Nothing Special   »   [go: up one dir, main page]

Pel-Dk - Differential Pressure Transmitter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

1131.

20en
03.02.2015

PEL-DK - DIFFERENTIAL PRESSURE TRANSMITTER

PEL-DK is a pressure transmitter for detecting


pressures and pressure differences in air handling
systems. The pressure measurement is temperature
compensated according to the ambient temperature.
The M models have RS-485 connection for
Modbus RTU communication. ML-SER tool is needed
at commissioning for making the Modbus settings.
The transmitter zero point is kept accurate by using the
regular automatic zeroing, eliminating the possible
zero point drifting. No re-calibration is normally
needed.
The influence of process disturbances (e.g.
turbulence) can be damped by selecting suitable time
constant (2 s or 8 s).
Technical data:
The N models have a backlit display. The display Supply 24 Vac/dc (22...28 V), 2 VA
resolution is 0,1 Pa for measured values below 200 Pa Measuring ranges 0...100 Pa ±50 Pa
and 1 Pa for values over 200 Pa. The display can be
0...200 Pa ±100 Pa
added also after commissioning.
0...500 Pa ±250 Pa
*0...1000 Pa ±500 Pa
Selecting measuring range:
Accuracy (at 25 C)
S4 -400…1000 Pa ± 3 Pa ± 1 % of reading
S2 S3
< -400 Pa ± 3 Pa ± 2 % of range
0…1000 Pa *) ±500 Pa Outputs *0...10 / 2…10 / 0…5 Vdc,
0…500 Pa ±250 Pa < 2 mA
0…200 Pa ±100 Pa *4…20 / 0…20 mA, 700 Ω
0…100 Pa ±50 Pa Communication (M models) Modbus RTU (RS-485)
) Time constant 2 s or *8 s
* Factory setting. The 0…1000 Pa range is also
Max. over pressure 13 kPa
used for the custom range setting. The range
Pressure connections Ø5 mm
limits can be changed with the ML-SER tool or via
Modbus. Operating temperature 0...+45 °C
Display (N models) backlit dot matrix display
Selecting time constant: Housing IP54, polycarbonate
Dimensions (w x h x d) 105 x 102 x 46 mm
S1 Time constant
* = factory setting
2s
)
8s*
*) Factory setting.

Wiring:

Ordering guide:
Model Product Description
number
PEL-DK 1131200 differential pressure transmitter
PEL-DK-N 1131201 differential pressure transmitter with
display
PEL-DK-M 1131390 differential pressure transmitter with
Modbus
PEL-DK-M-N 1131391 differential pressure transmitter with
Modbus and display
ML-SER 1139010 transmitter commissioning tool

Products fulfil the requirements of directive 2004/108/EC and are in accordance with the standards EN61000-6-3 (Emission) and EN61000-6-2 (Immunity).

Produal Oy Keltakalliontie 18, 48770 Kotka FINLAND Tel: +358 10 219 9100 / Fax: +358 5 230 9210 info@produal.fi www.produal.com