings
adjusted to suit local conditions, viz. grouping, maximum ambient temperature, etc.
As a minimum, submit the following for approval at the appropriate stages of the Works:
1. Detailed schedule of equipment and components and manufacturer's data,
including manufacturer's type test certificates and testing documents.
2. Cable routing drawings showing the coordinated routing of cables, the disposition