Nothing Special   »   [go: up one dir, main page]

LCD-100B-E Liquid Crystal Display: General

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

February 1, 2008 Version : C

LCD-100B-E
Liquid Crystal Display
Section: Annunciator Control Systems

General
The LCD-100B-E is a Liquid Crystal Display (LCD)
annunciator and remote control for the NOTIFIER®
N-6000 Fire Alarm Control Panel (FACP). The LCD-
100B-E will mimic the top portion of the N-6000 with
100-character LCD backlit display. This provides the
event and preprogrammed custom messages as displayed
on the main panel. The unit contains function keys and
status LED indicators.
Through the N-ACS communication port, FACP can
support up to 32 LCD-100B-E annunciators with 64 / 128
or 256 points/ zones capacity.
The LCD-100B-E has two basic modes of operation by
toggle different DIP switches:
y Normal Mode: Provides a remote or local digital
display for alarms/ troubles status of preprogrammed
points. It provides a vectored annunciation capability.
Individual devices/ zones can be installer-defined to
only display and print at specific locations. LCD-100B-E Liquid Crystal Display
y Shadow Mode: Repeat another LCD-100B-E signals
operating at the same address.
y Alarm and trouble event detail display.
Features y Local sounder for both alarm and trouble activation.
y 100-character (20 characters × 5 lines) Liquid Crystal y Supervisory mode option.
Display with backlit control. y Can be powered by 24VDC from the panel or by
y Support up to 32 LCD-100B-E in the system. remote power supplies.
y Daisy-chain connection with maximum wiring distance y Maximum display up to 256 points.
1,800m from the panel by using 1.0mm2 twisted-pair
Specification
cable.
y Six Status LED Indicators: Fire Alarm, Signal Silence, y Operating Voltage : 18 ~ 27VDC
Normal, Trouble, Communication and Feedback. y Standby Current: 40mA@24VDC (Backlit off)
y Four Fixed Function Keys: Lamp/ Self Test, y Alarm Current : 70mA@24VDC (All LEDs and
Acknowledge/ Signal Silence, Page Up and Page Down Backlit on)
y Alarm and trouble counter display. y Operating Temperature : -10 ~ 50 ºC
This document is not intended to be used for installation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover all specific applications or anticipate all
requirements. All specifications are subject to change without notice. For more information, please
contact NOTIFIER. Phone: +886 (2) 22487171 Fax: +886 (2) 22450927