Low Voltage 480 VSwitchgear 1
Low Voltage 480 VSwitchgear 1
Low Voltage 480 VSwitchgear 1
General Description
Low Voltage metal-enclosed switchgear is used in electric power distribution systems for the
control and protection of circuits and equipment. The switchgear employs drawout type low
voltage power circuit breakers.
Industrial Plants – for power and lighting networks and feeders, power generation and other
auxiliaries, and to provide power for machine tools and material handling equipment drivers.
Utility and Co-generation Facilities – for motor control centers to protect and distribute power to
electrical devices such as blowers, compressors, fans, pumps, and motors.
Commercial and Residential Buildings – for protection and distribution of power for lighting,
elevators, air conditioning, blowers, fans, motors, and pumps.
Available Types
The circuit breakers may be either manually or electrically operated, fused or unfused. CPC
utilizes General Electric circuit breakers and can offer Cutler Hammer, or Siemens air magnetic
circuit breakers for an additional cost.
CP does not manufacture switchboards or panelboards using molded case circuit breakers.
Static Trip units are provided on all low voltage circuit breakers. All circuit breakers are UL listed.
Tables 1 and 2 show the maximum nominal ratings for circuit breakers.
Industry Standards
CP's switchgear with power circuit breakers is designed, tested, and constructed to be in
accordance with:
• ANSI C37.20.1 – Metal-Enclosed Low Voltage Power Circuit Breaker Switchgear
• ANSI C37.50 – Test Procedure for Low Voltage AC Power Circuit Breakers Used in
Enclosures
• ANSI C37.51 – Conformance Testing of Metal-Enclosed Low Voltage AC Power Circuit
Breaker Switchgear Assemblies
LowVoltageSwitchgear.doc
Drawout circuit breakers are in accordance with: ANSI C37.13 – Low Voltage AC Power Circuit
Breakers Used in Enclosures
• ANSI C37.16 – Preferred Ratings, Related Requirements, and Application for Low
Voltage Power Circuit Breakers and AC Power Circuit Protectors
• ANSI C37.17 – Trip Devices for AC and General Purpose DC Low-Voltage Power
Circuit Breakers
• UL 1066 – Low Voltage AC & DC Power Circuit Breakers Used in Enclosures
CP switchgear provides efficient and safe power distribution and control. All applicable ANSI,
NEMA, and IEEE standards are met.
Closed-door racking is standard. Mechanical interlocks prevent racking a closed circuit breaker
or mismatching a breaker and a compartment. Each compartment is also enclosed with
grounded steel barriers.
Harmonics-induced trips are avoided with the static trip unit, standard on all circuit breakers. By
using RMS current sensing, accurate load protection is provided without causing unnecessary
shutdowns or jeopardizing system integrity due to high trip settings.
All switchgear is manufactured, assembled, and tested in one location. This assures an
integrated fit and high quality. The overall effect is guaranteed reliability.
Application Flexibility
Circuit breaker sizes are available with ratings from 800A to 5000A. Extended interruption ratings
are optional with up to 130kA without fuses and 200kA with fuses.
Frames rated up to 2000A can be stacked four high and can include integrally mounted fuses. A
single vertical section can accommodate a fused 3200A, 4000A, or 5000A circuit breaker. Three
widths of vertical sections are available to simplify planning and design: 22, 30, and 38 inches.
The 22 inch and 30 inch sections have a uniform depth of 60 inches, while the 38 inch section is
74 inches deep. Rear extensions are available as needed for additional cabling area. All breaker
sizes can be housed in a combination of these sections.
LowVoltageSwitchgear.doc
Description
The switchgear assembly consists of multiple metal-enclosed, vertical sections. Normally the end
sections are designed to allow for installation of future sections. Each vertical section consists of
up to four individually enclosed breaker or auxiliary compartments. Compartments are sized to
provide uniform height of each switchgear assembly.
In accordance with ANSI C37.20.1, the maximum temperature for parts that are handled is 50ºC.
The main bus maximum temperature rise is 65ºC above 40ºC ambient. The temperature rise of
the air surrounding the cable connection points is limited to 45ºC above 40ºC ambient.
Assembly Construction
Bolted steel-glass polyester compartments housing each power circuit breaker are mounted in
the vertical section to form the switchgear assembly. This assembly isolates the circuit breakers
from the bus/cable section and from adjacent circuit breaker compartments.
The bus/cable section includes the main horizontal bus, riser bus, connections from the main bus
to each set of primary disconnects, and load side copper run-back bus. The cable lugs are
accessible without reaching over the main bus. Grounded metal barriers can be provided to
isolate the main bus from the cable connections. Barriers are also available to isolate the
incoming line of the main circuit breakers from the main load bus of the switchgear.
The main three-phase horizontal bus is arranged vertically one phase above the other with edge-
to-edge alignment to provide high, short circuit strength. An insulated main and vertical bus are
optionally available.
The main bus ratings available are 1600, 2000, 3200, 4000, or 5000 amperes continuous current.
A neutral bus is furnished when specified, and can be rated 1600, 2000, 3200, or 4000 amperes
continuous current.
A standard ¼ x 2 inch copper ground bus extends through all sections and is securely bolted. A
cable lug can be mounted to the ground bus in each section. Minimum bus bracing is 65,000
amperes RMS symmetrical. Higher symmetrical bracings are available based on the highest
breaker short circuit rating in the group.
LowVoltageSwitchgear.doc
Control Wiring
Standard secondary and control wiring is #14 AWG extra-flexible, stranded copper type SIS.
Terminations are made with compression-type, insulated terminals.
For devices not having screw-type terminals, locking spade-type lugs are used. Sleeve-type
computer generated wire markers are provided as standard on each end of all control wires.
Insulation
The insulation used in the switchgear is fiberglass-reinforced, polyester material that has high
impact strength and low moisture absorption. Other features include high flame retardance, high
resistance to chemical fumes, and long life at high temperatures.
Typical circuit breaker compartments include primary disconnects, ground disconnect, drawout
rails, and associated safety interlocks and secondary disconnects, if appropriate. Compartments
for electrically operated circuit breakers include secondary disconnects and control circuit fuses.
The pullout fuse holder has a set of clips to store the holder in the fuse block when the circuit is
disconnected. Up to three current transformers for metering or relaying can be mounted in each
compartment.
Circuit breaker compartment front panels can be used to hold a variety of auxiliary devices. A
typical compliment of devices includes a breaker control switch with red & green light, ammeter
with switch, and test block.
Metering and auxiliary compartments are available to house devices such as voltage
transformers, metering, control power transformers, and supervisory devices that do not fit on a
normal breaker door.
Voltage transformers and control power transformers are mounted in auxiliary compartments.
These transformers are protected by primary pull-out type current-limiting fuses and secondary
fuses.
Current transformers are normally mounted on the compartment primary disconnect studs where
they are readily accessible.
Accessories
LowVoltageSwitchgear.doc
Outdoor Switchgear
CPC's outdoor switchgear is enclosed in a weather resistant (NEMA 3R) steel housing. All
exterior doors extend below the floor line and re sealed with synthetic rubber gaskets.
For protection from snow, rain, and dust, the switchgear rests on a six-inch, formed steel base,
which provides rigid support and a tight bottom seal. A heavy duty, coal tar emulsion protective
undercoating 1/32 inch thick is applied to the underside for protection against moisture and
corrosion. Shielded ventilation housing permit proper air circulation while excluding dust, dirt, and
foreign matter. The full-length front doors are hinged and may be padlocked. Rear doors are
hinged and secured with captive bolts.
A lighted, unobstructive service aisle is provided at the front of the switchgear allowing inspection
and maintenance without exposure to the elements. An access door equipped with an
emergency bar release is at each end of the aisle. A GFI convenience outlet is included.
As with all of CPC manufactured equipment, low voltage switchgear can be mounted in one of
our Power Control Centers and integrated with other power distribution equipment.
LowVoltageSwitchgear.doc