Catalogue AMTED399086EN (Web)
Catalogue AMTED399086EN (Web)
Catalogue AMTED399086EN (Web)
Catalogue | 2013
Ringmaster
Ring Main Unit
Ringmaster range General contents
Presentation 3
Remote control 91
Installation drawings 95
AMTED399086EN 1
2 AMTED399086EN
Presentation Contents
Applications 4
Switchgear description 5
Sepam series 10 9
AMTED399086EN 3
Presentation Applications
Product advantages
Simple, clear operation combined with compact size,
high functionality and reliability extends the applications
of the Ringmaster range.
Safety to personnel
Fully certified internal arc design.
Indoor/outdoor design
No need for expensive switchrooms.
Self-powered protection
Not reliant on costly battery chargers.
Compact
Reduced dimensions, gives reduced civil costs.
Virtually maintenance free
Low lifetime costs.
Modular design
Quick, simple & easy to install.
Proven design
Assured consistent quality.
ISO 9001 quality certification.
Environmental
Manufactured to ISO 14001 environmental standards.
PE40438
4 AMTED399086EN
Presentation Switchgear description
A variety of different panel types are available for each unit within the range, together
with a number of optional accessories enabling Ringmaster to satisfy the most
complex system specification.
PE57061
PE57064
electrical operation
b Interlocked MV cable test access (no need to
remove cable terminations or use loose earthing
devices)
PE57065
PE57067
PE57066
AMTED399086EN 5
Presentation Standards and quality
Both sites ie. Leeds in UK and Hyderabad in India, are, for many years,
been committed to a global quality approach and are certified:
b ISO 9001: 2000
b ISO 14001: 2004
b OHSAS 18001 (since 1999).
The Ringmaster switchboards comply with the requirements of the following standards and regulations:
Description IEC standard IEC classes EN standard
Switchboard IEC 62271-200 LSC partition class PM EN 62271-200
IEC 62271-1 Continuity of service of the cable EN 62271-1
connection and fuse compartments:
LSC2A (1)
Behaviour in the event of internal faults IEC 62271-200 EN 62271-200
Earthing switch IEC 62271-102 E2 EN 62271-102
Ring switch IEC 62271-103 M1, E3, C1
Circuit-breaker IEC 62271-100 M1, E2 EN 62271-100
Current transformer IEC 60044-1 EN 60044-1
Voltage transformer IEC 60044-2 EN 60044-2
Voltage presence indicators IEC 61958 EN 61958
Voltage detection systems IEC 61243-5 EN 61243-5
Protection against accidental contact, foreign bodies IEC 60529 EN 60529 1
and ingress of water
Installation HD 637 S
Operation of the electrical equipment EN 50110
6 AMTED399086EN
Presentation Time Fuse Link (TFL) protection
Self-powered reliability
TFL protection
An effective low cost option without compromising reliability.
CT operated trip coils (with TFL) provides phase overcurrent and earth fault inverse
time protection, the characteristic being given by a Time Fuse Link (TFL).
This option is suitable for transformer protection up to 1600 kVA.
Recommended Time Fuse Link (TFL) settings to ESI 12-6
DE60245-1
Benefits
b Low cost
b Fast clearance of LV faults
b Simple to replace
b Proven protection to EA standards
b Fast tripping for MV earth faults
b Improved discrimination with LV fuse
Principle of operation
The current transformer feeds a trip coil that is normally shunted by a time fuse link.
In the event of a fault the fuse ruptures, diverting all the fault current through the trip
coil, tripping the breaker. A residually connected trip coil provides instantaneous
earth fault protection.
AMTED399086EN 7
Presentation VIP protection relays
Self-powered reliability
Flexibility
The relay provides for a wide range of protection settings for most applications.
VIP 300 The IDMT characteristics employed for both the overcurrent and earth fault elements
b Pick-up current ranges: RN2c, RE2c, CN2, CE2 can be easily adjusted to provide discrimination with upstream MV and downstream
Overcurrent: 20-200 A. LV protective devices. Fast power-up of the VIP 300 also provides immediate
Earth fault: 2-160 A.
CE6 and RN6c Overcurrent: 80-800 A.
protection and can detect faults instructing the CB to trip in less than 40 ms.
Earth fault: 8 A to 640 A.
Hardened electronics Certified EMC performance to IEC
60255 and EN 50061, EN50082. Reliability
b Separate overcurrent and earth fault trip indication. The relay has a self monitoring device and diagnostic routine that constantly checks
b Flashing LED’s indicate when the relay is operating under the operation of the relay automatically.
fault conditions.
Self-powered reliability
PE57159
The VIP 300 protection relay is a self powered microprocessor based device which
requires no external DC power source or batteries, making it the ideal solution for
location in remote areas where auxiliary supplies are not readily available.
Ease of use
VIP 300 has improved operation and control with the relay settings being clearly
displayed on the front panel. Manual reset flags show separate ‘tripped on fault’ for
either phase or earth fault conditions.
VIP 35 Testing
provides protection against phase-to-phase faults The VAP 6 hand held test unit, is available to provide a simple check of the integrity
and earth faults. of the relay and can also be used to perform trip tests on the circuit breaker.
The circuit breaker “trip inhibit” facility allows the relay to be tested without tripping
the circuit breaker. Secondary injection can be carried out using conventional test
PE56826
equipment.
The VIP 30 and VIP 35 are self-powered devices, requiring no external DC power
source or batteries. They are designed for use in distribution networks providing
protection for transformers.
VAP 6
8 AMTED399086EN
Presentation Sepam series 10
Sepam series 10 is a high-quality protection relay that represents the most cost-
PB103446
AMTED399086EN 9
Presentation Sepam series 10
User-machine interface and dimensions
User-machine interface
1 Back-lit display
DE53450_SE
2 Status LEDs
3 Fault LEDs
4 Button for Sepam reset and maximeter reset
5 Battery housing (Sepam series 10 A)
6 Protection cover for settings
7 Identification zone
8 Lead-seal accessory
9 Button for setting selection and confirmation
10 Buttons for selection in a menu
11 Button to cancel entry
12 Buttons for setting adjustments
13 Button for menu selection and LED test
14 Menu pictograms
15 Cursor for menu selection
Dimensions
DE53451_SE
10 AMTED399086EN
Presentation Sepam series 10
Protection functions
t
DE53228
AMTED399086EN 11
Presentation Sepam series 10
Protection functions
1000
Tripping curve
b DT: Definite time
b SIT/A: IEC standard inverse
b VIT/B: IEC very inverse
b LTI/B: IEC long-time inverse
b EIT/C: IEC extremely inverse
100
b MI/D: IEEE moderately inverse
b VI/E: IEEE very inverse
b EI/F: IEEE extremely inverse
b RI
I>, I>> set points
10 DT curve 0.1...24 In (minimum: 1 A)
LTI/B IDMT curves 0.1...2.4 In (minimum: 1 A)
Accuracy ±5% or ±0.02 In
RI Drop out/pick up ratio 95%
SIT/A
Transient overshoot < 10%
1
Io>, Io>> set points
VIT/B DT curve Standard version Setting range: 0.1…24 Ino
(minimum: 1 A)
Sensitive version Setting range: 0.01…2.4 Ino
(minimum: 0.1 A)
EIT/C
High sensitivity Rating 0.2…24 A Setting range: 0.0004…0.05 Ino
0.1 version (Ino = 470 A)
1 2 5 10 20 I/I> Rating 2.0…240 A Setting range: 0.004…0.5 Ino
or (Ino = 470 A)
Io/Io>
IEC curves SI, VI, LTI, EI and RI curve IDMT curves Standard version Setting range: 0.2…2.4 Ino
(minimum: 1 A)
Sensitive version Setting range: 0.01…0.24 Ino
Sec (minimum: 0.1 A)
DE53194
12 AMTED399086EN
Presentation Fault passage indicators
and VPIS
Flair 22D
Flair 200C
Easergy Flair 200C is a remote monitoring unit designed to be installed in the MV
substations of a public-private distribution network or in customers’ substations.
A voltage presence indicating device can be integrated in all the functional units,
either on the cable side. It can be used to check whether or not a voltage
is present across the cables.
Flair 200C
PE58177
VPIS V2
AMTED399086EN 13
Presentation Network remote control
SCADA
Complete visibility
PE58319
14 AMTED399086EN
Presentation Network remote control
T200E telecontrol
PE57071
Internal view
of Easergy T200E
AMTED399086EN 15
Presentation Network remote control
Easergy L500
HV/MV
PE56312
DE40901EN
MV ring
Communication network
Network control centre
L500 network monitoring screen
RN2C RN2C RN2C
16 AMTED399086EN
Presentation Ringmaster selection guide
PE57072-1
RN2c or RN6c RE2c or RE6c RDE2c or RDE6c MU2 or MU6 CN2 SN6 CE2 or CE6 SE6
200 A or 630 A 200 A or 630 A 200 A or 630 A 200 A or 630 A 200 A 630 A 200 A or 630 A 630 A
non extensible extensible double extensible feeder non extensible non extensible extensible extensible
ring main unit ring main unit ring main unit metering unit circuit breaker switch circuit breaker switch
The Ringmaster catalogue allows easy selection and specification, based on a broad
range of worldwide applications.
Included in this publication is:
b panel type specifications
b details of optional accessories
b schematic diagrams
b Installation drawings.
Accessories
Accessories for the Ringmaster range are supplied either fitted or loose, where
stated enabling simple panel configuration on site. Details of accessories are
contained within the panel type pages.
AMTED399086EN 17
18 AMTED399086EN
Ring main units Contents
AMTED399086EN 19
Ring main units Characteristics - Electrical &
Mechanical
Characteristics of Ringmaster
Rated voltage (Ur) kV 12 13.8
Rated frequency (fr) Hz 50/60 50/60
Rated lightning impulse withstand voltage (Up) kV 75 95
Rated power frequency withstand voltage (Ud) kV 28 38
Rated current
Ring switches (Ir) A 630 630
Circuit breaker (Ir) A 200/630 200/630
Ring switch rated short time withstand, 3 s (Ik) kA 16 21
Ring switch earth short time withstand, 3 s (Ik) kA 16 21
Ring switch peak making current (Ip) kA 40 53
Ring switch earth peak making current (Ip) kA 40 53
Circuit breaker short time withstand, 3 s (Ik) kA 16 21
Ciruit breaker earth short time withstand, 3 s (Ik) kA 16 21
Circuit breaker peak making current (Ip) kA 40 53
Circuit breaker earth peak making current (Ip) kA 40 53
Internal arc withstand kA 16 21
Number of operating cycles
Mechanical: ring switch (main) 1000 1000
ring switch (in option) 5000 5000
ring switch (earth) 1000 1000
circuit breaker (main) 2000 2000
circuit breaker (earth) 1000 1000
circuit breaker (at rated short circuit breaking current) 11 10
SF6 gas
Pressure bar G 0.35 0.55
Weight (RN2c/RN6c) g 516 592
Weight (RE2c) g 612 703
20 AMTED399086EN
Ring main units Characteristics - Electrical &
Mechanical
AMTED399086EN 21
Ring main units Non-extensible ring main units
Specification
22 AMTED399086EN
Ring main units Non-extensible ring main units
Accessories
RN2c-T1 RN2c-T2 RN2c-T3 RN2c-T4 RN2c-T5 RN2c-T25 RN6c-T1 RN6c-T25 Kit no.
TFL VIP 300 VIP 30 VIP 35 Glass TFL Sepam 10 VIP 300 Sepam 10
Cable kits
Circuit breaker cable box v v v v v v RMR-A/F47
Circuit breaker cable box with integral cable test facility v v v v v v b b RMR-F325
Gland plate 1 x 3C O O O O O O O O RMR-A316
Gland plate 3 x 1C O O O O O O O O RMR-A319
Small gland plate 1 x 3C O O O O O O O O RMR-A322
Blank aluminium gland plate O O O O O O O O RMR-A320
Brass wiping gland 1 x 3C O O O O O O RMR-A10
Brass wiping gland 3 x 1C O O O O O O O O RMR-A11
Small brass wiping gland 1 x 3C O O O O O O O O RMR-A105
Tubular gland 1 x 3C O O O O O O O O RMR-A12
Tubular gland 3 x 1C O O O O O O O O RMR-A13
Small tubular gland O O O O O O O O RMR-A106
CES5 gland O O O O O O O O RMR-A120
CES5 gland plate 1 x 3C O O O O O O O O RMR-A321
CES5 gland adaptor O O O O O O O O RMR-A525
6 x ECON cable termination kit O O O O O O O O RMR-A314
3 x STD ECON end cap O O O O O O O O RMR-A370
3 x ECON cable termination kit O O O O O O O O RMR-A315
Top entry cables RH cable box (indoor only) v v v v v v v v RMR-F303
Top entry cables LH cable box (indoor only) v v v v v v v v RMR-F302
Rsw extension box for 2 x 3C cables (left hand) v v v v v v v v RMR-F523
Rsw extension box for 2 x 3C (right hand) v v v v v v v v RMR-F522
Angled gland plate 1 x 3C O O O O O O O O RMR-A317
Split gland plate 1 x 3C O O O O O O O O RMR-A318
Installation items
Transformer mounting kit v v v v v v v v RMR-A/F323
Extension trunking (to clear transformer radiators) O O O O O O O O RMR-A20
Set of padlocks - 11 no O O O O O O O O RMR-A343
Anti-vandal fixings, including tool O O O O O O O O RMR-A344
Foundation bolts (not required for transformer mounting) O O O O O O O O RMR-A22
Multicore pilot glands O O O O O O O O RMR-A342
Time Fuse Link (set of 2 - specify rating as table page 156) O O O O O O O O RMR-A17
RN2c to MU2 installation kit v v v v v v v v RMR-A350
Ariel mounting bracket O O O O O O O O RMR-A201
Operational items
Operating handle b b b b b b b b RMR-F345
LH ring switch control auxiliary sw for motorised v v v v v v v v RMR-F328
mechanism provision
LH ring switch termination block for motorised v v v v v v v v RMR-F363
mechanism provision (not Easergy)
RH ring switch control auxiliary sw for motorised v v v v v v v v RMR-F329
mechanism provision
RH ring switch termination block for motorised v v v v v v v v RMR-F364
mechanism provision (not Easergy)
Provision for motorised mechanism circuit breaker v v v v v v b b RMR-F543
Motorised mechanism - specify voltage v v v v v v v v RMR-F507
CB Termination block for motorised v v v v v v v v RMR-F365
mechanism provision (not Easergy)
Shunt trip coil (20-250 V DC, 110-250 V AC) TFL v v v v v v v v RMR-F581
Shunt trip coil (20-250 V DC, 110-250 V AC) VIP v v v v v v v v RMR-F582
Ring switch cable VPIS indication (3.3-13.8 kV) v v v v v v v v RMR-F341
Circuit breaker cable VPIS indication (11-13.8 kV) v v v v v v v v RMR-F340
Circuit breaker cable VPIS indication (3.3-7.2 kV) v v v v v v v v RMR-F347
Phase indication device O O O O O O O O RMR-A374
VAP 6 test unit for VIP 300/30/35 O O O O O O O O RMR-A202
Emergency trip push button v v v v v v v v RMR-F339
Gas pressure switch for remote indication only v v v v v v v v RMR-F368
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
AMTED399086EN 23
Ring main units Non-extensible ring main units
Accessories
RN2c-T1 RN2c-T2 RN2c-T3 RN2c-T4 RN2c-T5 RN2c-T25 RN6c-T1 RN6c-T25 Kit no.
TFL VIP 300 VIP 30 VIP 35 Glass TFL Sepam 10 VIP 300 Sepam 10
Mechanical interlocks
Circuit breaker - key free, EARTH ON v v v v v v v v RMR-F337
Circuit breaker - key free, MAIN OFF v v v v v v v v RMR-F338
Switch - key free, SWITCH OFF LH v v v v v v v v RMR-F335
Switch - key free, SWITCH OFF RH v v v v v v v v RMR-F336
N. B. specify lock symbol at time of ordering
(3 digits max) not available with motor mechanisms
Earth fault passage indication (choose provision kit
and an EFPI required if not using Easergy T200E)
Phase & earth fault provision for Easergy T200E O O O O O O O O RMR-F310
EFPI provision kit, inside cable box O O O O O O O O RMR-A304
EFPI provision kit, CT outside cable box O O O O O O O O RMR-A305
EFPI provision kit, inside cable box, top entry O O O O O O O O RMR-A308
EFPI provision kit, outside cable box, top entry O O O O O O O O RMR-A309
Bowden “RR” EFPI and CT O O O O O O O O RMR-A422
Bowden STD EFPI type NB O O O O O O O O RMR-A277
Bowden LV reset EFPI type NB1 O O O O O O O O RMR-A278
Bowden LV reset & alarm type NB2 O O O O O O O O RMR-A279
Fundamentals ER “FIND” EFPI and CT O O O O O O O O RMR-A57
N. B. above CT’s are ring type for split core -
please consult Schneider Electric
Key: v Factory fitted accessory O Loose accessory, assembled on site
24 AMTED399086EN
Ring main units Non-extensible ring main unit
200 A
RN2c-T1
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RN2c-T1/16 16 kA, 12 kV, 75 kV BIL
RN2c-T1/21 21 kA, 13.8 kV, 95 kV BIL
AMTED399086EN 25
Ring main units Non-extensible ring main unit
200 A
RN2c-T2
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RN2c-T2/16 16 kA, 12 kV, 75 kV BIL
RN2c-T2/21 21 kA, 13.8 kV, 95 kV BIL
26 AMTED399086EN
Ring main units Non-extensible ring main unit
200 A
RN2c-T3
MV transformer protection
DE60180
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable box (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RN2c-T3/16 16 kA, 12 kV, 75 kV BIL
RN2c-T3/21 21 kA, 13.8 kV, 95 kV BIL
AMTED399086EN 27
Ring main units Non-extensible ring main unit
200 A
RN2c-T4
MV transformer protection
DE60180
28 AMTED399086EN
Ring main units Non-extensible ring main unit
200 A
RN2c-T5
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee off cable box
Order information
Code Rating
RN2c-T5/16 16 kA, 12 kV, 75 kV BIL
RN2c-T5/21 21 kA, 13.8 kV, 95 kV BIL
AMTED399086EN 29
Ring main units Non-extensible ring main unit
200 A
RN2c-T25
RN2c-T25A: RMSCH-45
RN2c-T25AS: RMSCH-46
50/51
50N/51N Environment
49RMS
Indoor/outdoor
IP54
Ratings
Busbar 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Sepam 10 functions ANSI RN2c-T25 (1)
code Ring switch cable earth switch, 16/21 kA 3 s
B BS A AS
Transformer earth switch, 16/21 kA 3 s
Protection Anti-reflex operating handle
Earth-fault Standard 50N/51N b b Provision for motorised mechanism LH/RH ring switch
protection 0.01…2.4 In (2)
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
Sensitive 50G/51G b b
0.2…24 A Indication
Phase-overcurrent protection 50/51 b b b b
Mechanical tripped on fault flag indication
0.1…24 I (3)
Mechanical ON/OFF indication
Mechanical earth/main indication
Thermal overload protection 49RMS b b b b
Gas pressure indication
Phase-overcurrent and b b b b CB auxiliary contacts 1NO 1NC (3)
earth-fault cold load pick-up
CB earth position selected 1NO
Logic Blocking send 68 b b b b
CB earth ON, 1NO
discrimination Blocking reception b b
Test facility
External tripping via digital input b b
Integral ring switch cable test facility
Measurement
Cable
Earth-fault current b b b b
Bottom entry up to 1 x 3C 300 mm²
Phase currents b b b b
Bottom entry up to 3 x 1C 630 mm²
Peak demand currents b b b b
Accessories - see table, page 23
Control and supervision
CB, LH, RH motor kit
Circuit breaker tripping 86 b b b b RH and LH ring switch indication auxiliary contacts 1NO 1NC
and lockout
Earth ON auxiliary contact 1NO
Tripping annunciation 30 b b b b VPIS indication
Tripped on fault, volt free contact b b b b Inverted cable box (indoor only)
Relay watchdog contact b b Transformer mounting kit (4)
Remote CB position monitoring b b Freestanding tee-off cable box
Record of last fault b b b b Order information
Record of last five events b b
Code (1) Rating
Communications RN2c-T25B/21 21 kA, 13.8 kV, 95 kV BIL
Modbus b b RN2c-T25BS/21 21 kA, 13.8 kV, 95 kV BIL
IEC 60870-5-103 b b RN2c-T25A/21 21 kA, 13.8 kV, 95 kV BIL
RN2c-T25AS/21 21 kA, 13.8 kV, 95 kV BIL
(1) B (basic), BS (basic + sensitive earth-fault), A (advanced),
AS (advanced + sensitive earth-fault)
(2) In = Primary CT ratio
(3) Only with T25B and T25BS
(4) BS + AS not available with transformer mounted units.
30 AMTED399086EN
Ring main units Non-extensible ring main unit
630 A
RN6c-T1
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Circuit breaker earth switch 16/21 kA
Ring cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch and circuit breaker with plug
interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch and circuit breaker test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes (indoor only)
Freestanding
Order information
Code Rating
RN6c-T1/16 16 kA, 12 kV, 75 kV BIL
RN6c-T1/21 21 kA, 13.8 kV, 95 kV BIL
AMTED399086EN 31
Ring main units Non-extensible ring main unit
630 A
RN6c-T25
RN6c-T25A: RMSCH-45
RN6c-T25AS: RMSCH-46
50/51
50N/51N Environment
49RMS
Indoor/outdoor
IP54
Ratings
Busbar 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Sepam 10 functions ANSI RN6c-T25 (1)
code Ring switch cable earth switch, 16/21 kA 3 s
B BS A AS
Transformer earth switch, 16/21 kA 3 s
Protection Anti-reflex operating handle
Earth-fault Standard 50N/51N b b Provision for motorised mechanism LH/RH ring switch
protection 0.01…2.4 In (2)
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
Sensitive 50G/51G b b
0.2…24 A Indication
Phase-overcurrent protection 50/51 b b b b
Mechanical tripped on fault flag indication
0.1…24 In (2) Mechanical ON/OFF indication
Thermal overload protection 49RMS b b b b Mechanical earth/main indication
Gas pressure indication
Phase-overcurrent and b b b b
earth-fault cold load pick-up CB auxiliary contacts 1NO 1NC (3)
CB earth position selected 1NO
Logic Blocking send 68 b b b b
discrimination Blocking reception CB earth ON, 1NO
b b
External tripping via digital input b b
Test facility
Integral ring switch cable test facility
Measurement
Earth-fault current b b b b Cable
Bottom entry up to 1 x 3C 300 mm²
Phase currents b b b b
Bottom entry up to 3 x 1C 630 mm²
Peak demand currents b b b b
Control and supervision
Accessories - see table, page 23
CB, LH, RH motor kit
Circuit breaker tripping 86 b b b b
and lockout RH and LH ring switch indication auxiliary contacts 1NO 1NC
Earth ON auxiliary contact 1NO
Tripping annunciation 30 b b b b
VPIS indication
Tripped on fault, volt free contact b b b b
Inverted cable box (indoor only)
Relay watchdog contact b b Transformer mounting kit (4)
Remote CB position monitoring b b Freestanding tee-off cable box
Record of last fault b b b b Order information
Record of last five events b b
Code (1) Rating
Communications
RN6c-T25B/21 21 kA, 13.8 kV, 95 kV BIL
Modbus b b
RN6c-T25BS/21 21 kA, 13.8 kV, 95 kV BIL
IEC 60870-5-103 b b RN6c-T25A/21 21 kA, 13.8 kV, 95 kV BIL
RN6c-T25AS/21 21 kA, 13.8 kV, 95 kV BIL
(1) B (basic), BS (basic + sensitive earth-fault), A (advanced),
AS (advanced + sensitive earth-fault)
(2) In = Primary CT ratio
(3) Only with T25B and T25BS
(4) BS + AS not available with transformer mounted units.
32 AMTED399086EN
Ring main units Extensible ring main units
Specification
AMTED399086EN 33
Ring main units Extensible ring main units
Accessories
34 AMTED399086EN
Ring main units Extensible ring main units
Accessories
AMTED399086EN 35
Ring main units Extensible ring main unit 200 A
RE2c-T1
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Extensible (LHS and RHS)
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 34
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Integral circuit breaker test facility
Inverted cable boxes LH, CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RE2c-T1/16 16 kA, 12 kV, 75 kV BIL
RE2c-T1/21 21 kA, 13.8 kV, 95 kV BIL
36 AMTED399086EN
Ring main units Extensible ring main unit 200 A
RE2c-T2
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 34
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable box LH CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RE2c-T2/16 16 kA, 12 kV, 75 kV BIL
RE2c-T2/21 21 kA, 13.8 kV, 95 kV BIL
AMTED399086EN 37
Ring main units Extensible ring main unit 200 A
RE2c-T3
MV transformer protection
DE60211
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 34
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes LH, CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RE2c-T3/16 16 kA, 12 kV, 75 kV BIL
RE2c-T3/21 21 kA, 13.8 kV, 95 kV BIL
38 AMTED399086EN
Ring main units Extensible ring main unit 200 A
RE2c-T4
MV transformer protection
DE60211
AMTED399086EN 39
Ring main units Extensible ring main unit 200 A
RE2c-T25
MV transformer protection
DE60211
RN2c-T25AS: RMSCH-46
50/51 50/51
Environment
50N/51N
49RMS
50N/51N
49RMS
Indoor/outdoor
IP54
Ratings
Busbar 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Sepam 10 functions ANSI RE2c-T25 (1)
code Ring switch cable earth switch, 16/21 kA 3 s
B BS A AS
Transformer earth switch, 16/21 kA 3 s
Protection Anti-reflex operating handle
Earth-fault Standard 50N/51N b b Extensible RHS
protection 0.01…2.4 In (2)
Provision for motorised mechanism LH/RH ring switch
Sensitive 50G/51G b b Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
0.2…24 A
Phase-overcurrent protection 50/51 b b b b
Indication
0.1…24 In (2) Mechanical tripped on fault flag indication
Thermal overload protection 49RMS b b b b Mechanical ON/OFF indication
Mechanical earth/main indication
Phase-overcurrent and b b b b
earth-fault cold load pick-up Gas pressure indication
CB auxiliary contacts 1NO 1NC (3)
Logic Blocking send 68 b b b b
discrimination Blocking reception CB earth position selected 1NO
b b
CB earth ON, 1NO
External tripping via digital input b b
Test facility
Measurement
Integral ring switch cable test facility
Earth-fault current b b b b
Cable
Phase currents b b b b
Bottom entry up to 1 x 3C 300 mm²
Peak demand currents b b b b
Bottom entry up to 3 x 1C 630 mm²
Control and supervision
Accessories - see table, page 34
Circuit breaker tripping 86 b b b b
and lockout CB, LH, RH motor kit
RH and LH ring switch indication auxiliary contacts 1NO 1NC
Tripping annunciation 30 b b b b
Earth ON auxiliary contact 1NO
Tripped on fault, volt free contact b b b b
VPIS indication
Relay watchdog contact b b Inverted cable box (indoor only)
Remote CB position monitoring b b Transformer mounting kit (4)
Record of last fault b b b b Freestanding tee-off cable box
Record of last five events b b Order information
Communications
Code (1) Rating
Modbus b b
RN2c-T25B/21 21 kA, 13.8 kV, 95 kV BIL
IEC 60870-5-103 b b RN2c-T25BS/21 21 kA, 13.8 kV, 95 kV BIL
RN2c-T25A/21 21 kA, 13.8 kV, 95 kV BIL
(1) B (basic), BS (basic + sensitive earth-fault), A (advanced),
AS (advanced + sensitive earth-fault) RN2c-T25AS/21 21 kA, 13.8 kV, 95 kV BIL
(2) In = Primary CT ratio
(3) Only with T25B and T25BS
(4) BS + AS not available with transformer mounted units.
40 AMTED399086EN
Ring main units Double Extensible ring main unit
200 A or 630 A
RDE2c, RDE6c
MV transformer protection
DE60211-B
AMTED399086EN 41
42 AMTED399086EN
Circuit breaker, metering Contents
and switches
AMTED399086EN 43
Circuit breaker, metering Non-extensible circuit breakers
and switches
200 A
Specification
44 AMTED399086EN
Circuit breaker, metering Non-extensible circuit breakers
and switches
200 A
Accessories
AMTED399086EN 45
Circuit breaker, metering Non-extensible circuit breaker
and switches
200 A
CN2-T1
46 AMTED399086EN
Circuit breaker, metering Non-extensible circuit breaker
and switches
200 A
CN2-T6
AMTED399086EN 47
Circuit breaker, metering Non-extensible circuit breaker
and switches
200 A
CN2-T25
48 AMTED399086EN
Circuit breaker, metering Non-extensible switches 630 A
and switches Specification
SN6-S1 SN6-S2
Manual operation Provision for actuator
Environment
Indoor / outdoor b b
IP54 b b
Ratings
Normal rated current 630 A b b
13.8 kV 21 kA 3 seconds 95 kV BIL b b
Cable earth switch 21 kA 3 seconds b b
Transformer earth switch 3.15 kA 3 seconds b b
Mechanism
Independent manual b b
Provision for actuator 24 V DC b
Actuator 24 V DC O
Indication
Mechanical ON/OFF b b
Mechanical EARTH/MAIN b b
VPIS indication (6.6 - 13.8 kV) O O
Auxiliary switch contacts 1NO 2NC b
Phase and earth fault detection CT’s for Easergy 200E O
Provision for EFPI O O
Test facility
Integral cable test facility b b
Standard features
Operating handle b b
Transformer earth switch 3.15 kA 3 seconds b b
Cable (see available cable kit accessories)
Bottom entry up 300 mm2 1 x 3C b b
Bottom entry up 630 mm2 3 x 1C b b
Key: b Standard feature O Optional feature
AMTED399086EN 49
Circuit breaker, metering Non-extensible switches 630 A
and switches Accessories
50 AMTED399086EN
Circuit breaker, metering Non-extensible switch 630 A
and switches SN6-S1
Switch disconnector
DE60193
AMTED399086EN 51
Circuit breaker, metering Non-extensible switch 630 A
and switches SN6-S2
Switch disconnector
DE60194
52 AMTED399086EN
Circuit breaker, metering Non-extensible metering unit
and switches
200 A
Specification
AMTED399086EN 53
Circuit breaker, metering Non-extensible metering unit
and switches
200 A
Accessories
54 AMTED399086EN
Circuit breaker, metering Non-extensible metering unit
and switches
200 A
MU2-M1
AMTED399086EN 55
Circuit breaker, metering Non-extensible metering unit
and switches
200 A
MU2-M2
56 AMTED399086EN
Circuit breaker, metering Non-extensible metering unit
and switches
200 A
MU2-M3
AMTED399086EN 57
Circuit breaker, metering Non-extensible metering units
and switches
630 A
Specification
58 AMTED399086EN
Circuit breaker, metering Non-extensible metering units
and switches
630 A
Accessories
AMTED399086EN 59
Circuit breaker, metering Non-extensible metering units
and switches
630 A
MU6-N**
Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16 kA 1 s
Normal current rating 630 A
Normal rated voltage 12 kV
Normal rated BIL 75 kV
Standard features
Direct coupling between RMU and transformer
(optional freestanding cable connection)
Cable connection
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Cable box
Glands and plates
Installation kits
See page 59 for details
Order information
Code Rating
MU6-N** 16 kA, 12 kV, 75 kV BIL
60 AMTED399086EN
Circuit breaker, metering Extensible circuit breakers
and switches
200 A
Specification
(*) See complete titles footer CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2-
T2 T3 T7 T11 T12 T13 T14 T15 T16 T19 T20 T21 T25
Environment
Indoor / outdoor b b b b b b b b b b b b b
IP54 b b b b b b b b b b b b b
Ratings
Busbars 630 A b b b b b b b b b b b b b
Circuit breaker normal rated current 200 A b b b b b b b b b b b b b
12 kV 16 kA 3 seconds 75 kV BIL b b b b b b b b b b b b b
13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O O O O O O O O O
Cable earth switch 16 kA 3 seconds b b b b b b b b b b b b b
Cable earth switch 21 kA 3 seconds O O O O O O O O O O O O O
Mechanism
Independent manual b b b b b b b b b b b b b
Provision for actuator 24 V DC b b b b
Actuator 24 V DC O O O O
Operating handle b b b b b b b b b b b b b
Protection system
CT’s dual ratio - 500/200/1 A class x b b
Overcurrent relay - VIP 30 b
CT’s dual ratio - 100/50/5 A class X b
CT’s dual ratio 200/100/1 A 5P20 b
CT ratio - 200/1 A class X b b b b b b b b b
Overcurrent & earth fault CT operated trip coils b
Overcurrent & earth fault relay VIP 35 b
Time fuse link O
IDMT overcurrent & earth fault relay - VIP 300 b b b b b b b b b
IDMT overcurrent and earth fault relay Sepam 10 b
20 V-250 shunt trip coil b b b b b b b b b b b b b
Auxiliary switch 1NO 2NC b b b b b b b b b b b b b
Metering
CT’s -200/100/5 A 0.5s 10 VA b b b b b b b
VT’s -13.8 kV/110 V 0.5 10 VA 13.8/110 V/110 V 0.5 50 VA 3P 20 VA b b
VT’s -11 kV/110 V 0.5 50 VA b b b
VT’s -6.6 kV/110 V 0.5 50 VA b b
VT’s phase - phase, CT’s L1 & L3 b b b b
VT’s phase - earth, CT’s L1, L2 & L3 b b b
Indication
Mechanical ON/OFF b b b b b b b b b b b b b
Mechanical EARTH/MAIN b b b b b b b b b b b b b
Cable VPIS indication (6.6 - 13.8 kV) O O O O O O O O O O O O O
Auxiliary switch contacts 1NO 2NC b b b b b b b b b b b b b
Earth selected auxiliary contacts 1NO b b b b
Test facility
Integral cable test facility b b b b b b b b b b b b b
Cable
Bottom entry up to 300 mm2 1 x 3C b b b b b b b b b b b b b
Bottom entry up to 630 mm2 3 x 1C b b b b b b b b b b b b b
Top entry cables O O O O O O O O O O O O O
Key: b Standard feature O Optional feature
(*) Complete titles:
CE2-T2 - VIP 300
CE2-T3 - VIP 300 + Metering [Phase - Phase] (VT 11 kV/110 V)
CE2-T7 - Time Fuse Link (TFL)
CE2-T11 - VIP 300 + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE2-T12 - VIP 300 + Provision for Actuator
CE2-T13 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 11 kV/110 V)
CE2-T14 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE2-T15 - VIP 30
CE2-T16 - VIP 35
CE2-T19 - VIP 300 + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE2-T20 - VIP 300 + Metering [Phase - Earth] (VT 11 kV/110 V)
CE2-T21 - VIP 300 + Provision for Actuator + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE2-T25 - Sepam 10
AMTED399086EN 61
Circuit breaker, metering Extensible circuit breakers
and switches
200 A
Accessories
(*) See complete titles CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- Kit no.
footer T2 T3 T7 T11 T12 T13 T14 T15 T16 T19 T20 T21 T25
Cable kits
Gland plate 1 x 3C O O O O O O O O O O O O O RMR-A48
Gland plate 3 x 1C O O O O O O O O O O O O O RMR-A49
Angled gland plates (RMR) O O O O O O O O O O O O O RMR-A50
Blank aluminium gland plate O O O O O O O O O O O O O RMR-A52
Brass wiping gland 1 x 3C O O O O O O O O O O O O O RMR-A10
Brass wiping gland 3 x 1C O O O O O O O O O O O O O RMR-A11
Tubular gland 1 x 3C O O O O O O O O O O O O O RMR-A12
Tubular gland 3 x 1C O O O O O O O O O O O O O RMR-A13
CES5 gland plate 1 x 3C O O O O O O O O O O O O O RMR-A132
Top entry cables standard panels v v v v v v RMR-F93
Top entry cables MU6 only v v v v v v v RMR-F94
Installation items
3 phase busbars 630 A O O O O O O RMR-A14
3 phase busbars 630 A O O O O O O O RMR-A78
Busbar end kit O O O O O O O O O O O O O RMR-A15
Set of padlocks - 6 no O O O O O O O O O O O O O RMR-A18/6
Foundation bolts (not required b b b b b b b b b b b b b RMR-A22
for transformer mounting)
Multicore pilot glands O O O O O O O O O O O O O RMR-A16
Time Fuse Link (set of 2 - specify O RMR-A17
rating as table page 156)
Operational items
Operating handle b b b b b b b b b b b b b RMR-A23
Cable VPIS indication v v v v v v v v v v v v v RMR-F108
(6.6 - 13.8 kV)
Neon lamp test unit v v v v v v v v v v v v v RMR-A24
(including lamp)
Neon lamp O O O O O O O O O O O O RMR-A81
VAP 6 test unit for VIP 300 O O O O O O O O O O O O RMR-A202
Actuator 24 V DC v v v RMR-F67
Polarity conversion kit (1) v v v RMR-F391
Mechanical interlocks
Key free, EARTH ON v v v v v v v RMR-F85
Key free, MAIN OFF v v v v v v v RMR-F86
N. B. specify lock symbol at time
of ordering (3 digits max)
not available with motor
mechanisms
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
(1) Only required when unit is used with RE2c ring main units and automation.
62 AMTED399086EN
Circuit breaker, metering Extensible circuit breakers
and switches
200 A
Accessories
(*) See complete titles CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- Kit no.
footer T2 T3 T7 T11 T12 T13 T14 T15 T16 T19 T20 T21 T25
Earth fault passage
indication (choose
provision kit and an EFPI
required if not using
Easergy 200E)
EFPI provision kit, inside O O O O O O O O O O O O O RMR-F30
cable box
Bowden STD EFPI type NB O O O O O O O O O O O O O RMR-A277
Bowden LV reset EFPI type NB1 O O O O O O O O O O O O O RMR-A278
Bowden LV reset & alarm O O O O O O O O O O O O O RMR-A279
type NB2
Bowden “RR” EFPI and CT O O O O O O O O O O O O O RMR-A56
Fundamentals ER “FIND” O O O O O O O O O O O O O RMR-A57
EFPI and CT
Ancillary items
Tool box O O O O O O O O O O O O O RMR-A80
Order code
12 kV, 16 kA, 75 kV BIL, 0.35bG CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- N/A CE2- N/A N/A
T2/16 T3/16 T7/16 T11/16 T12/16 T13/16 T14/16 T15/16 T16/16 T20/16
13.8 kV, 21 kA, 95 kV BIL, 0.55bG CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- N/A CE2- CE2-
T2/21 T3/21 T7/21 T11/21 T12/21 T13/21 T14/21 T15/21 T16/21 T19/21 T21/21 T25/21
General arrangement drawing RMINST-03 RMINST-02 RMINST-03 RMINST-02 RMINST-03 RMINST-02 RMINST-02 RMINST-03 RMINST-03 RMINST-02 RMINST-02 RMINST-02 RMINST-03
Page 100 Page 99 Page 100 Page 99 Page 100 Page 99 Page 99 Page 100 Page 100 Page 99 Page 99 Page 99 Page 100
Schematic drawing RMSCH-07 RMSCH-09 RMSCH-06 RMSCH-09 RMSCH-19 RMSCH-20 RMSCH-20 RMSCH-07 RMSCH-07 RMSCH-35 RMSCH-35 RMSCH-36 RMSCH-47 to 50
Page 129 Page 131 Page 128 Page 131 Page 135 Page 136 Page 136 Page 129 Page 129 Page 141 Page 141 Page 142 Pages 122 to 125
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
(*) Complete titles:
CE2-T2 - VIP 300
CE2-T3 - VIP 300 + Metering [Phase - Phase] (VT 11 kV/110 V)
CE2-T7 - Time Fuse Link (TFL)
CE2-T11 - VIP 300 + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE2-T12 - VIP 300 + Provision for Actuator
CE2-T13 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 11 kV/110 V)
CE2-T14 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE2-T15 - VIP 30
CE2-T16 - VIP 35
CE2-T19 - VIP 300 + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE2-T20 - VIP 300 + Metering [Phase - Earth] (VT 11 kV/110 V)
CE2-T21 - VIP 300 + Provision for Actuator + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE2-T25 - Sepam 10
AMTED399086EN 63
Circuit breaker, metering Extensible circuit breaker 200 A
and switches CE2-T2
64 AMTED399086EN
Circuit breaker, metering Extensible circuit breaker 200 A
and switches CE2-T7
AMTED399086EN 65
Circuit breaker, metering Extensible circuit breaker 200 A
and switches CE2-T*
66 AMTED399086EN
Circuit breaker, metering Extensible circuit breaker 200 A
and switches CE2-T12
AMTED399086EN 67
Circuit breaker, metering Extensible circuit breaker 200 A
and switches CE2-T**
68 AMTED399086EN
Circuit breaker, metering Extensible circuit breaker 200 A
and switches CE2-T13
AMTED399086EN 69
Circuit breaker, metering Extensible circuit breaker 200 A
and switches CE2-T15
70 AMTED399086EN
Circuit breaker, metering Extensible circuit breaker 200 A
and switches CE2-T16
AMTED399086EN 71
Circuit breaker, metering Extensible circuit breaker 200 A
and switches CE2-T25
72 AMTED399086EN
Circuit breaker, metering Extensible circuit breakers
and switches
630 A
Specification
(*) See complete titles footer CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6-
T4 T5 T6 T8 T9 T10 T22 T23 T24 T25
Environment
Indoor / outdoor b b b b b b b b b b
IP54 b b b b b b b b b b
Ratings
Busbars 630 A b b b b b b b b b b
Circuit breaker normal rated current 630 A b b b b b b b b b b
12 kV 16 kA 3 seconds 75 kV BIL b b b b b b b b b b
13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O O O O O O
Cable earth switch 16 kA 3 seconds b b b b b b b b b b
Cable earth switch 21 kA 3 seconds O O O O O O O O O O
Mechanism
Independent manual b b b b b b b b b b
Provision for actuator 24 V DC b b b b
Actuator 24 V DC O O O O
Operating handle b b b b b b b b b b
Protection system
CT ratio - 800/1 A class X b b b b b b b b b
CT dual ratio 800/400/1 A 5P20 b
IDMT overcurrent & earth fault relay - VIP 300 b b b b b b b b b
IDMT overcurrent & earth fault relay Sepam 10 b
20 V-250 V shunt trip coil b b b b b b b b b b
Auxiliary switch 1NO 2NC b b b b b b b b b b
Metering
CT’s - 400/200/5 A 0.5s 10 VA b b b b b b b
VT’s - 13.8 kV/110 V/110 V/ 0.5 50 VA 3P 20 VA b b
VT’s - 11 V/110 V 0.5 50 VA b b b
VT’s - 6.6 kV/110 V 0.5 50 VA b b
VT’s - phase - phase, CT’s L1 & L3 b b b b
VT’s phase - earth, CT’s L1, L2 & L3 b b b
Indication
Mechanical ON/OFF b b b b b b b b b b
Mechanical EARTH/MAIN b b b b b b b b b b
Cable VPIS indication (6.6 - 13.8 kV) O O O O O O O O O O
Auxiliary switch contacts 1NO 2NC b b b b b b b b b b
Indication CT 600/5 A 5 VA CLS 1 L2 ph b b b b b b b b b
Ammeter 0-600 A b b b b b b b b b
Earth selected auxiliary contacts 1NO b b b
Gas pressure indicator b b b b b b b b b b
Test facility
Integral cable test facility b b b b b b b b b b
Cable
Bottom entry up to 300 mm2 1 x 3C b b b b b b b b b b
Bottom entry up to 630 mm2 3 x 1C b b b b b b b b b b
Top entry cables O O O O O O O O O O
Key: b Standard feature O Optional feature
(*) Complete titles:
CE6-T4 - VIP 300
CE6-T5 - VIP 300 + Metering [Phase - Phase] (VT 11 kV/110 V)
CE6-T6 - VIP 300 + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE6-T8 - VIP 300 + Provision for Actuator
CE6-T9 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 11 kV/110 V)
CE6-T10 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE6-T22 - VIP 300 + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE6-T23 - VIP 300 + Provision for Actuator + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE6-T24 - VIP 300 + Metering [Phase - Earth] (VT 11 kV/110 V)
CE6-T25 - Sepam 10
AMTED399086EN 73
Circuit breaker, metering Extensible circuit breakers
and switches
630 A
Accessories
(*) See complete titles footer CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6- Kit no.
T4 T5 T6 T8 T9 T10 T22 T23 T24 T25
Cable kits
Gland plate 1 x 3C O O O O O O O O O O RMR-A48
Gland plate 3 x 1C O O O O O O O O O O RMR-A49
Angled gland plates (RMR) O O O O O O O O O O RMR-A50
Blank aluminium gland plate O O O O O O O O O O RMR-A52
Brass wiping gland 1 x 3C O O O O O O O O O O RMR-A10
Brass wiping gland 3 x 1C O O O O O O O O O O RMR-A11
Tubular gland 1 x 3C O O O O O O O O O O RMR-A12
Tubular gland 3 x 1C O O O O O O O O O O RMR-A13
CES5 gland plate 1 x 3C O O O O O O O O O O RMR-A132
Top entry cables standard panels v v v RMR-F93
Top entry cables MU6 only v v v v v v v RMR-F94
Installation items
3 phase busbars 630 A O O O RMR-A14
3 phase busbars 630 A O O O O O O O RMR-A78
Busbar end kit O O O O O O O O O O RMR-A15
Set of padlocks - 6 no O O O O O O O O O O RMR-A18/6
Foundation bolts (not required for b b b b b b b b b b RMR-A22
transformer mounting)
Multicore pilot glands O O O O O O O O O O RMR-A16
Operational items
Operating handle b b b b b b b b b b RMR-A23
Cable VPIS indication (6.6 - 13.8 kV) v v v v v v v v v v RMR-A108
Neon lamp test unit (including lamp) O O O O O O O O O O RMR-A24
Neon lamp O O O O O O O O O O RMR-A81
VAP 6 test unit for VIP 300 O O O O O O O O RMR-A202
Actuator 24 V DC v v v v RMR-F67
Polarity conversion kit (1) v v v v RMR-F391
Mechanical interlocks
Key free, EARTH ON v v v v v v RMR-F85
Key free, MAIN OFF v v v v v v RMR-F86
N. B. specify lock symbol at time of ordering
( 3 digits max) not available with motor
mechanisms
Earth fault passage indication
(choose provision kit and an EFPI
required if not using Easergy T200E)
EFPI provision kit, inside cable box O O O O O O O O O O RMR-F30
Bowden STD EFPI type NB O O O O O O O O O O RMR-A277
Bowden LV reset EFPI type NB1 O O O O O O O O O O RMR-A278
Bowden LV reset & alarm type NB2 O O O O O O O O O O RMR-A279
Bowden “RR” EFPI and CT O O O O O O O O O O RMR-A56
Fundamentals ER “FIND” EFPI and CT O O O O O O O O O O RMR-A57
Ancillary items
Tool box O O O O O O O O O O RMR-A80
Order code
12 kV, 16 kA, 75 kV BIL, 0.35bG CE6- CE6- CE6- CE6- CE6- CE6- N/A N/A CE6-
T4/16 T5/16 T6/16 T8/16 T9/16 T10/16 T24/16
13.8 kV, 21 kA, 95 kV BIL, 0.55bG CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6- N/A CE6-
T4/21 T5/21 T6/21 T8/21 T9/21 T10/21 T22/21 T23/21 T25/21
General arrangement drawing RMINST-03 RMINST-02 RMINST-02 RMINST-03 RMINST-02 RMINST-02 RMINST-02 RMINST-02 RMINST-02 RMINST-03
Page 100 Page 99 Page 99 Page 100 Page 99 Page 99 Page 99 Page 99 Page 99 Page 100
Schematic drawing RMSCH-08 RMSCH-10 RMSCH-10 RMSCH-23 RMSCH-24 RMSCH-24 RMSCH-37 RMSCH-38 RMSCH-37 RMSCH-47 to 50
Page 130 Page 132 Page 132 Page 139 Page 140 Page 140 Page 143 Page 144 Page 143 Pages 122 to 125
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
(1) Only required when unit is used with RE2c ring main units and automation.
74 AMTED399086EN
Circuit breaker, metering Extensible circuit breaker 630 A
and switches CE6-T4
AMTED399086EN 75
Circuit breaker, metering Extensible circuit breaker 630 A
and switches CE6-T*
76 AMTED399086EN
Circuit breaker, metering Extensible circuit breaker 630 A
and switches CE6-T8
AMTED399086EN 77
Circuit breaker, metering Extensible circuit breaker 630 A
and switches CE6-T25
78 AMTED399086EN
Circuit breaker, metering Extensible circuit breaker 630 A
and switches CE6-T**
AMTED399086EN 79
Circuit breaker, metering Extensible switches 630 A
and switches Specification
80 AMTED399086EN
Circuit breaker, metering Extensible switches 630 A
and switches Accessories
AMTED399086EN 81
Circuit breaker, metering Extensible switch 630 A
and switches SE6-S1
Switch disconnector
DE60201
82 AMTED399086EN
Circuit breaker, metering Extensible switch 630 A
and switches SE6-S2
Switch disconnector
DE60202
AMTED399086EN 83
Circuit breaker, metering Extensible switch 630 A
and switches SE6-E1
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-N/A
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical earth/main indicator
Gas pressure indicator
Test facility
N/A
Cable
N/A
Accessories
Interlocks
Busbar kit
See page 81 for details
Order information
Code Rating
SE6-E1/21 21 kA, 13.8 kV, 95 kV BIL
84 AMTED399086EN
Circuit breaker, metering Extensible bus-section 630 A
and switches Specification
AMTED399086EN 85
Circuit breaker, metering Extensible bus-section 630 A
and switches Accessories
86 AMTED399086EN
Circuit breaker, metering Extensible bus-section 630 A
and switches SE6-B1
Bus-section disconnector
DE60204
AMTED399086EN 87
Circuit breaker, metering Extensible bus-section 630 A
and switches CE6-B3
88 AMTED399086EN
Circuit breaker, metering Extensible bus-section 630 A
and switches CE6-B5
AMTED399086EN 89
90 AMTED399086EN
Remote control Contents
Telecontrol cabinet
Easergy T200 E - Specification 92
Easergy T200-E02M 93
Easergy T200-E04M 93
AMTED399086EN 91
Remote control Telecontrol cabinet
Easergy T200 E - Specification
92 AMTED399086EN
Remote control Telecontrol cabinet
Easergy T200-E02M
Easergy T200-E04M
AMTED399086EN 93
94 AMTED399086EN
Installation drawings Contents
Summary 96
Typical switchboard 97
Extensible units 98
ref RMINST-01, RMINST-02, RMINST-03
AMTED399086EN 95
Installation drawings Summary
Non-extensible equipment
Schematic Page number General arrangement Page number
diagram drawing
Ring main units 200 A RN2c-T1 RMSCH-01 112 RMINST-06 103
RN2c-T2 RMSCH-03 114 RMINST-06 103
RN2c-T3 RMSCH-02 113 RMINST-06 103
RN2c-T4 RMSCH-15 115 RMINST-06 103
RN2c-T5 RMSCH-01 112 RMINST-06 103
RN2c-T25B RMSCH-43 116 RMINST-06 103
RN2c-T25BS RMSCH-44 117 RMINST-06 103
RN2c-T25A RMSCH-45 118 RMINST-06 103
RN2c-T25AS RMSCH-46 119 RMINST-06 103
Ring main units 630 A RN6c-T1 RMSCH-42 120 RMINST-06 103
RN6c-T25B RMSCH-43 116 RMINST-06 103
RN6c-T25BS RMSCH-44 117 RMINST-06 103
RN6c-T25A RMSCH-45 118 RMINST-06 103
RN6c-T25AS RMSCH-46 119 RMINST-06 103
Circuit breakers 200 A CN2-T1 RMSCH-26 127 RMINST-04 101
CN2-T6 RMSCH-11 126 RMINST-06 103
CN2-T25B RMSCH-47 122 RMINST-03 100
CN2-T25BS RMSCH-48 123 RMINST-03 100
CN2-T25A RMSCH-49 124 RMINST-03 100
CN2-T25AS RMSCH-50 125 RMINST-03 100
Switches 630 A SN6-S1 N/A - RMINST-04 101
SN6-S2 RMSCH-28 145 RMINST-04 101
Metering units MU2-M1, MU2-M2, MU2-M3 RMSCH-14 121 RMINST-07/08 105-104
MU6-N1, MU6-N2, MU6-N3 RMSCH-14 121 RMINST-07/08 105-104
MU6-N5 RMSCH-14 121 RMINST-07/08 105-104
Telecontrol cabinets Easergy T200-E02M RMSCH-17 147 RMINST-11 106
Easergy T200-E04M RMSCH-17 147 RMINST-11 106
Extensible equipment
Schematic Page number General arrangement Page number
diagram drawing
Ring main units 200 A RN2c-T1 RMSCH-01 112 RMINST-06 103
RN2c-T2 RMSCH-03 114 RMINST-06 103
RN2c-T3 RMSCH-02 113 RMINST-06 103
RN2c-T4 RMSCH-15 115 RMINST-06 103
RE2c-T25B RMSCH-43 116 RMINST-06 103
RE2c-T25BS RMSCH-44 117 RMINST-06 103
RE2c-T25A RMSCH-45 118 RMINST-06 103
RE2c-T25AS RMSCH-46 119 RMINST-06 103
Circuit breakers 200 A CE2-T2 RMSCH-07 129 RMINST-03 100
CE2-T3 RMSCH-09 131 RMINST-02 99
CE2-T7 RMSCH-06 128 RMINST-03 100
CE2-T11 RMSCH-09 131 RMINST-02 99
CE2-T12 RMSCH-19 135 RMINST-03 100
CE2-T13 RMSCH-20 136 RMINST-02 99
CE2-T14 RMSCH-20 136 RMINST-02 99
CE2-T15 RMSCH-12 133 RMINST-03 100
CE2-T16 RMSCH-13 134 RMINST-03 100
CE2-T19 RMSCH-35 141 RMINST-02 99
CE2-T20 RMSCH-35 141 RMINST-02 99
CE2-T21 RMSCH-36 142 RMINST-02 99
CE2-T25B RMSCH-47 122 RMINST-02 99
CE2-T25BS RMSCH-48 123 RMINST-02 99
CE2-T25A RMSCH-49 124 RMINST-02 99
CE2-T25AS RMSCH-50 125 RMINST-02 99
Circuit breakers 630 A CE6-T4 RMSCH-08 130 RMINST-03 100
CE6-T5 RMSCH-10 132 RMINST-02 99
CE6-T6 RMSCH-10 132 RMINST-02 99
CE6-T8 RMSCH-23 139 RMINST-03 100
CE6-T9 RMSCH-24 140 RMINST-02 99
CE6-T10 RMSCH-24 140 RMINST-02 99
CE6-T22 RMSCH-37 143 RMINST-02 99
CE6-T23 RMSCH-38 144 RMINST-02 99
CE6-T24 RMSCH-37 143 RMINST-02 99
CE6-T25B RMSCH-47 122 RMINST-02 99
CE6-T25BS RMSCH-48 123 RMINST-02 99
CE6-T25A RMSCH-49 124 RMINST-02 99
CE6-T25AS RMSCH-50 125 RMINST-02 99
Switches 630 A SE6-S1 N/A - RMINST-03 100
SE6-S2 RMSCH-29 146 RMINST-03 100
SE6-E1 N/A - RMINST-03 100
Bus sections 630 A SE6-B1 N/A - RMINST-01 98
CE6-B3 RMSCH-21 137 RMINST-01 98
CE6-B5 RMSCH-22 138 RMINST-01 98
96 AMTED399086EN
Installation drawings Typical switchboard
DE59806
799
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500
AMTED399086EN 97
Installation drawings Extensible unit
ref RMINST-01
DE59807
799
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500
98 AMTED399086EN
Installation drawings Extensible unit
DE59808
ref RMINST-02
799
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500
AMTED399086EN 99
Installation drawings Extensible unit
ref RMINST-03
DE59809
799
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500
100 AMTED399086EN
Installation drawings Non-extensible unit
DE59811
ref RMINST-04
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500
AMTED399086EN 101
Installation drawings Extensible ring main unit
c/w tee off cable box
ref RMINST-22
DE59810
985
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500
102 AMTED399086EN
Installation drawings Non-extensible ring main unit
for transformer mounting unit
ref RMINST-06
DE59812
DE60268
AMTED399086EN 103
Installation drawings Non-extensible ring main unit
c/w MU2 metering unit & tee off cable box
ref RMINST-08
DE59814
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500
104 AMTED399086EN
Installation drawings Non-extensible metering unit
DE59813
ref RMINST-07
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500
AMTED399086EN 105
Installation drawings Telecontrol cabinet
ref RMINST-11
DE59815
DE60268
106 AMTED399086EN
Schematic diagrams Contents
AMTED399086EN 107
Schematic diagrams Schematic legends
Specification
CN2-T6 100/50/5 A
Class X
CN2-T25 200/100/1 A
5P20
CE2-T7 100/50/5 A
Class X
CE2-T2 200/1 A
Class X
CE2-T3 200/1 A 200/100/5 A 11000/110 V
Class X 10 VA Class 0.5s 50 VA Class 0.5
CE2-T11 200/1 A 200/100/5 A 6600/110 V
Class X 10 VA Class 0.5s 50 VA Class 0.5
CE2-T12 200/1 A
Class X
CE2-T13 200/1 A 200/100/5 A 11000/110 V
Class X 10 VA Class 0.5s 50 VA Class 0.5
CE2-T14 200/1 A 200/100/5 A 6600/110 V
Class X 10 VA Class 0.5s 50 VA Class 0.5
CE2-T15 200/1 A
Class X
CE2-T16 200/1 A
Class X
CE2-T19 200/1 A 200/100/5 A 13800/110 V/110 V
Class X 10 VA Class 0.5s 50 VA Class 0.5
20 VA class 3 P
CE2-T20 200/1 A 200/100/5 A 11000/110 V/110 V
Class X 10 VA Class 0.5s 50 VA Class 0.5
20 VA class 3 P
CE2-T21 200/1 A 200/100/5 A 13800/110 V/110 V
Class X 10 VA Class 0.5s 50 VA Class 0.5
20 VA class 3 P
CE2-T25 200/100/1 A
5P20
108 AMTED399086EN
Schematic diagrams Schematic legends
Specification
AMTED399086EN 109
Schematic diagrams Ring main units accessories
DE59820
L1 L2 L3
110 AMTED399086EN
Schematic diagrams Ring main units accessories
Circuit breaker
DE59821
AMTED399086EN 111
Schematic diagrams Non-extensible / extensible
ring main unit
ref RMSCH-01
DE59822-1
L1
L2
L3
PROVISION FOR
SHUNT TRIP COIL
112 AMTED399086EN
Schematic diagrams Non-extensible / extensible
ring main unit
ref RMSCH-02
DE59824-1
L1
L2
L3
PROVISION FOR
SHUNT TRIP COIL
AMTED399086EN 113
Schematic diagrams Non-extensible / extensible
ring main unit
ref RMSCH-03
DE59823-1
L1
L2
L3
PROVISION FOR
SHUNT TRIP COIL
114 AMTED399086EN
Schematic diagrams Non-extensible / extensible
ring main unit
ref RMSCH-15
DE59825-1
L1
L2
L3
PROVISION FOR
SHUNT TRIP COIL
AMTED399086EN 115
Schematic diagrams Non-extensible / extensible
ring main unit
ref RMSCH-43
DE59853
116 AMTED399086EN
Schematic diagrams Non-extensible / extensible
ring main unit
ref RMSCH-44
DE59854
AMTED399086EN 117
Schematic diagrams Non-extensible / extensible
ring main unit
ref RMSCH-45
DE59855
118 AMTED399086EN
Schematic diagrams Non-extensible / extensible
ring main unit
ref RMSCH-46
DE59856
AMTED399086EN 119
Schematic diagrams Non-extensible ring main unit
ref RMSCH-42
DE59826
L1
L2
L3
120 AMTED399086EN
Schematic diagrams Non-extensible metering unit
DE59834
ref RMSCH-14
L1 L3
AMTED399086EN 121
Schematic diagrams Non-extensible / extensible
circuit breaker units
ref RMSCH-47
DE59857
122 AMTED399086EN
Schematic diagrams Non-extensible / extensible
circuit breaker units
ref RMSCH-48
DE59858
AMTED399086EN 123
Schematic diagrams Non-extensible / extensible
circuit breaker units
ref RMSCH-49
DE59859
124 AMTED399086EN
Schematic diagrams Non-extensible / extensible
circuit breaker units
ref RMSCH-50
DE59860
AMTED399086EN 125
Schematic diagrams Non-extensible
circuit breaker units
ref RMSCH-11
DE59833
L1 L2 L3
126 AMTED399086EN
Schematic diagrams Non-extensible
circuit breaker units
ref RMSCH-26
DE59843
L1 L2 L3
AMTED399086EN 127
Schematic diagrams Extensible circuit breaker units
ref RMSCH-06
DE59828
L1 L2 L3
128 AMTED399086EN
Schematic diagrams Extensible circuit breaker units
DE59829
ref RMSCH-07
L1 L2 L3
AMTED399086EN 129
Schematic diagrams Extensible circuit breaker units
ref RMSCH-08
DE59830
L1 L2 L3
L2
130 AMTED399086EN
Schematic diagrams Extensible circuit breaker units
DE59831
ref RMSCH-09
L1 L2 L3
L1 L3
AMTED399086EN 131
Schematic diagrams Extensible circuit breaker units
ref RMSCH-10
DE59832
L1 L2 L3
L2
L2
L1 L3
132 AMTED399086EN
Schematic diagrams Extensible circuit breaker units
DE59835
ref RMSCH-12
L1
L2
L3
AMTED399086EN 133
Schematic diagrams Extensible circuit breaker units
ref RMSCH-13
DE59835
L1
L2
L3
134 AMTED399086EN
Schematic diagrams Extensible circuit breaker units
DE59837
ref RMSCH-19
L1 L2 L3
AMTED399086EN 135
Schematic diagrams Extensible circuit breaker units
ref RMSCH-20
DE59838
L1 L2 L3
L1 L3
136 AMTED399086EN
Schematic diagrams Extensible circuit breaker units
DE59839
ref RMSCH-21
L1 L2 L3
L2
L1 L3
AMTED399086EN 137
Schematic diagrams Extensible circuit breaker units
ref RMSCH-22
DE59840
L1 L2 L3
L2
L1 L3
138 AMTED399086EN
Schematic diagrams Extensible circuit breaker units
DE59841
ref RMSCH-23
L1 L2 L3
L2
AMTED399086EN 139
Schematic diagrams Extensible circuit breaker units
ref RMSCH-24
DE59842
L1 L2 L3
L2
L1 L3
140 AMTED399086EN
Schematic diagrams Extensible circuit breaker units
DE59846
ref RMSCH-35
L1 L2 L3
L1 L2 L3
AMTED399086EN 141
Schematic diagrams Extensible circuit breaker units
ref RMSCH-36
DE59847
L1 L2 L3
L1 L2 L3
142 AMTED399086EN
Schematic diagrams Extensible circuit breaker units
DE59848
ref RMSCH-37
L1 L2 L3
L2
L1 L2 L3
AMTED399086EN 143
Schematic diagrams Extensible circuit breaker units
ref RMSCH-38
DE59849
L1 L2 L3
L2
L1 L2 L3
144 AMTED399086EN
Schematic diagrams Non-extensible switch units
DE59844
ref RMSCH-28
L1 L2 L3
AMTED399086EN 145
Schematic diagrams Non-extensible switch units
ref RMSCH-29
DE59845
L1 L2 L3
146 AMTED399086EN
Schematic diagrams Telecontrol unit block diagram
DE59827
ref RMSCH-17
90-230 V AC
50 Hz
L1
L2
L3
AMTED399086EN 147
148 AMTED399086EN
Accessories & options Contents
AMTED399086EN 149
Accessories & options Accessories description
MV substation remote monitoring unit
Flair 200C
Voltage indicator and relay VD23
The Flair 200C is an efficient tool for reducing MV substation remote monitoring unit Flair 200C
repair and fault finding times.
It improves quality of service and A product dedicated to remote monitoring of MV substations with a high level
operation for power supply companies. of function integration
Easergy Flair 200C is a remote monitoring unit designed to be installed in the MV
substations of a public-private distribution network or in customers’ substations.
Easergy Flair 200C is a tool that complements control units for MV substations
PE57570
Flair 200C
The VD23 is a voltage detecting system for Voltage indicator and relay VD23
automatic transfer system or interlock
applications.
Features
b Various combinations:
The VD23 is a compact voltage relay for 3 kV to 36 kV, 50/60 Hz medium
v presence or absence voltage relay
voltage networks. It is associated with a capacitive divider and a VPIS-VO.
v zero sequence voltage relay
b 2 output relays based on 2 functional modes:
v phase-to-neutral or phase-to-phase voltage
v R1 = Voltage presence (typically used for automatic transfer switching)
v phase selection.
v R2 = Voltage absence (typically used for interlocking of earthing switch).
b Easy to install: b Thresholds can be set as a percent of phase-to-neutral voltage (V),
v compact 96 x 48 mm DIN format phase-to-phase voltage (U) or residual voltage (VO)
v terminal connection for VPIS-VO b All combinations of voltage conditions are possible:
v no need for HV transformer v 3 phases and residual: V1+V2+V3+VO
v hot installation v 3 phases: V1+V2+V3 or U12+U13+U23
v auto-adaptation of nominal voltage. v single phase: Vo, V1, V2, V3, U12, U13 or U23
b Output is a tripping order via two output relays with a normal or inverse active
position
b Signalling and tripping outputs may be set with a delay.
PE57787
Display principle
b Voltage value (% of Un) of L1, L2 and L3 shown on the display
b Voltage presence/absence indication via LED
b Settings by front pushbuttons and LCD
v thresholds, delays and smart parameters
v display of all settings on LCD.
VD23 b Auto-adaptation of the nominal system voltage
b Check on voltage status.
Advanced settings
All the combinations can be set with microswitches on the rear of the device.
The use of two relays provides safety backup operation for each combination
6 microswitches: 1: Ph-N voltage(V) / Ph-Ph voltage(U)
1 2 3 4 5 6 2: Direct / inverse action on output relays
1 3: Phase 1 used / not used
0
4: Phase 2 used / not used
L1
5: Phase 3 used / not used
L2 6: Residual voltage used / not used
L3
VD23
Wiring (with VPIS-VO)
DM100060
All the combinations can be set with microswitches on the rear of the device.
The use of two relays provides safety backup operation for each combination.
150 AMTED399086EN
Accessories & options Accessories description
Fault passage indicators
Flair 21D and Flair 22D
Flair 21D, 22D is a family of DIN format Applications and main features
fault passage indicators. They are small in size,
self-powered and adapt automatically to the The Flair range increases your power availability by providing indicators
network. suitable for fault locating and MV network load management.
b Indication of phase-phase and phase-earth faults
These devices use cutting-edge technology to b Display of settings
detect earth faults on underground MV networks b Indication of the faulty phase
with isolated, resistor-earthed or directly earthed b Display of the load current including peak demand and frequency.
neutral and overcurrents on all networks.
These fault passage indicators are reliable and easy to use.
b Self-powered, the fault current passage
b Automatic setting on the site
detection and indication system operates
b Fault indication with LED or outdoor lamp
continuously
b 15-year battery life for Flair 22D
b Adjustment-free, they are immediately b More accurate fault detection if Flair 22D is connected to voltage presence
operational (numerous manual adjustments indication system (VPIS) voltage output
are however possible) b Can be factory-mounted in Premset cubicles or added on the site
b Compact, their DIN format easily fits b Easy on-site addition without removing MV cables using split-type current sensor.
in MV cubicles
b Smart, they offer an ammeter/digital maximeter
function.
Fault detection functions
Overcurrent detection
b Automatic mode for adjustment-free calibration of detection thresholds
b Manual mode for special override settings:
PE57783
Indication reset
b Automatic reset upon load current recovery (configurable time delay on Flair 22D)
b Manual reset via front panel button
b Reset via external Reset input
b Reset by time delay: fixed (4 hr) for Flair 21D and adjustable using front
panel keypad (2 hr to 16 hr) for Flair 22D.
AMTED399086EN 151
Accessories & options Accessories description
Fault passage indicators
Flair 21D and Flair 22D
VPIS-VO
option Standard applications
Flair 21D Maintenance-free, adjustment-free fault detector
Flair 22D Fault detector for networks with very low load current (< 2 A) with possibility
of manual adjustments.
Flair 22D
Reset Indication
152 AMTED399086EN
Accessories & options Accessories description
VPIS V2
Thresholds
PE58178
b In compliance with the IEC 62271-206 standard, the indicator lamp outputs of
the VPIS are lit or flashing when the network voltage is > 45% of the rated voltage.
IEC 62271-206: Equivalent percentage Status of VPIS
percentage of of rated voltage V indicator lamps
network voltage U
Phase-to-phase Phase-to-earth
Voltage indicator
Voltage value 10% 17% Extinguished
at VPIS input
PE58142
Ringmaster 3 kV 6 kV 10 kV 15 kV
First Without VO VPI62401 VPI62401 VPI62403 VPI62403
choice With VO VPI62411 VPI62411 VPI62413 VPI62413
50/60 Hz (3.4 kV-7.5 kV) (3.4 kV-7.5 kV) (7.1 kV-16 kV) (7.1 kV-16 kV)
Standard surge protection Second Without VO VPI62402
choice With VO VPI62412
PE58144
AMTED399086EN 153
Accessories & options Accessories description
Motorization
DSC0456
154 AMTED399086EN
Accessories & options Accessories description
Motorization
Process of motorization
DSC0444
DSC0443
Manual pre-wired Ring Main Unit Position the Motorpack to the RMU
DSC0437
DSC0434
DSC0430
Position the Motorpack in front Plug-in the motorpack in its location Secure by special nut provided
of mechanism (pad lockable)
DSC0424
AMTED399086EN 155
Accessories & options Accessories description
Other accessories
Options
The following pages clarify options:
RMR-F47 - Tee-off cable box (drawing RMINST 05/09)
RMR-A50 - Angled gland tray (drawing RMINST 10)
RMR-A317 - Angled gland tray (drawing RMINST 05)
RMR-A14/A15/A78/A79
DE60270
Busbar assemblies
b Each kit comprises a three phase set of busbars, 630 A
b Specify at time of ordering:
v 1 off RMR-A15 - end panel kit, plus busbar kits
v Quantity required = No. of panels - 1
Note: Different busbar kits are required for metering units and bus-sections
Busbars are dispatched loose.
RMR-A17
Time Fuse Links
DE60245-1
RMR-A202
PE58310
156 AMTED399086EN
Accessories & options Non-extensible ring main unit
c/w angled ring cable gland plates
ref RMINST-05
DE60246
208 208
AMTED399086EN 157
Accessories & options Tee-off cable box fitted
to SN6/CN2
ref RMINST-09
DE60247
158 AMTED399086EN
Accessories & options Ringmaster range
cabling accessories
ref RMINST-10
DE59850
799
AMTED399086EN 159
160 AMTED399086EN
Schneider Electric, Contents
an overview
and order form
Applications 162
Building systems and solutions
Industrial systems and solutions
Energy and infrastructure systems and solutions
Package substations
Mining industry
Index 175
AMTED399086EN 161
Schneider Electric, Applications
an overview
and order form
Schneider Electric operates the largest, dedicated sales force in the electrical industry.
Sales engineers have specialist expertise and an understanding of the customer
needs within each of the following market sectors:
b Building systems and solutions
b Industrial systems and solutions
b Energy and infrastructure systems and solutions
b Package substations
b Mining industry.
162 AMTED399086EN
Schneider Electric, Applications
an overview Building systems and solutions
and order form
The real reason for putting technology into buildings is to simplify tasks, enhance
PE58312
The same objectives apply to commercial buildings such as offices, hotels, shopping
centres, hospitals, schools and care facilities for the elderly.
Schneider Electric offer a wide range of solutions in the area of building management
services and uses its expertise in all of these buildings to protect people and
equipment.
b Entertainment centres
b Offices
b Warehouses
b Agriculture
b Factory
b Private residential
b Public residential.
Principal customers in the construction market
b Contracting authorities
b Main contractors
b Building engineers.
AMTED399086EN 163
Schneider Electric, Applications
an overview Industrial systems and solutions
and order form
Our products and services adapt to each specific business and environment, from
discrete manufacturing and production lines to continuous processes in a wide
variety of industries such as:
b Automotive
b Food and beverage
b Pharmaceuticals
b Construction materials
b Waste management.
164 AMTED399086EN
Schneider Electric, Applications
an overview Energy and infrastructure systems
and order form
and solutions
Schneider Electric is involved in the entire electrical distribution chain from power
PE58315
Infrastructure
Schneider Electric is involved in developing infrastructure and transportation
systems around the world. In areas where no failures can be tolerated, such as road
and rail equipment, harbour installations and airports, Schneider Electric provides
solutions in electrical distribution, control and monitoring, automation and
supervision.
Key markets
b Electricity distribution
b Water
b Rail
b Airports
b Seaports
b Defence
b Gas
b Telecommunications
PE58316
b Road.
Principal customers in the electric power market
b Power suppliers involved in generation and distribution
b Utility companies
b Major contractors
b Large end user sites
b Government departments.
AMTED399086EN 165
Schneider Electric, Applications
an overview Package substations
and order form
PE58321
Flexibility of tailored configurations are available from the wide range of Schneider
Electric products which include:
b Transformers from 315 kVA to 2000 kVA (up to 5 MVA for special applications)
b Extensible and non-extensible Ringmaster MV switchgear
Unit substation 4 way LV cabinet b LV SAIF and shielded fusegear from 800 A to 3200 A
and Ringmaster RN2c RMU
b LV acb and mccb pillars up to 3200 A
b Automation and monitoring systems
b Tailor made enclosures can be mounted on the transformer underbase to provide
single lift complete installation.
Cost savings are achieved by reducing the foundation area requirement due to
the direct coupling which requires minimum cabling and reduced maintenance.
Space requirements are minimised by direct connection, logistics costs minimalised
because the complete substation is delivered as a single unit. One stop package
substations also reduce the time commitment needed by customers for the overall
project.
PE58320
166 AMTED399086EN
Schneider Electric, Applications
an overview Package substations
and order form
Features
b One contact
b Complete system, delivered as one unit
b Typical drawing and technical specification with tender
b Metering facilities-optional
b Remote control-optional
b Free breathing, conservator or hermetically sealed tank option
b Premium quality of Schneider Electric
b Direct coupled MV & LV equipment
b Additional enclosure option.
PE58324
AMTED399086EN 167
Schneider Electric, Applications
an overview Mining industry
and order form
168 AMTED399086EN
AMTED399086EN 169
Schneider Electric, Order form
an overview Ring Main Unit (RMU)
and order form
Only one of the boxes (ticked X or filled by Basic RMU configuration Quantity
the needed value) have to be considered between each
Rated voltage Ur (kV)
horizontal line.
Green box X corresponds to none priced functions. Impulse rating and short-time withstand 21 kA 3 s, 95 kVbil
RMU options
Low gas pressure switch (contact)
VPIS on switches 3.3-13.8 kV
C type bushings on switches (Check with us for availability)
170 AMTED399086EN
Schneider Electric, Order form
an overview Ring Main Unit (RMU) cont.
and order form
Only one of the boxes (ticked X or filled by Options for ring switch 1 - Left hand side
the needed value) have to be considered between each Inverted cable box for top entry
horizontal line. Cable entry - 1 - 3c cable
Green box X corresponds to none priced functions. Gland plates 3 - 1c cable
Angled 1 - 3c cable
Split gland plate 1 x 3c
Blank aluminium
Cable gland Brass wiping 3 - 1c cable 1 - 3c cable
(only if Small brass wiping 3 - 1c cable
required)
Galvanised tubular 3 - 1c cable 1 - 3c cable
Heat shrinkable 1 - 3c cable
Motor provision - auxiliary switch 1 x N/O, 1 x N/C
Motor pack (includes motor provision) 24 Vdc
Mechanical key interlock (not available with motor option)
Key free main OFF
Bowden earth fault passage indication (includes external current transformer)
Self powered Std LV reset LV reset + alarm
Dual powered - battery Remote reset + alarm
Easergy T200 current transformers
Termination boots “Econ”
Accessories
Operating handle
Phase comparitor
VAP6
TFL fuses
(A) 3 5 7.5 10 12.5 15
Extension kit RE2c to RMR RE2c only
AMTED399086EN 171
Schneider Electric, Order form
an overview Ring Modular Range (RMR)
and order form
Circuit breaker
Only one of the boxes (ticked X or filled by Basic RMR configuration Quantity
the needed value) have to be considered between each
Rated voltage Ur (kV)
horizontal line.
Green box X corresponds to none priced functions. Impulse rating and short-time withstand 21 kA 3 s, 95 kVbil
Options
VPIS 3.3-13.8 kV
Neon lamp unit
Neon lamp with verification unit
Shunt trip coil (included if VIP) 20-48 Vdc, 110-250 Vac/dc
Shunt trip coil (included if TFL)
Motor provision - auxiliary switch 1 x N/O, 2 x N/C
Motor / Actuator - MOTOR PROVISION MUST BE SELECTED 24 Vdc
Mechanical key interlock (not available with motor option)
Tx earth sw key free earth on Key free main OFF Key free earth ON
Low gas pressure switch (contact)
Accessories
Operating handle
Busbar kit & end panel kit are included to assemble switchboard
Phase comparitor
VAP6
TFL fuses
(A) 3 5 7.5 10 12.5 15
Only one of the boxes (ticked X or filled by Basic RMR configuration Quantity
the needed value) have to be considered between each
Rated voltage Ur (kV)
horizontal line.
Green box X corresponds to none priced functions. Impulse rating and short-time withstand 21 kA 3 s, 95 kVbil
Panel configuration
630 A non extensible cable in/out standard
630 A non extensible cable in/out with 3.15 kA tx earth switch
630 A extensible
Bus section & busbar earthing switch
Choose and fill-in from “Guide Metering & Bus section”, e.g.: SE6-B1
Options
VPIS 3.3-13.8 kV
Neon lamp unit
Neon lamp with verification unit
Motor provision - auxiliary switch 1 x N/O, 1 x N/C
Motor / Actuator - MOTOR PROVISION MUST BE SELECTED 24 Vdc
Mechanical key interlock (not available with motor option)
Tx earth sw key free earth on Key free main OFF Key free earth ON
Bowden earth fault passage indication (includes external current transformer)
Self powered Std LV reset LV reset + alarm
Dual powered - battery Remote reset + alarm
Easergy T200 current transformers
Low gas pressure switch (contact)
Accessories
Operating handle
Phase comparitor
AMTED399086EN 173
Schneider Electric, Guide Metering & Bus section
an overview
and order form
174 AMTED399086EN
Schneider Electric, Index
an overview
and order form
A Page
Accessories 150
Actuator panel types 49, 61, 73
Angled gland trays 157
Applications 162
B
Busbar options sections 86
Bus sections 85
C
200 A 44, 45
600 A 73, 74
Circuit breakers 61, 62
Control & protection 7 to 12
D
Drawing index 96
E
Easergy telecontrol unit 92
I
IDMT protection 7, 11, 12
IEC/BS/IS standards 6
M
Metered CB’s 61, 62, 73, 74
Metering units 53, 54
Motor retrofit 33, 34, 61, 62
P
Protection selection 7
Protection - TFL 7
Protection - VI 12
R
Ring main units extensible 61, 62
Ring main units non-extensible 22, 23
S
Schematics 108
Selection guide 17
Self powered protection 7
Switchboard GA 97
Switches 49, 80
T
Telecontrol 92
Telephone communication 92
TFL protection 7
Time fuse links 7
V
VIP protection 8
Please note: Due to the constant progress in standards and equipment, the characteristics shown
in the texts and images in this document are only binding once expressly confirmed by ourselves
AMTED399086EN 175
Ringmaster Notes
176 AMTED399086EN
ART45334 © Schneider Electric Industries SAS - All rights reserved
AMTED399086EN 07-2013