Nothing Special   »   [go: up one dir, main page]

Diesel Powered Generating Sets C350 D5: Standard Genset Features Generator Set Performance Generator Set Options

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

P M

Diesel Powered
Generating Sets
C350 D5

Standard Genset Features Generator Set Performance Generator Set Options


Cummins water cooled Diesel engine, Voltage Regulation Mechanical Options
Oil and fuel filter fitted, water separator, Maintains voltage output to within ±1.0%. Compliance - CE Certification (Guarding)
Lube-oil drain valve fitted At any power factor between 0.8 and 1.0
Electric starter & Charge alternator 24 v D.C. At any variations from No load to Full load. Fuel options
Electronic governor At any variations from Cold to Hot. Fuel Tank deletion
Normal duty air filter At speed droop variations up to 4.5%.
Single bearing alternator, class H/H , IP23 Frequency Regulation
Standard voltage 400/230 volts 50 Hz Isochronous under varying loads from no Exhaust Options
Exciter/Voltage reg - Torque Match as std load to 100% full load when electronic Exhaust Silencer - Industrial (9 dB), In-Line
PCC2100 without Bargraph governor is ?tted. Exhaust Bellows
3 pole MCCB Exhaust Silencer - Residential (25 dB), In-Line
Welded steel base frame with A/V mounting, Random Frequency Variation Installation Kit - Industrial Silencer
Anti Vibration Mounts Will not exceed ±0.25% of its mean value for
Single skin metal fuel tank constant loads – no load to full load.
Tank capacity of min 8 hours operation at Waveform Warranty
70% standby load Total harmonic distortion open circuit voltage Warranty - 5 Year Extended Standby Appln
Loose 9 dB(A) silencer waveform in the order of 1.8%. Three-phase Warranty - 2 Year Extended Prime Appln
Set mounted starting battery balanced load in the order of 5.0%.
Engine Tractor Blue & Alternator Munsell Jade Green Telephone In?uence Factor (TIF) Voltage Connections
Radiator and Guarding black TIF better than 50. 277/480V, 3 Phase
Packing under shrunk plastic film THF to BS 4999 Part 40 better than 2%. 254/440V, 3 Phase
Operation & Maintenance manual Alternator Temperature Rise 240/416V, 3 Phase
Standard set of labels Class H insulation. 230/400V, 3 Phase
220/380V, 3 Phase
Radio Interference 127/220V
In compliance with BS 800 and VDE levels 115/200V, 3 Phase
G and N. 110/190V, 3 Phase
Miscellaneous Options
Engine Specification Alternator Specification Coolant heater -240V
Cummins NT855G6 Type Battery Charger 240V,5A
In-line direct injection Brushless single bearing, revolving ?eld, PCC2100 with bargraph
6-cylinder diesel engine. pole, drip proof, screen protected. Packing - Export Box
Type Class H Insulation. Packing - Export Box
Water cooled, four cycle IC 01 cooling system. Compliance Standards
Turbocharged Fully interconnected damper winding. To BS4999/5000 pt 99,
Construction AC exciter and rotating recti?er unit. VDE 0530, UTE5100,
Two valves per cylinder, forged steel Epoxy coated stator winding. NEMA MG1-22, CEMA,
crankshaft and connecting rods, cast iron Rotor and exciter impregnated with tropical IEC 34, CSA A22.2,
block. grade insulating oil and acid resisting AS1359, BSS 5514,
Starting polyester resin. Dynamically balanced rotor ISO 3046 and ISO 8528
24 volt negative earth. Battery charging BS 5625 grade 2.5.
alternator 35 amp on engine. Cranking Sealed for life bearings.
current 640 amps at 0°C. Layer wound mechanically wedged rotor.
Fuel System
24 volt fail safe actuator. Spin-on paper Exciter
element fuel ?lters with Bosch fuel Triple dipped in moisture, oil and acid
pump injection system with integral resisting polyester varnish and coated with
Electronic governor. Dual ?exible fuel lines anti-tracking varnish.
and connectors. Standard fuel water
separator.
Filters Output windings with 2/3 pitch for improved
Air cleaner with dry element and restriction harmonics and paralleling ability.
indicator. Spin-on full ?ow lube oil ?lter. Close coupled engine/alternator for perfect
Cooling alignment.
50°C radiator as std
Stone guard. Oil cooler. Drain Tap

Model name kVA kWe


ESP PRP ESP PRP
C350 D5 350 320 280 256

Specifications may change without notice www.mayphatdien-vn.com C350 D5


P M

TECHNICAL DATA
Model C350 D5 Speed 1500 rpm
Set output 380-440 V 50 Hz Alternator voltage regulation ±1.0%
Prime Rating 256 kWe 320 kVA Alternator insulation class H
Standby Rating 280 kWe 350 kVA Fuel consumption (Prime) 69 l/hr
Engine Make Cummins Fuel consumption (Standby) 76 l/hr
Engine Model NT855G6 Lubrication system oil capacity 38.6 Litres
Cylinders Six Base fuel tank capacity – open set 750 or 900 Litres
Engine build In-line Coolant capacity 63.9 Litres
Standard Governor/Class Electronic/Class G2 Exhaust temp – prime 574°C
Aspiration and cooling Turbocharged Exhaust gas flow – prime 1071 l/s
Bore and stroke 140 mm x152 mm Exhaust gas back pressure max 76 mm Hg
Compression Ratio 14:1 Air flow – radiator* 4.92m3/s
Cubic capacity 14 Litres Air intake – engine (Prime) 361 Litre/s
Starting/Min °C Unaided / 4°C Minimum air opening to room 2.10 sq m
Battery capacity 100 A/hr Minimum discharge opening 1.39 sq m
Gross Engine output – Prime 280 kWm Pusher fan head (duct allowance)* 13 mm Wg
Gross Engine output – Standby 310 kWm Heat radiated by eng (Prime) 50 kWm

PRIME POWER (PRP)


Prime power is available for an unlimited number of annual operating hours in variable
load applications, in accordance with ISO8528-1. A 10% overload capability is available
for a period of 1 hour within a 12-hour period of operation, in accordance with ISO
3046-1. STANDBY POWER RATING (ESP)
The Standby Power Rating is applicable for supplying emergency power for the duration of a utility power interruption. No overload, utility parallel or negotiated outage
operation capability is available at this rating.
In installations served by unreliable utility sources (where outages last longer or occur more frequently), where operation is likely
to exceed 200 hours per year, the prime power rating should be applied. The Standby Power rating is only applicable for
emergency and standby applications where the generator set serves as the back up to the normal utility source.
All ratings are based on the following reference conditions:
- Ambient - Altitude above sea level – 150 metres - Relative humidity – 60%
temperature – 27oC

Dimensions and Weights


Set weight wet Enclosed Weight
Model Engine Length (mm) Width (mm) Height (mm) Set weight dry (Kg)
(Kg) Wet (Kg)

C350 D5 NT855G6 3549 1100 2028 2078 3448 3258

Specifications may change without notice


See your distributor for more information.
Cummins Power Generation P.M.G.,JSC
Limited
No1, Zone B, Alley 178 Giai Phong Str, Thanh Xuan
www.mayphatdien-vn.com Dist, Hanoi City, Vietnam
Tel : (04) 36290294/22.431.521
www.cumminspower.com Fax:(04) 36290295
www.mayphatdien-vn.com
www.cummins.com

C350 D5