GENSET PERFORMANCE DATA

Customer Name : PERTAMINA HULU MAHAKAN - NPU SITE Generator Model : C840D5
Engine Model : QSK23 - G3 Generator S / N : J08S800410
Engine S / N : 00317397 SMR :
Test Date : 21 Feb 2020 Capacity : KVA : 630 , Volt : 400 , Amp : 909 , KW : 504 , PF : 0.8

Room Temp. : 32
Deg. C
Deg. C

A. Genset Operating Data Test


Time Voltage Ampere Freq Oil Press W/Temp O/Temp Boost Press Rail Fuel
% Load KW PF RPM
(minutes) R-S S-T T-R R S T HZ (Bar) (°C) (°C) (in.Hg) Press (PSI)

0 5 402 403 403 0 0 0 0 1 50.09 4.6 44.9 49.8 n/a 230 1500

50 10 401 402 402 297 311 303 190.1 0.95 50.09 4.3 73.3 70.5 n/a 230 1500

80 30 402 403 402 559 591 566 382.3 0.99 50.10 4.1 75.3 93.1 n/a 230 1500

90 30 404 405 405 662 681 655 461.4 0.99 49.92 4.0 76.1 92.4 n/a 230 1500

B. Max. Load Condition C. Electrical Control Panel (Switchboard) D. Maintenance Evaluation E. Engine Safety Device (Shutdown)
CONDITION
INSPECTION ITEM INSPECTION ITEM CONDITION INSPECTION ITEM CONDITION Inspection Item Test Condition
at 80% at 100%

Fuel Rail Pressure 230 230 PSI Voltage Meter Good Engine Oil Reuse Low Oil Pressure - PSI

Turbo Boost Pressure - - in.Hg Ampere Meter Good Engine Oil Filter Reuse High Water Temp - °C
Engine Blow by - - in.Hg Frequency Meter Good Fuel Filter New Over Speed - RPM
Exhaust Gas Temp. 450 480 °C KW Meter Good Air Cleaner Reuse Over Crank - Sec

Exhaust Smoke DCA Consitration Good

F. Suggestion / Recommendation
Note :
1. Test Performance After Midlife
2.
3.
4.

Inspected by : Acknowledge by :

Tomy W. Budi Susanto Mochtar Riyadi


Mechanic Mechanic Electrician